LIMESTONE CREEK ELEMENTARY
 
LIMESTONE CREEK ELEMENTARY
6701 CHURCH ST.
JUPITER, 33458
FISH Drill Down
 Campus Info.
 Buildings:9 Rooms:341
 Portables:7
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
323531 03/12/2018 276370 00 0000 M Turn barbs down on all fencing. (East and north property lines adjacent to retention ponds)
416633 03/12/2018 478924 2 001 M Determine cause of water damaged ceiling tiles in corridor adjacent to 2-102 and replace tiles
416620 03/12/2018 478898 2 002 M Repair water leak above ceiling and repair large hole in ceiling in corridor adjacent to 2-113 (water is dripping in plastic garbage can)
416632 03/12/2018 478922 2 104 M Determine cause of water damaged ceiling tiles next to sink and adjacent to projector screen and replace tiles
416630 03/12/2018 478918 2 105 M Repair exterior exit door to close properly
416631 03/12/2018 478920 2 106 M Repair exterior exit door to close properly
416629 03/12/2018 478916 2 107B M Repair ventilation fan in bathroom
416624 03/12/2018 478906 2 109 M Determine cause of water damaged ceiling tiles and replace tiles
416626 03/12/2018 478910 2 109 M Replace missing ceiling tiles at exterior exit door
416625 03/12/2018 478908 2 109B M Determine cause of water damaged ceiling tiles in bathroom and replace tiles
416628 03/12/2018 478914 2 110 M Determine cause of water damaged ceiling tiles and replace tiles
416623 03/12/2018 478904 2 111B M Determine cause of water damaged ceiling tiles and replace tiles
416627 03/12/2018 478912 2 112B M Determine cause of water damaged ceiling tiles and replace tiles
416619 03/12/2018 478896 2 119B M Secure loose metal corner strip on wall in bathroom
416616 03/12/2018 478890 2 127B M Repair ventilation fan in bathroom
416618 03/12/2018 478894 2 128 M Repair exterior exit door to close and latch properly
391477 03/12/2018 424595 2 180 M Repair exhaust fan in custodial room
416622 03/12/2018 478902 2 192 M Provide cover on exposed electrical junction box in electric room (cover is marked sound panel)
416600 03/12/2018 478856 3 001 M Replace missing vinyl base in corridor adjacent to 3-180
416598 03/12/2018 478852 3 110 M Determine cause of water damaged ceiling tiles next to sink and replace tiles
416595 03/12/2018 478846 3 118 M Replace missing ceiling tiles
416606 03/12/2018 478868 3 193 M Re-attach motor-pulley guard on motor in ductwork for AHU3-2
416635 03/12/2018 478928 4 106 M Determine cause of water damaged ceiling tiles and replace tiles
416644 03/12/2018 478946 5 103G M Determine cause of water damaged ceiling tiles and replace tiles
416645 03/12/2018 478948 5 103H M Determine cause of water damaged ceiling tiles and replace tiles
416646 03/12/2018 478950 5 103L M Replace missing escutcheon on fire sprinkler head
416637 03/12/2018 478932 5 105 M Repair entrance door adjacent to 5-105E at northwest corner of cafeteria to close properly
416640 03/12/2018 478938 5 105 M Determine cause of water damaged ceiling tiles in cafeteria adjacent to east exit doors and replace tiles
416641 03/12/2018 478940 5 107B M Secure hanging exhaust fan grill to ceiling in men's restroom
416642 03/12/2018 478942 5 108 M Determine cause of water damaged ceiling tiles in staff dining room next to exterior exit door and replace tiles
416643 03/12/2018 478944 5 108 M Repair damaged corner of wall in teacher dining room next to door into cafeteria
416636 03/12/2018 478930 5 113 M Determine cause of water damaged ceiling tiles and replace tiles
416614 03/12/2018 478885 7 0000 M Trim tree branches overgrowing roof of old wooden P.E. Pavilion
416609 03/12/2018 478874 P 9204 M Repair emergency lighting at rear door
416607 03/12/2018 478870 P 9347 M Determine cause of water damaged ceiling tiles and replace tiles
416608 03/12/2018 478872 P 9347 M Repair rear door to close properly
416610 03/12/2018 478877 P 9728 M Repair emergency lighting at both front and rear doors
416611 03/12/2018 478879 P 9728 M Repair or replace rear door with hole rusted through it
416612 03/12/2018 478881 P 9729 M Repair emergency lighting at both front and rear doors
416617 03/12/2018 478892 2 127 O Remove and prohibit flammable fabric curtains on cabinets
416615 03/12/2018 478888 2 130 O Remove and prohibit flammable fabric curtains
416601 03/12/2018 478858 3 0000 O Prohibit parking personal vehicles on grass areas around Building 3 (all personal vehicles should be parked on hard surface parking areas provided at front of school)
416597 03/12/2018 478850 3 108 O Remove paper covering emergency evacuation map at entrance door
416603 03/12/2018 478862 3 114 O Prohibit plugging surge protector into extension cord located under computer table
416599 03/12/2018 478854 3 115 O Keep area within 18 inches of fire sprinkler head clear and unobstructed
416621 03/12/2018 478900 2 192 MS Provide current inspection tag for fire extinguisher
416604 03/12/2018 478864 3 292 MS Repair top latching hardware on stationary door of mechanical room (latch is not secured to door)
416634 03/12/2018 478926 4 001 MS Recharge fire extinguisher located on wall adjacent to exit door into corridor 4-002
416638 03/12/2018 478934 5 105A MS Provide current inspection tag for fire extinguisher located on stage
416639 03/12/2018 478936 5 193 MS Provide current inspection tag for fire extinguisher
416613 03/12/2018 478883 7 0000 MS Provide current inspection tag for fire extinguisher located on post in wooden P.E. Pavilion
416594 03/12/2018 478844 1 191 OS Remove storage from electrical room
416593 03/12/2018 478842 1 192 OS Remove storage from telecom room (room is filled with empty cardboard boxes)
416602 03/12/2018 478860 3 001 OS Prohibit paper covering fire extinguisher in corridor across from 3-117 to provide clear access to fire extinguisher
416605 03/12/2018 478866 3 009 OS Prohibit use of floor wedge to hold open fire door at top landing of stairs
416596 03/12/2018 478848 3 104 OS Prohibit storage of flammable spray paint
261552 03/12/2018 143830 1 0000 N/A No violations observed
261553 03/12/2018 143831 2 0000 N/A No violations observed
261554 03/12/2018 143832 3 0000 N/A No violations observed
261555 03/12/2018 143833 4 0000 N/A No violations observed
261556 03/12/2018 143834 5 0000 N/A No violations observed
266081 03/12/2018 152009 6 0000 N/A No violations observed
266079 03/12/2018 152004 7 0000 N/A No violations observed
261567 03/12/2018 143845 P 9201 N/A No violations observed
416591 03/12/2018 478836 P 9201 N/A Portable has no access because mold remediation is in progress. Interior is sealed off. Unknown how much longer unit will be closed.
416592 03/12/2018 478839 P 9202 N/A Portable has no access because mold remediation is in progress. Interior is sealed off. Unknown how much longer unit will be closed.
266092 03/12/2018 152031 P 9202 N/A No violations observed
266097 03/12/2018 152040 P 9203 N/A No violations observed
261573 03/12/2018 143851 P 9204 N/A No violations observed
261563 03/12/2018 143841 P 9347 N/A No violations observed
261559 03/12/2018 143837 P 9728 N/A No violations observed
261560 03/12/2018 143838 P 9729 N/A No violations observed
370092 12/07/2017 378395 2 119B M Repair ventilation fan in bathroom
266080 12/07/2017 152007 8 0000 N/A No violations observed
402938 04/10/2017 449363 1 104 M Properly chain cylinder to wall
402869 04/10/2017 449213 1 127 M Provide cover on exposed electrical junction box at missing clock
402870 04/10/2017 449215 1 130 M Adjust corridor door to latch properly
402856 04/10/2017 449186 2 102 M Determine cause of water damaged ceiling tiles and replace tiles
402857 04/10/2017 449188 2 105 M Adjust exterior door to latch properly
402854 04/10/2017 449182 2 106 M Provide cover on exposed electrical junction box adjacent to teachers desk
402858 04/10/2017 449190 2 107 M Repair exterior door to close properly, too fast
402853 04/10/2017 449180 2 109 M Determine cause of water damaged ceiling tiles and replace tiles, replace missing tiles
402859 04/10/2017 449192 2 111 M Determine cause of water damaged ceiling tiles and replace tiles
402860 04/10/2017 449194 2 111 M Repair exterior door to open and close properly
402861 04/10/2017 449196 2 113 M Repair exterior door to close properly
402850 04/10/2017 449172 2 116 M Secure loose bracket for fire extinguisher
402851 04/10/2017 449174 2 116 M Adjust exterior door to latch properly
402863 04/10/2017 449201 2 121 M Repair exterior door to close properly
402864 04/10/2017 449203 2 122 M Determine cause of water damaged ceiling tiles and replace tiles
402867 04/10/2017 449209 2 123 M Repair bent weather strip at bottom of exterior door
402865 04/10/2017 449205 2 126 M Repair damaged wall adjacent to exterior door
402866 04/10/2017 449207 2 128 M Repair exterior door to close and latch properly
402872 04/10/2017 449219 2 132 M Determine cause of water damaged ceiling tiles and replace tiles
402852 04/10/2017 449176 2 181 M Repair hole in wall
402934 04/10/2017 449355 3 002 M Determine cause of water damaged ceiling tiles adjacent to 3-171 and replace tiles
402933 04/10/2017 449353 3 125 M Determine cause of water damaged ceiling tiles and replace tiles
402936 04/10/2017 449359 3 204 M Repair door to close properly, too fast
402937 04/10/2017 449361 3 208 M Determine cause of water damaged ceiling tiles and replace tiles
402939 04/10/2017 449365 3 210 M Determine cause of water damaged ceiling tiles and replace tiles
402925 04/10/2017 449334 4 109 M Adjust exterior door to close and latch properly
402924 04/10/2017 449332 4 110 M Adjust exterior door to open and close properly
402878 04/10/2017 449231 4 180 M Determine cause of water damaged ceiling tiles and replace tiles
402929 04/10/2017 449345 4 194 M Repair broken emergency lighting
402930 04/10/2017 449347 4 194 M Secure cover and replace missing latch for electrical panel 277
402931 04/10/2017 449349 4 194 M Repair door to close properly
402876 04/10/2017 449227 5 101A M Replace missing ceiling tiles
402882 04/10/2017 449239 5 103 M Adjust west exterior door to latch properly
402877 04/10/2017 449229 5 103P M Secure loose data outlet junction box to wall
402881 04/10/2017 449237 5 104 M Adjust corridor door to latch properly
391497 04/10/2017 424638 5 105 M Provide tempered or safety glazing in display cabinet
402875 04/10/2017 449225 5 105A M Replace missing escutcheon on fire sprinkler head
402873 04/10/2017 449221 5 108 M Determine cause of water damaged ceiling tiles and replace tiles
402942 04/10/2017 449371 P 9201 M Repair emergency lighting at both doors
402943 04/10/2017 449373 P 9201 M Determine cause of water damaged ceiling tiles and replace tiles, replace missing tiles
402941 04/10/2017 449369 P 9202 M Repair emergency lighting at rear door
402944 04/10/2017 449375 P 9203 M Adjust rear door to close properly
402945 04/10/2017 449377 P 9203 M Repair emergency lighting at rear door
402946 04/10/2017 449379 P 9203 M Mount fire extinguisher at maximum five feet above floor
402940 04/10/2017 449367 P 9204 M Adjust rear door to close and latch properly
402948 04/10/2017 449383 P 9728 M Repair light in exit sign at entrance door
402949 04/10/2017 449385 p 9728 M Adjust rear door to close and latch properly
402947 04/10/2017 449381 P 9729 M Adjust rear door to close properly
402868 04/10/2017 449211 1 127B O Prohibit plugging surge protector into surge protector
402871 04/10/2017 449217 1 130 O Prohibit plugging surge protector into white multi outlet extension cord, prohibit multi outlet extension cord, plug surge protector directly into permanent electrical outlet
402855 04/10/2017 449184 2 106 O Prohibit plugging surge protector into surge protector
402923 04/10/2017 449330 4 111 O Prohibit white 13A extension cord or replace with minimum 15A single outlet extension cord
402862 04/10/2017 449199 2 0000 MS Adjust smoke doors adjacent to 2-113 to latch properly
402879 04/10/2017 449233 4 191 MS Replace missing fire extinguisher
402927 04/10/2017 449341 4 193 MS Provide current inspection tag for fire extinguisher
402928 04/10/2017 449343 4 194 MS Provide current inspection tag for fire extinguisher
402932 04/10/2017 449351 4 195 MS Provide current inspection tag for fire extinguisher
402926 04/10/2017 449336 5 109 MS Provide current inspection tag for fire extinguisher
402880 04/10/2017 449235 5 194 MS Provide current inspection tag for fire extinguisher
402935 04/10/2017 449357 3 104 OS Maintain clear aisle to exit
402874 04/10/2017 449223 5 105A OS Prohibit storage on stage ramp to maintain clear aisle to exit
391460 12/14/2016 424561 P 9347 M Replace missing lens on light fixture in bathroom
391458 12/13/2016 424557 3 180 M Provide current inspection log for hot water heater - signs of rust is visible. Repair or replace if needed
323533 04/19/2016 276375 00 0000 M Repair damaged chain link fencing at property line east of Bldg. 5
391476 04/19/2016 424593 2 107 M Determine cause of water damaged ceiling tiles and replace tiles
391475 04/19/2016 424591 2 109 M Determine cause of water damaged ceiling tiles and replace tiles
391482 04/19/2016 424605 2 110 M Provide cover on exposed electrical junction box where clock was
391481 04/19/2016 424603 2 114 M Adjust water flow for drinking spout
391468 04/19/2016 424577 2 129 M Secure loose lens on light fixture adjacent to ceiling projector
391453 04/19/2016 424547 3 104 M Secure loose faucet to sink
391459 04/19/2016 424559 3 127 M Determine cause of water damaged ceiling tiles and replace tiles in exterior storage room
391486 04/19/2016 424614 4 110 M Adjust exterior door to latch properly
391490 04/19/2016 424623 4 180 M Replace missing ceiling tiles
391485 04/19/2016 424612 5 107 M Provide current inspection tag for kitchen hood fire suppression system and make any necessary repairs if indicated on report. The kitchen hood suppression system was not tagged
391483 04/19/2016 424607 5 107E M Provide protective cage around fire sprinkler head in freezer (X2)
391484 04/19/2016 424609 5 107F M Provide protective cage around fire sprinkler head in refrigerator (X2)
391462 04/19/2016 424565 P 9202 M Secure loose ceiling tile grid in center of portable unit
391461 04/19/2016 424563 P 9204 M Adjust front door to latch properly
391463 04/19/2016 424567 00 9599 O Remove pile of rotted wood and damaged Rubbermaid storage unit adjacent to shed at north end of play field to keep site free of hazardous debris
391479 04/19/2016 424599 2 102 O Secure electrical cord cover strip to flooring adjacent to teacher desk to eliminate slip hazard
391472 04/19/2016 424585 2 111 O Remove all storage from stove burners to eliminate fire hazard
391474 04/19/2016 424589 2 111 O Remove and prohibit paper on window blinds
391473 04/19/2016 424587 2 113 O Remove and prohibit paper on window blinds
391471 04/19/2016 424583 2 121 O Remove all storage from stove burners to eliminate fire hazard
391470 04/19/2016 424581 2 126 O Remove and prohibit excessive flammable red vinyl sheathing on table
391469 04/19/2016 424579 2 127 O Secure electrical cord cover strip to flooring adjacent to teacher desk to eliminate slip hazard
391467 04/19/2016 424575 2 130 O Prohibit plugging surge protector into surge protector under computer stations. Plug each surge protector directly into a permanent electrical outlet
391466 04/19/2016 424573 2 132 O Prohibit plugging surge protector into surge protector under computer stations. Plug each surge protector directly into a permanent electrical outlet
391457 04/19/2016 424555 3 111 O Replace burned out light bulbs in light fixture in handicapped bathroom or have maintenance repair light fixture
391452 04/19/2016 424545 3 214 O Remove and prohibit paper on window blinds
391451 04/19/2016 424543 3 216 O Remove and prohibit paper on window blinds
391487 04/19/2016 424616 4 109 O Eliminate white extension cord with multiple outlet end for tape player adjacent to teacher desk or replace with a surge protector
391489 04/19/2016 424620 4 111 O Eliminate white extension cord with multiple outlet end adjacent to computer stations or replace with a surge protector
391491 04/19/2016 424625 5 101 O Eliminate white extension cord with multiple outlet end for fan in corner or replace with a surge protector
391498 04/19/2016 424640 5 101 O Remove and prohibit hanging excessive decorations and netting from frame structure below ceiling. Also remove all storage above frame structure
391493 04/19/2016 424630 5 107 O Prohibit running electrical cords across floor in serving area. Contact School Food Services for a permanent solution
391494 04/19/2016 424632 5 105A MS Adjust curtain in back of stage to move freely in front of exit door to music room. Curtain is currently attached to a fixed loop on ceiling track
391480 04/19/2016 424601 2 0000 OS Remove all student work on floor from corridor between classrooms 2-104 and 2-106 to maintain safe egress
391478 04/19/2016 424597 2 192 OS Remove ladders and light bulb boxes from electrical room
391454 04/19/2016 424549 3 206 OS Relocate paper recycling cardboard box adjacent to corridor door to maintain clear path to exit
391455 04/19/2016 424551 3 206A OS Remove easel and floor fan from bathroom vestibule to maintain 3 ft clear path to to both bathrooms
391456 04/19/2016 424553 3 208 OS Rearrange furniture to maintain 3 ft clear path to corridor door
391488 04/19/2016 424618 4 0000 OS Remove table for corridor adjacent to 4-111 to maintain safe egress
391495 04/19/2016 424634 5 0000 OS Prohibit parking a car at bottom of sidewalk adjacent to aftercare office. Car blocks safe egress from sidewalk outside music room exterior door
391496 04/19/2016 424636 5 0000 OS Remove display cabinet from exit corridor between art classroom and media center to maintain safe egress from Bldg. Also glass in display cabinet is not marked tempered or safety glass. Coordinate with M&PO to provide safety film or tempered glass in display cabinet before use
391492 04/19/2016 424627 5 0000 OS Remove storage from corridor adjacent to music room
391464 04/19/2016 424569 P 9728 OS Remove easel from bathroom to keep clear path to bathroom sink
391465 04/19/2016 424571 P 9729 OS Remove curtain rod on back door to maintain clear access to door. Curtain is covering door lever and door is not clearly visible. Also prohibit use of curtain. It does not have a tag that meets the flammability resistant requirement
370089 03/12/2015 378389 1 103 M Determine cause of water damaged ceiling tiles and replace tiles
370088 03/12/2015 378386 1 192 M Repair inoperable DX air conditioner in telecom room
370098 03/12/2015 378407 2 104 M Determine cause of water damaged ceiling tiles and replace tiles
370097 03/12/2015 378405 2 107 M Determine cause of water damaged ceiling tiles and replace tiles
355915 03/12/2015 347536 2 107A M Install light fixture inside storage room
370095 03/12/2015 378401 2 109B M Determine cause of water damaged ceiling tiles and replace tiles
370094 03/12/2015 378399 2 111B M Determine cause of water damaged ceiling tiles and replace tiles
370096 03/12/2015 378403 2 112 M Determine cause of water damaged ceiling tiles and replace tiles
370090 03/12/2015 378391 2 116 M Determine cause of water damaged ceiling tiles and replace tiles
370091 03/12/2015 378393 2 124 M Determine cause of water damaged ceiling tiles and replace tiles
370093 03/12/2015 378397 2 131 M Secure hanging heat detector
370106 03/12/2015 378423 3 111 M Secure loose toilet seat
370099 03/12/2015 378409 4 002 M Determine cause of water damaged ceiling tiles and replace tiles
370113 03/12/2015 378437 5 102 M Determine cause of water damaged ceiling tiles and replace tiles
370109 03/12/2015 378430 5 104 M Repair double entrance doors to close properly
370112 03/12/2015 378435 5 105E M Secure hanging escutcheon on fire sprinkler head
370108 03/12/2015 378427 5 107 M Provide current inspection tag for kitchen hood fire suppression system (tag indicated last inspection was March, 2014)
370107 03/12/2015 378425 5 107G M Repair condensation line on air conditioner above door (water dripping onto floor and staff is using garbage can to collect the water)
370105 03/12/2015 378421 6 0000 M Secure loose drinking fountain to wall adjacent to bathroom door
370102 03/12/2015 378415 P 9203 M Repair loose vinyl base along wall at rear door
370103 03/12/2015 378417 P 9347 M Repair loose vinyl base along wall at bathroom door
370104 03/12/2015 378419 P 9347 M Repair emergency lighting at rear door
323516 03/12/2015 276340 P 9347 M Gutter downspout drops rain water between P-10 & P-11 and rain water goes under P-10. Redirect drainage away from unit
370101 03/12/2015 378413 P 9728 M Replace missing ceiling tiles adjacent to window
370100 03/12/2015 378411 P 9729 M Repair rear door to close properly
370111 03/12/2015 378433 5 105A MS Provide current inspection tag for fire extinguisher
355920 10/28/2014 347543 2 115 M Repair damaged ceiling above bathroom stalls in girls bathroom
355935 10/28/2014 347577 5 005 M Provide non-slip surface for ramps adjacent to 5-104 music room
348734 01/24/2014 331486 00 9599 M Provide hurricane anchorage for shed adjacent to north property line (north of P-14)
355917 01/24/2014 347540 2 114 M Determine cause of water damaged ceiling tiles and replace tiles
355911 01/24/2014 347525 2 122 M Determine cause of water damaged ceiling tiles in bathroom and replace tiles
355913 01/24/2014 347529 2 123 M Secure loose faucet to sink
355923 01/24/2014 347552 3 109 M Determine cause of water damaged ceiling tiles at windows and replace tiles
355921 01/24/2014 347548 3 180 M Close ceiling hatch
355922 01/24/2014 347550 3 180 M Provide current maintenance log for hot water heater (60 gallons or higher)
355924 01/24/2014 347554 3 211 M Determine cause of water damaged ceiling tiles and replace tiles
355929 01/24/2014 347563 4 112A M Secure loose grill in ceiling
355928 01/24/2014 347561 4 114 M Anchor loose toilet to floor inside boys bathroom
355926 01/24/2014 347558 4 180 M Connect dryer duct to back of clothes dryer
355925 01/24/2014 347556 4 194 M Repair emergency lighting in generator room
355933 01/24/2014 347571 5 102 M Determine cause of water damaged ceiling tiles and replace tiles
355934 01/24/2014 347573 5 103C M Replace missing escutcheon on fire sprinkler head
355938 01/24/2014 347584 5 105 M Determine cause of water damaged ceiling tiles and replace tiles
355936 01/24/2014 347580 5 105B M Determine cause of water damaged ceiling tiles and replace tiles
355939 01/24/2014 347587 5 108 M Determine cause of water damaged ceiling tiles and replace tiles
355932 01/24/2014 347569 5 190 M Provide cover on exposed electrical junction box on wall next to 5-190A
355940 01/24/2014 347589 P 9204 M Repair emergency lighting at front door
355937 01/24/2014 347582 5 105 O Remove string hanging from fire sprinkler head adjacent to stage ramp
355931 01/24/2014 347567 5 190 MS Provide current inspection tag for fire extinguisher
355930 01/24/2014 347565 5 190A MS Provide current inspection tag for fire extinguisher
355927 10/23/2013 347559 4 180 M Connect dryer duct to back of clothes dryer
323519 10/23/2013 276349 00 0000 C Provide fencing around fire main between Bldgs. 3 & 4
276219 04/04/2013 174180 00 0000 M Label fire department connections and the buildings which they serve
348741 04/04/2013 331500 00 9599 M Repair light in exit sign under covered walkway between Bldgs. 2 and 4
348462 04/04/2013 330904 1 104 M Secure disconnected end of chain for helium cylinder to wall
348710 04/04/2013 331435 2 104 M Adjust exterior door to latch properly
348651 04/04/2013 331306 2 105 M Adjust exterior door to latch properly
348648 04/04/2013 331300 2 111B M Determine cause of water damaged ceiling tiles and replace tiles
348493 04/04/2013 330969 2 130 M Adjust exterior door to latch properly
348494 04/04/2013 330971 2 130B M Repair exhaust fan in bathroom
330036 04/04/2013 291123 2 182 M Repair or replace noisy ventilation fan
348467 04/04/2013 330914 3 109 M Adjust water flow for drinking spout
348464 04/04/2013 330908 3 112 M Adjust water flow for drinking spout
348468 04/04/2013 330916 3 114 M Adjust water flow for drinking spout
348480 04/04/2013 330942 5 107E M Replace missing escutcheon on fire sprinkler head in freezer
348735 04/04/2013 331488 7 0000 M Provide insulated cover for GFCI electrical outlet adjacent to drinking fountain at pavilion
348731 04/04/2013 331480 P 9202 M Repair damaged flooring adjacent to mate line
348730 04/04/2013 331478 P 9204 M Repair emergency lighting above both doors
348728 04/04/2013 331473 P 9347 M Replace missing lens on bathroom light fixture
348653 04/04/2013 331310 2 102 O Eliminate and prohibit use of brown extension cord with multipe outlet end plugged into surge protector under teacher desk
348652 04/04/2013 331308 2 105 O Remove and prohibit hanging paper from ceiling
348654 04/04/2013 331312 2 106 O Prohibit plugging surge protector into extension cord and into another surge projector - plug each surge directly into wall outlet and eliminate use of extension cord
348655 04/04/2013 331314 2 106 O Provide cover strip for electrical cords acorss floor and secure cover strip to floor to eliminate tripping
348713 04/04/2013 331441 2 106 O Eliminate extension cord with multiple outlet end adjacent to computer stations or replace with a surge protector
348711 04/04/2013 331437 2 108 O Remove and prohibit flammable shower curtain covering window blinds
348712 04/04/2013 331439 2 108 O Remove and prohibit hanging decorations from ceiling
348650 04/04/2013 331304 2 109 O Prohibit plugging surge protector into extension cord with multiple outlet end adjacent to teacher desk - plug surge protector directly into wall outlet and eliminate use of extension cord
348649 04/04/2013 331302 2 111 O Remove and prohibit hanging paper from ceiling
348647 04/04/2013 331298 2 121 O Prohibit plugging surge protector into surge protector under computer stations - plug each surge protector directly into wall outlet
348489 04/04/2013 330960 2 122 O Remove and prohibit hanging decorations from ceiling
348646 04/04/2013 331295 2 123 O Eliminate white extension cord with multiple outlet end adjacent to writing board on south wall or replace with a surge protector
348490 04/04/2013 330962 2 124 O Remove and prohibit hanging decorations from ceiling
348495 04/04/2013 330973 2 124 O Remove and prohibit flammable vinyl table cloth covering tables
348645 04/04/2013 331293 2 131 O Replace burned out light bulbs in light fixtures at exterior storage room
348492 04/04/2013 330967 2 132 O Remove and prohibit posting paper on ceiling tiles
348476 04/04/2013 330933 3 114 O Provide electrical cord cover strip for cord running across floor adjacent to teacher desk and secure cover strip to flooring
348470 04/04/2013 330920 3 210 O Eliminate green extension cord with multiple outlet end to TV behind teacher desk or replace with a surge protector
348471 04/04/2013 330922 3 210 O Remove and prohibit paper covering window in corridor door (X2)
348474 04/04/2013 330929 4 102 O Prohibit plugging copier into extension cord and into a surge protector - plug copier directly into wall outlet or request an electrical outlet box to be installed adjacent to copier
348475 04/04/2013 330931 4 102 O Provide electrical cord cover strip for cords running across floor and secure cover strip to flooring
348477 04/04/2013 330935 4 180 O Remove all storage on exhaust duct behind dryer in custodial receiving
348486 04/04/2013 330954 5 101 O Remove and prohibit hanging decorations from ceiling
348483 04/04/2013 330948 5 104 O Remove and prohibit hanging decorations from ceiling
348484 04/04/2013 330950 5 104 O Prohibit plugging surge protector into surge protector adjacent to teacher desk - plug each surge protector directly into permanent electrical outlet
348485 04/04/2013 330952 5 104 O Provide cover strip for electrical cords across floor and secure cover strip to flooring to eliminate trip hazard
348488 04/04/2013 330958 5 105D O Eliminate 13A extension cord adjacent to both desks (X2)
348733 04/04/2013 331484 P 9201 O Prohibit plugging surge protector into surge protector adjacent to teacher desk - plug each surge directly into wall outlet
348732 04/04/2013 331482 P 9202 O Remove and prohibit paper covering window blinds
348729 04/04/2013 331475 P 9204 O Provide cover strip for electrical cords running across floor and secure cover strip to flooring to eliminate trip hazard
348739 04/04/2013 331496 P 9728 O Relocate storage blocking view of electrical panel
348736 04/04/2013 331490 P 9728 O Provide cover strip for electrical cords running across floor and secure cover strip to flooring to eliminate trip hazard
348737 04/04/2013 331492 P 9729 O Provide cover strip for electrical cords running across floor and secure cover strip to flooring to eliminate trip hazard
348740 04/04/2013 331498 P 9729 O Relocate green screen blocking view of electrical panel
348727 04/04/2013 331471 2 120 C Modify emergency lighting so that room may not be left in darkness if single bulb fails
348721 04/04/2013 331459 4 108 C Modify emergency lighting so that room may not be left in darkness if single bulb fails
348720 04/04/2013 331457 4 109 C Modify emergency lighting so that room may not be left in darkness if single bulb fails
348725 04/04/2013 331466 5 103 C Provide or verify that media center has emergency lights - no separate light switch for emergency lights was provided and light fixtures were not labeled
348723 04/04/2013 331462 5 103A C Provide emergency lighting in classroom
348726 04/04/2013 331469 5 103D C Modify emergency lighting so that room may not be left in darkness if single bulb fails
348715 04/04/2013 331445 3 193 MS Provide current quarterly inspection tag for fire sprinkler system
348716 04/04/2013 331447 3 292 MS Provide current quarterly inspection tag for fire sprinkler system
348482 04/04/2013 330946 5 104 MS Adjust corridor door to latch properly
348479 04/04/2013 330940 5 110A MS Adjust corridor door to latch properly
348463 04/04/2013 330906 1 190 OS Remove storage from mechanical room and relocate pressure cleaner to flammable storage room 4-195
348461 04/04/2013 330902 1 191 OS Remove storage from electrical room
348491 04/04/2013 330965 2 127 OS Remove and prohibit use of toaster oven in classroom
348472 04/04/2013 330925 3 004 OS Prohibit use of trash can as hold open device on fire doors at top of stairwell
348465 04/04/2013 330910 3 110A OS Remove storage unit from bathroom
348466 04/04/2013 330912 3 204A OS Remove file cabinet from bathroom
348469 04/04/2013 330918 3 206B OS Remove all storage from bathroom vestibule
348473 04/04/2013 330927 4 108 OS Relocate desk to maintain 3 ft clear path to back exit door
348481 04/04/2013 330944 5 0000 OS Remove tables from corridor adjacent to music room
348487 04/04/2013 330956 5 105D OS Rearrange storage to maintain 3 ft clear aisle to back exterior door
348738 04/04/2013 331494 P 9728 OS Remove storage bins from bathroom
348460 04/04/2013 330900 00 0000 FS Repair problems with fire alarm system - Troubles indicated on panel
330043 01/18/2013 291140 3 193 M Provide cover on exposed electrical junction box on wall behind air handler unit
330044 01/18/2013 291142 3 292 MS Provide current inspection tag for fire sprinkler system (current tag is marked quarterly on 6-1-11, and is not current)
330040 01/18/2013 291131 2 101 FS Secure hanging heat detector in closet
330039 03/29/2012 291129 2 109 M Return ceiling tiles back into metal ceiling grid
330038 03/29/2012 291126 2 129A M Replace loose ceiling tiles in storage closet
330045 03/29/2012 291145 4 194 M Repair emergency light in generator room
330046 03/29/2012 291149 5 107 M Replace missing escutcheon on fire sprinkler head in serving line
330042 03/29/2012 291133 P 9201 M Repair emergency lighting at rear door
330034 03/29/2012 291119 2 0000 MS Recharge fire extinguisher in corridor accross from 2-117
323452 12/09/2011 276192 2 0000 M Repair uneven concrete paving in play area between Bldg. 2 and 2-131
323448 12/09/2011 276183 2 114B M Repair exhaust fan in bathroom
323455 12/09/2011 276200 2 120B M Repair exhaust fan in bathroom
323535 05/02/2011 276379 00 0000 M Remove rebar in grassed area east of Media Center at east property line. Bent #5 bar about 4' out of ground
323542 05/02/2011 276396 1 104 M Chain gas cylinder to wall
323562 05/02/2011 276438 2 0000 M Emergency lights in classrooms can not be shut off with light switch. Lights are on when switch is up or down
323447 05/02/2011 276181 2 0000 M Repair outside drinking fountain adjacent to 2-131
323463 05/02/2011 276220 2 111 M Determine cause of water damaged ceiling tiles and replace tiles
323456 05/02/2011 276202 2 111B M Grout crack in bathroom floor
323437 05/02/2011 276158 2 111B M Expansion joint leaking through wall in bathroom. Go to exterior wall and seal expansion joint
323458 05/02/2011 276208 2 115 M Repair leaking flush valve on handicapped toilet
323459 05/02/2011 276210 2 118 M Anchor toilet #2 to floor
323453 05/02/2011 276194 2 119 M Determine cause of water damaged ceiling tiles and replace tiles
323454 05/02/2011 276197 2 119 M Replace damaged vinyl floor tile
323451 05/02/2011 276190 2 121B M Repair leaking flush valve on toilet
323460 05/02/2011 276212 2 132B M Repair exhaust fan in bathroom
323736 05/02/2011 276844 2 192 M Replace burnt out relays in gutter above panel HC labeled "Lighting Relays". Top row of relays #2, #3, and #5 from left to right are burnt out. Burnt out relays will not allow emergency lights to be turned off
323523 05/02/2011 276357 3 180 M Replace leaking union on water heater
323545 05/02/2011 276401 3 191 M Provide panel schedule for panel H1
323467 05/02/2011 276230 4 113 M Repair leaking flush valve on handicapped toilet
323561 05/02/2011 276436 4 180A M Repair or replace vacuum breaker under sink. Runs continually
323466 05/02/2011 276228 4 193 M Remove green wire wrapped around light fixture
323438 05/02/2011 276160 5 0000 M Remove pine needles from roof, blocking overflow scuppers
323444 05/02/2011 276175 5 0000 M Determine cause of water damaged ceiling tiles in corridor adjacent to 5-112 and replace tiles
323521 05/02/2011 276352 5 101 M Clean out sink traps
323461 05/02/2011 276214 5 102A M Repair exhaust fan in bathroom
323441 05/02/2011 276169 5 105 M Adjust 3 east doors to exterior to latch properly
323442 05/02/2011 276171 5 105 M Determine cause of water damaged ceiling tiles and replace tiles
323445 05/02/2011 276177 5 107 M Repair latch for panel KH, hard to operate.
323446 05/02/2011 276179 5 107 M Repair circuit for tripped breaker on panel KH
323439 05/02/2011 276164 5 190A M Remove old construction lighting from bar joists
323449 05/02/2011 276185 6 101A M Repair exhaust fan in bathroom
323450 05/02/2011 276187 6 101C M Repair exhaust fan in bathroom
323518 05/02/2011 276346 P 0000 M Provide lock on gate of fencing around transformer outside of 2-129
323538 05/02/2011 276385 P 9728 M Provide impervious wall finish for minimum six foot height in bathroom
294679 05/02/2011 213527 P 9728 M Fill and cover exposed foundation
323440 05/02/2011 276167 00 0 O No access was available to 4-106, 4-107 and 5-113. Please be prepared to access these rooms during the report review meeting.
323464 05/02/2011 276223 2 112 O Eliminate multiple outlet extension cord adjacent to teacher's station or replace with minimum 15A cord
323465 05/02/2011 276225 2 127 O Eliminate multiple outlet extension cord adjacent to dry marker board or replace with minimum 15A cord
323546 05/02/2011 276403 3 115 O Keep area within 18" of fire sprinkler heads clear
323526 05/02/2011 276361 P 9728 O Provide clear access to electrical panel
323527 05/02/2011 276365 P 9729 O Provide clear access to electrical panel
303374 05/02/2011 232294 00 0000 C Provide suitable area for storage and recharging of golf carts and batteries
323462 05/02/2011 276216 5 104 C Provide illuminated exit sign at corridor door or change max occupancy sign to 49 max
323547 05/02/2011 276405 3 008 MS Adjust fire doors in 2nd floor corridor at elevator vestibule to latch properly
323443 05/02/2011 276173 5 107 MS Provide current inspection for kitchen hood fire suppression system
302280 02/25/2011 229914 4 180 M Replace missing dryer vent hose
294655 02/25/2011 213476 P 9347 M Repair holes in floor at mate line
194784 02/25/2011 6753 00 9500 C Provide covered walkway to portables
302254 02/25/2011 229855 3 292 C Provide wrench and fire sprinkler heads for fire sprinkler spare heads box
302161 04/16/2010 229652 1 0000 M Provide signage for unumbered communications room adjacent to 1-002 corridor indicating room name and number at appropriate height with raised and Braille characters
302183 04/16/2010 229703 2 0000 M Repair drinking fountain in corridor adjacent to 2-180
302184 04/16/2010 229705 2 0000 M Adjust corridor doors adjacent to 2-180 to open and close properly
302185 04/16/2010 229708 2 102 M Adjust exterior door to close properly
302187 04/16/2010 229712 2 108 M Adjust exterior door to open and close properly
302189 04/16/2010 229716 2 112 M Replace missing ceiling tiles
302171 04/16/2010 229676 2 121 M Determine cause of water damaged ceiling tiles and replace tiles
302165 04/16/2010 229661 2 128 M Adjust door closer on exterior door to control speed of closing door
302167 04/16/2010 229666 2 129 M Secure loose ceiling tile
302193 04/16/2010 229724 2 192 M Repair light fixture, lights do not turn on
302202 04/16/2010 229742 3 190 M Repair door to close and latch properly
302233 04/16/2010 229810 3 215B M Replace missing escutcheon on fire sprinkler head
302286 04/16/2010 229926 4 108 M Repair hole in wall
302282 04/16/2010 229918 4 109 M Provide stencil or sticker with arrow indicating location of fire alarm pull station
302278 04/16/2010 229910 4 180 M Replace missing letter signs for rooms within 4-180. 4-180 B,C,D
302281 04/16/2010 229916 4 180 M Secure loose handle on emergency eye wash
302274 04/16/2010 229900 4 194 M Repair torn duct seal on generator
302275 04/16/2010 229902 4 194 M Provide cover on exposed electrical junction box adjacent to door
302295 04/16/2010 229944 5 103C M Replace missing ceiling tiles
302299 04/16/2010 229953 5 103G M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
302298 04/16/2010 229950 5 103J M Replace missing escutcheon on fire sprinkler head
294643 04/16/2010 213449 5 105A M Remove lock from exit door to 5-104
194809 04/16/2010 6795 5 107 M Provide current inspection tag for kitchen steamer
302289 04/16/2010 229932 5 113 M Determine cause of water damaged ceiling tiles and replace tiles
294651 04/16/2010 213472 P 0000 M Provide impervious wall finish for minimum six foot height for all bathrooms in concrete portables
302200 04/16/2010 229738 P 9203 M Repair rear door to open properly
302198 04/16/2010 229734 P 9204 M Adjust main entrance door to close and latch properly
302195 04/16/2010 229728 P 9728 M Repair main entrance door to close properly
302194 04/16/2010 229726 P 9729 M Secure loose fire extinguisher bracket
302177 04/16/2010 229689 2 103 O Prohibit multi outlet extension cord @ fish tank or replace with minimum 15A single outlet cord or surge protector
302179 04/16/2010 229693 2 103 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
302180 04/16/2010 229695 2 103 O Prohibit plugging surge protector into surge protector
302186 04/16/2010 229710 2 104 O Prohibit plugging surge protector into extension cord
302188 04/16/2010 229714 2 108 O Remove and prohibit combustible beanbag chairs
302176 04/16/2010 229686 2 109 O Prohibit plugging surge protector into surge protector then into extension cord
302173 04/16/2010 229680 2 111 O Remove and prohibit air freshener (peppermint spray)
302190 04/16/2010 229718 2 114 O Remove and prohibit excessive flammable wall coverings, limit coverage area to 20% of wall when room is not protected by fire sprinklers
302191 04/16/2010 229720 2 114 O Prohibit plugging surge protector into surge protector
302172 04/16/2010 229678 2 119 O Remove and prohibit air freshener
302170 04/16/2010 229674 2 121 O Prohibit plugging surge protector into surge protector @ computers
302169 04/16/2010 229672 2 123 O Prohibit plugging surge protector into extension cord @ computers
302160 04/16/2010 229650 2 124 O Prohibit plugging surge protector into surge protector
302162 04/16/2010 229655 2 126 O Prohibit plugging extension cord into surge protector adjacent to teacher's desk
302163 04/16/2010 229657 2 126 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
302168 04/16/2010 229668 2 127 O Prohibit plugging surge protector into surge protector @ computers
302164 04/16/2010 229659 2 128 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
302213 04/16/2010 229765 3 106 O Eliminate string line below 6'8
302204 04/16/2010 229746 3 107 O Remove and prohibit air freshener
302212 04/16/2010 229763 3 108A O Prohibit storage blocking fire alarm horn and strobe
302205 04/16/2010 229748 3 109 O Prohibit black multi outlet extension cords (x2) or replace with minimum 15A single outlet cords
302210 04/16/2010 229759 3 110 O Prohibit multi outlet electrical adaptor
302208 04/16/2010 229755 3 112 O Prohibit white 13A extension cord or replace with minimum 15A single outlet cord
302206 04/16/2010 229751 3 115 O Keep area within 18" of fire sprinkler head clear
302209 04/16/2010 229757 3 191 O Prohibit storage @ electrical panels to provide clear access to electrical panels
302255 04/16/2010 229857 3 203 O Remove and prohibit excessive flammable wall coverings, limit coverage area to 50% of wall space when room is protected by fire sprinklers
302214 04/16/2010 229767 3 204 O Remove and prohibit excessive flammable wall coverings, limit coverage area to 50% of wall space when room is protected by fire sprinklers
302216 04/16/2010 229772 3 206 O Remove and prohibit excessive flammable wall coverings, limit coverage area to 50% of wall space when room is protected by fire sprinklers
302229 04/16/2010 229799 3 214 O Remove and prohibit excessive flammable wall coverings, limit coverage area to 50% of wall space when room is protected by fire sprinklers
302243 04/16/2010 229829 3 215 O Remove and prohibit excessive flammable wall coverings, limit coverage area to 50% of wall space when room is protected by fire sprinklers
302236 04/16/2010 229813 3 217 O Remove and prohibit excessive flammable wall coverings, limit coverage to 50% of wall space when room protected by fire sprinklers
302232 04/16/2010 229808 3 218 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
302283 04/16/2010 229920 4 109 O Prohibit plugging surge protector into surge protector
302284 04/16/2010 229922 4 109 O Prohibit plugging microwave into multi outlet extension cord - plug directly into permanent electrical outlet. Prohibit multi outlet extension cord
302285 04/16/2010 229924 4 109 O Remove and prohibit air freshener
302296 04/16/2010 229946 5 103A O Post sign indicating primary and secondary evacuation routes
302294 04/16/2010 229942 5 104 O Prohibit white 13A extension cord @ computer or replace with minimum 15A single outlet cord or surge protector
302291 04/16/2010 229936 5 107 O Prohibit white 13A extension cord adjacent to reach in freezer
302292 04/16/2010 229938 5 107 O Prohibit plugging surge protector into extension cord
302288 04/16/2010 229930 5 113 O Prohibit orange multi outlet electrical adaptor
302196 04/16/2010 229730 P 9204 O Prohibit storage (magnets)on electrical panel to provide clear access to electrical panel
194783 04/16/2010 6743 00 0000 C Modify all emergency lighting so that no room may be left in darkness if single bulb fails
194787 04/16/2010 55714 00 9599 C Provide or designate and mark stabilized drive surface to allow fire department vehicle access to portable classrooms and the east and northeast sides of main buildings
275830 04/16/2010 173370 1 0000 C Provide illuminated exit sign at exterior doors at end of corridor outside 1-190
294396 04/16/2010 212941 4 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for unnumbered room adjacent to 4-112
276176 04/16/2010 174093 5 107 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for two locker rooms and laundry room (rooms still have old, Bldg. 4 signs)
276140 04/16/2010 174018 5 190A C Provide signage indicating room name and number at appropriate height with raised and Braille characters
302207 04/16/2010 229753 3 171 MS Remove storage (boxes) from elevator machine room
302300 04/16/2010 229955 5 101 MS Provide current inspection tag for fire extinguisher
302297 04/16/2010 229948 5 103H MS Provide current inspection tag for fire extinguisher
302181 04/16/2010 229697 2 101 OS Maintain clear aisle to corridor exit door
302182 04/16/2010 229701 2 101 OS Prohibit flammable plastic tablecloths
302178 04/16/2010 229691 2 103 OS Maintain clear aisle to exterior exit door
302175 04/16/2010 229684 2 109 OS Maintain clear aisle to exterior exit door
302174 04/16/2010 229682 2 111 OS Prohibit rope attached to ceiling grid, rope displaces ceiling tiles. Prohibit string line below 6'8"
302166 04/16/2010 229664 2 130 OS Maintain clear aisle to exit doors
302192 04/16/2010 229722 2 192 OS Remove storage from electrical room
302203 04/16/2010 229744 3 004 OS Remove and prohibit storage under stairs
302211 04/16/2010 229761 3 106 OS Maintain clear aisle to corridor exit door
302201 04/16/2010 229740 3 118 OS Prohibit storage of golf cart
302215 04/16/2010 229770 3 206 OS Maintain clear aisle to exit
302225 04/16/2010 229783 3 208 OS Prohibit flammable plastic tablecloth (on bulletin board)
302227 04/16/2010 229795 3 210 OS Maintain clear aisle to exit
302253 04/16/2010 229852 3 292 OS Prohibit hold open devices on fire door
302277 04/16/2010 229908 4 180 OS Prohibit charging batteries in room
302279 04/16/2010 229912 4 191 OS Remove storage from mechanical room
302290 04/16/2010 229934 5 107 OS Provide clear access to type "K" fire extinguisher adjacent to laundry room
302287 04/16/2010 229928 5 113 OS Provide clear access to fire extinguisher
302293 04/16/2010 229940 5 194 OS Provide clear access to fire extinguisher
302199 04/16/2010 229736 P 9201 OS Maintain clear aisle to exit doors
302197 04/16/2010 229732 P 9204 OS Maintain clear aisle to exit doors
302276 04/16/2010 229904 4 180C FS Provide heat detector in storage room
294403 10/21/2009 212957 3 291 M Investigate and eliminate cause of standing water on floor
294689 10/21/2009 213545 P 0000 M Provide chain and lock on gate of fenced electrical enclosure adjacent to P-12
294661 10/21/2009 213491 P 9728 M Determine cause of water damaged ceiling tiles and replace tiles
294401 10/21/2009 212952 2 0000 MS Adjust fire doors in corridor adjacent to 2-191 to latch properly
275935 10/21/2009 173583 3 008 MS Repair fire doors at elevator to latch - latches appear to be dogged down
294364 04/21/2009 212877 00 0000 M Replace cover for cleanout in grassed area NE of 2-132
294368 04/21/2009 212885 00 0000 M Fill holes in ground of play fields marked by cones. Holes caused by irrigation system leaks. Repair irrigation system
294375 04/21/2009 212899 2 0000 M Secure loose vinyl floor tile in corridor adjacent to 2-180
294384 04/21/2009 212916 2 107 M Secure loose laminate on cabinet adjacent to drinking fountain
295491 04/21/2009 215253 2 111B M Determine cause of water damaged ceiling tiles and replace tiles
294376 04/21/2009 212901 2 118 M Repair cracked corner in wall to NE
294380 04/21/2009 212908 2 120 M Replace missing vinyl floor tile adjacent to exit to exterior
294383 04/21/2009 212914 2 124B M Repair exhaust fan in bathroom
294382 04/21/2009 212912 2 131 M Replace missing light fixture
294377 04/21/2009 212903 2 134 M Repair door to open and close properly
294389 04/21/2009 212926 2 191 M Provide cover on exposed electrical gutter
294404 04/21/2009 212959 3 008 M Replace or remove broken plexiglass in fire extinguisher cabinet adjacent to 3-206
294398 04/21/2009 212946 3 009 M Replace missing escutcheon on fire sprinkler head at intermediate landing
294390 04/21/2009 212928 3 170 M Provide current inspection tag for elevator
294400 04/21/2009 212950 4 109B M Repair exhaust fan in bathroom
294553 04/21/2009 213267 5 005 M Secure loose handrail in corridor
294408 04/21/2009 212968 5 101 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
294365 04/21/2009 212879 5 103 M Repair light in exit sign at main entry
294554 04/21/2009 213269 5 103J M Replace missing ceiling tiles
294366 04/21/2009 212881 5 104 M Repair lights in 2 exit signs
294407 04/21/2009 212966 5 105 M Repair light in exit sign
294550 04/21/2009 213261 5 105A M Repair light in exit sign
294549 04/21/2009 213259 5 107 M Repair lights in 2 exit signs
276177 04/21/2009 174095 5 107E M Replace missing escutcheon on fire sprinkler head
294548 04/21/2009 213257 5 109 M Repair door to open and close properly
294409 04/21/2009 212971 5 111A M Replace missing escutcheon on fire sprinkler head
294695 04/21/2009 213567 6 0000 M Secure drinking fountain to wall
250575 04/21/2009 121162 7 0000 M Make repairs to wood pavilion behind portables per recommendation letter by Bill Brown dated 02-17-06.
294644 04/21/2009 213456 P 9201 M Repair holes in floor at mate line
294645 04/21/2009 213458 P 9202 M Repair holes in floor at mate line
294647 04/21/2009 213463 P 9202 M Secure loose base along wall
294648 04/21/2009 213467 P 9203 M Determine cause of water damaged ceiling tiles and replace tiles
294646 04/21/2009 213460 P 9203 M Repair holes in floor at mate line
294790 04/21/2009 213771 P 9203 M Repair emergency lighting
294791 04/21/2009 213773 P 9204 M Repair emergency lighting
294792 04/21/2009 213775 P 9292 M Repair emergency lighting
294659 04/21/2009 213489 P 9347 M Repair or extend rain gutter downspout to prevent drainage from undermining sidewalk and fill eroded area
294682 04/21/2009 213534 P 9728 M Repair damaged gutter downspout
294663 04/21/2009 213499 P 9728 M Secure sink to wall in bathroom
294665 04/21/2009 213502 P 9728 M Seal seam in bathroom flooring
294666 04/21/2009 213506 P 9729 M Seal seam in bathroom flooring
294668 04/21/2009 213508 P 9729 M Seal expansion joint on exterior wall
294362 04/21/2009 212871 1 104 O Prohibit plugging surge protector into surge protector
249913 04/21/2009 119765 2 102 O Eliminate extension cord running through ceiling adjacent to corridor door
294363 04/21/2009 212874 2 103 O Prohibit plugging surge protector into extension cord
294378 04/21/2009 212905 2 111 O Remove and prohibit storage on range top
294370 04/21/2009 212889 2 120 O Prohibit plugging surge protector into extension cord
294373 04/21/2009 212895 2 122 O Prohibit plugging extension cord into surge protector
294374 04/21/2009 212897 2 122 O Eliminate extension cord to small TV or replace with minimum 15A cord
294402 04/21/2009 212955 3 180 O Remove and prohibit storage on top of water heater
294397 04/21/2009 212944 3 215 O Eliminate multiple outlet extension cords
294393 04/21/2009 212935 4 110 O Prohibit plugging surge protector into surge protector
294394 04/21/2009 212937 4 111 O Prohibit plugging surge protector into surge protector
276144 04/21/2009 174026 4 180 O Prohibit plugging refrigerator into extension cord - plug directly into permanent electrical outlet
294674 04/21/2009 213520 P 9729 O Provide clear access to electrical panel
276171 04/21/2009 174083 5 105 C Provide sign indicating maximum occupancy adjacent to main entrance (Max. occupancy = 336)
294696 04/21/2009 213569 5 105A C Install maximum occupancy signage (Max. occupancy = 76)
294556 04/21/2009 213273 5 194 C Provide auto closer on door
294399 04/21/2009 212948 2 0000 MS Provide current inspection tag for fire extinguisher in corridor adjacent to 2-132
294372 04/21/2009 212893 2 121 MS Provide current inspection tag for type K fire extinguisher
294388 04/21/2009 212924 2 191 MS Remove storage from mechanical room
275912 04/21/2009 173537 3 003 MS Repair fire doors at elevator to latch - latches appear to be dogged down
294391 04/21/2009 212930 3 004 MS Adjust fire doors at top and bottom of stairs to latch properly
294385 04/21/2009 212918 3 118 MS Provide current inspection tag for fire extinguisher
294392 04/21/2009 212932 4 001 MS Provide current inspection tags for 3 fire extinguishers in corridor
294405 04/21/2009 212962 4 193 MS Provide current inspection tag for fire extinguisher
294406 04/21/2009 212964 4 194 MS Provide current inspection tag for fire extinguisher
294789 04/21/2009 213769 5 107 MS Provide current inspection tag for kitchen hood fire suppression system
294557 04/21/2009 213275 5 109 MS Provide current inspection tag for fire sprinkler system anf provide head wrench in spare fire sprinkler head box
294552 04/21/2009 213265 5 190A MS Provide current inspection tag for fire extinguisher
294369 04/21/2009 212887 2 109 OS Maintain clear aisle to rear exit
294371 04/21/2009 212891 2 121 OS Maintain clear aisle to rear exit
294386 04/21/2009 212920 2 123 OS Maintain clear aisle to rear exit
294387 04/21/2009 212922 2 124 OS Maintain clear aisle to rear exit
276192 04/21/2009 174125 4 193 OS Remove storage from electrical room
294555 04/21/2009 213271 5 113 OS Prohibit storage of gas powered equipment
231162 04/21/2009 85301 5 192 OS Remove storage from mechanical room
294671 04/21/2009 213513 P 9729 OS Prohibit running phone cord through ceiling grid
294684 04/21/2009 213540 P 9729 OS Remove and prohibit desk blocking clear access to exit
294367 04/21/2009 212883 1 101 FS Provide fire alarm log book at fire alarm panel
294381 04/21/2009 212910 2 113A FS Secure hanging heat detector
275909 12/23/2008 173531 3 004 M Replace missing escutcheon on fire sprinkler head at 1st floor landing
276151 12/23/2008 174041 3 118 M Replace missing escutcheon on fire sprinkler head
194812 12/23/2008 6796 5 107 M Verify activation of hood fire suppression system will initiate school fire alarm
276215 12/23/2008 174172 P 266 M Adjust steps to make risers equal
276196 12/23/2008 174133 P 4519 M Repair or replace deteriorated wood siding along ramp
266088 12/23/2008 152024 P 5023 M Repair damaged flooring at stair door
276218 12/23/2008 174178 P 694 M Repair ramp door to close and latch properly
194828 12/23/2008 55762 P 695 M Adjust landing at base of steps to make stair risers equal
275892 12/23/2008 173496 2 101 O Prohibit plugging extension cord into surge protector
275893 12/23/2008 173498 2 102 O Eliminate extension cord or replace with minimum 15A cord
275891 12/23/2008 173494 2 103 O Eliminate extension cord or replace with minimum 15A cord at projector
275895 12/23/2008 173502 2 104 O Eliminate extension cord or replace with minimum 15A cord
275887 12/23/2008 173486 2 105 O Eliminate extension cord or replace with minimum 15A cord
275885 12/23/2008 173482 2 107 O Eliminate extension cord or replace with minimum 15A cord
275886 12/23/2008 173484 2 107 O Prohibit plugging extension cord into surge protector
275898 12/23/2008 173508 2 108 O Eliminate extension cord or replace with minimum 15A cord at projector
275883 12/23/2008 173477 2 109 O Eliminate extension cords or replace with minimum 15A cords at projector and at TV
275901 12/23/2008 173514 2 110 O Eliminate extension cord or replace with minimum 15A cord at projector
275905 12/23/2008 173522 2 112 O Eliminate extension cord or replace with minimum 15A cord at projector
275835 12/23/2008 173380 2 116 O Remove and prohibit combustible beanbag chairs
275869 12/23/2008 173450 2 121 O Prohibit plugging microwave oven into extension cord - plug directly into permanent electrical outlet
275870 12/23/2008 173453 2 121 O Prohibit plugging extension cord into surge protector
275841 12/23/2008 173392 2 122 O Prohibit plugging surge protector into extension cord
275842 12/23/2008 173394 2 122 O Eliminate extension cord or replace with minimum 15A cord
275846 12/23/2008 173402 2 124 O Prohibit plugging surge protector into surge protector
275865 12/23/2008 173441 2 125 O Eliminate extension cord or replace with minimum 15A cord
275856 12/23/2008 173422 2 128 O Prohibit plugging surge protector into surge protector into extension cord - plug each directly to electrical outlet
275916 12/23/2008 173545 3 114 O Prohibit plugging surge protector into surge protector at teacher's desk
276174 12/23/2008 174089 5 107J O Eliminate extension cord or replace with minimum 15A cord
276656 12/23/2008 175136 2 0000 C Provide electrical outlets at ceilings of all classrooms to power projectors to eliminate improperly attaching extension cords to ceiling grid and using extension cords as permanent wiring
276143 12/23/2008 174024 4 180A C Provide signage indicating room name and number at appropriate height with raised and Braille characters
276213 12/23/2008 174168 P 0000 C Replace existing fencing around garden area between P-1 & P-2 with new, appropriate, safe and secure fencing or remove existing fencing
276195 12/23/2008 174131 P 4519 C Provide bottom rail on ramp landing guardrail at two inches above floor
276199 12/23/2008 174139 P 4519 C Provide bottom rail on stair landing guardrail at two inches above floor
276200 12/23/2008 174141 P 5023 C Provide bottom rail on stair landing guardrail at two inches above floor
276201 12/23/2008 174143 P 5023 C Provide bottom rail on ramp landing guardrail at two inches above floor
275834 12/23/2008 173378 3 193 MS Provide current inspection tag for fire sprinkler system
275854 12/23/2008 173418 2 128 OS Remove and prohibit use of toaster oven
275876 12/23/2008 173464 2 191 OS Remove storage from mechanical room
276153 12/23/2008 174046 3 118 OS Prohibit charging golf cart batteries in room
276148 12/23/2008 174035 4 180 OS Prohibit storage of flammable dust mop spray and gum remover
194802 12/23/2008 6736 4 180 OS Prohibit charging batteries in room
276166 12/23/2008 174073 5 005 OS Remove all storage from corridor outside 5-104
276169 12/23/2008 174079 5 105 OS Prohibit wedging open corridor doors
276173 12/23/2008 174087 5 107J OS Prohibit running extension cord through doorway
276141 12/23/2008 174020 5 190 OS Remove storage from mechanical room
266084 12/23/2008 152016 P 4452 N/A No violations observed
266085 12/23/2008 152018 P 458 N/A No violations observed
261562 12/23/2008 143840 P 4817 N/A No violations observed
249919 03/03/2008 119777 00 0000 M Remove dirt around fire department connection adjacent to P-12 to allow enough room for fire department to hook up hose lines, and turn connection to face gate inside fence enclosure
275829 03/03/2008 173368 1 0000 M Provide left arrow for illuminated exit sign between Bldgs. 1 & 2, which points towards doors at end of corridor of Bldg. 1
275832 03/03/2008 173374 1 190 M Repair door to open/close properly - door drags on sidewalk
275877 03/03/2008 173467 2 0000 M Provide cover on exposed electrical junction box in ceiling of corridor adjacent to fire doors outside 2-111
275890 03/03/2008 173492 2 103 M Repair exteior door to close and latch properly
275900 03/03/2008 173512 2 110 M Adjust exterior door to latch properly
275875 03/03/2008 173462 2 119B M Repair damage at corner of wall
275864 03/03/2008 173439 2 127 M Seal gap between electrical outlet cover plate and wall and secure loose cover plate
275863 03/03/2008 173437 2 127A M Replace missing ceiling tiles
266103 03/03/2008 152054 3 009 M Replace missing escutcheon on fire sprinkler head in stairway (above intermediate landing)
275920 03/03/2008 173553 3 108A M Anchor plastic shelving to wall or have shelving removed
275919 03/03/2008 173551 3 110A M Anchor plastic shelving to wall or have shelving removed
276152 03/03/2008 174043 3 118 M Determine cause of water damaged ceiling tiles and replace tiles
275914 03/03/2008 173541 3 180 M Secure loose cover plate at light switch
275913 03/03/2008 173539 3 193 M Repair door to close and latch properly
276187 03/03/2008 174115 4 101 M Repair hole in wall
276191 03/03/2008 174123 4 106 M Replace missing ceiling tiles
276183 03/03/2008 174107 4 111B M Determine cause of water damaged ceiling tiles and replace tiles
276146 03/03/2008 174031 4 180 M Remove center astragal from double doors which prevents right hand leaf from being opened from the inside
276142 03/03/2008 174022 4 180A M Remove hasp and padlock from door
276150 03/03/2008 174039 4 180D M Replace missing ceiling tiles
266072 03/03/2008 151990 4 191 M Provide cover on exposed electrical junction box
276193 03/03/2008 174127 4 194 M Provide certification that all student occupied spaces have emergency lights and all are operable
276194 03/03/2008 174129 4 195 M Change sign indicating room name from Electrical Room to Flammable Storage Room
276168 03/03/2008 174077 5 105B M Repair double doors at stage to close and latch properly
276175 03/03/2008 174091 5 106 M Replace missing ceiling tiles
276165 03/03/2008 174071 5 180 M Repair holes in ceiling
276154 03/03/2008 174049 6 101A M Secure hanging light lens
276206 03/03/2008 174154 P 0000 M Provide lock on gate for lift station enclosure outside P-3
276203 03/03/2008 174148 P 0000 M Provide padlock on gate for fence enclosure adjacent to P-13
276214 03/03/2008 174170 P 266 M Repair ramp door to close and latch properly - damaged strike plate and door cannot be secured
276197 03/03/2008 174135 P 4519 M Determine cause of water damaged ceiling tiles and replace tiles
276198 03/03/2008 174137 P 4519 M Repair hole in wall above sink
276204 03/03/2008 174150 P 458 M Repair exhaust fan in bathroom
276205 03/03/2008 174152 P 458 M Repair ramp door to close and latch properly
276202 03/03/2008 174146 P 9202 M Repair lock on front door to unlock with key
266089 03/03/2008 152026 P 9347 M Repair seam in vinyl flooring in bathroom
276207 03/03/2008 174156 P 9728 M Repair damaged downspout outside rear door
276208 03/03/2008 174158 P 9728 M Replace missing waterproof cover for electrical outlet on exterior wall outside rear door
276209 03/03/2008 174160 P 9728 M Rehang fire extinguisher bracket which has come off wall and hang extinguisher on bracket
276211 03/03/2008 174164 P 9729 M Secure hanging cover plate for junction box on wall in bathroom
276138 03/03/2008 174014 00 0000 O Prohibit parking on grass area at bus loop
275896 03/03/2008 173504 2 104 O Remove and prohibit combustible beanbag chairs
275884 03/03/2008 173480 2 107A O Remove and prohibit air freshener spray
275897 03/03/2008 173506 2 108 O Prohibit plugging surge protector into surge protector
275899 03/03/2008 173510 2 108 O Remove and prohibit air freshener
275881 03/03/2008 173475 2 111 O Prohibit plugging extension cord into surge protector
275904 03/03/2008 173520 2 112 O Remove and prohibit halogen lamps (x2)
275906 03/03/2008 173524 2 112 O Prohibit plugging surge protector into surge protector
275908 03/03/2008 173529 2 114 O Prohibit plugging surge protector into extension cord
275836 03/03/2008 173382 2 116 O Remove and prohibit Lysol spray
275837 03/03/2008 173384 2 117 O Remove and prohibit air freshener
275839 03/03/2008 173388 2 120 O Remove paper covering outside face of corridor door and prohibit paper covering window in door
275847 03/03/2008 173404 2 124 O Prohibit plugging extension cord into surge protector
275848 03/03/2008 173406 2 124 O Prohibit plugging refrigerator into extension cord - plug directly into permanent electrical outlet
275845 03/03/2008 173400 2 124 O Eliminate extension cord or replace with minimum 15A cord
275866 03/03/2008 173443 2 125 O Prohibit plugging extension cord into surge protector
275850 03/03/2008 173410 2 126 O Prohibit plugging microwave oven and refrigerator into surge protector - plug directly into permanent electrical outlet
275861 03/03/2008 173433 2 127 O Replace bulbs in emergency light fixture
275862 03/03/2008 173435 2 127 O Remove and prohibit combustible (residential) leather chair
275855 03/03/2008 173420 2 128 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
275852 03/03/2008 173414 2 128B O Remove and prohibit air freshener spray
275860 03/03/2008 173431 2 132 O Remove and prohibit combustible (residential) leather chair
275923 03/03/2008 173559 3 009 O Prohibit covering sign at 1st floor indicating stair name and number
275944 03/03/2008 173601 3 009 O Prohbiit covering sign indicating stair number at 2nd floor
275927 03/03/2008 173567 3 104 O Remove and prohibit flammable fabric covering windows
275910 03/03/2008 173533 3 105 O Remove and prohibit combustible beanbag chairs
275924 03/03/2008 173561 3 106 O Remove and prohibit combustible beanbag chairs
275941 03/03/2008 173597 3 204A O Remove and prohibit air freshener spray
275942 03/03/2008 173599 3 204A O Prohibit covering sign indicating room number
275934 03/03/2008 173580 3 205A O Remove and prohibit air freshener spray
275940 03/03/2008 173595 3 206 O Remove and prohibit combustible beanbag chairs
275939 03/03/2008 173591 3 208 O Remove and prohibit air freshener spray
275937 03/03/2008 173587 3 217 O Remove and prohibit air freshener
276190 03/03/2008 174121 4 101 O Remove and prohibit Lysol spray
276188 03/03/2008 174117 4 102 O Remove and prohibit multi-outlet electrical adaptor
276189 03/03/2008 174119 4 104A O Remove and prohibit air freshener spray and Lysol spray
276186 03/03/2008 174113 4 109 O Remove and prohibit Lysol spray
276185 03/03/2008 174111 4 110A O Remove and prohibit Lysol spray
276180 03/03/2008 174101 4 111E O Remove curtain covering window in door
276181 03/03/2008 174103 4 111W O Remove curtain covering window in door
276155 03/03/2008 174051 5 101 O Prohibit plugging surge protector into extension cord
276156 03/03/2008 174053 5 101 O Eliminate extension cord or replace with minimum 15A cord
276158 03/03/2008 174057 5 101 O Remove flammable paper lanterns
276159 03/03/2008 174059 5 101 O Remove and prohibit curtain covering windows and window in door
276162 03/03/2008 174065 5 103 O Remove and prohibit paper covering outside face of double doors and covering windows in double doors
276163 03/03/2008 174067 5 103 O Remove and prohibit flammable trees and poly/cotton 'snow' outside double doors
276160 03/03/2008 174061 5 103B O Prohibit plugging surge protector into surge protector
276161 03/03/2008 174063 5 103D O Remove and prohibit all flammable wall hangins in CCTV studio - bamboo curtain, cloth curtain, plastic shade and string curtain
276178 03/03/2008 174097 5 113 O No access was available to this room. Please be prepared to access this room during the report review meeting.
276216 03/03/2008 174174 P 695 O Remove and prohibit air freshener in bathroom
276212 03/03/2008 174166 P 9729 O Prohibit plugging microwave oven and refrigerator into extension cord - plug directly into permanent electrical outlet
275947 03/03/2008 173609 3 113 C Install GFCI outlets at two single outlets next to sinks
275833 03/03/2008 173376 2 181 MS Provide current inspection tag for fire extinguisher (dated 8/06)
276170 03/03/2008 174081 5 105 MS Repair doors at corridor adjacent to 5-107 to latch automatically or provide sign on fixed leaf of double doors that door is to remain closed and latched at all times except when moving equipment
276139 03/03/2008 174016 5 190A MS Provide current inspection tag for fire extinguisher
275831 03/03/2008 173372 1 190 OS Remove storage from mechanical room
275894 03/03/2008 173500 2 102 OS Relocate computer table blocking clear path to corridor door
275888 03/03/2008 173488 2 103 OS Relocate desk blocking clear path to corridor door
275879 03/03/2008 173469 2 111 OS Remove and prohibit storage on stove
275880 03/03/2008 173472 2 111 OS Remove storage blocking clear access to fire extinguisher next to stove
275902 03/03/2008 173516 2 112 OS Relocate desk blocking clear path to corridor door
275903 03/03/2008 173518 2 112 OS Arrange desks to provide minimum 3' wide clear path to exterior door
275907 03/03/2008 173526 2 114 OS Provide and maintain minimum 3' wide clear path to exterior door
275872 03/03/2008 173457 2 119 OS Remove and prohibit storage on stove
275874 03/03/2008 173459 2 119 OS Relocate art easel blocking clear path to exterior door
275840 03/03/2008 173390 2 120 OS Relocate storage and chairs blocking clear path to exterior door
275867 03/03/2008 173445 2 121 OS Remove and prohibit storage on stove
275871 03/03/2008 173455 2 121 OS Remove and prohibit candles
275843 03/03/2008 173396 2 124 OS Relocate desk blocking clear path to corridor door
275844 03/03/2008 173398 2 124 OS Relocate storage and tables blocking clear path to exterior door
275851 03/03/2008 173412 2 126 OS Relocate bookcase blocking clear path to exterior door
275849 03/03/2008 173408 2 126 OS Remove bookcase from corridor between 2-126 & 2-128
275853 03/03/2008 173416 2 128A OS Prohibit storage of flammable Dust Off spray
275859 03/03/2008 173429 2 132 OS Relocate desk blocking clear path to exterior door
275838 03/03/2008 173386 2 192 OS Remove storage from electrical room
275928 03/03/2008 173569 3 004 OS Prohibit wedging open doors at top of stairs at 2nd floor landing
275938 03/03/2008 173589 3 005 OS Prohibit wedging open fire doors at top of stairs at 2nd floor landing
275946 03/03/2008 173604 3 006 OS Remove decorations covering fire extinguisher cabinet adjacent to 3-202
275936 03/03/2008 173585 3 007 OS Remove chairs from corridor outside 3-212
275925 03/03/2008 173563 3 106 OS Relocate garbage can blocking clear path to corridor door
275926 03/03/2008 173565 3 106 OS Remove chair from corridor outside classroom door
275911 03/03/2008 173535 3 107 OS Relocate bookcase blocking clear path to corridor door
275921 03/03/2008 173555 3 108 OS Remove chairs from corridor outside classroom door
275922 03/03/2008 173557 3 108 OS Relocate chair blocking clear path to corridor door
275915 03/03/2008 173543 3 116 OS Prohibit wedging open corridor door
275917 03/03/2008 173547 3 191 OS Remove storage from electrical room
275918 03/03/2008 173549 3 191 OS Prohibit charging batteries in electrical room
275929 03/03/2008 173572 3 202 OS Prohibit wedging open corridor door
275930 03/03/2008 173574 3 203 OS Remove chair from corridor outside classroom door
275932 03/03/2008 173576 3 205 OS Remove chair from corridor outside classroom door
276184 03/03/2008 174109 4 110 OS Remove and prohibit use of toaster
276179 03/03/2008 174099 4 111E OS Relocate bookcase blocking clear path to exterior door
276182 03/03/2008 174105 4 111W OS Relocate table blocking clear access to exterior door
276172 03/03/2008 174085 4 112 OS Remove chair from corridor outside classroom door
276147 03/03/2008 174033 4 180 OS Prohibit storage of flammable charcoal lighter fluid
276149 03/03/2008 174037 4 180D OS Prohibit storage of flammable WD40
266073 03/03/2008 151992 4 191 OS Remove storage from mechanical room
276167 03/03/2008 174075 5 005 OS Remove damaged table outside doors at end of corridor
276157 03/03/2008 174055 5 101 OS Prohibit running extension cord through cabinet door opening
276164 03/03/2008 174069 5 103 OS Remove chairs blocking clear path to double exit doors leading to corridor
276217 03/03/2008 174176 P 694 OS Remove storage at ramp door
276210 03/03/2008 174162 P 9729 OS Prohibit running electrical cords under rug - provide appropriate rubber cover strip over cords
266108 11/08/2007 152066 3 004 OS Prohibit charging batteries in stairway landing
266106 11/08/2007 152060 3 005 OS Remove and prohibit storage under stairway
261568 11/08/2007 143846 P 266 N/A No violations observed
261565 11/08/2007 143843 P 4519 N/A No violations observed
261566 11/08/2007 143844 P 5023 N/A No violations observed
261572 11/08/2007 143850 P 694 N/A No violations observed
261574 11/08/2007 143852 P 695 N/A No violations observed
249938 09/20/2007 119817 P 4817 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements (per Pat Joyce)
194825 09/20/2007 6776 P 5023 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements (per Pat Joyce)
266109 04/12/2007 152069 3 004 M Replace missing escutcheon on fire sprinkler head in lower landing
266067 04/12/2007 151980 4 108 M Replace missing ceiling tiles
266066 04/12/2007 151977 4 109 M Adjust exterior exit door to latch properly
266064 04/12/2007 151971 4 109A M Determine cause of water damaged ceiling tiles and replace tiles
266069 04/12/2007 151983 4 111B M Provide signage indicating room name and number at appropriate height with raised and Braille characters on bathroom
266077 04/12/2007 152001 5 005 M Secure loose handrail on ramp behind stage
266082 04/12/2007 152012 P 266 M Replace missing sign indicating portable FISH #
266087 04/12/2007 152022 P 4519 M Repair stair door to close properly
266101 04/12/2007 152046 P 4817 M Re-attach guardrails at stair landing (guardrail is currently lying on the ground beside stair)
266086 04/12/2007 152020 P 694 M Repair door to close properly
266094 04/12/2007 152034 P 9201 M Replace missing emergency lighting at rear door
266091 04/12/2007 152028 P 9204 M Repair rear door to close properly
266083 04/12/2007 152014 P 9728 M Repair rear door to close properly
249915 04/12/2007 119769 2 110 O Eliminate extension cord powering overhead projector or have maintenance install permanent wiring for projector
249896 04/12/2007 119727 2 122 O Eliminate extension cord powering overhead projector or have maintenance install permanent wiring for projector
249900 04/12/2007 119735 2 124 O Eliminate extension cord powering overhead projector or have maintenance install permanent wiring for projector
194789 04/12/2007 20645 1 199 C Provide illuminated exit sign at courtyard side of corridor on the east side of the building to be visible from within courtyard
194790 04/12/2007 20646 1 199 C Provide illuminated exit sign at courtyard side of corridor on the west side of the building to be visible from within courtyard
194811 04/12/2007 55754 5 107 MS Verify that electricity to appliances shuts off upon activation of hood suppression system
249907 04/12/2007 119752 2 191 OS Remove storage from mechanical room
249893 04/12/2007 119721 2 192 OS Remove storage from electrical room
266110 04/12/2007 152072 3 004 OS Remove and prohibit storage under stairs
266107 04/12/2007 152063 3 180 OS Prohibit storage of flammable materials (Krylon spray paint)
266071 04/12/2007 151986 4 111 OS Remove and prohibit use of toaster oven
194782 12/21/2006 6777 00 0000 M Provide verification that all student occupied spaces have emergency lights and all are operable
249931 12/21/2006 119803 4 404 M Provide signage indicating room name and number at appropriate height with raised and Braille characters
231159 12/21/2006 85295 4 413 M Repair auto closer on freezer door
194813 12/21/2006 6710 4 417 M Relocate pull station for hood suppression system to be near exit door
194818 12/21/2006 55761 4 423 M Provide dated flame resistance label on stage curtain
249945 12/21/2006 119833 P 694 M Adjust steps to make risers equal
230853 12/21/2006 84638 2 209 O Remove and prohibit combustible (residential) recliner chair
249897 12/21/2006 119729 2 226 O Eliminate multiple outlet adaptor plugged into outlet on west wall
249899 12/21/2006 119733 2 226 O Eliminate surge protector powering microwave oven
249901 12/21/2006 119738 2 228 O Prohibit plugging appliances into surge protector
249917 12/21/2006 119773 3 317 O Eliminate extension cord powering refrigerator
249925 12/21/2006 119790 4 401 O Eliminate extension cord powering lamp and T.V.
249930 12/21/2006 119801 4 424 O Eliminate extension cord or replace with minimum 15A cord @ computers
249943 12/21/2006 119828 P 695 O Provide clear access to electrical panel
249939 12/21/2006 119819 P 9729 O Provide clear access to electrical panel
249928 12/21/2006 119796 4 437 C Provide signage indicating room name and number at appropriate height with raised and Braille characters (room has sign on door saying P.T.O.)
249908 12/21/2006 119754 2 239 MS Adjust smoke stor doors in corridor adjacent to 2-213 to latch properly
249912 12/21/2006 119763 2 200 OS Prohibit storage of flammable chewing gum remover
249911 12/21/2006 119761 2 201 OS Prohibit electrical cord from running under rug
230848 12/21/2006 84628 2 204 OS Prohibit electrical cord from running under rug
249910 12/21/2006 119759 2 209 OS Prohibit storage on stove top
230859 12/21/2006 84650 2 223 OS Remove flammable materials stored on stove top
249902 12/21/2006 119740 2 235 OS Prohibit storage of flammable graffitti remover, store flammable materials inside a flammable storage cabinet
249923 12/21/2006 119786 4 409 OS Remove storage from mechanical room
249933 12/21/2006 119807 4 421 OS Remove hold open devices (floor wedges) from fire doors at corridor 4-450
231160 12/21/2006 85297 4 454 OS Remove storage from corridor
249950 12/21/2006 119843 P 9347 OS Maintain clear aisle to rear exit door
249940 12/21/2006 119821 P 9728 OS Maintain clear aisle to rear exit door
249889 04/25/2006 119713 00 0000 M Replace missing ceiling tiles in rooms throughout all buildings
231256 04/25/2006 85496 00 9599 M Repair broken sidewalk at southwest corner of portable P-1
249891 04/25/2006 119717 1 0000 M Replace missing cover on knox box and supply keys to allow fire department access
249914 04/25/2006 119767 2 208 M Eliminate plug-in deodorizor plugged into outlet adjacent to closet
194791 04/25/2006 6780 2 209B M Repair roof leaks
194792 04/25/2006 6781 2 209C M Repair roof leaks
249922 04/25/2006 119784 3 303C M Repair ventilation fan in bathroom
249920 04/25/2006 119779 3 308 M Repair door on boys bathroom to close properly
231243 04/25/2006 85471 P 266 M Adjust stair landing to be level with interior floor
249947 04/25/2006 119837 P 4519 M Repair emergency lighting
249942 04/25/2006 119826 P 458 M Provide cover on exposed junction box on exterior by ramp
249949 04/25/2006 119841 P 5023 M Repair ramp and stair doors to close properly
249944 04/25/2006 119830 P 695 M Repair emergency lighting
249953 04/25/2006 119849 P 9201 M Repair emergency lighting
249937 04/25/2006 119815 P 9203 M Adjust front door to latch properly
249941 04/25/2006 119823 P 9728 M Adjust front door to latch properly
230860 04/25/2006 84652 00 0000 O Highlight specific evacuation routes on evacuation maps throughout campus
249906 04/25/2006 119750 2 221 O Eliminate multiple outlet adaptor plugged into outlet @ computer station
249895 04/25/2006 119725 2 222 O Eliminate room deodorizor
194795 04/25/2006 55748 2 228 O Remove and prohibit combustible (residential) rocking chair, or provide certification that it has been treated to be flame retardant
249903 04/25/2006 119742 2 233 O Eliminate multiple outlet adaptor on wall @ computer
231130 04/25/2006 85239 3 303 O Eliminate surge protector powering microwave oven and small appliances
231149 04/25/2006 85275 3 323 O Eliminate multiple extension cords
249927 04/25/2006 119794 4 437 O No access was available to this room. Please be prepared to access this room during the report review meeting.
249951 04/25/2006 119845 P 9204 O Remove paper covering electrical panel
194819 04/25/2006 6749 4 423 C Provide illuminated exit sign above door into 4-425
249909 04/25/2006 119756 2 211 MS Provide current inspection tag for type-K fire extinguisher
249892 04/25/2006 119719 2 220 MS Provide current inspection tag for fire extinguisher
249904 04/25/2006 119744 2 225 MS Provide current inspection tag for type-K fire extinguisher
249905 04/25/2006 119747 2 236 MS Adjust smoke stop doors on corridor adjacent to 2-223 to latch properly
249924 04/25/2006 119788 4 409A MS Provide current inspection tag for fire extinguisher
249932 04/25/2006 119805 4 417 MS Provide current inspection tag for kitchen hood fire suppression system
249929 04/25/2006 119799 4 429 MS Provide current inspection tag for fire extinguisher
249926 04/25/2006 119792 4 449 MS Provide current inspection tag for fire extinguisher in corridor adjacent to 4-448
249916 04/25/2006 119771 2 212 OS Eliminate toaster oven in classroom
249894 04/25/2006 119723 2 222 OS Maintain clear aisle to exterior exit door
249898 04/25/2006 119731 2 226 OS Maintain clear aisle to exterior exit door
249921 04/25/2006 119781 3 306 OS Maintain clear aisle to exterior exit door
249918 04/25/2006 119775 3 317 OS Prohibit storage of gas powered tiller and leaf blower
249935 04/25/2006 119811 P 9203 OS Provide clear access to fire extinguisher
249936 04/25/2006 119813 P 9203 OS Maintain clear aisle to rear exit door
249890 04/25/2006 119715 1 101 FS Provide certification that fire alarm system has been tested and is fully operational
194820 02/28/2006 6758 P 266 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
194830 02/28/2006 6774 P 4452 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
194824 02/28/2006 6775 P 4519 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
194829 02/28/2006 6771 P 458 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
194826 02/28/2006 6761 P 694 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
194827 02/28/2006 6767 P 695 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
194786 02/17/2006 6744 00 9599 C Provide engineer's drawings or certification indicating wood pavilion behind portables was designed and constructed to support required loads
231150 02/06/2006 85277 3 317 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
231157 02/06/2006 85291 4 408 M Replace plastic dryer vent with metal vent pipe
194807 02/06/2006 6792 4 408 M Repair rusted door frame
194808 02/06/2006 6793 4 409 M Insulate chilled water lines
231161 02/06/2006 85299 4 428 M Adjust exterior on corridor door to latch properly
231239 02/06/2006 85459 P 266 M Repair ramp door to close properly
230852 02/06/2006 84636 2 209 O Eliminate extension cords by computer and TV cart
230857 02/06/2006 84646 2 217 O Eliminate extension cord powering lamp
231148 02/06/2006 85273 3 323A O Provide clear access to electrical panel
194800 02/06/2006 55732 3 306 C Provide additional electrical outlets to prevent the need for multiple extension cords for electrical and electronic equipment
194805 02/06/2006 55733 3 324 C Provide additional electrical outlets to prevent the need for multiple extension cords for electrical and electronic equipment
231158 02/06/2006 85293 4 412 C Replace missing emergency release hardware in freezer
249934 02/06/2006 119809 4 421 C Provide magnetic release hold open devices for fire doors in cafeteria @ entrance from 4-450
231133 02/06/2006 85244 3 304A MS Provide heat detector in storage room
230863 02/06/2006 84658 2 225 OS Prohibit storage of flammable spray paint
231151 02/06/2006 85279 3 311 OS Remove storage from mechanical room
231153 02/06/2006 85283 3 317 OS Prohibit storage of flammable spray paint
231132 02/06/2006 85243 3 304 FS Provide heat detector in storage room
194785 02/01/2005 55764 00 9599 M Repair broken sidewalk adjacent to portable labeled C-1 which was broken during portable moves.
230842 02/01/2005 84616 1 107 M Chain helium cylinder to wall
230843 02/01/2005 84618 1 112 M Determine cause of water damaged ceiling tiles and replace tiles
230844 02/01/2005 84620 1 123 M Re-attach exhaust fan in women's bathroom
230849 02/01/2005 84630 2 208 M Repair exterior door to latch properly
230856 02/01/2005 84644 2 211 M Adjust exterior door to latch properly
230858 02/01/2005 84648 2 221 M Adjust exterior door to latch properly
230866 02/01/2005 84667 2 231C M Determine cause of water damaged ceiling tiles and replace tiles
230868 02/01/2005 84671 2 234C M Determine cause of water damaged ceiling tiles and replace tiles
231145 02/01/2005 85256 3 304A M Adjust exterior door next to 3-304C to latch properly
231154 02/01/2005 85285 3 317 M Mount fire extinguisher at maximum five feet above floor at east door
231155 02/01/2005 85287 3 317 M Determine cause of water damaged ceiling tiles and replace tiles by east door
194814 02/01/2005 6716 4 417 M Replace broken latch on electrical panel "K"
194815 02/01/2005 55724 4 419 M Replace missing fire door to dishwashing room to protect fire envelope for kitchen.
194822 02/01/2005 6800 P 266 M Adjust steps to make risers equal
231242 02/01/2005 85469 P 266 M Repair or replace damaged exterior wood trim on both doors
231246 02/01/2005 85477 P 4452 M Repair emergency lighting
231250 02/01/2005 85483 P 4519 M Repair emergency lighting
194823 02/01/2005 6811 P 4519 M Replace missing tie down straps
231252 02/01/2005 85489 P 5023 M Repair stair door to close properly
231244 02/01/2005 85473 P 695 M Repair emergency lighting
231245 02/01/2005 85475 P 695 M Secure exhaust fan to ceiling in bathroom
231268 02/01/2005 85521 P 9202 M Replace damaged floor tiles at the center of portable
231164 02/01/2005 85305 P 9203 M Replace damaged floor tile in the center of portable
231165 02/01/2005 85307 P 9204 M Mount fire extinguisher at maximum five feet above floor
230846 02/01/2005 84625 2 201 O Remove and prohibit paper covering window in door
230847 02/01/2005 84626 2 204 O Remove and prohibit paper covering window in door
230850 02/01/2005 84632 2 208 O Remove and prohibit combustible (residential) floor cushions
230862 02/01/2005 84656 2 225 O Eliminate extension cord or replace with minimum 15A cord
194796 02/01/2005 55737 2 229 O Eliminate multiple extension cords
194797 02/01/2005 55743 2 231B O Eliminate ungrounded extension cords (x2)
230867 02/01/2005 84669 2 234 O Remove and prohibit paper covering window in door
231129 02/01/2005 85237 3 303 O Remove and prohibit combustible leather chair
231131 02/01/2005 85241 3 303 O Remove and prohibit paper covering window in door
231146 02/01/2005 85270 3 306 O Eliminate extension cord or replace with minimum 15A cord
194799 02/01/2005 55738 3 306 O Eliminate multiple extension cords
194804 02/01/2005 55731 3 324 O Prohibit use of 6-way electrical outlet extension adjacent to teacher's desk
231156 02/01/2005 85289 4 406 O Provide clear access to electrical panel
231163 02/01/2005 85303 4 439 O Eliminate extension cord or replace with minimum 15A cord
231248 02/01/2005 85479 P 4452 O Eliminate extension cord or replace with minimum 15A cord
194832 02/01/2005 55734 P 4452 O Provide clear access to electrical panel
231229 02/01/2005 85442 P 9202 O Remove and prohibit paper covering window in door
194793 02/01/2005 6745 2 219A C Provide partitions between urinals
230865 02/01/2005 84665 2 230C C Re-attach exhaust fan to ceiling in bathroom
194801 02/01/2005 6746 3 308 C Provide partitions between urinals
194803 02/01/2005 6701 3 324 C Provide sign indicating maximum occupancy adjacent to main entrance for when partition wall between 3-321 and 3-324 in folded open
194817 02/01/2005 55726 4 421 F Provide magnetic release hold open device for fire doors @ corridor to eliminate school's need to prop door open
194798 02/01/2005 55725 2 239 MS Adjust fire door to latch properly (adjacent to 2-213)
194810 02/01/2005 55758 4 417 MS Provide current inspection for fire suppression system
230845 02/01/2005 84622 2 200 OS Prohibit storage of flammable gum remover
230851 02/01/2005 84634 2 207 OS Maintain clear aisle to exterior door
230854 02/01/2005 84640 2 209 OS Maintain clear aisle to exterior door next to computer
230855 02/01/2005 84642 2 209 OS Remove flammable storage on stove top
230861 02/01/2005 84654 2 225 OS Remove storage of flamable materials from stove top
230869 02/01/2005 84673 2 235 OS Prohibit storage of flammable graffiti remover
231126 02/01/2005 85226 3 301 OS Maintain clear aisle to exterior door
194816 02/01/2005 55751 4 421 OS Prohibit hold open devices on corridor doors
194821 02/01/2005 55728 P 266 OS Relocate stored furniture blocking clear access to exit door
194831 02/01/2005 55729 P 4452 OS Relocate teacher's desk to provide clear path to door
231254 02/01/2005 85491 P 5023 OS Maintain clear aisle to rear exit
194788 02/01/2005 55744 1 101 FS Install smoke detector @ fire alarm panel
194794 02/01/2005 55753 2 226B FS Secure loose and hanging heat detector
194806 02/01/2005 6709 4 406A FS Provide heat detector in bathroom used for storage