CROSSROADS ACADEMY
 
CROSSROADS ACADEMY
S.W. E AVE
BELLE GLADE, 33430
FISH Drill Down
 Campus Info.
 Buildings:0 Rooms:0
 Portables:40
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
419151 04/10/2018 484302 00 9599 M Remove steel rebar protruding from landscape area north of custodial receiving 1-139 to eliminate hazardous condition
419152 04/10/2018 484304 00 9599 M Repair leaning STOP signs and handicapped signs through out parking lot
419136 04/10/2018 484272 2 103A M Repair light fixture in bathroom to work properly
419095 04/10/2018 484182 P 2500 M Repair problems with fire alarm system - Troubles indicated on panel
419096 04/10/2018 484184 P 2500 M Repair toilet to work properly - toilet does not flush
419146 04/10/2018 484292 P 520 M Repair emergency lighting
419139 04/10/2018 484278 P 6231 M Repair emergency lighting in boys bathroom
419140 04/10/2018 484280 P 6231 M Adjust boys bathroom door to latch properly
419141 04/10/2018 484282 P 6231 M Replace broken soap dispenser in boys bathroom
419112 04/10/2018 484217 P 6416 M Secure drinking spout to sink
419113 04/10/2018 484219 P 6417 M Secure loose exhaust fan grille to ceiling in bathroom
419114 04/10/2018 484221 P 6417 M Repair damaged laminate at cabinet above sink
419115 04/10/2018 484223 P 6418 M Secure faucet to sink
419116 04/10/2018 484225 P 6418 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to bathroom
419118 04/10/2018 484229 P 6420 M Repair emergency lighting above front door
419120 04/10/2018 484233 P 6421 M Secure drinking spout to sink
419121 04/10/2018 484235 P 6422 M Repair emergency lighting above front door
419123 04/10/2018 484239 P 6422 M Secure loose fascia board under sink
419097 04/10/2018 484186 P 7003 M Repair or replace rusted hot water heater in closet inside clinic boys bathroom
419098 04/10/2018 484188 P 7003 M Provide tempered glass, safety glass, or stainless steel for mirror in boys bathroom
419099 04/10/2018 484190 P 7003 M Provide tempered glass, safety glass, or stainless steel for mirror in girls bathroom
419100 04/10/2018 484192 P 7003 M Adjust door to girls bathroom to latch properly
419111 04/10/2018 484215 P 9185 M Adjust front door closer to control speed of closing door - door slams hard
419109 04/10/2018 484210 P 9205 M Adjust back door to latch properly
419110 04/10/2018 484213 P 9207 M Repair broken vinyl base along wall adjacent to back door
419107 04/10/2018 484206 P 9253 M Determine cause of water damaged ceiling tiles and replace tiles
419144 04/10/2018 484288 P 9256 M Repair emergency lighting above front door
419150 04/10/2018 484300 P 9257 M Remove vegetation grown from gutter outside back door
419142 04/10/2018 484284 P 9257 M Repair emergency lighting above front door
419143 04/10/2018 484286 P 9257 M Replace missing screws for light switch cover plate adjacent to front door
419148 04/10/2018 484296 P 9258 M Remove vegetation grown from gutter outside front door
419145 04/10/2018 484290 P 9258 M Secure loose lens on ceiling light fixture
419149 04/10/2018 484298 P 9261 M Remove vegetation grown from gutter outside front door
419108 04/10/2018 484208 P 9263 M Pad and mark corners of communications unit which are lower than 6 feet 8 inches
419103 04/10/2018 484198 P 9299 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to back window
419104 04/10/2018 484200 P 9300 M Patch hole in exterior wall finish adjacent to front door
419106 04/10/2018 484204 P 9300 M Pad and mark corners of communications unit which are lower than 6 feet 8 inches
419147 04/10/2018 484294 P 9417 M Adjust door closer to control speed of closing door - front door slams hard
419101 04/10/2018 484194 P 9528 M Repair toilet to work properly - water keep running inside toilet
419102 04/10/2018 484196 P 9529 M Determine cause of water damaged ceiling tiles and replace tiles
419133 04/10/2018 484265 P 9631 M Repair deteriorated wall finish adjacent to front door
419134 04/10/2018 484268 P 9635 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to back door
419135 04/10/2018 484270 P 9635 M Repair water damaged wall finish adjacent to back door
419117 04/10/2018 484227 P 6419 O Prohibit plugging surge protector into surge protector behind hutch - plug each surge protector directly into wall outlet
419122 04/10/2018 484237 P 6422 O Prohibit plugging surge protector into surge protector at teacher desk - plug each surge protector directly into wall outlet
419105 04/10/2018 484202 P 9300 O Prohibit plugging surge protector into surge protector under computer stations - plug each surge protector directly into wall outlet
419137 04/10/2018 484274 P 6231 MS Provide current inspection tag for fire extinguisher in girls bathroom or remove
419119 04/10/2018 484231 P 6421 OS Remove all storage from bathroom
302817 04/10/2018 231088 2 0000 N/A No violations observed
297483 04/10/2018 219513 P 2500 N/A No violations observed
257828 04/10/2018 136994 P 520 N/A No violations observed
297470 04/10/2018 219488 P 6416 N/A No violations observed
297486 04/10/2018 219519 P 6417 N/A No violations observed
297485 04/10/2018 219517 P 6418 N/A No violations observed
297466 04/10/2018 219480 P 6419 N/A No violations observed
297465 04/10/2018 219478 P 6420 N/A No violations observed
297464 04/10/2018 219476 P 6421 N/A No violations observed
297463 04/10/2018 219474 P 6422 N/A No violations observed
297484 04/10/2018 219515 P 7003 N/A No violations observed
297446 04/10/2018 219440 P 9185 N/A No violations observed
297438 04/10/2018 219421 P 9205 N/A No violations observed
297441 04/10/2018 219428 P 9207 N/A No violations observed
297478 04/10/2018 219503 P 9253 N/A No violations observed
297471 04/10/2018 219489 P 9256 N/A No violations observed
297472 04/10/2018 219492 P 9257 N/A No violations observed
297449 04/10/2018 219446 P 9258 N/A No violations observed
297434 04/10/2018 219413 P 9261 N/A No violations observed
297437 04/10/2018 219419 P 9263 N/A No violations observed
297452 04/10/2018 219452 P 9299 N/A No violations observed
297477 04/10/2018 219501 P 9300 N/A No violations observed
297480 04/10/2018 219507 P 9528 N/A No violations observed
298233 04/10/2018 221127 P 9529 N/A No violations observed
297475 04/10/2018 219497 P 9631 N/A No violations observed
297474 04/10/2018 219495 P 9635 N/A No violations observed
419138 01/12/2018 484276 P 6231 M Repair exhaust fan in all group and individual bathrooms (X4)
336107 01/12/2018 304259 7 0000 N/A No violations observed
257829 01/12/2018 136996 P 521 N/A No violations observed
297473 01/12/2018 219494 P 6231 N/A No violations observed
297447 01/12/2018 219442 P 9184 N/A No violations observed
297445 01/12/2018 219438 P 9186 N/A No violations observed
297459 01/12/2018 219466 P 9187 N/A No violations observed
297476 01/12/2018 219499 P 9188 N/A No violations observed
297439 01/12/2018 219423 P 9206 N/A No violations observed
297440 01/12/2018 219425 P 9208 N/A No violations observed
297450 01/12/2018 219448 P 9259 N/A No violations observed
297448 01/12/2018 219444 P 9260 N/A No violations observed
297453 01/12/2018 219454 P 9262 N/A No violations observed
321502 01/12/2018 271939 P 9416 N/A No violations observed
321501 01/12/2018 271937 P 9417 N/A No violations observed
297481 01/12/2018 219509 P 9527 N/A No violations observed
297479 01/12/2018 219505 P 9530 N/A No violations observed
403219 04/04/2017 449965 00 0000 M Remove vegetation growing from gutters throughout campus
403248 04/04/2017 450025 2 0000 M Place fill dirt around foundation of cafeteria building to prevent varmint intrusion
403246 04/04/2017 450021 2 102 M Repair east exit door to close properly
403247 04/04/2017 450023 2 102 M Repair emergency lighting in kitchen next to east exit door
403245 04/04/2017 450019 2 103 M Repair emergency lighting in kitchen office
403244 04/04/2017 450017 2 190 M Place ceiling tile back into metal ceiling grid
403214 04/04/2017 449954 P 2500 M Repair emergency lighting at west exit door
403237 04/04/2017 450003 P 6231 M Eliminate insect infestation on floor in girls restroom
403238 04/04/2017 450005 P 6231 M Replace missing grill on exhaust fan in women's staff restroom
403239 04/04/2017 450007 P 6231 M Repair emergency lighting in boy's restroom
403240 04/04/2017 450009 P 6231 M Repair flush valve on toilet (water does not shut off)
403241 04/04/2017 450011 P 6231 M Repair damage to wall above doorway at fire/strobe light in boys restroom
403242 04/04/2017 450013 P 6231 M Replace broken ceramic floor tiles at doorway and at plumbing chase door
403254 04/04/2017 450037 P 6416 M Repair emergency lighting at rear door
403253 04/04/2017 450035 P 6417 M Determine cause of water damaged ceiling tiles and replace tiles
403252 04/04/2017 450033 P 6418 M Repair emergency lighting at rear door
403250 04/04/2017 450029 P 6419 M Determine cause of water damaged ceiling tiles and replace tiles
403251 04/04/2017 450031 P 6419 M Adjust rear door to latch properly
403249 04/04/2017 450027 P 6420 M Determine cause of water damaged ceiling tiles (X3) and replace tiles
403216 04/04/2017 449958 P 7003 M Repair emergency lighting in clinic office
403217 04/04/2017 449960 P 7003 M Repair door on girls bathroom to close properly
403230 04/04/2017 449987 P 9185 M Repair emergency lighting at front door
403229 04/04/2017 449985 P 9188 M Repair emergency lighting at front door
403228 04/04/2017 449983 P 9208 M Repair emergency lighting at rear door
403255 04/04/2017 450041 P 9257 M Repair damaged downspout at front door
403231 04/04/2017 449989 P 9258 M Repair emergency lighting at front and rear door
403218 04/04/2017 449963 P 9262 M Repair emergency lighting at front door
403225 04/04/2017 449977 P 9263 M Repair emergency lighting at front door
403226 04/04/2017 449979 P 9263 M Repair damaged downspout at front door
403243 04/04/2017 450015 P 9299 M Determine cause of water damaged ceiling tiles above desk and replace tiles
403232 04/04/2017 449992 P 9416 M Repair emergency lighting at front door
403233 04/04/2017 449994 P 9417 M Repair damaged wall around rear door
403234 04/04/2017 449997 P 9417 M Repair hanging metal ceiling grid
403235 04/04/2017 449999 P 9417 M Replace missing floor tiles
403236 04/04/2017 450001 P 9527 M Repair damaged downspout at front door
403223 04/04/2017 449973 P 9527 M Provide non-slip impervious floor surface in bathroom (seam in flooring goes under toilet)
403224 04/04/2017 449975 P 9527 M Determine cause of water damaged ceiling tiles adjacent to A/C unit and replace tiles
403220 04/04/2017 449967 P 9529 M Place ceiling tiles back into metal ceiling grid
403221 04/04/2017 449969 P 9529 M Anchor toilet to floor
403222 04/04/2017 449971 P 9529 M Determine cause of water damaged ceiling tiles and replace tiles
403215 04/04/2017 449956 P 2500 OS Remove and prohibit use of space heater at Ms. Esparza's desk
403227 04/04/2017 449981 P 9205 OS Remove and prohibit use of candles
388101 04/08/2016 417340 P 2500 M Fire alarm inspection indicates see report to AHJ for list of deficiencies. Report to AHJ not included in report. Provide report to AHJ and repair items on report
388096 04/07/2016 417330 2 101 M Repair emergency lighting X 2
388097 04/07/2016 417332 2 103A M Anchor toilet to floor
388099 04/07/2016 417336 P 2500 M Caulk sink to wall
388100 04/07/2016 417338 P 2500 M Repair emergency lighting
388102 04/07/2016 417342 P 520 M Adjust front door to latch properly
388103 04/07/2016 417344 P 520 M Caulk sink to bathroom wall
388104 04/07/2016 417348 P 521 M Eliminate wasps nests at gable end of roof at A-C unit
388105 04/07/2016 417350 P 6231 M Replace missing placard that covers connections for time clock in plumbing chase
388106 04/07/2016 417352 P 6231 M Repair emergency lighting in girls restroom
388107 04/07/2016 417354 P 6231 M Repair exhaust fan in boys bathroom
388108 04/07/2016 417357 P 6231 M Wall in mens single bathroom has separated at corner. It appears that the 2 halves of the concreteable are coming apart. Check the gap between the halves in the plumbing chase room. Contact Patrick Joyce for repair procedure
388109 04/07/2016 417360 P 6231 M Repair exhaust fan in mens single bathroom
388110 04/07/2016 417362 P 6416 M Seal wall at bathroom sink to provide impervious wall finish
388112 04/07/2016 417367 P 6418 M Secure projection screen backer board to wall
388113 04/07/2016 417369 P 6419 M Secure projection screen backer board to wall
388115 04/07/2016 417375 P 6419 M Seal bathroom wall at sink to provide impervious wall finish
388114 04/07/2016 417371 P 6420 M Secure projection screen backer board to wall
388116 04/07/2016 417378 P 6421 M Seal wall at bathroom sink to provide impervious wall finish
388118 04/07/2016 417383 P 9206 M Repair emergency lighting at front door
388119 04/07/2016 417385 P 9208 M Repair emergency lighting at rear door
388120 04/07/2016 417387 P 9253 M Repair emergency lighting at rear door
388122 04/07/2016 417391 P 9261 M Repair emergency lighting X 2
388121 04/07/2016 417389 P 9416 M Seal open joint at mate line at rear exterior
388123 04/07/2016 417393 P 9417 M Seal open joints at mate line, front and rear exterior
388124 04/07/2016 417395 P 9527 M Repair emergency lighting at rear door
388128 04/07/2016 417401 P 9529 M Caulk bathroom sink to wall
388132 04/07/2016 417406 P 9631 M Replace missing grate for exhaust fan in bathroom
388133 04/07/2016 417414 P 9635 M Repair emergency lighting X 2
388117 04/07/2016 417381 2 102 O Provide clear access to electrical panel
388098 04/07/2016 417334 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus
388111 04/07/2016 417364 P 6418 MS Recharge fire extinguisher
388125 04/07/2016 417397 P 9528 OS Maintain 3 foot clear aisle to rear exit
373883 04/13/2015 386580 00 0000 M Repair damaged, uneven concrete walk at entrance gate
373863 04/13/2015 386536 00 8087 M Provide covers on exposed electrical junction boxes on columns of covered walk at 1-109, 1-104, 1-123, 1-132, 1-135
373871 04/13/2015 386555 00 9699 M Repair drinking fountain at basketball courts
373851 04/13/2015 386510 2 101 M Repair emergency lighting on west wall
373849 04/13/2015 386505 2 101A M Remove and prohibit storage of expired fire extinguisher
373853 04/13/2015 386516 2 102 M Provide current inspection tag for kitchen hood cleaning
373852 04/13/2015 386512 2 103 M Replace missing cover for data outlet box on wall adjacent to desk
373850 04/13/2015 386508 P 2500 M Repair emergency lighting adjacent to receptionist desk
373848 04/13/2015 386503 P 2500 M Make repairs as noted on fire alarm report
373854 04/13/2015 386518 P 521 M Repair east door to close and latch properly
373884 04/13/2015 386582 P 6231 M Repair emergency lighting in both single and group mens and womens bathrooms
373885 04/13/2015 386584 P 6231 M Repair damaged tile walls in mens group bathroom. Repair separated wall tiles in accessible stall and at door to plumbing chase
373886 04/13/2015 386587 P 6231 M Repair or replace rusty, damaged door frame at door to plumbing chase in mens bathroom
373872 04/13/2015 386557 P 7003 M Repair emergency lighting
373861 04/13/2015 386532 P 9185 M Repair south door to close and latch properly
373860 04/13/2015 386530 P 9186 M Adjust door closer on north door to control speed of closing door
373855 04/13/2015 386520 P 9187 M Repair emergency lighting
373856 04/13/2015 386522 P 9187 M Repair south door to close and latch properly
373859 04/13/2015 386528 P 9188 M Repair emergency lighting at south door
373858 04/13/2015 386526 P 9207 M Repair or remove alarm device on door
361580 04/13/2015 359868 P 9257 M Repair emergency lighting at south door, test button broken
373864 04/13/2015 386538 P 9258 M Repair emergency lighting at north door, test button broken
373865 04/13/2015 386540 P 9258 M Eliminate termites in bookshelves
373867 04/13/2015 386544 P 9258 M Replace missing emergency lighting at north door
373868 04/13/2015 386546 P 9258 M Repair north door to open properly
373862 04/13/2015 386534 P 9259 M Repair emergency lighting at north door, test button broken
373877 04/13/2015 386567 P 9261 M Adjust door closer on south door to control speed of closing door
373878 04/13/2015 386569 P 9261 M Pad and mark corners of data unit adjacent to entrance door, which are lower than 6 feet 8 inches
373875 04/13/2015 386563 P 9261 M Repair emergency lighting (x2)
373879 04/13/2015 386571 P 9299 M Secure loose bracket for gutter on south wall
373881 04/13/2015 386574 P 9300 M Pad and mark corners of data unit adjacent to entrance door, which are lower than 6 feet 8 inches
373882 04/13/2015 386578 P 9300 M Secure loose data outlet box on north wall
373866 04/13/2015 386542 P 9416 M Repair north door to close and latch properly
373869 04/13/2015 386548 P 9417 M Repair emergency lighting at north door
373870 04/13/2015 386551 P 9417 M Repair south door to close and latch properly
373876 04/13/2015 386565 P 9528 M Repair emergency lighting at south door
373874 04/13/2015 386561 P 9528 O Replace surge protector with damaged cord, at teachers desk
348685 04/13/2015 331379 00 0000 C Provide security night lighting
348658 04/13/2015 331322 P 521 C Provide exhaust fan in bathroom
373857 04/13/2015 386524 P 9635 C Provide impervious wall finish in bathroom
373873 04/13/2015 386559 P 9528 MS Replace missing fire extinguisher
361575 12/17/2014 359858 2 101 M Exterminate termites and repair damage at east windows and around AC unit
361572 12/17/2014 359851 2 102 M Verify that kitchen hood has supression nozzles and that they are operable and necessary. Nozzles are not visible yet system has a current inspection tag
361655 12/17/2014 360031 P 2500 M Replace missing pieces of skirt on portable
361653 12/17/2014 360025 P 7003 M Repair or replace deteriorated wood siding at north side. Replace missing pieces of skirt on south and west sides
336126 12/17/2014 304301 00 0000 C Modify or improve site drainage around all portable foundations
361587 12/17/2014 359885 P 2500 C Provide bottom rail on ramp landing guardrail at 2 inches above floor
257819 12/17/2014 136976 2 0000 N/A No violations observed
361607 04/09/2014 359929 00 0000 M Replace missing protective cover for electrical outlet adjacent to metal detector
361574 04/09/2014 359856 2 101 M Repair emergency lighting at east exterior door
361573 04/09/2014 359854 2 103 M Repair emergency lighting
361576 04/09/2014 359860 P 520 M Repair threshold at south door
361577 04/09/2014 359862 P 520 M Repair hole in wall at east door
361570 04/09/2014 359847 P 520 M Determine cause of water damaged ceiling tiles and replace tiles
361571 04/09/2014 359849 P 520 M Repair auto closer on north door
361578 04/09/2014 359864 P 521 M Repair auto closer on door
361579 04/09/2014 359866 P 521 M Repair west door to close and latch properly
361567 04/09/2014 359840 P 6231 M Repair emergency lighting
361568 04/09/2014 359843 P 6231 M Replace bulbs in light fixture in plumbing chase
361569 04/09/2014 359845 P 6231 M Replace broken floor and wall tile in boys restroom
361565 04/09/2014 359836 P 6231 M Replace missing wall tile adjacent to paper towel holder and trash can
348665 04/09/2014 331336 P 6231 M Seal open joint at mate line at rear of unit
348662 04/09/2014 331330 P 6231 M Repair emergency lighting in mens single bathroom
348663 04/09/2014 331332 P 6231 M Repair crack in wall in girls bathroom at base of wall behind toilets
361605 04/09/2014 359923 P 6416 M Repair emergency lighting at south door
361600 04/09/2014 359913 P 6417 M Repair emergency lighting at south door
361596 04/09/2014 359905 P 6419 M Repair emergency lighting
361591 04/09/2014 359894 P 6421 M Determine cause of water damaged ceiling tiles and replace tiles
361588 04/09/2014 359887 P 6421 M Repair emergency lighting at south door
361589 04/09/2014 359890 P 6421 M Replace missing base on wall at north door
361618 04/09/2014 359955 P 9184 M Repair emergency lighting at south door
361616 04/09/2014 359949 P 9185 M Repair emergency lighting at north door
361615 04/09/2014 359947 P 9186 M Adjust door closer at north door to control speed of closing door
361613 04/09/2014 359941 P 9188 M Repair emergency lighting at north door
361614 04/09/2014 359945 P 9188 M Repair broken hinge plate at north door
361609 04/09/2014 359933 P 9205 M Repair emergency lighting at north door
361610 04/09/2014 359935 P 9206 M Repair emergency lighting (x2)
361612 04/09/2014 359939 P 9207 M Repair emergency lighting at south door, test button broken
361611 04/09/2014 359937 P 9208 M Repair emergency lighting at south door
348688 04/09/2014 331385 P 9257 M Replace broken vinyl floor tile at mate line
361626 04/09/2014 359971 P 9258 M Repair emergency lighting at south door, test button broken
361624 04/09/2014 359967 P 9259 M Repair emergency lighting at north door
361625 04/09/2014 359969 P 9259 M Adjust door closer on north door to control speed of closing door
361621 04/09/2014 359961 P 9260 M Repair emergency lighting at north door
361622 04/09/2014 359963 P 9260 M Adjust door closer on north door to control speed of closing door
361652 04/09/2014 360023 P 9262 M Repair south door to close and latch properly
361650 04/09/2014 360019 P 9262 M Repair emergency lighting at south door
361651 04/09/2014 360021 P 9263 M Replace missing pad for corner of unit at south door which is below 6 feet 8 inches
361638 04/09/2014 359995 P 9299 M Repair broken test button on emergency lighting at south door
361639 04/09/2014 359997 P 9299 M Repair emergency lighting at north door
361644 04/09/2014 360007 P 9300 M Repair broken test button for emergency lighting at south door
361627 04/09/2014 359973 P 9416 M Repair emergency lighting at south door
361629 04/09/2014 359977 P 9416 M Verify that glass in display cabinets is tempered or safety glazing or provide tempered glass or safety glazing for glass
361630 04/09/2014 359979 P 9416 M Adjust door closer on north door to control speed of closing door
361631 04/09/2014 359981 P 9417 M Repair south door to open and close properly
361646 04/09/2014 360011 P 9527 M Verify impervious wall finish in bathroom and provide sign with date of application or provide impervious wall finish
361640 04/09/2014 359999 P 9528 M Repair emergency lighting at north door
361641 04/09/2014 360001 P 9528 M Remove unnecessary, expired fire extinguisher
361642 04/09/2014 360003 P 9528 M Anchor toilet to floor
361643 04/09/2014 360005 P 9528 M Verify impervious wall finish in bathroom and provide sign with date of application or provide impervious wall finish
361633 04/09/2014 359985 P 9529 M Anchor toilet to floor
361634 04/09/2014 359987 P 9529 M Verify impervious wall finish in bathroom and provide sign with date of application or provide impervious wall finish
361637 04/09/2014 359993 P 9529 M Repair emergency lighting (x2)
361632 04/09/2014 359983 P 9530 M Verify impervious wall finish in bathroom and provide sign with date of application or provide impervious wall finish
361593 04/09/2014 359899 P 9530 M Determine cause of water damaged ceiling tiles and replace tiles
361594 04/09/2014 359901 P 9530 M Repair hole in west wall
361584 04/09/2014 359878 P 9631 M Repair damaged door frame at bathroom door
361564 04/09/2014 359834 P 2500 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
361601 04/09/2014 359915 P 6417 O Prohibit plugging microwave (on south wall) into surge protector - plug directly into permanent electrical outlet
361602 04/09/2014 359917 P 6417 O Prohibit use of damaged surge protector at west desk
361604 04/09/2014 359921 P 6417 O Prohibit plugging surge protector into surge protector into surge protector at east wall
361599 04/09/2014 359911 P 6418 O Prohibit plugging surge protector into surge protector
361566 04/09/2014 359838 P 6422 O Prohibit orange multi outlet extension cord
361617 04/09/2014 359952 P 9185 O Provide certificate from manufacturer stating that furniture has been treated with flame retardant or remove and prohibit combustible (residential) furniture
361608 04/09/2014 359931 P 9205 O Prohibit use of grey multi outlet extension cord adjacent to tree, use 15A single outlet extension cord or surge protector
361647 04/09/2014 360013 P 9253 O Remove and prohibit air freshener
361649 04/09/2014 360017 P 9253 O Prohibit plugging surge protector into surge protector at computers in center of room
361620 04/09/2014 359959 P 9260 O Remove and prohibit air freshener
361645 04/09/2014 360009 P 9300 O Prohibit plugging surge protector into surge protector at computers in center of room
361648 04/09/2014 360015 P 9523 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
361592 04/09/2014 359897 P 9530 O Prohibit plugging surge protector into surge protector into surge protector
361583 04/09/2014 359875 P 9530 O Remove and prohibit air freshener
361582 04/09/2014 359873 7 0000 C Provide auto closer on door
348656 04/09/2014 331318 P 520 C Provide exhaust fan in bathroom
361606 04/09/2014 359925 P 6416A C Verify impervious wall finish and provide sign or provide impervious wall finish
361603 04/09/2014 359919 P 6417A C Verify impervious wall finish in bathroom and provide sign with date of application or provide impervious wall finish
361598 04/09/2014 359909 P 6418 C Verify impervious wall finish in bathroom and provide sign with date of application or provide impervious wall finish
361597 04/09/2014 359907 P 6419 C Verify impervious wall finish in bathroom and provide sign with date of application or provide impervious wall finish
361595 04/09/2014 359903 P 6420 C Verify impervious wall finish in bathroom and provide sign with date of application or provide impervious wall finish
361590 04/09/2014 359892 P 6421 C Verify impervious wall finish in bathroom and provide sign with date of application or provide impervious wall finish
361585 04/09/2014 359880 P 6422 C Verify impervious wall finish in bathroom and provide sign with date of application or provide impervious wall finish
361654 04/09/2014 360027 P 7003 C Provide bottom rail on ramp landing guardrail at 2 inches above floor
361586 04/09/2014 359883 P 9631A C Verify impervious wall finish in bathroom and provide sign with date of application or provide impervious wall finish
361581 04/09/2014 359870 P 9187 MS Provide current inspection tag for fire extinguisher
361636 04/09/2014 359991 P 9529 MS Recharge fire extinguisher
361619 04/09/2014 359957 P 0000 OS Prohibit signs at rear doors reading - Do not allow students to use back door. Signs may read Emergency Exit Only
348659 12/19/2013 331324 P 520 M Secure loose laminate in bathroom
348679 12/19/2013 331366 P 6422 M Repair emergency lighting at front of unit
348681 12/19/2013 331370 P 9184 M Repair emergency lighting at rear of unit
348682 12/19/2013 331372 P 9186 M Repair emergency lighting at rear of unit
348694 12/19/2013 331400 P 9300 M Repair emergency lighting at front of unit
348696 12/19/2013 331404 P 9527 M Repair emergency lighting
348698 12/19/2013 331408 P 9527 M Seal seam in bathroom flooring
348704 12/19/2013 331420 P 9631 M Repair emergency lighting at rear of unit
348670 12/19/2013 331347 P 2500 O Provide clear access to electrical panel
348673 12/19/2013 331353 00 0000 C Provide fire hydrant or dry standpipe on site. Only existing hydrant at NE corner of site on other side of fence (NA, Per V. Chodora, site plans approved as is)
348671 04/30/2013 331349 00 0000 M Unband all palm trees
348709 04/30/2013 331431 00 0000 M Secure loose spout on drinking fountain outside of 1-131
348714 04/30/2013 331433 00 0000 M Provide chain and lock on gate of fencing around electrical enclosure adjacent to 1-135
348717 04/30/2013 331450 00 0000 M Provide chain and lock on gate of fencing around lift station enclosure adjacent to 1-135
348719 04/30/2013 331454 00 0000 M Provide chain and lock on gate of fencing around electrical equipment adjacent to 1-136
348722 04/30/2013 331460 00 0000 M Replace cover for open 12 or 16 inch storm drain cleanout at rear of 1-103
348724 04/30/2013 331465 00 0000 M Provide chain and lock on gate of fencing around lift station enclosure adjacent to 1-103
336122 04/30/2013 304292 2 000 M Fill in dirt along foundation of building to prevent animal intrusion under the building
348672 04/30/2013 331351 2 103A M Repair leaking flush valve on toilet
348657 04/30/2013 331320 P 521 M Repair termite damage in bathroom and eliminate termites
336123 04/30/2013 304294 P 521 M Repair emergency lighting
348660 04/30/2013 331326 P 6231 M Repair leaking toilet supply line in womens single bathroom
348661 04/30/2013 331328 P 6231 M Replace broken toilet seat in mens single bathroom
348666 04/30/2013 331338 P 6231 M Fill holes in ground at rear of unit and adjacent to electrical enclosure at side of unit
348664 04/30/2013 331334 P 6231 M Repair leaking supply line for toilet 1 in girls bathroom
348667 04/30/2013 331340 P 6416 M Replace damaged drinking fountain
348669 04/30/2013 331344 P 6418 M Repair hole in bathroom wall
336115 04/30/2013 304278 P 6419 M Replace missing signage indicating FISH number above door (FISH number is 6419)
348675 04/30/2013 331358 P 6420 M Repair emergency lighting at rear of unit
348676 04/30/2013 331360 P 6421 M Determine cause of water damaged ceiling tiles and replace tiles
348677 04/30/2013 331362 P 6421 M Secure loose handicapped grabrail
348678 04/30/2013 331364 P 6421 M Repair leaking toilet supply line
348683 04/30/2013 331374 P 9187 M Replace safety pin on fire extinguisher
336124 04/30/2013 304296 P 9205 M Repair emergency lighting at front door
348684 04/30/2013 331377 P 9207 M Repair emergency lighting at rear of unit
336125 04/30/2013 304298 P 9208 M Repair emergency lighting at rear door
348686 04/30/2013 331381 P 9257 M Replace safety pin on fire extinguisher
348687 04/30/2013 331383 P 9257 M Repair emergency lighting at rear of unit
348691 04/30/2013 331393 P 9260 M Repair air conditioning unit, not running
348693 04/30/2013 331397 P 9261 M Repair air conditioning unit, not running
348695 04/30/2013 331402 P 9417 M Secure loose piece of ceiling grid
348699 04/30/2013 331410 P 9527 M Seal wall at bathroom sink to provide impervious wall finish
348701 04/30/2013 331414 P 9529 M Repair leaking hose outlet at rear of unit
348702 04/30/2013 331416 P 9529 M Replace safety pin on fire extinguisher
348703 04/30/2013 331418 P 9529 M Repair emergency lighting at front of unit
348705 04/30/2013 331423 P 9631 M Anchor toilet to floor
348706 04/30/2013 331425 P 9631 M Seal wall at bathroom sink to provide impervious wall finish
348707 04/30/2013 331427 P 9635 M Exterior junction boxes are in contact with ground. Remove dirt from under boxes so they do not contact ground
348718 04/30/2013 331452 00 0000 O Remove chain and padlock from gate with panic hardware from 1-102 to parking lot
348680 04/30/2013 331368 P 7003 O Keep both shower drains filled with water. Every 2 months pour 1 quart of water down drains
348689 04/30/2013 331387 P 9258 O Provide clear access to electrical panel
348692 04/30/2013 331395 P 9260 O Provide clear access to electrical panel
348708 04/30/2013 331429 P 0000 C Provide epoxy paint in bathrooms of P-103 to 111 and P-131 to 134 and provide sign indicating epoxy paint and when applied
348668 04/30/2013 331342 P 6418 MS Recharge fire extinguisher
348674 04/30/2013 331356 P 6419 MS Recharge fire extinguisher
348690 04/30/2013 331391 P 9260 MS Recharge fire extinguisher
348697 04/30/2013 331406 P 9527 MS Recharge fire extinguisher
348700 04/30/2013 331412 P 9528 MS Recharge fire extinguisher
336108 01/08/2013 304262 2 103 M Repair emergency lighting
336128 01/08/2013 304307 P 6416 M Repair loose vinyl base along wall at rear door
336116 01/08/2013 304280 P 6419 M Repair emergency lighting at rear door
336120 01/08/2013 304288 P 6420 M Secure hanging metal ceiling tile grid at two locations
336117 01/08/2013 304282 P 6422 M Repair emergency lighting at both entrance doors
336114 05/04/2012 304272 P 6417 M Determine cause of water damaged ceiling tiles and replace tiles
336121 05/04/2012 304290 P 6420 M Repair emergency lighting at rear door
336119 05/04/2012 304286 P 6420 M Determine cause of water damaged ceiling tiles and replace tiles
336118 05/04/2012 304284 P 6421 M Determine cause of water damaged ceiling tiles and replace tiles
336130 05/04/2012 304311 P 9416 M Repair entrance door to close properly (door drags on jamb)
336109 05/04/2012 304265 2 102 MS Provide current inspection tag for kitchen hood fire suppression system (inspection tag date was 02/2011)
336129 05/04/2012 304309 P 9528 OS Relocate storage at rear exit door to maintain clear aisle to exit
321480 04/07/2011 271894 00 9599 M Provide fill dirt for eroded areas on campus to prevent tripping hazards
321515 04/07/2011 271967 2 190 M Replace missing ceiling tiles
321513 04/07/2011 271963 2 9698 M Repair damaged chain link fencing adjacent to ramp @ 2-102 rear door
321516 04/07/2011 271969 P 521 M Secure loose ceiling tiles
321511 04/07/2011 271959 P 6231 M Replace missing section of wall in boy's bathroom
321470 04/07/2011 271873 P 6416 M Repair emergency lighting
321471 04/07/2011 271876 P 6416 M Repair/replace damaged vent on air conditioning unit, louvers are broken and missing
321474 04/07/2011 271882 P 6418 M Repair rear door to close properly
321478 04/07/2011 271890 P 6422 M Repair lock on bathroom door, lock button is missing
321479 04/07/2011 271892 P 6422 M Replace missing cover for pipe in grass adjacent to rear (north) door of P-6422 (1-109)
321518 04/07/2011 271973 P 9184 M Adjust door closer @ entrance door to control speed of closing door
321527 04/07/2011 271992 P 9188 M Repair deteriorated wall finish, paint is peeling
321525 04/07/2011 271987 P 9206 M Remove broken grounding plug from electrical outlet adjacent to fire extinguisher
321523 04/07/2011 271983 P 9207 M Mount fire extinguisher at maximum five feet above floor
321509 04/07/2011 271953 P 9256 M Repair emergency lighting
321504 04/07/2011 271943 P 9260 M Replace broken gauge on fire extinguisher
321481 04/07/2011 271896 P 9262 M Repair emergency lighting
321482 04/07/2011 271898 P 9262 M Repair rear (south) door to close properly
321497 04/07/2011 271928 P 9263 M Pad and mark corners of unit which are lower than 6'8
321490 04/07/2011 271914 P 9299 M Pad and mark corners of unit which are lower than 6'8
321492 04/07/2011 271918 P 9299 M Secure loose ceiling tile
321484 04/07/2011 271902 P 9527 M Replace missing transition strip/edge piece on air conditioning unit
321487 04/07/2011 271908 P 9528 M Secure loose toilet paper holder
321488 04/07/2011 271910 P 9529 M Replace missing ceiling tiles
321469 04/07/2011 271871 P 2500 O Prohibit grey multi outlet power strip or replace with approved surge protector
321517 04/07/2011 271971 P 520 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
321473 04/07/2011 271880 P 6418 O Prohibit plugging surge protector into surge protector
321475 04/07/2011 271884 P 6419 O Prohibit plugging surge protector into extension cord
321477 04/07/2011 271888 P 6421 O Remove and prohibit air freshener (in bathroom)
321519 04/07/2011 271975 P 9184 O Prohibit plugging surge protector into surge protector
321522 04/07/2011 271981 P 9185 O Prohibit plugging microwave and coffee maker into media cart - plug directly into permanent electrical outlet
321526 04/07/2011 271989 P 9205 O Prohibit plugging microwave and coffee maker into surge protector - plug directly into permanent electrical outlet
321524 04/07/2011 271985 P 9206 O Prohibit plugging surge protector into surge protector
321494 04/07/2011 271922 P 9253 O Prohibit plugging surge protector into surge protector
321508 04/07/2011 271951 P 9256 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
321510 04/07/2011 271955 P 9256 O Prohibit white 13A extension cord or replace with minimum 15A cord
321506 04/07/2011 271947 P 9259 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
321495 04/07/2011 271924 P 9263 O Remove and prohibit air freshener
321496 04/07/2011 271926 P 9263 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
321491 04/07/2011 271916 P 9299 O Remove and prohibit air freshener
321493 04/07/2011 271920 P 9300 O Prohibit plugging surge protector into surge protector @ computer and teacher's desk
321500 04/07/2011 271934 P 9416 O Prohibit plugging surge protector into extension cord
321486 04/07/2011 271906 P 9528 O Remove and prohibit air freshener
321503 04/07/2011 271941 P 9635 O Prohibit plugging surge protector into surge protector (X2)
321472 04/07/2011 271878 P 0000 C Provide impervious wall finish for minimum six foot height in bathrooms and identify by dated sign or stencil in each bathroom
321476 04/07/2011 271886 P 6420 F Provide heat detector in bathroom being used as a storage room or prohibit storage in bathroom
321512 04/07/2011 271961 2 102 MS Provide current inspection tag for kitchen hood fire suppression system or verify that system is not active
321514 04/07/2011 271965 2 103 MS Provide current inspection tag for fire extinguisher
321520 04/07/2011 271977 P 9184 MS Recharge fire extinguisher
321521 04/07/2011 271979 P 9185 MS Recharge fire extinguisher
321505 04/07/2011 271945 P 9260 MS Provide current inspection tag for fire extinguisher
321499 04/07/2011 271932 P 9416 MS Provide current inspection tag for fire extinguisher
321498 04/07/2011 271930 P 9417 MS Provide current inspection tag for fire extinguisher
321507 04/07/2011 271949 P 9257 OS Maintain clear aisle to exit doors
321483 04/07/2011 271900 P 9262 OS Prohibit sign on door reading "Do not open", sign may read "Emergency Exit Only"
321485 04/07/2011 271904 P 9527 OS Prohibit sign on door reading "Do not open" sign may read "Emergency Exit Only"
321489 04/07/2011 271912 P 9530 OS Prohibit sign on door reading "Do not open" sign may read "Emergency Exit Only"
302818 03/04/2010 231090 2 101A M Replace missing ceiling tiles
302806 03/04/2010 231064 P 7003 M Repair hole in wall next to boys bathroom in clinic
302810 03/04/2010 231073 P 9207 M Repair rear door to close and latch properly
302813 03/04/2010 231080 P 9257 M Repair door to close and latch properly
302811 03/04/2010 231076 P 9258 M Repair front door to close and latch properly
302814 03/04/2010 231082 P 9631 M Repair door to close properly
302809 03/04/2010 231071 P 9207 O Relocate cabinet to provide clear access to electrical panel
302812 03/04/2010 231078 P 9256 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
302807 03/04/2010 231067 P 9528 O Relocate cabinet to provide clear access to electrical panel
302808 03/04/2010 231069 P 9530 O Provide clear access to electrical panel
297456 03/04/2010 219460 00 0000 C Provide exterior signage indicating property address
302804 03/04/2010 231057 00 0000 MS Provide Knox box padlock on west gate next to Administartive Office to allow fire department access
302816 03/04/2010 231086 P 6419 OS Relocate table to maintain clear aisle to front exit door
302815 03/04/2010 231084 P 6420 OS Relocate table to maintain clear aisle to front exit door
302819 03/04/2010 231092 2 102 CS Provide auto closer on exterior exit door in kitchen
283882 10/30/2009 190510 00 0000 M Gym (Off Site) - Men's Restroom - Replace missing escutcheon on fire sprinkler head(Boys and Girls Club no longer used by school)
297435 10/30/2009 219415 P 9300 M Mount fire extinguisher adjacent to front door at maximum five feet above floor
297458 10/30/2009 219464 00 0000 C Provide permanent fencing around entire perimeter of property
283878 10/30/2009 190502 00 0000 C Provide adequate signage to direct visitors to an accessible route to the Main Office
297454 10/30/2009 219456 P 0000 C Provide emergency lighting in temporary Cafeteria Portable
297425 10/30/2009 219394 P 2500 C Provide signage at all rooms indicating room name and number at appropriate height with raised and Braille characters
297460 10/30/2009 219468 P 6231 C Provide signage indicating room names and numbers at appropriate height with raised and Braille characters
297426 10/30/2009 219396 P 7003 C Provide signage at all rooms indicating room name and number at appropriate height with raised and Braille characters
297455 10/30/2009 219458 00 0000 MS Provide Knox box to allow fire department access
297469 10/30/2009 219486 P 6417 OS Relocate computer desk blocking front exit door
283883 04/30/2009 190512 00 0000 M Gym (Off Site) - Men's Restroom - Repair emergency lighting
283884 04/30/2009 190514 00 0000 M Gym (Off Site) - Repair SE exit doors to open properly - panic hardware does not retract latching device
283887 04/30/2009 190520 00 0000 M Gym (Off Site) - Women's Restroom - Repair emergency lighting
283888 04/30/2009 190522 00 0000 M Gym (Off Site) - Repair doors at NW exit to open properly - panic hardware does not control latching devices
297468 04/30/2009 219484 P 6417 M Adjust rear exit door to latch properly
297467 04/30/2009 219482 P 6418 M Replace broken glass in rear exit door
297428 04/30/2009 219400 P 7003 M Replace missing ceiling tile in filing room
297436 04/30/2009 219417 P 9253 M Repair rear door to close properly
297433 04/30/2009 219411 P 9530 M Determine cause of water damaged ceiling tiles and replace tiles (Elemetary Transitions West)
297444 04/30/2009 219436 P 9188 O Prohibit plugging surge protector into surge protector at teachers desk
297430 04/30/2009 219405 P 9527 O Relocate bookcase blocking clear access to electrical panel (Elementary Transitions West)
297461 04/30/2009 219470 P 9635 O Maintain room in an orderly manner
297431 04/30/2009 219407 P 9528 OS Remove storage blocking rear exit door (Elementary Transitions West)
297462 04/30/2009 219472 P 9631 OS Maintain clear aisle to rear exit door
297427 04/30/2009 219398 P 2500 FS Provide heat detector in storage room@ front office
283885 02/24/2009 190516 00 0000 M Gym (Off Site) - Replace missing cover on thermostat equipment near SE exit
245262 02/24/2009 110122 00 0000 M Verify emergency lights in all rooms are operable - lights too high to reach
257798 02/24/2009 136929 00 8087 M Provide Engineer's evaluation of rotted framing members for covered walkway throughout campus and repair or replace deteriorated wood framing according to Engineer's recommendations
283928 02/24/2009 190610 1 104C M Remove lock from one door to allow egress from bathroom vestibule at all times
283897 02/24/2009 190545 10 102 M Provide current inspection tag for kitchen steamer (boiler)
228827 02/24/2009 25050 3 108 M Adjust steps to make risers equal - to grassy area
245269 02/24/2009 110136 9 107 M Adjust steps at west end of corridor to make risers equal
228944 02/24/2009 25035 P 520 M Modify existing foundations and anchorage to comply with engineering requirements
228865 02/24/2009 25036 P 521 M Modify existing foundations and anchorage to comply with engineering requirements
229019 02/24/2009 24917 00 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters throughout campus
228813 02/24/2009 24989 00 8087 C Modify guardrails along covered walkways where walks are more than 18" above the ground to be a minimum of 42" high
228943 02/24/2009 25034 00 9500 C Provide covered walkway between all portable units
229022 02/24/2009 24991 00 9599 C Provide ramp with handrails in lieu of stairs at east end of campus (leading to portables)
229024 02/24/2009 25039 00 9599 C Turn barbs down on all fencing
229026 02/24/2009 24993 00 9599 C Provide graspable handrails on each side of ramp at between 34-38 inches high (ramp leads to PE field on south side of campus)
229027 02/24/2009 24994 1 101 C Make exterior walkway level with interior floor
228870 02/24/2009 24995 1 102D C Make exterior walkway level with interior floor
229030 02/24/2009 24996 1 103 C Make exterior walkway level with interior floor
257775 02/24/2009 136883 1 103C C Make exterior walkway level with interior floor
228816 02/24/2009 24999 1 104D C Make exterior walkway level with interior floor (CIT/BIA office)
228818 02/24/2009 25000 1 107 C Make exterior walkway level with interior floor (data processor)
228884 02/24/2009 25028 10 101 C Adjust steps outside east door to make risers equal and landing level with interior floor (cafeteria)
228982 02/24/2009 25029 10 101 C Make exterior walkway level with interior floor (cafeteria) (northwest doors)
228862 02/24/2009 25032 10 101A C Provide handicapped accessibility to stage
228820 02/24/2009 25001 2 107 C Make exterior walkway level with interior floor
228821 02/24/2009 25002 2 108 C Make exterior walkway level with interior floor (A-1)
228824 02/24/2009 25003 3 101 C Make exterior walkway level with interior floor
228972 02/24/2009 25004 3 104 C Make exterior walkway level with interior floor (B-1)
228940 02/24/2009 25010 5 102 C Make exterior walkway level with interior floor
228834 02/24/2009 57438 5 108 C Make exterior walkway level with interior floor
228836 02/24/2009 25015 5 109 C Adjust steps at west end of corridor to make risers equal (covered walk)
228975 02/24/2009 25016 6 101 C Make exterior walkway level with interior floor
228837 02/24/2009 25017 6 103 C Make exterior walkway level with interior floor
228912 02/24/2009 25020 7 102 C Make exterior walkway level with interior floor
228980 02/24/2009 25021 7 103 C Make exterior walkway level with interior floor
228941 02/24/2009 25022 7 104 C Make exterior walkway level with interior floor
229008 02/24/2009 25023 7 107 C Adjust steps at west and south ends of corridor to make risers equal (covered walk)
228851 02/24/2009 57439 9 101 C Make exterior walkway level with interior floor(X2)
228859 02/24/2009 66023 9 101C C Provide exhaust fan in bathroom
245272 02/24/2009 110143 9 103B C Provide exhaust fan in bathroom
229009 02/24/2009 57423 9 104B C Provide exhaust fan in bathroom
297429 02/24/2009 219402 P 0000 C Provide concrete pad at rear doors of all portables to make exterior walkway level with interior floor (Exception to this code was written by Victor Chodora on March 24, 2009. These doors will have no exterior concrete pad and will have signs stating "Not an Exit") due to making the exterior electrical boxes below grade
245275 02/24/2009 110149 P 521 C Provide exhaust fan in bathroom
283893 02/24/2009 190536 7 103A MS Close attic access hatch
228878 02/24/2009 24988 00 0000 CS Modify fencing at north side of campus to allow egress at all times and remove padlock
228906 02/24/2009 24992 00 9599 CS Modify perimeter fencing and gates to allow at least one means of egress from campus to open fields on south and west sides of campus at all times and remove padlocks
283924 02/24/2009 190600 2 102 FS Provide inspection report for fire alarm panel
257821 02/24/2009 136980 4 0000 N/A No violations observed
257825 02/24/2009 136988 8 0000 N/A No violations observed
283886 04/30/2008 190518 00 0000 M Gym (Off Site) Repair damaged emergency light in NE corner of gym - bulb hanging by wires
283929 04/30/2008 190612 1 105 M Provide cover on exposed electrical junction box
283895 04/30/2008 190540 10 101 M Determine why there is electrical tape over electrical outlet next to bug fan at center door on west wall and repair outlet or fan as necessary
283916 04/30/2008 190584 4 103 M Connect dryer duct to back of clothes dryer
283920 04/30/2008 190592 5 102 M Determine cause of water damaged ceiling tiles and replace tiles
283921 04/30/2008 190594 5 103 M Determine cause of water damaged ceiling tiles and replace tiles
283889 04/30/2008 190525 P 520 M Determine cause of water damaged ceiling tiles and replace tiles
283926 04/30/2008 190605 1 102 O Prohibit plugging extension cord into surge protector
283927 04/30/2008 190607 1 103 O Prohibit plugging surge protector into surge protector
283896 04/30/2008 190543 10 101 O Prohibit plugging vending machine into surge protector - plug directly into permanent electrical outlet
283898 04/30/2008 190547 10 101 O Prohibit plugging microwave oven into extension cord - plug directly into permanent electrical outlet
283922 04/30/2008 190596 2 108 O Prohibit plugging surge protector into extension cord
283923 04/30/2008 190598 2 108 O Eliminate extension cord or replace with minimum 15A cord
283915 04/30/2008 190582 3 101 O Prohibit plugging surge protector into surge protector
283909 04/30/2008 190570 3 102 O Prohibit plugging surge protector into extension cord
283912 04/30/2008 190576 3 102 O Eliminate extension cord or replace with minimum 15A cord
283913 04/30/2008 190578 3 104 O No access was available to this room. Please be prepared to access this room during the report review meeting.
283918 04/30/2008 190588 4 102 O Eliminate extension cord or replace with minimum 15A cord
283904 04/30/2008 190560 4 104 O No access was available to this room. Please be prepared to access this room during the report review meeting.
283905 04/30/2008 190562 5 101 O No access was available to this room. Please be prepared to access this room during the report review meeting.
283919 04/30/2008 190590 5 102 O Prohibit plugging surge protector into extension cord
283899 04/30/2008 190549 6 101 O Remove and prohibit paper covering windows
283900 04/30/2008 190551 6 101 O Eliminate extension cord or replace with minimum 15A cord
283901 04/30/2008 190554 6 101 O Prohibit plugging surge protector into extension cord
283907 04/30/2008 190566 6 102 O Prohibit plugging surge protector into extension cord
283910 04/30/2008 190572 6 102 O Eliminate extension cord or replace with minimum 15A cord
283911 04/30/2008 190574 6 104 O Eliminate extension cord or replace with minimum 15A cord
283908 04/30/2008 190568 6 104 O Prohibit plugging surge protector into extension cord
283903 04/30/2008 190558 6 107 O No access was available to this room. Please be prepared to access this room during the report review meeting.
283892 04/30/2008 190533 7 104 O Prohibit plugging surge protector into extension cord
283891 04/30/2008 190531 7 104A O Replace missing bulb in light fixture
283894 04/30/2008 190538 7 105 O No access was available to this room. Please be prepared to access this room during the report review meeting.
283881 04/30/2008 190508 8 102 O Prohibit plugging surge protector into surge protector
283880 04/30/2008 190506 8 108 O No access was available to this room. Please be prepared to access this room during the report review meeting.
283879 04/30/2008 190504 8 109 O No access was available to this room. Please be prepared to access this room during the report review meeting.
283890 04/30/2008 190529 9 104 O Prohibit plugging microwave oven, refrigerator and water cooler into surge protector - plug each directly into permanent electrical outlet
228909 04/30/2008 66034 3 102 MS Provide current inspection tag for fire extinguisher
283902 04/30/2008 190556 6 101 MS Replace missing fire extinguisher
245260 04/30/2008 110118 00 0000 OS Keep doors of rooms that are signed FIRE ALARM INSIDE unlocked when facility is occupied to allow access to fire alarm pull station
245261 04/30/2008 110120 00 0000 OS Keep doors of rooms that are signed FIRE EXTINGUISHER INSIDE unlocked when facility is occupied to access fire extinguisher
283925 04/30/2008 190602 1 101 OS Relocate plant blocking clear access to fire extinguisher
283914 04/30/2008 190580 3 103 OS Relocate bookcase so fire extinguisher can be kept on its bracket adjacent to the door
283917 04/30/2008 190586 4 103 OS Keep gas powered blower inside flammable storage cabinet
257771 02/21/2008 136879 00 0000 M Make top of ramp north of Building 1 level with sidewalk
229025 02/21/2008 25040 00 9599 M Make top of ramp east of Building 8 level with covered walkway
228868 02/21/2008 63211 P 520 M Adjust ramp and stair landings to be level with interior floor
245270 02/21/2008 110138 9 101 O Prohibit plugging surge strips into surge strips (D-5)
245271 02/21/2008 110140 9 101 C Provide additional electric outlets for computers to eliminate need for extension cords (D-5)
257788 02/21/2008 136915 2 106 OS Prohibit storage of gas powered equipment
245286 02/21/2008 110172 6 102A OS Prohibit running electrical cord through door opening
228985 02/21/2008 24921 10 9599 CS Modify gate between Bldgs. 6 & 10 to allow egress at all times and remove padlock to eliminate dead end corridor
257827 02/21/2008 136992 10 0000 N/A No violations observed
257820 02/21/2008 136978 3 0000 N/A No violations observed
257822 02/21/2008 136982 5 0000 N/A No violations observed
257823 02/21/2008 136984 6 0000 N/A No violations observed
257824 02/21/2008 136986 7 0000 N/A No violations observed
257826 02/21/2008 136990 9 0000 N/A No violations observed
257768 03/21/2007 136871 00 0000 M Repair damaged chain link fencing west of Building 2
257769 03/21/2007 136874 00 0000 M Repair broken sidewalk north of Building 1
257790 03/21/2007 136919 2 103 M Determine cause of water damaged ceiling tiles and replace tiles
257793 03/21/2007 136924 3 102A M Repair door to open and close properly
257778 03/21/2007 136894 3 107 M Repair termite damage to door
257789 03/21/2007 136917 4 102A M Anchor toilet to floor
257787 03/21/2007 136911 4 104 M Determine cause of water damaged ceiling tiles and replace tiles
257779 03/21/2007 136896 5 102 M Determine cause of water damaged ceiling tiles and replace tiles
257780 03/21/2007 136898 5 103 M Determine cause of water damaged ceiling tiles and replace tiles
257782 03/21/2007 136902 5 103 M Repair emergency lighting
257784 03/21/2007 136906 5 108 M Replace missing base along wall
257786 03/21/2007 136908 5 108 M Repair emergency lighting
257792 03/21/2007 136922 6 105 M Secure sink to wall
257807 03/21/2007 136952 8 102 M Repair emergency lighting
257814 03/21/2007 136966 8 105 M Anchor toilets to floor
257815 03/21/2007 136968 8 105 M Provide escutcheon around toilet supply
257816 03/21/2007 136970 8 105 M Cover opening in wall at toilet supply line escutcheon
257813 03/21/2007 136963 8 106 M Anchor toilet to floor
257808 03/21/2007 136955 9 103 M Repair emergency lighting
257805 03/21/2007 136947 9 103 M Replace missing vinyl floor tiles
257810 03/21/2007 136958 9 104 M Repair emergency lighting
257803 03/21/2007 136944 9 104B M Repair termite damage to door frame
257800 03/21/2007 136938 P 520 M Determine cause of water damaged ceiling tiles and replace tiles
257777 03/21/2007 136891 00 0 O No access was available to 5-101, 7-105 & 7-106. Please be prepared to access these rooms during the report review meeting.
258936 03/21/2007 139339 9 103B F Lower heat detector to be beneath ceiling tiles rather than above tiles
257801 03/21/2007 136941 P 520 MS Provide current inspection tag for fire extinguisher (dated 2000)
257817 03/21/2007 136972 P 521 OS Prohibit running electrical cord through door opening
245293 10/17/2006 110187 00 0 O No access was available to 8-108, 8-109. Please be prepared to access these rooms during the report review meeting.
229021 10/17/2006 24918 00 9599 C Stripe and sign, "No Parking, Fire Lane" in parking lot behind kitchen door to allow fire department access
245276 10/17/2006 110151 P 521 F Provide fire alarm strobe light
245291 10/17/2006 110183 7 103A OS Prohibit electrical cord from running through door opening
245280 10/17/2006 110160 5 103 FS Provide heat detector in room used for storage (B-7)
245282 11/30/2005 110164 00 9699 M Lock up electric meter and panel adjacent to P-2 to prohibit student access to electrical equipment
245259 11/30/2005 110116 10 101 M Determine cause of water damaged ceiling tiles and replace tiles
228864 11/30/2005 66013 10 8088 M Label all circuit breakers in electrical panel on east exterior wall adjacent to propane tank
228879 11/30/2005 66014 2 103 M Label all fuses in electrical panels adjacent to fire alarm panel
245267 11/30/2005 110132 2 105 M Determine cause of water damaged ceiling tiles and replace tiles
245268 11/30/2005 110134 2 106 M Repair sagging ceiling grid
245266 11/30/2005 110130 2 108 M Determine cause of water damaged ceiling tiles and replace tiles (A-1)
245285 11/30/2005 110170 3 107 M Repair emergency lighting
245284 11/30/2005 110168 4 101 M Repair emergency lighting
245278 11/30/2005 110156 4 103 M Provide metal vent for dryer.
245283 11/30/2005 110166 4 104 M Determine cause of water damaged ceiling tiles and replace tiles
245264 11/30/2005 110126 5 102 M Determine cause of water damaged ceiling tiles and replace tiles (B-6)
245281 11/30/2005 110162 5 103 M Determine cause of water damaged ceiling tiles and replace tiles (B-7)
245288 11/30/2005 110176 5 105 M Anchor 1st toilet to floor
245277 11/30/2005 110153 6 101 M Replace safety pin on fire extinguisher (C-4)
245289 11/30/2005 110179 6 105 M Anchor handicapped toilet to floor
245292 11/30/2005 110185 7 103A M Provide cover on exposed electrical junction box in attic space
245256 11/30/2005 110110 8 106 M Patch holes in tile on wall
245257 11/30/2005 110112 8 106 M Tile around floor drain to eliminate standing water and make floor impervious
245258 11/30/2005 110114 8 106 M Cover or remove old sink supply line that is protruding from wall
245273 11/30/2005 110145 P 521 M Determine cause of water damaged ceiling tiles and replace tiles
245274 11/30/2005 110147 P 521 M Repair exhaust fan in bathroom
245263 11/30/2005 110124 3 104 MS Provide current inspection tag for fire extinguisher (B-1)
245279 11/30/2005 110158 5 102 MS Recharge fire extinguisher (B-6)
245287 11/30/2005 110174 7 101 MS Recharge fire extinguisher (C-5)
245290 11/30/2005 110181 7 102 MS Provide current inspection tag for fire extinguisher (C-6)
245265 11/30/2005 110128 2 107 OS Prohibit storage of gas powered equipment
245538 11/30/2005 110697 4 103 OS Do not use dryer until vent is connected
229034 11/30/2005 66024 2 103 FS Provide certification that fire alarm system has been tested and is fully operational - System indicated trouble
229018 08/24/2004 66000 M No access was available to 6-107. Please be prepared to access this room during the report review meeting.
229023 08/24/2004 25038 00 9599 M Provide hurricane anchorage for Petrolane tank east of Building 10
228945 08/24/2004 25037 00 9599 M Fill hole in grass area and undermined foundation at NE corner of Bldg. 10
228856 08/24/2004 66001 1 101E M Determine cause of water damaged ceiling tiles and replace tiles
228817 08/24/2004 66002 1 104D M Replace missing ceiling tile
228942 08/24/2004 66030 10 101 M Replace safety pin on fire extinguisher adjacent to stage
228983 08/24/2004 66003 10 101A M Secure loose ceiling tile at west side of stage and replace ceiling tile which has a hole on east side of stage
228863 08/24/2004 66012 10 102 M Label all circuit breakers in electrical panels
229035 08/24/2004 66068 2 103 M Patch hole in wall finish above electrical panels
229032 08/24/2004 66004 2 103 M Repair sagged ceiling tile grid and replace damaged tiles
228907 08/24/2004 66005 2 108 M Determine cause of water damaged ceiling tiles and replace tiles
228822 08/24/2004 66018 2 109 M Provide cover for exposed electrical box on heater or remove heater if not in use
228939 08/24/2004 66045 3 101A M Repair light fixture in closet
228830 08/24/2004 66061 3 102 M Provide sign indicating "Fire Extinguisher Inside"
228880 08/24/2004 66046 3 102A M Repair light fixture in closet
228825 08/24/2004 66047 3 103A M Repair light fixture in closet
228828 08/24/2004 66066 4 102 M Secure loose threshold
228881 08/24/2004 66006 4 104 M Determine cause of mold on ceiling tiles and replace tiles
228829 08/24/2004 66048 5 102A M Repair light fixture in closet
228831 08/24/2004 66007 5 103 M Determine cause of water damaged ceiling tiles and replace tiles
228832 08/24/2004 66049 5 103A M Repair light fixture in closet
228833 08/24/2004 66050 5 104A M Repair light fixture in closet
228886 08/24/2004 57443 5 105 M Replace broken and missing ceramic tiles in bathroom adjacent to urinals
228835 08/24/2004 66008 5 108 M Replace missing ceiling tile
228976 08/24/2004 66009 6 101 M Replace all missing ceiling tiles around communications cabinet
229004 08/24/2004 66051 6 101A M Repair light fixture in closet
228978 08/24/2004 66052 6 102A M Repair light fixture in closet
228838 08/24/2004 66053 6 103A M Repair light fixture in closet
228839 08/24/2004 66054 6 104A M Repair light fixture in closet
228910 08/24/2004 66010 6 106 M Repair door to open properly - door sticks
229005 08/24/2004 66067 6 106 M Repair exhaust fan in bathroom
228841 08/24/2004 66059 6 109 M Secure loose drinking fountain adjacent to 6-106
228842 08/24/2004 66031 7 101 M Replace safety pin on fire extinguisher
228843 08/24/2004 66065 7 101 M Provide sign indicating "Fire Alarm Pull Station Inside"
228883 08/24/2004 66062 7 101 M Provide sign indicating "Fire Extinguisher Inside"
228911 08/24/2004 66019 7 101A M Replace broken cover plate for light switch
229006 08/24/2004 66055 7 101A M Repair light fixture in closet
228844 08/24/2004 66056 7 103A M Repair light fixture in closet
228848 08/24/2004 66063 8 104 M Provide sign indicating "Fire Extinguisher Inside"
228852 08/24/2004 66011 9 101 M Repair west door to open and close properly
228855 08/24/2004 66057 9 101C M Repair light fixture in bathroom
228860 08/24/2004 66058 9 103A M Repair light fixture in closet
228861 08/24/2004 66064 9 104 M Replace torn signage indicating "Fire Extinguisher Inside"
228986 08/24/2004 63210 P 1 M Adjust ramp and stair landings to be level with interior floor
228784 08/24/2004 66039 P 521 M Secure loose flooring edge strip adjacent to east door
228814 08/24/2004 66020 1 102 O Eliminate use of cord with a 4-outlet electrical box adjacent to principal's desk or replace with minimum 15A surge protector
228815 08/24/2004 66021 1 103 O Eliminate extension cord adjacent to teacher's desk or replace with minimum 15A surge protector
228984 08/24/2004 66015 10 102 O Relocate kitchen equipment to provide clear access to electrical panels
228819 08/24/2004 66042 2 101 O Keep cover mounted on air conditioning unit to eliminate hazard
229033 08/24/2004 66016 2 103 O Provide clear access to electrical panels adjacent to fire alarm panel
228908 08/24/2004 66040 3 101 O Remove and prohibit combustible beanbag chairs
228826 08/24/2004 66043 3 104 O Prohibit use of sanitizing cabinet for paper product storage to eliminate fire hazard. Have maintenance remove the cabinet or remove the electrical cord for the cabinet
228977 08/24/2004 66044 6 102 O Prohibit use of sanitizing cabinet for paper product storage to eliminate fire hazard. Have maintenance remove the cabinet or remove the electrical cord for the cabinet
228854 08/24/2004 66017 9 101A O Relocate storage to provide clear access to electrical panel
228914 08/24/2004 66022 9 104 O Prohibit use of extension cord to power small refrigerator adjacent to teacher's desk
229020 08/24/2004 66060 00 0000 C Paint building numbers on exterior walls throughout campus to be visible to fire rescue personnel
228869 08/24/2004 24990 00 9599 C Provide fencing around electrical panel and transformer south of Building 10 (x2)
229031 08/24/2004 24997 1 103B C Provide exhaust fan in bathroom
228857 08/24/2004 24998 1 104B C Provide exhaust fan in bathroom
228872 08/24/2004 25030 10 101 C Provide sign indicating maximum occupancy adjacent to main entrance (cafeteria)
228973 08/24/2004 25008 3 107 C Provide exhaust fan in bathroom
228858 08/24/2004 25009 4 101A C Provide exhaust fan in bathroom
228882 08/24/2004 25011 5 105 C Provide partitions between urinals (bathroom)
228974 08/24/2004 25014 5 108 C Provide partitions between urinals (bathroom)
228979 08/24/2004 25019 6 106 C Provide doors for toilet stalls (bathroom)
228840 08/24/2004 25018 6 106 C Provide partitions between urinals (bathroom)
228849 08/24/2004 25024 8 106 C Provide partitions between urinals (bathroom)
228850 08/24/2004 25025 8 106 C Provide doors for toilet stalls (bathroom)
228885 08/24/2004 25026 9 101 C Provide tempered glazing, safety glass, or safety plastic in windows within 48 inches of doors
228871 08/24/2004 25027 9 101 C Provide sign indicating maximum occupancy adjacent to main entrance (D-5)
228913 08/24/2004 24920 9 104 C Provide emergency lighting
228785 08/24/2004 63209 P 520 C Provide handicapped accessible door hardware
228866 08/24/2004 63208 P 521 C Provide handicapped accessible door hardware
228867 08/24/2004 66041 P 521 C Provide tempered glass, safety glass, or stainless steel for mirror
228916 08/24/2004 25033 P 521 C Make exterior walkway level with interior floor
228823 08/24/2004 66037 2 109 MS Prohibit storage of flammable paint which belongs to maintenance
229003 08/24/2004 66032 6 101 MS Recharge fire extinguisher
228845 08/24/2004 66029 7 104 MS Replace missing fire extinguisher
228846 08/24/2004 66033 8 103 MS Recharge fire extinguisher
228847 08/24/2004 66035 8 104 MS Provide current inspection tag for fire extinguisher
228853 08/24/2004 66036 9 101 MS Provide current inspection tag for fire extinguisher
229028 08/24/2004 66025 1 101 OS Relocate plant blocking view and access to fire extinguisher
228915 08/24/2004 66026 10 101 OS Relocate soda machine blocking clear access to fire extinguisher adjacent to door
228873 08/24/2004 57426 2 109 OS Prohibit storage of flammable marking spray paint
228981 08/24/2004 66038 8 108 OS Prohibit storage of flammable paint
228786 08/24/2004 66027 P 520 OS Relocate storage to provide clear access to fire extinguisher and fire alarm pull station
229007 08/24/2004 66028 7 103 CS Provide new CO2 fire extinguisher in computer classroom