JERRY THOMAS ELEMENTARY
 
JERRY THOMAS ELEMENTARY
800 MAPLEWOOD DR
JUPITER, 33458
FISH Drill Down
 Campus Info.
 Buildings:17 Rooms:415
 Portables:0
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
418090 04/17/2018 482037 00 0000 M Make necessary repairs to fire sprinkler system as indicated on inspection report. Red annual and yellow semi-annual and quarterly tags
418091 04/05/2018 482040 00 0000 M Clean out all rain gutters and downspouts of all covered walk-ways and remove trees growing in gutters
418157 04/05/2018 482181 00 0000 M Provide lock on gate of fencing around old lift station NW of building 13
418158 04/05/2018 482183 00 0000 M Old transformer north of building 13 has rusted through lid. Disconnect power to transformer
418162 04/05/2018 482192 00 0000 M Remove 2 stumps from play fields. One 4 inches high south of building 11 and other 18 inches high NE of basketball courts
364684 04/05/2018 366529 00 0000 M Trim trees off of all roofs and covered walkways throughout campus
418092 04/05/2018 482042 1 112 M Repair tagged light fixture
418139 04/05/2018 482143 10 0000 M Open clean-out in cooling tower compound is flowing sewage. Repair plumbing and install cap on clean-out. Repair work in progress at time of inspection
418140 04/05/2018 482145 10 190 M Adjust door to latch properly
418109 04/05/2018 482078 10 192 M Replace missing screws for cover of electrical panel 10LP section 2
418114 04/05/2018 482089 10 195 M Repair or replace surge suppressor for electrical panel SDP. Not lit
418115 04/05/2018 482092 10 195 M Repair roof leaks through concrete ceiling
418161 04/05/2018 482190 11 105B M Repair exhaust fan in bathroom
418150 04/05/2018 482166 12 101A M Secure handicapped grabrail to wall
418151 04/05/2018 482168 12 101A M Cover hole in wall behind toilet to provide impervious finish
418152 04/05/2018 482170 12 104 M Remove damaged pencil sharpener on counter top
418154 04/05/2018 482174 12 108 M Repair exhaust fan in bathroom
418155 04/05/2018 482176 13 0000 M Secure loose spout on drinking fountain outside of entry doors to corridor
418147 04/05/2018 482159 13 002 M Secure faucet to sink
418156 04/05/2018 482178 13 101A M Repair exhaust fan in bathroom
418129 04/05/2018 482122 2 0000 M Bury irrigation plumbing outside of 2-102 door to exterior
418130 04/05/2018 482125 2 102 M Adjust door closer to control speed of closing door, too fast. Door to exterior
418148 04/05/2018 482162 3 0000 M Provide lock on gate of fencing around domestic water back-flows west of building 3
418098 04/05/2018 482055 3 101C M Repair leaking toilet supply line
418097 04/05/2018 482053 3 114B M Determine cause of water damaged ceiling tiles and replace tiles
418094 04/05/2018 482046 3 171 M Replace missing latch plate on door frame
418093 04/05/2018 482044 3 190 M Repair leaking air handler
418095 04/05/2018 482048 3 192 M Replace missing screws for cover of electrical panel 3SH
418101 04/05/2018 482061 3 201C M Repair door hardware, sticky latch
418136 04/05/2018 482137 3 212 M Repair electrical outlet tagged DEAD OUTLET
418103 04/05/2018 482065 3 212A M Repair faucet, low flow
418112 04/05/2018 482085 3 214 M Repair or replace cabinet lock. Slide bolt will not move
418138 04/05/2018 482141 3 214A M Repair door hardware, sticky latch. Bathroom door cannot be locked
418132 04/05/2018 482129 3 216B M Repair leaking supply line for toilet
418133 04/05/2018 482131 3 216C M Repair leaking supply line for toilet
418106 04/05/2018 482072 4 190 M Secure Greenfield conduit fitting to purple box at missing belt guard
418125 04/05/2018 482114 5 101C M Repair exhaust fan in bathroom
418124 04/05/2018 482112 5 104A M Repair toilet. Broken flush arm
418127 04/05/2018 482118 6 002 M Determine cause of water damaged ceiling tiles in corridor at 6-102 and replace tiles
418108 04/05/2018 482076 7 180 M Replace or remove old water heater
418107 04/05/2018 482074 7 190 M Repair leaking air handler
418117 04/05/2018 482097 8 102B M Repair door hardware, sticky latch. Bathroom door cannot be locked
418116 04/05/2018 482095 8 102C M Secure handicapped grabrail to wall
418118 04/05/2018 482099 8 105 M Secure power pole to floor
418142 04/05/2018 482149 9 102A M Replace missing ceiling tile at exhaust fan grate
418144 04/05/2018 482153 9 103 M Secure loose and replace damaged vinyl floor tile
418089 04/05/2018 482035 00 0 O No access was available to 3-110, 10-106C and 10-106D (walk-in cooler and freezer in Kitchen). Please provide access to these rooms during the report review meeting
418163 04/05/2018 482194 14 190 O Provide clear access to electrical panel
418153 04/05/2018 482172 12 104 MS Adjust corridor door to latch properly
418145 04/05/2018 482155 13 103 MS Adjust corridor door to latch properly
418099 04/05/2018 482057 3 101C MS Secure door handle to door
418137 04/05/2018 482139 3 116 MS Adjust corridor door to latch properly
418102 04/05/2018 482063 3 280 MS Provide current inspection tag for fire extinguisher or remove un-0needed extinguisher
418123 04/05/2018 482110 5 190 MS Recharge fire extinguisher
418128 04/05/2018 482120 6 104 MS Adjust corridor door to latch properly
418120 04/05/2018 482103 7 101 MS Adjust corridor door to latch properly
418121 04/05/2018 482105 7 102 MS Adjust corridor door to latch properly
418119 04/05/2018 482101 7 106 MS Adjust corridor door to latch properly
418141 04/05/2018 482147 10 102 OS Maintain clear aisle to Stage exit to exterior, Stage right
418160 04/05/2018 482187 11 104 OS Provide clear access to fire extinguisher
418126 04/05/2018 482116 6 105 OS Provide clear access to fire extinguisher. Remove paper covering cabinet
418122 04/05/2018 482107 7 102 OS Provide clear access to fire extinguisher. Remove paper covering cabinet
261866 04/05/2018 144144 1 0000 N/A No violations observed
261877 04/05/2018 144155 12 0000 N/A No violations observed
270009 04/05/2018 160600 14 0000 N/A No violations observed
274968 04/05/2018 171469 2 0000 N/A No violations observed
261871 04/05/2018 144149 6 0000 N/A No violations observed
261872 04/05/2018 144150 7 0000 N/A No violations observed
418113 12/22/2017 482087 00 0000 M Fill drop off at sidewalk and basketball court SE of building 14
418164 12/22/2017 482197 00 0000 M Repair downed chain link fencing. West campus at parent drop off pick up loop
418110 12/22/2017 482080 10 191 M Repair 2 leaking water heaters
418149 12/22/2017 482164 13 106 M Repair exhaust fan in bathroom
418146 12/22/2017 482157 13 190 M Repair leaking air handler
364716 12/22/2017 366598 15 001 M Repair door lock cylinder. Key will not go in.
418111 12/22/2017 482082 17 0000 M Remove trees growing in chiller yard
418096 12/22/2017 482051 3 0000 M Repair exhaust fan in bathrooms 3-112A and 3-112B
418100 12/22/2017 482059 3 101 M Repair broken window blinds
418131 12/22/2017 482127 3 103 M Repair broken window blinds. Missing slats
418134 12/22/2017 482133 3 204 M Repair broken window blinds
418135 12/22/2017 482135 3 290 M Repair condensate leak from chilled water line above bucket
418104 12/22/2017 482067 4 190 M Repair leaking air handler
418105 12/22/2017 482069 4 190 M Install belt guard for motor
400863 12/22/2017 444908 7 104C M Repair exhaust fan in bathroom
400865 12/22/2017 444912 7 105C M Replace broken grille on exhaust fan in bathroom
400892 12/22/2017 444968 8 101A M Repair exhaust fan in bathroom
400867 12/22/2017 444917 8 102B M Repair exhaust fan in bathroom
418143 12/22/2017 482151 9 180 M Repair exhaust fan in Custodial closet
418168 12/22/2017 482206 11 002 OS Remove and prohibit table and chairs in exit corridor
418159 12/22/2017 482185 11 190 OS Remove storage from mechanical room, benches
418167 12/22/2017 482204 13 002 OS Remove and prohibit tables and chairs in exit corridor
418165 12/22/2017 482200 5 002 OS Remove and prohibit desks, chairs and tables in exit corridor
418166 12/22/2017 482202 8 002 OS Remove and prohibit tables and chairs in exit corridor
261875 12/22/2017 144153 10 0000 N/A No violations observed
261876 12/22/2017 144154 11 0000 N/A No violations observed
261878 12/22/2017 144156 13 0000 N/A No violations observed
270010 12/22/2017 160602 15 0000 N/A No violations observed
270011 12/22/2017 160604 16 0000 N/A No violations observed
326789 12/22/2017 284110 17 0000 N/A No violations observed
261868 12/22/2017 144146 3 0000 N/A No violations observed
261869 12/22/2017 144147 4 0000 N/A No violations observed
261870 12/22/2017 144148 5 0000 N/A No violations observed
261873 12/22/2017 144151 8 0000 N/A No violations observed
261874 12/22/2017 144152 9 0000 N/A No violations observed
400875 02/17/2017 444934 10 106C M Provide protective cage around fire sprinkler head in freezer
400882 02/17/2017 444948 10 182 M Repair exhaust fan in flammable storage room
400881 02/17/2017 444946 10 193 M Repair chiller water pipes to eliminate water leak in back of chiller room
400873 02/17/2017 444930 13 103 M Adjust exterior door to latch properly
400887 02/17/2017 444958 2 190 M Adjust mechanical room door to latch properly
400888 02/17/2017 444960 3 003 M Repair water damaged wall finish under window at top of stairwell
400841 02/17/2017 444863 3 102 M Adjust water flow for drinking spout
400840 02/17/2017 444861 3 106 M Adjust water flow for drinking spout
400850 02/17/2017 444881 3 202 M Repair drinking spout to work properly - No water
400844 02/17/2017 444869 3 204 M Adjust water flow for drinking spout
400855 02/17/2017 444892 3 207 M Determine cause of water damaged ceiling tiles and replace tiles
400851 02/17/2017 444883 3 208 M Repair drinking spout to work properly - No water
400843 02/17/2017 444867 3 210 M Adjust water flow for drinking spout
400852 02/17/2017 444885 3 211 M Repair drinking spout to work properly - No water
400845 02/17/2017 444871 3 215 M Adjust water flow for drinking spout
400842 02/17/2017 444865 3 216 M Adjust water flow for drinking spout
400894 02/17/2017 444972 4 0000 M Repair uneven sidewalk outside 4-190 at west side of Bldg. 4
400856 02/17/2017 444894 9 102B M Replace missing ceiling tiles
400853 02/17/2017 444887 9 103 M Repair drinking spout to work properly - No water
400874 02/17/2017 444932 10 181 O Remove and prohibit use of tape to prevent custodial room door from latching. Keep door to custodial room locked and latched to prohibit student access
400883 02/17/2017 444950 10 184 O Remove and prohibit storage blocking access to fire sprinkler riser - maintain a minimum of 3 ft clear path
400884 02/17/2017 444952 13 101 O Remove and prohibit air freshener
400848 02/17/2017 444877 3 102 O Remove and prohibit string line across room adjacent to bathrooms - you may run string lines along walls and up to 2 inches away from walls
400857 02/17/2017 444896 3 201 O Remove paper covering electrical outlets under writing board (X2)
400859 02/17/2017 444900 3 209C O Replace burned out light bulbs in girls bathroom or have maintenance repair light fixture
400849 02/17/2017 444879 3 214 O Remove and prohibit excessive flammable blue vinyl sheathing on desks adjacent to corridor door
400861 02/17/2017 444904 6 104 O Remove and prohibit paper covering window in corridor door
400890 02/17/2017 444964 6 180 O Keep door to custodial room locked and latched to prohibit student access
400862 02/17/2017 444906 7 102 O Remove and prohibit excessive flammable netting hanging from ceiling and vinyl scenery on wall behind computer station
400866 02/17/2017 444914 7 105B O Remove and prohibit excessive flammable vinyl shower curtain at storage space
400868 02/17/2017 444919 8 102 O Remove and prohibit use of slippery floor mat adjacent to sink
400891 02/17/2017 444966 8 180 O Keep door to custodial room locked and latched to prohibit student access
364763 02/17/2017 366697 3 291 C Raise fire sprinkler to ceiling. Ceiling at 20 feet, fire sprinkler at 10 feet
400876 02/17/2017 444936 10 106K MS Provide current inspection tag for fire extinguisher in exterior communications room
400879 02/17/2017 444942 10 190 MS Provide current inspection tag for fire extinguisher
400880 02/17/2017 444944 10 192 MS Provide current inspection tag for fire extinguisher
400877 02/17/2017 444938 10 193 MS Provide current inspection tag for fire extinguisher
400878 02/17/2017 444940 10 193A MS Provide current inspection tag for fire extinguisher
400872 02/17/2017 444927 13 103 MS Adjust corridor door to latch properly
400885 02/17/2017 444954 2 180 MS Provide current inspection tag for fire extinguisher
400839 02/17/2017 444859 3 109B MS Repair hardware on bathroom door - lock sticks
400886 02/17/2017 444956 3 191 MS Provide current inspection tag for fire extinguisher
400889 02/17/2017 444962 6 190 MS Repair or replace damaged lock on door - exterior mechanical room
400864 02/17/2017 444910 7 104C MS Repair hardware on bathroom door to work properly - lock sticks
400869 02/17/2017 444921 8 104 MS Adjust corridor door to latch properly
400871 02/17/2017 444925 11 102 OS Rearrange furniture to maintain a minimum 3 ft clear path between corridor door and exterior door - room serves as an exit path from corridor
400893 02/17/2017 444970 14 190 OS Remove storage from electrical room
400858 02/17/2017 444898 3 201 OS Remove desk from corridor outside classroom door
400854 02/17/2017 444890 3 201A OS Remove storage container from bathroom vestibule to maintain 3 ft clear path to 3-203
400847 02/17/2017 444875 3 202A OS Remove storage from bathroom
400860 02/17/2017 444902 3 209A OS Remove storage container from bathroom vestibule - projects into door opening
400846 02/17/2017 444873 3 210 OS Remove and prohibit use of toaster oven
400870 02/17/2017 444923 8 105B OS Remove large storage unit from bathroom
368003 11/28/2016 373858 00 0000 M Modify or improve site drainage to eliminate standing water on sidewalk between buildings 9 and 10
387208 03/11/2016 415404 00 0000 M Remove tree growing in dumpster enclosure west of building 10
387210 03/11/2016 415408 00 0000 M Make necessary repairs as indicated on fire sprinkler inspection report. Risers located in 10-184, 3-005
364685 03/11/2016 366531 00 0000 M Clean out all rain gutters, downspouts and roof drains on campus
387236 03/11/2016 415464 1 120 M Repair loose, leaky emergency eye wash
387213 03/11/2016 415414 1 190 M Repair leaking air handler to ensure that air conditioning system operates as designed
387214 03/11/2016 415416 1 190 M Replace missing screws in electrical panel OLH and unmarked panel adjacent to panel A
387232 03/11/2016 415455 1 8087 M Repair damaged rain gutter - downspout adjacent to 1-191
387204 03/11/2016 415394 10 101 M Determine cause of water damaged ceiling tiles at north windows and replace tiles
387205 03/11/2016 415396 10 101D M Replace missing escutcheon on fire sprinkler head
387206 03/11/2016 415400 10 106 M Provide current inspection tag for kitchen hood cleaning
387211 03/11/2016 415410 10 190 M Repair leaking air handler to ensure that air conditioning system operates as designed
368008 03/11/2016 373869 10 191 M Repair or replace leaking water heater
387212 03/11/2016 415412 10 193 M Repair leaking air handler to ensure that air conditioning system operates as designed
364773 03/11/2016 366718 12 0000 M Repair drinking fountain outside of 12-104. Not working. Removed
387198 03/11/2016 415382 12 101 M Provide cover on exposed electrical junction box on wall adjacent to missing clock
387201 03/11/2016 415388 12 103 M Repair exterior door to close and latch properly
387202 03/11/2016 415390 13 106 M Repair damaged ceiling
387203 03/11/2016 415392 13 106 M Replace bulbs in light fixture
367981 03/11/2016 373811 17 001 M Remove trees and weeds growing in chiller compound
364745 03/11/2016 366660 17 001 M Re-install shaft guard on chilled water pump
387234 03/11/2016 415460 2 001 M Replace missing ceiling tiles
387233 03/11/2016 415458 2 8087 M Repair damaged, cut out area of concrete sidewalk under covered walk south of building 2
387226 03/11/2016 415443 3 0000 M Repair exhaust fans in bathrooms
387224 03/11/2016 415439 3 0000 M Determine cause of water damaged ceiling tiles and replace tiles
387231 03/11/2016 415453 3 005 M Replace missing magnetic release hold open device for fire door at 1st floor corridor door
387221 03/11/2016 415433 3 109 M Determine cause of water damaged ceiling tiles and replace tiles
387222 03/11/2016 415435 3 118A M Adjust door closer to control speed of closing door
387215 03/11/2016 415418 3 192 M Provide cover on exposed electrical junction box adjacent to electrical panel 3SL1
387227 03/11/2016 415445 3 207 M Determine cause of water damaged ceiling tiles and replace tiles
387223 03/11/2016 415437 3 211 M Determine cause of water damaged ceiling tiles and replace tiles
387228 03/11/2016 415447 3 290 M Repair leaking air handler to ensure that air conditioning system operates as designed
364746 03/11/2016 366662 4 101B M Repair exhaust fan in bathroom
364747 03/11/2016 366664 4 101C M Repair exhaust fan in bathroom
387196 03/11/2016 415378 4 9599 M Remove broken tree branch adjacent to 4-190
387195 03/11/2016 415376 5 190 M Repair leaking air handler to ensure that air conditioning system operates as designed
368000 03/11/2016 373852 6 190 M Insulate chilled water lines
387194 03/11/2016 415374 8 104 M Provide covers for exposed electrical outlets on power pole
367992 03/11/2016 373835 9 102A M Repair ventilation fan air intake damper. Motorized damper not functioning and closed
387209 03/11/2016 415406 10 180 O Maintain clear access to emergency eye wash - shower
387200 03/11/2016 415386 12 103 O Prohibit use of orange multi outlet extension cord at coffee maker or replace with minimum 15A single outlet extension cord
387217 03/11/2016 415423 3 101 O Relocate string line to hang no more than 2 inches from wall surface
387218 03/11/2016 415425 3 101 O Remove and prohibit excessive flammable decorations on walls, limit coverage area to 50 percent of each wall in a building with fire sprinklers
387219 03/11/2016 415427 3 101 O Prohibit white multi outlet extension cord at decorative holiday light string or replace with minimum 15A single outlet extension cord
387220 03/11/2016 415429 3 101C O Replace bulbs in light fixture
387230 03/11/2016 415451 3 202 O Remove and prohibit flammable blue light covers on ceiling lights
387207 03/11/2016 415402 10 101E OS Remove and prohibit use of candles
387197 03/11/2016 415380 11 190 OS Remove storage from mechanical room
387199 03/11/2016 415384 12 106 OS Relocate furniture at exterior door to maintain clear aisle to exit
387235 03/11/2016 415462 2 103 OS Relocate table at exterior door to maintain clear aisle to exit
387225 03/11/2016 415441 3 0000 OS Prohibit tables and chairs in corridors to maintain clear aisle to exits
387216 03/11/2016 415420 3 106 OS Remove and prohibit use of hot plate
387229 03/11/2016 415449 3 201A OS Prohibit storage of ladder hanging on wall to allow proper door operation and maintain clear aisle to exit
364779 12/04/2015 366733 11 101A M Repair exhaust fan in bathroom
326697 12/04/2015 283913 11 102B M Replace missing exhaust fan in bathroom
367976 12/04/2015 373801 11 105B M Repair exhaust fan in bathroom
367967 12/04/2015 373782 13 101A M Repair exhaust fan in bathroom
367970 12/04/2015 373788 13 190 M Repair leaking air handler
364727 12/04/2015 366620 14 001 M Remove rust from and refinish steel column base plates
364669 12/04/2015 366493 2 104 M Repair exhaust fan in bathroom
364737 12/04/2015 366643 2 190 M Repair leaking air handler
364723 12/04/2015 366612 6 101A M Repair exhaust fan in bathroom
364697 12/04/2015 366556 7 102C M Repair exhaust fan in bathroom
364696 12/04/2015 366554 7 103C M Repair exhaust fan in bathroom
364695 12/04/2015 366552 7 104C M Repair exhaust fan in bathroom
367962 12/04/2015 373772 00 0000 O String lines in classrooms are only allowed when the string lines are against the wall, a maximum of 2 inches off of the wall
367960 02/25/2015 373768 00 0000 M Fill voids in sidewalk north of bike rack at south property line.
368019 02/25/2015 373892 00 0000 M Repair leaking packing and over pressure relief drain on Fire Main backflows SE of building 3
368012 02/25/2015 373878 00 0000 M Repair uneven sidewalk at large Oak tree between buildings 5, 6, 7, and 8
368002 02/25/2015 373856 10 0000 M Secure loose diamond plate metal cover at bottom of ramp from exterior stage
367972 02/25/2015 373792 10 106 M Clean kitchen hood and provide tag with date cleaned. Last tag dated 6-18-13
368006 02/25/2015 373864 10 180 M Repair emergency eye wash, low flow
367971 02/25/2015 373790 10 182 M Chain both cylinders to wall
367963 02/25/2015 373774 10 184 M Provide current quarterly inspection tag for fire sprinkler system
364691 02/25/2015 366544 10 193 M Mount chemical pump on wall like other 2 chemical pumps. Pump sitting on top of barrel
367961 02/25/2015 373770 10 193A M Repair roof leaks. Concrete ceiling is cracked and leaks
364686 02/25/2015 366533 10 195 M Repair roof leaks. Concrete deck is cracked and leaking
368009 02/25/2015 373871 11 101 M Provide cover on old clock box
368004 02/25/2015 373860 11 190 M Repair leaking air handler
367977 02/25/2015 373803 12 105 M Repair or replace leaking sink faucet
367966 02/25/2015 373780 12 108 M Repair leaking supply line for 1st toilet
368011 02/25/2015 373875 13 002 M Secure center faucet to sink and cover openings on sink bowls, rusting
367982 02/25/2015 373814 17 001 M Floor of chiller compound holds water. Lower drains at bottom of walls to eliminate standing water
368013 02/25/2015 373880 2 0000 M Repair uneven sidewalk from building 2 to building 3
367983 02/25/2015 373816 2 104 M Secure loose handicapped grabrail
364672 02/25/2015 366499 2 180 M Replace leaking water heater. Standing water in drain pan. Water heater removed
368020 02/25/2015 373894 3 0000 M Adjust gate south of building 3 to latch properly, sticky latch
368028 02/25/2015 373912 3 0000 M Determine cause of water damaged ceiling tiles in 2nd floor corridor adjacent to 3-280 and 3-291 and replace tiles
368014 02/25/2015 373882 3 003 M Secure loose inside handrail at intermediate landing for stairs
368021 02/25/2015 373896 3 005 M Provide current quarterly inspection tag for fire sprinkler system
368018 02/25/2015 373890 3 101B M Repair leaking supply line for toilet
368017 02/25/2015 373888 3 105 M Repair drinking fountain, low flow
368016 02/25/2015 373886 3 109B M Repair leaking supply line for toilet
368015 02/25/2015 373884 3 115A M Repair leaking supply line for toilet
367979 02/25/2015 373807 3 116 M Determine cause of water damaged ceiling tiles and replace tiles
367980 02/25/2015 373809 3 116B M Adjust bathroom sink faucet. Shuts off to quickly
367978 02/25/2015 373805 3 190 M Repair leaking air handler
368029 02/25/2015 373914 3 209B M Repair leaking supply line for toilet
368025 02/25/2015 373904 3 211 M Determine cause of water damaged ceiling tiles and replace tiles
368026 02/25/2015 373906 3 213 M Repair or replace leaking faucet
368030 02/25/2015 373916 3 213B M Repair leaking supply line for toilet
368023 02/25/2015 373900 4 102C M Repair emergency escape window to open properly or remove emergency egress sign. Escape window not needed. Space has exit doors. Sign removed
368022 02/25/2015 373898 4 103 M Adjust door to exterior to latch properly
367985 02/25/2015 373820 4 190 M Surge suppressor for panel CB is in fault. Repair or replace surge suppressor
364753 02/25/2015 366676 5 101A M Repair dripping faucet
364721 02/25/2015 366608 5 105C M Secure loose handicapped grabrail
367999 02/25/2015 373850 6 190 M Secure loose fire extinguisher bracket
368001 02/25/2015 373854 6 190 M Adjust door to latch properly, sticky latch
364698 02/25/2015 366558 7 101A M Repair exhaust fan in bathroom
367995 02/25/2015 373841 7 103 M Repair or replace dripping faucet
367987 02/25/2015 373824 7 104C M Replace broken flushing lever for toilet
367996 02/25/2015 373843 7 190 M Adjust door to latch properly, sticky latch
367988 02/25/2015 373827 8 102B M Secure loose handicapped grabrail
367990 02/25/2015 373831 8 104 M Secure loose faucet to sink
367989 02/25/2015 373829 8 104C M Adjust door to latch properly, sticky latch
368007 02/25/2015 373867 10 180 O Prohibit charging batteries in room. Room approved for battery charging
367991 02/25/2015 373833 9 102 O Eliminate multiple outlet extension cord at Teachers station or replace with minimum 15A cord
368005 02/25/2015 373862 11 002 MS Recharge fire extinguisher in corridor
367974 02/25/2015 373796 12 104 MS Adjust corridor door to latch properly
367975 02/25/2015 373798 12 105 MS Adjust corridor door to latch properly
368010 02/25/2015 373873 13 102 MS Adjust corridor door to latch properly. Loose hinge
367969 02/25/2015 373786 13 105 MS Adjust corridor door to latch properly
367984 02/25/2015 373818 2 180 MS Provide current inspection tag for fire extinguisher
368027 02/25/2015 373909 3 202 MS Adjust corridor door to latch properly, sticky latch
368024 02/25/2015 373902 3 292 MS Provide current inspection tag for fire extinguisher
367998 02/25/2015 373847 5 105 MS Adjust corridor door to latch properly
367997 02/25/2015 373845 7 190 MS Provide current inspection tag for fire extinguisher
364788 02/25/2015 366752 11 002 OS Prohibit storing chairs and desks in exit corridor
367964 02/25/2015 373776 12 002 OS Remove and prohibit chairs and desks in exit corridor
367973 02/25/2015 373794 12 104 OS Maintain clear aisle to rear exit. Relocate table and fan
367965 02/25/2015 373778 13 002 OS Remove and prohibit chairs and desks in exit corridor
367994 02/25/2015 373839 7 002 OS Remove and prohibit chairs and desks exit corridor
367993 02/25/2015 373837 8 002 OS Remove and prohibit chairs and desks in exit corridor
367986 02/25/2015 373822 8 101 OS Prohibit blocking open door with wedge or stick on the hinge side of the door between the door and frame. This will damage the door, frame and hinges. Temporarily block door open with a wedge between the bottom of the door and floor
304461 02/25/2015 234689 3 105 CS Provide CO2 fire extinguisher in computer lab
367959 09/26/2014 373765 00 0000 M Repair broken sidewalk at perimeter fence south of building 14
364676 09/26/2014 366511 10 184 M Provide current inspection tag for fire sprinkler system. No annual tags on riser.
364724 09/26/2014 366614 14 001 M Fill around covered play area to eliminate drop off at edge of concrete
364726 09/26/2014 366618 14 190 M Provide screen over vent on wall to keep trash, dirt and bugs out of room
364732 09/26/2014 366631 3 004 M Replace missing ceiling tiles in corridor adjacent to 3-103
364733 09/26/2014 366633 3 004 M Repair leaking plumbing line above ceiling in corridor adjacent to 3-103. Look for wet or missing ceiling tiles
364738 09/26/2014 366645 3 191 M Close and secure lid for card access cabinet
364749 09/26/2014 366668 4 190 M Install screen over louvers on door to keep trash, dirt and bugs out of room
364750 09/26/2014 366670 4 190 M Repair leaking air handler
364710 09/26/2014 366585 5 0000 M Repair leaking irrigation line outside of 5-190
364694 09/26/2014 366550 7 105C M Reset loose ceramic floor tile. Tile secure per Jim Bowen
364725 09/26/2014 366616 14 190 O Clean exhaust fan grate
364760 09/26/2014 366691 3 006 MS Adjust auto closer on fire door at bottom of stairs. Closes too fast
364714 05/19/2014 366594 1 0000 M Provide chain and lock on gate of fencing around A-C equipment outside of 1-115
364673 05/19/2014 366501 10 0000 M Replace cover for 4 inch PVC cleanout north of 10-193
364728 05/19/2014 366622 14 001 M Extend downspouts to prevent storm water from accumulating on covered play area
364711 05/15/2014 366587 00 0000 M Install cap on fire department standpipe connection north of 10-184 adjacent to fire main backflows
364713 05/15/2014 366592 00 0000 M Adjust auto closer on gate between buildings 1 and 2. Closes too fast
364739 05/15/2014 366647 00 0000 M Eliminate fire ant infestation at SE exterior of building 3 adjacent to fire department connection and fire hydrant
364791 05/15/2014 366758 00 0000 M Provide chain and lock on gate of fencing around lift station north of building 14
364771 05/15/2014 366714 00 0000 M Provide chain and lock on gate of fencing around electrical equipment east of building 13
364683 05/15/2014 366527 1 0000 M Provide chain and lock on gate of fencing around A-C equipment outside of 1-101
364668 05/15/2014 366491 1 190 M Close and secure lids for ITV and FA cabinets
364675 05/15/2014 366505 10 0000 M Provide chain and lock on gate of fencing around A-C equipment outside of 10-106K
364682 05/15/2014 366525 10 101 M Secure loose spouts on 2 drinking fountains at main entry
364680 05/15/2014 366521 10 101C M Repair leaking supply line for toilet 2
364681 05/15/2014 366523 10 101C M Caulk handicapped sink to wall
364709 05/15/2014 366583 10 101G M Repair leaking toilet supply line
364692 05/15/2014 366546 10 106C M Provide protective cage around fire sprinkler head in walk-in freezer
364693 05/15/2014 366548 10 106D M Provide protective cage around fire sprinkler head in walk-in cooler
364677 05/15/2014 366513 10 106E M Connect vent to dryer
364678 05/15/2014 366515 10 106G M Seal cracks in corners of bathroom walls. Ceramic tile finish
364679 05/15/2014 366517 10 106H M Seal cracks in corners of bathroom walls. Ceramic tile finish
364674 05/15/2014 366503 10 106J M Open exhaust dampers in dishwashing machine ductwork
364780 05/15/2014 366735 10 180C M Repair leaking toilet supply line
364690 05/15/2014 366542 10 193 M Label all circuits on electrical panel H1
364790 05/15/2014 366756 11 102 M Remove damaged pencil sharpener adjacent to 11-102A
364789 05/15/2014 366754 11 104 M Adjust auto closer on door to exterior. Closes too fast
364786 05/15/2014 366748 11 190 M Close and secure covers for 2 Fire alarm cabinets
364787 05/15/2014 366750 11 190 M Label all circuits on electrical panel EMHF
364774 05/15/2014 366720 12 102 M Replace GFCI outlet that will not trip
364775 05/15/2014 366723 12 102 M Provide cover over old clock box
364772 05/15/2014 366716 12 104 M Remove pencil sharpener without cover at rear door
364794 05/15/2014 366764 12 105 M Replace GFCI outlet that will not trip
364777 05/15/2014 366729 12 107 M Repair leaking supply line for 2nd urinal
364793 05/15/2014 366762 12 190 M Close and secure lid for fire alarm cabinet
364769 05/15/2014 366710 13 002 M Secure loose faucet
364776 05/15/2014 366727 13 106 M Repair leaking supply line for 1st urinal
326626 05/15/2014 283756 13 107 M Provide key lock on storage room inside girls bathroom
364778 05/15/2014 366731 13 180 M Repair door lock. Key spins in cylinder
364792 05/15/2014 366760 13 190 M Close and secure lid for fire alarm cabinet
364717 05/15/2014 366600 15 001 M Repair or replace auto closer on door
364715 05/15/2014 366596 2 0000 M Repair uneven concrete for play area between buildings 2 and 15
364670 05/15/2014 366495 2 101 M Replace GFCI outlet that will not trip
364671 05/15/2014 366497 2 101B M Repair door to open and close properly. Door hits frame
364734 05/15/2014 366637 2 190 M Label all circuits on new electrical panel adjacent to door. No ID on panel
364735 05/15/2014 366639 2 190 M Provide spacers in new electrical panel adjacent to door
364736 05/15/2014 366641 2 190 M Close and secure lids for 2 FA cabinets
364731 05/15/2014 366629 3 001 M Adjust SE door to latch properly
364744 05/15/2014 366658 3 102A M Toilet runs continually. Check flush valve for leaks and repair
364743 05/15/2014 366656 3 107 M Repair or replace lock cylinder. Key will not go in
364741 05/15/2014 366652 3 190 M Repair leaking air handler
364742 05/15/2014 366654 3 190 M Standing water on floor. Check outside air intake for possible leaks and repair
364754 05/15/2014 366679 3 201 M Secure loose drinking fountain
364755 05/15/2014 366681 3 201B M Secure loose faucet
364757 05/15/2014 366685 3 205C M Secure loose toilet seat
364761 05/15/2014 366693 3 210A M Repair leaking toilet supply line
364765 05/15/2014 366701 3 211 M Secure loose faucet
364766 05/15/2014 366703 3 213B M Secure loose toilet seat
364767 05/15/2014 366705 3 214B M Caulk sink to wall
364768 05/15/2014 366707 3 218 M Replace missing ceiling tiles to NW
364758 05/15/2014 366687 3 290 M Anchor air handler at 4 corners
364759 05/15/2014 366689 3 290 M Outside air intake duct is open at corner adjacent to exterior wall. Seal duct
364764 05/15/2014 366699 3 291 M Close and secure lids for fire alarm and ITV cabinets
364762 05/15/2014 366695 3 292 M Provide cover on open electrical junction box above door
364751 05/15/2014 366672 4 190 M Close and secure lid for fire alarm cabinet
364748 05/15/2014 366666 4 191 M Close and secure lid on fire alarm cabinet
364718 05/15/2014 366602 5 190 M Close and secure lids for FA and security cabinets
364719 05/15/2014 366604 5 190 M Time clock for Outside Lights is not working. Clock motor not running
364720 05/15/2014 366606 5 190 M Label all circuits on electrical panel adjacent to fire extinguisher
364722 05/15/2014 366610 6 002 M Determine cause of water damaged ceiling tiles and replace tiles
364699 05/15/2014 366561 7 103 M Repair or replace leaking faucet
364705 05/15/2014 366574 8 102 M Secure loose handicapped grabrail behind toilet
364704 05/15/2014 366572 8 104 M Replace GFCI outlet that will not trip
364701 05/15/2014 366566 8 190 M Install fire extinguisher sitting on floor at maximum five feet above floor adjacent to exit
364702 05/15/2014 366568 8 190 M Close and secure lids on 2 fire alarm cabinets
364703 05/15/2014 366570 8 190 M Adjust door to latch properly. Sticky latch. Room cannot be secured
364707 05/15/2014 366579 9 101A M Determine cause of water damaged ceiling tiles and replace tiles
364706 05/15/2014 366576 9 104 M Secure loose faucet to handicapped sink
364688 05/15/2014 366538 10 180 O Maintain clear access to emergency eye wash - shower
364781 05/15/2014 366737 10 180B O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
364782 05/15/2014 366739 10 180C O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
364756 05/15/2014 366683 3 203 O Remove and prohibit hanging paper on blinds. Paper is acceptable on walls, windows and string lines that are against the wall
364700 05/15/2014 366563 7 103 O Remove and prohibit paper covering window in door
364712 05/15/2014 366590 2 101 C Provide illuminated exit sign at communicating door into 2-102
364667 05/15/2014 366489 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus
364689 05/15/2014 366540 10 106K MS Provide current inspection tag for fire extinguisher
364730 05/15/2014 366626 3 002 MS Provide current inspection tag for fire extinguisher in corridor adjacent to elevator
364740 05/15/2014 366650 3 110 MS Fire extinguisher bracket is behind shelf at far side of room. Relocate fire extinguisher to be adjacent to exit door or remove unneeded extinguisher
364708 05/15/2014 366581 10 102 OS Maintain clear aisles to both stage exits
364687 05/15/2014 366536 10 180 OS Provide clear access to fire extinguisher
364770 05/15/2014 366712 13 103 OS Maintain 3 foot clear aisle to rear exit
364729 05/15/2014 366624 3 004 OS Remove and prohibit storing back packs in corridor
364752 05/15/2014 366674 5 104 OS Maintain 3 foot clear aisle to rear exit
364783 05/15/2014 366741 10 106K CS Provide automatic fire sprinkler coverage for room. No sprinkler visible. Plan does not indicate that walls are rated
364784 02/21/2014 366744 10 106K M Close and secure lids for 2 cabinets
348876 02/21/2014 331793 6 105C M Replace missing cover for fan
348898 01/18/2013 331838 1 120 M Secure loose emergency eye wash sink basin
348862 01/18/2013 331764 10 102 M Replace missing escutcheon on fire sprinkler head adjacent to 10-103
326707 01/18/2013 283934 10 102 M Provide dated flame resistance label on stage curtains (dated July/06)
348865 01/18/2013 331771 10 106 M Replace missing trim piece at top of Delfield reach-in coolers
348864 01/18/2013 331768 10 180 M Adjust flow of emergency eye wash
348889 01/18/2013 331819 11 104 M Adjust door closer on exterior door to control speed of closing door
348888 01/18/2013 331817 11 105 M Adjust door closer on corridor door to control speed of closing door
348886 01/18/2013 331813 12 101A M Anchor toilet to floor
348885 01/18/2013 331811 12 102 M Adjust door closer on exterior door to control speed of closing door
348883 01/18/2013 331807 12 105 M Adjust door closer on exterior door to control speed of closing door
348887 01/18/2013 331815 12 190 M Adjust door closer to control speed of closing door
348882 01/18/2013 331805 14 101 M Replace missing ceiling tiles
348890 01/18/2013 331822 2 101 M Secure loose base on wall adjacent to sink
348891 01/18/2013 331824 3 109A M Replace missing escutcheon on fire sprinkler head
348892 01/18/2013 331826 3 204B M Secure loose toilet seat
348894 01/18/2013 331830 3 205 M Anchor white shelving to wall
348893 01/18/2013 331828 3 206 M Anchor white shelving to wall
348895 01/18/2013 331832 3 211 M Determine cause of water damaged ceiling tiles and replace tiles
348896 01/18/2013 331834 3 214 M Anchor white shelving adjacent to 3-214A to wall
348866 01/18/2013 331773 4 101 M Repair out of order drinking fountain
348867 01/18/2013 331775 4 102C M Remove one latch from emergency escape window
348881 01/18/2013 331803 5 105 M Adjust door closer on corridor door to control speed of closing door
348880 01/18/2013 331801 5 190 M Fill voids in electrical panel D, adjacent to fire extinguisher
348878 01/18/2013 331797 6 102C M Adjust door closer to control speed of closing door
348879 01/18/2013 331799 6 102C M Anchor toilet to floor
348877 01/18/2013 331795 6 103 M Adjust door closer on exterior door to control speed of closing door
348875 01/18/2013 331791 7 102 M Adjust door closer on corridor door to control speed of closing door
348874 01/18/2013 331789 8 101A M Anchor toilet to floor
348872 01/18/2013 331785 8 102 M Pad and mark corners of VCR unit which are lower than 6 feet 8 inches
348873 01/18/2013 331787 8 103 M Pad and mark corners of VCR unit which are lower than 6 feet 8 inches
348870 01/18/2013 331781 8 103B M Anchor toilet to floor
348869 01/18/2013 331779 8 105 M Pad and mark corners of VCR unit which are lower than 6 feet 8 inches
348868 01/18/2013 331777 8 105B M Repair light fixture in bathroom
348863 01/18/2013 331766 10 106 MS Recharge fire extinguisher adjacent to exterior door
326604 01/18/2013 283712 10 106 MS Provide current inspection tag for kitchen hood fire suppression system
348897 01/18/2013 331836 3 280 MS Replace Co2 fire extinguisher with ABC fire extinguisher
348871 01/18/2013 331783 8 102 MS Recharge fire extinguisher
326617 01/18/2013 283738 00 0000 CS Provide suitable area for recharging batteries for golf carts and floor cleaning machines
326736 12/15/2011 283993 00 0000 M Keep all mechanical rooms lock to prohibit unauthorized access (2-190, 6-190, 11-190, 12-190 & 13-190)
326605 12/15/2011 283714 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
326705 12/15/2011 283929 00 9599 M Install cap on fire department standpipe connection at SE corner of Bldg. 3
326733 12/15/2011 283988 00 9599 M Provide cover for clean-out in ground adjacent to 2-190
326606 12/15/2011 283716 10 105 M Replace missing ceramic tile on wall at NE pass through between serving area and kitchen
326628 12/15/2011 283761 11 104 M Adjust exterior door to latch properly
326619 12/15/2011 283743 13 190 M Repair door lock to work properly
326703 12/15/2011 283925 14 190 M Provide current inspection log for hot water heater - water leak
326787 12/15/2011 284105 15 0000 M Paint building number on exterior wall to be visible to fire rescue - storage Bldg. adjacent to Bldg. 2
326788 12/15/2011 284107 17 0000 M Change building number from 15 to 17 on exterior wall to match FISH map and to be visible to fire rescue - Chillers Bldg.
323566 12/15/2011 276449 2 190 M Replace missing belt guard on air handler
323567 12/15/2011 276451 2 190 M Repair leaking valve on cold water return line on air handler unit
326609 12/15/2011 283723 3 005 M Replace missing magnetic hold open devise hardware for fire door at bottom of stairwell
326614 12/15/2011 283732 4 101 M Adjust exterior door to latch properly at west end of media center
326706 12/15/2011 283932 4 102C M Provide sign indicating emergency escape window
326700 12/15/2011 283919 7 190 M Repair lock on door to work properly
326696 12/15/2011 283911 8 190 M Repair door lock to work properly lock sticks
326610 12/15/2011 283725 9 104 M Repair broken grille for vent on exterior wall adjacent to sink in boys bathroom
326743 12/15/2011 284009 12 102 O Remove and prohibit combustible curtains or provide certification that material is flame retardant
326741 12/15/2011 284003 12 105 O Remove and prohibit combustible curtains or provide certification that material is flame retardant
326748 12/15/2011 284015 12 105 O Remove and prohibit combustible residential armchair or provide certification that material is flame retardant
326629 12/15/2011 283763 12 105 O Prohibit plugging surge protector into surge protector at teacher's station - plug each surge protector directly into wall outlet
326739 12/15/2011 283996 12 106 O Remove and prohibit combustible curtains or provide certification that material is flame retardant
326601 12/15/2011 283706 3 101 O Remove glass mirror adjacent to sink or provide mirror made of tempered glass, safety glass, or stainless steel
326594 12/15/2011 283691 3 202 O Eliminate brown extension cord with multiple outlet end for lamp at teacher's desk or replace with a surge protector
326595 12/15/2011 283693 3 203 O Eliminate white extension cord with multiple outlet end at teacher's desk or replace with a surge protector
326598 12/15/2011 283700 3 216A O Replace burned out bulbs in light fixture
326596 12/15/2011 283696 3 218 O Replace burned out light bulbs in two light fixtures
326745 12/15/2011 284011 5 105 O Remove and prohibit combustible curtains or provide certification that material is flame retardant
326702 12/15/2011 283923 6 103 O Remove and prohibit black vinyl table skirt (X2)
326701 12/15/2011 283921 6 105 O Prohibit plugging extension cord into surge protector - plug extension cord directly into wall outlet
326611 12/15/2011 283727 9 102 O Remove glass mirrors adjacent to sink in arts classroom or provide mirrors made of tempered glass, safety glass, or stainless steel (X2)
326710 12/15/2011 283939 1 122 C Make necessary repairs as indicated on CCTV studio rigging inspection report
326708 12/15/2011 283936 10 102 C Make necessary repairs as indicated on stage rigging inspection report dated 4/28/09
326704 12/15/2011 283927 00 9599 MS Provide padlock on PIV,and chain & padlock on OS&Y water main at SE corner of Bldg. 3
326607 12/15/2011 283718 10 105 MS Replace type K fire extinguisher with an ABC fire extinguisher in serving area
326603 12/15/2011 283710 10 184 MS Provide current inspection tag for fire sprinkler system - tagged quarterly 6/1/2011
326699 12/15/2011 283917 12 104 MS Adjust corridor door to latch properly
326621 12/15/2011 283748 12 190 MS Provide current inspection tag for fire extinguisher
326620 12/15/2011 283745 13 102 MS Adjust corridor door to latch properly
326602 12/15/2011 283708 3 005 MS Provide current inspection tag for fire sprinkler system - tagged quarterly 6/1/2011
326608 12/15/2011 283721 3 005 MS Adjust fire door at bottom of stairwell to latch properly
326615 12/15/2011 283735 10 180 OS Prohibit charging batteries in room
326698 12/15/2011 283915 11 102 OS Immediately remove hasp and padlock from exit door in corridor
326627 12/15/2011 283759 12 106 OS Prohibit use of wedge as hold open device on corridor door to prevent spread of smoke or fire
326600 12/15/2011 283704 3 210A OS Remove cart from bathroom
326612 12/15/2011 283729 3 213 OS Prohibit use of wedge as hold open device on corridor door to prevent spread of smoke or fire
326599 12/15/2011 283702 3 214 OS Rearrange desks to maintain 3 ft clear aisle to corridor door
326597 12/15/2011 283698 3 216C OS Remove bookcase from bathroom
304905 04/28/2011 235656 10 106D M Adjust door of walk-in refrigerator to close properly, door drags on floor
323578 04/28/2011 276473 12 104 M Repair or replace auto closer on exterior exit door (door slams shut with too much force)
323572 04/28/2011 276461 3 003 M Repair broken vinyl base at upper landing of stairway
323570 04/28/2011 276457 3 109 M Replace missing cap on drinking fountain at sink
323568 04/28/2011 276453 3 191 M Provide cover on exposed electrical junction box at ceiling
323575 04/28/2011 276467 5 100 M Replace missing ceiling tiles in entrance corridor
323576 04/28/2011 276469 7 100 M Replace missing ceiling tiles in corridor by entrance door
323577 04/28/2011 276471 8 105 M Repair or replace leaking auto closer on door, and adjust closer so door does not slam shut
323565 04/28/2011 276447 1 109 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
323579 04/28/2011 276475 12 106 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
323573 04/28/2011 276463 3 210 O Remove and prohibit flammable curtains and window covering
323569 04/28/2011 276455 3 0000 OS Prohibit use of hold open devices (wedges) on corridor doors in all classrooms
323571 04/28/2011 276459 3 113A OS Remove and prohibit use of toaster oven or prohibit student access to room
323564 04/28/2011 276445 1 116 FS Provide heat detector in normally unoccupied space
323574 04/28/2011 276465 5 106 FS Secure hanging heat detector
304904 04/12/2010 235653 10 106C M Adjust door of walk-in freezer to close properly, door drags on floor
304903 04/12/2010 235646 10 191 M Repair damaged/cut insulation on hot water return line
304898 04/12/2010 235635 11 102B M Repair exhaust fan in bathroom
304897 04/12/2010 235633 11 103C M Repair exhaust fan in bathroom
304894 04/12/2010 235627 11 104C M Repair exhaust fan in bathroom
304895 04/12/2010 235629 11 104C M Replace missing piece (guard) of exhaust fan in bathroom
304891 04/12/2010 235620 11 190 M Repair door hardware, door handle is missing
304883 04/12/2010 235604 12 107 M Secure light fixture cover
304889 04/12/2010 235616 13 102 M Remove inappropriate sign indicating emergency escape window. Window is not designed as an emergency window
304887 04/12/2010 235612 13 104A M Remove tape from heat detector
304487 04/12/2010 234751 2 190 M Repair leaking air handler unit
304468 04/12/2010 234708 3 116A M Determine cause of water damaged ceiling tiles and replace tiles
304479 04/12/2010 234733 3 190 M Repair door to close properly
304558 04/12/2010 234874 5 001 M Secure loose ceiling tiles adjacent to 5-106
304768 04/12/2010 235351 5 102 M Provide cover on exposed electrical junction box adjacent to computers
304769 04/12/2010 235355 5 102B M Repair exhaust fan in bathroom
304767 04/12/2010 235348 5 103 M Repair broken/deteriorated base along wall adjacent to 5-103C
304559 04/12/2010 234876 5 105C M Repair exhaust fan in bathroom
304770 04/12/2010 235358 6 002 M Replace missing ceiling tiles
304777 04/12/2010 235370 6 103C M Repair exhaust fan in bathroom
304786 04/12/2010 235389 7 190 M Repair door to close and latch properly
304807 04/12/2010 235431 8 102B M Repair exhaust fan in bathroom
304809 04/12/2010 235435 8 105 M Provide cover on exposed electrical junction box under computers
304788 04/12/2010 235393 8 106 M Repair light fixture, lights do not work
304907 04/12/2010 235660 9 101 M Determine cause of water damaged ceiling tiles and replace tiles
304902 04/12/2010 235644 00 0000 O No access was available to these rooms. Please be prepared to access these rooms during the report review meeting
304906 04/12/2010 235658 1 101 O Remove and prohibit air freshener
304908 04/12/2010 235662 1 111 O Remove and prohibit air freshener
304488 04/12/2010 234754 1 120 O Remove and prohibit air freshener
304899 04/12/2010 235637 10 180 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
304900 04/12/2010 235639 10 180 O Prohibit plugging orange extension cord into surge protector
304901 04/12/2010 235641 10 184 O Provide clear access to fire sprinkler riser
297003 04/12/2010 218486 11 104 O Remove and prohibit combustible beanbag chairs
304884 04/12/2010 235606 12 104 O Prohibit brown 13A extension cord @ projector or replace with minimum 15A cord
304888 04/12/2010 235614 13 103 O Eliminate string line below 6'8
304886 04/12/2010 235610 13 105 O Prohibit white 13A extension cord under computers or replace with minimum 15A single outlet cord or surge protector
304554 04/12/2010 234865 2 102 O Prohibit brown 13A extension cord @ radio or replace with minimum 15A cord
304456 04/12/2010 234679 3 0000 O Prohibit covering mounted egress maps with other evacuation maps, hang additional maps adjacent to mounted egress maps
304452 04/12/2010 234669 3 101 O Provide certification that residential furniture has been treated with approved flame retardant or remove and prohibit combustible (residential) furniture
304448 04/12/2010 234666 3 102 O Maintain separate bathroom facilities for males and females
304447 04/12/2010 234664 3 102A O Remove and prohibit air freshener
304439 04/12/2010 234635 3 104A O Maintain separate bathroom facilities for males and females
304471 04/12/2010 234714 3 116 O Remove and prohibit combustible beanbag chairs
304481 04/12/2010 234737 3 201 O Prohibit multi outlet electrical adaptor behind teacher's desk or replace with minimum 15A single outlet cord or approved surge protector
304484 04/12/2010 234743 3 205 O Remove and prohibit combustible (residential rattan chair and table) furniture
304472 04/12/2010 234717 3 216A O Maintain separate bathroom facilities for males and females
304556 04/12/2010 234870 4 101 O Prohibit plugging surge protector into extension cord @ palm trees
304557 04/12/2010 234872 4 101 O Remove and prohibit combustible beanbag chairs
304565 04/12/2010 234887 5 103 O Prohibit plugging surge protector into surge protector adjacent to raised platform area
304778 04/12/2010 235374 6 102 O Prohibit plugging surge protector into surge protector @ computers
304775 04/12/2010 235366 6 104 O Prohibit plugging surge protector into surge protector adjacent to raised platform area
304772 04/12/2010 235360 6 105 O Prohibit plugging surge protector into surge protector adjacent to raised platform area
304802 04/12/2010 235421 8 104 O Prohibit plugging surge protector into surge protector @ computer adjacent to raised platform area
304794 04/12/2010 235397 8 105 O Prohibit white 13A extension cord (plugged into surge protector). Prohibit plugging surge protector into tan extension cord. Use only 15A single outlet extension cord plugged directly into a permanent electrical outlet
269900 04/12/2010 160351 12 103 C Provide illuminated exit sign at exterior door
304910 04/12/2010 235666 10 193 MS Provide current inspection tag for fire extinguisher
304909 04/12/2010 235664 10 193A MS Provide current inspection tag for fire extinguisher
304811 04/12/2010 235439 14 101 MS Provide current inspection tag for fire extinguisher
296985 04/12/2010 218449 10 191 OS Remove storage from boiler room
269897 04/12/2010 160345 11 103 OS Relocate table and storage blocking clear path to exterior door
304896 04/12/2010 235631 11 103A OS Prohibit storage of flammable materials (sterno)
304892 04/12/2010 235623 11 190 OS Remove storage from mechanical room
304893 04/12/2010 235625 11 190 OS Prohibit charging batteries in room
297007 04/12/2010 218495 12 109 OS Remove storage from electrical room
304890 04/12/2010 235618 13 102 OS Maintain clear aisle to exit doors
297014 04/12/2010 218509 13 108 OS Remove storage from electrical room
304885 04/12/2010 235608 13 190 OS Remove storage from mechanical room
304812 04/12/2010 235443 14 190 OS Remove storage from electrical room
296972 04/12/2010 218423 2 001 OS Remove and prohibit use of toaster oven
304441 04/12/2010 234652 3 102A OS Remove and prohibit candles
304469 04/12/2010 234711 3 116 OS Maintain clear aisle to exit
304478 04/12/2010 234731 3 190 OS Prohibit charging batteries in room
304480 04/12/2010 234735 3 201 OS Remove and prohibit candle
304475 04/12/2010 234723 3 211 OS Prohibit hold open devices on fire door
304474 04/12/2010 234720 3 216C OS Prohibit flammable plastic tablecloth
304477 04/12/2010 234729 3 280 OS Remove and prohibit unnecessary CO2 fire extinguisher in custodial closet
304773 04/12/2010 235363 6 105 OS Remove and prohibit candles
304782 04/12/2010 235376 7 105 OS Prohibit flammable plastic curtain
304805 04/12/2010 235426 8 102B OS Maintain clear aisle to exterior door
304799 04/12/2010 235414 8 104 OS Maintain clear aisle corridor door
297004 11/18/2009 218489 11 103 O Remove and prohibit combustible beanbag chairs
296975 11/18/2009 218429 3 111 O Remove and prohibit combustible furniture (round rattan chair with fabric cushion)
296970 11/18/2009 218419 00 0000 C Provide exterior signage indicating property address
297005 11/18/2009 218491 11 102 OS Maintain clear aisle to exterior exit door
296983 04/27/2009 218445 10 180 M Chain Helium cylinders to wall
296981 04/27/2009 218441 10 180B M Replace broken toilet seat
296982 04/27/2009 218443 10 180C M Replace broken toilet seat
297008 04/27/2009 218497 12 101 M Replace missing ceiling tiles
297009 04/27/2009 218499 12 190 M Provide cover on exposed electrical junction box
297010 04/27/2009 218501 13 0000 M Provide cover on exposed electrical junction box on exterior wall @ main entrance door
296978 04/27/2009 218435 3 207 M Determine cause of water damaged ceiling tiles and replace tiles
296980 04/27/2009 218439 4 101 M Repair southeast exterior exit door to close properly
296993 04/27/2009 218465 6 102 M Determine cause of water damaged ceiling tiles and replace tiles
297000 04/27/2009 218480 8 103 M Repair corridor door to close and latch properly
296999 04/27/2009 218478 8 104 M Repair corridor door to close and latch properly
296984 04/27/2009 218447 10 184 O Provide clear access to fire sprinkler riser piping
296995 04/27/2009 218469 7 105 O Prohibit plugging surge protector into surge protector at computer table
274967 04/27/2009 171460 10 184 MS Provide current inspection tag for fire sprinkler system
296987 04/27/2009 218453 10 190 MS Provide current inspection tag for fire extinguisher
296988 04/27/2009 218455 10 192 MS Provide current inspection tag for fire extinguisher
296989 04/27/2009 218457 10 193 MS Provide current inspection tag for fire extinguisher
296990 04/27/2009 218459 10 193A MS Provide current inspection tag for fire extinguisher
296971 04/27/2009 218421 2 180 MS Provide current inspection tag for fire extinguisher
296973 04/27/2009 218425 3 003 MS Repair fire doors at bottom landing of stairway to close properly
274904 04/27/2009 171330 3 005 MS Provide current inspection tag for fire sprinkler system
296976 04/27/2009 218431 3 110 MS Provide current inspection tag for fire extinguisher
296974 04/27/2009 218427 3 113A MS Provide current inspection tag for fire extinguisher
296979 04/27/2009 218437 3 280 MS Provide current inspection tag for fire extinguisher
296991 04/27/2009 218461 5 190 MS Provide current inspection tag for fire extinguisher
296986 04/27/2009 218451 10 190 OS Remove storage from mechanical room
297013 04/27/2009 218507 13 102 OS Maintain clear aisle to exterior exit door
297012 04/27/2009 218505 13 105 OS Relocate storage blocking exterior exit door
297001 04/27/2009 218482 14 101 OS Prohibit storage of gasoline powered leaf blower
296977 04/27/2009 218433 3 203 OS Prohibit running electrical cord through cabinet door
296992 04/27/2009 218463 6 104 OS Maintain clear aisle to exterior exit door (relocate desk)
296997 04/27/2009 218474 7 102 OS Remove storage blocking exterior exit door
296996 04/27/2009 218472 7 102A FS Secure hanging heat detector
269844 02/04/2009 160219 3 0000 OS Prohibit wedging open all corridor doors
274910 02/04/2009 171343 6 002 OS Prohibit storage of tables and chairs in corridor
274963 03/07/2008 171447 00 9698 M Replace missing caps on fire department standpipe connection north of driveway north of Building 10
274946 03/07/2008 171419 10 101D M Replace missing ceiling tiles
274956 03/07/2008 171443 10 190 M Provide cover on exposed electrical junction boxes (X2)
274916 03/07/2008 171356 14 101 M Determine cause of water damaged ceiling tiles and replace tiles
274899 03/07/2008 171311 3 109 M Repair or replace frayed cord on refrigerator
274901 03/07/2008 171325 3 110 M Replace missing ceiling tiles
274909 03/07/2008 171341 3 208 M Secure cover on exposed electrical junction box on north wall
274908 03/07/2008 171339 3 212 M Determine cause of water damaged ceiling tiles and replace tiles
274941 03/07/2008 171407 9 102 M Adjust exterior exit door to latch properly
274930 03/07/2008 171386 9 190 M Repair or replace rusted door on mechanical room
269861 03/07/2008 160262 10 184 O Arrange storage to maintain clear path to fire sprinkler riser and test valves
274919 03/07/2008 171362 11 102 O Eliminate multiple outlet extension cords (X2) at teachers desk
274944 03/07/2008 171414 4 102A O Prohibit plugging microwave oven into extension cord - plug directly into permanent electrical outlet
274914 03/07/2008 171352 6 103 O Prohibit plugging surge protector into surge protector
274936 03/07/2008 171395 9 101 C Install maximum occupancy signage in music room (max. occ. = 76)
274923 03/07/2008 171370 13 106 F Replace missing fire alarm strobe/horn in bathroom
274953 03/07/2008 171437 10 106 MS Provide current inspection tag for kitchen hood fire suppression system
274951 03/07/2008 171430 10 106J MS Provide current inspection tag for fire extinguisher
274954 03/07/2008 171440 10 193 MS Provide current inspection tag for fire extinguisher
274900 03/07/2008 171323 3 110 MS Provide current inspection tag for fire extinguisher
274915 03/07/2008 171354 00 0000 OS Prohibit hold open devices (floor wedges) on corridor doors in all classroom buildings
274921 03/07/2008 171365 11 102 OS Maintain clear aisle to exterior exit door
274906 03/07/2008 171335 3 203 OS Remove and prohibit use of toaster oven
274912 03/07/2008 171347 6 103 OS Relocate tables and chairs blocking egress at exterior exit door
274911 03/07/2008 171345 6 105 OS Relocate tables and chairs blocking egress at exterior exit door
274942 03/07/2008 171412 9 102 CS Provide fire extinguisher at door of kiln room
274902 10/25/2007 171328 3 102 M Replace missing escutcheon on fire sprinkler head
269872 10/25/2007 160286 2 101 C Provide illuminated exit sign at primary exit
269871 04/20/2007 160284 00 0000 M Remove "Emergency Escape" signs from windows in each classroom in pod buildings 5-8 & 11-13
269873 04/20/2007 160288 00 9599 M Provide padlocks on gates of all fence enclosures for electrical units, mechanical units and refrigerent units
269866 04/20/2007 160274 10 101E M Adjust exterior door to latch properly
269856 04/20/2007 160249 10 180D M Replace missing ceiling tiles
269862 04/20/2007 160264 10 182 M Chain cylinder to wall
269902 04/20/2007 160355 12 109 M Change sign indicating room name from Storage to Electrical Room
269907 04/20/2007 160366 13 104 M Provide cover on exposed electrical junction box at old clock
269906 04/20/2007 160364 13 106 M Secure loose toilet in handicapped stall
269912 04/20/2007 160376 13 108 M Change sign indicating room name from Storage to Electrical Room
269905 04/20/2007 160361 13 180 M Repair lock cylinder - lock spins in doorknob - no access to room
269875 04/20/2007 160292 2 102 M Reverse door handle on door into common area so that lock is on outside of classroom
269850 04/20/2007 160231 3 109A M Chain cylinder to wall
269892 04/20/2007 160333 5 102 M Secure loose power pole and cover open box - wires are exposed
269890 04/20/2007 160331 5 103C M Repair exhaust fan in bathroom
269887 04/20/2007 160323 5 190 M Provide correct bracket for fire extinguisher
269882 04/20/2007 160313 6 106 M Remove extra fire extinguishers from floor or relocate to custodial receiving area
269881 04/20/2007 160311 7 180 M Repair door to open/close properly
269877 04/20/2007 160296 8 102 M Determine cause of water damaged ceiling tiles and replace tiles
269869 04/20/2007 160280 8 105 M Adjust door closer for exterior door to control speed of closing door
269870 04/20/2007 160282 8 105 M Anchor metal shelving adjacent to 8-105B or remove shelving
269849 04/20/2007 160229 10 103 O Remove and prohibit toaster oven
269865 04/20/2007 160272 10 106B O Remove storage within 18" of fire sprinkler heads
269895 04/20/2007 160340 11 104 O Eliminate extension cord or replace with minimum 15A cord
269904 04/20/2007 160359 12 101A O Remove and prohibit air freshener spray
269911 04/20/2007 160374 13 102 O Remove and prohibit combustible (residential) chair
269910 04/20/2007 160372 13 102A O Replace bulbs in light fixture
269914 04/20/2007 160380 13 108 O Replace bulbs in light fixture
269864 04/20/2007 160269 2 101 O Remove or secure curled rug
269874 04/20/2007 160290 2 102 O Remove and prohibit combustible beanbag chairs
269853 04/20/2007 160237 3 102 O Prohibit covering signs indicating bathroom names and numbers and prohibit labeling rooms as Adult and Student - separate Male and Female bathrooms are required
269854 04/20/2007 160239 3 102A O Remove excessive storage from bathroom
269852 04/20/2007 160235 3 102A O Relocate file cabinet and table blocking clear path to Girls' Bathroom
269855 04/20/2007 160241 3 118 O Remove and prohibit toaster oven
269847 04/20/2007 160225 3 201 O Remove and prohibit toaster oven
269848 04/20/2007 160227 3 209 O Prohibit plugging refrigerator into extension cord
269846 04/20/2007 160223 3 214 O Provide verification that written permission from principal has been provided to keep guinea pig in the classroom and that all required safety precautions are being followed. Animal may only be kept in room as part of a particular curriculum and removed when that curriculum is complete.
269845 04/20/2007 160221 3 216A O Remove storage shelving from bathroom vestibule that projects into clear width of door opening
269894 04/20/2007 160338 5 101A O Remove and prohibit air freshener spray
269893 04/20/2007 160336 5 102 O Prohibit plugging surge protector into surge outlet adaptor
269886 04/20/2007 160321 5 190 O Replace bulbs in light fixtures
269885 04/20/2007 160319 6 101A O Remove and prohibit air freshener spray
269883 04/20/2007 160315 6 102 O Remove and prohibit combustible beanbag chairs
269878 04/20/2007 160299 8 101 O Remove and prohibit toaster oven
269860 04/20/2007 160260 8 103 O Eliminate extension cord or replace with minimum 15A cord
269868 04/20/2007 160278 9 102 O Remove or secure curled floor mat outside entrance doors
269915 04/20/2007 160382 P 0000 C All portables are scheduled for demolition and not occupied at time of inspection. Portables were not inspected. Provide inspection by Bldg. Dept. prior to occupancy if demolition plans change.
269859 04/20/2007 160258 2 101B F Secure heat detector that is hanging by wires
269863 04/20/2007 160266 00 9599 MS Provide knox padlock on fence gates to allow fire department access
269857 04/20/2007 160251 10 180 OS Remove storage blocking clear access to fire alarm pull station
269858 04/20/2007 160256 10 180E OS Prohibit storage of gas powered pressure cleaner in caged storage area
269896 04/20/2007 160342 11 104 OS Remove storage blocking clear path to exterior door
269901 04/20/2007 160353 12 103 OS Arrange tables to provide minimum 3' wide clear path to exterior door
269903 04/20/2007 160357 12 109 OS Remove storage from electrical room
269898 04/20/2007 160347 12 190 OS Remove storage blocking clear access to fire extinguisher
269899 04/20/2007 160349 12 190 OS Remove old light bulbs stored in mechanical room
269908 04/20/2007 160368 13 102 OS Provide minimum 3' wide clear path from corridor door to exterior door
269909 04/20/2007 160370 13 102 OS Remove TV cart blocking clear access to exterior door
269913 04/20/2007 160378 13 108 OS Remove storage from electrical room
269851 04/20/2007 160233 3 004 OS Remove desk from corridor adjacent to 3-005
269889 04/20/2007 160329 5 103 OS Provide minimum 3' wide clear path to exterior door
269888 04/20/2007 160325 5 105 OS Provide minimum 3' wide clear path to exterior door
269884 04/20/2007 160317 6 102 OS Arrange desks to provide minimum 3' wide clear path from corridor door to exterior door
269880 04/20/2007 160303 7 103 OS Remove flag covering exterior door and keep blinds across exterior door open when room is occupied
269879 04/20/2007 160301 7 105 OS Remove TV cart blocking clear path to exterior door
269876 04/20/2007 160294 8 102 OS Arrange desks to provide minimum 3' wide clear path from corridor door to exterior door
269867 04/20/2007 160276 9 101 OS Arrange chairs to provide minimum 3' wide clear path to exterior (rear) door
193439 02/15/2007 10355 00 0000 M Provide verification that all student occupied spaces have emergency lights and all are operable
193463 02/15/2007 31713 9 008 M Replace extension cord to TV box with permanent wiring and remove cord that has exposed wires
193468 02/15/2007 10402 P 691 M Repair damaged rain downspout at northwest side of portable
203744 02/15/2007 78227 1 022 O Eliminate extension cord powering refrigerator
203745 02/15/2007 78228 4 010 O Eliminate multiple extension cord powering computers or have maintenance install additional electrical outlets
193442 02/15/2007 10324 00 9599 C Provide fence around drainage/retention pond @ south east corner of campus
257122 02/15/2007 135500 00 9599 C Turn barbs down on fencing at bike racks
246501 02/15/2007 112716 4 001 C Provide illuminated exit sign above new exterior exit door @ southeast corner of room
193472 02/15/2007 31723 P 116 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
193480 02/15/2007 31725 P 1866 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
246547 02/15/2007 112809 P 3648 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
193476 02/15/2007 31724 P 4188 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
246545 02/15/2007 112805 P 468 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
246553 02/15/2007 112821 P 627 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
246548 02/15/2007 112811 P 628 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
246551 02/15/2007 112817 P 750 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
246546 02/15/2007 112807 P 754 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
203758 02/15/2007 78252 6 009 OS Prohibit hold open devices on hallway doors
246520 02/15/2007 112753 7 008 OS Remove storage from mechanical room
246522 02/15/2007 112757 7 009 OS Prohibit hold open devices on corridor doors
246534 02/15/2007 112781 9 009 OS Prohibit hold open devices on all corridor doors
261892 02/02/2007 144170 P 1866 N/A No violations observed
261888 02/02/2007 144166 P 3648 N/A No violations observed
261893 02/02/2007 144171 P 3676 N/A No violations observed
261889 02/02/2007 144167 P 4188 N/A No violations observed
261883 02/02/2007 144161 P 468 N/A No violations observed
261891 02/02/2007 144169 P 597 N/A No violations observed
261884 02/02/2007 144162 P 627 N/A No violations observed
261885 02/02/2007 144163 P 628 N/A No violations observed
261890 02/02/2007 144168 P 691 N/A No violations observed
261886 02/02/2007 144164 P 750 N/A No violations observed
261887 02/02/2007 144165 P 754 N/A No violations observed
246483 04/13/2006 112675 1 012B M Provide lock on door leading into room used for construction storage
203722 04/13/2006 78191 10 005 M Patch hole on ceiling
203729 04/13/2006 78200 11 012 M Repair exterior doors to close properly
246503 04/13/2006 112720 3 004 M Chain helium cylinder to wall
246495 04/13/2006 112702 4 008 M Repair emergency escape window to open properly and remove bush outside window
246527 04/13/2006 112768 8 002A M Adjust door to latch properly
246529 04/13/2006 112771 8 002A M Repair non-working ventilation fan in bathroom
246541 04/13/2006 112795 P 116 M Replace missing ceiling tile
246554 04/13/2006 112823 P 627 M Repair ramp door to close properly
246549 04/13/2006 112813 P 628 M Repair emergency lighting
246550 04/13/2006 112815 P 628 M Determine cause of water damaged ceiling tiles and replace tiles
246542 04/13/2006 112799 P 691 M Repair stair door to close properly (drags on threshold)
246552 04/13/2006 112819 P 750 M Repair stair door to latch properly
246477 04/13/2006 112666 1 012 O Eliminate extension cord powering microwave oven
246484 04/13/2006 112679 1 012A O Eliminate plugging microwave and refrigerator into surge protector
203747 04/13/2006 78230 10 004 O Eliminate 13 amp extension cord powering recorder or replace with a minimum 15 amp cord
246505 04/13/2006 112723 3 001A O Eliminate extension cord powering surge protector
246536 04/13/2006 112785 9 006 O Prohibit hot plate in room
246471 04/13/2006 112649 00 0000 MS Provide current inspection tag for fire extinguishers
246493 04/13/2006 112685 1 0000 MS Provide key to gate in construction fencing to allow secondary egress from 1-012A (fencing with gate locked does not allow emergency egress from area, issue key to each teacher in building)
246539 04/13/2006 112792 11 004 OS Maintain clear aisle to exterior door
246555 04/13/2006 112825 12 007 OS Remove storage from mechanical room
246506 04/13/2006 112727 4 012 OS Remove storage from mechanical room
246512 04/13/2006 112738 5 001 OS Maintain clear aisle to exterior door
246513 04/13/2006 112740 5 008 OS Remove storage from mechanical room
246519 04/13/2006 112751 6 003 OS Maintain clear aisle to exterior door
246515 04/13/2006 112743 6 008 OS Remove storage from mechanical room
246530 04/13/2006 112773 8 004 OS Maintain clear aisle to exterior door
246523 04/13/2006 112760 8 008 OS Remove storage from mechanical room
246531 04/13/2006 112775 9 008 OS Remove storage from mechanical room
246532 04/13/2006 112778 9 008 OS Prohibit charging batteries in room
193465 02/28/2006 31718 P 3673 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
193482 02/28/2006 31726 P 3676 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
193469 02/28/2006 31720 P 3994 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
193471 02/28/2006 31721 P 597 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
193467 02/28/2006 31719 P 691 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
193444 01/09/2006 31727 1 006 M Repair exhaust fan in bathroom
203748 01/09/2006 78232 1 006 M Repair cover on ventilation fan in bathroom
203749 01/09/2006 78234 1 008 M Repair cover on ventilation fan in bathroom
203724 01/09/2006 78195 2 001 M Repair all entrance doors to close properly
203725 01/09/2006 78196 4 005 M Repair exterior door to close properly
203726 01/09/2006 78197 6 009 M Repair exterior doors to close properly
203774 01/09/2006 78283 P 116 M Repair exterior siding on east wall by ramp
193479 01/09/2006 10408 P 1866 M Provide center hurricane ties
203740 01/09/2006 78217 P 1866 M Repair emergency lighting
203798 01/09/2006 78338 P 3673 M Repair exterior siding on north side of portable
203741 01/09/2006 78222 P 3994 M Repair emergency lighting
193475 01/09/2006 10407 P 4188 M Provide center hurricane ties
203742 01/09/2006 78224 P 691 M Repair emergency lighting
203743 01/09/2006 78226 1 004 O Eliminate extension cord powering TV
203756 01/09/2006 78248 7 007 O Remove and prohibit combustible beanbag chairs from storage room
203755 01/09/2006 78246 P 3673 O Remove and prohibit excessive flammable decorations
193450 01/09/2006 10305 2 015 OS Remove storage from mechanical room (cafeteria)
193451 01/09/2006 31708 2 016A OS Remove storage from electrical room
203759 01/09/2006 78254 3 003 OS Chain helium tank to wall
203714 12/15/2004 78182 1 021 M Determine cause of water damaged ceiling tiles and replace tiles
193446 12/15/2004 31737 11 009 M Repair rusted door frame
203750 12/15/2004 78236 2 001 M Reattach fire extinguisher to wall @ east entrance doors
203762 12/15/2004 78260 4 012 M Provide cover on exposed electrical junction box
193457 12/15/2004 61332 4 012 M Remove hasp and padlock from mechanical room door
203715 12/15/2004 78183 5 001 M Determine cause of water damaged ceiling tiles and replace tiles
203716 12/15/2004 78184 5 002 M Determine cause of water damaged ceiling tiles and replace tiles
203757 12/15/2004 78250 5 004 M Adjust cabinet doors to close properly
203717 12/15/2004 78185 6 002 M Determine cause of water damaged ceiling tiles and replace tiles
203718 12/15/2004 78186 6 003 M Determine cause of water damaged ceiling tiles and replace tiles
203738 12/15/2004 78213 7 009 M Scure dangling light fixture into ceiling tile in hallway
203739 12/15/2004 78215 8 009 M Secure hanging light fixture
203719 12/15/2004 78187 8 009 M Determine cause of water damaged ceiling tiles and replace tiles in entrance corridor
203727 12/15/2004 78198 8 009 M Repair exterior doors to close properly
203731 12/15/2004 78204 9 004 M Repair door to close properly
203728 12/15/2004 78199 9 009 M Repair exterior doors to close properly
203761 12/15/2004 78258 P 1866 M Secure and protect insulation on portable unit
203760 12/15/2004 78256 P 3673 M Pad and mark corners of A/V unit which are lower than 6'8"
203720 12/15/2004 78188 P 3676 M Determine cause of water damaged ceiling tiles and replace tiles
203721 12/15/2004 78189 P 3994 M Determine cause of water damaged ceiling tiles and replace tiles
203746 12/15/2004 78229 6 004 O Eliminate extension cord powering refrigerator
203771 12/15/2004 78277 7 001 O Post sign indicating evacuation routes
203723 12/15/2004 78193 9 003 O Remove and prohibit paper covering window in door
193473 12/15/2004 31716 P 116 O Remove floor tile used as a sidewalk to the portable
193470 12/15/2004 31743 P 3994 O Provide clear access to electrical panel
203763 12/15/2004 78262 1 8088 C Remove extra knox box @ front office wall
203754 12/15/2004 78244 2 014 MS Provide current inspection tag for fire extinguisher
203753 12/15/2004 78242 6 002 MS Recharge fire extinguisher
203751 12/15/2004 78238 10 001 OS Provide clear access to fire extinguisher
193449 12/15/2004 20662 2 014 OS Prohibit storage of gas powered leaf blower and gasoline
203732 12/15/2004 78206 3 004 OS Arrange tables and chairs to provide a clear path of travel to the exits
193456 12/15/2004 10308 4 012 OS Remove golf cart and prohibit recharging batteries in mechanical room (media center)
203733 12/15/2004 78207 5 001 OS Maintain clear aisle to exit
203734 12/15/2004 78208 7 003 OS Maintain clear aisle to exit
203735 12/15/2004 78209 7 004 OS Maintain clear aisle to exit
203752 12/15/2004 78240 P 1866 OS Provide clear access to fire extinguisher
203736 12/15/2004 78210 P 3673 OS Remove piano blocking clear aisle to exit
203737 12/15/2004 78211 P 3676 OS Maintain clear aisle to exit
228743 12/15/2004 81082 P 3994 OS Remove chair from ramp landing
193447 06/30/2004 61334 2 0000 M Repair or replace rusted door frame for generator room
193453 06/30/2004 61331 3 001 M Remove carpet used as wall covering
193454 06/30/2004 10373 3 001C M Determine cause of water damaged ceiling tiles and replace tiles
193455 06/30/2004 31730 3 004D M Determine cause of water damaged ceiling tiles and replace tiles
193462 06/30/2004 31733 9 004C M Repair exhaust fan in bathroom
193477 06/30/2004 31741 P 4188 M Repair ramp door closer. Arm is bent and hangs down below the top of the door frame
193466 06/30/2004 10403 P 691 M Repair split corners in bathroom walls
193481 06/30/2004 10350 P 8 M Repair bathroom walls to be impervious
193483 06/30/2004 31742 P 8 M Repair or replace deteriorated wood siding, west side
193459 06/30/2004 61333 7 002 O Remove and prohibit beanbag chairs
193441 06/30/2004 10323 00 9599 C Provide fencing around transformer adjacent to Building 12
193443 06/30/2004 10359 1 005 C Provide cover for panel "HA" - it is open and adjacent to water source (custodial closet)
193474 06/30/2004 10346 P 116 C Provide proper grounding for portable - land ground wire on panel
193478 06/30/2004 10348 P 4188 C Provide proper grounding for portable - land ground wire on panel
193438 06/30/2004 20664 00 0000 OS Provide suitable area for storage of gas powered equipment
193445 06/30/2004 31714 10 111 OS Remove storage from mechanical room
193452 06/30/2004 10307 2 Gen. OS Remove storage from generator room
193458 06/30/2004 31709 6 008 OS Remove storage from mechanical room
193460 06/30/2004 31710 7 008 OS Remove storage from mechanical room
193461 06/30/2004 31711 8 008 OS Remove storage from mechanical room
193464 06/30/2004 10321 9 008 OS Prohibit storage of golf cart and gas powered pressure cleaner in mechanical room (Building 5)
193440 06/30/2004 31700 00 8088 CS Relocate Fire Department Knox box to be outside of locked doors, on wall at the east entry and provide a key for the portables
193448 06/30/2004 31701 2 006 FS Provide heat detector in washer and dryer closet