DR MARY MCLEOD BETHUNE ELEMENTARY
 
DR MARY MCLEOD BETHUNE ELEMENTARY
This site is a Hurricane Shelter
1501 AVENUE "U"
RIVIERA BEACH, 33404
FISH Drill Down
 Campus Info.
 Buildings:2 Rooms:281
 Portables:0
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
408449 03/01/2018 461363 1 215A M Repair leaking toilet supply line
408324 03/01/2018 461102 00 0 O No access was available to 1-106C. Please provide access to this room during the report review meeting
408335 02/19/2018 461126 00 0000 M West chiller is leaking oil. Repair chiller
408360 02/19/2018 461178 00 0000 M Eliminate ants from play fields.
408361 02/19/2018 461180 00 0000 M Break up and rake out red clay in ball field. Very hard and compacted and slick when it is rained on
408372 02/19/2018 461202 00 0000 M Chain up cylinder in Chiller Compound or remove cylinder
408390 02/19/2018 461241 00 0000 M Clean out all roof drains and downspouts on Campus
408370 02/19/2018 461196 1 0000 M Determine cause of water damaged ceiling tiles and replace tiles at top of stairs south of 1-115
408461 02/19/2018 461387 1 0000 M Determine cause of water damaged ceiling tiles in 2nd floor corridor at 1-229 and replace tiles
408473 02/19/2018 461416 1 0000 M Determine cause of water damaged ceiling tiles and replace tiles in rooms 1-104B, 1-104C, 1-106D, 1-107E, 1-107F, 1-108, 1-109, 1-109A, 1-115, 1-185, 1-191, 1-208, 1-214, 1-215B, 1-217, 1-222B and 1-229
408430 02/19/2018 461324 1 101B M Repair exhaust fan in bathroom
408354 02/19/2018 461164 1 102 M Determine cause of water damaged ceiling tiles and replace tiles. SE corner of Cafeteria
408374 02/19/2018 461207 1 102C M Caulk toilet to wall
408376 02/19/2018 461209 1 102C M Grout around clean out in floor of handicapped stall to provide impervious floor surface
408358 02/19/2018 461172 1 102D M Anchor toilet to wall
408359 02/19/2018 461175 1 102D M Secure vertical handicapped grabrail
408356 02/19/2018 461167 1 103E M Refinish bathroom wall behind toilet to provide impervious finish
408347 02/19/2018 461149 1 105A M Caulk toilets to wall
408348 02/19/2018 461151 1 105C M Caulk toilets to wall
408345 02/19/2018 461145 1 109A M Replace missing escutcheon on fire sprinkler head
408357 02/19/2018 461170 1 112 M Provide illuminated exit signs at both exits. Max occupancy of room is 67
408409 02/19/2018 461277 1 115A M Remove sharp staple pieces from closet door
408410 02/19/2018 461283 1 115B M Repair exhaust fan in bathroom
408411 02/19/2018 461285 1 119B M Repair exhaust fan in bathroom
408412 02/19/2018 461287 1 119C M Repair exhaust fan in bathroom
408413 02/19/2018 461290 1 119C M Anchor toilet to floor
408417 02/19/2018 461295 1 121B M Fire sprinkler head in Kiln room has red bulb. Replace with sprinkler head with higher heat rating
408431 02/19/2018 461326 1 122 M Repair exhaust fan in bathroom
408389 02/19/2018 461239 1 129 M Secure sink to counter top
408438 02/19/2018 461341 1 130 M Repair or replace leaking faucet
408433 02/19/2018 461328 1 133A M Refinish wall behind toilet to provide impervious finish
408404 02/19/2018 461270 1 170 M Provide current inspection tag for elevator
408339 02/19/2018 461133 1 193 M Provide cover on exposed electrical junction box above SE corner of AHU 6
408340 02/19/2018 461135 1 193 M Reinsulate chilled water line to prevent condensate from dripping on floor
408385 02/19/2018 461226 1 194A M Secure loose fire extinguisher bracket to wall. Extinguisher not needed, removed
408421 02/19/2018 461306 1 195 M Label all circuits on electrical panel 1LSHA
408423 02/19/2018 461308 1 195 M Replace missing screws for cover of electrical panel 1LB1
408424 02/19/2018 461312 1 195 M Breaker 17 on electrical panel 1DB tripped. Repair circuit
408428 02/19/2018 461316 1 195 M Breaker 45 on electrical panel 1LB2 tripped. Repair circuit
408364 02/19/2018 461186 1 196A M Repair emergency lighting
408472 02/19/2018 461413 1 196B M Centurion alarm panel on wall has phase 1 light lit yellow. Phases 2 and 3 are not lit. Repair
408392 02/19/2018 461243 1 198A M Repair leaking air handler
408395 02/19/2018 461248 1 198B M Replace missing screws for cover of electrical panel 1HMB
408397 02/19/2018 461253 1 198C M Replace missing screws for cover of electrical panel 1HMA
408441 02/19/2018 461347 1 202B M Repair leaking toilet supply line
408445 02/19/2018 461355 1 203A M Repair exhaust fan in bathroom
408442 02/19/2018 461349 1 204B M Repair leaking toilet supply line
408443 02/19/2018 461351 1 204B M Caulk sink to wall
408444 02/19/2018 461353 1 204B M Replace missing door handle inside of bathroom
408450 02/19/2018 461365 1 205C M Repair leaking toilet supply line
408448 02/19/2018 461361 1 215A M Repair exhaust fan in bathroom
408451 02/19/2018 461368 1 216B M Repair leaking toilet supply line
408466 02/19/2018 461398 1 219A M Repair exhaust fan in bathroom
408455 02/19/2018 461377 1 220 M Repair or replace leaking faucet
408467 02/19/2018 461400 1 221B M Repair exhaust fan in bathroom
408456 02/19/2018 461379 1 224 M Eliminate ants from room
408458 02/19/2018 461381 1 224 M Repair or replace leaking faucet
408459 02/19/2018 461384 1 224B M Replace missing push button for bathroom faucet
408463 02/19/2018 461392 1 225A M Caulk sink to wall
408446 02/19/2018 461357 1 291 M Breaker 41 on electrical panel 2LA-2 tripped. Repair circuit
408468 02/19/2018 461403 1 294 M Breaker 25 on electrical panel 2DB tripped. Repair circuit
408469 02/19/2018 461405 1 294 M Breakers 43 and 45 on electrical panel 2LB-2 tripped. Repair circuits
408419 02/19/2018 461301 1 119A O Bathroom used for storage. Every 2 months pour 1 quart of water down all drains
408437 02/19/2018 461336 1 132B O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
408332 02/19/2018 461115 1 103 C Make repairs to kitchen hood fire suppression system as indicated on inspection report
408439 02/19/2018 461343 1 0000 MS Adjust fire door from stairs to corridor next to 1-213 to latch properly
408454 02/19/2018 461374 1 0000 MS Adjust fire doors in 2nd floor corridor at 1-219 to latch properly. Door leaves hit each other at top
408403 02/19/2018 461266 1 101J MS Provide current inspection tag for fire extinguisher
408378 02/19/2018 461212 1 0000 OS Remove and prohibit storing recycle bin in exit corridor south of 1-123 to maintain clear aisle to exit
408327 09/19/2017 461110 00 0000 M Make necessary repairs to fire sprinkler system as indicated on inspection report. Red annual tag
394069 09/19/2017 430324 1 0000 M Make necessary repairs as indicated on fire sprinkler inspection report dated December 2015, sprinkler system has a red annual inspection tag
353715 09/19/2017 342684 1 0000 C Modify evacuation route maps in all classromms to show both primary and secondary evacuation routes (current maps show only a primary route, a secondary route should also be shown in a different color)
255422 09/19/2017 131919 1 0000 N/A No violations observed
255424 09/19/2017 131921 2 0000 N/A No violations observed
291680 09/19/2017 207154 3 0000 N/A No violations observed
394097 03/01/2017 430381 1 0000 M Determine cause of water damaged ceiling tiles in second floor corridor adjacent to 1-230 and replace tiles
394056 03/01/2017 430297 1 101 M Determine cause of water damaged ceiling tiles in corridor adjacent to 1-101K and replace tiles
394057 03/01/2017 430299 1 101 M Provide covers on exposed electrical junction boxes under main reception desk
394059 03/01/2017 430303 1 102 M Determine cause of water damaged ceiling tiles and replace tiles
394080 03/01/2017 430346 1 102 M Repair broken magnetic release hold open device for fire door at 1-105
394060 03/01/2017 430305 1 103C M Determine cause of water damaged ceiling tiles and replace tiles
394061 03/01/2017 430307 1 103F M Determine cause of water damaged ceiling tiles and replace tiles
394068 03/01/2017 430322 1 107E M Determine cause of water damaged ceiling tiles and replace tiles
394084 03/01/2017 430354 1 108 M Determine cause of water damaged ceiling tiles and replace tiles
394081 03/01/2017 430348 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
394082 03/01/2017 430350 1 109A M Determine cause of water damaged ceiling tiles and replace tiles
394083 03/01/2017 430352 1 109B M Anchor toilet to floor
394078 03/01/2017 430342 1 110 M Determine cause of water damaged ceiling tiles and replace tiles
394073 03/01/2017 430332 1 124 M Determine cause of water damaged ceiling tiles and replace tiles
394071 03/01/2017 430328 1 131 M Secure loose base along wall
394070 03/01/2017 430326 1 132B M Anchor toilet to floor
394077 03/01/2017 430340 1 170 M Provide current inspection tag for elevator
394067 03/01/2017 430320 1 185 M Determine cause of water damaged ceiling tiles and replace tiles
394058 03/01/2017 430301 1 191 M Determine cause of water damaged ceiling tiles and replace tiles
394062 03/01/2017 430309 1 196A M Provide certification that all student occupied spaces have emergency lights and all are operable, certificate dated August 2015 is expired
394063 03/01/2017 430311 1 196A M Repair or replace damaged door to 1-196B
394064 03/01/2017 430313 1 196B M Repair door to close properly, exterior door closes too fast
394089 03/01/2017 430364 1 201 M Determine cause of water damaged ceiling tiles and replace tiles
394088 03/01/2017 430362 1 201C M Repair ventilation fan
394087 03/01/2017 430360 1 207 M Determine cause of water damaged ceiling tiles and replace tiles
394086 03/01/2017 430358 1 207A M Repair ventilation fan
394085 03/01/2017 430356 1 210 M Determine cause of water damaged ceiling tiles and replace tiles
394090 03/01/2017 430366 1 214 M Determine cause of water damaged ceiling tiles and replace tiles
394091 03/01/2017 430369 1 214C M Replace missing escutcheon on fire sprinkler head
394092 03/01/2017 430371 1 215B M Determine cause of water damaged ceiling tiles and replace tiles
394093 03/01/2017 430373 1 218B M Repair ventilation fan
394094 03/01/2017 430375 1 219 M Determine cause of water damaged ceiling tiles and replace tiles
394095 03/01/2017 430377 1 222 M Determine cause of water damaged ceiling tiles and replace tiles
394096 03/01/2017 430379 1 228 M Determine cause of water damaged ceiling tiles and replace tiles
381714 03/01/2017 403625 1 291 M Repair air conditioning unit above door to ensure it operates as designed
394076 03/01/2017 430338 1 118 O Remove and prohibit air freshener
394075 03/01/2017 430336 1 123 O Prohibit running green extension cord at projector into ceiling
394074 03/01/2017 430334 1 124A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
191115 03/01/2017 25178 1 291 C Provide automatic fire sprinkler coverage for electrical room (walls are not 2 hour fire rated)
394079 03/01/2017 430344 1 106D OS Maintain clear aisle to stair exit door
394072 03/01/2017 430330 1 124 OS Prohibit hanging decorative grass over corridor exit door
394065 03/01/2017 430316 2 103 OS Prohibit storage of gas powered pressure cleaner, store in flammable storage room
394066 03/01/2017 430318 2 103A OS Provide clear access to fire extinguisher
381722 09/08/2016 403642 1 0000 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report 12.17.2014 - risers are in stairwell adjacent to main office
381709 09/07/2016 403615 00 9599 M Secure loose post for chain link fencing around propane gas tank north of chiller enclosure
381719 09/07/2016 403635 1 180 M Repair door to open and close properly - door rubs on frame
381559 09/07/2016 403292 2 105A M Repair exhaust fan in bathroom
381564 01/13/2016 403303 1 0000 M Adjust exit doors at end of corridor adjacent to 1-121 to latch properly
381565 01/13/2016 403305 1 0000 M Adjust exit doors at end of corridor adjacent to 1-108 to latch properly
381702 01/13/2016 403601 1 103 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to kitchen hood
381703 01/13/2016 403603 1 103 M Provide protective cage around fire sprinkler head in cooler and freezer (X2)
381704 01/13/2016 403605 1 103J M Determine cause of water damaged ceiling tiles and replace tiles in dry storage room
381707 01/13/2016 403611 1 104B M Determine cause of water damaged ceiling tiles and replace tiles in mens bathroom
381718 01/13/2016 403633 1 107E M Determine cause of water damaged ceiling tiles and replace tiles
381697 01/13/2016 403591 1 109A M Determine cause of water damaged ceiling tiles and replace tiles
381713 01/13/2016 403623 1 113A M Secure loose escutcheon on fire sprinkler head
381716 01/13/2016 403629 1 114A M Secure ceiling tile in place or replace
381557 01/13/2016 403288 1 127B M Caulk gap between sink and wall in bathroom
381556 01/13/2016 403286 1 129B M Caulk gap between sink and wall in bathroom
381543 01/13/2016 403259 1 130 M Secure loose drinking spout to sink
381555 01/13/2016 403284 1 131B M Caulk gap between sink and wall in bathroom
381554 01/13/2016 403282 1 132B M Caulk gap between sink and wall in bathroom
381700 01/13/2016 403597 1 185 M Determine cause of water damaged ceiling tiles and replace tiles above double doors
381701 01/13/2016 403599 1 185 M Adjust double doors to latch properly
381706 01/13/2016 403609 1 191 M Determine cause of water damaged ceiling tiles and replace tiles in communications room
381699 01/13/2016 403595 1 196 M Adjust door to latch properly
381563 01/13/2016 403301 1 198A M Repair air handler to eliminate water leak
381696 01/13/2016 403589 1 217 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to window
381695 01/13/2016 403587 1 217C M Repair exhaust fan in bathroom
381693 01/13/2016 403583 1 224B M Secure sink to wall
381694 01/13/2016 403585 1 294 M Secure ceiling tile in place
381558 01/13/2016 403290 2 102 M Repair exhaust fan in bathroom
381561 01/13/2016 403296 2 105A M Repair damaged plaster on ceiling
381560 01/13/2016 403294 2 190 M Repair exhaust fan in flammable storage room
381562 01/13/2016 403299 3 106 M Replace rotted wood ramp for golf cart storage trailer
381698 01/13/2016 403593 1 110 O Remove and prohibit excessive flammable vinyl pink skirting at teacher desk
381711 01/13/2016 403619 1 112 O Prohibit running electrical cord across floor in front of door to back of stage
381717 01/13/2016 403631 1 116A O Replace burned out light bulbs or have maintenance repair light fixture
381549 01/13/2016 403272 1 124 O Remove and prohibit excessive flammable vinyl skirting adjacent to teacher desk and vinyl sheathing on wall adjacent to sink
381550 01/13/2016 403274 1 124 O Remove and prohibit combustible shower curtain adjacent to corridor door
381547 01/13/2016 403268 1 125 O Remove and prohibit excessive flammable vinyl skirting at teacher desk and at table adjacent to sink
381548 01/13/2016 403270 1 125B O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
381545 01/13/2016 403263 1 126 O Remove and prohibit excessive flammable yellow vinyl table cloth and skirting in classroom
381546 01/13/2016 403265 1 127 O Remove and prohibit excessive flammable vinyl sheathing on walls: above microwave, adjacent to sink, adjacent to teacher desk and in corridor adjacent to corridor door (X4)
381544 01/13/2016 403261 1 128 O Remove and prohibit excessive flammable vinyl netting hanging from ceiling adjacent to corridor door
381541 01/13/2016 403255 1 129B O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
381542 01/13/2016 403257 1 131B O Remove paper covering bathroom name and number with raised and Braille characters
381552 01/13/2016 403278 1 132 O Remove and prohibit excessive flammable vinyl table cloth adjacent to corridor door
381553 01/13/2016 403280 1 132 O Remove paper covering electrical outlet adjacent to closet
381540 01/13/2016 403253 1 132A O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
381551 01/13/2016 403276 1 133 O Remove and prohibit excessive flammable vinyl skirting at table adjacent to corridor door and at teacher desk
381720 01/13/2016 403637 1 190 O Relocate storage to provide 3 ft clear path to electrical panels
381691 01/13/2016 403579 1 206 O Remove and prohibit combustible leopard print curtain stapled to wall adjacent to bathroom
381539 01/13/2016 403251 1 209A O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
381538 01/13/2016 403249 1 210A O Replace burned out light bulbs in bathroom or have maintenance repair light fixture
381715 01/13/2016 403627 1 215 O Remove and prohibit excessive flammable light blue vinyl sheathing on wall adjacent to sink counter
381721 01/13/2016 403639 1 0000 MS Repair door lever on exterior corridor doors at main entrance between admin. office and dining room - two levers are stuck in the vertical position
381705 01/13/2016 403607 1 103 MS Recharge fire extinguisher on west wall in serving area
381712 01/13/2016 403621 1 112 MS Adjust north door to latch properly
381566 01/13/2016 403307 1 197 MS Provide current inspection tag for fire extinguisher
381710 01/13/2016 403617 1 112 OS Relocate table to maintain 3 ft clear path to west exit door
381692 01/13/2016 403581 1 208 OS Relocate table to maintain 3 ft clear path to corridor door
381537 01/13/2016 403247 1 213 CS Provide auto closer on corridor door
366389 02/12/2015 370312 1 0000 M Determine cause of water damaged ceiling tiles in corridor adjacent to 1-102A and replace tiles
366396 02/12/2015 370326 1 0000 M Determine cause of water damaged ceiling tiles in corridor adjacent to 1-109 and replace tiles
366375 02/12/2015 370283 1 0000 M Remove and repair rust on damaged door frame on exit doors at bottom landing of stairway adjacent to 1-132
366377 02/12/2015 370287 1 0000 M Determine cause of water damaged ceiling tiles in second floor corridor adjacent to 1-230 and replace tiles
366382 02/12/2015 370297 1 0000 M Replace missing escutcheon on fire sprinkler head in second floor corridor adjacent to 1-204
366383 02/12/2015 370299 1 0000 M Determine cause of water damaged ceiling tiles in corridor adjacent to 1-201 and replace tiles
366384 02/12/2015 370301 1 102 M Determine cause of water damaged ceiling tiles and replace tiles
366388 02/12/2015 370310 1 102A M Repair emergency lighting
366391 02/12/2015 370316 1 103 M Determine cause of water damaged ceiling tiles in kitchen and replace tiles
366390 02/12/2015 370314 1 103F M Determine cause of water damaged ceiling tiles in kitchen manager's office and replace tiles
366392 02/12/2015 370318 1 103J M Determine cause of water damaged ceiling tiles and replace tiles
366393 02/12/2015 370320 1 104 M Determine cause of water damaged ceiling tiles in bathroom vestibule and replace tiles
366394 02/12/2015 370322 1 104C M Determine cause of water damaged ceiling tiles in teacher's dining room and replace tiles
366387 02/12/2015 370308 1 106B M Repair emergency lighting
366386 02/12/2015 370306 1 106D M Determine cause of water damaged ceiling tiles and replace tiles
366371 02/12/2015 370275 1 107D M Determine cause of water damaged ceiling tiles and replace tiles
366370 02/12/2015 370273 1 107E M Determine cause of water damaged ceiling tiles and replace tiles
366397 02/12/2015 370328 1 108 M Determine cause of water damaged ceiling tiles and replace tiles
366398 02/12/2015 370330 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
366399 02/12/2015 370332 1 109 M Replace missing escutcheon on fire sprinkler head adjacent to 1-109B
366400 02/12/2015 370334 1 111 M Determine cause of water damaged ceiling tiles and replace tiles
366401 02/12/2015 370336 1 112A M Secure loose vinyl base on north wall
366372 02/12/2015 370277 1 126B M Anchor shelving to wall
366373 02/12/2015 370279 1 128A M Repair door to close and latch properly
366369 02/12/2015 370271 1 141A M Secure loose toilet seat
366385 02/12/2015 370303 1 191 M Determine cause of water damaged ceiling tiles and replace tiles
366402 02/12/2015 370338 1 192 M Repair door to close and latch properly
366365 02/12/2015 370263 1 198 M Repair leak in chilled water pipe on air handler (water leaking onto floor)
366380 02/12/2015 370293 1 208 M Determine cause of water damaged ceiling tiles and replace tiles
366381 02/12/2015 370295 1 213 M Determine cause of water damaged ceiling tiles and replace tiles
366379 02/12/2015 370291 1 215 M Determine cause of water damaged ceiling tiles and replace tiles
366376 02/12/2015 370285 1 230 M Determine cause of water damaged ceiling tiles and replace tiles
366378 02/12/2015 370289 1 294 M Determine cause of water damaged ceiling tiles and replace tiles
366364 02/12/2015 370261 2 0000 M Remove rust and repair rusted areas on all doors on P.E. Pavillion
366363 02/12/2015 370259 00 0000 O Provide name of Lead Crowd Manager who successfully completed the Crowd Management course as indicated in Bulletin # P-14808
366374 02/12/2015 370281 1 132 O Prohibit plugging surge protector into surge protector
366368 02/12/2015 370269 1 0000 MS Adjust fire door in corridor adjacent to 1-171 to close and latch properly
366366 02/12/2015 370265 1 0000 MS Provide current inspection tag for fire extinguisher located in corridor adjacent to 1-182
366395 02/12/2015 370324 1 0000 MS Provide current inspection tag for fire extinguisher in corridor adjacent to 1-109
366367 02/12/2015 370267 1 171 MS Recharge fire extinguisher in elevator equipment room
353729 09/10/2014 342716 1 198A M Repair or replace rusted steel door frame
349654 12/12/2013 333446 1 0000 M Replace heavily rusted cover for fire alarm annunciator panel at school entrance
353789 12/12/2013 342860 1 0000 M Determine cause of water damaged ceiling tiles in second floor corridor adjacent to 1-290 and replace tiles
353794 12/12/2013 342870 1 0000 M Determine cause of water damaged ceiling tiles in second floor corrridor adjacent to 1-229 and replace tiles
353796 12/12/2013 342874 1 0000 M Provide cover on exposed electrical junction box inside fire sprinkler riser enclosure, in stairway adjacent to main office
353797 12/12/2013 342876 1 0000 M Provide sign or stencil sign on door of sprinkler riser enclosure indicating Fire Sprinkler Riser Inside (riser encloser is located in stairway adjacent to main office)
353710 12/12/2013 342674 1 101N M Determine cause of water damaged ceiling tiles and replace tiles
353782 12/12/2013 342840 1 106B M Repair emergency lighting in boys dressing room
353781 12/12/2013 342836 1 106C M Repair emergency lighting in girls dressing room
353784 12/12/2013 342846 1 106D M Determine cause of water damaged ceiling tiles and replace tiles
353713 12/12/2013 342680 1 107F M Determine cause of water damaged ceiling tiles and replace tiles
353778 12/12/2013 342830 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
353779 12/12/2013 342832 1 109A M Replace missing escutcheon on fire sprinkler head
353777 12/12/2013 342828 1 110 M Determine cause of water damaged ceiling tiles and replace tiles
353776 12/12/2013 342826 1 111 M Determine cause of water damaged ceiling tiles and replace tiles
353718 12/12/2013 342691 1 125B M Anchor shelving to wall in storage room
353716 12/12/2013 342687 1 127B M Repair bathroom door to close properly (door hits door jamb and does not close properly)
353714 12/12/2013 342682 1 132B M Replace missing escutcheon on fire sprinkler head in bathroom
353786 12/12/2013 342852 1 185 M Determine cause of water damaged ceiling tiles and replace tiles
353783 12/12/2013 342842 1 191 M Determine cause of water damaged ceiling tiles and replace tiles
353780 12/12/2013 342834 1 193 M Repair emergency lighting in mechanical room
353785 12/12/2013 342848 1 196A M Repair emergency lighting in generator room
353787 12/12/2013 342854 1 201 M Determine cause of water damaged ceiling tiles and replace tiles
353788 12/12/2013 342858 1 203 M Replace missing escutcheon on fire sprinkler head
353791 12/12/2013 342864 1 222 M Trim tree branches away from the exterior of emergency egress window
353793 12/12/2013 342868 1 229 M Determine cause of water damaged ceiling tiles and replace tiles
353795 12/12/2013 342872 1 230 M Determine cause of water damaged ceiling tiles and replace tiles
318638 12/12/2013 265752 1 291 M Repair air conditioning unit above door to work properly in electrical room
353790 12/12/2013 342862 1 294 M Determine cause of water damaged ceiling tiles and replace tiles
349628 12/12/2013 333392 2 0000 M Remove rust, prime and paint rusted bottom of columns at pavilion
353728 12/12/2013 342713 2 102 M Repair or replace rusted steel door frame
353727 12/12/2013 342711 2 103 M Repair or replace rusted steel door frame
353711 12/12/2013 342676 1 101Q O Eliminate multiple outlet extension cord powering lamp or replace extension cord with minimum 15A cord
353719 12/12/2013 342693 1 124 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
353792 12/12/2013 342866 1 227A O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
353712 12/12/2013 342678 1 190 OS Remove storage from electrical room
349629 09/26/2013 333394 1 198B M Repair door to open and close properly - door rubs on frame
349630 09/26/2013 333396 1 198B M Replace heavily damaged and rusted door and frame
349632 09/26/2013 333400 1 198B M Replace heavily rusted vent grille above door
349633 09/26/2013 333402 1 198C M Replace heavily rusted vent grille above door
349631 09/26/2013 333398 1 198C M Replace heavily damaged and rusted door and frame
349643 04/30/2013 333423 1 110 M Adjust water flow for drinking spout
349612 04/30/2013 333359 1 180 M Adjust door to latch properly - door rubs on frame
349639 04/30/2013 333414 1 185 M Adjust single door to latch properly
349638 04/30/2013 333412 1 191 M Determine cause of water damaged ceiling tiles and replace tiles
349626 04/30/2013 333387 1 195 M Repair air conditioning unit above door to work properly
349622 04/30/2013 333379 1 214A M Determine cause of water damaged ceiling tiles and replace tiles
349618 04/30/2013 333371 1 215 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to teacher desk
349621 04/30/2013 333377 1 215B M Determine cause of water damaged ceiling tiles and replace tiles
349625 04/30/2013 333385 1 294 M Repair air conditioning unit above door to work properly
349627 04/30/2013 333390 2 105 M Secure loose grille for air conditioning unit on exterior wall adjacent to door
349644 04/30/2013 333425 1 111 O Remove and prohibit paper covering window in corridor door
349645 04/30/2013 333427 1 114 O Remove and prohibit hanging decorations from ceiling
349646 04/30/2013 333429 1 118 O Remove and prohibit hanging decorations (lanterns) from ceiling
349637 04/30/2013 333410 1 121A O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
349636 04/30/2013 333408 1 124 O Remove and prohibit hanging paper and decorations from ceiling
349635 04/30/2013 333406 1 125 O Remove and prohibit hanging paper from ceiling
349647 04/30/2013 333431 1 126 O Remove and prohibit hanging decorations from ceiling
349649 04/30/2013 333435 1 128 O Remove and prohibit hanging curtains from ceiling
349650 04/30/2013 333437 1 130 O Remove and prohibit hanging paper from ceiling
349651 04/30/2013 333439 1 130 O Remove and prohibit combustible beanbag chair
349648 04/30/2013 333433 1 130B O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
349634 04/30/2013 333404 1 131 O Remove and prohibit paper covering glass windows
349652 04/30/2013 333441 1 132 O Remove and prohibit hanging paper from ceiling
349615 04/30/2013 333365 1 204 O Eliminate string line below 6 feet 8 inches running across room - can run string line along walls and up to 2 inches away from walls
349614 04/30/2013 333363 1 209 O Remove and prohibit hanging paper from ceiling
349613 04/30/2013 333361 1 210 O Remove and prohibit hanging paper from ceiling
349624 04/30/2013 333383 1 213 O Keep door locked and latched to prohibit student access - room has access ladder to roof
349619 04/30/2013 333373 1 215 O Remove and prohibit paper covering glass windows
349620 04/30/2013 333375 1 215 O Remove and prohibit paper covering electrical outlets under writing board
349617 04/30/2013 333369 1 217A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
349616 04/30/2013 333367 1 221 O Remove and prohibit paper covering glass windows
349623 04/30/2013 333381 1 213 MS Remove dog leg hold open device from fire door
349641 04/30/2013 333419 1 112 OS Relocate piano to maintain 3 ft clear path to corridor door
349642 04/30/2013 333421 1 112B OS Remove and prohibit use or storage of space heater
349653 04/30/2013 333443 1 132A OS Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
349640 04/30/2013 333416 00 0000 CS Provide suitable area for charging floor cleaning machines
336361 02/04/2013 304822 1 0000 MS Provide current, complete inspection tags for fire sprinkler system. Both annual and quarterly inspection punched. East stairwell adjacent to 1-101
336341 02/04/2013 304774 1 0000 CS Provide automatic fire sprinkler coverage for first floor areas under stairs in east facing stairwells (x2) (coverage is needed, confirmed by D. Betts) - (NA - not required per NFPA 13, 8.15.3.2.1 verified with M. Lodge)
336337 05/01/2012 304766 1 0000 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to 1-107D
336362 05/01/2012 304824 1 0000 M Verify location of spare fire sprinkler heads and wrench box. Not visible at fire sprinkler riser in east stairwell adjacent to 1-101
336363 05/01/2012 304826 1 0000 M Provide covers on exposed electrical junction boxes adjacent to fire sprinkler risers in east stairwell adjacent to 1-101
336348 05/01/2012 304790 1 0000 M Close ceiling access hatch at hurricane shutters at west center corridor doors
336351 05/01/2012 304796 1 0000 M Adjust smoke doors adjacent to 1-112 to close properly
318716 05/01/2012 265916 1 102 M Provide dated flame resistance label on stage curtains in dining room
318715 05/01/2012 265914 1 106 M Provide dated flame resistance label on all stage curtains
318713 05/01/2012 265910 1 107C M Provide dated flame resistance label on curtains in CCTV studio
336355 05/01/2012 304805 1 108 M Repair broken corridor door handle
336354 05/01/2012 304803 1 108A M Replace broken toilet seat
336349 05/01/2012 304792 1 113 M Replace missing ceiling tile
336357 05/01/2012 304809 1 185 M Determine cause of water damaged ceiling tiles and replace tiles
336356 05/01/2012 304807 1 196A M Repair emergency lighting
336344 05/01/2012 304782 1 198A M Pad and mark corners of AHU-5 duct which are lower than 6 feet 8 inches
336301 05/01/2012 304682 1 214 M Determine cause of water damaged ceiling tiles and replace tiles
336300 05/01/2012 304680 1 215 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to windows and lights at 1-215B
336287 05/01/2012 304653 1 218 M Secure loose data outlet box located on wall under audio enhancement unit
336286 05/01/2012 304650 1 293 M Verify that gap between bottom of door and floor tile is acceptable or replace (damaged) door (maintenance was instructed to cut door to ventilate room)
275372 05/01/2012 172328 1 0000 O Highlight primary and secondary evacuation routes on all evactuation maps
336353 05/01/2012 304800 1 108 O Prohibit hanging papers on windows
336352 05/01/2012 304798 1 111 O Prohibit hanging papers on windows
336350 05/01/2012 304794 1 113B O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
336347 05/01/2012 304788 1 117 O Relocate string line to be no more than 2 inches from wall, prohibit papers hanging from ceiling
336345 05/01/2012 304784 1 123 O Prohibit brown 13A extension cord at projector or replace with minimum 15A single outlet cord
336346 05/01/2012 304786 1 123 O Remove and prohibit excessive paper coverage hanging on walls and prohibit decorations hanging from ceiling
336342 05/01/2012 304777 1 125 O Relocate string line to hang no more than 2 inches from wall
336338 05/01/2012 304768 1 128 O Replace missing sign indicating primary and secondary evacuation routes
336339 05/01/2012 304770 1 128 O Prohibit green multi outlet extension cord adjacent to teachers computer or replace with minimum 15A single outlet cord
336284 05/01/2012 304644 1 207 O Prohibit papers hanging from ceiling
336283 05/01/2012 304641 1 210 O Prohibit papers hanging from ceiling
336299 05/01/2012 304678 1 217 O Prohibit papers hanging from ceiling
336288 05/01/2012 304655 1 218 O Prohibit plugging surge protector into surge protector at computers adjacent to office call button
336298 05/01/2012 304676 1 224 O Prohibit papers hanging on windows
336297 05/01/2012 304674 1 225 O Prohibit papers hanging from ceiling and on windows
336296 05/01/2012 304672 1 227A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
336290 05/01/2012 304660 1 228B O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
336295 05/01/2012 304670 1 229B O Prohibit papers hanging from ceiling
336294 05/01/2012 304666 1 230 O Prohibit hanging papers on window blinds
336343 05/01/2012 304779 2 105 O Prohibit plugging microwave and refrigerator into black multi outlet extension cord - plug directly into permanent electrical outlet, prohibit multi outlet extension cord
293179 05/01/2012 210358 00 0000 C Indicate primary and secondary evacuation routes on evacuation maps with directional arrows, not verbal directions
336302 05/01/2012 304684 1 182 C Provide auto closer on door
336358 05/01/2012 304811 1 193 C Provide auto closer on corridor door
191117 05/01/2012 25226 1 294 C Provide adequate ventilation for electrical room (room is too hot)
336359 05/01/2012 304813 1 102 MS Prohibit running electrical cords for mounted TVs (x2) and projector into ceiling
336360 05/01/2012 304819 1 103 MS Provide current inspection tag for kitchen hood fire suppression system
336291 05/01/2012 304662 1 230 MS Provide current inspection tag for type K fire extinguisher
318724 05/01/2012 265932 1 0000 OS Remove plants from corridor adjacent to 1-132
336340 05/01/2012 304772 1 132 OS Prohibit running electrical cord under connecting door to 1-130
336285 05/01/2012 304647 1 218 OS Remove and prohibit use of hot plate
336289 05/01/2012 304657 1 218 OS Prohibit storage of charcoal
318675 02/24/2011 265831 1 113 M Adjust door closer to control speed of closing door
318591 02/24/2011 265657 1 129 M Mount evacuation map at 5 ft to center
318606 02/24/2011 265689 1 198B M Adjust door to latch properly
318607 02/24/2011 265692 2 105 M Mount fire extinguisher at maximum five feet above floor
318629 02/24/2011 265738 1 106D O Relocate storage to keep area within 18" of fire sprinkler head clear and unobstructed
318625 02/24/2011 265727 1 107E O Relocate globes above top shelf to keep area within 18" of fire sprinkler head clear and unobstructed
318711 02/24/2011 265906 1 113 O Tape down curled edges on rug or remove
318587 02/24/2011 265651 1 115 O Replace missing evacuation map in class
318665 02/24/2011 265806 1 117 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
318613 02/24/2011 265704 1 124 O Remove mirror adjacent to sink or provide mirror made of tempered glass, safety glass, or stainless steel
318618 02/24/2011 265712 1 124A O Relocate storage to keep area within 18" of fire sprinkler head clear and unobstructed
318679 02/24/2011 265839 1 125 O Eliminate 13A extension cord for document camera
318619 02/24/2011 265718 1 125A O Relocate storage to keep area within 18" of fire sprinkler head clear and unobstructed
318712 02/24/2011 265908 1 126 O Remove or replace slippery floor mat adjacent to closet door
318681 02/24/2011 265843 1 127A O Maintain storage room in an orderly manner
318721 02/24/2011 265926 1 131 O Eliminate 13A white extension cord with multiple outlet end adjacent to teacher's desk or replace with a surge protector
318722 02/24/2011 265928 1 131 O Eliminate (3) plug electrical outlet adaptor adjacent to teacher's desk or replace with a surge protector
318723 02/24/2011 265930 1 131 O Prohibit plugging surge protector into surge protector under computer stations - plug each surge protector directly into wall outlet
318595 02/24/2011 265668 1 131 O Replace missing evacuation map in class
318594 02/24/2011 265663 1 133 O Replace missing evacuation map in class
318580 02/24/2011 265617 1 214 O Replace missing evacuation map in classroom
318646 02/24/2011 265768 1 219 O Replace burned light bulbs in light fixture adjacent to closet
318649 02/24/2011 265776 1 219 O Remove solid paper covering corridor door
318584 02/24/2011 265645 1 224 O Replace missing evacuation map in class
318717 02/24/2011 265918 1 102 C Provide records that rigging has been inspected and conforms to required safety standards in dining room (included in stage rigging report per Tom Kat Rigging - report is posted on stage 1-106)
318714 02/24/2011 265912 1 107C C Provide records that CCTV studio rigging has been inspected and conforms to required safety standards
318670 02/24/2011 265818 00 0000 MS Provide current inspection tag for fire sprinkler system - inspected quarterly (6/1/10). Riser is in stairwell adjacent to 1-101
318568 02/24/2011 265610 1 101J MS Provide current inspection tag for fire extinguisher
318633 02/24/2011 265744 1 109 MS Adjust corridor door to latch properly
318569 02/24/2011 265613 1 171 MS Provide current inspection tag for fire extinguisher
318641 02/24/2011 265763 1 0000 OS Remove table from corridor adjacent to 1-226
318677 02/24/2011 265835 1 113 OS Relocate table adjacent to corridor door - table projects into door opening
318718 02/24/2011 265920 1 185 OS Prohibit storage and charging golf cart in room - Relocate to 3-106 adjacent to PE Bldg.
318658 02/24/2011 265785 1 217 OS Relocate table adjacent to corridor door - table projects into door opening
318660 02/24/2011 265800 1 225 OS Relocate table adjacent to corridor door - table projects into door opening
318720 02/24/2011 265924 2 103 OS Prohibit storage and charging floor cleaning machines in room - Relocate to 3-106
318719 02/24/2011 265922 2 104 OS Prohibit storage of golf cart in room - Relocate to 3-106
299244 01/18/2010 223405 1 0000 M Replace missing glass panel in fire extinguisher cabinet in corridor adjacent to 1-101
299242 01/18/2010 223401 1 0000 M Determine cause of water damaged ceiling tiles and replace tiles in stairway adjacent to 1-294
299233 01/18/2010 223383 1 0000 M Adjust smoke doors in corridor adjacent to 1-117 so that the doors will close properly (doors hit each other and will not close)
299226 01/18/2010 223368 1 102 M Determine cause of water damaged ceiling tiles at northeast corner of cafeteria and replace tiles
299230 01/18/2010 223376 1 103 M Repair walk-in freezer door to close and latch properly
299229 01/18/2010 223374 1 103C M Re-attach dryer vent pipe on back of dryer
291565 01/18/2010 206897 1 170 M Provide current inspection tag for elevator
299227 01/18/2010 223370 1 185 M Secure fire extinguisher bracket by door
299239 01/18/2010 223395 1 195 M Repair inoperable air conditioner (electric room is overheated)
299231 01/18/2010 223378 1 110 O Eliminate 13 amp multiple outlet extension cord powering lamp
299232 01/18/2010 223380 1 117 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
299238 01/18/2010 223393 1 124A O Keep area within 18" of fire sprinkler head clear
299240 01/18/2010 223397 1 129B O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
299241 01/18/2010 223399 1 223B O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
299234 01/18/2010 223385 1 119B C Provide tempered glass, safety glass, or stainless steel for mirrors
299235 01/18/2010 223387 1 119C C Provide tempered glass, safety glass, or stainless steel for mirrors
299236 01/18/2010 223389 1 194B MS Replace badly rusted sprinkler piping in mechanical room
299228 01/18/2010 223372 1 196B MS Seal penetration around conduit in east wall of switch gear room
299243 01/18/2010 223403 1 294 MS Provide current inspection tag for fire extinguisher
245515 01/18/2010 110645 1 185 OS Prohibit charging batteries in room
299237 01/18/2010 223391 1 194B OS Remove storage from mechanical room
291760 09/03/2009 207330 1 101 M Modify sign adjacent to exterior door to read 1-101, not 1-101X
191099 09/03/2009 25232 1 103 M Provide current inspection tag for kitchen boiler (steamer)
291603 09/03/2009 206982 3 106 M Provide sign at door indicating door is to be in locked open or locked closed position at all times
191111 09/03/2009 25175 1 201 C Lower emergency rescue opening to be maximum 44" above finished floor (Not required per Victor Chodora 6-7-06)
291567 09/03/2009 206901 1 107C OS Relocate chairs to maintain clear aisle to exit
291600 04/20/2009 206976 00 0000 M Install cap on fire department standpipe connection, exterior wall adjacent to NE stairwell
291601 04/20/2009 206978 00 0000 M Keep PIV valve in Open position
291616 04/20/2009 207010 1 0000 M Replace missing escutcheon on fire sprinkler head in corridor between rooms 1-224 and 1-225
291564 04/20/2009 206895 1 101 M Verify that glass in display cabinet is tempered or has safety glazing or provide safety glazing for glass
291597 04/20/2009 206968 1 102 M Replace broken plastic in door of fire extinguisher cabinet, adjacent to 1-191 and SE exterior door
291599 04/20/2009 206974 1 103 M Repalce broken floor tiles in freezer
291569 04/20/2009 206905 1 198A M Verify air handler is functioning properly, it vibrates excessively
291596 04/20/2009 206966 1 198C M Pad and mark corners of hot water heater shelf which are lower than 6'8
291666 04/20/2009 207124 1 208 M Replace missing escutcheon on fire sprinkler head
291610 04/20/2009 206997 1 213 M Replace missing ceiling tile
291611 04/20/2009 206999 1 291 M Mount fire extinguisher at maximum five feet above floor
291669 04/20/2009 207130 2 9699 M Repair damaged drinking fountain
291566 04/20/2009 206899 1 107B O Prohibit plugging surge protector into surge protector
291668 04/20/2009 207128 1 109 O Remove excessive flammable wall coverings and decorations
291667 04/20/2009 207126 1 110 O Remove excessive flammable wall coverings and decorations
291677 04/20/2009 207146 1 114 O Prohibit use of multi outlet electrical adaptors (x2 under teacher's desk)
291678 04/20/2009 207148 1 114 O Remove and prohibit air freshener
291675 04/20/2009 207142 1 114B O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
291676 04/20/2009 207144 1 114B O Remove and prohibit air freshener
291673 04/20/2009 207138 1 117 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
291672 04/20/2009 207136 1 118 O Remove and prohibit air freshener
291607 04/20/2009 206990 1 121A O Prohibit plugging refrigerator and microwave into multi outlet adaptor - plug directly into permanent electrical outlet
291671 04/20/2009 207134 1 127 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
291661 04/20/2009 207114 1 132 O Remove excessive flammable wall coverings
291663 04/20/2009 207118 1 207 O Treat residential furniture with flame retardant spray or remove and prohibit combustible (residential) furniture
291664 04/20/2009 207120 1 210 O Remove and prohibit air freshener
291662 04/20/2009 207116 1 217 O Remove excessive flammable wall coverings
291622 04/20/2009 207022 1 219 O Remove and prohibit paper covering window in door
291620 04/20/2009 207018 1 226A O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
291617 04/20/2009 207012 1 230 O Remove storage from stove burners
291602 04/20/2009 206980 1 101 F Set clock on fire alarm panel to correct time
291609 04/20/2009 206994 1 0000 MS Adjust fire doors at top of stairs adjacent to 1-291 to latch properly
291563 04/20/2009 206893 1 101J MS Provide current inspection tag for fire extinguisher
291670 04/20/2009 207132 1 124 MS Provide current inspection tag for fire extinguisher
291605 04/20/2009 206986 1 132 MS Provide current inspection tag for fire extinguisher
291608 04/20/2009 206992 1 191 MS Provide current inspection tag for fire extinguisher
291621 04/20/2009 207020 1 224 MS Provide current inspection tag for fire extinguisher
291618 04/20/2009 207014 1 230 MS Provide current inspection tag for fire extinguisher
291598 04/20/2009 206972 1 103D OS Prohibit storage of sterno fuel
291674 04/20/2009 207140 1 114B OS Remove and prohibit use of toaster oven
291679 04/20/2009 207150 1 115 OS Remove and prohibit candles
291568 04/20/2009 206903 1 119A OS Relocate file cabinet to maintain clear aisle to exit
291612 04/20/2009 207002 1 201 OS Keep area clear at emergency rescue window
291613 04/20/2009 207004 1 201A OS Prohibit running electrical cord under door
291665 04/20/2009 207122 1 202 OS Keep area clear at emergency rescue window
291615 04/20/2009 207008 1 222 OS Keep area clear at emergency rescue window
291604 04/20/2009 206984 1 227 OS Prohibit hold open devices on fire door
291619 04/20/2009 207016 1 230 OS Remove and prohibit candle
255330 11/25/2008 131718 1 201 M Replace missing sign indicating emergency rescue window
245520 11/25/2008 110650 1 0000 C Provide ventilated room or building for recharging batteries of floor machines and electric carts (per Brad, corrected by installation of Mtl. Stor. Bldg. CCd by Bldg. Dept. Verify exp. proof heat detector and exhaust fan, signage indicating door to be in locked open/close position, doors are adequate distance from adjacent building per Victor)
191114 11/25/2008 25224 1 291 C Provide adequate ventilation for electrical room (room is too hot)
275317 03/26/2008 172216 00 0000 M Provide padlock on Chiller Enclosure
275342 03/26/2008 172218 00 0000 M Provide covers for inground valves (x2)which are enclosed by plastic pipes. Pipes protrude from grass, open tops create a hazard. Located in grass adjacent to 1-197
275369 03/26/2008 172319 1 0000 M Add extender to magnet on fire door adjacent to 1-106C to allow door to be held open by magnet
275455 03/26/2008 172499 1 0000 M Determine cause of water damaged ceiling tiles and replace tiles in stairwell adjacent to 1-124
275202 03/26/2008 171973 1 102 M Determine cause of water damaged ceiling tiles and replace tiles
275357 03/26/2008 172277 1 103 M Align two burner stove to be directly under supression nozzle
275362 03/26/2008 172302 1 103 M Paint line around two burner stove to ensure correct placement
275364 03/26/2008 172315 1 106B M Repair emergency lighting
275430 03/26/2008 172455 1 107D M Determine cause of water damaged ceiling tiles and replace tiles
275373 03/26/2008 172333 1 108A M Determine cause of water damaged ceiling tiles and replace tiles
275374 03/26/2008 172335 1 109A M Determine cause of water damaged ceiling tiles and replace tiles
275204 03/26/2008 171977 1 112 M Provide cover on exposed electrical junction box in ceiling adjacent to projector
275409 03/26/2008 172411 1 125B M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
275413 03/26/2008 172419 1 132 M Determine cause of water damaged ceiling tiles and replace tiles
275381 03/26/2008 172351 1 184 M Determine cause of water damaged ceiling tiles and replace tiles
275314 03/26/2008 172209 1 185 M Replace missing ceiling tiles
275380 03/26/2008 172340 1 194B M Repair leaking chilled water return
275370 03/26/2008 172326 1 197 M Mount fire extinguisher at maximum five feet above floor
275434 03/26/2008 172463 1 204 M Replace missing escutcheon on fire sprinkler head
275457 03/26/2008 172511 1 222 M Determine cause of water damaged ceiling tiles and replace tiles
275436 03/26/2008 172468 1 294 M Replace cracked ceiling tile
275402 03/26/2008 172370 2 9699 M Provide weather cover for electrical outlet in covered play area
275203 03/26/2008 171975 1 106 O Prohibit orange 13A extension cord on stage or replace with minimum 15A cord
275313 03/26/2008 172207 1 112 O Prohibit plugging surge protector into surge protector @ computers
275411 03/26/2008 172417 1 133A O Remove and prohibit air freshener
275431 03/26/2008 172460 1 209 O Remove and prohibit air freshener
275467 03/26/2008 172531 1 224 O Remove and prohibit air freshener
275469 03/26/2008 172536 1 225 O Remove and prohibit paper covering window in door
275473 03/26/2008 172541 1 225 O Prohibit brown 13A extension cord (@ projector) or replace with minimum 15A cord
275474 03/26/2008 172548 1 227 O Remove and prohibit air freshener
275487 03/26/2008 172573 1 228 O Remove and prohibit air freshener
275483 03/26/2008 172562 1 229 O Maintain classroom and storage closet in an orderly manner
275385 03/26/2008 172356 1 195 C Provide adequate ventilation for electrical room (room is too hot)
275405 03/26/2008 172402 1 198C MS Replace missing fire extinguisher
275489 03/26/2008 172576 1 108 OS Prohibit hold open devices on fire door
275410 03/26/2008 172415 1 126 OS Remove and prohibit candles
275375 03/26/2008 172337 1 192 OS Remove storage from electrical room
275315 03/26/2008 172212 1 196 OS Remove storage from electrical room
275462 03/26/2008 172516 1 222 OS Keep area clear to emergency rescue window
275464 03/26/2008 172526 1 223B OS Prohibit storage of flammable materials (white board cleaner)
275485 03/26/2008 172569 1 230 OS Keep area clear to emergency rescue window
275388 03/26/2008 172366 2 103 OS Prohibit storage of gasoline and gas powered pressure cleaner
275316 03/26/2008 172214 1 196B FS Verify location of heat detector in switch gear room or provide heat detector
255255 02/09/2007 131560 1 0000 M Determine cause of corrosion and replace corroded sprinkler head in corridor adjacent to 1-121
255352 02/09/2007 131754 1 101A M Lower fire sprinkler head to be a minimum 1" below ceiling
255353 02/09/2007 131767 1 101A M Determine cause of water damaged ceiling tiles and replace damaged and missing tiles
255229 02/09/2007 131505 1 101C M Repair noisy exhaust fan in bathroom
255355 02/09/2007 131770 1 101J M Determine cause of water damaged ceiling tiles and replace tiles
255234 02/09/2007 131516 1 103 M Replace missing escutcheon on fire sprinkler head in freezer
255235 02/09/2007 131518 1 103E M Repair exhaust fan in bathroom
255232 02/09/2007 131511 1 104A M Repair exhaust fan in bathroom
255233 02/09/2007 131514 1 104B M Repair exhaust fan in bathroom
255231 02/09/2007 131509 1 104C M Determine cause of water damaged ceiling tiles and replace tiles
255260 02/09/2007 131572 1 109 M Adjust temperature of air conditioning per teacher
255258 02/09/2007 131566 1 114 M Replace missing escutcheon on fire sprinkler head
255264 02/09/2007 131579 1 132 M Determine cause of water damaged ceiling tiles and replace tiles
245498 02/09/2007 110613 1 182 M Replace missing escutcheon on fire sprinkler head
255241 02/09/2007 131524 1 194A M Provide correct signage indicating room name and number at appropriate height with raised and Braille characters. Current sign states room is an Electrical Room and it is not. The room is being used for storage
255247 02/09/2007 131544 1 194B M Mount fire extinguisher at maximum five feet above floor
255338 02/09/2007 131726 1 198B M Reposition drain pipe over drain hole to prevent water from draining on floor. Keep floor dry
255287 02/09/2007 131629 1 214B M Secure loose escutcheon on fire sprinkler head
255284 02/09/2007 131623 1 222 M Determine cause of water damaged ceiling tiles and replace tiles
255282 02/09/2007 131619 1 224 M Secure loose escutcheon on fire sprinkler head
255279 02/09/2007 131612 1 230 M Repair single action lever on emergency rescue window
255236 02/09/2007 131520 1 106B O No access was available to this room. Please be prepared to access this room during the report review meeting
255257 02/09/2007 131564 1 117 O Eliminate three 13A extension cords or replace with minimum 15A cords. Prohibit extension cords with multi outlets (One brown and two grey cords)
255253 02/09/2007 131556 1 197 O No access was available to this room. Please be prepared to access this room during the report review meeting
255252 02/09/2007 131554 1 198B O No access was available to this room. Please be prepared to access this room during the report review meeting
255294 02/09/2007 131643 1 201 O Prohibit white 13A extension cord or replace with minimum 15A cord
255291 02/09/2007 131637 1 203 O Prohibit brown 13A extension cord or replace with minimum 15A cord
255293 02/09/2007 131641 1 206 O Remove and prohibit bathroom air freshener and Lysol spray
255290 02/09/2007 131635 1 207 O Post sign indicating evacuation routes
255288 02/09/2007 131631 1 210 O Remove and prohibit air freshener
255286 02/09/2007 131627 1 217 O Prohibit white 13A extension cord or replace with minimum 15A cord
255281 02/09/2007 131617 1 224 O Prohibit plugging microwave into surge protector, plug microwave directly into wall outlet
255249 02/09/2007 131548 2 103 O No access was available to this room. Please be prepared to access this room during the report review meeting
255251 02/09/2007 131552 2 190 O No access was available to this room. Please be prepared to access this room during the report review meeting
191102 02/09/2007 25223 1 195 C Provide adequate ventilation for electrical room (room is too hot)
255356 02/09/2007 131773 1 101M MS Provide current inspection tag for fire extinguisher
255256 02/09/2007 131562 1 121 MS Provide current inspection tag for fire extinguisher
255254 02/09/2007 131558 1 124 MS Provide current inspection tag for fire extinguisher
255261 02/09/2007 131574 1 127 MS Provide current inspection tag for fire extinguisher
255263 02/09/2007 131576 1 131 MS Provide current inspection tag for fire extinguisher
255230 02/09/2007 131507 1 191 MS Provide current inspection tag for fire extinguisher
255280 02/09/2007 131614 1 224 MS Provide current inspection tag for fire extinguisher
255265 02/09/2007 131582 1 230 MS Provide current inspection tag for fire extinguisher
255248 02/09/2007 131546 1 126 OS Remove lamp with modified electric cord, adjacent to teacher's desk
255327 02/09/2007 131709 1 201 OS Prohibit white multi outlet extension cord running under door into storage room. Replace with minimum 15A cord and prohibit cord under door
255292 02/09/2007 131639 1 206 OS Remove and prohibit candles
255285 02/09/2007 131625 1 221 OS Remove and prohibit candle
255277 02/09/2007 131608 1 229 OS Keep area clear to emergency rescue window
255278 02/09/2007 131610 1 230 OS Keep area clear to emergency rescue window
255283 02/09/2007 131621 1 281 OS Prohibit charging batteries in room
255250 02/09/2007 131550 2 104 OS Prohibit charging batteries in room
191103 02/09/2007 25170 1 196B CS Provide automatic fire sprinkler coverage for electrical room (walls are not 2 hour fire rated)
191104 02/09/2007 25171 1 198 CS Provide automatic fire sprinkler coverage for mechanical room
191106 02/09/2007 25172 1 198A CS Provide automatic fire sprinkler coverage for mechanical room
191108 02/09/2007 25173 1 198B CS Provide automatic fire sprinkler coverage for mechanical room
191110 02/09/2007 25174 1 198C CS Provide automatic fire sprinkler coverage for mechanical room
255289 09/18/2006 131633 1 170 M Provide certification that elevator has current inspection tag
255237 09/18/2006 131522 1 112 O Prohibit surge protector plugged into surge protector, plug each surge protector directly into wall outlet
255323 09/18/2006 131703 1 201 O Prohibit surge protector plugged into surge protector, plug each surge protector directly into wall outlet
191116 09/18/2006 32260 1 293 C Provide adequate ventilation for communications room (room is too hot)
245484 09/18/2006 110581 00 0000 MS Provide current inspection tags for all fire extinguishers throughout entire campus
245479 09/18/2006 110563 1 0000 MS Provide current inspection tag for fire sprinkler system in stairwell outside 1-101
255332 09/18/2006 131721 1 201 OS Keep area clear to emergency rescue window
245503 03/29/2006 110621 1 0000 M Determine cause of water damaged ceiling tiles in corridors adjacent to 1-102, 1-101H, and stairway adjacent to 1-171 and replace tiles
245505 03/29/2006 110627 1 102 M Determine cause of water damaged ceiling tiles in storage areas at northeast and southeast corners of cafeteria and replace tiles
245501 03/29/2006 110617 1 102D M Repair deteriorated ceiling in womens bathroom
245508 03/29/2006 110633 1 103 M Replace missing escutcheon on fire sprinkler head at serving line
245512 03/29/2006 110641 1 103 M Repair damaged tile flooring inside walk-in freeer
245510 03/29/2006 110636 1 104C M Determine cause of water damaged ceiling tiles in teachers dining room and replace tiles
245506 03/29/2006 110630 1 105A M Repair deteriorated ceiling in girls bathroom
245496 03/29/2006 110610 1 112 M Determine cause of water damaged ceiling tiles and replace tiles
245495 03/29/2006 110605 1 113 M Provide cover on exposed electrical junction box in ceiling next to overhead projector
245528 03/29/2006 110674 1 213 M Determine cause of water damaged ceiling tiles and replace tiles
245522 03/29/2006 110662 1 222 M Determine cause of water damaged ceiling tiles and replace tiles
245527 03/29/2006 110670 1 0000 OS Prohibit use of hold open devices (wedges) on corridor doors throughout campus
245487 03/29/2006 110591 1 190 OS Remove storage from electrical room
245521 03/29/2006 110659 2 104 OS Prohibit storage of flammable mineral spirits
232539 12/09/2005 87909 1 103C M Replace plastic flexible exhaust duct for dryer with a metal duct
232586 12/09/2005 88010 2 102 M Repair exhaust fan in bathroom
232568 02/11/2005 87970 1 0000 M Adjust exterior door at bottom of stairwell adjacent to 1-133 to latch properly
232581 02/11/2005 87999 1 103 M Replace missing escutcheon on fire sprinkler head in freezer
232577 02/11/2005 87990 1 103J M Adjust sprinkler head to extend a minimum of 1" below escutcheon
191100 02/11/2005 25168 1 112 M Fill in maximum occupancy sign to indicate allowable maximum occupancy
232541 02/11/2005 87913 1 121B M Replace missing ceiling tiles around exhaust fan in kiln room
232578 02/11/2005 87993 1 122 M Adjust sprinkler head to extend a minimum of 1" below escutcheon
232582 02/11/2005 88001 1 185 M Replace missing escutcheon on fire sprinkler head
232540 02/11/2005 87911 1 185 M Replace plastic flexible exhaust duct for dryer with a metal duct
232579 02/11/2005 87995 1 206B M Adjust sprinkler head to extend a minimum of 1" below escutcheon
232580 02/11/2005 87997 1 216 M Adjust sprinkler head to extend a minimum of 1" below escutcheon
232570 02/11/2005 87974 1 110B O Remove and prohibit use of toaster oven
232543 02/11/2005 87917 1 115 O Prohibit use of surge protector to power microwave, plug appliances directly into wall outlet
232557 02/11/2005 87946 1 123 O Provide certification that carpet meets flame spread requirement or remove carpet
232571 02/11/2005 87976 1 124 O Remove paper tray from stove burners to eliminate fire hazard
232558 02/11/2005 87948 1 125 O Provide certification that area rug meets flame spread requirement or remove area rug
232561 02/11/2005 87954 1 125 O Remove and prohibit combustible residential small chair
232544 02/11/2005 87919 1 125 O Prohibit plugging one surge protector into another under computer stations, plug surge protector directly into wall outlet
232562 02/11/2005 87956 1 127 O Remove and prohibit combustible residential small chair "planets pattern design"
232563 02/11/2005 87959 1 129 O Remove and prohibit combustible residential small chair
232565 02/11/2005 87964 1 131 O Remove and prohibit two combustible residential small chairs
232559 02/11/2005 87950 1 131 O Provide certification that brown area rug meets flame spread requirement or remove area rug
232567 02/11/2005 87968 1 201 O Remove mirror or provide mirror made of tempered glass, safety glass, or stainless steel
232560 02/11/2005 87952 1 203 O Provide certification that carpet meets flame spread requirement or remove carpet
232566 02/11/2005 87966 1 203 O Remove and prohibit combustible beanbag chairs
232545 02/11/2005 87921 1 203 O Prohibit use of surge protector to power microwave and refrigerator, plug appliances directly into wall outlet
232576 02/11/2005 87986 1 206 O Post sign indicating evacuation routes
232551 02/11/2005 87933 1 210 O Eliminate extension cord for computer equipment and replace with a surge protector
232546 02/11/2005 87923 1 214 O Prohibit use of extension cord to power surge protector, plug surge protector directly into wall outlet
232547 02/11/2005 87925 1 214A O Prohibit use of surge protector to power microwave and coffee maker, plug appliances directly into wall outlet
232548 02/11/2005 87927 1 221A O Prohibit use of surge protector to power microwave and refrigerator, plug appliances directly into wall outlet
232549 02/11/2005 87929 1 223 O Prohibit plugging one surge protector into another under computer station cart adjacent to closet, plug surge protector directly into wall outlet
232550 02/11/2005 87931 1 223 O Prohibit plugging one surge protector into another under scanner adjacent to corridor door, plug surge protector directly into wall outlet
232555 02/11/2005 87942 1 223 O Remove and prohibit paper covering corridor door
232572 02/11/2005 87978 1 226 O Remove and prohibit use of toaster oven
232542 02/11/2005 87915 1 226 O Remove and prohibit paper covering windows
232573 02/11/2005 87980 2 190 O Remove and prohibit use of tape to prevent door from latching
232569 02/11/2005 87972 1 0000 F Repair magnetic release hold open device on fire door adjacent to 1-106C to work properly
191118 02/11/2005 25183 2 190 F Relocate heat detector to under-side of roof deck
232553 02/11/2005 87937 1 107 OS Relocate display cabinet blocking access to fire alarm pull station and view of fire alarm horn/strobe
232574 02/11/2005 87982 1 185 OS Prohibit recharging batteries for floor cleaning machine in room
232584 02/11/2005 88006 1 193 OS Remove storage from mechanical room
232554 02/11/2005 87940 1 223 OS Remove desk light which was clipped to fire extinguisher
232585 02/11/2005 88008 1 292 OS Remove storage from mechanical room
232583 02/11/2005 88004 1 294 OS Remove storage from electrical room
232556 02/11/2005 87944 2 103 OS Prohibit storage of gas powered pressure cleaner
191097 02/11/2005 25164 1 0000 CS Provide fire extinguisher in the corridor adjacent to 1-101Q
232552 02/11/2005 87935 00 0000 FS Provide certification that fire alarm system has been tested and is fully operational - Inspection report was not available at the fire alarm panel
191105 06/30/2004 25180 1 198A F Relocate heat detector to underside of roof structure
191107 06/30/2004 25181 1 198B F Relocate heat detector to under-side of roof deck
191109 06/30/2004 25182 1 198C F Relocate heat detector to under-side of roof deck
191112 06/30/2004 25207 1 224 MS Replace 3 lb. fire extinguisher with a minimum 2A capacity adjacent to cooking range
191101 06/30/2004 25169 1 121 CS Provide fire extinguisher adjacent to kiln room
191113 06/30/2004 25177 1 230 CS Replace existing fire extinguisher with minimum 2A extinguisher
191098 06/30/2004 32249 1 101 FS Install smoke detector @ fire alarm panel