Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
415166 05/08/2018 475784 2 292 M Repair or replace surge suppressors for electrical panels 2D2 and 2H2 Not illuminated
415248 05/08/2018 475960 4 208 M Replace missing escutcheon on fire sprinkler head
415222 05/08/2018 475906 5 103 M Replace missing escutcheon on fire sprinkler head
415220 05/08/2018 475902 5 191 M Repair or replace surge suppressor for panel 5H1. Not illuminated
415406 05/08/2018 476294 8 195 M Repair or replace surge suppressor for electrical panel 8H. Not illuminated
257395 05/08/2018 136092 4 0000 N/A No violations observed
257396 05/08/2018 136094 5 0000 N/A No violations observed
415356 04/17/2018 476187 12 106A M Repair exhaust fan in bathroom
415358 04/17/2018 476191 12 107B M Repair exhaust fan in bathroom
415150 04/17/2018 475750 3 101C M Repair exhaust fan at kiln. Teacher advised not to use kiln until fan is repaired
415398 04/17/2018 476278 9 102 M Repair backflow preventer in Kitchen Hood wash down cabinet. Water continually running out of differential pressure dump
415203 04/17/2018 475864 1 115 O Prohibit plugging surge protector into surge protector. Two locations
400329 04/17/2018 443765 2 006 OS Prohibit storage in stairwell to maintain clear aisle to exit
257392 04/17/2018 136086 1 0000 N/A No violations observed
257394 04/17/2018 136090 3 0000 N/A No violations observed
257400 04/17/2018 136102 9 0000 N/A No violations observed
400485 04/05/2018 444108 10 105 OS Remove storage from electrical room. IMMEDIATELY REMOVE 20 cases of spray paint and propane cylinders
415195 04/05/2018 475848 10 106 OS Prohibit storage of Propane
257401 04/05/2018 136104 10 0000 N/A No violations observed
415197 03/30/2018 475852 00 0000 M Repair pole lights at bus loop and parking lot at Glades Road
415198 03/30/2018 475854 00 0000 M Provide anchors for shipping container under home bleachers
415146 03/30/2018 475740 00 0000 M Remove plants growing on covered walkway roof at 1-101
415138 03/30/2018 475721 00 0000 M Remove downed trees at parking lot and west property line
415209 03/30/2018 475877 1 101 M Repair light in exit sign
415154 03/30/2018 475758 1 104 M Replace electrical outlet with burn mark on outlet plate at west wall
415204 03/30/2018 475866 1 115 M Determine cause of water damaged ceiling tiles and replace tiles
415151 03/30/2018 475752 1 123 M Adjust door to latch properly
415144 03/30/2018 475734 1 135B M Repair leaking toilet supply line and adjust flush length, too short
415140 03/30/2018 475725 1 145 M Caulk sink to wall and seal wall to provide impervious finish
415139 03/30/2018 475723 1 147 M Caulk sink to wall
415210 03/30/2018 475879 1 155B M Repair damaged wall finish behind toilet to provide impervious finish
415211 03/30/2018 475881 1 155C M Repair damaged wall finish behind toilet and sink to provide impervious finish
415206 03/30/2018 475870 1 192 M Replace belt guard on outside air intake motor
415190 03/30/2018 475838 10 0000 M Secure spout to drinking fountain on exterior wall outside of 10-106
415179 03/30/2018 475816 10 0000 M Connect downspout to storm drainage outside of 10-108, south exterior wall
415201 03/30/2018 475860 10 102 M Repair inoperable urinal
415192 03/30/2018 475842 10 103 M Replace missing 2 x 2 ceramic floor tile and base tile at entry
415193 03/30/2018 475844 10 103 M Replace missing wall finish at entry
415202 03/30/2018 475862 10 104 M Secure handicapped grabrail
415147 03/30/2018 475742 10 108 M Repair emergency lighting
415278 03/30/2018 476022 11 0000 M Secure fence fabric to frame on top of press-box
415282 03/30/2018 476032 11 001 M Provide current inspection tag for elevator
415281 03/30/2018 476029 11 191 M Repair emergency lighting
415383 03/30/2018 476246 12 0000 M Repair exhaust fan in bathrooms 12-213A and 12-213B
415367 03/30/2018 476210 12 101 M Determine cause of water damaged ceiling tiles and replace tiles
415354 03/30/2018 476182 12 104E M Replace missing shield for drinking fountain
415353 03/30/2018 476180 12 105A M Determine cause of water damaged ceiling tiles and replace tiles
415357 03/30/2018 476189 12 106A M Repair leaking toilet supply line
415370 03/30/2018 476217 12 113 M Determine cause of water damaged ceiling tiles and replace tiles
415371 03/30/2018 476221 12 114 M Replace missing shield for drinking fountain
415373 03/30/2018 476225 12 115 M Secure faucet to sink
415374 03/30/2018 476227 12 118 M Determine cause of water damaged ceiling tiles and replace tiles
415363 03/30/2018 476202 12 119 M Replace broken toilet seat
415364 03/30/2018 476204 12 119 M Caulk handicapped toilet and all sinks to wall
415360 03/30/2018 476195 12 120 M Secure urinal to wall
415361 03/30/2018 476197 12 120 M Replace missing toilet seat
415362 03/30/2018 476199 12 120 M Seal open corner in handicapped stall
415365 03/30/2018 476206 12 122 M Repair light fixtures
415366 03/30/2018 476208 12 122 M Determine cause of water damaged ceiling tiles and replace tiles
415359 03/30/2018 476193 12 180 M Repair damaged wall finish at floor sink. Cover with tile, plastic or metal
415368 03/30/2018 476213 12 191 M Investigate cause of standing water on floor behind AHU 12-1
415369 03/30/2018 476215 12 191 M Label all circuits on electrical panel HEQ-2
415375 03/30/2018 476229 12 203 M Determine cause of water damaged ceiling tiles and replace tiles
415376 03/30/2018 476231 12 203B M Determine cause of water damaged ceiling tiles and replace tiles
415385 03/30/2018 476250 12 209 M Determine cause of water damaged ceiling tiles and replace tiles
415387 03/30/2018 476254 12 210 M Secure projection screen backer board to wall
415384 03/30/2018 476248 12 213B M Refinish wall behind toilet to provide impervious finish
415381 03/30/2018 476242 12 216 M Caulk 1 sink and handicapped toilet to wall
415382 03/30/2018 476244 12 216 M Repair out of order toilet
415377 03/30/2018 476233 12 218 M Determine cause of water damaged ceiling tiles and replace tiles
415379 03/30/2018 476238 12 290 M Run ground from equipment rack to terminal bar
415178 03/30/2018 475814 2 0000 M Remove tree growing in Styrofoam frieze board on exterior wall outside of 2-191
415191 03/30/2018 475840 2 102 M Remove or replace broken view panel for fire extinguisher cabinet
415152 03/30/2018 475754 2 102 M Adjust door to latch properly
415186 03/30/2018 475830 2 103 M Secure handicapped grabrail
415187 03/30/2018 475832 2 103 M Seal wood backing for sink to provide impervious finish
415188 03/30/2018 475834 2 103 M Secure sink to wall
415180 03/30/2018 475818 2 103A M Secure handicapped grabrail
415153 03/30/2018 475756 2 105B M Secure faucet to sink
415185 03/30/2018 475828 2 106A M Provide dated flame resistance certification for Stage curtains. Curtains tagged 2016. Certification is 2012
415183 03/30/2018 475824 2 106B M Replace missing ceiling tiles
415182 03/30/2018 475822 2 106D M Caulk sink to wall
415181 03/30/2018 475820 2 106F M Caulk sink to wall
415149 03/30/2018 475748 2 106J M Secure table saw to floor and paint or mark safety lines around it. Saw is moved to different locations to make Stage sets
415141 03/30/2018 475727 2 107 M Staff indicates that lights in Gym are always on. Repair circuits
415143 03/30/2018 475731 2 107 M Repair emergency electrical outlet in Gym. No power
415176 03/30/2018 475806 2 192 M Replace leaking shaft seal on fire pump. Designed to leak water
415159 03/30/2018 475769 3 0000 M Seal open joint on north exterior wall outside of 3-106
415155 03/30/2018 475760 3 0000 M Repair exhaust fan in bathrooms 3-109 and 3-110
415171 03/30/2018 475795 3 002 M Replace missing ceiling tiles
415162 03/30/2018 475775 3 101 M Adjust south door to exterior to latch properly
400400 03/30/2018 443925 3 101 M Repair or replace broken purge fan button
415175 03/30/2018 475804 3 101B M Determine cause of water damaged ceiling tiles and replace tiles
415157 03/30/2018 475765 3 103C M Repair damaged wall finish behind toilets to provide impervious finish
415158 03/30/2018 475767 3 103C M Repair or replace leaking faucets
415161 03/30/2018 475773 3 103D M Caulk toilets to wall
415173 03/30/2018 475800 3 104A M Determine cause of water damaged ceiling tiles and replace tiles
415160 03/30/2018 475771 3 105D M Secure handicapped grabrail
415156 03/30/2018 475762 3 109 M Repair damaged wall finish behind toilet to provide impervious finish
415172 03/30/2018 475798 3 111 M Secure Ballet bar to wall
415174 03/30/2018 475802 3 180 M Anchor shelving to wall
415267 03/30/2018 476001 3 202 M Determine cause of water damaged ceiling tiles and replace tiles
415272 03/30/2018 476010 3 216 M Caulk handicapped sink to wall
415271 03/30/2018 476008 3 217 M Secure and caulk sinks to wall
415268 03/30/2018 476003 3 218 M Adjust door to exterior to latch properly
415269 03/30/2018 476005 3 280 M Anchor shelving to wall
415276 03/30/2018 476020 3 292 M Provide cover on open fire alarm junction box above oval duct
415212 03/30/2018 475885 4 0000 M Remove tree growing in frieze band on exterior wall between 4-101 and 4-105
415215 03/30/2018 475891 4 101 M Bulbs for hi-hat lites in Media center are falling out of fixtures. Repair or replace fixtures or use correct bulb. See Media Specialist
415214 03/30/2018 475889 4 170 M Provide current inspection tag for elevator
415213 03/30/2018 475887 4 171 M Replace missing latch plate on door frame. Plate inside of room sitting on uni-strut to right of door
415216 03/30/2018 475893 4 190 M Replace missing ceiling tiles
415237 03/30/2018 475938 4 201 M Replace missing shield for drinking fountain
415238 03/30/2018 475941 4 202 M Repair damaged ceiling grid. Loose piece
415246 03/30/2018 475957 4 207 M Repair broken window blinds
415251 03/30/2018 475965 4 213 M Replace missing shield for drinking fountain
415245 03/30/2018 475954 4 218 M Repair inoperable handicapped toilet
415241 03/30/2018 475947 4 219 M Repair inoperable urinal
415243 03/30/2018 475950 4 219 M Secure lower trim piece for 1st toilet partition
415249 03/30/2018 475962 4 290 M Replace missing ceiling tiles
415223 03/30/2018 475908 5 103 M Several gas outlets not working. Blue tape on handle indicates that outlet works. Repair gas plumbing. Gas shut off to all but 1 lab
415224 03/30/2018 475910 5 104 M Repair or replace dripping faucet
415233 03/30/2018 475928 5 107 M Repair electrical outlets on sides of tables. See Teacher for locations
415234 03/30/2018 475930 5 108 M Repair electrical outlets on sides of tables. See Teacher for locations
415225 03/30/2018 475912 5 112 M Repair hole in wall at base at door
415230 03/30/2018 475922 5 112A M Repair exhaust fan in bathroom
415226 03/30/2018 475914 5 113 M Replace missing handicapped sink
415227 03/30/2018 475916 5 113 M Repair inoperable urinal
415228 03/30/2018 475918 5 114 M Secure 2 handicapped grabrails
415229 03/30/2018 475920 5 114 M Secure handicapped sink to wall
415221 03/30/2018 475904 5 116 M Repair or replace dripping faucet
415255 03/30/2018 475974 5 215B M Refinish wall behind toilet to provide impervious finish
415252 03/30/2018 475969 5 217 M Repair inoperable urinal
415254 03/30/2018 475971 5 217 M Secure handicapped grabrails x 2
415259 03/30/2018 475983 6 006 M Adjust corridor door to exterior at 6-291 to latch properly
415219 03/30/2018 475900 6 106 M Replace damaged electrical outlet at door to 6-105
415235 03/30/2018 475932 6 106C M Repair light fixture
415265 03/30/2018 475996 6 203B M Secure handicapped grabrail
415262 03/30/2018 475987 6 215 M Eliminate background noise on PA system in room
415266 03/30/2018 475998 6 216 M Caulk sinks to wall
415264 03/30/2018 475994 6 280 M Anchor shelving to wall
415350 03/30/2018 476174 7 0000 M Repair exhaust fan in bathrooms 7-111A and 7-111B
415339 03/30/2018 476149 7 101 M Replace tubes in light fixture. Too high for Custodian
415344 03/30/2018 476160 7 101 M Paint safety lines around drill press. Drill press gone
415336 03/30/2018 476143 7 105 M Determine cause of water damaged ceiling tiles and replace tiles
415351 03/30/2018 476176 7 111B M Replace missing floor tile grout at shower
415352 03/30/2018 476178 7 113 M Replace missing floor tile grout at shower
415346 03/30/2018 476164 7 180 M Repair hot water recirculating pump. Bad bearing
415341 03/30/2018 476153 7 181 M Replace tubes in light fixtures. Too high for Custodian
415337 03/30/2018 476146 7 192 M Adjust door to latch properly
415347 03/30/2018 476168 7 192 M Rehang fire extinguisher sitting on floor
415349 03/30/2018 476172 7 192 M Check air compressor for air and oil leaks
415409 03/30/2018 476303 8 101 M Determine cause of water damaged ceiling tiles and replace tiles at east hood
415416 03/30/2018 476318 8 101 M Light pilot lights on all Kitchen equipment
415417 03/30/2018 476320 8 101 M Repair leaking hose reels x 2
415421 03/30/2018 476329 8 102B M Repair exhaust fan in bathroom
415412 03/30/2018 476310 8 103 M Secure projection screen backer board to wall
415405 03/30/2018 476292 8 108A M Repair exhaust fan in bathroom
415420 03/30/2018 476327 8 112 M Replace missing ceiling tiles
415419 03/30/2018 476325 8 113 M Secure handicapped sink to wall
415390 03/30/2018 476261 8 115 M Caulk handicapped sink to wall
415391 03/30/2018 476263 8 115 M Repair inoperable toilet
415392 03/30/2018 476265 8 115 M Replace missing push button on faucet
415393 03/30/2018 476267 8 115 M Replace damaged soap dispenser
415388 03/30/2018 476257 8 116 M Repair inoperable toilet
415389 03/30/2018 476259 8 116 M Caulk handicapped sink to wall
415394 03/30/2018 476269 8 117 M Repair exhaust fan in bathroom
415410 03/30/2018 476305 8 180 M Repair hole in wall from door handle and provide door stop
415413 03/30/2018 476312 8 193 M Chain cylinders to wall in chiller room
415414 03/30/2018 476314 8 194 M Remove trees growing in cooling tower compound
415395 03/30/2018 476271 9 0000 M Repair exhaust fan in bathrooms 9-102F and 9-102G
415142 03/30/2018 475729 9 101 M Staff indicates that Cafeteria lights are always on. Repair circuits
415401 03/30/2018 476284 9 101C M Determine cause of water damaged ceiling tiles and replace tiles
415400 03/30/2018 476282 9 102B M Adjust door to walk-in freezer in Kitchen to latch properly
415397 03/30/2018 476275 9 102F M Repair damaged wall behind toilet to provide impervious finish
415396 03/30/2018 476273 9 102G M Repair damaged wall behind toilet to provide impervious finish
415402 03/30/2018 476286 9 102H M Repair or replace dryer vent line. Pinched shut
415407 03/30/2018 476297 9 180 M Adjust flow of emergency eye wash, low
415145 03/30/2018 475738 00 0000 O Doors are being blocked open on the hinge side with a stick or block of wood between the door and door frame. This will and has damaged the door, hinges and door frame. Temporarily block open doors with a wedge between the bottom of the door and the floor
415199 03/30/2018 475856 00 0000 O Prohibit storing gas powered John Deere Gator and other combustible storage under home bleachers
415207 03/30/2018 475873 1 192 O Renstall grate on floor drain
415194 03/30/2018 475846 10 106 O Keep all fixture drains filled with water. Room used for storage
415279 03/30/2018 476027 11 0000 O Do not put chairs without feet on top of pressbox. This has already damaged roof
415386 03/30/2018 476252 12 0000 O Remove mold from top flight of stairs on east side of building. Pressure clean
400344 03/30/2018 443798 12 104A O Prohibit storage of expired fire extinguishers, arrange for removal of expired extinguishers by maintenance zone team
415355 03/30/2018 476185 12 104C O Remove trash from behind dryer
415170 03/30/2018 475793 2 0000 O Remove and prohibit storage on floor of catwalk above audience in Auditorium
400403 03/30/2018 443932 2 102A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
415189 03/30/2018 475836 2 105A O Keep all fixture drains filled with water. Bathroom converted to custodial closet
415184 03/30/2018 475826 2 106A O Eliminate non protected 3 outlet extension cord at rear of Stage and Stage right. Replace with surge suppressor outlet strip
415148 03/30/2018 475745 2 106J O Keep sawdust cleaned from surfaces
415218 03/30/2018 475898 4 103A O Eliminate non 15 amp multi-outlet extension cord or replace with minimum 15A surge suppressor outlet strip. Cord to left of door when you enter room
415232 03/30/2018 475926 5 107 O Keep area clear to emergency gas disconnect to allow ready access. Relocate Buddha figurine
415403 03/30/2018 476288 8 110 O Remove trash from behind dryer
415408 03/30/2018 476301 9 180 O Flush emergency eye wash weekly to maintain proper operation
415240 03/30/2018 475943 4 220 C Post sign indicating primary and secondary evacuation routes in contrasting colors
415263 03/30/2018 475992 6 214 C Post sign indicating primary and secondary evacuation routes in contrasting colors
415418 03/30/2018 476323 8 101 C Secure loose Ansul drop on Kitchen hood. See Chef Baumeyer
415422 03/30/2018 476331 8 101 C East hood in Culinary Kitchen not operational. Repair hood
415208 03/30/2018 475875 1 003 MS Adjust fire door in corridor at 1-127 to latch properly
415200 03/30/2018 475858 10 102 MS Provide current inspection tag for fire extinguisher in bathroom
415196 03/30/2018 475850 10 107 MS Provide current inspection tag for fire extinguisher
415380 03/30/2018 476240 12 290 MS Provide current inspection tag for fire extinguisher
415378 03/30/2018 476235 12 292 MS Provide current inspection tag for fire extinguisher
415165 03/30/2018 475782 2 107 MS Provide current inspection tag for fire extinguisher at SW corner of Gym
415168 03/30/2018 475788 2 291 MS Provide current inspection tag for fire extinguisher
415167 03/30/2018 475786 2 292 MS Recharge fire extinguisher
415273 03/30/2018 476014 3 207 MS Adjust corridor door to latch properly
415274 03/30/2018 476016 3 209 MS Adjust corridor door to latch properly
415275 03/30/2018 476018 3 210 MS Adjust corridor door to latch properly
415257 03/30/2018 475978 5 206 MS Secure closer to door
415258 03/30/2018 475981 5 210 MS Adjust corridor door to latch properly
277075 03/30/2018 176030 9 001 MS Remove lock from door leading into serving line to eliminate dead end corridor
415205 03/30/2018 475868 1 192 OS Remove storage from mechanical room
400494 03/30/2018 444126 2 106 OS Relocate temporary stage steps to maintain a minimum 3 foot clear path to meet ADA and exiting requirements
415169 03/30/2018 475790 2 294 OS Remove storage from electrical room
415163 03/30/2018 475777 3 103F OS Remove and prohibit storage in exit corridor
415164 03/30/2018 475780 3 193 OS Remove storage from boiler room
415217 03/30/2018 475895 4 103A OS Maintain 3 foot clear aisle to exit to exterior
415231 03/30/2018 475924 5 107 OS Maintain 3 foot clear aisle to rear exit
415236 03/30/2018 475934 6 192 OS Remove storage from electrical room
415348 03/30/2018 476170 7 192 OS Remove storage from mechanical room
415404 03/30/2018 476290 8 109 OS Maintain 3 foot clear aisle to exit to exterior
415411 03/30/2018 476307 8 190 OS Remove storage from mechanical room
415399 03/30/2018 476280 9 180 OS Remove chain and padlock from gate to caged area in Custodial receiving. Gate has lock on door handle
257402 03/30/2018 136106 11 0000 N/A No violations observed
257397 03/30/2018 136096 6 0000 N/A No violations observed
257398 03/30/2018 136098 7 0000 N/A No violations observed
400319 11/17/2017 443740 00 0000 M Provide current inspection tags for fire sprinkler system and make any necessary repairs if indicated on report. Fire Sprinkler risers had either expired tags or no tags
372070 11/17/2017 382665 12 170 M Provide current inspection tag for elevator (current tag expired 8-1-14)
415177 11/17/2017 475812 2 192 M Provide current inspection tag for fire sprinkler system and make any necessary repairs if indicated on report. Tags expired
382068 11/17/2017 404406 8 181 M Repair exhaust fan in flammable storage room
415415 11/17/2017 476316 8 194 M Remove rust from and refinish badly rusted chilled water lines
415137 11/17/2017 475719 00 0 O No access was available to 1-120, 1-141 and 2-105E (chair lift). Please provide access to these rooms during the report review meeting
341973 11/17/2017 317017 00 9599 O Remove wooden platform structure at baseball field or provide certification by Building Department that structure meets code and design requirements (stair risers not equal, bottom risers not sturdy, missing balasters & graspable handrails, not ADA accessible, electrical outlets not marked as GFCI, etc...)
400963 11/17/2017 445118 12 203C O Prohibit use of room for chemical storage. Use only a designated chemical storage room to store chemicals. This room was designed for Material Storage
400379 11/17/2017 443880 5 105 O Store chemicals properly in designated chemical storage room
400375 11/17/2017 443872 5 106 O Prohibit plastic sheet covering air intake vents in ceiling
400449 11/17/2017 444031 6 210 O Properly secure DVD player located beneath TV. DVD player removed
257403 11/17/2017 136108 12 0000 N/A No violations observed
257393 11/17/2017 136088 2 0000 N/A No violations observed
257399 11/17/2017 136100 8 0000 N/A No violations observed
400487 04/14/2017 444112 00 0000 M Remove trees growing under home bleachers
400488 04/14/2017 444114 00 0000 M Repair bleachers as instructed in the Bleacher Structural Inspection Report. Contact Patrick Joyce if questions occur
400470 04/14/2017 444074 00 0000 M Remove wasp nest on auto closer for exterior gates between buildings 4 and 5
400336 04/14/2017 443779 00 0000 M Repair damaged concrete walk in courtyard north of 9-101 and at 12-191. Repair damaged areas of concrete walk with exposed rebar on second floor exterior corridor
400459 04/14/2017 444052 00 8087 M Repair and secure damaged grounding wire on covered walk at bus loop adjacent to 8-195
400460 04/14/2017 444054 00 8088 M Remove trees growing from exterior walls adjacent to gutter at 8-194, NE corner of 4-101 and on north wall of 2-106
400323 04/14/2017 443752 1 154 M Remove expired, unnecessary fire extinguisher
400325 04/14/2017 443756 1 180 M Repair damaged wall finish at sink
400320 04/14/2017 443742 1 191 M Fill void in electrical panels 1EQH1 and 1H1
400321 04/14/2017 443748 1 191 M Mount fire extinguisher at maximum five feet above floor
400486 04/14/2017 444110 10 101 M Repair damaged wall finish above door
400338 04/14/2017 443783 12 003 M Repair light in exit sign
400339 04/14/2017 443785 12 004 M Repair lights in exit signs
400346 04/14/2017 443804 12 203A M Replace missing covers on light fixtures
400345 04/14/2017 443800 12 210 M Repair door to close properly
400348 04/14/2017 443808 12 218 M Determine cause of water damaged ceiling tiles and replace tiles
400415 04/14/2017 443959 2 001 M Repair damaged flooring at south exterior doors
400481 04/14/2017 444097 2 004 M Repair hole in wall in auditorium entrance vestibule
400335 04/14/2017 443777 2 105 M Repair damaged wall finish at south doors
400482 04/14/2017 444099 2 106 M Repair damaged wall finish at exterior doors
400491 04/14/2017 444120 2 106B M Provide cover on exposed electrical junction box above mirror
400417 04/14/2017 443963 2 106E M Provide cover on data outlet junction box adjacent to 2-106F
400326 04/14/2017 443759 2 107 M Repair or replace broken exit signs in gym
400327 04/14/2017 443761 2 107 M Repair damaged wall above west exterior doors
400328 04/14/2017 443763 2 107 M Secure loose section of padded east wall at 2-006
400402 04/14/2017 443930 2 180 M Repair damaged wall finish at sink
400331 04/14/2017 443769 2 290 M Seal penetration in exterior wall
400392 04/14/2017 443908 3 002 M Repair deteriorated wall finish at 3-104
400426 04/14/2017 443981 3 008 M Repair damaged wall finish at 3-207
400401 04/14/2017 443928 3 101C M Repair exhaust fan at kiln
400390 04/14/2017 443904 3 105 M Anchor loose bench adjacent to 3-105A
400391 04/14/2017 443906 3 105B M Secure loose base on wall
400387 04/14/2017 443897 3 110 M Replace missing sign indicating room name and number mounted at appropriate height with raised and Braille characters
400490 04/14/2017 444118 3 8088 M Provide bollard around gas line on exterior wall of 3-193
400472 04/14/2017 444078 4 101 M Adjust SW exterior door to latch properly
400473 04/14/2017 444080 4 104 M Determine cause of water damaged ceiling tiles and replace tiles
400427 04/14/2017 443983 4 280 M Repair damaged wall finish at sink
400443 04/14/2017 444018 5 007 M Repair damaged wall finish in corridor adjacent to 5-207, provide doorstop to prevent further damage
400383 04/14/2017 443888 5 101 M Adjust flow of emergency eye wash
400380 04/14/2017 443882 5 103 M Repair exterior door to close properly
400378 04/14/2017 443878 5 105 M Adjust flow of emergency eye wash
400376 04/14/2017 443874 5 106 M Adjust flow of eye wash
400373 04/14/2017 443868 5 107 M Adjust flow of eye wash
400367 04/14/2017 443857 5 109 M Adjust flow of eye wash
400366 04/14/2017 443855 5 110 M Adjust flow of eye wash
400371 04/14/2017 443864 5 111 M Adjust flow of eye wash
400377 04/14/2017 443876 5 112A M Replace missing soap dispenser
400381 04/14/2017 443884 5 115 M Determine cause of water damaged ceiling tiles and replace tiles
400382 04/14/2017 443886 5 116 M Adjust flow of eye wash
400442 04/14/2017 444016 5 216 M Repair or replace damaged bottom of toilet partition
400451 04/14/2017 444035 5 217 M Repair damaged flooring and grout in accessible stall, staff reports that water leaks through to 1st floor ceiling
400438 04/14/2017 444008 5 218 M Replace missing escutcheon on fire sprinkler head adjacent to 5-218A
400365 04/14/2017 443852 6 101B M Chain cylinder to wall
400363 04/14/2017 443849 6 102 M Repair exterior door to close properly
400357 04/14/2017 443836 6 106 M Repair door to close properly
400362 04/14/2017 443846 6 111 M Repair damaged bottom of toilet partitions
400361 04/14/2017 443843 6 180 M Repair damaged wall at sink
400467 04/14/2017 444068 6 192 M Repair door to close properly, rubs on leaf
400445 04/14/2017 444022 6 201 M Secure data outlet box adjacent to teachers desk
400452 04/14/2017 444037 6 217 M Repair damaged flooring and grout in accessible stall, staff reports that water leaks through to 1st floor ceiling
400356 04/14/2017 443826 7 004 M Replace missing sign indicating room name and number at appropriate height with raised and Braille characters
400352 04/14/2017 443819 7 101 M Repair or replace damaged dust collector hose
400349 04/14/2017 443810 7 101 M Repair south courtyard doors to close properly, too fast
400350 04/14/2017 443815 7 181 M Mount fire extinguisher at maximum five feet above floor, provide current inspection tag for fire extinguisher
400465 04/14/2017 444064 7 192 M Mount fire extinguisher at maximum five feet above floor
400466 04/14/2017 444066 7 192 M Repair door to close properly, rubs on leaf
400337 04/14/2017 443781 8 101 M Repair broken exit sign at 8-104
400457 04/14/2017 444048 8 194 M Remove trees and plants growing in chiller yard
400458 04/14/2017 444050 8 195 M Chain cylinders to wall
400455 04/14/2017 444044 8 196 M Mount fire extinguisher at maximum five feet above floor
400456 04/14/2017 444046 8 196 M Repair emergency lighting
400496 04/14/2017 444130 9 101 M Repair broken auto closer on NE exterior doors to allow doors to close properly
400498 04/14/2017 444134 9 101C M Provide sign to be mounted adjacent to room name and number sign indicating FACP (Fire Alarm Control Panel)
400499 04/14/2017 444136 9 101C M Make repairs as indicated on fire alarm inspection report
400500 04/14/2017 444138 9 101C M Determine cause of water damaged ceiling tiles and replace tiles
400454 04/14/2017 444042 9 102B M Make necessary repairs to walk in freezer door or seal to prevent ice buildup
400461 04/14/2017 444056 9 180 M Adjust flow of emergency eye wash
400341 04/14/2017 443789 12 113 O Remove and prohibit air freshener (gel beads)
400343 04/14/2017 443796 12 115 O Remove and prohibit air freshener
400342 04/14/2017 443794 12 180 O Replace bulbs in light fixture
400334 04/14/2017 443775 2 104A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
400483 04/14/2017 444103 2 106 O Prohibit running electrical cords from control booth across floor and in front of doors. Coordinate with school district maintenance zone team for proper installation
400492 04/14/2017 444122 2 106B O Prohibit ducting portable air conditioning unit above ceiling
400421 04/14/2017 443972 2 106C O Prohibit use of lighters, open flames
400493 04/14/2017 444124 2 190 O Prohibit storage in telecommunications room
400398 04/14/2017 443921 3 102 O Remove and prohibit items hanging on purge fan button
400399 04/14/2017 443923 3 102D O Prohibit storage of broken glass
400384 04/14/2017 443891 3 108 O Prohibit flags hanging across room, flags may hang against the wall, no more than 2 inches from wall surface
400425 04/14/2017 443977 3 218A O Prohibit storage of expired fire extinguisher, arrange for removal of expired extinguisher by maintenance zone team
400471 04/14/2017 444076 4 102 O Prohibit black multi outlet extension cord at teachers desk or replace with 15A single outlet extension cord or surge protector
400474 04/14/2017 444082 4 104 O Prohibit plugging surge protector into extension cord adjacent to 4-103A
400431 04/14/2017 443991 4 210 O Prohibit storage of expired fire extinguisher, arrange for removal of expired extinguisher by maintenance zone team
400432 04/14/2017 443995 4 211 O Prohibit hanging flags over windows
400374 04/14/2017 443870 5 107 O Maintain clear access to emergency eye wash - shower
400370 04/14/2017 443862 5 108A O Remove and prohibit air freshener (plug in)
400435 04/14/2017 444001 5 218 O Provide certification that couch meets California TB 117 standards or remove and prohibit combustible (residential) couch
400440 04/14/2017 444012 5 218 O Remove storage from stove burners
400441 04/14/2017 444014 5 218 O Prohibit black multi outlet extension cord adjacent to teachers computer or replace with minimum 15A single outlet extension cord or surge protector
400439 04/14/2017 444010 5 218A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
400446 04/14/2017 444024 6 202 O Replace missing sign indicating primary and secondary evacuation routes in contrasting colors
400450 04/14/2017 444033 6 211 O Remove and prohibit air freshener (plug in)
400351 04/14/2017 443817 7 104 O No access was available to this room. Please provide access to this room during the report review meeting
400322 04/14/2017 443750 1 007 MS Provide current inspection tag for fire extinguisher adjacent to 1-154
400489 04/14/2017 444116 11 201 MS Provide current inspection tag for fire extinguisher in pressbox
400347 04/14/2017 443806 12 203 MS Recharge fire extinguisher
400495 04/14/2017 444128 2 0000 MS Provide current inspection tag for fire extinguisher on catwalk
400480 04/14/2017 444095 2 105E MS Provide current inspection tag for fire extinguisher
400330 04/14/2017 443767 2 290 MS Provide current inspection tag for fire extinguisher
400333 04/14/2017 443773 2 291 MS Provide current inspection tag for fire extinguisher
400332 04/14/2017 443771 2 292 MS Provide current inspection tag for fire extinguisher
400393 04/14/2017 443910 3 103B MS Provide current inspection tag for fire extinguisher
400395 04/14/2017 443914 3 103F MS Provide current inspection tag for fire extinguisher
400389 04/14/2017 443902 3 105E MS Provide current inspection tag for fire extinguisher
400479 04/14/2017 444093 3 192 MS Provide current inspection tag for fire extinguisher
400477 04/14/2017 444089 3 291 MS Provide current inspection tag for fire extinguisher
400478 04/14/2017 444091 3 292 MS Provide current inspection tag for fire extinguisher
400468 04/14/2017 444070 5 191 MS Provide current inspection tag for fire extinguisher
400469 04/14/2017 444072 5 192 MS Provide current inspection tag for fire extinguisher
400475 04/14/2017 444085 6 291 MS Provide current inspection tag for fire extinguisher
400476 04/14/2017 444087 6 292 MS Provide current inspection tag for fire extinguisher
400497 04/14/2017 444132 8 004 MS Provide current inspection tag for fire extinguisher at 8-116
400453 04/14/2017 444039 8 181 MS Provide current inspection tag for fire extinguisher
400464 04/14/2017 444062 8 190 MS Provide current inspection tag for fire extinguisher
400463 04/14/2017 444060 8 191 MS Provide current inspection tag for fire extinguisher
400462 04/14/2017 444058 8 192 MS Provide current inspection tag for fire extinguisher
400324 04/14/2017 443754 1 116 OS Remove and prohibit dog leg hold open device on door
400484 04/14/2017 444105 10 105 OS Prohibit storage of propane in electrical room, store in flammable storage room or cabinet
400340 04/14/2017 443787 12 110 OS Relocate trash and recycle bins to maintain clear aisle to exit
400419 04/14/2017 443968 2 106C OS Maintain clear aisle to exits
400418 04/14/2017 443965 2 106E OS Maintain clear aisle to exits
400397 04/14/2017 443916 3 102B OS Prohibit unsafe use of toaster oven, storage observed on toaster oven. Use in area without students, prohibit storage on toaster oven
400394 04/14/2017 443912 3 103F OS Maintain clear aisle to exit
400385 04/14/2017 443893 3 106 OS Maintain clear aisle to exterior exit
400386 04/14/2017 443895 3 109 OS Remove and prohibit hasp lock from door
400388 04/14/2017 443900 3 110 OS Remove and prohibit hasp lock from door
400423 04/14/2017 443974 3 201 OS Remove and prohibit use of candles
400429 04/14/2017 443988 4 204 OS Remove hasp lock from door
400372 04/14/2017 443866 5 107 OS Prohibit hanging decorations over corridor door
400369 04/14/2017 443859 5 108 OS Relocate hanging display at corridor door to maintain clear aisle to exit
400437 04/14/2017 444005 5 210 OS Prohibit No Exit sign on exterior door, sign may read Emergency Exit Only
400444 04/14/2017 444020 5 210 OS Relocate desks to maintain a minimum 3 foot clear aisle to exit
400359 04/14/2017 443839 6 105 OS Remove and prohibit use of space heater
400447 04/14/2017 444026 6 215 OS Relocate green decorative paper hanging at corridor door to maintain clear aisle to exit
400448 04/14/2017 444028 6 215 OS Remove and prohibit use of toaster oven
382267 11/22/2016 404847 12 203C M Repair exhaust fan in chemical storage room (NA, room is designated as Material Storage and does not have an exhaust fan, verified by M. Lodge December 2016)
382408 11/18/2016 405145 11 001 M Repair pressbox elevator to work properly and verify elevator has current inspection tag. Elevator was not accessible
382367 11/18/2016 405060 12 192 M Repair air conditioning unit above door to ensure it operates as designed
382051 11/18/2016 404370 2 198 M Make necessary repairs to fire pump as indicated on inspection report - RED tag date 7.28.15
382052 11/18/2016 404372 2 198 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report - RED tag date 7.28.15
382409 11/18/2016 405147 6 0000 M Coordinate with school to remove cardboard and plywood on AC vents in 6-106 and repair air conditioning system to ensure it operates as designed. 6-105 and 6-106 temperature is cold and below District indoor air quality temperature range
382365 11/18/2016 405056 6 191 M Repair air conditioning wall unit in electrical room to ensure it operates as designed
341679 11/18/2016 316386 2 106 O Reconfigure wooden control booth structure to provide wheel chair access. Complete alterations in accordance with District policy 7.26 (November 2016 Per T. Hogarth structure accepted as is, school staff will coordinate with zone team to properly install wiring)
382070 02/15/2016 404410 00 0000 M Provide verification that space has emergency lights and lights are operable - old certificate in 8-196
382072 02/15/2016 404414 00 9599 M Repair damaged chain link fencing and repair damaged fence post east of kitchen trash dumpsters
382060 02/15/2016 404388 00 9599 M Adjust hardware on center exit gates in courtyard to latch properly - between Bldgs. 1 and 9
382406 02/15/2016 405141 00 9599 M Provide hurricane anchors for Suncast shed at batting cages - north side of student parking
382407 02/15/2016 405143 00 9599 M Repair auto closer on exit courtyard gate at south side of Bldg. 3
382396 02/15/2016 405118 00 9599 M Replace missing tie down strap for Rubbermaid shed at baseball field
382039 02/15/2016 404345 1 121 M Repair broken vinyl base along wall
382059 02/15/2016 404386 1 191 M Repair air conditioning unit above door to ensure it operates as designed
382405 02/15/2016 405138 10 0000 M Repair uneven concrete walkway outside boys and girls bathrooms 10-106 and 10-107
382398 02/15/2016 405123 10 103 M Replace missing signage indicating room name and number with Braille characters
382403 02/15/2016 405128 10 103 M Replace broken tile base along wall in girls bathroom vestibule
382404 02/15/2016 405136 10 180 M Repair damaged wall finish around mop sink
382391 02/15/2016 405107 11 0000 M Replace missing screws to secure bottom of ramp to walkway - Ramp located in front of home bleachers at south end
382393 02/15/2016 405113 11 0000 M Remove vegetation growing from top of downspout on exterior wall of electrical room 11-190
372167 02/15/2016 382863 11 0000 M Repair bleachers as instructed in the Bleacher Structural Inspection Report. Contact Patrick Joyce if questions occur.
382381 02/15/2016 405090 11 191 M Repair emergency lighting in elevator machine room
382038 02/15/2016 404343 12 104 M Repair broken vinyl base along wall adjacent to exterior door
382269 02/15/2016 404852 12 203 M Replace missing lens on fixtures
382273 02/15/2016 404859 12 204 M Secure loose lens to light fixture
382369 02/15/2016 405064 12 280 M Repair damaged wall finish around mop sink
382371 02/15/2016 405068 12 291 M Pad and mark corners of motor cover unit which are lower than 6 feet 8 inches in mechanical room
382054 02/15/2016 404376 2 0000 M Mount fire extinguisher at maximum five feet above floor on back wall of catwalk. It was supported by a zip tie along catwalk railing. I placed it at the end of the catwalk on the floor to eliminate hazard
382050 02/15/2016 404368 2 103 M Repair damaged flooring adjacent to door
382053 02/15/2016 404374 2 106A M Repair damaged flooring in back of stage adjacent to boys and girls dressing rooms
382047 02/15/2016 404362 2 107 M Provide cover on exposed electrical junction box adjacent to 2-107A
382048 02/15/2016 404364 2 107A M Secure ceiling tile in place
382380 02/15/2016 405086 3 0000 M Repair light in (3) exit signs at 2nd floor covered walkway between Bldgs. 3 and 4
382241 02/15/2016 404795 3 008 M Repair illuminated exit sign hanging from wire in corridor adjacent to 3-208
382248 02/15/2016 404811 3 101A M Repair light fixture to work properly
372115 02/15/2016 382757 3 101C M Replace corroded fire sprinkler head in kiln room
382255 02/15/2016 404823 3 103 M Repair damaged flooring adjacent to 3-103A
382259 02/15/2016 404828 3 105C M Replace missing ceiling tile in laundry room adjacent to door
382261 02/15/2016 404836 3 108 M Replace missing signage indicating room name and number with Braille characters adjacent to corridor door
382264 02/15/2016 404843 3 111 M Secure loose railing to wall in dance room
382362 02/15/2016 405049 3 180 M Repair damaged wall finish around mop sink
382410 02/15/2016 405150 4 171 M Replace heavily rusted louver designed for 1.5 hr fire rated door to maintain fire rating - coordinate with Rickie Mann if assistance is needed
382378 02/15/2016 405078 5 0000 M Repair damaged concrete walkway with exposed rusted rebars according to Pat Joyce recommendation - 2nd floor between Bldgs. 4 and 5
382173 02/15/2016 404646 5 116 M Adjust water flow for emergency eye wash
382188 02/15/2016 404677 5 201 M Adjust exterior door to latch properly
382364 02/15/2016 405054 6 001 M Repair damaged flooring at exit doors in corridor adjacent to 6-101
382174 02/15/2016 404648 6 102C M Repair light fixture to work properly
382176 02/15/2016 404652 6 106 M Provide cover on exposed electrical junction box behind teacher station (X2)
382372 02/15/2016 405071 6 203A M Replace missing escutcheon on fire sprinkler head
382374 02/15/2016 405074 6 203A M Replace broken base tile along wall adjacent to sink
382370 02/15/2016 405066 6 280 M Repair damaged wall finish around mop sink
382366 02/15/2016 405058 7 104 M Determine cause of water damaged ceiling tiles and replace tiles in back corner
382302 02/15/2016 404920 8 101 M Repair freezer door handle to work properly
382303 02/15/2016 404922 8 101 M Provide protective cage around fire sprinkler head in cooler
382069 02/15/2016 404408 8 181 M Replace burned out light bulbs in flammable storage room
382073 02/15/2016 404416 8 194 M Remove all vegetation from cooling tower enclosure and adjacent to enclosure door next to irrigation station
359280 02/15/2016 354911 9 0000 M Repair leaks in rain gutter on north side of cafeteria
382062 02/15/2016 404392 9 101C M Replace missing ceiling tiles
382064 02/15/2016 404396 9 102 M Repair rusted bottom of door frame at door to serving area adjacent to 9-102H
382067 02/15/2016 404404 9 102 M Provide current state inspection tag for kitchen steamer
382066 02/15/2016 404402 9 102B M Provide protective cage around fire sprinkler head in freezer
382065 02/15/2016 404400 9 102C M Provide protective cage around fire sprinkler head in cooler
382071 02/15/2016 404412 00 9599 O Keep site free of hazardous debris adjacent to trash dumpsters behind kitchen
382045 02/15/2016 404357 1 006 O Remove paper covering electrical outlets facing staff bathrooms 1-145 and 1-147
382040 02/15/2016 404347 1 131 O Prohibit plugging surge protector into surge protector under desk - plug each surge protector directly into wall outlet
359236 02/15/2016 354820 1 192 O Eliminate extension cords used on battery chargers inside mechanical room
309208 02/15/2016 245000 10 107 O Remove storage from accessible stall
382388 02/15/2016 405103 11 202 O Replace missing tube bulb in light fixture at pressbox
382043 02/15/2016 404353 12 104 O Remove yellow school map covering evacuation map with primary and secondary evacuation routes in contrasting colors
382276 02/15/2016 404864 12 202 O Remove paper covering electrical outlets adjacent to corridor door
382281 02/15/2016 404873 12 202 O Replace missing light bulbs in floor lamp socket or remove floor lamp from classroom
382271 02/15/2016 404856 12 205 O Remove and prohibit hanging decorations from ceiling
382057 02/15/2016 404382 2 0000 O Remove rotted wood boards from dust collector enclosure outside stage shop 2-106J
382056 02/15/2016 404380 2 002 O Remove and prohibit storage of foam sheets in corridor facing 2-101
382304 02/15/2016 404924 2 104A O Relocate storage to keep area within 18 inches of fire sprinkler heads clear and unobstructed
382055 02/15/2016 404378 2 106 O Eliminate white 13A extension cord with multiple outlet end at wooden control booth or replace with a surge protector and plug surge protector into a permanent electrical outlet
341457 02/15/2016 315890 2 106 O Provide proper installation of electrical oultets at wooden structure control booth to eliminate excessive extension cords - contact FMC for assistance and approval
382046 02/15/2016 404360 2 291 O Replace burned out light bulbs in mechanical room
382246 02/15/2016 404797 3 101 O Keep exterior kiln fenced area locked and latched to prohibit unauthorized access
382253 02/15/2016 404821 3 102 O Eliminate string line in center of art classroom
382252 02/15/2016 404816 3 102B O Remove and prohibit storage blocking access to fire sprinkler riser
382240 02/15/2016 404789 3 211 O Prohibit plugging surge protector into surge protector at sink counter - replace with a longer cord surge protector and plug directly into wall outlet
382237 02/15/2016 404785 3 211A O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
382300 02/15/2016 404916 4 103A O Maintain CCTV studio in an orderly manner and maintain 3 ft clear path to all doors
382301 02/15/2016 404918 4 103A O Prohibit running electrical cord across path to exterior door to eliminate trip hazard
341412 02/15/2016 315807 4 103A O Remove and prohibit storage of all combustible residential furniture in CCTV studio
382299 02/15/2016 404914 4 105 O Prohibit plugging surge protector into surge protector and into an extension cord under computer stations - Replace with longer cord surge protectors and plug each surge protector directly into wall outlet
382189 02/15/2016 404679 4 221 O Prohibit plugging surge protector into surge protector at teacher desk - plug each surge protector directly into wall outlet
382172 02/15/2016 404643 5 106 O Provide cover strip for electrical cords running across floor adjacent to teacher station and secure cover strip to flooring to eliminate trip hazard
382170 02/15/2016 404639 5 106A O Maintain closet room in an orderly manner
382171 02/15/2016 404641 5 107 O Provide cover strip for electrical cords running across floor adjacent to teacher station and secure cover strip to flooring to eliminate trip hazard
382186 02/15/2016 404673 5 208 O Remove and prohibit hanging decorations from ceiling
382175 02/15/2016 404650 6 102 O Secure electrical cord cover strip to flooring to eliminate trip hazard
382185 02/15/2016 404671 6 204 O Remove glass mirror behind sink or provide mirror made of tempered glass, safety glass, or stainless steel
382181 02/15/2016 404663 6 208 O Remove and prohibit hanging paper and decorations from ceiling
382182 02/15/2016 404665 6 208 O Remove glass mirror in back corner or provide mirror made of tempered glass, safety glass, or stainless steel
382179 02/15/2016 404659 6 211 O Remove glass mirror behind teacher desk or provide mirror made of tempered glass, safety glass, or stainless steel
382180 02/15/2016 404661 6 214 O Remove glass mirror on metal cabinet or provide mirror made of tempered glass, safety glass, or stainless steel
382183 02/15/2016 404667 6 215 O Eliminate 13A white extension cord with multiple outlet end plugged into a surge protector at teacher desk
382184 02/15/2016 404669 6 218 O Remove and prohibit excessive flammable vinyl sheathing on wall: behind sink, behind computer stations, on window glass and on the board
382177 02/15/2016 404654 6 220 O Remove and prohibit plug in air freshener
382178 02/15/2016 404656 6 220 O Remove glass mirror behind teacher desk or provide mirror made of tempered glass, safety glass, or stainless steel
382061 02/15/2016 404390 9 101B O Keep custodial room in dining room locked and latched to prohibit student access
332383 02/15/2016 296177 9 180 O Remove chain and padlock from gate on cage to allow egress from inside cage at all times
382308 02/15/2016 404935 3 002 MS Replace BC with ABC fire extinguisher in corridor adjacent to 3-104
382262 02/15/2016 404839 3 108 MS Adjust corridor door to latch properly
382282 02/15/2016 404878 4 171 MS Replace missing fire extinguisher in elevator machine room
382187 02/15/2016 404675 5 206 MS Adjust corridor door to latch properly - door rubs on frame
359193 02/15/2016 354731 1 192 OS Remove all storage from mechanical room
246597 02/15/2016 112917 1 192 OS Prohibit storage of golf cart and charging golf cart batteries in mechanical room
341695 02/15/2016 316423 10 105 OS Remove storage from electrical room
246786 02/15/2016 113307 11 0000 OS Remove all combustible and flammable storage below bleachers including tires, gas powered lawn equipment, storage container and mats
382042 02/15/2016 404351 12 117 OS Relocate table blocking clear access to exterior door
382368 02/15/2016 405062 12 192 OS Remove storage from electrical room
372281 02/15/2016 383111 2 006 OS Remove and prohibit storage on stairway to mechanical mezzanine
382058 02/15/2016 404384 2 102H OS Remove storage in front of corridor door to maintain 3 ft clear path to exit door
382049 02/15/2016 404366 2 107B OS Remove all storage within yellow striped space around equipment in back of room
382247 02/15/2016 404807 3 101 OS Prohibit storage of tire in exterior kiln fenced area - relocate to flammable storage room 8-181
317569 02/15/2016 263449 4 191 OS Prohibit charging Golf Cart batteries in room
382363 02/15/2016 405052 5 192 OS Prohibit storage of golf cart and charging batteries in mechanical room
372081 02/15/2016 382688 6 192 OS Prohibit storing golf cart and charging batteries in mechanical room
277199 02/15/2016 176287 7 101 OS Prohibit storing golf cart and charging batteries in room
332404 02/15/2016 296221 7 192 OS Prohibit storing golf cart and charging batteries in mechanical room
359243 10/23/2015 354824 00 0000 M Repair broken lawn sprinklers or provide drainage in tree islands in courtyard North of Cafeteria and in front of Building 5 to prevent standing water and mosquito breeding areas
372287 10/23/2015 383123 2 0000 M Repair broken safety chain on second floor landing of access ladder to catwalk adjacent to telecommunications room
372159 10/23/2015 382847 2 0000 M Repair leaking expansion joint in ceiling under exterior walkway on the north side of gymnasium
332386 10/23/2015 296183 9 191 M Provide current state inspection tag for boiler (boiler is 200 gallons)
372079 10/23/2015 382684 6 106 O Prohibit plugging surge protector into surge protector at teachers desk
359246 10/23/2015 354838 7 111 O Remove and prohibit combustible furniture (residential couch)
277217 10/23/2015 176323 12 0000 C Provide roof over exterior stair on east side of building - Has another roofed means of egress to other buildings
372095 10/23/2015 382718 10 106 OS Prohibit and remove storage of flammable materials in bathroom (store flammables in flammable storage room)
372166 10/23/2015 382861 11 190 OS Remove storage from electrical room (pitching machine and plastic banner)
332328 10/23/2015 296059 2 0000 OS Remove and prohibit all storage on second level landing of ladder going up to catwalk above 2-190 (furniture and other flammables stored on landing)
359197 10/23/2015 354739 2 294 OS Remove storage from electrical room
341701 10/23/2015 316438 4 221 OS Relocate computer station tables adjacent to both exit doors to maintain 3 ft clear path to exits
257354 10/23/2015 136004 7 103 OS Relocate computer table adjacent to door to provide minimum 12" clearance on latch side of door
359298 03/18/2015 354948 00 0000 M Repair or replace damaged center mullion on gates in east courtyard at Northeast corner of Building 8
372289 03/18/2015 383127 1 0000 M Seal expansion joint on exterior wall under covered walkway on the north side of Building 1 adjacent to 1-126
372269 03/18/2015 383087 1 192 M Provide current annual and quarterly inspection tag for fire sprinkler system
372270 03/18/2015 383089 1 192 M Repair damaged wall adjacent to door
372161 03/18/2015 382851 10 102 M Replace broken ceramic base tile at entrance to men's restroom
341693 03/18/2015 316418 10 105 M Provide correct signage (10-105) indicating room name and number at both exterior doors- current sign reads 10-106
341975 03/18/2015 317022 11 0000 M Provide correct signage indicating room name and number at appropriate height with raised and Braille characters for pressbox - Current signs numbers are not correct
359204 03/18/2015 354753 11 202 M Determine cause of water damaged ceiling tiles and replace tiles
372071 03/18/2015 382668 12 0000 M Secure loose center handrail on exterior stairs
372271 03/18/2015 383091 12 002 M Determine cause of water damaged ceiling tiles in corridor adjacent to drinking fountains and replace tiles
372072 03/18/2015 382670 12 110 M Determine cause of water damaged ceiling tiles and replace tiles
372073 03/18/2015 382672 12 118 M Determine cause of water damaged ceiling tiles and replace tiles
372074 03/18/2015 382674 12 180 M Repair hole in wall next to mop sink
372068 03/18/2015 382661 12 191 M Provide current quarterly inspection tag for fire sprinkler system
372069 03/18/2015 382663 12 203 M Repair drinking fountain by windows
372288 03/18/2015 383125 2 102D M Replace sound deadening panels on wall or remove sharp edged mounting brackets which held the old sound panels to the wall
372286 03/18/2015 383121 2 105 M Determine cause of water damaged ceiling tiles in corridor at south entrance doors and replace tiles
372285 03/18/2015 383119 2 105F M Determine cause of water damaged and missing ceiling tiles and replace tiles
341663 03/18/2015 316352 2 107B M Replace missing ceiling tiles
372157 03/18/2015 382843 3 002 M Determine cause of water damaged ceiling tiles and replace tiles
372114 03/18/2015 382755 3 101C M Repair exhaust fan at kiln
372156 03/18/2015 382841 3 102B M Provide current quarterly inspection tag for fire sprinkler system
341380 03/18/2015 315736 3 103B M Determine cause of water damaged ceiling tiles and replace tiles
372168 03/18/2015 382865 3 193 M Provide correct mounting bracket for fire extinguisher and mount fire extinguisher at maximum five feet above floor (extinguisher is currently sitting on the floor because mounting bracket does not fit extinguisher)
372112 03/18/2015 382751 3 201 M Repair non-working light fixture
372110 03/18/2015 382747 3 216 M Secure sink to wall in girls bathroom
372111 03/18/2015 382749 3 217 M Secure loose metal bottom edge on divider between urinal and toilet stall
372109 03/18/2015 382745 3 292 M Provide current quarterly inspection tag for fire sprinkler system
372279 03/18/2015 383107 4 101 M Determine cause of water damaged ceiling tiles adjacent to 4-103 and replace tiles
372107 03/18/2015 382741 4 217 M Replace missing ceiling tiles
372108 03/18/2015 382743 4 292 M Provide current quarterly inspection tag for fire sprinkler system
372106 03/18/2015 382739 5 0000 M Replace broken lighted exit sign in second floor exterior walkway adjacent to 5-291
372089 03/18/2015 382704 5 102 M Determine cause of water damaged ceiling tiles at teachers desk and replace tiles
372088 03/18/2015 382702 5 106A M Determine cause of water damaged ceiling tiles and replace tiles
372090 03/18/2015 382706 5 115 M Determine cause of water damaged ceiling tiles and replace tiles
372085 03/18/2015 382696 5 192 M Repair damaged wall at door
372086 03/18/2015 382698 5 192 M Provide current quarterly inspection tag for fire sprinkler system
372099 03/18/2015 382725 5 209 M Repair non-working light fixture
372100 03/18/2015 382727 5 210A M Repair non-working light fixture
372098 03/18/2015 382723 5 215B M Repair damaged wall behind toilet in women's restroom
372094 03/18/2015 382715 5 216 M Replace missing ceramic wall tile at entrance to girls restroom
372093 03/18/2015 382712 5 217 M Repair damaged wall next to floor at the entrance to boys restroom
372091 03/18/2015 382708 5 292 M Provide current quarterly inspection tag for fire sprinkler system
372092 03/18/2015 382710 5 292 M Pad and mark corners of ductwork which are lower than 6 feet 8 inches
372080 03/18/2015 382686 6 103 M Determine cause of water damaged ceiling tiles and replace tiles
372078 03/18/2015 382682 6 107 M Determine cause of water damaged ceiling tiles and replace tiles
372082 03/18/2015 382690 6 192 M Provide current quarterly inspection tag for fire sprinkler system
372083 03/18/2015 382692 6 192 M Repair damaged wall at door
372103 03/18/2015 382733 6 210A M Anchor toilet to floor
372101 03/18/2015 382729 6 292 M Provide current quarterly inspection tag for fire sprinkler system
372102 03/18/2015 382731 6 292 M Repair wall damage at entrance door
372077 03/18/2015 382680 7 113 M Anchor toilet to floor in boy's restroom
372075 03/18/2015 382676 7 192 M Replace missing fire sprinkler heads in spare heads box
372076 03/18/2015 382678 7 192 M Provide current quarterly inspection tag for fire sprinkler system
372273 03/18/2015 383095 8 102 M Repair inoperable light fixture
372272 03/18/2015 383093 8 105 M Repair inoperable light fixture
372274 03/18/2015 383097 8 190 M Provide current quarterly inspection tag for fire sprinkler system
372275 03/18/2015 383099 8 196 M Provide current emergency lighting and generator certificate (current certification indicates last certification was 6-24-13)
372277 03/18/2015 383103 9 101 M Determine cause of water damaged ceiling tiles around sprinkler head at north exit door and replace tiles
372278 03/18/2015 383105 9 102D M Replace missing lens on light fixture
372276 03/18/2015 383101 9 180 M Repair hole in wall above baseboard at rear exterior exit door
372172 03/18/2015 382875 9 190 M Provide current quarterly inspection tag for fire sprinkler system
359308 03/18/2015 354968 00 0000 O Prohibit the use of stones to hold open security gates on the north side of Gymnasium Building
341678 03/18/2015 316383 2 107B O Maintain storage room in an orderly manner and provide 3 ft path to mechanical equipment in the back
372282 03/18/2015 383113 2 292 O Prohibit electrical cords from being running through electric room door and down stairway
341401 03/18/2015 315781 4 103 O Eliminate (6) plug electrical outlet adaptor adjacent to windows or replace with a surge protector
372097 03/18/2015 382720 5 206 O Remove and prohibit use of plug in air fresheners
246738 03/18/2015 113208 00 0000 C Provide returns at ends of all intermediate handrails for all exterior stairs
372164 03/18/2015 382857 10 106 C Provide correct signage on south door indicating room name and number at appropriate height with raised and Braille characters (current sign indicates 10-108, replace sign with one that corresponds with Fish number on map 10-106)
372165 03/18/2015 382859 10 108 C Provide signage on north door indicating room name and number at appropriate height with raised and Braille characters (use sign after removing it from south door of 10-106 and place it on the north door of 10-108, see Fish map for proper room numbers)
372162 03/18/2015 382853 10 105 MS Recharge fire extinguisher
372280 03/18/2015 383109 2 107 MS Recharge fire extinguisher at northeast exit door of Auditorium
372284 03/18/2015 383117 2 290 MS Provide current inspection tag for fire extinguisher in mechanical room
372283 03/18/2015 383115 2 291 MS Provide current inspection tag for fire extinguisher in mechanical room
372113 03/18/2015 382753 3 001 MS Recharge fire extinguisher in corridor
372158 03/18/2015 382845 3 002 MS Provide current inspection tag for fire extinguisher
372104 03/18/2015 382735 6 210 MS Provide current inspection tag for type K fire extinguisher next to range
372105 03/18/2015 382737 6 220 MS Provide current inspection tag for fire extinguisher
372169 03/18/2015 382867 8 193 MS Provide current inspection tag for fire extinguisher
341711 03/18/2015 316461 10 105 OS Prohibit storage of propane gas cylinder - relocate to flammable storage room adjacent to custodial receiving
372087 03/18/2015 382700 5 108 OS Remove pictures covering fire extinguisher cabinet
359260 03/18/2015 354867 5 192 OS Prohibit storing golf cart and charging batteries in mechanical room
277069 03/18/2015 176018 9 180 OS Prohibit charging batteries for floor cleaning machines in room
372163 03/18/2015 382855 10 105 CS Replace fire extinguisher which has been spray painted with white spray paint (gage and inspection tag are covered with white paint, cannot see what they indicate)
359307 11/26/2014 354966 00 0000 M Repair or replace broken auto closers on security gates on north side of Gymnasium
359299 11/26/2014 354950 00 0000 M Repair or replace all broken closers and latching mechanisms on gates at east courtyard to provide campus to be properly secured
359291 11/26/2014 354932 00 0000 M Repair or replace bent column on covered walkway at east bus loop adjacent to 8-193
341974 11/26/2014 317019 11 0000 M Replace missing lens on light fixture in pressbox
332327 11/26/2014 296057 12 170 M Provide current inspection tag for elevator (current tag expired 8-01-09)
359198 11/26/2014 354741 2 105D M Replace missing ceiling tiles
359196 11/26/2014 354737 2 106A M Replace broken floor tiles at south exit door of stage
372160 11/26/2014 382849 3 101C M Replace corroded fire sprinkler head inside kiln room
359215 11/26/2014 354776 4 0000 M Repair or replace broken plastic elbow on rain downspout on the west side of Building 4
359257 11/26/2014 354860 8 194 M Remove trees and vegetation growing inside cooling tower enclosure
341699 11/26/2014 316432 3 201 O Remove and prohibit combustible residential armchair
341413 11/26/2014 315809 4 105 O Remove and prohibit combustible residential couch
341700 11/26/2014 316434 4 106A O Prohibit plugging surge protector into surge protector under computer stations adjacent to teacher's desk and adjacent to exterior door (X2)
359271 11/26/2014 354892 6 102B O Remove and prohibit combustible (residential) furniture (sofa and chair)
341324 11/26/2014 315617 6 106 O Eliminate extension cords with multiple outlet end adjacent to teacher's station (X2)
359287 11/26/2014 354920 8 194 C Replace rusted and missing safety railings at the top of Cooling Tower CT2 inside cooling tower enclosure
372084 11/26/2014 382694 5 192 OS Remove and prohibit golf cart storage in mechanical room (N/A, this is duplicate of citation 359260)
332405 11/26/2014 296223 7 192 OS Prohibit charging golf cart batteries in mechanical room (N/A, this is a duplicate of citation 332404)
341676 11/26/2014 316379 00 0000 CS Provide suitable area for storage or charging golf cart batteries
341677 11/26/2014 316381 00 0000 CS Provide suitable area for charging floor cleaning machines
359309 03/18/2014 354971 00 0000 M Repair broken conduit so electrical wiring is not exposed in damaged support column of covered walkway at east bus loop east of Building 8
359279 03/18/2014 354909 12 010 M Secure hanging lighted exit sign in second floor corridor at east exit door
359277 03/18/2014 354905 12 105 M Secure hanging lighted exit sign
359301 03/18/2014 354954 12 209 M Determine cause of water damaged ceiling tiles and replace tiles
359278 03/18/2014 354907 12 213 M Repair lock on door to operate properly
359235 03/18/2014 354816 12 216 M Replace missing toilet seat
359300 03/18/2014 354952 12 291 M Provide current maintenace log for hot water heater (over 60 gallons)
359194 03/18/2014 354733 2 106A M Replace missing center mullion on fire doors on stage
359202 03/18/2014 354749 2 292 M Replace missing doors on electrical panels 2L2 and 2H2 to maintain electrical equipment in a safe, secure condition
359206 03/18/2014 354757 3 0000 M Determine cause of banging noise comming from water pipes in girls locker room and repair problem
359217 03/18/2014 354780 3 0000 M Secure loose handrail at bottom landing of stairway on east side of Building 3
359205 03/18/2014 354755 3 002 M Replace missing escutcheon on fire sprinkler head in corridor adjacent to 3-111
359220 03/18/2014 354784 3 008 M Place ceiling tiles in corridor adjacent to 3-205 back into metal ceiling grid
359207 03/18/2014 354759 3 105F M Repair hole in wall above vinyl base
359210 03/18/2014 354765 3 106 M Place ceiling tiles back into metal ceiling grid
359208 03/18/2014 354761 3 107 M Repair doors to corridor to close properly
359209 03/18/2014 354763 3 107 M Replace broken ceiling tile and place other tiles back into metal ceiling grid
359211 03/18/2014 354767 4 104 M Determine cause of water damaged ceiling tiles and replace tiles
359212 03/18/2014 354769 4 180 M Provide maintenance inspection log for hot water heater (60 gallons or more)
359267 03/18/2014 354884 5 112 M Repair inoperable light fixtures (X2)
359306 03/18/2014 354964 5 208 M Repair inoperable light fixture
359305 03/18/2014 354962 5 210 M Repair inoperable light fixture
359221 03/18/2014 354790 5 292 M Repair holes in wall adjacent to door
359274 03/18/2014 354899 6 106C M Secure loose door handle
359275 03/18/2014 354901 6 108 M Determine cause of water damaged ceiling tiles and replace tiles
359272 03/18/2014 354895 6 112 M Replace missing ceiling tiles in entrance of boys restroom
359269 03/18/2014 354888 6 191 M Provide cover on exposed electrical junction box on wall above air conditioner unit
359304 03/18/2014 354960 6 207 M Repair inoperable light fixture
359302 03/18/2014 354956 6 211 M Repair inoperable light fixture
359276 03/18/2014 354903 7 105 M Determine cause of water damaged ceiling tiles and replace tiles
359226 03/18/2014 354799 8 004 M Determine cause of water damaged ceiling tiles in corridor adjacent to 8-117 and replace tiles
359252 03/18/2014 354854 8 111 M Place ceiling tiles back into metal ceiling grid
359225 03/18/2014 354796 8 115 M Replace broken toilet seat in boys bathroom
359283 03/18/2014 354913 8 193 M Secure loose fire alarm strobe - horn to wall inside chiller room next to entrance door
359223 03/18/2014 354793 9 101C M Determine cause of water damaged ceiling tiles and replace tiles
359250 03/18/2014 354845 9 102 M Secure loose door handle on door between kitchen and serving line
359251 03/18/2014 354852 9 102F M Anchor toilet to floor in mens room
359229 03/18/2014 354805 9 180 M Connect dryer duct to back of clothes dryer in custodial receiving room
359231 03/18/2014 354809 9 191 M Mount fire extinguisher to wall at maximum five feet above floor
277109 03/18/2014 176099 2 106B O Prohibit plugging portable a/c unit into extension cord - plug directly into permanent electrical outlet
359273 03/18/2014 354897 6 110 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
359303 03/18/2014 354958 6 208 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
341651 03/18/2014 316328 7 111 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
359192 03/18/2014 354729 1 003 MS Provide current inspection tag for fire extinguisher located in corridor
359199 03/18/2014 354743 2 105 MS Recharge fire extinguisher in corridor in front of concessions room
359200 03/18/2014 354745 2 290 MS Provide current inspection tag for fire extinguisher in second floor mehanical room
359203 03/18/2014 354751 2 291 MS Provide current inspection tag for fire extinguisher in second floor mechanical room
359201 03/18/2014 354747 2 292 MS Provide current inspection tag for fire extinguisher in electric room
341664 03/18/2014 316354 3 102B MS Provide current inspection tags for fire sprinkler system - annual and quarterly
359233 03/18/2014 354812 12 203 OS Relocate trash container blocking clear access to fire extinguisher
277110 03/18/2014 176101 2 106B OS Prohibit ducting portable a/c unit above ceiling
359195 03/18/2014 354735 2 106J OS Provide clear access to fire extinguisher at exit door
359213 03/18/2014 354774 4 191 OS Remove storage from mechanical room
341326 03/18/2014 315619 6 106 OS Prohibit running electrical cord across path to exterior door
332406 12/04/2013 296225 00 0000 M Provide spare sprinkler head boxes with spare sprinkler heads and wrench in all first floor mechanical rooms containing fire sprinkler control valves and main lines
332408 12/04/2013 296229 12 191 M Replace missing wrench from fire sprinkler spare heads box
341441 12/04/2013 315873 2 106F M Repair door lever to turn easily
341661 12/04/2013 316348 3 101C M Replace broken dial for exhaust fan timer in kiln room
341672 12/04/2013 316370 1 122 O Prohibit plugging copier into surge protector - plug directly into permanent electrical outlet
341675 12/04/2013 316376 1 135A O Prohibit plugging microwave into surge protector in principal's closet - plug directly into permanent electrical outlet or place a work order to have an outlet closer to the microwave
341705 12/04/2013 316446 12 206B O Remove lock and screw eyes from door
341706 12/04/2013 316448 12 206C O Remove lock and screw eyes from door
341355 12/04/2013 315683 3 107 O Remove and prohibit paper/ tape covering windows in corridor door
341696 12/04/2013 316426 3 201B O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
341698 12/04/2013 316430 3 203 O Remove and prohibit hanging decorations from ceiling
341697 12/04/2013 316428 3 210 O Remove and prohibit hanging paper from ceiling
341402 12/04/2013 315786 4 103 O Remove and prohibit hanging decorations from ceiling adjacent to back door
341341 12/04/2013 315654 6 208 O Remove mirror or provide mirror made of tempered glass, safety glass, or stainless steel located in the back adjacent to the microwave
341343 12/04/2013 315658 6 211 O Remove and prohibit paper on ceiling tiles
341653 12/04/2013 316332 7 101 O Prohibit plugging surge protector into extension cord behind computer stations adjacent to 7-111. Plug surge protector directly into wall outlet
341650 12/04/2013 316326 9 101B O Keep custodial room door locked and latched to prohibit unauthorized access
246590 12/04/2013 112903 1 190 C Provide additional fire sprinkler head to provide coverage on both sides of equipment
341640 12/04/2013 316306 1 192 MS Provide current inspection tag for fire sprinkler system
341641 12/04/2013 316308 12 191 MS Provide current annual inspection tag for fire sprinkler system (X2)
341352 12/04/2013 315678 2 192 MS Provide current annual inspection tag for fire sprinkler system
341660 12/04/2013 316346 3 101C MS Replace heavily corroded fire sprinkler head in kiln room
341349 12/04/2013 315673 3 292 MS Provide current annual inspection tag for fire sprinkler system
341350 12/04/2013 315675 4 191 MS Provide current annual inspection tag for fire sprinkler system
341348 12/04/2013 315670 4 292 MS Provide current annual inspection tag for fire sprinkler system
341644 12/04/2013 316314 5 192 MS Provide current annual inspection tag for fire sprinkler system
341347 12/04/2013 315668 5 292 MS Provide annual current inspection tag for fire sprinkler system
341643 12/04/2013 316312 6 192 MS Provide current annual inspection tag for fire sprinkler system
341345 12/04/2013 315664 6 292 MS Provide current annual inspection tag for fire sprinkler system
341642 12/04/2013 316310 7 192 MS Provide current annual inspection tag for fire sprinkler system
341639 12/04/2013 316304 8 190 MS Provide current annual inspection tag for fire sprinkler system
341638 12/04/2013 316302 9 190 MS Provide current annual inspection tag for fire sprinkler system
341437 12/04/2013 315862 2 106C OS Relocate storage to maintain 3 ft clean path to corridor door
341353 12/04/2013 315681 3 105E OS Remove and prohibit use of toaster oven
341654 12/04/2013 316334 6 192 OS Remove and prohibit storing golf cart and charging batteries in room
341634 02/19/2013 316294 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
341694 02/19/2013 316420 10 106 M Replace missing signage indicating room name and number - 10-106 signs were posted incorrectly on 10-105
341689 02/19/2013 316410 10 108 M Replace missing light bulbs and grille for light fixture
341424 02/19/2013 315833 2 0000 M Determine cause of water damaged ceiling tiles and replace tiles in corridor between gym and auditorium
341666 02/19/2013 316358 2 001 M Secure exit sign hanging from wires in corridor adjacent to 2-102
341419 02/19/2013 315821 2 103 M Replace missing sinks (X2)
341429 02/19/2013 315847 2 105F M Determine cause of water damaged ceiling tiles and replace tiles
341972 02/19/2013 317014 2 106A M Secure all electrical wiring for speakers at front edge of stage
341687 02/19/2013 316405 2 107 M Modify maximum occupancy signage to read 1850 occupants - sign adjacent to SE exit doors read 2400
341378 02/19/2013 315733 3 103D M Caulk gap between sinks to wall
341377 02/19/2013 315687 3 105D M Replace missing graspable bar behind toilet in handicapped stall
341381 02/19/2013 315739 3 201 M Replace missing signage indicating room name and number with Braille characters
341383 02/19/2013 315743 3 218 M Repair emergency lighting in classroom to work properly
341385 02/19/2013 315747 3 280 M Secure ceiling tile in place
341703 02/19/2013 316442 4 213 M Adjust exterior door to latch properly
341387 02/19/2013 315749 5 007 M Repair light in exit sign adjacent to 5-206 (corridor)
341338 02/19/2013 315649 5 106 M Replace damaged floor tiles adjacent to 5-106A
341652 02/19/2013 316330 7 101 M Replace missing lever for emergency eye wash adjacent to 7-111
341636 02/19/2013 316298 8 101 M Replace missing ceiling tiles adjacent to sinks
341637 02/19/2013 316300 8 101 M Replace missing lens on light fixture adjacent to sinks
341633 02/19/2013 316292 9 102 M Adjust two burners cook top to be under hood fire suppression nozzle
341632 02/19/2013 316290 9 182 M Repair exhaust fan
341673 02/19/2013 316372 1 122 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
341674 02/19/2013 316374 1 122 O Prohibit plugging surge protector into surge protector - plug each surge directly into wall outlet
341691 02/19/2013 316414 10 101 O Prohibit plugging refrigerator into extension cord - plug directly into permanent electrical outlet
341709 02/19/2013 316455 12 101 O Prohibit covering electrical outlet with paper under writing board
341707 02/19/2013 316451 12 203 O Remove and prohibit hanging decorations from ceiling
341704 02/19/2013 316444 12 210 O Eliminate extension cord with multiple outlet end for fan on back wall or replace with a surge protector
341708 02/19/2013 316453 12 214 O Remove and prohibit use of halogen lamp
341671 02/19/2013 316368 2 104 O Remove and prohibit combustible residential couch
341669 02/19/2013 316364 2 104A O Eliminate gray extension cord with multiple outlet end or replace with a surge protector
341428 02/19/2013 315842 2 105E O Prohibit plugging surge protector into surge protector in control booth - plug each surge protector directly into wall outlet
341435 02/19/2013 315858 2 106 O Remove steps in front of stage. Steps do not meet code requirements(X2)
341680 02/19/2013 316389 2 106 O Prohibit plugging surge protector into extension cord at wooden control booth
341962 02/19/2013 316992 2 106 O Remove small control station and related wiring to restore wheel chair seating area
341667 02/19/2013 316360 2 106A O Replace missing center mullion on double fire doors to corridor adjacent to 2-106B
341655 02/19/2013 316336 2 106A O Eliminate extension cord with multiple outlet end for lamp on wall between dressing rooms 2-106C & 2-106E. Contact FMC for installing proper light fixture
341657 02/19/2013 316340 2 106A O Maintain storage at loft above stage in an orderly manner and maintain clear path to electrical room
341417 02/19/2013 315813 4 104 O Remove mirror on column adjacent to door into media center or provide mirror made of tempered glass, safety glass, or stainless steel
341702 02/19/2013 316440 4 201B O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
341339 02/19/2013 315652 5 115 O Post sign indicating evacuation routes
341323 02/19/2013 315615 6 106 O Prohibit plugging surge protector into surge protector at teacher's station - plug each surge protector directly into wall outlet
341321 02/19/2013 315611 6 106C O Remove glass top table or replace with tempered glass or safety glass
341335 02/19/2013 315642 6 108 O Remove and prohibit placing decorations on ceiling tiles
341330 02/19/2013 315631 6 109 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
341331 02/19/2013 315635 6 110 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
341333 02/19/2013 315637 6 110 O Eliminate (6) plug electrical outlet adaptor adjacent to teacher's desk or replace with a surge protector
341344 02/19/2013 315661 6 203 O Remove and prohibit paper covering light fixture
341690 02/19/2013 316412 10 108 C Provide emergency lighting in locker room
246930 02/19/2013 113576 2 0000 C Provide fire sprinkler coverage for chair lift room between 2-105 & 2-105E
341659 02/19/2013 316344 3 101C F Replace rusted heat detector in kiln room
341422 02/19/2013 315827 2 0000 MS Replace missing fire extinguisher in corridor adjacent to 2-103
341668 02/19/2013 316362 2 101 MS Adjust corridor door to latch properly
341670 02/19/2013 316366 2 104 MS Replace missing fire extinguisher
341662 02/19/2013 316350 3 106 MS Adjust corridor door to latch properly
341646 02/19/2013 316318 12 107 OS Prohibit use of door wedge as hold open device on corridor door
341710 02/19/2013 316457 12 114 OS Rearrange desks to maintain 3 ft clear path to corridor door
341647 02/19/2013 316320 12 116 OS Prohibit use of door wedge as hold open device on corridor door
341648 02/19/2013 316322 12 117 OS Prohibit use of door wedge as hold open device on corridor door
341688 02/19/2013 316408 12 204 OS Prohibit use of door wedge as hold open device on corridor door
341649 02/19/2013 316324 12 211 OS Prohibit use of door wedge as hold open device on corridor door
341665 02/19/2013 316356 2 001 OS Remove all storage from corridor adjacent to 2-102
341685 02/19/2013 316400 2 105E OS Prohibit running electrical cord through window to wooden control booth in auditorium
341683 02/19/2013 316395 2 106 OS Remove all storage along ramp to stage (X2)
341684 02/19/2013 316397 2 106 OS Prohibit running electrical cords along and across aisles in auditorium and ramps to stage to maintain safe egress. Some cords were covered with carpret remnants which are not acceptable
341444 02/19/2013 315877 2 106A OS Remove all storage from access ladder area to catwalk to maintain safe egress (ground and intermediate landing)
341439 02/19/2013 315867 2 106E OS Relocate storage to maintain 3 ft clean path to corridor door
341431 02/19/2013 315850 2 190C OS Remove all storage from systems room and keep door locked and latched
341656 02/19/2013 316338 2 294 OS Remove storage from electrical room at loft above stage and keep door locked and latched
341658 02/19/2013 316342 3 101 OS Relocate floor fan to maintain clear access to exterior door
341336 02/19/2013 315646 5 106A OS Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
332420 02/19/2013 296254 5 115A OS Prohibit surge protector cord from running through doorway to 5-115
341322 02/19/2013 315613 6 106 OS Remove cord tied to exterior door - prohibiting right door leaf from opening
341328 02/19/2013 315625 6 107A OS Remove and prohibit use of electrical cooker (Xpress-Redi Set Go)
341645 02/19/2013 316316 6 108 OS Prohibit use of door wedge as hold open device on corridor door
341389 02/19/2013 315755 6 206 OS Prohibit use of wedge as hold open device on corridor door
341390 02/19/2013 315759 6 207 OS Prohibit use of door wedge as hold open device on corridor door
341392 02/19/2013 315763 6 215 OS Prohibit use of wedge as hold open device on corridor door
341635 02/19/2013 316296 8 101A OS Remove dining room tables from exit hallway adjacent to 8-109
309191 02/19/2013 244964 9 182 OS Prohibit storage of flammable materials, relocate tires to flammable storage room
341692 02/19/2013 316416 10 101 CS Provide ABC fire extinguisher in concession room
246622 02/19/2013 112972 9 102 CS Relocate pull station for kitchen hood suppression system to be along path of egress
332324 10/19/2012 296052 2 101 M Replace missing center mullion on double fire door going into corridor
309146 10/19/2012 244871 4 103A M Provide dated flame resistance label on CCTV curtain
332390 10/19/2012 296191 8 101 M Repair or replace seal on freezer door to prevent ice forming around door, preventing it from closing properly
277143 10/19/2012 176170 2 106J O Provide rated cabinet for flammable storage
332314 10/19/2012 296032 2 106A C Repair or replace torn stage curtain
332413 10/19/2012 296239 12 107 OS Prohibit storage of propane tanks inside room
277144 10/19/2012 176172 2 106J OS Keep all flammable materials stored in flammable storage cabinet
246698 10/19/2012 113126 5 192 OS Immediately remove and prohibit golf cart and charging batteries in mechanical room
332306 03/26/2012 296015 1 125 M Replace missing ceiling tiles
332325 03/26/2012 296053 10 0000 M Repair signs on rooms 10-105 and 10-106 to correspond to FISH map numbers
277227 03/26/2012 176343 10 106 M Replace missing signage indicating room name and number - current sign reads 10-105
332326 03/26/2012 296055 10 107 M Replace missing signage indicating room name and number
317625 03/26/2012 263563 12 0000 M Repair or replace deteriorated/dislodged handrail for stairs on landing/ closest to building # 7
332412 03/26/2012 296237 12 107 M Determine cause of water damaged ceiling tiles and replace tiles
332414 03/26/2012 296241 12 110 M Determine cause of water damaged ceiling tiles and replace tiles
332410 03/26/2012 296233 12 291 M Repair two leaky valves on chilled water return lines in mechanical room (water leaking onto floor)
332322 03/26/2012 296048 2 104 M Mount fire extinguisher to wall (bracket is broken and fire extinguisher is on the floor)
332320 03/26/2012 296044 2 105 M Replace missing escutcheon on fire sprinkler head in corridor
332318 03/26/2012 296040 2 105D M Replace missing ceiling tiles in concessions room
332317 03/26/2012 296038 2 105F M Replace missing ceiling tiles
332311 03/26/2012 296026 2 106 M Replace missing center divider mullion on fire doors to corridor on north side of stage
332309 03/26/2012 296022 2 106J M Replace missing ceiling tiles
332335 03/26/2012 296074 3 003 M Replace hose and nozzle on fire extinguisher inside cabinet at east exit door of corridor
332330 03/26/2012 296064 3 101C M Repair exhaust fan in kiln room
332331 03/26/2012 296066 3 103B M Determine cause of water damaged ceiling tiles and replace tiles
332332 03/26/2012 296068 3 105 M Secure hanging lighted exit sign in boys locker room
332334 03/26/2012 296072 3 190 M Replace missing ceiling tiles
332396 03/26/2012 296205 3 208 M Determine cause of water damaged ceiling tiles and replace tiles
332397 03/26/2012 296207 3 292 M Provide covers on exposed electrical junction boxes on ceiling (X2) in mechanical room
332398 03/26/2012 296209 3 292 M Mount fire extinguisher at maximum five feet above floor
332378 03/26/2012 296167 4 105 M Replace missing escutcheon on fire sprinkler head
332377 03/26/2012 296165 4 106 M Determine cause of water damaged ceiling tiles and replace tiles
309152 03/26/2012 244883 5 104 M Determine cause of water damaged ceiling tiles and replace tiles
332416 03/26/2012 296246 5 106 M Determine cause of water damaged ceiling tiles above teachers desk and next to north wall and replace tiles
332419 03/26/2012 296252 5 115A M Replace missing escutcheon on fire sprinkler head
332400 03/26/2012 296213 5 213 M Place ceiling tiles back into metal ceiling grid
332402 03/26/2012 296217 6 203A M Replace missing escutcheon on fire sprinkler head in womens restroom
332387 03/26/2012 296185 8 110 M Provide cover for exposed 220 volt electrical outlet next to dryer
332388 03/26/2012 296187 8 110 M Replace missing ceiling tiles
332380 03/26/2012 296171 8 115 M Repair broken toilet seat in handicap stall
332384 03/26/2012 296179 8 181 M Repair crack in west wall next to ceiling in flammable storage room
332385 03/26/2012 296181 8 196 M Repair emergency lighting in generator room
332379 03/26/2012 296169 9 101 M Repair Northwest exit door of cafeteria to close properly (adjust closer to overcome inside air pressure so door will close)
332381 03/26/2012 296173 9 101C M Replace missing ceiling tiles
332382 03/26/2012 296175 9 101C M Replace broken lens on light fixture
332393 03/26/2012 296197 9 190 M Mount fire extinguisher at maximum five feet above floor
332305 03/26/2012 296012 1 222 O Prohibit plugging microwave oven and refrigerator into surge protector - plug directly into permanent electrical outlet
332329 03/26/2012 296062 2 106A O Prohibit plugging multiple extension cords into other extension cords powering small lights at front of stage floor
332308 03/26/2012 296020 2 106J O Prohibit plugging microwave oven into multi-outlet extension cord - plug directly into permanent electrical outlet
332333 03/26/2012 296070 3 101 O Remove and prohibit paper covering window in door
317551 03/26/2012 263412 3 105 O Post sign indicating evacuation routes
332417 03/26/2012 296248 5 106 O Prohibit plugging surge protector into extension cord at aquarium
332421 03/26/2012 296256 5 205 O Prohibit plugging microwave oven into surge protector (adjacent to teachers desk)- plug directly into permanent electrical outlet
332395 03/26/2012 296202 5 214 O Prohibit plugging microwave oven and refrigerator into surge protector - plug directly into permanent electrical outlet
317642 03/26/2012 263609 9 101F O Remove extension cord extending through ceiling
332422 03/26/2012 296259 2 106 C Remove wooden structure at rear of seating area in auditorium or provide certification by Building Department that structure meets code and design requirements
332304 03/26/2012 296010 00 0000 MS Provide chain and padlock on valves on red fire main at southwest corner of Building 2 (Gym) to prevent tampering of fire main
332307 03/26/2012 296017 1 154 MS Provide current inspection tag for fire extinguisher
332407 03/26/2012 296227 12 190 MS Provide current inspection tag for fire extinguisher in systems room
332411 03/26/2012 296235 12 290 MS Provide current inspection tag for fire extinguisher
332321 03/26/2012 296046 2 104 MS Recharge fire extinguisher
332312 03/26/2012 296028 2 106 MS Provide current inspection tags for two (2)fire extinguishers on catwalk above stage
332376 03/26/2012 296163 4 103B MS Provide current inspection tag for fire extinguisher in CCTV Control Room
332401 03/26/2012 296215 5 008 MS Recharge fire extinguisher in second floor corridor adjacent to south exit doors
332418 03/26/2012 296250 5 102 MS Provide current inspection tag for fire extinguisher
332403 03/26/2012 296219 6 220 MS Provide current inspection tag for fire extinguisher
332389 03/26/2012 296189 8 001 MS Provide current inspection tag for fire extinguisher in corridor adjacent to north entrance door
332392 03/26/2012 296195 8 192 MS Provide current inspection tag for fire extinguisher
293671 03/26/2012 211399 2 001 OS Remove all storage from corridor
332323 03/26/2012 296050 2 002 OS Immediately remove and prohibit all storage from exit corridor
332319 03/26/2012 296042 2 105 OS Immediately remove and prohibit storage of folding tables in exit corridor
332315 03/26/2012 296034 2 106 OS Remove lights and extension cords from stage ramps to maintain clear aisle for exiting from stage
332316 03/26/2012 296036 2 106 OS Prohibit extension cords from running under rugs at rear of seating areas and behind Seating Row X
332313 03/26/2012 296030 2 106A OS Prohibit electrical cord from running over stage rigging to power lights on stage (extension cords are not to be used to replace permenant wiring)
332310 03/26/2012 296024 2 106A OS Remove tape on door of fire extinguisher cabinet to allow access to fire extinguisher
332423 03/26/2012 296262 2 106H OS Remove and prohibit storage under roll-up fire door so door will close properly in case of fire
309122 03/26/2012 244821 2 107A OS Prohibit charging floor machine batteries in room
332399 03/26/2012 296211 5 292 OS Prohibit charging floor cleaning machine batteries in mechanical room
332415 03/26/2012 296244 7 108 OS Prohibit storage of motorcycle, gas powered bicycle, and automotive lubricants
332391 03/26/2012 296193 8 101 OS Prohibit charging floor machine batteries in room
246640 03/26/2012 113011 3 0000 CS Provide fire sprinkler coverage for outside kiln room (this is an outside storage room with kilns that are no longer operable and are stored in the space)
317616 01/26/2012 263550 2 102 M Replace missing threshold in 3/4 hour double door
317682 01/26/2012 263689 8 101 M Remove debris from fire sprinkler head, looks like gum, north walk-in cooler
317646 01/26/2012 263614 8 116 M Repair broken tile base in accessible stall
309210 01/26/2012 245004 10 101 O Remove black stove w/burners or provide a commercial hood system
277067 01/26/2012 176014 10 101 O Remove and prohibit use of deep fat fryers
309120 01/26/2012 244817 2 105D O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
317694 01/26/2012 263711 9 102 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
309115 01/26/2012 244807 2 106J OS Prohibit charging Golf Cart batteries in room
309113 01/26/2012 244803 2 190 OS Prohibit hold open devices on fire doors
293578 01/26/2012 211196 5 116 OS Prohibit running electrical cord under door to 5-115A
293879 03/03/2011 211839 00 0000 M Provide fire sprinkler spare heads box and wrench adjacent to all fire sprinkler risers throughout school
317700 03/03/2011 263728 1 154 M Mount fire extinguisher at maximum five feet above floor
317697 03/03/2011 263721 1 155A M Provide cover on exposed electrical junction box
317508 03/03/2011 263321 10 001 M Mount fire extinguisher at maximum five feet above floor
317509 03/03/2011 263323 11 0000 M Replace exterior outlet cover
317630 03/03/2011 263575 12 0000 M Repair cover in exit sign on 2nd floor balcony
317601 03/03/2011 263521 12 107 M Replace missing ceiling tile above projector screen
317603 03/03/2011 263523 12 120 M Repair out of order urinal, covered w/black plastic bag
317608 03/03/2011 263534 12 190 M Repair panic hardware, cover missing
317631 03/03/2011 263582 12 203 M Repair fire extinguisher cabinet
317633 03/03/2011 263585 12 210 M Repair door to close properly
317618 03/03/2011 263554 2 101 M Repair two hanging escutcheons on fire sprinkler heads
317612 03/03/2011 263543 2 102H M Replace missing ceiling tile
317610 03/03/2011 263539 2 102K M Repair loose door handle
317510 03/03/2011 263325 2 103A M Secure sink to wall in accessible stall
317511 03/03/2011 263327 2 103A M Repair out of service toilet covered with plastic bag
317516 03/03/2011 263339 2 104 M Replace missing escutcheon on fire sprinkler head
317619 03/03/2011 263557 2 105E M Mount fire extinguisher at maximum five feet above floor
317620 03/03/2011 263559 2 105E M Provide cover on exposed electrical junction box on 2nd level
317513 03/03/2011 263333 2 107B M Provide cover on exposed electrical junction box above ceiling
317514 03/03/2011 263335 2 107B M Replace broken electrical outlet
278241 03/03/2011 178494 2 107B M Replace missing ceiling tiles
317515 03/03/2011 263337 2 292 M Provide panel schedule for Panel 2LSH2
317517 03/03/2011 263341 3 0000 M Provide cover on exposed outlet at soda machine closest to building #2
317518 03/03/2011 263343 3 007 M Repair exterior door to close properly
317546 03/03/2011 263402 3 102 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to entry door
317548 03/03/2011 263406 3 103G M Replace missing escutcheon on fire sprinkler head
317549 03/03/2011 263408 3 105 M Repair hanging exit sign
317550 03/03/2011 263410 3 105G M Repair door to close properly
317558 03/03/2011 263428 3 107 M Replace broken ceiling tile
317552 03/03/2011 263414 3 110 M Repair loose door handle
317523 03/03/2011 263355 4 0000 M Replace cover on exterior outlet at vending machine adjacent to 4-104
317524 03/03/2011 263357 4 0000 M Replace cover on exterior outlet adjacent to 3-192
317567 03/03/2011 263442 4 101 M Determine cause of water damaged ceiling tiles and replace tiles, above bookcase containing 569/COH & 468/BAR, also to the right of the front desk
317559 03/03/2011 263431 4 104 M Determine cause of water damaged ceiling tiles and replace tiles, center of room between sprinkler heads
317562 03/03/2011 263437 4 106A M Determine cause of water damaged ceiling tiles and replace tiles
317571 03/03/2011 263453 4 191 M Repair wall damaged by Golf Cart
317520 03/03/2011 263348 4 208 M Replace missing escutcheon on fire sprinkler head
317521 03/03/2011 263350 4 209 M Replace missing escutcheon on fire sprinkler head
317519 03/03/2011 263345 4 218 M Repair faucet in accessible stall
317522 03/03/2011 263353 4 292 M Mount fire extinguisher at maximum five feet above floor
309147 03/03/2011 244873 5 101 M Determine cause of water damaged ceiling tiles and replace tiles
317542 03/03/2011 263393 5 103 M Repair hanging escutcheon on fire sprinkler head
317540 03/03/2011 263389 5 105 M Determine cause of water damaged ceiling tiles and replace tiles
317543 03/03/2011 263395 5 113 M Repair faucet # 2
309154 03/03/2011 244887 5 115 M Determine cause of water damaged ceiling tiles and replace tiles
317574 03/03/2011 263461 5 192 M Repair door to close properly
317536 03/03/2011 263381 5 210 M Repair exterior door to close properly
317538 03/03/2011 263385 5 291 M Unlock panel 5LSH2 for inspection
317537 03/03/2011 263383 5 292 M Unlock panel 5EQHZ for inspection
317583 03/03/2011 263481 6 102 M Repair exterior door to close properly
317585 03/03/2011 263484 6 102 M Determine cause of water damaged ceiling tiles and replace tiles, above teachers desk
317582 03/03/2011 263478 6 102C M Determine cause of water damaged ceiling tiles and replace tiles
309181 03/03/2011 244943 6 108 M Determine cause of water damaged ceiling tiles and replace tiles
317525 03/03/2011 263359 6 191 M Repair cover for panel 6D1 section 2 to properly close
317535 03/03/2011 263379 6 205 M Anchor shelving to wall
317534 03/03/2011 263377 6 206 M Replace missing escutcheon on fire sprinkler head
317533 03/03/2011 263375 6 210 M Determine cause of water damaged ceiling tiles and replace tiles
317529 03/03/2011 263367 6 212 M Replace broken light cover on 2 x 4 fixture
317589 03/03/2011 263495 7 191 M Provide cover on exposed electrical junction box on Horn/F.A.
317588 03/03/2011 263491 7 192 M Repair leaky bypass valve assembly
317681 03/03/2011 263687 8 101 M Repair exterior door adjacent to 8-180 to close properly
317650 03/03/2011 263626 8 108B M Anchor toilet to floor
317686 03/03/2011 263697 8 110 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to sprinkler head
317687 03/03/2011 263699 8 110 M Replace missing escutcheon on fire sprinkler head
317683 03/03/2011 263691 8 111 M Replace missing escutcheon on fire sprinkler head
317684 03/03/2011 263693 8 111 M Replace missing ceiling tile
317606 03/03/2011 263529 8 170 M Provide certification that all student occupied spaces have emergency lights and all are operable, old certificate dated 8-1-2009
317655 03/03/2011 263637 8 181 M Mount fire extinguisher at maximum five feet above floor
317658 03/03/2011 263643 8 194 M Provide cover on exposed electrical junction box adjacent to door
317635 03/03/2011 263590 9 0000 M Provide cover on exterior outlet
309186 03/03/2011 244953 9 101C M Determine cause of water damaged ceiling tiles and replace tiles
317653 03/03/2011 263630 9 180 M Repair door to interior cooridor to close properly
309111 03/03/2011 244799 1 135A O Eliminate multi-outlet adapter adjacent to refrigerator
317634 03/03/2011 263587 12 214 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
309119 03/03/2011 244815 2 105D O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
317512 03/03/2011 263329 2 105F O Prohibit plugging extension cord into surge protector
317547 03/03/2011 263404 3 103 O Post sign indicating evacuation routes
317541 03/03/2011 263391 5 105 O Keep area within 18" of fire sprinkler head clear
317578 03/03/2011 263468 6 102C O Prohibit plugging refrigerator and microwave into surge protector - plug directly into permanent electrical outlet
317580 03/03/2011 263475 6 102C O Prohibit plugging extension cord into surge protector
317577 03/03/2011 263464 6 104 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
317531 03/03/2011 263371 6 210 O Repair or replace dryer to eliminate hazardous condition, top of dryer extremely hot when operating. Do not use dryer.
317530 03/03/2011 263369 6 214 O Replace missing sign indicating evacuation routes
246743 03/03/2011 113218 11 200 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for all rooms at football field pressbox
246935 03/03/2011 113587 2 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for chair lift room between 2-105 & 2-105E
293685 03/03/2011 211428 2 102H C Provide tempered glass, safety glass, or stainless steel for mirrors
317699 03/03/2011 263724 1 154 MS Provide current inspection tag for fire extinguisher
317613 03/03/2011 263546 2 102 MS Provide current inspection tag for fire extinguisher
317544 03/03/2011 263397 3 001 MS Provide current inspection tag for fire extinguisher, fix cover on cabinet also
317561 03/03/2011 263434 4 103B MS Provide current inspection tag for fire extinguisher
317527 03/03/2011 263363 6 192 MS Provide current inspection tag for fire sprinkler system, existing tag marked as quarterly inspection and expired
317532 03/03/2011 263373 6 210 MS Provide current inspection tag for type "K" fire extinguisher
317528 03/03/2011 263365 6 292 MS Provide current inspection tag for fire sprinkler system, existing tag marked as quarterly inspection and expired
317643 03/03/2011 263612 8 004 MS Provide current inspection tag for fire extinguisher
317685 03/03/2011 263695 8 101 MS Provide current inspection tag for type "K" fire extinguisher adjacent to cook-top sub-panel 2
317689 03/03/2011 263703 8 192 MS Replace missing fire extinguisher
317696 03/03/2011 263716 1 113 OS Prohibit storage of flammable paints and engine cleaner
309112 03/03/2011 244801 1 149 OS Prohibit hold open devices on fire door
317545 03/03/2011 263400 3 102B OS Prohibit storage of flammable spray paint and mineral spirits
317688 03/03/2011 263701 8 110 OS Prohibit storage of flammable Sterno
317691 03/03/2011 263706 9 101C FS Provide certification that fire alarm system has been tested and is fully operational, not tagged but current report is in folder
309201 11/05/2010 244986 12 002 M Repair drinking fountain adjacent to 12-118
309204 11/05/2010 244992 12 216 M Secure sink to wall
277234 11/05/2010 176357 00 0000 O No access was available to plastic storage shed adjacent to football field. Please be prepared to access this shed during the report review meeting.
277112 11/05/2010 176105 2 106 O Eliminate extension cord below control booth window
277111 11/05/2010 176103 2 106B O Eliminate extension cord or replace with minimum 15A cord and prohibit running extension cord above ceiling
293648 11/05/2010 211348 3 218A O Remove and prohibit combustible (residential) sofa or prohibit access to room by students
293566 11/05/2010 211172 6 106 O Prohibit piggy backed surge protectors at table adjacent to exterior door - plug each surge protector directly into permanent electrical outlet and eliminate use of extension cord
277178 11/05/2010 176242 6 106A O Remove and prohibit halogen lamp
293565 11/05/2010 211170 6 106C O Prohibit plugging surge protector into surge protector and into extension cord - plug each surge protector directly into permanent electrical outlet and eliminate use of extension cord
246770 11/05/2010 113275 10 105 OS Immediately remove all storage from electrical room - especially propane cylinders
309207 11/05/2010 244998 10 107 OS Prohibit storage of flammable materials in room, (propane tanks)
309116 11/05/2010 244809 2 106J OS Prohibit storage of flammable spray paint
309197 04/29/2010 244977 00 0000 M Repair interior courtyard door between buildings #8 & #7 to open/close properly
293878 04/29/2010 211831 00 9599 M Provide hurricane anchorage for two storage containers just west of Bldg. 10
309110 04/29/2010 244797 1 115 M Determine cause of water damaged ceiling tiles and replace tiles
293660 04/29/2010 211376 1 115 M Adjust air flow to AC vent in video room
309206 04/29/2010 244996 10 102 M Repair damaged faucet @ fifth sink
246726 04/29/2010 113183 11 001 M Provide current inspection tag for elevator
309199 04/29/2010 244981 12 103 M Determine cause of water damaged ceiling tiles and replace tiles
309200 04/29/2010 244984 12 115 M Repair sink
309203 04/29/2010 244990 12 206 M Replace broken ceiling tile
309118 04/29/2010 244813 2 105 M Repair drinking fountain
277145 04/29/2010 176174 2 106J M Connect dust collection system for use with woodworking equipment
309123 04/29/2010 244823 2 107 M Repair rear door to open/close properly adjacent to 2-107A
309125 04/29/2010 244827 3 101A M Replace missing ceiling tile
309124 04/29/2010 244825 3 101C M Patch hole in drywall ceiling
298521 04/29/2010 221750 3 103B M Remove and prohibit reflective film covering window in doors and windows adjacent to door
298522 04/29/2010 221752 3 103G M Remove and prohibit reflective film covering window in doors and windows adjacent to door
293632 04/29/2010 211316 3 103G M Replace missing escutcheon on fire sprinkler head
277127 04/29/2010 176138 3 103H M Provide proper transition from flexible duct to rigid duct behind dryer
298523 04/29/2010 221754 3 105A M Remove and prohibit reflective film covering window in doors and windows adjacent to door
309127 04/29/2010 244831 3 105B M Replace base along wall
298524 04/29/2010 221756 3 105E M Remove and prohibit reflective film covering window in doors and windows adjacent to door
309132 04/29/2010 244841 3 106 M Determine cause of water damaged ceiling tiles and replace tiles
309134 04/29/2010 244845 3 109 M Repair door to open/close properly
309135 04/29/2010 244847 3 111 M Provide cover for exposed electrical outlet in mirror wall
309138 04/29/2010 244855 3 210 M Determine cause of water damaged ceiling tiles and replace tiles
309144 04/29/2010 244864 4 103A M Repair exterior door to open/close properly
309139 04/29/2010 244857 4 104 M Adjust ceiling tiles
309149 04/29/2010 244875 5 102 M Determine cause of water damaged ceiling tiles and replace tiles
309150 04/29/2010 244879 5 103 M Replace missing escutcheon on fire sprinkler head
309153 04/29/2010 244885 5 113 M Secure sink to wall in accessible stall
309160 04/29/2010 244901 6 216 M Patch hole in drywall ceiling
309179 04/29/2010 244938 6 220 M Replace missing escutcheon on fire sprinkler head
309166 04/29/2010 244907 6 290 M Repair drinking fountain
309198 04/29/2010 244979 7 105 M Determine cause of water damaged ceiling tiles and replace tiles
309190 04/29/2010 244962 9 101 M Repair fire extinguisher cabinet adjacent to 9-101C
309185 04/29/2010 244951 9 101 M Repair air curtain at doors
309188 04/29/2010 244957 9 101C M Replace missing ceiling tiles
309193 04/29/2010 244968 9 102H M Dryer vent crushed
309108 04/29/2010 244793 1 152 O Prohibit plugging toaster and coffee maker into surge protector - plug directly into permanent electrical outlet
293598 04/29/2010 211240 12 205 O Eliminate white extension cord with multiple outlet end behind teacher's desk or replace with a surge protector
309205 04/29/2010 244994 12 212 O Prohibit plugging refrigerator and microwave into surge protector - plug directly into permanent electrical outlet
277211 04/29/2010 176311 12 213 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
309114 04/29/2010 244805 2 106 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
309133 04/29/2010 244843 3 107 O Remove and prohibit paper covering window in door
293570 04/29/2010 211180 6 101C O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
309196 04/29/2010 244975 8 193 O No access was available to this room. Please be prepared to access this room during the report review meeting.
293673 04/29/2010 211403 9 102 O Prohibit plugging microwave into surge protector adjacent to 9-181 - plug directly into permanent electrical outlet
309192 04/29/2010 244966 9 191 O No access was available to this room. Please be prepared to access this room during the report review meeting.
294812 04/29/2010 213819 10 108 C Provide sign indicating maximum occupancy adjacent to main entrance
294810 04/29/2010 213815 10 108 C Provide emergency lighting
277088 04/29/2010 176056 5 105 C Provide 1/2" lips on shelves used for chemical storage
277077 04/29/2010 176034 9 101 C Provide illuminated exit sign in serving line area at door into 9-001
309195 04/29/2010 244973 8 194 F Repair broken fire alarm strobe/horn in cooling tower area
309209 04/29/2010 245002 10 108 MS Provide current inspection tag for fire extinguisher
309117 04/29/2010 244811 2 104 MS Provide current inspection tag for fire extinguisher
309126 04/29/2010 244829 3 103G MS Provide current inspection tag for fire extinguisher
309128 04/29/2010 244833 3 105B MS Replace missing fire extinguisher
309131 04/29/2010 244839 3 114 MS Provide current inspection tag for fire extinguisher
309130 04/29/2010 244837 3 193 MS Provide current inspection tag for fire extinguisher
293667 04/29/2010 211390 8 101 MS Provide current inspection tag for kitchen hood fire suppression system
277228 04/29/2010 176345 10 106 OS Prohibit storage of flammable spray paint
293854 04/29/2010 211784 11 191 OS Remove storage from electrical room
293672 04/29/2010 211401 2 002 OS Remove all storage from corridor
277142 04/29/2010 176168 2 106J OS Provide and maintain minimum 3' wide clear path to both doors
309158 04/29/2010 244894 5 210A OS Prohibit storage of flammable spray paint
246745 04/29/2010 113223 10 101 CS Provide type K fire extinguisher in concession booth
309194 04/29/2010 244970 9 101C FS Repair punchlist items as indicated on fire alarm inspection report dated 12/19/09
309202 01/08/2010 244988 12 191 M Replace missing wrench from fire sprinkler spare heads box
293856 01/08/2010 211788 2 105 M Replace rusted fire sprinkler head at north end of corridor
293655 01/08/2010 211364 2 106A M Mount light bars above stage ramps - see Mr. Blank (X2)
293656 01/08/2010 211366 2 106A M Repair fire curtain to operate properly - see Mr. Blank
293657 01/08/2010 211368 2 106A M Replace rusted fire sprinkler head above catwalk - see Mr. Blank
277146 01/08/2010 176176 2 106A M Replace missing section of guardrail along edge of fly system adjacent to exterior door
293893 01/08/2010 211867 2 106B M Adjust air flow to AC vent - see Mr. Blank
293555 01/08/2010 211150 6 112 M Replace rusted fire sprinkler head above handicapped stall
293554 01/08/2010 211148 6 216 M Replace rusted fire sprinkler head adjacent to bathroom vestibule
309109 01/08/2010 244795 1 110 O Remove and prohibit combustible (residential chairs) furniture, or treat with flame retardant and provide certification of that treatment
257329 01/08/2010 135947 2 006 O Remove and prohibit storage in stairwell
293677 01/08/2010 211412 2 104A O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
293678 01/08/2010 211414 2 104A O Prohibit plugging extension cord into surge protector and eliminate use of 13A extension cord
293680 01/08/2010 211418 2 104A O Relocate storage to keep area within 18" of fire sprinkler head clear
309121 01/08/2010 244819 2 105E O Remove and prohibit combustible (residential) furniture/ futon couch on 2nd level or treat with flame retardant and provide certification of that treatment
309136 01/08/2010 244850 3 201 O Remove and prohibit combustible (residential) furniture, couches, or treat with flame retardant and provide certification of that treatment
309137 01/08/2010 244853 3 208 O Remove and prohibit combustible (residential) furniture, chair
293644 01/08/2010 211340 3 211 O Eliminate extension cord with multiple oultet end adjacent to corridor door or replace with a surge protector
293623 01/08/2010 211298 3 211A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
277222 01/08/2010 176333 4 103A O Remove and prohibit combustible (residential) sofa and loveseat or treat with flame retardant and provide certification of that treatment
293650 01/08/2010 211354 4 105 O Remove mirror or provide mirror made of tempered glass, safety glass, or stainless steel
246777 01/08/2010 113289 5 106 O Remove and prohibit plugging surge protector into extension cord at aquarium - replace with surge protector long enough to reach to electrical outlet
293576 01/08/2010 211192 5 107 O Prohibit plugging surge protector into surge protector behind aquarium
293577 01/08/2010 211194 5 107 O Provide verification that written permission from principal has been provided to keep snakes in the classroom and that all required safety precautions are being followed
293574 01/08/2010 211188 5 108 O Prohibit plugging extension cord into surge protector at teacher's desk
293572 01/08/2010 211184 5 201B O Prohibit plugging refrigerator into extension cord - plug directly into permanent electrical outlet
293587 01/08/2010 211218 5 218 O Remove storage from stove burners
293571 01/08/2010 211182 6 101C O Remove and prohibit combustible residential couch and bean bag chair
293568 01/08/2010 211176 6 105 O Prohibit piggy backed surge protectors under computer stations at center of room - plug each surge protector directly into permanent electrical outlet and eliminate use of extension cord
293563 01/08/2010 211166 6 106A O Prohibit plugging microwave and toaster into surge protector - plug appliances directly into permanent electrical outlet
257158 01/08/2010 135587 6 106A O Prohibit surge protector plugged into surge protector, plug each surge protector directly into wall outlet
277165 01/08/2010 176215 6 202A O Remove and prohibit combustible (residential) sofa or prohibit access to room by students
293592 01/08/2010 211225 6 206 O Eliminate (3) plug electrical outlet adaptor adjacent to teacher's desk
293593 01/08/2010 211231 6 210 O Prohibit plugging surge protector into surge protector under computer stations
293603 01/08/2010 211249 6 213 O Remove and prohibit paper covering corridor door
293601 01/08/2010 211244 6 214 O Keep evacuation map inside designated frame on wall adjacent to door
277198 01/08/2010 176284 7 101 O Remove and prohibit halogen lamp - adjacent to door to fenced enclosure
293687 01/08/2010 211432 9 102 O Adjust two burner cook top to be under hood fire suppression nozzle
246565 01/08/2010 112847 2 106A C Provide gate at bottom of catwalk access ladder to prohibit unauthorized access to catwalks
293658 01/08/2010 211370 2 0000 MS Provide current inspection tag for fire extinguisher(X2) at stage catwalk
277219 01/08/2010 176327 12 209 OS Relocate desk to provide minimum 3' wide clear path to corridor door
293659 01/08/2010 211372 2 0000 OS Remove all storage from access ladder shaft to catwalk above stage
293683 01/08/2010 211424 2 102K OS Prohibit storage of flammable sterno cans
293855 01/08/2010 211786 2 105 OS Remove tables from corridor
277092 01/08/2010 176065 3 192 OS Remove storage from mechanical room
246748 01/08/2010 113229 4 221 OS Relocate computer tables blocking clear access to both exit doors
293586 01/08/2010 211215 5 218A OS Clean lint trap inside dryer and prohibit placing boxes on washer and dryer
293579 01/08/2010 211199 5 292 OS Remove custodial storage from mechanical room
293861 01/08/2010 211798 6 106 OS Prohibit use of wedge to hold fire door in open position
293862 01/08/2010 211800 6 108 OS Prohibit use of wedge to hold fire door in open position
257299 01/08/2010 135883 6 202 OS Remove computer tables from exit corridor
293674 01/08/2010 211405 8 109 OS Rearrange desks to maintain 3 ft clear path to exterior door
277073 01/08/2010 176026 9 101 OS Prohibit wedging open fire doors at 8-004
277076 01/08/2010 176032 9 180 OS Prohibit wedging open fire door at 9-001
277084 01/08/2010 176048 9 180 OS Remove and prohibit chain and padlock on gate in caged area
277196 01/08/2010 176280 12 190 CS Provide fire extinguisher in Systems Room
277216 01/08/2010 176321 12 290 CS Provide fire extinguisher in Systems Room
277156 03/27/2009 176196 11 200 M Determine cause of water damaged ceiling tiles and replace tiles in right room of pressbox
293557 03/27/2009 211154 12 107 M Determine cause of water damaged ceiling tiles and replace tiles at center of room
293558 03/27/2009 211156 12 115 M Secure loose door lever
293559 03/27/2009 211158 12 170 M Provide current inspection tag for elevator
246933 03/27/2009 113582 2 0000 M Provide current inspection tag for chair lift between 2-105 & 2-105E
277137 03/27/2009 176158 2 102E M Replace missing sound panel on wall
293684 03/27/2009 211426 2 102E M Provide cover for exposed electrical outlet
293628 03/27/2009 211309 3 007 M Adjust exterior doors at end of corridor to latch properly
293630 03/27/2009 211312 3 103H M Replace missing ceiling tiles
246654 03/27/2009 113041 3 105C M Provide signage indicating room name and number at appropriate height with raised and Braille characters
277128 03/27/2009 176140 3 114 M Seal gaps between fire sprinkler escutcheon and ceiling
293626 03/27/2009 211305 3 201B M Replace missing ceiling tiles
293617 03/27/2009 211287 4 006 M Adjust exterior doors at end of corridor to latch properly
293649 03/27/2009 211352 4 102 M Adjust exterior door to latch properly
293852 03/27/2009 211778 4 170 M Provide current inspection tag for elevator
293575 03/27/2009 211190 5 108 M Repair missing diffuser caps on emergency eye wash nozzles
277099 03/27/2009 176079 5 115 M Determine cause of water damaged ceiling tiles and replace tiles
293584 03/27/2009 211208 5 217 M Patch hole in wall adjacent to bathroom vestibule
293553 03/27/2009 211146 6 006 M Adjust exterior doors at end of corridor to latch properly
293567 03/27/2009 211174 6 106 M Replace missing ceiling tile adjacent to 6-105
293880 03/27/2009 211841 6 201 M Provide additional shelves for metal shelving unit to prevent using area underneath shelving as student space or barricade area to prevent student desks under shelving
293881 03/27/2009 211843 6 204 M Provide additional shelves for metal shelving unit to prevent using area underneath shelving as student space or barricade area to prevent student desks under shelving
293562 03/27/2009 211164 7 101 M Secure drill press to table top adjacent to 7-107
277086 03/27/2009 176052 8 101 M Replace missing bulb in socket in walk-in cooler next to cage area (light fixture adjacent to door)
277056 03/27/2009 175992 9 101 M Replace missing escutcheon on fire sprinkler head adjacent to 9-101A
293857 03/27/2009 211790 9 101 M Replace rusted and leaking fire sprinkler head at center of room
293686 03/27/2009 211430 9 8087 M Secure loose metal sheathing to sidewalk adjacent to 9-190
265546 03/27/2009 150819 00 0000 O Prohibit driving golf carts under covered walkway @ drop-off area behind Building 9, causing damage to walkway columns
293663 03/27/2009 211382 1 122 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
293665 03/27/2009 211386 1 152 O Prohibit plugging microwave and toasters into surge protector - plug appliances directly into permanent electrical outlet
293666 03/27/2009 211388 1 153 O Eliminate (3) plug electrical outlet adaptor adjacent to refrigerator
277062 03/27/2009 176004 12 0000 O Prohibit parking on grass area behind Bldg. 12
277185 03/27/2009 176258 12 104E O Remove and prohibit paper covering window in door
293681 03/27/2009 211420 2 104 O Remove mirror or provide mirror made of tempered glass, safety glass, or stainless steel
293682 03/27/2009 211422 2 104 O Remove and prohibit combustible residential couch
293642 03/27/2009 211336 3 102 O Eliminate string line and clothes hanging from ceiling in art room
293625 03/27/2009 211302 3 208 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
293573 03/27/2009 211186 5 110 O Eliminate (3) plug electrical outlet adaptor at science tables (X2)
293580 03/27/2009 211201 5 209 O Eliminate (6) plug electrical outlet adaptor behind teacher's desk
293569 03/27/2009 211178 6 102 O Prohibit plugging surge protector into extension cord at teacher's desk - plug surge protector directly into permanent electrical outlet and eliminate use of extension cord
293564 03/27/2009 211168 6 107A O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
293596 03/27/2009 211233 6 210 O Eliminate brown extension cord with multiple outlet end under teacher's desk or replace with a surge protector
293675 03/27/2009 211407 9 102A O Eliminate brown extension cord with multiple outlet end under desk
277079 03/27/2009 176038 9 102B O Remove storage from top shelf of center shelving unit to allow proper coverage of fire sprinkler heads
277070 03/27/2009 176020 9 180 O Remove storage from top shelf of free standing metal shelving unit to allow proper coverage of fire sprinkler heads
294813 03/27/2009 213821 10 108 C Provide or verify adequate ventilation for use as a locker room
294811 03/27/2009 213817 10 108 F Provide fire alarm horn / strobe light
293664 03/27/2009 211384 1 154 MS Provide current inspection tag for fire extinguisher
293853 03/27/2009 211782 11 200 MS Provide current inspection tag for fire extinguisher in pressbox
293551 03/27/2009 211142 12 010 MS Provide current inspection tag for fire extinguisher in corridor facing 12-206
293556 03/27/2009 211152 12 107A MS Provide current inspection tag for fire extinguisher
293670 03/27/2009 211397 2 102 MS Provide current inspection tag for fire extinguisher
293651 03/27/2009 211356 2 290 MS Provide current inspection tag for fire extinguisher
293653 03/27/2009 211360 2 291 MS Provide current inspection tag for fire extinguisher
293652 03/27/2009 211358 2 292 MS Provide current inspection tag for fire extinguisher
293633 03/27/2009 211318 3 103B MS Provide current inspection tag for fire extinguisher
293634 03/27/2009 211320 3 105E MS Provide current inspection tag for fire extinguisher
293635 03/27/2009 211323 3 191 MS Provide current inspection tag for fire extinguisher
293636 03/27/2009 211325 3 192 MS Provide current inspection tag for fire extinguisher
293621 03/27/2009 211293 3 218 MS Replace ABC fire extinguisher with a CO2 fire extinguisher in computer classroom
293552 03/27/2009 211144 6 220 MS Provide current inspection tag for fire extinguisher
293561 03/27/2009 211162 7 109 MS Provide current inspection tag for fire extinguisher
293668 03/27/2009 211393 9 102 MS Provide current inspection tag for kitchen hood fire suppression system
293669 03/27/2009 211395 9 102D MS Provide current inspection tag for fire extinguisher
293661 03/27/2009 211378 1 118 OS Remove and prohibit use of space heater
277059 03/27/2009 175998 1 125 OS Relocate display board blocking clear access to and visibility of fire alarm pull station
293560 03/27/2009 211160 12 105 OS Relocate table to provide clear access to fire extinguisher cabinet adjacent to 12-104A
293860 03/27/2009 211796 12 107 OS Prohibit use of wedge to hold fire door in open position
293859 03/27/2009 211794 12 117 OS Prohibit use of wedge to hold fire door in open position
293679 03/27/2009 211416 2 104A OS Remove and prohibit use of toaster oven
293654 03/27/2009 211362 2 106A OS Remove light bars along stage ramps (X2)
277147 03/27/2009 176178 2 106A OS Relocate all stage equipment to provide clear access to fire extinguisher cabinet, fire hose cabinet and stage curtain release
293676 03/27/2009 211410 2 106J OS Prohibit storage and recharging of golf cart in woodshop
293640 03/27/2009 211328 3 102B OS Prohibit leaving glue gun plugged in electrical outlet while unattended - glue gun was left plugged during Christmas break
293643 03/27/2009 211338 3 203 OS Remove and prohibit storage of insect spray in classroom under teacher's desk
277100 03/27/2009 176081 3 204 OS Remove storage blocking clear access to Emergency Access Window
293619 03/27/2009 211289 4 206 OS Remove desks blocking clear access to Emergency Access Window
293864 03/27/2009 211804 4 215 OS Prohibit use of wedge to hold fire door in open position
293863 03/27/2009 211802 5 206 OS Prohibit use of wedge to hold fire door in open position
277074 03/27/2009 176028 9 001 OS Prohibit wedging open fire door at cafeteria
277151 03/27/2009 176186 2 105D CS Provide fire extinguisher in concession booth
293875 03/27/2009 211821 00 9599 FS Provide heat detectors in two storage containers just west of Bldg. 10
277229 03/27/2009 176347 10 106 FS Provide heat detector in unsupervised room - used for storage
293858 03/27/2009 211792 9 101C FS Repair problems with fire alarm system - Troubles indicated on panel
277235 01/06/2009 176359 00 9599 M Replace missing top rail and secure loose fencing adjacent to 3rd base dugout on baseball field
277054 01/06/2009 175988 1 101 M Repair door to exterior (adjacent to fire alarm pull station) to open properly - hits concrete sidewalk
246942 01/06/2009 113599 2 106A M Install safety chain where catwalk meets ladder
277123 01/06/2009 176130 3 110 M Secure loose escutcheon on outside face of door lever
277122 01/06/2009 176128 3 111 M Replace missing escutcheon on fire sprinkler head
277107 01/06/2009 176095 4 103A M Change number on maximum occupancy sign from 91 to 49
277207 01/06/2009 176303 4 204 M Provide room name on sign indicating room number
277078 01/06/2009 176036 9 102D M Replace missing escutcheon on fire sprinkler head
278232 01/06/2009 178475 2 105 O Eliminate extension cord or replace with minimum 15A cord
277114 01/06/2009 176109 2 105E O Eliminate extension cord or replace with minimum 15A cord
277140 01/06/2009 176164 2 106J O Eliminate extension cords or replace with minimum 15A cords
277124 01/06/2009 176132 3 107 O Replace bulbs in emergency light fixture
277180 01/06/2009 176248 5 108 O Eliminate extension cord with multi-outlet end - replace with surge protector
277161 01/06/2009 176206 5 208 O Replace bulbs in emergency light fixture
277168 01/06/2009 176221 6 106A O Prohibit plugging extension cord into surge protector and prohibit use of multi-outlet extension cord
277068 01/06/2009 176016 9 180A O Replace electrical outlet box (used as an extension cord) with surge protector
246658 01/06/2009 113048 3 107 C Install GFCI outlet next to water fountain
277116 01/06/2009 176116 2 107B MS Provide current inspection tag for fire sprinkler system
277152 01/06/2009 176188 11 200 OS Remove and prohibit candles in center room of pressbox
277186 01/06/2009 176260 12 104 OS Prohibit parking car outside exterior door
277209 01/06/2009 176307 12 202 OS Remove storage adjacent to door to maintain minimum 12" clearance on latch side of door
277113 01/06/2009 176107 2 004 OS Remove and prohibit chairs in exit vestibule
277136 01/06/2009 176156 2 102K OS Remove and prohibit storage of flammable field marker paint
277141 01/06/2009 176166 2 106J OS Keep all sawdust cleaned from floors, equipment and other surfaces
257328 01/06/2009 135945 2 107A OS Prohibit charging batteries in room
246641 01/06/2009 113013 3 0000 OS Prohibit storage of propane gas cylinders in outside kiln room
277097 01/06/2009 176075 5 103 OS Provide minimum 3' wide clear path to exterior door
277108 01/06/2009 176097 5 105 OS Keep flammable acetone in flammable storage room or flammable storage cabinet
246637 01/06/2009 113005 9 180 OS Keep fire door at corridor closed and latched
257337 01/06/2009 135969 9 182 OS Prohibit charging batteries in room
277177 04/07/2008 176240 00 0000 M Replace missing waterproof outlet covers for all electrical outlets along exterior walls of courtyard
277061 04/07/2008 176002 1 190 M Replace missing ceiling tiles
277233 04/07/2008 176355 10 104 M Repair door to unlock properly
277226 04/07/2008 176341 10 108 M Repair door to latch properly - can pull door open when door is locked
277155 04/07/2008 176194 11 200 M Adjust door to latch properly for right room of pressbox
277153 04/07/2008 176190 11 200 M Adjust door to latch properly for center room of pressbox
277188 04/07/2008 176264 12 115 M Repair emergency lighting
277189 04/07/2008 176266 12 115 M Repair lights - half of lights do not turn on
277210 04/07/2008 176309 12 204 M Repair emergency lights
277139 04/07/2008 176162 2 001 M Adjust exterior door at end of corridor to latch properly
277133 04/07/2008 176150 2 101A M Repair door to close properly
277134 04/07/2008 176152 2 102D M Replace missing ceiling tiles
277115 04/07/2008 176111 2 107A M Replace out of place ceiling tile
277087 04/07/2008 176054 3 0000 M Secure loose metal cover strip plate at expansion joint in floor of 2nd floor covered walkway between Bldgs. 3 & 4
277063 04/07/2008 176006 3 001 M Replace ceiling tile with hole in it
277064 04/07/2008 176008 3 001 M Replace or remove broken plastic cover in fire extinguisher cabinet
277102 04/07/2008 176085 3 009 M Secure loose cover on exit sign outside 3-208
277125 04/07/2008 176134 3 103G M Secure hanging lens on light fixture
277130 04/07/2008 176144 3 114 M Adjust door to latch properly
246967 04/07/2008 113654 3 202 M Provide tempered glass, safety glass, or stainless steel for mirror or remove mirror (not needed)
277126 04/07/2008 176136 3 218 M Provide correct bracket for fire extinguisher and mount extinguisher adjacent to door
277096 04/07/2008 176073 5 103 M Repair inoperable Purge Fan
277090 04/07/2008 176061 5 104 M Relocate sign indicating Purge Fan to be over Purge Fan button - currently located above Emergency Shut-Off button
277183 04/07/2008 176254 5 106 M Determine cause of water damaged ceiling tiles and replace tiles
277181 04/07/2008 176250 5 108 M Repair faucets at student work stations to prevent spraying when shut-off valve under teacher's desk is turned on
277167 04/07/2008 176219 6 007 M Replace safety pin on fire extinguisher adjacent to 6-209
277176 04/07/2008 176237 6 101A M Chain helium cylinder to wall
277170 04/07/2008 176225 6 106 M Adjust exterior door adjacent to 6-106C to latch properly
277202 04/07/2008 176293 6 108 M Determine cause of water damaged ceiling tiles and replace tiles
277201 04/07/2008 176291 6 192 M Adjust door to latch properly
277200 04/07/2008 176289 7 191 M Adjust door to latch properly
277072 04/07/2008 176024 8 0000 M Replace damaged center mullion and damaged gate hinge on metal gate outside Bldg. 8 - gate cannot be closed
277081 04/07/2008 176042 8 101 M Repair hole in ceiling in cage area
277085 04/07/2008 176050 8 101A M Replace or remove broken plastic cover in fire extinguisher cabinet adjacent to 8-107
277071 04/07/2008 176022 8 192 M Replace missing ceiling tiles
277083 04/07/2008 176046 8 195 M Label all interior walls as 2 hour fire rated
277082 04/07/2008 176044 8 196 M Repair emergency lighting
277055 04/07/2008 175990 9 101A M Replace missing ceiling tiles
277060 04/07/2008 176000 1 132 O Remove and prohibit air freshener
277208 04/07/2008 176305 12 202 O Eliminate extension cord or replace with minimum 15A cord
277215 04/07/2008 176319 12 205 O Remove flags hanging from ceiling
277218 04/07/2008 176325 12 210 O Eliminate extension cord or replace with minimum 15A cord
277065 04/07/2008 176010 3 101 O Remove and prohibit paper covering window in door
277121 04/07/2008 176126 3 102 O Eliminate extension cord or replace with minimum 15A cord adjacent to 3-102B
257301 04/07/2008 135887 3 105 O Post sign indicating evacuation routes
277221 04/07/2008 176331 3 105E O Remove and prohibit reflective film covering window in door and windows adjacent to door
277132 04/07/2008 176148 3 201B O Remove and prohibit bug spray
277103 04/07/2008 176087 3 292 O Replace missing cover on floor drain and keep cover on drain
277104 04/07/2008 176089 4 0000 O Prohibit parking on grass area behind Bldg. 4
277206 04/07/2008 176301 4 220 O Replace missing sign indicating evacuation routes
277105 04/07/2008 176091 5 0000 O Prohibit parking on grass area behind Bldg. 5
277098 04/07/2008 176077 5 101 O Replace bulbs in emergency light fixture
277095 04/07/2008 176071 5 103 O Replace bulbs in emergency light fixture
277160 04/07/2008 176204 5 206 O Remove and prohibit air freshener
277157 04/07/2008 176198 5 292 O Replace cover on floor drain and keep cover on drain
277171 04/07/2008 176227 6 102B O Prohibit plugging surge protectors into surge protectors
277173 04/07/2008 176231 6 102C O Prohibit plugging appliance into extension cord - plug directly into permanent electrical outlet
277174 04/07/2008 176233 6 102C O Eliminate extension cord or replace with minimum 15A cord
277164 04/07/2008 176213 6 201 O Replace bulbs in emergency light fixtures
277166 04/07/2008 176217 6 206 O Remove and prohibit paper covering ceiling tiles
257303 04/07/2008 135892 6 206 O Remove and prohibit excessive flammable decorations, 20% coverage of walls is maximum
277204 04/07/2008 176297 6 211 O Remove and prohibit air freshener spray
277205 04/07/2008 176299 6 292 O Replace cover on floor drain and keep cover on drain
277197 04/07/2008 176282 7 101 O Eliminate extension cord or replace with minimum 15A cord adjacent to emergency eye wash
277052 04/07/2008 175984 00 0000 C Designate visitor parking spaces so that spaces are readily visible upon entering parking lot - signage in lot leads toward staff parking spaces
277135 04/07/2008 176154 2 102G C Provide tempered glass, safety glass, or stainless steel for mirrors
277172 04/07/2008 176229 6 102B C Provide suitable wiring for computers to eliminate need for multiple surge protectors
277057 04/07/2008 175994 1 192 MS Replace missing fire extinguisher
277225 04/07/2008 176339 10 107 MS Provide current inspection tag for fire extinguisher
277184 04/07/2008 176256 12 121 MS Adjust corridor door to latch properly
277192 04/07/2008 176272 12 171 MS Provide current inspection tag for fire extinguisher (dated 7/06)
277191 04/07/2008 176270 12 191 MS Provide current inspection tag for fire extinguisher (dated 7/06)
277193 04/07/2008 176274 12 192 MS Provide current inspection tag for fire extinguisher (dated 7/06)
277106 04/07/2008 176093 4 292 MS Provide current inspection tag for fire extinguisher (dated 7/06)
277194 04/07/2008 176276 6 191 MS Provide current inspection tag for fire extinguisher (dated 7/06)
277195 04/07/2008 176278 6 192 MS Provide current inspection tag for fire extinguisher (dated 7/06)
277080 04/07/2008 176040 9 182 MS Replace missing fire extinguisher
277053 04/07/2008 175986 1 101 OS Relocate plant from in front of fire extinguisher cabinet
277058 04/07/2008 175996 1 191 OS Remove storage from electrical room
246596 04/07/2008 112915 1 192 OS Remove storage from mechanical room
277066 04/07/2008 176012 10 101 OS Remove and prohibit storage of propane cylinder
277150 04/07/2008 176184 10 105 OS Keep fire extinguisher on bracket
277187 04/07/2008 176262 12 107 OS Prohibit running electrical cord through door into 12-107A
277190 04/07/2008 176268 12 111 OS Remove desk adjacent to corridor door to maintain minimum 12" clearance on latch side of door
277214 04/07/2008 176317 12 207 OS Relocate desks blocking clear path to door
277212 04/07/2008 176313 12 292 OS Keep fire extinguisher on bracket
277213 04/07/2008 176315 12 292 OS Remove storage from mechanical room
277138 04/07/2008 176160 2 001 OS Remove and prohibit all storage along corridor
277148 04/07/2008 176180 2 006 OS Remove and prohibit running electrical cord up steps and through doors into 2-290 and 2-292
277149 04/07/2008 176182 2 105 OS Remove tables from corridor
278238 04/07/2008 178487 2 105D OS Prohibit use of electric grill in concession booth
277118 04/07/2008 176120 3 101B OS Remove and prohibit storage of flammable air duster and turpenoid
277119 04/07/2008 176122 3 102B OS Prohibit storage of flammable spray paint
277120 04/07/2008 176124 3 102B OS Remove and prohibit use of toaster oven
277129 04/07/2008 176142 3 114 OS Remove and prohibit storage on fire extinguisher
277091 04/07/2008 176063 3 192 OS Keep fire extinguisher on bracket
277131 04/07/2008 176146 3 201B OS Remove and prohibit storage of field marker paint
277101 04/07/2008 176083 3 214 OS Remove and prohibit use of toaster and toaster oven
277224 04/07/2008 176337 4 101 OS Relocate flag covering fire extinguisher cabinet adjacent to staff desk
277223 04/07/2008 176335 4 103A OS Remove furniture blocking clear path to exterior door
277093 04/07/2008 176067 5 102 OS Prohibit wedging open corridor door
277094 04/07/2008 176069 5 103 OS Prohibit wedging open corridor door
277089 04/07/2008 176058 5 104 OS Prohibit wedging open corridor door
257166 04/07/2008 135610 5 109 OS Remove and prohibit Raid Bug Spray
277179 04/07/2008 176246 5 110A OS Remove and prohibit propane cylinder
277182 04/07/2008 176252 5 111 OS Prohibit wedging open corridor door
277158 04/07/2008 176200 5 203 OS Prohibit wedging open corridor door
277159 04/07/2008 176202 5 206 OS Prohibit wedging open corridor door
277162 04/07/2008 176208 5 209 OS Relocate desk blocking clear path to corridor door
277163 04/07/2008 176210 5 210A OS Prohibit storage of flammable spray paint and flammable spray adhesive
277175 04/07/2008 176235 6 101C OS Remove and prohibit use of toaster oven
277169 04/07/2008 176223 6 106B OS Remove and prohibit use of toaster oven
277203 04/07/2008 176295 6 213 OS Prohibit wedging open corridor door
277232 04/07/2008 176353 10 102 FS Provide heat detector in unsupervised room
277231 04/07/2008 176351 10 103 FS Provide heat detector in unsupervised room
277230 04/07/2008 176349 10 107 FS Provide heat detector in unsupervised room - used for storage
277154 04/07/2008 176192 11 200 FS Secure hanging heat detector in right room of pressbox
277117 04/07/2008 176118 3 101C FS Secure hanging heat detector
265545 11/20/2007 150816 00 0000 M Repair damaged aluminum column covers along covered walkway at drop-off area behind Building 9
257311 11/20/2007 135908 1 125 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
246725 11/20/2007 113180 12 170 M Provide current inspection tag for elevator
257369 11/20/2007 136035 2 101 M Secure hanging escutcheon on fire sprinkler head
257314 11/20/2007 135914 2 102C M Replace missing escutcheon on fire sprinkler head
257320 11/20/2007 135929 2 106A M Remove and prohibit wooden storage rooms (x2)
257376 11/20/2007 136050 3 114 M Replace missing escutcheons on fire sprinkler heads
246670 11/20/2007 113074 4 170 M Provide current inspection tag for elevator - dated 3/23/04
257297 11/20/2007 135879 6 218C M Determine cause of corrosion and replace corroded sprinkler head
257346 11/20/2007 135987 8 111 M Replace missing ceiling tiles
246720 11/20/2007 113171 4 212 O Eliminate extension cord or replace with minimum 15A cord
265548 11/20/2007 150825 5 0000 O Maintain clear paths, in all science labs, from teacher's work station to emergency shut off button
246910 11/20/2007 113536 5 104 O Replace missing fire blanket
257169 11/20/2007 135616 5 116 O Eliminate 13A extension cord powering turtle tank or replace with minimum 15A cord or surge protector
257373 11/20/2007 136044 5 192 O Remove and prohibit storage of golf cart
257298 11/20/2007 135881 6 202 O Remove and prohibit combustible (residential) furniture
257300 11/20/2007 135885 6 202A O Prohibit use of multi outlet electrical adaptor
257368 11/20/2007 136033 9 101F O Prohibit extension cords plugged into each other, plug each cord directly into wall outlet
248324 11/20/2007 116468 00 0000 C Provide suitable area for storage of golf carts and charging golf cart batteries
257384 11/20/2007 136066 10 102 MS Replace missing fire extinguisher
257385 11/20/2007 136068 10 103 MS Replace missing fire extinguisher
257315 11/20/2007 135916 2 102C MS Remove plastic protectors on fire sprinkler heads
257366 11/20/2007 136028 1 121 OS Prohibit charging batteries in room
257279 11/20/2007 135838 3 101B OS Prohibit storage of flammable spray paint
246775 11/20/2007 113284 3 201 OS Remove and prohibit toaster oven
257273 11/20/2007 135825 3 213 OS Remove and prohibit candles
257167 11/20/2007 135612 5 108 OS Provide clear access to fire extinguisher
257165 11/20/2007 135608 5 109 OS Remove and prohibit candles (located in display case)
246697 11/20/2007 113124 6 292 OS Immediately remove and prohibit charging batteries in mechanical room
246784 11/20/2007 113303 7 101 OS Remove mats from exit corridors
257391 02/15/2007 136083 00 0000 M Provide sign indicating "Fire Sprinkler Riser Inside" at all Fire Sprinkler Riser Rooms
265543 02/15/2007 150811 00 0000 M Secure loose labels indicating 2-hour fire rating on interior walls of all electrical rooms
265544 02/15/2007 150813 00 9599 M Provide padlock on gate for fence enclosure at electrical transformers along drop-off area in behind Building 8
257365 02/15/2007 136026 1 103 M Replace missing ceiling tiles
257367 02/15/2007 136030 1 115 M Secure A/C vent cover
257310 02/15/2007 135906 1 191 M Mount fire extinguisher at maximum five feet above floor
257379 02/15/2007 136056 10 102 M Repair damaged flooring at entrance to restroom, missing floor tiles
257389 02/15/2007 136079 11 200 M Determine cause of water damaged ceiling tiles and replace tiles
257309 02/15/2007 135904 12 107B M Repair exhaust fan in bathroom
257371 02/15/2007 136039 12 206A M Replace missing base along wall
257316 02/15/2007 135920 2 102J M Replace missing ceiling tiles
257319 02/15/2007 135926 2 106 M Replace missing section of wall finish
257312 02/15/2007 135910 2 106A M Replace missing doorknob stop in wall
257317 02/15/2007 135922 2 106B M Provide cover on exposed electrical junction box
257325 02/15/2007 135939 2 107 M Replace missing A/C vent cover
257327 02/15/2007 135943 2 107 M Replace missing exit sign above exterior door
265547 02/15/2007 150822 2 107B M Paint a line around area designated for storage
257278 02/15/2007 135835 3 101C M Mount fire extinguisher at maximum five feet above floor
257281 02/15/2007 135843 3 103B M Determine cause of water damaged ceiling tiles and replace tiles
257276 02/15/2007 135831 3 202 M Replace missing ceiling tiles
257274 02/15/2007 135827 3 208 M Replace sign indicating Emergency Egress with sign indicating Emergency Access
257272 02/15/2007 135823 3 213 M Replace missing ceiling tiles
257269 02/15/2007 135817 4 005 M Repair hole in wall
257360 02/15/2007 136016 4 104 M Replace missing escutcheon on fire sprinkler head
257362 02/15/2007 136020 4 104 M Determine cause of water damaged ceiling tiles and replace tiles
257363 02/15/2007 136022 4 191 M Mount fire extinguisher at maximum five feet above floor
257270 02/15/2007 135819 4 208 M Replace missing escutcheon on fire sprinkler head
257295 02/15/2007 135874 5 006 M Secure loose escutcheon on fire sprinkler head
257358 02/15/2007 136012 5 101 M Repair broken sidewalk at covered walkway outside exterior door to 5-101, uneven concrete creates a tripping hazard
257168 02/15/2007 135614 5 104 M Determine cause of water damaged ceiling tiles and replace tiles
257289 02/15/2007 135861 5 206 M Repair hole in wall where doorknob stopper was pushed in
257286 02/15/2007 135855 5 210 M Replace missing ceiling tiles
257293 02/15/2007 135870 5 218 M Replace missing escutcheon on fire sprinkler head
257294 02/15/2007 135872 5 218 M Reposition cover back into place on exposed electrical junction box
257163 02/15/2007 135601 6 105 M Replace missing escutcheon on fire sprinkler head
257162 02/15/2007 135597 6 106 M Provide cover on exposed electrical junction box on west wall
257160 02/15/2007 135593 6 106 M Replace missing ceiling tiles and ceiling tiles with holes
265549 02/15/2007 150828 6 106 M Patch holes in wall adjacent to 6-105 where drinking fountain was removed
246682 02/15/2007 113101 6 205 M Change sign indicating Emergency Egress to Emergency Access
246683 02/15/2007 113103 6 209 M Change sign indicating Emergency Egress to Emergency Access
257352 02/15/2007 136000 7 101 M Paint safety lines around equipment
257353 02/15/2007 136002 7 101 M Anchor and secure shelves to wall
257355 02/15/2007 136006 7 103 M Provide covers on exposed electrical junction boxes
257347 02/15/2007 135989 8 0000 M Provide tempered or safety glass or film in display cabinet across from 8-102
257334 02/15/2007 135959 8 0000 M Repair holes in wall adjacent to 8-108A
257343 02/15/2007 135981 8 101 M Provide sign indicating location of fire alarm pull station
257344 02/15/2007 135983 8 101 M Replace missing ceiling tiles
257345 02/15/2007 135985 8 101 M Mount K fire extinguisher at maximum five feet above floor
257332 02/15/2007 135955 8 101A M Replace missing cover on exposed electrical junction across from 8-109
257349 02/15/2007 135993 8 193 M Determine cause of water leaking on floor and repair, floor is covered in standing water
247008 02/15/2007 113734 9 101 M Provide sign at doors leading into bathroom corridor 8-004 indicating "No Exit"
257336 02/15/2007 135967 9 102D M Mount fire extinguisher at maximum five feet above floor
257364 02/15/2007 136024 1 152 O Prohibit microwave plugged into surge protector, plug microwave directly into wall outlet
257307 02/15/2007 135900 12 121 O Remove and prohibit air freshener
257372 02/15/2007 136041 12 213 O Prohibit microwave and refrigerator plugged into surge protector, plug each appliance into a wall outlet
257318 02/15/2007 135924 2 106 O Eliminate orange 13A extension cord or replace with minimum 15A cord. Prohibit plugging extension cords into surge protectors, plug each directly into a wall outlet
257321 02/15/2007 135931 2 106H O Remove broken mirror
257323 02/15/2007 135935 2 106J O Maintain storage room in an orderly manner
257326 02/15/2007 135941 2 107B O Remove storage from area around cold water return pipes
257271 02/15/2007 135821 3 211A O Prohibit microwave plugged into surge protector, plug microwave directly into wall outlet
257275 02/15/2007 135829 3 214 O Prohibit microwave plugged into surge protector, plug microwave directly into wall outlet
257288 02/15/2007 135859 5 206 O Remove and prohibit air fresheners
257164 02/15/2007 135606 6 102C O Prohibit coffee pot plugged into surge protector, plug coffee pot directly into wall outlet
257159 02/15/2007 135589 6 106B O Prohibit microwave plugged into surge protector, plug microwave directly into wall outlet
257302 02/15/2007 135889 6 204 O Remove and prohibit air freshener
246881 02/15/2007 113494 6 220 O Replace bulbs in emergency lights
257306 02/15/2007 135898 6 221 O Replace bulbs in emergency light fixture
246837 02/15/2007 113418 7 181 O Remove storage from in front of lower exhaust vent in flammable storage room
257339 02/15/2007 135973 8 181 O Keep door to flammable storage room closed and locked
246634 02/15/2007 112997 9 101F O Provide appropriate cover over electrical cord instead of taping cord
257357 02/15/2007 136010 9 190 O No access was available to this room. Please be prepared to access this room during the report review meeting.
246730 02/15/2007 113193 11 200 C Provide emergency lighting in each room of football field pressbox
246949 02/15/2007 113617 2 106C C Provide tempered glass, safety glass, or stainless steel for mirrors
246951 02/15/2007 113622 2 106E C Provide tempered glass, safety glass, or stainless steel for mirrors
246958 02/15/2007 113636 3 103A C Provide sign indicating maximum occupancy adjacent to main entrance (max. occupancy = 46)
246959 02/15/2007 113638 3 105G C Provide sign indicating maximum occupancy adjacent to main entrance (max. occupancy = 46)
246961 02/15/2007 113642 3 106 C Provide tempered glass, safety glass, or stainless steel for mirrors
246963 02/15/2007 113645 3 111 C Provide tempered glass, safety glass, or stainless steel for mirrors
257383 02/15/2007 136064 10 105 MS Provide current inspection tag for fire extinguisher
257378 02/15/2007 136054 10 180 MS Provide current inspection tag for fire extinguisher
257388 02/15/2007 136075 11 200 MS Provide current inspection tag for fire extinguisher
246579 02/15/2007 112880 2 290 MS Provide current inspection tag for fire extinguisher
246578 02/15/2007 112878 2 291 MS Provide current inspection tag for fire extinguisher
246576 02/15/2007 112874 2 292 MS Provide current inspection tag for fire extinguisher and recharge extinguisher
257282 02/15/2007 135845 3 103G MS Provide current inspection tag for fire extinguisher
257375 02/15/2007 136048 3 114 MS Provide current inspection tag for fire extinguisher
257377 02/15/2007 136052 3 193 MS Provide current inspection tag for fire extinguisher
257361 02/15/2007 136018 4 104 MS Provide current inspection tags for fire extinguishers (x2)
257170 02/15/2007 135622 4 221 MS Replace missing fire extinguisher
257161 02/15/2007 135595 6 106 MS Provide current inspection tag for fire extinguisher
257305 02/15/2007 135896 6 210 MS Provide current inspection tag for fire extinguisher
257296 02/15/2007 135876 6 219 MS Provide current inspection tag for fire extinguisher
257350 02/15/2007 135995 7 109 MS Provide current inspection tag for fire extinguisher
257341 02/15/2007 135977 8 101 MS Provide current inspection tag for fire suppression (hood) system
257331 02/15/2007 135951 8 101A MS Replace missing fire extinguisher adjacent to 8-109
246602 02/15/2007 112928 8 190 MS Provide current inspection tag for fire sprinkler riser
246618 02/15/2007 112965 8 193 MS Remove storage from mechanical room
257348 02/15/2007 135991 8 193 MS Provide current inspection tag for fire extinguisher
257338 02/15/2007 135971 8 195 MS Seal penetration in enclosure walls or ceilings to prevent spread of fire or smoke
257335 02/15/2007 135961 9 102 MS Provide current inspection tag for fire suppression (hood) system (3/2006)
257390 02/15/2007 136081 1 149 OS Prohibit storage of flammable materials (Tiki Torches filled with oil)
257380 02/15/2007 136058 10 101 OS Prohibit storage of flammable materials (propane)
257386 02/15/2007 136071 10 103 OS Prohibit storage of flammable materials (paint, bug spray, gas leaf blower)
257387 02/15/2007 136073 10 103 OS Prohibit charging batteries in room
257381 02/15/2007 136060 10 105 OS Prohibit storage of flammable materials (propane BBQ grill, field marker paint)
257382 02/15/2007 136062 10 105 OS Provide clear access to fire extinguisher
257308 02/15/2007 135902 12 104B OS Remove and prohibit storage of propane grill
257313 02/15/2007 135912 2 102B OS Prohibit storage of Raid Bug Spray
257324 02/15/2007 135937 2 106J OS Provide clear access to fire extinguisher
257322 02/15/2007 135933 2 106J OS Prohibit storage of flammable field marker paint
257277 02/15/2007 135833 3 101 OS Prohibit storage of flammable turpenoid
257280 02/15/2007 135841 3 102 OS Provide clear access to fire extinguisher
246776 02/15/2007 113287 3 214 OS Remove and prohibit toaster oven
257359 02/15/2007 136014 4 103B OS Provide clear access to fire extinguisher
257171 02/15/2007 135624 4 210 OS Keep area clear to emergency rescue window
257291 02/15/2007 135865 5 201 OS Remove and prohibit candles
257290 02/15/2007 135863 5 202 OS Remove and prohibit candle
257283 02/15/2007 135847 5 210 OS Prohibit storage of tiki torches filled with flammable oil
257284 02/15/2007 135849 5 210 OS Prohibit storage of sterno
257285 02/15/2007 135851 5 210 OS Remove and prohibit candles
257292 02/15/2007 135868 5 218 OS Remove and prohibit use of toaster oven
257157 02/15/2007 135585 6 107 OS Remove and prohibit use of toaster oven
257304 02/15/2007 135894 6 210 OS Remove and prohibit use of toaster oven
257356 02/15/2007 136008 7 101 OS Prohibit charging batteries in room
257351 02/15/2007 135998 7 108 OS Prohibit storage of flammable materials (aerosol cans and paint thinner)
257333 02/15/2007 135957 8 0000 OS Prohibit charging batteries in area in front of 8-108A
257340 02/15/2007 135975 8 180 OS Prohibit charging batteries in room
257342 02/15/2007 135979 8 101 CS Relocate pull station for kitchen hood suppression system to be along path of egress
246615 02/15/2007 112959 8 101 CS Modify gate for caged storage area to allow egress at all times and remove chain and padlock
257287 10/02/2006 135857 00 0000 M Modify all emergency access windows handles to open with a single action lever (Not required per Tom Hogarth and Victor Chodora)
246572 10/02/2006 112864 2 102 M Repair hole in wall outside corridor door
246953 10/02/2006 113624 2 107 M Change number on maximum occupancy sign in gym from 2400 to 1877 (per Angel Goitia, Bldg. Dept.)
246968 10/02/2006 113656 3 204 M Replace sign indicating Emergency Egress with sign indicating Emergency Access
246975 10/02/2006 113668 4 206 M Replace sign indicating Emergency Egress with sign indicating Emergency Access
246976 10/02/2006 113672 4 210 M Replace sign indicating Emergency Egress with sign indicating Emergency Access
246981 10/02/2006 113681 5 0000 M Adjust steps to make risers equal for bottom run of stairs into courtyard
246707 10/02/2006 113144 5 0000 M Label teacher's stations in all science labs to indicate Shut Off Valves inside in location that is visible from within classroom
246924 10/02/2006 113565 5 101 M Turn water on to emergency eye wash/shower
246925 10/02/2006 113568 5 116 M Turn water on to emergency eye wash/shower
246979 10/02/2006 113677 5 204 M Replace sign indicating Emergency Egress with sign indicating Emergency Access
246980 10/02/2006 113679 5 208 M Replace sign indicating Emergency Egress with sign indicating Emergency Access
246993 10/02/2006 113702 6 106 M Relocate drinking fountain that is too close to door leading from room 6-105 or remove adjacent cabinet to maintain minimum 3' wide clear path through doorway
246620 10/02/2006 112970 9 101 M Remove illuminated exit signs leading into kitchen at serving line
246945 10/02/2006 113608 2 106A O Remove metal roof decking that protrudes into opening for ladder to roof on upper catwalk
246564 10/02/2006 112845 2 106C O Replace missing bulbs in light fixtures above mirror
246764 10/02/2006 113262 3 211A O Remove and prohibit combustible (residential) sofa
246662 10/02/2006 113058 4 103A O Provide flame resistance label on curtain or remove curtain
246872 10/02/2006 113485 5 203 O Replace bulbs in emergency lights
246928 10/02/2006 113572 1 0000 C Provide illuminated exit signs at covered walkway between Bldgs. 1 & 9
246595 10/02/2006 112912 1 191 C Provide fire sprinkler coverage or label interior walls as 2 hour fire rated
247005 10/02/2006 113727 12 0000 C Adjust steps to make risers equal for bottom run of stairs into courtyard
246956 10/02/2006 113631 2 191 C Provide fire sprinkler coverage or label walls as 2 hour fire rated
246966 10/02/2006 113651 3 191 C Provide fire sprinkler coverage or label walls as 2 hour fire rated
246704 10/02/2006 113138 3 291 C Provide fire sprinkler coverage or label interior walls as 2 hour fire rated
246973 10/02/2006 113664 4 192 C Provide fire sprinkler coverage or label walls as 2 hour fire rated
246705 10/02/2006 113140 4 291 C Provide fire sprinkler coverage or label interior walls as 2 hour fire rated
246985 10/02/2006 113689 5 191 C Provide fire sprinkler coverage or label walls as 2 hour fire rated
246706 10/02/2006 113142 5 291 C Provide fire sprinkler coverage or label interior walls as 2 hour fire rated
246995 10/02/2006 113708 6 191 C Provide fire sprinkler coverage or label walls as 2 hour fire rated
246703 10/02/2006 113136 6 291 C Provide fire sprinkler coverage or label interior walls as 2 hour fire rated
246731 10/02/2006 113195 7 191 C Provide fire sprinkler coverage or label walls as 2 hour fire rated
246600 10/02/2006 112923 8 191 C Provide fire sprinkler coverage or label interior walls to indicate 2 hour fire rating
246727 10/02/2006 113186 10 101 MS Provide current inspection tag for fire extinguisher
246559 10/02/2006 112835 2 106A MS Provide current inspection tags for fire extinguishers on auditorium catwalks
246646 10/02/2006 113023 3 103B MS Provide current inspection tag for fire extinguisher
246648 10/02/2006 113027 3 105A MS Provide current inspection tag for fire extinguisher
246653 10/02/2006 113039 3 105B MS Recharge fire extinguisher
246647 10/02/2006 113025 3 105E MS Provide current inspection tag for fire extinguisher
246751 10/02/2006 113234 6 292 OS Remove storage from mechanical room
246737 10/02/2006 113205 10 180 FS Provide heat detector in custodial room
246609 10/02/2006 112947 8 195 FS Replace missing cover on heat detector
246842 04/20/2006 113429 00 0000 M Repair cracked concrete pavement in courtyard adjacent to 12-171
246843 04/20/2006 113431 00 0000 M Repair damaged chain link fencing at bike racks
246922 04/20/2006 113559 00 0000 M Secure loose bench seat at front entrance to campus
248320 04/20/2006 116458 00 9599 M Replace all damaged STOP signs throughout campus
248321 04/20/2006 116460 00 9599 M Remove all hurricane debris from SE parking lot
246599 04/20/2006 112921 1 192 M Rehang fire extinguisher
246847 04/20/2006 113439 10 102 M Replace broken ceramic floor tiles
246695 04/20/2006 113120 11 0000 M Exterminate ants
246744 04/20/2006 113220 11 200 M Provide signs indicating "Fire Alarm Pull Station Inside" and "Fire Extinguisher Inside" for center room of football field pressbox
246846 04/20/2006 113437 11 200 M Repair or replace all rusted steel doors at football field pressbox
246898 04/20/2006 113518 12 102 M Replace missing ceiling tiles
246912 04/20/2006 113539 12 104E M Replace missing lock on door
246899 04/20/2006 113519 12 201 M Replace missing ceiling tiles
246900 04/20/2006 113521 12 203 M Replace missing ceiling tiles
246901 04/20/2006 113522 12 204 M Replace missing ceiling tiles
246902 04/20/2006 113523 12 206B M Replace missing ceiling tiles
246692 04/20/2006 113115 12 213 M Determine cause of water damaged ceiling tiles and replace tiles
246693 04/20/2006 113116 12 218 M Determine cause of water damaged ceiling tiles and replace tiles
246573 04/20/2006 112866 2 101 M Adjust corridor door to latch properly
246557 04/20/2006 112831 2 101A M Determine cause of water damaged ceiling tiles and replace tiles
246561 04/20/2006 112839 2 105D M Replace missing ceiling tiles
246937 04/20/2006 113593 2 106A M Label smoke hatch releases
246944 04/20/2006 113605 2 106A M Install KO seal on top of box for fire alarm strobe at ladder to catwalk
246581 04/20/2006 112882 2 107B M Replace missing ceiling tiles
246571 04/20/2006 112862 2 180 M Replace missing ceiling tiles
246659 04/20/2006 113051 3 003 M Replace missing ceiling tiles
246643 04/20/2006 113017 3 102 M Repair exterior door to open,close and latch properly
246644 04/20/2006 113019 3 102C M Replace missing ceiling tiles
246649 04/20/2006 113029 3 103A M Relocate signage indicating room name and number to be outside room (sign is on inside face of door)
246960 04/20/2006 113640 3 105E M Determine cause of water damaged ceiling tiles and replace tiles
246650 04/20/2006 113031 3 105G M Relocate signage indicating room name and number to be outside room (sign is on inside face of door)
246656 04/20/2006 113046 3 106 M Adjust exterior door to latch properly
246655 04/20/2006 113044 3 114 M Replace missing ceiling tiles
246651 04/20/2006 113033 3 180 M Anchor shelving and relocate away from fire sprinkler head
246965 04/20/2006 113648 3 190 M Replace missing escutcheon on fire sprinkler head
246687 04/20/2006 113110 3 201B M Determine cause of water damaged ceiling tiles and replace tiles
246685 04/20/2006 113105 3 208 M Complete wall finish at corner
246666 04/20/2006 113065 4 101 M Repair SW exterior door to close and latch properly
246663 04/20/2006 113060 4 103A M Provide cover on exposed electrical junction box on wall above door into 4-104
248322 04/20/2006 116463 4 103A M Change number on maximum occupancy sign to 49
248323 04/20/2006 116465 4 103A M Remove illuminated exit sign leading into 4-103B
246672 04/20/2006 113078 4 171 M Mount fire extinguisher on bracket
246673 04/20/2006 113081 4 192 M Repair door to close and latch properly
246688 04/20/2006 113111 4 202 M Determine cause of water damaged ceiling tiles and replace tiles
246984 04/20/2006 113685 5 0000 M Remove locks from cabinet doors under teachers' stations to allow access to emergency shut off valves in all science labs
246677 04/20/2006 113088 5 102 M Adjust flow of emergency eye wash
246689 04/20/2006 113112 5 105 M Determine cause of water damaged ceiling tiles and replace tiles
246723 04/20/2006 113175 5 105 M Provide cover on exposed electrical junction box at ceiling
246841 04/20/2006 113426 5 115 M Repair corridor door to close and latch properly
246679 04/20/2006 113093 5 204 M Anchor shelving to wall
246897 04/20/2006 113517 5 218B M Replace missing ceiling tiles
246680 04/20/2006 113096 5 280 M Anchor shelving to wall
246845 04/20/2006 113435 6 102 M Repair hole in wall next to emergency eye wash
246690 04/20/2006 113113 6 103 M Determine cause of water damaged ceiling tiles and replace tiles
246691 04/20/2006 113114 6 108 M Determine cause of water damaged ceiling tiles and replace tiles
246905 04/20/2006 113526 6 110 M Replace missing cover on thermostat
246918 04/20/2006 113553 6 112 M Secure loose base along wall at corridor
246917 04/20/2006 113550 6 192 M Secure fire extinguisher bracket and keep extinguisher on bracket
246914 04/20/2006 113545 6 202 M Secure cover on junction box at ceiling
246907 04/20/2006 113531 6 203A M Replace missing escutcheon on fire sprinkler head
246908 04/20/2006 113534 6 216 M Replace missing escutcheon on fire sprinkler head
246915 04/20/2006 113548 6 218 M Secure cover on junction box at ceiling
246923 04/20/2006 113563 6 280 M Anchor shelving to wall
246844 04/20/2006 113433 7 101 M Repair damaged wall finish next to emergency eye wash
246696 04/20/2006 113122 7 109 M Fill hole in wall next to door
246709 04/20/2006 113149 7 112 M Modify lock on bathroom door to allow door to be unlocked from the outside without a special key
246710 04/20/2006 113151 7 113 M Modify lock on bathroom door to allow door to be unlocked from the outside without a special key
246635 04/20/2006 113001 8 004 M Repair inoperable water fountain
246614 04/20/2006 112956 8 101 M Adjust exterior doors adjacent to 8-180 to latch properly
246617 04/20/2006 112963 8 111 M Replace missing ceiling tiles
246612 04/20/2006 112953 8 180 M Determine cause of water damaged ceiling tiles and replace tiles
246619 04/20/2006 112967 8 192 M Adjust damaged ceiling at fire sprinkler head
246629 04/20/2006 112987 9 191 M Provide correct bracket for fire extinguisher and keep extinguisher on bracket
246630 04/20/2006 112989 9 191 M Provide current inspection tag for hot water heater
246584 04/20/2006 112889 1 103 O No access was available to this room. Please be prepared to access this room during the report review meeting.
246585 04/20/2006 112892 1 116 O Prohibit covering sign indicating room name and number with raised and Braille characters
246587 04/20/2006 112895 1 118 O Eliminate extension cord or replace with minimum 15A cord and prohibit use of multi-outlet adaptor
246588 04/20/2006 112898 1 120 O Prohibit covering sign indicating room name and number with raised and Braille characters
246591 04/20/2006 112905 1 124 O Replace bulbs in emergency lights
246592 04/20/2006 112907 1 125 O Replace bulbs in emergency lights
246589 04/20/2006 112900 1 127 O Remove and prohibit air freshener
246606 04/20/2006 112936 1 143 O Remove and prohibit air freshener
246605 04/20/2006 112934 1 146 O Replace bulbs in emergency lights
246604 04/20/2006 112932 1 155B O Remove and prohibit air freshener spray
246603 04/20/2006 112930 1 155C O Remove and prohibit air freshener spray
246742 04/20/2006 113216 12 101 O Post sign indicating evacuation routes
246757 04/20/2006 113248 12 213A O Remove and prohibit air freshener
246769 04/20/2006 113272 12 217 O Remove and prohibit halogen lamp
246558 04/20/2006 112833 2 101C O Remove and prohibit toaster oven
246575 04/20/2006 112870 2 102 O No access was available to this room (waxing floor). Please be prepared to access this room during the report review meeting.
246574 04/20/2006 112868 2 104 O No access was available to this room (waxing floor). Please be prepared to access this room during the report review meeting.
246939 04/20/2006 113596 2 106 O Post signs indicating evacuation routes
246947 04/20/2006 113613 2 106C O Post sign indicating evacuation routes
246950 04/20/2006 113619 2 106E O Post sign indicating evacuation routes
246568 04/20/2006 112856 2 106J O Remove storage closet built from plywood
246569 04/20/2006 112858 2 106J O Maintain storage room in an orderly manner and remove excessive storage
246570 04/20/2006 112860 2 106J O Remove plywood attached to metal storage shelves
246642 04/20/2006 113015 3 101 O Replace bulbs in emergency lights
246645 04/20/2006 113021 3 102C O Eliminate extension cord or replace with minimum 15A cord
246756 04/20/2006 113246 3 201 O Remove and prohibit air freshener
246865 04/20/2006 113478 3 203 O Replace bulbs in emergency lights
246866 04/20/2006 113479 3 207 O Replace bulbs in emergency lights
246719 04/20/2006 113169 3 208 O Eliminate extension cord or replace with minimum 15A cord
246781 04/20/2006 113296 3 211 O Remove and prohibit use of multi-outlet electrical adaptor adjacent to sink
246668 04/20/2006 113068 4 101 O Prohibit powering copy machine with surge protector - plug directly into electrical outlet
246664 04/20/2006 113063 4 103 O Remove and prohibit toaster oven
246758 04/20/2006 113251 4 201 O Remove and prohibit air freshener spray
246867 04/20/2006 113480 4 203 O Replace bulbs in emergency lights
246759 04/20/2006 113253 4 210 O Remove and prohibit air freshener spray
246868 04/20/2006 113481 4 214 O Replace bulbs in emergency lights
246869 04/20/2006 113482 4 216 O Replace bulbs in emergency lights
246774 04/20/2006 113282 4 220 O Remove and prohibit toaster oven
246870 04/20/2006 113483 4 221 O Replace bulbs in emergency lights
246779 04/20/2006 113291 5 108 O Eliminate extension cord or replace with minimum 15A cord
246780 04/20/2006 113294 5 108A O Eliminate extension cord or replace with minimum 15A cord
246754 04/20/2006 113240 5 115A O Remove storage within 18" of fire sprinkler heads
246871 04/20/2006 113484 5 202 O Replace bulbs in emergency lights
246873 04/20/2006 113486 5 205 O Replace bulbs in emergency lights
246761 04/20/2006 113257 5 205 O Remove and prohibit air fresheners
246874 04/20/2006 113487 5 208 O Replace bulbs in emergency lights
246875 04/20/2006 113488 5 211 O Replace bulbs in emergency lights
246876 04/20/2006 113489 5 214 O Replace bulbs in emergency lights
246762 04/20/2006 113259 5 215B O Remove and prohibit air fresheners
246716 04/20/2006 113162 6 102 O Prohibit plugging surge protector to surge protector
246717 04/20/2006 113165 6 102 O Prohibit plugging surge protectors into extension cords and extension cords into surge protectors - each cord must be plugged directly into an outlet
246913 04/20/2006 113543 6 102B O Replace missing sign indicating evacuation routes
246755 04/20/2006 113244 6 104 O Remove and prohibit air freshener
246714