Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
417135 03/28/2018 479994 00 0000 M Provide waterproof cover on exposed electrical outlet for water fountain at P.E. Pavilion
417136 03/28/2018 479997 00 0000 M Remove all dead trees and branches from around retention pond
417133 03/28/2018 479988 1 119 M Replace missing water heater and cover all open electrical wiring for heater in janitorial closet
417113 03/28/2018 479947 2 204 M Replace missing ceiling tiles in women's restroom
417123 03/28/2018 479967 2 219 M Provide dated flame resistance label on stage curtain (last certified on April 23, 2012)
417124 03/28/2018 479970 2 219 M Secure loose handrail on steps in front of stage
417126 03/28/2018 479974 2 222 M Secure hanging lens on light fixture
417128 03/28/2018 479979 2 223 M Provide non-slip surface for ramp
417130 03/28/2018 479982 2 235 M Repair exterior exit doors (X2) to close properly
417118 03/28/2018 479958 2 242A M Replace missing ceiling tiles and secure hanging heat detector
417121 03/28/2018 479962 2 242A M Repair exhaust fan at kiln room and inspect kiln for proper working condition
417117 03/28/2018 479955 2 243 M Secure hanging light fixture lens in men's restroom
417109 03/28/2018 479936 3 312 M Secure cover on exposed electrical junction box next to door (cover is marked "Fire Alarm")
417111 03/28/2018 479941 3 314 M Provide current emergency generator and lighting certificate (last date on certificate is March 22, 2016)
417107 03/28/2018 479931 3 322 M Place cover on open wiring in clock enclosure
417073 03/28/2018 479862 4 0000 M Adjust smoke doors in corridor adjacent to 4-413 to close properly
417076 03/28/2018 479868 4 401 M Provide cover on exposed electrical wiring in clock enclosure
417075 03/28/2018 479866 4 403 M Replace damaged floor tiles at exterior door
417071 03/28/2018 479858 4 414 M Determine cause of water damaged ceiling tile above clock and replace tiles
417072 03/28/2018 479860 4 416A M Replace rusted sink in girl's bathroom
417051 03/28/2018 479815 4 418 M Mount fire extinguisher at maximum five feet above floor (extinguisher is sitting on floor)
417070 03/28/2018 479856 4 423 M Replace missing ceiling tiles
417069 03/28/2018 479854 4 425 M Repair exterior exit door to close properly (drags on exterior concrete pad)
417052 03/28/2018 479818 4 428 M Secure hanging lens on light fixture
417065 03/28/2018 479844 4 429 M Repair exterior exit door to close and latch properly
417058 03/28/2018 479830 4 432 M Repair exterior exit door to close properly
417063 03/28/2018 479840 4 433 M Repair exterior exit door to close properly
417061 03/28/2018 479835 4 434 M Replace missing vinyl base at exterior exit door
417082 03/28/2018 479880 6 0000 M Provide cover on exposed electrical junction box on exterior wall between 6-104 and 6-105
417077 03/28/2018 479870 6 102A M Replace missing ceiling tiles
417078 03/28/2018 479872 6 103 M Provide cover on exposed electrical junction box on east wall next to flag
417079 03/28/2018 479874 6 103 M Repair emergency lighting on west wall
417080 03/28/2018 479876 6 104 M Repair broken emergency lighting
417081 03/28/2018 479878 6 104B M Secure hanging grill on exhaust fan in bathroom
417083 03/28/2018 479882 6 105 M Replace missing ceiling tiles
417084 03/28/2018 479884 6 105 M Secure fire extinguisher mounting bracket to wall (bracket has pulled out of wall)
417085 03/28/2018 479886 6 105 M Secure loose faucet to sink
417086 03/28/2018 479888 6 105 M Repair or replace broken emergency light
417074 03/28/2018 479864 4 411 O Remove and prohibit flammable curtains on cabinets
417056 03/28/2018 479826 4 430 O Remove and prohibit hanging paper and decorations from ceiling
255052 03/28/2018 131156 1 0000 N/A No violations observed
255053 03/28/2018 131159 2 0000 N/A No violations observed
255054 03/28/2018 131161 3 0000 N/A No violations observed
255055 03/28/2018 131163 4 0000 N/A No violations observed
255056 03/28/2018 131165 6 0000 N/A No violations observed
387144 02/21/2017 415270 1 115 M Repair rusty areas and leaking AHU system to ensure it operates as designed
401566 02/21/2017 446415 2 227 M Adjust exterior door to latch properly for PE storage room
401561 02/21/2017 446405 3 310 M Replace missing ceiling tiles
401563 02/21/2017 446409 3 315 M Repair light fixture in flammable storage room to work properly
401547 02/21/2017 446376 4 404 M Determine cause of water damaged ceiling tiles and replace tiles
401551 02/21/2017 446384 4 411A M Replace broken ceramic tile on wall under light switch in bathroom
401553 02/21/2017 446388 4 422C M Determine cause of water damaged ceiling tiles and replace tiles in bathroom
401556 02/21/2017 446394 4 425B M Anchor toilet to floor
401555 02/21/2017 446392 4 427C M Secure exhaust fan grille to ceiling
401558 02/21/2017 446399 4 436 M Provide current inspection log for hot water heater
401548 02/21/2017 446378 4 408 O Remove and prohibit air freshener adjacent to teacher desk
401549 02/21/2017 446380 4 410 O Eliminate brown extension cord with multiple outlet end under computer stations or replace with a surge protector
401564 02/21/2017 446411 4 417 O Keep door to custodial room locked and latched to prohibit student access - located outside exit doors and behind girls bathroom
401554 02/21/2017 446390 4 431 O Remove or tape down rolled edge of area rug to eliminate trip hazard (X2)
401562 02/21/2017 446407 2 202 MS Provide current inspection tag for fire extinguisher
401565 02/21/2017 446413 2 253 MS Replace missing fire extinguisher in corridor adjacent to custodial room 2-217
401557 02/21/2017 446396 4 423 MS Provide current inspection tag for fire extinguisher adjacent to sink counter
401560 02/21/2017 446403 4 435 MS Secure safety pin and provide current inspection tag for fire extinguisher in corridor adjacent to 4-427
401559 02/21/2017 446401 4 439 MS Provide current inspection tag for fire extinguisher in corridor adjacent to 4-408
401550 02/21/2017 446382 4 409 OS Relocate storage adjacent to exterior door to maintain safe egress
401552 02/21/2017 446386 4 411 OS Remove and prohibit use of toaster oven
387103 12/01/2016 415183 3 312 M Replace missing insulation on chilled water lines
376918 04/28/2016 393158 00 0000 C Modify or improve drainage to eliminate standing water on bus loop pavement west of building 4
376869 03/28/2016 393054 00 0000 M Clean out all rain gutters and downspouts on campus. Weeds growing in gutters and on building 3 roof
387107 03/28/2016 415192 00 0000 M Provide hurricane anchorage for propane tank west of building 3
387111 03/28/2016 415200 00 0000 M Repair uneven concrete walk between buildings 3 and 4
194057 03/28/2016 20581 00 9599 M Turn barbs down on all fencing
387145 03/28/2016 415272 1 114 M Determine cause of water damaged ceiling tiles and replace tiles
387143 03/28/2016 415268 1 8087 M Remove wasp nest on fire alarm horn strobe on exterior wall at 1-115
387097 03/28/2016 415171 2 224 M Secure loose AC vent cover adjacent to corridor door
387098 03/28/2016 415173 2 225 M Secure hanging heat detector
387099 03/28/2016 415175 2 233 M Make exterior landing level with interior floor
387014 03/28/2016 414987 2 233 M Replace worn non-slip surface for ramp
387100 03/28/2016 415177 2 243 M Repair broken accessible door control button on wall in corridor
387102 03/28/2016 415181 3 312 M Repair clogged floor drain
387108 03/28/2016 415194 3 321 M Determine cause of water damaged ceiling tiles and replace tiles
387109 03/28/2016 415196 3 325 M Secure loose base on wall
387118 03/28/2016 415215 4 403 M Secure loose base on wall adjacent to computers
387120 03/28/2016 415221 4 403 M Provide cover on exposed electrical junction box at missing clock
387116 03/28/2016 415211 4 404 M Determine cause of water damaged ceiling tiles adjacent to window and replace tiles
387121 03/28/2016 415223 4 409 M Provide type K fire extinguisher adjacent to stove, remove ABC type fire extinguisher
387122 03/28/2016 415225 4 411 M Determine cause of water damaged ceiling tiles and replace tiles
387125 03/28/2016 415231 4 421 M Repair emergency lighting
387128 03/28/2016 415237 4 423 M Replace missing cabinet
387135 03/28/2016 415252 4 424C M Determine cause of water damaged ceiling tiles and replace tiles
387129 03/28/2016 415239 4 425 M Repair loose threshold
387130 03/28/2016 415242 4 425 M Repair uneven concrete at exterior door to allow door to close properly
387134 03/28/2016 415250 4 428C M Anchor toilet to floor
387131 03/28/2016 415244 4 433 M Adjust door closer on exterior door to control speed of closing door
387114 03/28/2016 415207 4 9599 M Replace missing clean out cover adjacent to exterior door of 4-408
387142 03/28/2016 415266 4 9599 M Repair uneven concrete at exterior door of 4-430
387138 03/28/2016 415258 6 101 M Mount fire extinguisher at maximum five feet above floor
387140 03/28/2016 415262 6 104 M Repair emergency lighting
387139 03/28/2016 415260 6 105 M Secure loose base on wall
387141 03/28/2016 415264 6 9599 M Provide chain (lock is on fence) for fence enclosure at 6-190
387105 03/28/2016 415188 3 315 O Replace bulbs in light fixture
387104 03/28/2016 415185 3 316 O Prohibit running electrical cord under door
387101 03/28/2016 415179 3 318 O Maintain clear access to emergency eye wash - shower
387136 03/28/2016 415254 6 101 O Relocate cabinet to allow view of emergency escape sign at window
387137 03/28/2016 415256 6 101 O Remove storage from stove burners
387110 03/28/2016 415198 3 301 MS Adjust exterior corridor door to latch properly
387119 03/28/2016 415219 4 403 MS Adjust exterior door to latch properly
387115 03/28/2016 415209 4 404 MS Adjust exterior door to latch properly
387113 03/28/2016 415204 4 412 MS Adjust exterior door to latch properly
387124 03/28/2016 415229 4 413 MS Remove storage from mechanical room
387112 03/28/2016 415202 4 417 MS Replace missing fire extinguisher
387133 03/28/2016 415248 4 430 MS Adjust exterior door to latch properly
387132 03/28/2016 415246 4 435 MS Replace missing fire extinguisher adjacent to 4-433
387106 03/28/2016 415190 2 215 OS Remove storage from mechanical room
387123 03/28/2016 415227 4 413 OS Remove storage from mechanical room
387127 03/28/2016 415235 4 421 OS Remove and prohibit use of toaster oven
387126 03/28/2016 415233 4 421C OS Prohibit hanging curtain over bathroom door to maintain clear egress access
364660 12/02/2015 366472 3 312 M Repair leaking plumbing from cast iron fitting on booster pump plumbing. Water is leaking on pump and pump casing is rusting
376872 05/15/2015 393060 00 0000 M Repair or replace broken LB for TV cable at base of ITV tower
376912 05/15/2015 393146 00 0000 M Repair irrigation system south of 3-311. Reset valve box and fill hole
364610 05/15/2015 366367 2 213 M Repair exhaust fan in bathroom
364611 05/15/2015 366369 2 214 M Repair exhaust fan in bathroom
364654 05/15/2015 366459 2 239B M Repair exhaust fan in bathroom
364655 05/15/2015 366461 2 239C M Repair exhaust fan in bathroom
376878 05/15/2015 393073 4 419 M Secure faucet to sink
364653 05/08/2015 366457 00 0000 M Seal open joints in brick all around buildings 1-4
376919 05/08/2015 393160 00 0000 M Repair or replace OUT OF SERVICE fire hydrant south of Kitchen
376908 05/08/2015 393138 1 116 M Adjust doors to latch properly
364613 05/08/2015 366374 2 203 M Repair exhaust fan in bathroom
364614 05/08/2015 366376 2 204 M Repair exhaust fan in bathroom
376862 05/08/2015 393040 2 204 M Repair OUT OF ORDER toilet
376914 05/08/2015 393150 2 205B M Adjust door to latch properly
376863 05/08/2015 393042 2 213 M Repair leaking toilet supply line
376915 05/08/2015 393152 2 236D M Repair light fixture, not working
376865 05/08/2015 393046 2 239B M Repair OUT OF ORDER toilet
376916 05/08/2015 393154 3 301 M Adjust rear door to latch properly
376864 05/08/2015 393044 3 310A M Determine cause of water damaged ceiling tiles and replace tiles
376870 05/08/2015 393056 3 313 M Panel F breaker 22 tripped. Repair circuit
376871 05/08/2015 393058 3 313 M Repair panel F to latch
376917 05/08/2015 393156 3 324 M Replace missing vinyl floor tile at rear door
376910 05/08/2015 393142 3 326 M Adjust corridor doors to east and west to latch properly
376894 05/08/2015 393107 4 0000 M Exterminate ants in classrooms in building 4
376897 05/08/2015 393113 4 111A M Repair exhaust fan in bathroom
376898 05/08/2015 393115 4 111B M Determine cause of water damaged ceiling tiles and replace tiles
376893 05/08/2015 393104 4 408 M Eliminate rats from room
376895 05/08/2015 393109 4 409 M Determine cause of water damaged ceiling tiles and replace tiles
376896 05/08/2015 393111 4 409 M Replace leaking faucet
376899 05/08/2015 393119 4 416 M Secure handicapped grab rail to wall
376900 05/08/2015 393121 4 417 M Cover openings in wall where faucet supply lines come through wall
376879 05/08/2015 393075 4 419 M Repair leaking supply line for 1st urinal
376880 05/08/2015 393077 4 419 M Fill opening around escutcheon at handicapped toilet to provide impervious wall finish
376907 05/08/2015 393136 4 422 M Adjust rear door to latch properly
376909 05/08/2015 393140 4 422 M Secure loose base along wall between closet and bathroom
376905 05/08/2015 393132 4 423B M Secure handicapped grab rail to wall
376906 05/08/2015 393134 4 425 M Determine cause of water damaged ceiling tiles and replace tiles
376881 05/08/2015 393079 4 425B M Anchor toilet to floor
376887 05/08/2015 393091 4 426C M Repair exhaust fan in bathroom
376877 05/08/2015 393071 4 428 M Repair or replace electrical outlet below marker board, no power. See teacher
376886 05/08/2015 393089 4 428C M Repair exhaust fan in bathroom
376875 05/08/2015 393067 4 430C M Repair exhaust fan in bathroom
376876 05/08/2015 393069 4 430C M Repair leaking toilet supply line
376902 05/08/2015 393125 4 431C M Repair sticky latch on door knob
376903 05/08/2015 393128 4 431C M Secure handicapped grab rail to wall
376883 05/08/2015 393083 4 432C M Determine cause of water damaged ceiling tiles and replace tiles in bathroom
376884 05/08/2015 393085 4 432C M Repair exhaust fan in bathroom
376885 05/08/2015 393087 4 432C M Secure loose faucet
376882 05/08/2015 393081 4 433C M Repair or replace faucet
376873 05/08/2015 393062 6 0000 M Provide chain and lock on gate of fencing around A-C equipment at west side of building
376866 05/08/2015 393048 6 101A M Repair exhaust fan in bathroom
376867 05/08/2015 393050 6 102B M Repair exhaust fan in bathroom
376890 05/08/2015 393098 6 103 M Remove damaged pencil sharpener at window
376868 05/08/2015 393052 6 104B M Repair exhaust fan in bathroom
376891 05/08/2015 393100 6 105 M Secure drinking fountain to sink
376861 05/08/2015 393038 00 0 O No access was available to 2-231. Please provide access to this room during the report review meeting
376904 05/08/2015 393130 4 421 O Remove and prohibit excessive flammable decorations hung from ceiling. Limit amount hung from ceiling to 12 sheets of standard sized sheets
376889 05/08/2015 393096 6 102C O Store old loose light tubes in box
376892 05/08/2015 393102 6 190 MS Provide current inspection tag for fire extinguisher
376913 05/08/2015 393148 2 212 OS Prohibit hold open device on fire door from bathroom vestibule to Kitchen
376874 05/08/2015 393065 4 426 OS Maintain clear aisle to rear exit
376901 05/08/2015 393123 4 429 OS Maintain clear aisle to rear exit
376888 05/08/2015 393093 6 101 OS Keep area clear at emergency escape window
364625 02/19/2015 366399 00 0000 M Repair uneven sidewalk from building 4 to building 6
364620 02/19/2015 366388 1 114 M Repair or replace torn laminate on cabinet at door
364623 02/19/2015 366394 1 115 M Repair leaking air handler
364592 02/19/2015 366332 6 0000 M Repair exhaust fans in all bathrooms in building 6
364618 05/21/2014 366384 1 103 M Replace left GFCI outlet that will not trip
364612 05/21/2014 366371 2 213 M Repair leaking toilet supply line
364656 05/21/2014 366463 2 232 M Determine cause of water damaged ceiling tiles and replace tiles
364600 05/21/2014 366348 3 303A M Determine cause of water damaged ceiling tiles and replace tiles
364666 05/21/2014 366486 3 326 M Center exit sign over correct door leaf in corridor
364606 05/21/2014 366360 4 411 M Repair damaged wall at rear door
364641 05/21/2014 366431 4 417 M Repair damaged wall finish
364616 05/21/2014 366380 4 425B M Repair leaking toilet supply line
364604 05/21/2014 366356 4 428C M Repair flush valve that leaks
364639 05/21/2014 366427 4 432C M Determine cause of water damaged ceiling tiles and replace tiles
364632 05/21/2014 366413 6 190 MS Provide current inspection tag for fire extinguisher
364649 05/16/2014 366449 00 0000 M Repair leaking plumbing. Ground is saturated south of 3-313 at valve box in ground
364646 05/16/2014 366442 1 0000 M Eliminate bees nest on soffit outside of 1-112
364617 05/16/2014 366382 1 101 M Provide fire alarm log book at fire alarm panel
364619 05/16/2014 366386 1 103 M Determine cause of water damaged ceiling tiles and replace tiles
364621 05/16/2014 366390 1 114 M Determine cause of water damaged ceiling tiles and replace tiles
364622 05/16/2014 366392 1 117 M Secure loose grid piece in ceiling and replace missing ceiling tiles
364650 05/16/2014 366451 2 0000 M Lock electrical panel in corridor outside of 2-217. Square D panel
364659 05/16/2014 366470 2 0000 M 1 half inch PVC pipes mark a box in ground outside of 2-209. Ends are sharp and broken. Install caps on pipes or remove pipes
364609 05/16/2014 366365 2 205A M Repair exhaust fan in bathroom. Wrong room number
364662 05/16/2014 366476 2 215 M Repair or replace lock cylinder. Key will not go in
364607 05/16/2014 366361 2 217 M Attach cover to fire alarm cabinet. Missing screws
364652 05/16/2014 366455 2 220 M Determine cause of water damaged ceiling tiles and replace tiles
364664 05/16/2014 366482 2 224 M Adjust door to exterior to latch properly
364657 05/16/2014 366466 2 224 M Repair door to open and close properly, drags on floor
364658 05/16/2014 366468 2 227 M Determine cause of water damaged ceiling tiles and replace tiles
364624 05/16/2014 366396 2 236A M Determine cause of water damaged ceiling tiles and replace tiles
364651 05/16/2014 366453 2 242 M Determine cause of water damaged ceiling tiles and replace tiles and replace missing tiles
364615 05/16/2014 366378 2 242 M Replace several GFCI outlets at sinks that will not trip
364647 05/16/2014 366444 3 0000 M Replace cover for 2 inch PVC cleanout outside of 3-311
364640 05/16/2014 366429 3 301A M Determine cause of water damaged ceiling tiles and replace tiles
364602 05/16/2014 366352 3 301C M Repair exhaust fan in bathroom
364601 05/16/2014 366350 3 303A M Repair exhaust fan in bathroom
364598 05/16/2014 366344 3 305 M Replace GFCI outlet that will not trip
364597 05/16/2014 366342 3 306 M Adjust door to exterior to latch properly
364595 05/16/2014 366338 3 309 M Repair damaged wall and secure loose ceramic base tile at toilet to provide impervious wall finish
364661 05/16/2014 366474 3 312 M Close 2 open junction boxes at door adjacent to floor
364648 05/16/2014 366446 3 314 M Provide certification that all student occupied spaces have emergency lights and all are operable. Last certification dated 6-15-11
364629 05/16/2014 366407 4 0000 M Eliminate bees nest on soffit outside of 4-422
364626 05/16/2014 366401 4 0000 M Replace cover for 2 inch PVC cleanout outside of 4-428
364588 05/16/2014 366324 4 406 M Adjust door to exterior to latch properly
364636 05/16/2014 366421 4 407 M Determine cause of water damaged ceiling tiles and replace tiles
364637 05/16/2014 366423 4 407 M Adjust rear door to latch properly
364638 05/16/2014 366425 4 407 M Remove pencil sharpener without cover at rear door
364586 05/16/2014 366320 4 408 M Secure loose power pole
364589 05/16/2014 366326 4 416A M Repair leaking supply line for 5th toilet
364643 05/16/2014 366435 4 419A M Repair leaking supply lines for urinals 2, 4, and 5
364644 05/16/2014 366437 4 419A M Caulk all urinals to wall
364645 05/16/2014 366439 4 419A M Repair leaking supply line for toilet 2
364642 05/16/2014 366433 4 420 M Secure loose ground on 3M box labeled 4188 Protected Entrance Terminal
364635 05/16/2014 366419 4 421C M Repair leaking toilet supply line
364605 05/16/2014 366358 4 423 M Adjust door to exterior to latch properly
364627 05/16/2014 366403 4 427 M Adjust door to exterior to latch properly
364628 05/16/2014 366405 4 427 M Repair or replace leaking faucet
364633 05/16/2014 366415 4 433 M Remove pencil shsrpener without cover at sink
364634 05/16/2014 366417 4 433 M Repair or replace leaking faucet
364584 05/16/2014 366316 4 434 M Adjust door to exterior to latch properly
350183 05/16/2014 334582 6 0000 M Clean rain gutters - east side of building
364590 05/16/2014 366328 6 101 M Determine cause of water damaged ceiling tiles and replace tiles
364591 05/16/2014 366330 6 101 M Remove damaged pencil sharpener adjacent to range
364593 05/16/2014 366334 6 103 M Replace GFCI outlet to right of sink that will not trip
364594 05/16/2014 366336 6 105A M Repair leaking toilet supply line
364631 05/16/2014 366411 6 191 M Secure loose top right ground on ground bar to grounding lug
364583 05/16/2014 366314 00 0 O No access was available to 2-231. Please provide access to this room during the report review meeting
364663 05/16/2014 366480 2 224 O Prohibit plugging surge protector into surge protector at teachers station
364587 05/16/2014 366322 4 404 O Remove and prohibit attaching paper to blinds. Paper is acceptable on walls, windows and string lines against walls
364603 05/16/2014 366354 4 418 MS Adjust door to corridor to latch properly
364608 05/16/2014 366363 2 216 OS Prohibit hold open device on corridor door
364599 05/16/2014 366346 3 305 OS Maintain 3 foot clear aisle to rear exit
364596 05/16/2014 366340 3 307 OS Maintain 3 foot clear aisle to rear exit
364665 05/16/2014 366484 3 313 OS Remove loose light tubes stored in electrical room. Store in box in custodial receiving or custodial closet
364630 05/16/2014 366409 4 403 OS Maintain 3 foot clear aisle to rear exit
364585 05/16/2014 366318 4 408 OS Maintain 3 foot clear aisle to rear exit
326806 02/20/2014 284153 2 215 M Provide current state inspection tag for hot water storage tank in excess of 120 gallons
294734 02/20/2014 213652 00 0000 C Provide suitable area for storage and recharging floor cleaning machines
350121 05/02/2013 334456 2 217 M Repair door to latch properly
350123 05/02/2013 334460 2 224 M Adjust door closer on exterior door to control speed of closing door
350124 05/02/2013 334462 2 224 M Anchor metal shelving adjacent to 2-222 to wall
350125 05/02/2013 334464 2 232 M Determine cause of water damaged ceiling tiles and replace tiles
350127 05/02/2013 334468 2 236A M Determine cause of water damaged ceiling tiles and replace tiles
350119 05/02/2013 334452 2 242 M Repair exterior door to close properly
350120 05/02/2013 334454 2 242 M Replace missing floor tile
350132 05/02/2013 334478 3 301 M Adjust door closers (x2) to control speed of closing doors
350130 05/02/2013 334474 3 306 M Anchor tall shelving adjacent to exterior door to wall
350134 05/02/2013 334482 3 314 M Provide certification that all student occupied spaces have emergency lights and all are operable, certificate is expired
350133 05/02/2013 334480 3 315 M Adjust door closer to control speed of closing door
350128 05/02/2013 334470 3 318 M Adjust flow of emergency eye wash
350129 05/02/2013 334472 3 322 M Adjust door closer on exterior door to control speed of closing door
350173 05/02/2013 334562 4 401 M Adjust door closer on exterior door to control speed of closing door
350174 05/02/2013 334564 4 404 M Adjust door closer on exterior door to control speed of closing door
350170 05/02/2013 334556 4 408 M Adjust door closer on corridor door to control speed of closing door
350164 05/02/2013 334544 4 409 M Adjust door closer on exterior door to control speed of closing door
350160 05/02/2013 334536 4 411 M Repair deteriorated wall finish adjacent to exterior door
350161 05/02/2013 334538 4 411 M Determine cause of water damaged ceiling tiles and replace tiles
350167 05/02/2013 334550 4 412 M Determine cause of water damaged ceiling tiles and replace tiles
350157 05/02/2013 334530 4 414 M Secure loose base on wall at exterior door
350158 05/02/2013 334532 4 414 M Adjust exterior door to close and latch properly
350155 05/02/2013 334526 4 421 M Adjust door closer on exterior door to control speed of closing door
350136 05/02/2013 334487 4 422 M Repair exterior door to close and latch properly
350154 05/02/2013 334524 4 423 M Repair exterior door to close and latch properly
350152 05/02/2013 334519 4 428 M Repair corridor door to close and latch properly
350138 05/02/2013 334491 4 428C M Secure exhaust fan in bathroom
350139 05/02/2013 334493 4 428C M Anchor toilet to floor
350150 05/02/2013 334515 4 429 M Repair corridor door to close and latch properly
350151 05/02/2013 334517 4 429 M Adjust door closer on exterior door to control speed of closing door
350141 05/02/2013 334497 4 430 M Repair doors (x2) to close and latch properly
350149 05/02/2013 334513 4 431 M Repair exterior door to close and latch properly
350142 05/02/2013 334499 4 432C M Anchor toilet to floor
350143 05/02/2013 334501 4 432C M Repair leaking toilet
350148 05/02/2013 334511 4 433 M Determine cause of water damaged ceiling tiles and replace tiles
350146 05/02/2013 334507 4 434 M Repair exterior door to close and latch properly
350176 05/02/2013 334568 4 9599 M Repair uneven concrete sidewalk north of 4-439 exterior doors
350178 05/02/2013 334572 6 101 M Repair emergency lighting
350179 05/02/2013 334574 6 103 M Replace missing base on wall at entrance door
350180 05/02/2013 334576 6 103 M Repair emergency lighting
350182 05/02/2013 334580 6 104 M Repair emergency lighting
350177 05/02/2013 334570 6 9599 M Repair uneven concrete sidewalk at 6-101
350137 05/02/2013 334489 4 0000 O Relocate flags in corridors to hang flush against walls
350175 05/02/2013 334566 4 402 O Remove and prohibit air freshener
350168 05/02/2013 334552 4 405 O Relocate string line to hang no more than 2 inches from wall
350171 05/02/2013 334558 4 406 O Prohibit plugging refrigerator into extension cord - plug directly into permanent electrical outlet
350172 05/02/2013 334560 4 406 O Prohibit plugging extension cord into surge protector
350165 05/02/2013 334546 4 409 O Remove storage from stove burners
350162 05/02/2013 334540 4 409 O Relocate string line to hang no more than 2 inches from wall
350163 05/02/2013 334542 4 409 O Remove and prohibit (flammable) plastic grass decoration
350166 05/02/2013 334548 4 412 O Prohibit plugging surge protector into surge protector at computers
350135 05/02/2013 334485 4 418 O Prohibit plugging surge protectors into surge protector box (adjacent to bookshelves)
350153 05/02/2013 334522 4 425 O Relocate string line to hang no more than 2 inches from wall
350145 05/02/2013 334505 4 432 O Prohibit (flammable) blue plastic sheets covering shelves
350147 05/02/2013 334509 4 433 O Prohibit plugging surge protector into surge protector adjacent to teachers desk
350181 05/02/2013 334578 6 104 O Prohibit white 13A extension cord or replace with minimum 15A single outlet cord
350122 05/02/2013 334458 2 233 C Verify or provide non-slip surface for ramp adjacent to 2-224
350131 05/02/2013 334476 3 304 OS Maintain clear aisle to exterior exit
350169 05/02/2013 334554 4 408 OS Maintain clear aisle to exterior exit
350159 05/02/2013 334534 4 411 OS Maintain clear aisle to exterior exit
350156 05/02/2013 334528 4 414 OS Maintain clear aisle to exterior exit
350184 05/02/2013 334584 6 190 CS Provide fire extinguisher in telecommunications room located on east side of 6-103B
350126 05/02/2013 334466 2 238A FS Secure hanging heat detector
326839 02/12/2013 284224 2 205A M Repair latches for panels LK & LKA in kitchen
326849 02/12/2013 284245 2 219 M Provide dated flame resistance label on stage curtain
350144 02/12/2013 334503 4 0000 M Repair exhaust fans in bathrooms
326793 02/12/2013 284120 4 416A M Repair exhaust fan in bathroom
326834 02/12/2013 284214 2 230 O Provide dated flame resistance label on CCTV or Studio curtain or remove curtain
326837 02/12/2013 284220 00 0000 C Provide protection for gas line on wall outside of custodial receiving adjacent to door
326805 03/27/2012 284151 00 0000 M Eliminate rats and mice from buildings
326797 03/27/2012 284130 00 0000 M Provide lock on gate of fencing around transformers adjacent to portables
326807 03/27/2012 284155 00 0000 M Replace cover for box in grassed area adjacent to 6-191
326801 03/27/2012 284141 00 0000 M Replace cover for cleanout outside of 4-404
326791 03/27/2012 284116 1 115 M Secure loose junction box to A/C return duct
326804 03/27/2012 284149 1 123A M Determine cause of water damaged ceiling tiles and replace tiles
326838 03/27/2012 284222 2 205A M Replace GFCI outlet adjacent to hand sink that won't trip
326848 03/27/2012 284243 2 220 M Anchor shelving to wall
326836 03/27/2012 284218 2 224 M Determine cause of water damaged ceiling tiles and replace tiles
326796 03/27/2012 284128 2 229 M Eliminate glue board with dead mouse
326832 03/27/2012 284210 2 236 M Repair circuit 24, breaker tripped
326833 03/27/2012 284212 2 236C M Determine cause of water damaged ceiling tiles and replace tiles
326830 03/27/2012 284206 2 242 M Determine cause of water damaged ceiling tiles and replace tiles
326831 03/27/2012 284208 2 242 M Remove broken and uncovered pencil sharpener adjacent to corridor door
326829 03/27/2012 284204 2 244 M Secure loose handicapped grabrail in left stall
326822 03/27/2012 284190 3 302 M Replace missing ceiling tiles
326841 03/27/2012 284228 3 302A M Determine cause of water damaged ceiling tiles and replace tiles
326843 03/27/2012 284232 3 304 M Replace GFCI outlet that won't trip
326845 03/27/2012 284236 3 309 M Repair leaking urinal supply line
326847 03/27/2012 284241 3 313 M Provide schedule for panel DPF
326846 03/27/2012 284239 3 315 M Relocate fire extinguisher to be adjacent to active leaf of door
326844 03/27/2012 284234 3 323 M Repair ceiling grid that is sagging
326799 03/27/2012 284134 4 403 M Attach loose wire mould to wall adjacent to entry
326824 03/27/2012 284194 4 419A M Repair leaking handicapped toilet supply line
326823 03/27/2012 284192 4 420 M Provide listed cover plate inside panel C
326795 03/27/2012 284125 4 422 M Replace broken faucet
326827 03/27/2012 284200 4 429C M Anchor toilet to floor
326794 03/27/2012 284122 4 430C M Secure loose handicapped grabrail
326828 03/27/2012 284202 4 431 M Secure loose base along wall adjacent to bathroom
326820 03/27/2012 284182 4 434C M Repair leaking toilet supply line
326798 03/27/2012 284132 6 101 M Determine cause of water damaged ceiling tiles and replace tiles
326817 03/27/2012 284176 6 102 M Replace GFCI outlet that won't trip
326818 03/27/2012 284178 6 102 M Secure loose faucet to sink
326815 03/27/2012 284172 6 102B M Repair exhaust fan in bathroom
326813 03/27/2012 284167 6 103 M Repair emergency lighting
326814 03/27/2012 284170 6 103 M Secure loose base along wall
326812 03/27/2012 284165 6 103A M Repair exhaust fan in bathroom
326811 03/27/2012 284163 6 104 M Repalce missing sign indicating emergency escape window
326808 03/27/2012 284157 6 104B M Repair exhaust fan in bathroom
326809 03/27/2012 284159 6 104B M Repair leaking toilet supply line
326816 03/27/2012 284174 6 105A M Repair exhaust fan in bathroom
326790 03/27/2012 284113 00 0 O No access was available to 1-102, 1-107, 2-223, 3-307 and 3-317. Please provide access to these rooms during the report review meeting.
326792 03/27/2012 284118 1 108 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
326821 03/27/2012 284188 3 301 O Remove and prohibit hanging paper on blinds
326800 03/27/2012 284139 4 405 O Remove and prohibit hanging paper on string line
326802 03/27/2012 284143 4 407 O Prohibit plugging surge protector into surge protector
326819 03/27/2012 284180 4 433 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
194056 03/27/2012 20477 00 9500 C Provide covered walkway to portables. Portables demolished
326842 03/27/2012 284230 3 326 MS Adjust doors at both ends of corridor to latch properly
326835 03/27/2012 284216 2 Mezz OS Prohibit storing used light tubes in mechanical room. Store in custodian closet, custodial receiving or other storage room
326840 03/27/2012 284226 3 318 OS Prohibit storage of gas powered equipment, (leaf blower)
326803 03/27/2012 284146 4 413 OS Do not store used light tubes in mechanical room. Store in custodial closet, custodial receiving or other storage room
326825 03/27/2012 284196 4 423 OS Maintain clear aisle to exit to exterior
326810 03/27/2012 284161 6 104 OS Keep area clear at emergency escape window
326826 03/27/2012 284198 4 423C FS Secure hanging heat detector
255057 03/27/2012 131167 P 2140 N/A No violations observed
255058 03/27/2012 131169 P 697 N/A No violations observed
303416 10/07/2011 232390 1 0000 M Fill voids where asphalt meets concrete landing into building 1
194116 10/07/2011 20571 P 2140 M Modify existing foundations and anchorage to comply with engineering requirements
323479 05/06/2011 276261 2 212 M Determine cause of water damaged ceiling tiles and replace tiles
323485 05/06/2011 276273 2 216 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to stage
323483 05/06/2011 276271 2 219 M Provide dated flame resistance label on stage curtain
323493 05/06/2011 276293 2 232 M Determine cause of water damaged ceiling tiles and replace tiles
323497 05/06/2011 276302 2 236 M Determine cause of water damaged ceiling tiles and replace tiles
323498 05/06/2011 276304 2 236A M Determine cause of water damaged ceiling tiles and replace tiles
323502 05/06/2011 276312 2 236B M Determine cause of water damaged ceiling tiles and replace tiles
323501 05/06/2011 276310 2 236D M Repair light fixture, lights do not turn on
323495 05/06/2011 276297 2 238A M Repair emergency lighting
323457 05/06/2011 276204 2 242A M Secure loose ceiling tile
323482 05/06/2011 276268 2 243 M Anchor toilet to floor
323481 05/06/2011 276264 2 8088 M Secure loose door hook on exterior wall adjacent to 2-212
323552 05/06/2011 276415 3 303 M Adjust door closer on exterior door to control speed of closing door
323478 05/06/2011 276257 3 312 M Secure exposed wires on unit above AHU-2, adjacent to duct detector
323476 05/06/2011 276255 3 314 M Repair door to close and latch properly
323475 05/06/2011 276253 3 315 M Repair door to close and latch properly
323504 05/06/2011 276314 4 403 M Repair exterior door to close and latch properly
323524 05/06/2011 276356 4 413 M Prohibit storage of expired type "K" fire extinguisher
323529 05/06/2011 276369 4 424C M Anchor toilet to floor
323551 05/06/2011 276413 4 425 M Repair broken handle on drinking fountain
323550 05/06/2011 276411 4 425B M Anchor toilet to floor
323549 05/06/2011 276409 4 427 M Repair exterior door to close and latch properly
323548 05/06/2011 276407 4 429 M Anchor wooden shelving (x3) to wall
323544 05/06/2011 276399 4 431 M Determine cause of water damaged ceiling tiles and replace tiles
323534 05/06/2011 276380 4 432 M Repair exterior door to open properly
323540 05/06/2011 276391 4 433 M Determine cause of water damaged ceiling tiles and replace tiles
323539 05/06/2011 276388 4 434 M Repair exterior door to close and latch properly
303429 05/06/2011 232417 6 0000 M Repair exhaust fans in bathrooms in building 6
323555 05/06/2011 276421 6 104 M Repair emergency lighting
323556 05/06/2011 276425 6 104 M Secure loose base on wall
323558 05/06/2011 276429 6 105 M Repair emergency lighting
323563 05/06/2011 276441 P 2140 M Verify that wood panels used on interior walls is flame retardant/treated and has been approved for use
323487 05/06/2011 276280 P 697 M Determine cause of water damaged ceiling tiles and replace tiles
323496 05/06/2011 276299 2 228 O No access was available to this room. Please be prepared to access this room during the report review meeting
323554 05/06/2011 276419 3 306 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
323553 05/06/2011 276417 3 307 O No access was available to this room. Please be prepared to access this room during the report review meeting
323506 05/06/2011 276319 4 402 O Remove and prohibit air freshener
323507 05/06/2011 276321 4 402 O Prohibit running extension cord under carpet
323508 05/06/2011 276323 4 402 O Remove and prohibit excessive papers on walls, limit coverage to 20% of each wall, prohibit hanging papers from ceiling
323509 05/06/2011 276325 4 404 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
323510 05/06/2011 276327 4 405 O Remove and prohibit papers hanging from ceiling
323512 05/06/2011 276331 4 406 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
323517 05/06/2011 276343 4 406B O Keep storage away from heat detector
323513 05/06/2011 276333 4 408 O Prohibit brown 13A extension cord running under carpet @ teacher's desk or replace with minimum 15A cord, prohibit cord under carpet
323515 05/06/2011 276341 4 408 O Remove and prohibit papers hanging from ceiling and in front of windows
323520 05/06/2011 276347 4 409 O Remove and prohibit papers hanging from ceiling
323522 05/06/2011 276353 4 411 O Remove and prohibit paper covering window in (corridor) door
323532 05/06/2011 276376 4 426B O Maintain storage closet in an orderly manner
323541 05/06/2011 276393 4 433 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
323543 05/06/2011 276395 4 433 O Remove and prohibit papers hanging from ceiling
323537 05/06/2011 276386 4 434 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
323514 05/06/2011 276336 00 0000 C Provide exterior signage indicating property address
194064 05/06/2011 20578 2 205 C Provide magnetic release hold open device for fire door at dishwash room to make door close upon initiation of fire alarm (NFPA 96 kitchen hood)
294736 05/06/2011 213656 2 216 C Provide magnetic release hold open device for fire doors at corridor
323500 05/06/2011 276306 2 236D F Secure hanging heat detector
323474 05/06/2011 276251 2 242B F Secure hanging heat detector
323492 05/06/2011 276282 P 2140 MS Immediately remove screws from stair door to maintain egress access
323486 05/06/2011 276278 2 227 OS Prohibit storage of flammable materials (field marker paint)
323505 05/06/2011 276317 4 402 OS Maintain clear aisle to exit
323511 05/06/2011 276329 4 408 OS Prohibit hold open devices on fire door
323528 05/06/2011 276363 4 421C OS Prohibit hanging curtain over bathroom door to maintain clear aisle to exit
323525 05/06/2011 276360 4 422 OS Prohibit hold open devices on fire door
323530 05/06/2011 276372 4 424 OS Maintain clear aisle to (exterior) exit
323536 05/06/2011 276382 4 432 OS Relocate bookshelves @ corridor door to maintain clear aisle to exit
323557 05/06/2011 276427 6 105 OS Keep area clear at emergency escape window
323559 05/06/2011 276431 1 101 FS Make repairs as noted on report at fire alarm panel
303434 02/25/2011 232427 00 0000 M Repair lift station. Wire rack loose and hanging by cord. Rack prevents lid from shutting. Install rack and lock lid. Fill void between body of lift station and concrete lid
303393 02/25/2011 232336 00 0000 M Recaulk joints on brick on exterior walls of all buildings
303428 02/25/2011 232415 4 0000 M Repair uneven concrete through out outside play area
303392 04/05/2010 232334 00 0000 M Provide chain and lock of gate of fencing around propane gas tank south of 2-210
303417 04/05/2010 232392 2 0000 M Repair uneven concrete walkway to portables adjacent to 2-226
253662 04/05/2010 128138 2 205 M Provide current inspection tag for kitchen steamer
303413 04/05/2010 232384 2 205A M Replace broken ceramic floor tile at floor drain
303412 04/05/2010 232381 2 220 M Determine cause of water damaged ceiling tiles and replace tiles
303396 04/05/2010 232342 2 230 M Provide cover on old clock box behind curtain
303395 04/05/2010 232340 2 230A M Determine cause of water damaged ceiling tiles and replace tiles
303411 04/05/2010 232379 2 236A M Determine cause of water damaged ceiling tiles and replace tiles
303397 04/05/2010 232344 2 242 M Secure loose air conditioning grill
303402 04/05/2010 232360 2 243 M Secure loose cover on exhaust fan in bathroom
303405 04/05/2010 232366 3 302 M Adjust door to latch properly
303410 04/05/2010 232377 3 303A M Determine cause of water damaged ceiling tiles and replace tiles
303403 04/05/2010 232362 3 314 M Provide correct bracket for fire extinguisher
303433 04/05/2010 232425 4 0000 M Remove mold from exterior wall outside of room 4-421
303423 04/05/2010 232404 4 403 M Adjust exterior door to latch properly
303427 04/05/2010 232413 4 409 M Provide cover for exposed TV outlet on demountable wall
303407 04/05/2010 232371 4 411 M Determine cause of water damaged ceiling tiles and replace tiles
303415 04/05/2010 232388 4 416A M Anchor handicapped toilet to floor
303430 04/05/2010 232419 4 419A M Anchor toilet to floor
303419 04/05/2010 232396 4 425B M Determine cause of water damaged ceiling tiles and replace tiles
303422 04/05/2010 232402 4 427C M Anchor toilet to floor
303421 04/05/2010 232400 4 432C M Determine cause of water damaged ceiling tiles and replace tiles
303420 04/05/2010 232398 4 433 M Determine cause of water damaged ceiling tiles and replace tiles
303426 04/05/2010 232410 6 102 M Repair emergency lighting
303408 04/05/2010 232373 P 2140 M Repair damaged interior wall, 2 locations
303424 04/05/2010 232406 P 697 M Repair exhaust fan in bathroom
303394 04/05/2010 232338 00 0 O No access was available to 2-220, 2-223 and 3-307. Please be prepared to access these rooms during the report review meeting.
303431 04/05/2010 232421 00 0000 O Remove and prohibit paper covering windows in doors of classrooms
303399 04/05/2010 232354 2 215 O Replace tubes in light fixture
303418 04/05/2010 232394 3 0000 O Prohibit parking on grass adjacent to 3-307
303400 04/05/2010 232356 2 215 MS Remove storage from mechanical room
303406 04/05/2010 232368 4 411 MS Provide current inspection tag for type K fire extinguisher
303425 04/05/2010 232408 4 435 MS Adjust fire door in corridor adjacent to 4-421 to latch properly
303409 04/05/2010 232375 4 439 MS Provide current inspection tag for fire extinguisher in corridor adjacent to 4-410
303401 04/05/2010 232358 3 301 OS Maintain clear aisle to rear exit
303404 04/05/2010 232364 3 302 OS Prohibit storage of gas powered equipment
303414 04/05/2010 232386 1 101 FS Repair troubles indicated on fire alarm panel
303398 04/05/2010 232347 2 237 FS Provide heat detector in room used for storage
303432 04/05/2010 232423 4 428B FS Secure hanging heat detector
194079 11/10/2009 20609 4 0000 M Repair or replace exterior aluminum sills on windows (sills slope back into building) and recaulk exterior windows
294720 11/10/2009 213622 4 411 M Repair moisture damaged wall finish adjacent to window
294729 11/10/2009 213641 2 230 OS Prohibit running electrical cords under door between CCTV and control room
194078 11/10/2009 20529 3 326 CS Change swing of doors at west end of corridor adjacent to courtyard gates to swing in direction of egress
294730 05/14/2009 213643 2 224 O Eliminate (3) plug electrical outlet adaptor under projector screen
294731 05/14/2009 213645 2 224 O Eliminate 13A extension cords for piano and adjacent to teacher's desk (X2)
294727 05/14/2009 213637 2 230 O Remove and prohibit flammable curtains (X2)
294728 05/14/2009 213639 2 230 O Remove and prohibit combustible residential couch
294706 05/14/2009 213594 2 230 O Prohibit plugging surge protector into surge protector between desks
294704 05/14/2009 213590 3 325 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
294705 05/14/2009 213592 3 325 O Prohibit plugging surge protector into surge protector between desks
294724 05/14/2009 213630 4 402 O Remove and prohibit paper, decorations and lights hanging from ceiling
294722 05/14/2009 213626 4 405 O Prohibit plugging surge protector into surge protector behind teacher's desk
294710 05/14/2009 213602 4 406 O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
294755 05/14/2009 213697 4 418 O Prohibit plugging surge protector into extension cord under computer stations
294751 05/14/2009 213689 4 418 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
294752 05/14/2009 213691 4 418 O Eliminate 13A extension cord - currently plugged into surge protector behind teacher's desk
294739 05/14/2009 213662 4 422 O Prohibit plugging surge protector into surge protector adjacent to teacher's desk
294712 05/14/2009 213606 4 423 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
294738 05/14/2009 213660 4 424 O Prohibit plugging surge protector into surge protector under teacher's desk
294714 05/14/2009 213610 4 425 O Prohibit plugging surge protector into surge protector behind teacher's desk
294750 05/14/2009 213686 4 426 O Eliminate (3) plug electrical outlet adaptor currently plugged into surge protector adjacent to teacher's desk
294715 05/14/2009 213612 4 427 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
294716 05/14/2009 213614 4 427 O Prohibit plugging surge protector into surge protector behind teacher's desk
294717 05/14/2009 213616 4 427 O Eliminate extension cord with multiple outlet end behind teacher's desk
294743 05/14/2009 213670 4 433 O Prohibit plugging surge protector into surge protector behind teacher's desk
294744 05/14/2009 213673 4 433 O Prohibit plugging surge protector into TV cart outlet - plug directly into permanent electrical outlet
294745 05/14/2009 213675 4 433 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
294747 05/14/2009 213680 4 434 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
294749 05/14/2009 213683 4 434 O Eliminate white extension cord with multiple outlet end under computer stations at classroom corner or replace with a surge protector
294758 05/14/2009 213701 6 101 O Eliminate brown 13A extension cords adjacent to emergency window and adjacent to teacher's desk (X2)
294760 05/14/2009 213705 6 103 O Eliminate white extension cord with multiple outlet end under computer stations adjacent to teacher's desk or replace with a surge protector
294737 05/14/2009 213658 6 104 O Prohibit plugging surge protector into surge protector under teacher's desk
294703 05/14/2009 213587 3 317 OS Remove and prohibit use of space heater
294723 05/14/2009 213628 4 405 OS Relocate desk to maintain clear aisle to exterior door
294721 05/14/2009 213624 4 409 OS Relocate storage bin to maintain clear access to exterior door
294719 05/14/2009 213620 4 411 OS Relocate table to maintain clear aisle to exterior door
294741 05/14/2009 213666 4 435 OS Remove desks from corridor adjacent to 4-434
294756 05/14/2009 213699 6 101 OS Remove and prohibit use of toaster in classroom
294733 04/30/2009 213650 2 217 M Replace missing grille for exhaust fan in custodial room
294725 04/30/2009 213632 2 227 M Mount fire extinguisher at maximum five feet above floor adjacent to exterior door
294709 04/30/2009 213600 2 242A M Replace missing ceiling tiles in kiln room
294711 04/30/2009 213604 4 406 M Adjust exterior door to latch properly
294740 04/30/2009 213664 4 418 M Adjust exterior door to latch properly
294713 04/30/2009 213608 4 425B M Determine cause of water damaged ceiling tiles and replace tiles
294742 04/30/2009 213668 4 430 M Adjust exterior door to latch properly
294746 04/30/2009 213677 4 434 M Replace missing ceiling tiles
294726 04/30/2009 213634 2 224 O Remove poster covering maximum occupancy sign
294707 04/30/2009 213596 2 235 O Remove and prohibit combustible beanbag chairs (X2)
294754 04/30/2009 213693 4 418 O Prohibit plugging surge protector into surge protector under computer stations
294718 04/30/2009 213618 4 421B O No access was available to closet. Please be prepared to access this room during the report review meeting.
294701 04/30/2009 213583 1 107 MS Provide current inspection tag for fire extinguisher
294702 04/30/2009 213585 1 114 MS Provide current inspection tag for fire extinguisher
294735 04/30/2009 213654 2 216 OS Prohibit use of wedge to hold fire doors at corridor in open position
294708 04/30/2009 213598 2 235 OS Rearrange tables to maintain 3 ft clear aisle to both exterior doors
194076 04/30/2009 20539 3 318 OS Prohibit recharging golf cart batteries in room
294732 04/30/2009 213648 P 697 OS Remove all storage along ramp
281514 01/14/2009 185477 2 220 M Eliminate rat/mouse infestation
194054 01/14/2009 20560 00 0000 C Modify all emergency lighting so that no room may be left in darkness if single bulb fails
281533 04/23/2008 185517 1 107 M Install fire extinguisher at maximum five feet above floor adjacent to exit
281524 04/23/2008 185497 1 114 M Determine cause of water damaged ceiling tiles and replace tiles
281512 04/23/2008 185473 2 206 M Secure loose door handle
281522 04/23/2008 185495 2 218 M Anchor shelving to wall
281513 04/23/2008 185475 2 220 M Determine cause of water damaged ceiling tiles and replace tiles
281539 04/23/2008 185526 2 224 M Repair hole in wall. See teacher
281505 04/23/2008 185459 2 227 M Install fire extinguisher at maximum five feet above floor adjacent to exit
281517 04/23/2008 185485 2 236A M Determine cause of water damaged ceiling tiles and replace tiles
281519 04/23/2008 185488 2 236A M Anchor shelving to wall
281511 04/23/2008 185471 4 425 M Adjust door to exterior to latch properly
281510 04/23/2008 185469 4 427C M Determine cause of water damaged ceiling tiles and replace tiles
281508 04/23/2008 185465 4 428 M Provide cover on old clock box
281553 04/23/2008 185558 6 103 M Determine cause of water damaged ceiling tiles and replace tiles
281560 04/23/2008 185566 6 104 M Relocate sign indicating emergency escape window to be above file cabinet or relocate file cabinet
281555 04/23/2008 185560 6 104B M Repair exhaust fan in bathroom
281556 04/23/2008 185563 6 105A M Repair exhaust fan in bathroom
281543 04/23/2008 185536 P 697 M Seal seam in bathroom flooring
281548 04/23/2008 185541 P 697 M Seal corners of bathroom walls
281506 04/23/2008 185461 4 424 O Eliminate extension cord or replace with minimum 15A cord
281507 04/23/2008 185463 4 426 O Remove and prohibit flammable curtains at exit
281509 04/23/2008 185467 4 431 O Prohibit plugging surge protector into surge protector. Plug directly into outlet
281529 04/23/2008 185506 2 0000 MS Provide current inspection tag for fire extinguisher in mezzanine above 2-217
281504 04/23/2008 185457 2 205 MS Provide current inspection tag for kitchen hood fire suppression system
281515 04/23/2008 185479 2 243 MS Remove hold open device from fire door
281516 04/23/2008 185482 2 244 MS Remove hold open device from fire door
281525 04/23/2008 185500 3 307 MS Provide current inspection tag for fire extinguisher
281503 04/23/2008 185455 4 413 MS Remove storage from mechanical room
281502 04/23/2008 185453 4 439 MS Adjust fire doors in corridor adjacent to 4-413 to latch properly
281552 04/23/2008 185555 6 104 MS Provide current inspection tag for fire extinguisher
281551 04/23/2008 185552 6 191 MS Provide current inspection tag for fire extinguisher
281535 04/23/2008 185522 2 242 OS Prohibit hold open devices on fire door
281521 04/23/2008 185492 2 236D FS Secure hanging heat detector
281501 04/23/2008 185451 4 421 FS Provide heat detector in room used for storage
253698 01/17/2008 128223 4 411 MS Provide current inspection tag for type-K fire extinguisher
253655 01/17/2008 128122 2 227 OS Prohibit storage of flammable spray paints
229104 01/14/2008 81296 P 697 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
253650 01/24/2007 128112 1 102 M Determine cause of water damaged ceiling tiles and replace tiles
253663 01/24/2007 128141 2 212 M Replace missing ceiling tiles
253659 01/24/2007 128130 2 216 M Determine cause of water damaged ceiling tiles and replace tiles
253660 01/24/2007 128132 2 219 M Secure loose handrail @ front of stage
253661 01/24/2007 128135 2 220 M Determine cause of water damaged ceiling tiles and replace tiles
253657 01/24/2007 128126 2 233 M Replace damaged ceiling tiles around exit sign @ east exit
253653 01/24/2007 128118 2 236A M Determine cause of water damaged ceiling tiles and replace tiles
253654 01/24/2007 128120 2 236C M Determine cause of water damaged ceiling tiles and replace tiles
253651 01/24/2007 128114 2 242A M Repair exhaust fan at kiln
253667 01/24/2007 128149 3 307 M Adjust exterior exit door to latch properly
253701 01/24/2007 128229 4 403 M Adjust exterior exit door to latch properly
253700 01/24/2007 128227 4 409 M Adjust corridor door to latch properly
253679 01/24/2007 128176 4 413 M Provide cover on exposed electrical junction box on north wall
253673 01/24/2007 128161 4 426C M Replace missing ceiling tiles
253706 01/24/2007 128239 6 103 M Determine cause of water damaged ceiling tiles and replace tiles
253649 01/24/2007 128110 1 101 O Eliminate multi-outlet extension cord plugged into T.V. or replace with minimum 15A cord with single outlet
253658 01/24/2007 128128 2 223 O Remove and prohibit combustible beanbag chairs
253668 01/24/2007 128151 3 321 O Remove and prohibit paper covering window in door
253704 01/24/2007 128235 4 410 O Eliminate multiple extension cords @ A/V cart
253705 01/24/2007 128237 4 414 O Eliminate and prohibit use of toaster oven in classroom
253672 01/24/2007 128159 4 424 O Eliminate multiple outlet adaptor in outlet adjacent to bathroom
253708 01/24/2007 128243 6 104 O Remove and prohibit combustible (residential) overstuffed chair
253709 01/24/2007 128245 6 105 O Eliminate brown extension cord or replace with minimum 15A cord
253666 01/24/2007 128147 3 313 MS Provide current inspection tag for fire extinguisher
253665 01/24/2007 128145 3 314 MS Provide current inspection tag for fire extinguisher
253664 01/24/2007 128143 3 315 MS Provide current inspection tag for fire extinguisher
238817 01/24/2007 97213 4 409 MS Provide current inspection tag for fire extinguisher
253671 01/24/2007 128157 4 417 MS Provide current inspection tag for fire extinguisher
253676 01/24/2007 128170 4 425 MS Provide current inspection tag for fire extinguisher
253652 01/24/2007 128116 2 242B OS Prohibit storage of flammable spray paints
253670 01/24/2007 128155 3 301 OS Maintain clear aisle to exterior exit door
253702 01/24/2007 128231 4 404 OS Prohibit use of hot plate in classroom
253703 01/24/2007 128233 4 410 OS Maintain clear aisle to rear exterior exit door
253699 01/24/2007 128225 4 411 OS Remove and prohibit storage from stove burners
253675 01/24/2007 128167 4 425 OS Remove and prohibit storage from stove burners
253674 01/24/2007 128164 4 435 OS Remove and prohibit desks and chairs in exit corridor
253707 01/24/2007 128241 6 103 OS Keep area clear to emergency escape window
194053 09/05/2006 20580 00 0000 M Repair roof leaks throughout campus
253656 09/05/2006 128124 2 229 M Mount fire extinguisher at maximum five feet above floor
238792 09/05/2006 97155 2 239C M Replace damaged back splash at sink
238813 09/05/2006 97202 3 312 M Provide cover on exposed electrical junction box on AHU-2 (X2)
253669 09/05/2006 128153 3 301 O Post sign indicating evacuation routes
238825 09/05/2006 97235 2 205A MS Provide current inspection tag for type K fire extinguisher
253678 09/05/2006 128172 4 423 MS Replace out-of-date type-K fire extinguisher with ABC extinguisher
229055 09/05/2006 81198 1 123 OS Relocate cot blocking clear access to door
238790 09/05/2006 97150 1 101 FS Provide certification that fire alarm horns are audible without PA system. Staff indicates fire alarm is not audible through out campus
238818 09/05/2006 97217 4 409B FS Provide heat detector in bathroom used for storage
229059 09/16/2005 81205 00 0000 M Connect security wires for knox box (lid is on, keys are in box, but wires are not connected)
194058 09/16/2005 20583 00 9599 M Repair cracked, uneven sidewalk at student pick-up area outside 4-439
229391 09/16/2005 81812 00 9599 M Secure top rail for fence enclosure adjacent to P-1
238789 09/16/2005 97147 1 115 M Repair leaking air handler
238782 09/16/2005 97139 2 203 M Determine cause of water damaged ceiling tiles and replace tiles
229067 09/16/2005 81222 2 216 M Repair damaged wall finish and windowsill at windows
229351 09/16/2005 81725 2 221 M Replace damaged and missing drywall
229356 09/16/2005 81736 2 234 M Replace damaged drywall
238812 09/16/2005 97199 2 235 M Adjust NE door to latch properly
238783 09/16/2005 97140 2 236A M Determine cause of water damaged ceiling tiles and replace tiles
238784 09/16/2005 97141 2 236C M Determine cause of water damaged ceiling tiles and replace tiles
238824 09/16/2005 97232 2 238 M Secure loose shelf that is hanging from wall
238785 09/16/2005 97142 2 239B M Determine cause of water damaged ceiling tiles and replace tiles
229367 09/16/2005 81759 3 305 M Replace glazing in corridor door with fire rated glazing or wired glass
238786 09/16/2005 97143 3 318 M Determine cause of water damaged ceiling tiles and replace tiles
238787 09/16/2005 97144 4 414B M Determine cause of water damaged ceiling tiles and replace tiles
238796 09/16/2005 97165 4 416A M Secure loose handicapped grabrail
238803 09/16/2005 97180 4 427C M Repair exhaust fan in bathroom
238809 09/16/2005 97195 4 428 M Seure loose base along wall at exterior wall
238806 09/16/2005 97187 4 429 M Adjust door to exterior to latch properly
238793 09/16/2005 97157 4 431C M Secure loose handicappaed grabrail
238794 09/16/2005 97159 4 431C M Replace missing ceramic wall tile
238795 09/16/2005 97163 4 442 M Eliminate wasps on bottom of exterior beam
238820 09/16/2005 97221 6 104B M Repair exhaust fan in bathroom
238819 09/16/2005 97219 6 105 M Repair emergency lighting
238823 09/16/2005 97227 6 8088 M Seal open and damaged expansion joints on exterior wall
194118 09/16/2005 20633 P 2140 M Adjust steps to make risers equal
238822 09/16/2005 97225 P 697 M Replace deteriorated wood fascia at south end
238788 09/16/2005 97145 P 697 M Determine cause of water damaged ceiling tiles and replace tiles
238821 09/16/2005 97223 00 9699 O Prohibit parking on grass area next to P-2
229379 09/16/2005 81787 2 230 O Remove and prohibit shower curtains
229389 09/16/2005 81808 2 230A O Prohibit use of unprotected power strip
238807 09/16/2005 97189 3 306 O Prohibit using 3 way adapter on electric outlet
229316 09/16/2005 81652 4 418 O Prohibit plugging surge protector to surge protector
229075 09/16/2005 81236 4 430 O Prohibit plugging surge protector to surge protector
229101 09/16/2005 81289 6 191 O Clean all cobwebs from walls, ceiling and equipment
194068 09/16/2005 20579 2 216 C Provide magnetic release hold open devices for corridor fire doors
229071 09/16/2005 81230 P 2140 C Provide bottom rail on ramp landing guardrail at two inches above floor
238815 09/16/2005 97206 2 217 MS Provide current inspection tag for fire extinguisher in mechanical mezzanine above 2-217
229355 09/16/2005 81734 3 312 MS Remove storage from mechanical room
238810 09/16/2005 97197 3 314 MS Remove storage from mechanical room
229072 09/16/2005 81232 4 435 MS Adjust fire doors in corridor to latch properly
229368 09/16/2005 81761 2 224 OS Prohibit parking vehicle outside exterior door
229377 09/16/2005 81783 2 237 OS Limit occupancy to maximum 9 persons
238805 09/16/2005 97185 3 309 OS Prohibit running drain line for dehumidifier on floor across door opening
229357 09/16/2005 81739 3 315 OS Relocate flammable storage cabinet from flammable storage room to custodial receiving (3-318)
229352 09/16/2005 81727 3 318 OS Prohibit storage of gas powered blower or store in flammable storage cabinet
238816 09/16/2005 97210 4 409 OS Prohibit all storage on cook top
229337 09/16/2005 81695 4 414 OS Prohibit running drain line for dehumidifier on floor across door opening
238797 09/16/2005 97167 4 423 OS Prohibit all storage on cook top
238791 09/16/2005 97153 1 0000 CS Provide key for communication closet in fire department lock box to allow fire department access
238814 09/16/2005 97204 2 217 FS Provide heat detector in electrical room on mezzanine above 2-217
229388 09/16/2005 81806 2 228 FS Provide heat detector in room used for storage
229370 09/16/2005 81765 3 323 FS Provide heat detector in room used for storage
229065 04/17/2005 81218 00 9599 M Repair damaged chain link fencing around refrigeration units behind kitchen
229066 04/17/2005 81220 00 9599 M Secure loose cap on clean out in grass area outside cafeteria exterior door
229064 04/17/2005 81216 1 106 M Repair doors at end of corridor to close and latch properly
229062 04/17/2005 81211 1 115 M Repair leaking a/c equipment
229411 04/17/2005 81834 2 206 M Replace missing ceiling tiles
229412 04/17/2005 81835 2 215 M Replace missing ceiling tiles
229413 04/17/2005 81836 2 216 M Replace missing ceiling tiles
229350 04/17/2005 81723 2 218 M Determine cause of water damaged ceiling tiles and replace tiles
194069 04/17/2005 31449 2 219 M Provide dated flame resistance label on stage curtain (no tag visible)
229381 04/17/2005 81791 2 220 M Determine cause of water damaged ceiling tiles and replace tiles
229414 04/17/2005 81837 2 221A M Replace missing ceiling tiles
229415 04/17/2005 81838 2 221C M Replace missing ceiling tiles
229416 04/17/2005 81839 2 223 M Replace missing ceiling tiles
229417 04/17/2005 81840 2 224 M Replace missing ceiling tiles
229383 04/17/2005 81795 2 224 M Relocate maximum occupancy sign to be inside room
229418 04/17/2005 81841 2 230 M Replace missing ceiling tiles
229419 04/17/2005 81842 2 232 M Replace missing ceiling tiles
229420 04/17/2005 81843 2 236 M Replace missing ceiling tiles
229421 04/17/2005 81844 2 236A M Replace missing ceiling tiles
229422 04/17/2005 81845 2 236B M Replace missing ceiling tiles
229374 04/17/2005 81777 2 239 M Determine cause of water damaged ceiling tiles and replace tiles
229423 04/17/2005 81846 2 239A M Replace missing ceiling tiles
229385 04/17/2005 81799 2 239B M Remove broken mirror
229375 04/17/2005 81779 2 239B M Determine cause of water damaged ceiling tiles and replace tiles
229424 04/17/2005 81847 2 239C M Replace missing ceiling tiles
229425 04/17/2005 81848 2 241 M Replace missing ceiling tiles
229426 04/17/2005 81849 2 242 M Replace missing ceiling tiles
229427 04/17/2005 81850 2 242A M Replace missing ceiling tiles
229371 04/17/2005 81769 3 301 M Replace missing lens on light fixture
229380 04/17/2005 81789 3 301B M Determine cause of water damaged ceiling tiles and replace tiles
229362 04/17/2005 81749 3 303 M Remove dog leg hold open device from corridor door
229428 04/17/2005 81851 3 307 M Replace missing ceiling tiles
229361 04/17/2005 81747 3 308 M Remove dog leg hold open device from corridor door
229354 04/17/2005 81732 3 312 M Label room to indicate roof access inside
229359 04/17/2005 81743 3 323 M Adjust door to latch properly
229095 04/17/2005 81278 4 0000 M Immediately repair broken concrete in paved area outside 4-442 and replace broken cap for cleanout
229346 04/17/2005 81714 4 404 M Adjust exterior door to latch properly
229343 04/17/2005 81708 4 408 M Prohibit use of combustible beanbag chairs
229429 04/17/2005 81852 4 409B M Replace missing ceiling tiles
229430 04/17/2005 81853 4 410B M Replace missing ceiling tiles
229330 04/17/2005 81681 4 411A M Repair exhaust fan in bathroom
229318 04/17/2005 81656 4 417 M Secure loose cover on exhaust fan
229319 04/17/2005 81658 4 417 M Repair door to close and latch properly
229317 04/17/2005 81654 4 418 M Repair exterior door to close and latch properly
229335 04/17/2005 81691 4 421C M Repair exhaust fan in bathroom
229431 04/17/2005 81854 4 422C M Replace missing ceiling tiles
229432 04/17/2005 81855 4 424C M Replace missing ceiling tiles
229321 04/17/2005 81662 4 424C M Replace missing cover on exhaust fan
229322 04/17/2005 81664 4 424C M Replace missing cover on exhaust fan
229433 04/17/2005 81856 4 425B M Replace missing ceiling tiles
229434 04/17/2005 81857 4 425C M Replace missing ceiling tiles
229311 04/17/2005 81642 4 425C M Replace missing cover on exhaust fan
229435 04/17/2005 81858 4 426B M Replace missing ceiling tiles
229436 04/17/2005 81859 4 426C M Replace missing ceiling tiles
229324 04/17/2005 81668 4 426C M Repair exhaust fan in bathroom
229307 04/17/2005 81634 4 427 M Repair exhaust fan in bathroom
229437 04/17/2005 81860 4 427 M Replace missing ceiling tiles
229300 04/17/2005 81619 4 428B M Determine cause of water damaged ceiling tiles and replace tiles
229299 04/17/2005 81617 4 428C M Repair exhaust fan in bathroom
229438 04/17/2005 81861 4 428C M Replace missing ceiling tiles
229073 04/17/2005 81234 4 430C M Repair exhaust fan in bathroom
229081 04/17/2005 81250 4 432 M Adjust exterior door to latch properly
229082 04/17/2005 81252 4 432C M Repair exhaust fan in bathroom
229439 04/17/2005 81862 4 432C M Replace missing ceiling tiles
229440 04/17/2005 81863 4 433C M Replace missing ceiling tiles
229441 04/17/2005 81864 4 434C M Replace missing ceiling tiles
229085 04/17/2005 81257 4 434C M Replace missing seat on toilet
229315 04/17/2005 81650 4 437 M Replace missing ceiling tiles in corridor
229091 04/17/2005 81268 6 101A M Repair exhaust fan in bathroom
229094 04/17/2005 81276 6 103 M Secure loose door knob
229098 04/17/2005 81284 6 104 M Repair emergency escape window to open, close and latch properly
229112 04/17/2005 81313 P 697 M Extend sidewalk to bottom of steps
229070 04/17/2005 81227 0 0 O No access was available to 2-238, 3-316 & P-1. Please be prepared to access these rooms during the report review meeting.
229093 04/17/2005 81272 00 0000 O Prohibit use of air freshener sprays throughout school
229056 04/17/2005 81200 1 110 O Eliminate extension cord or replace with minimum 15A cord and prohibit plugging extension cord into surge protector
229372 04/17/2005 81771 2 239 O Replace bulbs in light fixture
229373 04/17/2005 81775 2 239B O Replace bulbs in light fixture
229369 04/17/2005 81763 3 324 O Eliminate extension cord or replace with minimum 15A cord and prohibit plugging extension cord to surge protector
229344 04/17/2005 81710 4 402 O Prohibit use of multi-outlet electrical adaptor
229345 04/17/2005 81712 4 403 O Prohibit use of multi-outlet electrical adaptor
229347 04/17/2005 81716 4 404 O Secure or remove curled mat at exterior door
229348 04/17/2005 81718 4 404 O Eliminate extension cord or replace with minimum 15A cord
229349 04/17/2005 81720 4 404 O Prohibit use of multi-outlet electrical adaptors
229331 04/17/2005 81683 4 414 O Eliminate extension cord or replace with minimum 15A cord and prohibit powering microwave oven with extension cord
229308 04/17/2005 81636 4 427 O Eliminate extension cord or replace with minimum 15A cord and prohibit plugging extension cord into surge protector
229302 04/17/2005 81623 4 428 O Eliminate extension cord or replace with minimum 15A cord and prohibit plugging extension cord into surge protector
229303 04/17/2005 81626 4 430 O Replace bulbs in emergency light
229378 04/17/2005 81785 00 0000 C Provide illuminated exit sign at courtyard exit between Bldgs. 3 & 4
229063 04/17/2005 81213 1 115 C Label room to indicate roof access inside
229386 04/17/2005 81801 2 219 C Provide handrail on one side of stage steps
229353 04/17/2005 81729 3 318 C Install GFCI outlet next to eye wash
194096 04/17/2005 31159 4 418 C Provide sufficient electrical outlets in classroom so extension cords are not required to power computers
194063 04/17/2005 20483 1 8088 F Repair fire alarm annunciator panel to operate properly
229393 04/17/2005 81816 1 115 MS Provide current inspection tag for fire extinguisher
229394 04/17/2005 81817 2 202 MS Provide current inspection tag for fire extinguisher
229395 04/17/2005 81818 2 205A MS Provide current inspection tag for fire extinguisher
229396 04/17/2005 81819 2 215 MS Provide current inspection tag for fire extinguisher
229397 04/17/2005 81820 2 227 MS Provide current inspection tag for fire extinguisher
229398 04/17/2005 81821 2 242A MS Provide current inspection tag for fire extinguisher
229399 04/17/2005 81822 3 312 MS Provide current inspection tag for fire extinguisher
229400 04/17/2005 81823 3 313 MS Provide current inspection tag for fire extinguisher
229401 04/17/2005 81824 3 314 MS Provide current inspection tag for fire extinguisher
229402 04/17/2005 81825 3 315 MS Provide current inspection tag for fire extinguisher
229329 04/17/2005 81679 4 411 MS Provide current inspection tag for fire extinguisher
229403 04/17/2005 81826 4 413 MS Provide current inspection tag for fire extinguisher
229338 04/17/2005 81697 4 413 MS Remove storage from mechanical room
229404 04/17/2005 81827 4 417 MS Provide current inspection tag for fire extinguisher
229405 04/17/2005 81828 4 420 MS Provide current inspection tag for fire extinguisher
229314 04/17/2005 81648 4 420 MS Remove storage from electrical room
229406 04/17/2005 81829 4 423 MS Provide current inspection tag for fire extinguisher
229407 04/17/2005 81830 4 425 MS Provide current inspection tag for fire extinguisher
229408 04/17/2005 81831 4 439 MS Provide current inspection tag for fire extinguisher
229409 04/17/2005 81832 6 180 MS Provide current inspection tag for fire extinguisher
229410 04/17/2005 81833 6 191 MS Provide current inspection tag for fire extinguisher
229057 04/17/2005 81202 1 113 OS Remove and prohibit space heater
229060 04/17/2005 81208 1 120 OS Remove storage from corridor
229382 04/17/2005 81793 2 209 OS Prohibit use of candles
229387 04/17/2005 81803 2 212 OS Prohibit wedging open fire door between kitchen and staff bathrooms
229392 04/17/2005 81814 2 236 OS Prohibit running phone wire through door opening
229054 04/17/2005 81194 2 242 OS Prohibit wedge hold open device on corridor door
229376 04/17/2005 81781 3 303 OS Remove tables and storage blocking clear path to both doors
229364 04/17/2005 81753 3 303 OS Prohibit blocking corridor door open
229365 04/17/2005 81755 3 304 OS Remove and prohibit space heater in classroom
229366 04/17/2005 81757 3 305 OS Remove storage and table blocking clear path to exterior door
229360 04/17/2005 81745 3 306 OS Remove storage and chair blocking clear path to exterior door
229390 04/17/2005 81810 3 307 OS Prohibit parking car outside exterior door
229363 04/17/2005 81751 3 308 OS Prohibit blocking corridor door open
229341 04/17/2005 81703 4 405 OS Relocate computer tables blocking clear path to exterior door
229342 04/17/2005 81705 4 405 OS Relocate table blocking clear path to corridor door
229339 04/17/2005 81699 4 409 OS Remove storage blocking clear path to exterior door
229340 04/17/2005 81701 4 410 OS Relocate table and chairs blocking clear path to exterior door
229327 04/17/2005 81675 4 411 OS Relocate table blocking clear path to exterior door
229328 04/17/2005 81677 4 411 OS Prohibit storage on stove
229313 04/17/2005 81646 4 413 OS Keep fixed leaf of double doors latched
229332 04/17/2005 81685 4 414 OS Prohibit use of electric skillet in classroom
229336 04/17/2005 81693 4 421 OS Remove excessive storage in area outside bathroom/closet
229320 04/17/2005 81660 4 422 OS Relocate table blocking clear path to exterior door
229333 04/17/2005 81687 4 423 OS Prohibit use of candles
229334 04/17/2005 81689 4 423 OS Remove storage blocking clear path to exterior door
229323 04/17/2005 81666 4 424 OS Remove storage blocking clear path to exterior door
229309 04/17/2005 81638 4 425 OS Remove storage blocking clear path to exterior door
229310 04/17/2005 81640 4 425 OS Prohibit storage on stove
229312 04/17/2005 81644 4 425 OS Provide clear access to fire extinguisher adjacent to stove
229326 04/17/2005 81673 4 426 OS Relocate table blocking clear path to exterior door
229306 04/17/2005 81632 4 427 OS Remove storage blocking clear path to exterior door
229301 04/17/2005 81621 4 428 OS Relocate table and chair blocking clear path to exterior door
229305 04/17/2005 81630 4 429 OS Remove storage blocking clear path to exterior door
229304 04/17/2005 81628 4 430 OS Remove chair blocking clear path to exterior door
229088 04/17/2005 81261 4 431 OS Relocate bookcase and desk blocking clear path to exterior door
229079 04/17/2005 81245 4 431 OS Prohibit wedging open corridor door
229080 04/17/2005 81248 4 432 OS Relocate chairs and storage blocking clear path to exterior door
229076 04/17/2005 81239 4 432 OS Prohibit wedging open corridor door
229078 04/17/2005 81243 4 433 OS Prohibit wedging open corridor door
229084 04/17/2005 81254 4 434 OS Remove storage blocking clear access to exterior door
229077 04/17/2005 81241 4 434 OS Prohibit wedging open corridor door
229089 04/17/2005 81265 6 101 OS Relocate table blocking clear access to emergency escape window
229097 04/17/2005 81281 6 105 OS Prohibit use of candles (3 found lit during inspection)
229106 04/17/2005 81299 P 697 OS Prohibit leaving tricycles on stair landing
229108 04/17/2005 81303 P 697 OS Provide and maintain minimum 3' wide clear path to stair door
229110 04/17/2005 81309 P 697 OS Prohibit parking vehicles on grass area adjacent to portable
229102 04/17/2005 81293 P 697 OS Remove decorations around fire alarm pull station which make it difficult to see pull station
229384 04/17/2005 81797 2 220 FS Secure heat detector hanging by wires
229358 04/17/2005 81741 2 236A FS Secure heat detector hanging by wires
229325 04/17/2005 81671 4 426B FS Secure heat detector hanging by wires
194059 01/12/2005 20582 00 9599 M Repair uneven concrete slabs in interior courtyard to eliminate tripping hazard
194060 01/12/2005 20584 00 Chiller Compound M Insulate chilled water lines
194065 01/12/2005 20589 2 205A M Provide current inspection tag for kitchen boiler (steamer)
194066 01/12/2005 20522 2 205A M Provide nozzle for fire suppression system in chain broiler
194086 01/12/2005 31469 4 406 M Repair deteriorated wall finish adjacent to exterior door
194100 01/12/2005 31389 4 423 M Replace type "K" fire extinguisher with minimum 4A capacity within 10 feet of cooking equipment.
194114 01/12/2005 31009 6 101 M Repair inoperable air conditioner
194108 01/12/2005 63197 4 430 O Eliminate blocked exit and remove excessive flammable decorations
194112 01/12/2005 31269 4 434 O Eliminate multiple extension cords for computers
194115 01/12/2005 31289 6 102 O Eliminate multiple extension cords for computers
194052 01/12/2005 20559 00 0000 C Provide signage indicating room names and numbers at appropriate height with raised and Braille characters throughout campus
194077 01/12/2005 20474 3 319 C Provide illuminated exit sign from courtyard into Building 3 (on side of door that swings in)
194083 01/12/2005 31119 4 404 C Provide sufficient electrical outlets in classroom so extension cords are not required to power computers
194091 01/12/2005 31129 4 410 C Provide sufficient electrical outlets in classroom so extension cords are not required to power computers
194117 01/12/2005 20569 P 1 C Provide bottom rail on stair landing guardrail at two inches above floor
194119 01/12/2005 20570 P 2140 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
194055 01/12/2005 20480 00 0000 F Provide fire alarm strobe lights in courtyard and along exterior walls
194061 01/12/2005 31349 1 101 F Provide certification that fire alarm system has been tested and is fully operational
194067 01/12/2005 20521 2 205A MS Provide current inspection for fire suppression system (dated 2001)
194051 01/12/2005 20479 00 0000 FS Provide heat detector in metal storage building adjacent to portables
194062 01/12/2005 20481 1 101A FS Provide heat detector in phone closet
194070 01/12/2005 20484 2 221C FS Provide heat detector in room used for storage
194071 01/12/2005 20485 2 223 FS Provide heat detector in storage room
194072 01/12/2005 20486 2 229 FS Provide heat detector in storage room
194073 01/12/2005 20488 3 301A FS Provide heat detector in storage room
194074 01/12/2005 20489 3 303A FS Provide heat detector in storage room
194075 01/12/2005 20490 3 310B FS Provide heat detector in shower room used as storage room
194080 01/12/2005 20491 4 401B FS Provide heat detector in storage room
194081 01/12/2005 20492 4 402B FS Provide heat detector in storage room
194082 01/12/2005 20493 4 403B FS Provide heat detector in storage room
194084 01/12/2005 20494 4 404B FS Provide heat detector in storage room
194085 01/12/2005 20495 4 405B FS Provide heat detector in storage room
194087 01/12/2005 20496 4 406B FS Provide heat detector in storage room
194088 01/12/2005 20497 4 407B FS Provide heat detector in storage room
194089 01/12/2005 20498 4 408B FS Provide heat detector in storage room
194090 01/12/2005 20499 4 409C FS Provide heat detector in storage room
194092 01/12/2005 20500 4 410B FS Provide heat detector in storage room
194093 01/12/2005 20501 4 411A FS Provide heat detector in storage room
194094 01/12/2005 20502 4 412B FS Provide heat detector in storage room
194095 01/12/2005 20503 4 414B FS Provide heat detector in storage room
194097 01/12/2005 20504 4 418A FS Provide heat detector in storage room
194098 01/12/2005 20505 4 421B FS Provide heat detector in storage room
194099 01/12/2005 20506 4 422B FS Provide heat detector in storage room
194101 01/12/2005 20507 4 423C FS Provide heat detector in storage room
194102 01/12/2005 20508 4 424B FS Provide heat detector in storage room
194103 01/12/2005 20509 4 425C FS Provide heat detector in storage room
194104 01/12/2005 20510 4 426B FS Provide heat detector in storage room
194105 01/12/2005 20511 4 427B FS Provide heat detector in storage room
194106 01/12/2005 20512 4 428B FS Provide heat detector in storage room
194107 01/12/2005 20513 4 429B FS Provide heat detector in storage room
194109 01/12/2005 20514 4 430B FS Provide heat detector in storage room
194110 01/12/2005 20515 4 431B FS Provide heat detector in storage room
194111 01/12/2005 20516 4 433B FS Provide heat detector in storage room
194113 01/12/2005 20517 4 434A FS Provide heat detector in storage room