JUPITER FARMS ELEMENTARY
 
JUPITER FARMS ELEMENTARY
17400 HAYNIE LANE
JUPITER, 33478
FISH Drill Down
 Campus Info.
 Buildings:14 Rooms:296
 Portables:7
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
420978 01/26/2018 488252 00 0000 M Clean debris and leaves from gutters throughout campus, rain observed flowing over side of gutters due to build up of debris
420985 01/26/2018 488266 00 0000 M Grind down and make repairs to uneven areas of concrete in center courtyard
420984 01/26/2018 488264 1 101 M Make repairs as noted on fire alarm inspection report
404227 01/26/2018 452132 1 120 M Repair exhaust fan in custodial closet
420969 01/26/2018 488230 10 002 M Repair emergency lighting
420708 01/26/2018 487659 2 201 M Repair emergency lighting
404228 01/26/2018 452134 2 202 M Repair exhaust fan for range
404229 01/26/2018 452136 2 202 M Repair or replace leaking faucet
420711 01/26/2018 487666 3 301A M Provide self illuminated exit sign indicating newly created exit from stage at curtain stop (reference citation 420710)
420726 01/26/2018 487701 3 301A M Provide current dated flame resistance label on stage curtain
420781 01/26/2018 487825 3 305 M Adjust door of walk in freezer to close properly
420780 01/26/2018 487823 3 307 M Secure loose electrical outlet at refrigerator
420964 01/26/2018 488220 3 316 M Provide current certification that all student occupied spaces have emergency lights and all are operable, certificate has expired
420994 01/26/2018 488282 3 323 M Fill void in electrical panel LF1
420779 01/26/2018 487821 3 325 M Repair or replace damaged, rusty door to allow egress at all times
404263 01/26/2018 452208 4 407A M Replace missing wall finish in bathroom
420976 01/26/2018 488248 5 510 M Provide CO2 fire extinguisher in computer lab, remove ABC fire extinguisher
420977 01/26/2018 488250 5 526 M Adjust door to latch properly
420995 01/26/2018 488288 6 602 M Adjust door closer to control speed of closing door
404251 01/26/2018 452183 6 602A M Repair exhaust fan in bathroom
420996 01/26/2018 488290 6 606 M Determine cause of water damaged ceiling tiles and replace tiles
420981 01/26/2018 488258 6 608D M Repair noisy exhaust fan in bathroom
420982 01/26/2018 488260 6 609A M Repair hole in wall adjacent to 6-609A and fire extinguisher
420983 01/26/2018 488262 6 612 M Adjust door to latch properly
420980 01/26/2018 488256 6 9599 M Eliminate drop off over 18 inches at sidewalk on south side of building 6 and make necessary repairs to prevent future erosion
420991 01/26/2018 488278 7 705 M Adjust north patio door to close properly
420986 01/26/2018 488268 7 706 M Adjust door closer on south door to control speed of closing door
420987 01/26/2018 488270 7 709 M Adjust door to latch properly
420992 01/26/2018 488280 7 714 M Adjust door to latch properly
420989 01/26/2018 488274 7 9699 M Make repairs to rotting wooden benches in patio area adjacent to 7-710 and 7-705
420966 01/26/2018 488224 P 6284 M Repair east emergency lighting
420967 01/26/2018 488226 P 6284 M Adjust east door to close properly
420971 01/26/2018 488235 P 9990 M Repair west emergency lighting
420972 01/26/2018 488237 P 9990 M Adjust door closer on east door to control speed of closing door
420970 01/26/2018 488233 P 9992 M Repair east emergency lighting
420990 01/26/2018 488276 1 113 O Remove and prohibit air freshener
420965 01/26/2018 488222 4 406 O Prohibit use of white multi outlet extension cord at smart board or replace with minimum 15A single outlet extension cord
420988 01/26/2018 488272 7 705 O Prohibit plugging surge protector into surge protector adjacent to teachers desk
420979 01/26/2018 488254 P 9373 O Prohibit use of multi outlet extension cord at microwave or replace with minimum 15A single outlet extension cord
241942 01/26/2018 103391 00 0000 C Modify or improve site drainage to eliminate standing water on play court adjacent to pavillion
420709 01/26/2018 487661 2 204 MS Recharge fire extinguisher
420710 01/26/2018 487664 3 301A MS Provide stop on stage curtain 3 feet from wall to provide secondary egress from stage when curtain is closed
420778 01/26/2018 487818 3 325 MS Recharge fire extinguisher
420973 01/26/2018 488239 5 525 MS Provide current inspection tag for fire extinguisher
420968 01/26/2018 488228 P 6284 OS Maintain clear aisle to east exit door
270247 01/26/2018 161123 10 0000 N/A No violations observed
406301 01/26/2018 456647 11 0000 N/A No violations observed
404215 01/26/2018 452107 12 0000 N/A No violations observed
262815 01/26/2018 145233 3 0000 N/A No violations observed
262817 01/26/2018 145235 5 0000 N/A No violations observed
262819 01/26/2018 145237 7 0000 N/A No violations observed
262820 01/26/2018 145238 8 0000 N/A No violations observed
262821 01/26/2018 145239 9 0000 N/A No violations observed
280277 01/26/2018 182847 P 6284 N/A No violations observed
280278 01/26/2018 182849 P 6285 N/A No violations observed
262823 01/26/2018 145241 P 9373 N/A No violations observed
262824 01/26/2018 145242 P 9374 N/A No violations observed
262825 01/26/2018 145243 P 9990 N/A No violations observed
262826 01/26/2018 145244 P 9991 N/A No violations observed
262827 01/26/2018 145245 P 9992 N/A No violations observed
404275 05/10/2017 452233 9 901 M Replace leaking shaft seal on blue pump next to white compressor
404279 04/05/2017 452243 00 0000 M Provide locks on gates of fencing around well enclosures. 1 at golf cart charging building and other at ball fields
404210 04/05/2017 452097 00 0000 M Clean out all rain gutters, downspouts and roof drains on campus and repair leaking gutters. Over flowing gutters are draining into soffits and fascias
404211 04/05/2017 452099 1 101 M Repair trouble indicated on fire alarm panel
404277 04/05/2017 452238 10 0000 M Provide lock on gate of fencing around pumps at building 10
404276 04/05/2017 452235 10 002 M Repair roof leaks. Open up crack on top and fill with sealant or hydraulic cement
404216 04/05/2017 452109 11 0000 M Provide signage indicating room name and number at appropriate height with raised and Braille characters. It is building 11 not building 10
404273 04/05/2017 452229 2 0000 M Secure loose spout on drinking fountain outside of 2-201
404230 04/05/2017 452138 2 203A M Repair exhaust fan in bathroom
404219 04/05/2017 452116 3 302 M Replace missing screws for cover of electrical panel K section 1
404226 04/05/2017 452130 3 304 M Repair thumb latch on deadbolt lock for walk-in cooler in Kitchen to work properly. Will not unlock door from inside cooler
404220 04/05/2017 452118 3 305 M Adjust door of walk-in freezer in Kitchen to latch properly
404221 04/05/2017 452120 3 306A M Repair exhaust fan in bathroom
404225 04/05/2017 452128 3 319B M Replace 1 piece of ceramic base tile along wall in bathroom
404224 04/05/2017 452126 3 322 M Repair light in exit sign
404223 04/05/2017 452124 3 323 M Replace missing screws for cover of electrical panel LF1
404249 04/05/2017 452179 4 402A M Repair exhaust fan in bathroom
404250 04/05/2017 452181 4 402B M Repair exhaust fan in bathroom
404261 04/05/2017 452203 4 407A M Repair exhaust fan in bathroom
404262 04/05/2017 452205 4 407B M Repair exhaust fan in bathroom
404270 04/05/2017 452222 4 409C M Replace missing KO seal in fire alarm junction box
404265 04/05/2017 452212 4 412 M Replace missing screws for cover of electrical panel LE1
404271 04/05/2017 452225 5 0000 M Fill at edge of sidewalk outside of 5-512 to eliminate drop off
404272 04/05/2017 452227 5 503 M Repair or replace leaking faucet
404259 04/05/2017 452199 5 512 M Adjust flow of drinking fountain. Low flow
404260 04/05/2017 452201 5 514 M Seal open corner in handicapped stall
404281 04/05/2017 452247 5 525 M Repair leaking air handler 3
389016 04/05/2017 419307 5 528 M Repair or replace rusted door
404257 04/05/2017 452195 6 601A M Reinsulate chilled water lines. Large amount of condensate water on floor
404258 04/05/2017 452197 6 601D M Repair exhaust fan in bathroom
404256 04/05/2017 452193 6 604B M Anchor shelving to wall
404253 04/05/2017 452187 6 606A M Repair leaking air handler
404254 04/05/2017 452189 6 606D M Determine cause of water damaged ceiling tiles and replace tiles
404252 04/05/2017 452185 6 610A M Repair exhaust fan in bathroom
404255 04/05/2017 452191 6 610D M Cap 1 exposed wire and provide cover on exposed A-C junction box
404283 04/05/2017 452251 7 714 M Replace missing screws for cover of electrical panel HB1
404278 04/05/2017 452240 P 0000 M Provide lock on gate of fencing around electrical equipment at P-6
404247 04/05/2017 452174 P 0000 M Clean out all yard drains for portables to allow them to function properly
404248 04/05/2017 452177 P 0000 M Provide lock on gate of fencing for electrical equipment at P-3
404217 04/05/2017 452112 P 6284 M Adjust bathroom door to latch properly
404218 04/05/2017 452114 P 6284 M Replace damaged hinge for cabinet door. Door labeled MRS COLAS CLASS
404233 04/05/2017 452145 P 9373 M Secure bathroom sink to wall
404234 04/05/2017 452147 P 9373 M Adjust rear door to latch properly
404235 04/05/2017 452149 P 9373 M Replace missing epoxy floor finish in bathroom
404236 04/05/2017 452151 P 9373 M Repair emergency lighting at front door
404237 04/05/2017 452153 P 9990 M Adjust rear door to latch properly
404238 04/05/2017 452155 P 9990 M Repair emergency lighting at rear door
404239 04/05/2017 452157 P 9990 M Replace missing epoxy floor finish in bathroom
404240 04/05/2017 452159 P 9990 M Remove form boards from rear landing
404241 04/05/2017 452162 P 9991 M Reconnect black drainage pipe at rear of unit. Open joint is eroding large hole in ground
404242 04/05/2017 452164 P 9991 M Exterior 12 X 12 junction box is partially buried. Remove dirt from beneath box so that it no longer contacts ground or raise box
404243 04/05/2017 452166 P 9991 M Seal wall at bathroom sink to provide impervious finish
404244 04/05/2017 452168 P 9992 M Exterior 12 X 12 junction box is partially buried. Remove dirt from beneath box so that it no longer contacts ground or raise box
404245 04/05/2017 452170 P 9992 M Repair emergency lighting at front door
404246 04/05/2017 452172 P 9992 M Replace missing epoxy floor finish in bathroom
404214 04/05/2017 452105 00 0 O No access was available to 5-518. Please provide access to this room during the report review meeting
404274 04/05/2017 452231 1 0000 O Remove sign on gate to parking lot between buildings 1 and 2 that says STOP NOT AN EXIT. Provide sign that reads EMERGENCY EXIT ONLY
404212 04/05/2017 452101 1 104 O Provide clear access to fire alarm pull station
404231 04/05/2017 452140 2 204 O Remove and prohibit paper covering window in door. Acceptable for CODE situation only
404232 04/05/2017 452142 2 204 O Remove and prohibit hot wax air freshener
404266 04/05/2017 452214 4 404 O Remove and prohibit attaching paper to blinds. Acceptable on window or string line in front of windows
404264 04/05/2017 452210 4 406 O Remove and prohibit fabric light covers
404267 04/05/2017 452216 4 408 O Remove and prohibit attaching paper to blinds. Acceptable on windows or string line in front of windows
404268 04/05/2017 452218 4 408 O Remove and prohibit fabric light covers
404280 04/05/2017 452245 7 0000 O Remove sign on gate to parking lot between buildings 1 and 7 that reads NOT AN EXIT. Replace with sign indicating EMERGENCY EXIT ONLY
404213 04/05/2017 452103 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus Dated 12-2015
404269 04/05/2017 452220 4 408 MS Adjust auto closer on corridor door. Closes too fast
404222 04/05/2017 452122 7 713 OS Keep area clear at emergency escape window
404282 04/05/2017 452249 7 714 OS Remove storage from electrical room
389002 01/23/2017 419275 3 308A M Repair ventilation fan in women's restroom
389001 01/23/2017 419273 3 308B M Repair ventilation fan in men's restroom
262813 01/23/2017 145231 1 0000 N/A No violations observed
262814 01/23/2017 145232 2 0000 N/A No violations observed
262816 01/23/2017 145234 4 0000 N/A No violations observed
262818 01/23/2017 145236 6 0000 N/A No violations observed
389007 03/18/2016 419286 00 0000 M Repair emergency light on west wall of fire pump room at pump Building
388993 03/18/2016 419257 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
388992 03/18/2016 419255 1 116 M Replace missing signage indicating room name and number
388994 03/18/2016 419259 2 201C M Determine cause of water damaged ceiling tiles and replace tiles
389017 03/18/2016 419311 3 0000 M Remove vegetation growing in rain gutter in front of 3-301
388997 03/18/2016 419265 3 301 M Replace missing grillwork in ceiling at entrance doors of cafeteria
388998 03/18/2016 419267 3 301 M Secure loose handrail on the left side at the front of stage inside cafeteria
389000 03/18/2016 419271 3 302 M Provide current state inspection tag for kitchen steamer (old style steamer still has pressure vessel)
388999 03/18/2016 419269 3 302B M Replace missing ceiling tile inside kitchen manager's office
389003 03/18/2016 419278 3 307 M Determine cause of water damaged ceiling tiles and replace tiles
388996 03/18/2016 419263 3 320 M Replace broken ceiling tiles
389018 03/18/2016 419313 4 401 M Replace missing ceiling tiles above sink
389015 03/18/2016 419305 5 522 M Replace ceiling tile with hole cut in it
389023 03/18/2016 419322 6 605 M Repair loose vinyl base along floor at computer table
389025 03/18/2016 419326 6 606D M Determine cause of water damaged ceiling tile inside bathroom and replace tiles
389024 03/18/2016 419324 6 608 M Secure loose faucet to sink
389026 03/18/2016 419328 7 706D M Replace missing exhaust fan inside bathroom
389006 03/18/2016 419284 9 0000 M Provide emergency lighting and generator certification that all student occupied spaces have emergency lights and all are operable
389004 03/18/2016 419280 9 901 M Repair emergency lighting (X2)
389005 03/18/2016 419282 9 901 M Repair door to close and latch properly
389012 03/18/2016 419299 P 9374 M Repair door to close and latch properly
389008 03/18/2016 419289 P 9991 M Replace broken plastic outlet cover adjacent to door
388995 03/18/2016 419261 2 202 O Eliminate storage on top of stove to prevent fire hazard
389020 03/18/2016 419316 4 401 O Remove and prohibit hanging paper and decorations from window blinds
389021 03/18/2016 419318 4 405 O Remove and prohibit hanging paper and decorations from window blinds
389022 03/18/2016 419320 5 522 O Replace burned out bulbs in light fixtures
389009 03/18/2016 419292 5 525 MS Recharge fire extinguisher located inside mechanical room
389010 03/18/2016 419295 P 9373 MS Recharge fire extinguisher
388991 03/18/2016 419253 1 117 OS Remove and prohibit use of space heater
389014 03/18/2016 419302 5 523 OS Prohibit storage of flammable field striping paint (store inside flammable storage cabinet or flammable storage room
375560 01/11/2016 390213 10 101 M Secure loose door lever at golf cart storage adjacent to basketball court
375559 04/10/2015 390211 2 203 M Adjust back door to latch properly
362337 04/10/2015 361498 3 318 M Curtain tracks are connected to ceiling tiles according to Terry Summerell - contact Pat Joyce for guidance
341907 04/10/2015 316872 3 319B M Repair noisy ventilation fan
375557 04/10/2015 390207 5 511 M Repair east door to open and close properly
375490 04/10/2015 390066 5 513 M Repair water damaged ceiling finish in boys bathroom adjacent to 5-509
375491 04/10/2015 390068 5 513 M Modify lockset so it cannot be locked from inside boys group bathroom adjacent to 5-509
375562 04/10/2015 390217 6 0000 M Make manhole cover level with concrete walkway facing 6-610
375487 04/10/2015 390060 6 606D M Determine cause of water damaged ceiling tiles and replace tiles in bathroom
375564 04/10/2015 390221 P 9373 M Adjust back door to latch properly
375565 04/10/2015 390223 P 9373 M Repair broken vinyl base along wall adjacent to back door
375563 04/10/2015 390219 P 9374 M Repair emergency lighting above front door
375566 04/10/2015 390226 00 0000 O Provide name of Lead Crowd Manager who successfully completed the Crowd Management course as indicated in Bulletin # P-14808
375489 04/10/2015 390064 4 408 O Remove and prohibit paper on window blinds
322779 04/10/2015 274730 P 0000 C Modify or improve roof drainage from portables 6 & 7. Get rain water away from portables. Currently storm water is eroding and undermining walks, foundations and landings and collecting under units
375488 04/10/2015 390062 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus
375561 04/10/2015 390215 5 528 OS Remove storage from electrical room
375558 04/10/2015 390209 7 710 OS Remove and prohibit use of toaster oven
362333 01/27/2015 361489 3 0000 M Provide panic hardware on exit gate in playground behind Bldg. 3 and remove padlock
362322 04/04/2014 361466 10 002 M Repair emergency lighting
362324 04/04/2014 361470 10 002 M Red tag on fire pump - make necessary repairs
362335 04/04/2014 361493 2 0000 M Repair uneven concrete walkway outside west exit doors of 2-202 and 2-203
362336 04/04/2014 361496 2 0000 M Secure metal plate to walkway outside west door of 2-201
362327 04/04/2014 361477 3 0000 M Patch holes in concrete walkway in front of playground behind Bldg. 3
362325 04/04/2014 361473 3 318 M Determine cause of water damaged ceiling tiles and replace tiles
362334 04/04/2014 361491 5 518 M Determine cause of mold on ceiling tiles - repair and replace ceiling tiles
362332 04/04/2014 361487 5 529 M Repair or replace rusted door
362321 04/04/2014 361464 6 606 M Replace missing ceiling tiles adjacent to bathroom
362203 04/04/2014 361197 7 703 M Secure ceiling tile in place above sink counter
362329 04/04/2014 361481 P 6285 M Adjust water flow for drinking spout
362328 04/04/2014 361479 P 9992 M Repair unlock button on bathroom door to work properly
362209 04/04/2014 361209 2 202 O Prohibit plugging surge protector into surge protector behind teacher desk. Plug each surge protector directly into a permanent electrical outlet
362326 04/04/2014 361475 3 322 O Remove and prohibit excessive flammable vinyl skirting at two tables adjaccent to kiln room
362208 04/04/2014 361207 3 322 O Prohibit plugging surge protector into surge protector behind document camera. Plug each surge protector directly into wall outlet
362207 04/04/2014 361205 4 403 O Prohibit plugging surge protector into surge protector behind teacher station. Plug each surge protector directly into wall outlet
362205 04/04/2014 361201 6 607 O Prohibit plugging surge protector into surge protector and extension cord into surge under TV. Plug each surge protector directly into wall outlet and extension cord also into wall outlet
362204 04/04/2014 361199 6 610 O Prohibit plugging surge protector into surge protector under computer stations. Plug each surge protector directly into a permanent electrical outlet
362330 04/04/2014 361483 P 6284 O Remove and prohibit excessive flammable vinyl scenery decorations on wall adjacent to back door
362206 04/04/2014 361203 P 9373 O Prohibit plugging surge protector into surge protector under teacher printer. Plug each surge protector directly into wall outlet
341923 04/04/2014 316905 00 0000 C Provide exterior signage indicating property address at entrance to school at Haynie Lane
362323 04/04/2014 361468 10 002 MS Provide current inspection tag for fire extinguisher
362201 04/04/2014 361193 7 701 MS Remove hold open device from fire door
362202 04/04/2014 361195 7 713 MS Remove hold open device from fire door
362331 04/04/2014 361485 5 528 OS Remove storage from electrical room
223829 04/04/2014 7068 7 701 CS Provide secondary egress
223833 04/04/2014 7069 7 713 CS Provide secondary egress
341905 01/22/2014 316868 3 302 M Provide current state inspection tag for kitchen boiler (Expired 10-7-12)
341908 01/22/2014 316874 5 527 M Replace missing signage indicating room name and number
341913 01/22/2014 316884 7 708 M Replace missing signage indicating room name and number
341918 01/22/2014 316894 P 6284 M Replace missing Fish Number signage above front door of portable
328569 01/22/2014 287972 3 320 C Provide correct signage indicating room name and number at appropriate height with raised and Braille characters, current sign reads 3-318D
341915 01/22/2014 316888 P 0000 C Provide fence around drainage grate at south side of P-1
341922 01/07/2013 316903 1 113 M Determine cause of water damaged ceiling tiles and replace tiles
341906 01/07/2013 316870 3 301 M Replace missing ceiling tiles in cafeteria
341903 01/07/2013 316862 3 316 M Provide certification that all student occupied spaces have emergency lights and all are operable (current certification expired 6-30-12)
341914 01/07/2013 316886 7 702 M Determine cause of water damaged ceiling tiles above sink and replace tiles
341919 01/07/2013 316897 P 6284 M Repair emergency lighting above rear door
341920 01/07/2013 316900 P 6285 M Repair emergency lighting (X2) above both exit doors
341917 01/07/2013 316892 P 9373 M Repair emergency lighting above rear door
341916 01/07/2013 316890 P 9374 M Repair emergency lighting above rear door
341909 01/07/2013 316876 5 511 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
341911 01/07/2013 316880 6 601 O Remove and prohibit hanging paper and decorations from ceiling
341912 01/07/2013 316882 6 608 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
328568 01/07/2013 287970 3 318 C Provide correct signage indicating room name and number at appropriate height with raised and Braille characters, current sign reads 3-320
341904 01/07/2013 316866 3 314 MS Provide current inspection tag for fire extinguisher
341910 01/07/2013 316878 5 105 MS Provide current inspection tag for fire extinguisher
322802 10/18/2012 274779 1 0000 M Provide signage indicating room name and number at appropriate height with raised and Braille characters for all rooms in building 1
327671 10/18/2012 286044 3 318 M Provide dated flame resistance label on curtain in music room
328570 10/18/2012 287974 3 318D M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
327700 10/18/2012 286106 10 002 MS Provide current inspection tag for fire pump
322826 03/13/2012 274833 00 0000 M Bury or protect exposed 1 - 1/4" PVC pipe at fence line south of building 6 if pipe is pressurized
322845 03/13/2012 274874 00 0000 M Repair uneven concrete in interior courtyard
327666 03/13/2012 286033 00 0000 M Repair uneven concrete between 2-205 and kindergarten play area
327701 03/13/2012 286109 10 002 M Repair emergency lighting
327668 03/13/2012 286038 2 203 M Adjust exterior door closer (adjacent to 2-203D) to control speed of closing door
327667 03/13/2012 286035 2 205 M Properly mount fire extinguisher at maximum five feet above floor
327678 03/13/2012 286061 3 301 M Repair light in exit sign above exterior door adjacent to dish washer room
327683 03/13/2012 286066 3 302 M Remove unused drinking fountain per Health Department, see Kitchen Manager for details. Located adjacent to exterior door and 3-306
327675 03/13/2012 286055 3 316 M Provide certification that all student occupied spaces have emergency lights and all are operable, emergency lighting certificate is expired
327672 03/13/2012 286048 3 323 M Fill void in electrical panel LF1
327669 03/13/2012 286040 3 328A M Determine cause of water damaged ceiling tiles and replace tiles
327710 03/13/2012 286129 4 403 M Adjust door closer to control speed of closing door
327709 03/13/2012 286127 5 510 M Adjust door closer on exterior door to control speed of closing door
327691 03/13/2012 286089 5 512 M Adjust door closer to control speed of closing door
327712 03/13/2012 286131 5 528 M Fill void in electrical panel LD2 SEC2
327719 03/13/2012 286146 6 602A M Determine cause of water damaged ceiling tiles and replace tiles
327713 03/13/2012 286134 6 604 M Adjust door closer to control speed of closing door
327714 03/13/2012 286136 6 609 M Adjust door closer to control speed of closing door
327716 03/13/2012 286141 7 704 M Adjust door closer on exterior courtyard door to control speed of closing door
327721 03/13/2012 286149 7 713 M Adjust door closer to control speed of closing door
327715 03/13/2012 286138 7 716 M Adjust door closer to control speed of closing door
327693 03/13/2012 286091 P 6285 M Adjust door closer on entrance door to control speed of closing door
327703 03/13/2012 286114 P 9373 M Anchor toilet to floor
327708 03/13/2012 286125 P 9373 M Adjust door closer on entrance door to control speed of closing door
327698 03/13/2012 286101 P 9992 M Replace missing protective cover for electrical outlet on exterior wall adjacent to rear door
327676 03/13/2012 286058 3 317 O Remove storage from hot water heater room
327686 03/13/2012 286075 4 405 O Prohibit white 13A extension cord at lamps or replace with minimum 15A single outlet cord or surge protector
327688 03/13/2012 286082 4 405 O Prohibit plugging surge protector into extension cord under carpet. Prohibit cords under carpet
223890 03/13/2012 66677 5 501 O Eliminate multiple extension cords which feed computers
327690 03/13/2012 286086 5 503 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
327695 03/13/2012 286095 P 6285 O Provide minimum one foot blank wall space on lock side of rear door
327706 03/13/2012 286117 P 9373 O Provide minimum one foot blank wall space on lock side of rear door
327707 03/13/2012 286122 P 9373 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
327670 03/13/2012 286042 3 318 C Provide records that curtain rigging in music room has been inspected and conforms to required safety standards
327673 03/13/2012 286050 3 320 MS Provide current inspection tag for fire extinguisher in storage room adjacent to stage
327722 03/13/2012 286152 6 602 OS Prohibit running electrical cords under carpet
327718 03/13/2012 286144 7 704 OS Remove and prohibit use of candles
322791 10/28/2011 274756 3 301A M Provide dated flame resistance label on stage curtain
322804 10/28/2011 274783 3 302A M Repair or replace rusted conduit at floor level for Somat machine disconnect
322805 10/28/2011 274785 3 309 M Replace badly rusted conduit at floor level. Exposed wires
322827 10/28/2011 274835 3 313 M Investigate standing water on floor. Either chilled water pump or backflow device for expansion tank is leaking
322795 04/28/2011 274765 00 0000 M Repair exhaust fan in bathrooms in Bldgs. 1, 2, 6 and 7. Fans were not running at time of inspection
322782 04/28/2011 274736 00 0000 M Provide lock on gate of fencing around pump adjacent to Bldg. 10
322783 04/28/2011 274738 00 0000 M Provide lock on gate of fencing around electrical panels adjacent to P-3
322784 04/28/2011 274740 00 0000 M Provide lock on gate of fencing around pump south of 6-609
322790 04/28/2011 274754 1 112 M Replace missing door knob
322811 04/28/2011 274799 2 204 M Repair range exhaust fan. Switch is stuck on
322797 04/28/2011 274769 2 205 M Remove rust and paint steel framing
322803 04/28/2011 274781 3 301A M Secure loose tread and riser covers on stage stairs
322828 04/28/2011 274837 3 313 M Reinstall belt guards on compressor
322792 04/28/2011 274758 3 314 M Replace broken toggle on flammable storage room light switch
322806 04/28/2011 274787 3 318A M Determine cause of water damaged ceiling tiles and replace tiles
322809 04/28/2011 274793 4 410 M Adjust door to latch properly
322822 04/28/2011 274824 5 0000 M Replace missing ridge cap shingles above 5-523 and 5-524
322786 04/28/2011 274744 5 511 M Adjust south door to latch properly
322825 04/28/2011 274831 5 524 M Repair light in exit sign
322785 04/28/2011 274742 5 529 M Repair door to open and close properly
322823 04/28/2011 274826 5 530 M Repair sticky latch on door. Room signed 5-529
322799 04/28/2011 274773 7 706 M Exterminate ants in classroom
322801 04/28/2011 274777 7 710 M Repair uneven concrete walk at entry to room
322796 04/28/2011 274767 7 711 M Remove rust and paint steel framing
322808 04/28/2011 274791 9 0000 M Provide certification that old emergency generator is operable. No log for it. Unit still runs weekly
322814 04/28/2011 274806 P 9373 M Repair emergency lighting
322815 04/28/2011 274808 P 9373 M Seal seam in bathroom flooring
322816 04/28/2011 274810 P 9374 M Repair emergency lighting
322817 04/28/2011 274812 P 9374 M Seal seam in bathroom flooring
322819 04/28/2011 274818 P 9990 M Seal seam in bathroom flooring
322820 04/28/2011 274820 P 9991 M Seal seam in bathroom flooring
322821 04/28/2011 274822 P 9992 M Seal seam in bathroom flooring
322778 04/28/2011 274728 00 0 O No access was available to 1-108, 1-116, 3-318C. 7-707, 7-708 and 7-709. Please be prepared to access these rooms during the report review meeting.
322781 04/28/2011 274734 00 0000 O Remove and prohibit excessive flammable decorations in classrooms. Prohibit hanging paper on strings, from ceilings and on windows and blinds. Paper should be directly attached to walls. Paper should be limited to covering 20% of the wall area in classrooms
322780 04/28/2011 274732 6 610 O Remove and prohibit excessive flammable decorations
322810 04/28/2011 274796 00 0000 C Provide outlets in mechanical rooms in classrooms for dehumidifier to eliminate need to run cord through door opening to get to electrical outlet. In bldgs 6 & 7 and room 2-204
322793 04/28/2011 274760 5 509 C Provide sign indicating secondary egress at door to 5-510
322787 04/28/2011 274747 2 201C F Uni-strut holding heat detector at ceiling has slipped down and needs to be reset so that heat detector is located back to high point of ceiling
322807 04/28/2011 274789 1 101 OS Provide clear access to fire alarm pull station
322800 04/28/2011 274775 2 203 OS Maintain clear aisle to rear exit
322824 04/28/2011 274829 4 412 OS Remove storage from electrical room
322798 04/28/2011 274771 6 601 OS Prohibit running electrical cord across floor
322789 04/28/2011 274752 6 610 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station and fire extinguisher
322788 04/28/2011 274750 7 702 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station and fire extinguisher
322794 04/28/2011 274763 7 702 OS Provide clear access to fire alarm pull station and fire extinguisher
322812 04/28/2011 274802 P 6285 OS Maintain 3' clear aisle to rear exit
322813 04/28/2011 274804 P 9373 OS Maintain 3' clear aisle to rear exit
322818 04/28/2011 274816 P 9990 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station
308353 02/15/2011 243109 3 301A C Make necessary repairs to stage as specified on "Tom Kat Rigging" report
270380 02/15/2011 161437 7 711 C Replace ladder and chain handrail at mezzanine to meet code requirements
241958 02/15/2011 103428 5 509 CS Provide secondary egress
308366 04/08/2010 243135 00 9599 M Close wide gap in chain link fence gate adjacent to fire pump Bldg. 10
308348 04/08/2010 243099 10 002 M Repair emergency lighting on south wall
308357 04/08/2010 243117 2 201A M Secure exhaust fan cover to ceiling in bathroom
298541 04/08/2010 221818 3 301 M Replace number on maximum occupancy sign in cafeteria to indicate maximum occupancy = 227 (per Angel Goitia, 6/15/09)
308355 04/08/2010 243113 3 302 M Secure cleanout cover to flooring at serving line and adjacent to dishwashing room
298542 04/08/2010 221822 5 501 M Replace number on maximum occupancy sign in media center to indicate maximum occupancy = 71 (per Angel Goitia, 6/15/09)
308359 04/08/2010 243121 7 704 M Secure loose electrical outlet pole
308358 04/08/2010 243119 7 715 M Repair custodial room door to latch properly
308350 04/08/2010 243103 9 901 M Repair emergency lighting (X2)
295832 04/08/2010 215980 P 0000 M Provide impervious wall finish for minimum six foot height in portable bathrooms
308364 04/08/2010 243131 4 401 O Prohibit plugging surge protector into cart outlet - plug surge protector directly into permanent electrical outlet
308365 04/08/2010 243133 4 406 O Prohibit plugging surge protector into cart outlet - plug surge protector directly into permanent electrical outlet
308351 04/08/2010 243105 5 501 O Secure electrical cord cover strips to flooring to eliminate slipping hazard
308360 04/08/2010 243123 7 706 O Prohibit plugging surge protector into extension cord and into another surge protector - plug each surge protector directly into permanent electrical outlet and eliminate use of extension cord
308361 04/08/2010 243125 7 709 O Remove and prohibit air freshener plugged into surge protector in PTO room
308363 04/08/2010 243129 P 6284 O Prohibit plugging surge protector into cart outlet - plug surge protector directly into permanent electrical outlet
308362 04/08/2010 243127 P 6285 O Prohibit plugging surge protector into cart outlet - plug surge protector directly into permanent electrical outlet
243119 04/08/2010 105788 2 205 C Replace ladder and chain handrail at mezzanine to meet code requirements
241944 04/08/2010 103396 3 318 C Provide illuminated exit sign at second exit to stage. Room is an assembly space and requires illuminated exit signs at both exits
223886 04/08/2010 7119 00 9599 MS Provide certification of proper operation and capacity of fire hydrants and fire pump (school has private water source)
308354 04/08/2010 243111 2 205 MS Recharge fire extinguisher
308356 04/08/2010 243115 2 203 OS Prohibit running electrical cord above ceiling
308349 04/08/2010 243101 5 511 OS Remove and prohibit use of space heater at teacher's desk
308352 04/08/2010 243107 5 528 OS Remove all bicycles from electrical room
308367 04/08/2010 243137 P 6284 OS Rearrange furniture to maintain a minimum 3 ft clear path to back exit door
295825 01/28/2010 215965 3 316 M Provide certification that all student occupied spaces have emergency lights and all are operable
295824 04/15/2009 215963 3 302A M Repair fusible link chain to function properly for pass through window in dishwashing room to maintain fire rating -chain was mangled
295826 04/15/2009 215968 3 322 M Repair light in exit sign
295843 04/15/2009 216004 00 0000 O Eliminate excessive storage in classrooms through out facility which causes excessive fuel load and keep classrooms in an orderly manner
295815 04/15/2009 215945 1 102 O Prohibit plugging surge protector into surge protector under nurse's station
295828 04/15/2009 215972 2 201 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
295827 04/15/2009 215970 2 203 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
295829 04/15/2009 215974 4 403B O Keep storage away from heat detector
295830 04/15/2009 215976 5 521 O Prohibit plugging extension cords into surge protector in control booth - plug extension cords directly into permanent electrical outlet
295840 04/15/2009 215997 6 608 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
295841 04/15/2009 215999 6 608 O Remove and prohibit paper hanging from ceiling
295842 04/15/2009 216001 6 609 O Prohibit plugging cart outlet into extension cord - plug directly into permanent electrical outlet
295817 04/15/2009 215949 7 701 O Prohibit plugging surge protector into extension cord adjacent to documet camera
295818 04/15/2009 215951 7 701 O Prohibit plugging surge protector into extension cord under computer stations and eliminate use of 13A extension cord with multiple outlet end
295823 04/15/2009 215961 7 706 O Eliminate string line below 6'8"
295837 04/15/2009 215991 P 9373 O Remove and prohibit paper covering windows
295838 04/15/2009 215993 P 9373 O Remove and prohibit excessive flammable decorations covering walls, bathroom door and cabinet doors
295839 04/15/2009 215995 P 9990 O Eliminate (3) plug electrical outlet adaptor currently plugged into surge protector at projector cart
295833 04/15/2009 215983 P 9992 O Prohibit plugging surge protector into surge protector under teacher's station
295831 04/15/2009 215978 5 520A MS Provide current inspection tag for fire extinguisher
295834 04/15/2009 215985 P 9991 MS Recharge fire extinguisher
295816 04/15/2009 215947 7 701B OS Remove and prohibit use of toaster oven - toaster oven was stored in closet
295819 04/15/2009 215953 7 703 OS Prohibit storage of flammable spray paint
295820 04/15/2009 215955 7 703 OS Relocate large storage cart blocking clear path to exterior door
295821 04/15/2009 215957 7 705 OS Prohibit running communication cords across path to back door
295822 04/15/2009 215959 7 706 OS Relocate file cabinets to maintain 3 ft clear aisle to back door
295835 04/15/2009 215987 P 9991 OS Relocate teacher's desk to maintain 3ft clear path to back door
295836 04/15/2009 215989 P 9991 OS Relocate storage cart to maintain 3ft clear path to front door
193922 01/27/2009 63015 10 002 M Provide a performance test report for the fire pump
241943 01/27/2009 103394 3 302 M Provide current state inspection tag for kitchen steamer
223922 01/27/2009 7152 7 711 M Provide signage indicating allowable loading of mezzanine (allowable load - 100 psf per Bill Brown of Building Dept.)
257123 01/27/2009 135503 00 0000 C Provide suitable area for storage of golf carts and general storage
241955 01/27/2009 103421 3 306 C Install GFCI or single outlet next to washing machine or verify breaker is GFCI
280312 04/22/2008 182917 3 302 M Adjust nozzle for kitchen hood fire supression system so that two burner cook top is covered
280297 04/22/2008 182888 3 302 M Replace missing ceiling tiles adjacent to freezer 3-305
280303 04/22/2008 182902 3 313 M Adjust east door of mechanical room to latch properly
280301 04/22/2008 182899 3 317 M Repair auto closer on door
280305 04/22/2008 182907 3 318C M Provide additional outlets to eliminate use of excessive extension cords behind refrigerator and freezer
280289 04/22/2008 182872 6 610C M Replace missing ceiling tile
280286 04/22/2008 182865 P 9373 M Adjust back door to latch properly
280287 04/22/2008 182867 P 9374 M Adjust front door to latch properly
280294 04/22/2008 182883 2 202 O Remove and prohibit combustible beanbag chairs (x2)
280308 04/22/2008 182910 3 318C O Prohibit plugging refrigerator and freezer into surge protector - plug appliances directly into permanent electrical outlet
280284 04/22/2008 182861 6 601 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
280326 04/22/2008 182952 6 601 O Remove excessive storage in classroom which causes excessive fuel load and keep area in an orderly manner
280324 04/22/2008 182949 6 607 O Remove excessive storage in classroom which causes excessive fuel load and keep area in an orderly manner
280323 04/22/2008 182945 6 608 O Remove excessive storage in classroom which causes excessive fuel load and remove signs hanging from ceiling tile grid
280313 04/22/2008 182923 6 608 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
280293 04/22/2008 182881 7 703 O Eliminate brown extension cord behind TV or replace with minimum 15A cord
280292 04/22/2008 182876 7 704 O Eliminate extension cord behind TV cart or replace with minimum 15A cord
280318 04/22/2008 182926 7 704B O Keep storage a minimum of one foot away from heat detector
280296 04/22/2008 182885 3 322 MS Provide current inspection tag for fire extinguisher adjacent to kiln room 3-322A
280279 04/22/2008 182851 4 409 OS Remove and prohibit use of toaster oven
280283 04/22/2008 182859 6 604 OS Remove and prohibit use of toaster oven
280282 04/22/2008 182857 7 701 OS Remove and prohibit use of toaster oven
280280 04/22/2008 182853 P 6284 OS Remove and prohibit use of toaster oven
280281 04/22/2008 182855 P 6284 OS Arrange desks to maintain a minimum 3 ft clear aisle to both exit doors
280288 04/22/2008 182869 P 9374 OS Relocate tables to maintain a minimum 3 ft clear aisle to back door
280285 04/22/2008 182863 5 517 FS Provide heat detector in storage room
223885 01/14/2008 7144 00 0000 C Provide certification by structural engineer that steel framing is suitable for applied loads for pavilion behind Building 5 (per Bill Brown's report dated 9/7/07)
269943 01/08/2008 160453 3 301A M Provide dated flame resistance label on stage curtains
269962 01/08/2008 160495 5 501 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
241962 05/01/2007 103436 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
223825 05/01/2007 7155 00 9599 M Re-grade soil around manhole and valve boxes between Building 5 and the pavilion to eliminate tripping hazard
269982 05/01/2007 160537 1 104 M Repair light socket in exit sign. School has replaced the bulb but it burns out right after it is replaced
269979 05/01/2007 160531 1 112 M Replace missing ceiling tile
269956 05/01/2007 160480 10 002 M Repair broken emergency lighting
269975 05/01/2007 160523 2 201C M Replace missing lens on light fixture
223889 05/01/2007 7148 2 205 M Post signage indicating allowable loading of mezzanine. Allowable load 100 psf per Building Department, Bill Brown
269974 05/01/2007 160521 2 205 M Close ceiling hatch
269944 05/01/2007 160455 3 301 M Repair drinking fountain
269942 05/01/2007 160451 3 318 M Provide dated flame resistance label on curtains
269972 05/01/2007 160517 4 409 M Repair exterior door to close properly
269963 05/01/2007 160497 5 501 M Repair door to close and latch properly
223810 05/01/2007 63031 5 525 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
223827 05/01/2007 63032 5 526 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
269947 05/01/2007 160461 9 901 M Repair emergency lighting
269967 05/01/2007 160506 P 9374 M Repair emergency lighting
269957 05/01/2007 160484 P 9991 M Provide cover for broken electrical outlet adjacent to door
269958 05/01/2007 160486 P 9992 M Repair emergency lighting
269976 05/01/2007 160525 1 108 O No access was available to this room. Please be prepared to access this room during the report review meeting
269977 05/01/2007 160527 2 203 O Remove excessive flammable wall coverings and decorations
269940 05/01/2007 160447 3 318C O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
269941 05/01/2007 160449 3 318C O Prohibit plugging refrigerator into extension cord, plug refrigerator directly into wall outlet
269948 05/01/2007 160463 3 318D O Prohibit excessive holiday lights plugged into each other and strung around room
269973 05/01/2007 160519 4 408 O Prohibit plugging surge protector into surge protector @ computers, plug each surge protector into a wall outlet
269970 05/01/2007 160512 5 509 O Prohibit plugging surge protector into surge protector, plug each directly into a wall outlet
269961 05/01/2007 160493 5 510 O Remove and prohibit air freshener
269953 05/01/2007 160475 5 527 O No access was available to this room. Please be prepared to access this room during the report review meeting
269969 05/01/2007 160510 6 609 O Prohibit powerstrip at computers, replace with surge protector
269964 05/01/2007 160499 P 9373 O Remove and prohibit air freshener
269960 05/01/2007 160491 P 9992 O Provide clear access to electrical panel
269981 05/01/2007 160535 7 710 MS Provide current inspection tag for fire extinguisher
269978 05/01/2007 160529 1 113 OS Keep area clear to exit door by using a square table instead of round (per Chris Finkley, PBC Fire Inspector)
269945 05/01/2007 160457 3 301 OS Arrange dining tables to maintain clear aisle to exits
269951 05/01/2007 160471 3 312 OS Prohibit charging batteries in room
269952 05/01/2007 160473 3 312 OS Prohibit storage of flammable materials (field marker paint, dust mop treatment)
269946 05/01/2007 160459 3 315 OS Prohibit storage of propane tanks, store in flammable storage room
269950 05/01/2007 160468 3 318 OS Relocate storage to maintain clear aisle to exits on stage
269939 05/01/2007 160445 3 318C OS Provide clear access to fire extinguisher
269955 05/01/2007 160477 5 512 OS Remove and prohibit candles
269965 05/01/2007 160502 6 608 OS Remove excessive flammable wall coverings
269980 05/01/2007 160533 7 704 OS Keep area to exterior door clear
269966 05/01/2007 160504 P 9373 OS Remove excessive flammable decorations and wall coverings
269959 05/01/2007 160488 P 9992 OS Maintain clear aisle to exit doors
223803 02/13/2007 66691 3 301 M Change maximum occupancy on sign to indicate maximum occupancy =300
241948 02/13/2007 103407 5 529 M Repair of replace leaking water heater
241946 02/13/2007 103401 5 522 C Provide panic hardware on exit doors from 5-522/5-524, occupancy is over 100 or change maximum occupancy to 99 maximum
223799 10/20/2005 66679 00 9599 M Repair damaged chain link fence and top-railing at kindergarten playground north of Building 2
223801 10/20/2005 65273 1 121 M Replace rusted exhaust fan grill
223888 10/20/2005 66668 2 201C M Determine cause of water damaged ceiling tiles and replace tiles
241941 10/20/2005 103388 2 205 M Adjust door to latch properly
223804 10/20/2005 66697 3 301A M Provide dated flame resistance label on stage curtain
223805 10/20/2005 7161 3 302 M Verify activation of hood fire suppression system will initiate school fire alarm
241954 10/20/2005 103419 3 315 M Repair auto closer on door
223840 10/20/2005 65275 3 320 M Replace moldy broken ceiling tile
241956 10/20/2005 103423 4 407A M Repair exhaust fan in bathroom
241953 10/20/2005 103417 4 411 M Repair water heater that is making noise, verify T&P relief valve is working
241951 10/20/2005 103413 5 523 M Determine cause of water damaged ceiling tiles and replace tiles
241952 10/20/2005 103415 5 523 M Replace broken vinyl floor tile
241947 10/20/2005 103405 5 523 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
241950 10/20/2005 103411 5 524 M Repair deteriorated folding partition wall. Exposed fiberglass insulation
241961 10/20/2005 103434 7 704D M Repair exhaust fan in bathroom
193944 10/20/2005 63040 7 713D M Repair exhaust fan in bathroom
223893 10/20/2005 66692 9 901 M Eliminate carpenter ant infestation
241960 10/20/2005 103432 9 901 M Repair emergency lighting
243128 10/20/2005 105809 P 9373 M Adjust ramp door to latch properly
223809 10/20/2005 63018 5 510 O Remove and prohibit combustible (residential) couch
243133 10/20/2005 105819 P 9374 O Provide clear access to electrical panel
223798 10/20/2005 7143 00 0000 C Modify or improve drainage to eliminate standing water in courtyard between Buildings 3 and 4
223802 10/20/2005 7147 2 205 C Provide engineer's certification that mezzanine inside room was designed to meet engineering requirements
223417 10/20/2005 7064 3 318 C Provide sign indicating maximum occupancy adjacent to main entrance
223832 10/20/2005 7151 7 711 C Provide engineer's certification that mezzanine inside room was designed to meet engineering requirements. Approved by Bill Brown
193931 10/20/2005 63030 3 324 F Duct detector not visible for return air. Provide or verify smoke detectors in air flow of return air outlet
241945 10/20/2005 103399 00 0000 MS Provide current inspection tag for all fire extinguishers throughout campus
241940 10/20/2005 103386 2 202 MS Provide current inspection tag for the type K fire extinguisher
193937 10/20/2005 65274 6 608 MS Provide current inspection tag for fire extinguisher
223415 10/20/2005 63017 5 526 OS Prohibit storage of flammable spray paint and PVC cleaner
241957 10/20/2005 103426 5 528 OS Remove storage from electrical room
223418 10/20/2005 63003 6 607 OS Prohibit electrical cord for dehumidifier from running across classroom door opening
193943 10/20/2005 63006 7 713A OS Prohibit electrical cord from running through door opening
241959 10/20/2005 103430 7 716 OS Prohibit storage of flammable spray paint
223443 10/20/2005 7063 1 0000 CS Replace roll-up gate at end of corridor between Buildings 1 and 7 with a gate that allows egress at all times
223831 10/20/2005 65276 7 707 FS Provide heat detector in normally unoccupied space
223480 08/30/2004 7153 00 0000 M Provide verification that all student occupied spaces have emergency lights and all are operable
223838 08/30/2004 7160 3 302 M Provide current inspection tag for kitchen boiler (steamer)
223839 08/30/2004 7165 3 318 M Provide emergency exit signs at both doors leading from stage
223414 08/30/2004 66678 3 322 M Repair light in exit sign
223808 08/30/2004 66671 4 405 M Secure loose electrical power pole
223847 08/30/2004 66672 4 409 M Secure loose electrical power pole
223445 08/30/2004 66669 5 522 M Determine cause of water damaged ceiling tiles and replace tiles at a/c return
223477 08/30/2004 66673 6 604 M Secure loose electrical power pole (teacher states there is a work-order in place to relocate power pole)
223828 08/30/2004 66674 6 609 M Secure loose electrical power pole
223891 08/30/2004 66675 6 610 M Secure loose electrical power pole
223478 08/30/2004 66676 7 701 M Secure loose electrical power pole
223416 08/30/2004 66687 7 704D M Repair auto closer on door
212040 08/30/2004 666686 P 9373 M Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
223830 08/30/2004 66693 7 705A O Keep shower drain filled with water
223892 08/30/2004 66694 7 710D O Keep shower drain filled with water
223837 08/30/2004 7062 00 9599 C Modify gate in kindergarten playground (between Buildings 2 and 3) to allow egress at all times
223807 08/30/2004 7065 3 322 C Provide sign indicating maximum occupancy adjacent to main entrance
223836 08/30/2004 66685 P 9374 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
223887 08/30/2004 66681 1 104 MS Provide current inspection tag for fire extinguisher (dated 7/03)
223806 08/30/2004 66680 3 307 MS Relocate fire extinguisher to be adjacent to exit door
223800 08/30/2004 66670 1 104 OS Keep area clear to all exits (relocate desk, boxes, and curtain)
223444 08/30/2004 66684 2 204 OS Provide approved flame resistant coating on Indian T-Pee or remove from classroom
223921 08/30/2004 66682 3 318C OS Prohibit storage of flammable spray paints
223826 08/30/2004 66683 4 404B OS Prohibit storage of flammable WD 40
223446 08/30/2004 66698 5 528 OS Remove custodial storage from electrical room