Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
407605 02/14/2018 459554 00 0000 M Repair damaged top rail on chain link perimeter fencing on the west side of Building 2
393661 02/14/2018 429447 00 9599 M Trim overgrown trees along west side of Bldg. 2
407600 02/14/2018 459543 1 190 M Determine cause of water damaged ceiling tiles and replace tiles
407607 02/14/2018 459558 2 118 M Determine cause of water damaged ceiling tile above sink and replace tiles
407620 02/14/2018 459586 2 124 M Replace missing escutcheon on fire sprinkler head
407608 02/14/2018 459561 2 130B M Eliminate plug in deodorizer to prevent health hazard
407611 02/14/2018 459567 2 140B M Replace missing ceiling tiles in storage closet
407603 02/14/2018 459550 2 193 M Repair leaky air handler unit to prevent water from running onto floor (water standing on floor)
407604 02/14/2018 459552 2 193 M Eliminate termite infestation
407609 02/14/2018 459563 2 197 M Secure bent door on electric panel in mechanical room (panel is labeled Video Equipment)
407619 02/14/2018 459583 4 101B M Repair emergency lighting
407617 02/14/2018 459579 4 107E M Determine cause of water damaged ceiling tiles in storage room and replace tiles
407618 02/14/2018 459581 4 107L M Repair door to close properly
407615 02/14/2018 459575 4 193 M Repair or replace rusted steel doors on golf cart storage room
407616 02/14/2018 459577 4 195 M Repair emergency lighting in generator room
407613 02/14/2018 459571 5 101 M Remove rust and repaint steel roof support beams on roof of P.E. Pavilion
393618 02/14/2018 429357 6 191 M Repair exhaust fan in flammable storage room
407597 02/14/2018 459534 1 114 O Prohibit plugging surge protector into extension cord in police office
407598 02/14/2018 459541 1 115 O Replace burned out bulbs in light fixture
407601 02/14/2018 459546 1 120 O Keep area within 18 inches of fire sprinkler head clear and unobstructed
407606 02/14/2018 459556 2 117 O Remove and prohibit flammable curtains or spray with a flame retardant
407612 02/14/2018 459569 2 144 O Remove and prohibit hanging flammable decorations (plastic flags) from ceiling
407614 02/14/2018 459573 3 108 O Remove and prohibit combustible (residential) furniture (cane chair and cushions)
407602 02/14/2018 459548 1 122 MS Provide current inspection tag for fire extinguisher
407610 02/14/2018 459565 2 147B MS Provide current inspection tag for fire extinguisher or remove from storage closet (another extinguisher is located within 75')
260294 08/29/2017 142191 1 0000 N/A No violations observed
260295 08/29/2017 142193 2 0000 N/A No violations observed
260296 08/29/2017 142195 3 0000 N/A No violations observed
260297 08/29/2017 142197 4 0000 N/A No violations observed
260298 08/29/2017 142199 5 0000 N/A No violations observed
260299 08/29/2017 142201 6 0000 N/A No violations observed
393620 12/09/2016 429361 1 102 M Repair emergency eye wash to work properly at nurse station
378276 12/09/2016 396197 2 101 M Provide emergency lighting in student occupied space
378277 12/09/2016 396199 2 102 M Provide emergency lighting in student occupied space
393867 12/09/2016 429890 2 108A M Replace rusted toilet paper dispenser in bathroom
393624 12/09/2016 429370 2 138 M Secure loose faucet to sink
393625 12/09/2016 429372 2 144B M Remove old fire extinguisher from closet - not required
393633 12/09/2016 429387 2 183 M Provide current inspection log for hot water heater
393634 12/09/2016 429393 2 193 M Provide current inspection log for hot water heater
393621 12/09/2016 429364 3 104A M Secure loose lens cover to light fixture
393619 12/09/2016 429359 5 103 M Adjust boys bathroom door to latch properly
393866 12/09/2016 429888 2 104 O Remove and prohibit paper on window blinds
393865 12/09/2016 429886 2 106 O Remove and prohibit paper on window blinds
393657 12/09/2016 429439 2 114A O Remove paper covering signage indicating bathroom name and number with raised and Braille characters
393653 12/09/2016 429429 2 114C O Remove paper covering signage indicating closet room name and number with raised and Braille characters
393655 12/09/2016 429436 2 114C O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
393642 12/09/2016 429408 2 117 O Remove and prohibit excessive flammable netting hanging from ceiling
393640 12/09/2016 429402 2 118 O Remove and prohibit excessive flammable netting hanging from ceiling
393650 12/09/2016 429421 2 119 O Prohibit plugging surge protector into extension cord at computer stations - use surge protectors with long enough cord to reach wall outlets and eliminate all extension cords
393643 12/09/2016 429410 2 121 O Remove and prohibit use of combustible curtains as a room divider
393645 12/09/2016 429414 2 121 O Eliminate (3) plug electrical outlet adaptor behind desk adjacent to bathroom or replace with a surge protector
393637 12/09/2016 429395 2 143 O Eliminate white extension cord with multiple outlet end behind desk or replace with a surge protector
393868 12/09/2016 429893 2 149 O Provide verification that small residential chair is flame retardant
393869 12/09/2016 429895 3 103 O Provide verification that blue fabric under ceiling light is flame retardant
393623 12/09/2016 429368 3 110 O Remove or replace area rugs with rolled up edges to eliminate trip hazard
393862 12/09/2016 429880 4 105 O Prohibit plugging surge protector into extension cord at keyboards - plug surge protector directly into wall outlet and eliminate extension cords with multiple outlet end
393863 12/09/2016 429882 4 105 O Provide cover strip for electrical cords running across floor and secure cover strip to flooring to eliminate trip hazard adjacent to keyboards
393861 12/09/2016 429878 4 107A O Remove and prohibit excessive flammable blue vinyl sheathing on table at serving area
393630 12/09/2016 429385 2 197 MS Provide current inspection tag for fire extinguisher
393659 12/09/2016 429443 2 104A OS Remove easel stored in bathroom
393629 12/09/2016 429380 2 144A OS Remove storage from bathroom
393864 12/09/2016 429884 4 002 OS Remove two carts along stage ramp to maintain safe egress
378326 09/09/2016 396309 1 102 M Repair split, damaged flooring
378282 09/09/2016 396210 2 128A M Repair exhaust fan in bathroom
378228 09/09/2016 396095 4 105B M Repair exhaust fan bathroom
378229 09/09/2016 396097 4 108A M Repair exhaust fan in bathroom
378230 09/09/2016 396099 4 108B M Repair exhaust fan in bathroom
378250 03/07/2016 396141 00 0000 M Remove unnecessary fire extinguishers and brackets from storage closets in classrooms. Fire extinguishers in corridors are sufficient. 2-149B, 2-142B, 2-140B, 2-138C,
378324 03/07/2016 396304 1 101 M Provide current inspection tag for fire alarm system
378325 03/07/2016 396306 1 102 M Repair door to close and latch properly
378285 03/07/2016 396216 2 006 M Adjust door closer on exterior door adjacent to 2-137 to control speed of closing door
378241 03/07/2016 396122 2 147 M Determine cause of water damaged ceiling tiles and replace tiles
378278 03/07/2016 396201 2 149A M Repair door to close and latch properly, rubs on frame
378263 03/07/2016 396171 3 103A M Replace missing cover for light switch
378243 03/07/2016 396128 3 190 M Provide correct bracket for fire extinguisher, current bracket does not properly hold fire extinguisher
378252 03/07/2016 396147 3 191 M Repair door lock, key does not fit into lock properly
378287 03/07/2016 396220 4 106 M Repair deteriorated wall finish at entrance door to 4-103
378288 03/07/2016 396222 4 106 M Provide additional security panel and or different style door handle at caged area to keep items secure, gap in gate at cage allows door handle to be reached from the outside
378299 03/07/2016 396243 4 107F M Repair door to close and latch properly, door rubs on frame
378322 03/07/2016 396299 4 107G M Repair door to close and latch properly, door rubs on frame
378231 03/07/2016 396102 4 195 M Provide current emergency lighting certificate
378227 03/07/2016 396093 4 196 M Repair door to close properly, door rubs on frame
378257 03/07/2016 396156 5 105 M Adjust door closer to control speed of closing door
378235 03/07/2016 396111 2 117 O Remove or relocate string line to hang no more than 2 inches from wall surface
378284 03/07/2016 396214 2 130 O Remove and prohibit air freshener
378236 03/07/2016 396113 3 107 O Remove or relocate string line to hang no more than 2 inches from wall surface
378232 03/07/2016 396104 3 110 O Remove and prohibit blue cloth light covers hanging from ceiling lights
378234 03/07/2016 396108 3 116 O Remove or relocate string line to hang no more than 2 inches from wall surface
378323 03/07/2016 396301 1 122 MS Provide current inspection tag for fire extinguisher
378274 03/07/2016 396193 1 128E MS Repair thumb latch for door lock
378280 03/07/2016 396204 2 124A MS Repair door lock, handle is missing thumb latch for door lock
378255 03/07/2016 396149 5 104 MS Repair thumb latch for door lock
378281 03/07/2016 396207 2 124 OS Remove and prohibit blue cloth light covers hanging from ceiling lights
378283 03/07/2016 396212 2 130C OS Remove and prohibit use of toaster oven
378273 03/07/2016 396191 3 103 OS Remove and prohibit blue cloth light covers hanging from ceiling lights
378259 03/07/2016 396160 3 105B OS Remove and prohibit storage in bathroom vestibule to maintain clear aisle to exit
378286 03/07/2016 396218 2 137 CS Provide Co2 fire extinguisher for computer lab
369706 02/24/2016 377567 00 0000 M Clean mold from play courts. Very slick when wet
378275 02/24/2016 396195 1 129C M Determine cause of water damaged ceiling and make necessary repairs
378289 02/24/2016 396224 4 106 M Provide current inspection tag for fire sprinkler system, make repairs as indicated on report dated March 2015
369733 09/02/2015 377622 2 111 M Secure loose faucet to sink
369721 09/02/2015 377597 3 110D M Repair exhaust fan in bathroom
369726 09/02/2015 377607 4 106C M Repair exhaust fan in bathroom
369727 09/02/2015 377609 4 106D M Repair exhaust fan in bathroom
378233 09/02/2015 396106 2 111 O Dark blue Cozy Shade light covers have been approved by P. Joyce and district purchasing department for use in areas with autistic students, the blue room 1-101B and 2-111. Product has been researched and meets NFPA standards
369712 03/10/2015 377579 00 0000 M Remove open 2 inch PVC pipe from ground at west boundary fence across from 2-194
369704 03/10/2015 377563 00 0000 M Repair leaking downspouts through out campus. Clean out all gutters and downspouts
369705 03/10/2015 377565 00 0000 M Eliminate ants in playfilds
369713 03/10/2015 377581 1 128J M Repair leaking toilet supply line
369714 03/10/2015 377583 2 111 M Repair leaking drinking fountain
369732 03/10/2015 377620 2 125A M Repair leaking toilet supply line
369734 03/10/2015 377624 2 137A M Adjust toilet flush length, too long
369708 03/10/2015 377571 2 180 M Repair exhaust fan in janitors closet
369707 03/10/2015 377569 2 194 M Repair leaking air handler
356283 03/10/2015 348351 2 194 M Repair leaks on fire sprinkler line at tee at NE corner of air handler and at elbow SE of air handler
369731 03/10/2015 377618 2 199 M Surge protector for panel 2HC1 in fault, repair or replace
369720 03/10/2015 377595 3 106D M Adjust toilet flush length, too long
369722 03/10/2015 377599 3 110C M Repair leaking supply line for toilet
369715 03/10/2015 377585 4 008 M Determine cause of water damaged ceiling tiles and replace tiles in vestibule to bathrooms for teachers dining room
369729 03/10/2015 377613 4 103A M Adjust handicapped toilet flush length, too long
369730 03/10/2015 377615 4 103A M Replace missing grout around bathroom door frame inside of room
369728 03/10/2015 377611 4 103B M Caulk handicapped sink to wall
369725 03/10/2015 377605 4 106B M Determine cause of water damaged ceiling tiles and replace tiles
369711 03/10/2015 377577 4 107 M Clean kitchen hood and provide tag indicating date cleaned
369710 03/10/2015 377575 4 107E M Replace missing escutcheon on fire sprinkler head
369718 03/10/2015 377591 6 191 M Repair exhaust fan for flammable storage room
369717 03/10/2015 377589 1 122 MS Provide current inspection tag for fire extinguisher
369716 03/10/2015 377587 2 190 MS Provide current inspection tag for fire extinguisher
369709 03/10/2015 377573 4 105A MS Provide current inspection tag for fire extinguisher
369719 03/10/2015 377593 4 194 MS Adjust fire door to 4-195 to latch properly. Someone turned latch around
327484 12/18/2014 285640 00 0000 C Turn barbs down on all fencing, NE campus at Gopher Tortoise preserve. Not our fence or property
356274 10/24/2014 348333 3 0000 M Repair leak in irrigation system SE of 3-191. Look for hole in ground at leaning tree
369723 10/24/2014 377601 3 108A M Repair exhaust fan in bathroom. Wrong room number
369724 10/24/2014 377603 3 108B M Repair exhaust fan in bathroom. Wrong room number
310439 10/24/2014 247727 2 0000 CS Provide panic hardware on gate at SW corner of campus to allow safe egress
356259 03/18/2014 348299 00 0000 M Cut down and cap 3 or 4 inch grey PVC pipe sticking out of ground west of gate to preserve area in front of school
327483 03/18/2014 285638 00 0000 M Attach loose grounds for covered walkway north of building 2 at west end of walkway
356278 03/18/2014 348341 1 101 M Remote generator panel has been removed and wires are left exposed. Cover exposed wires and replace generator panel
356269 03/18/2014 348323 2 0000 M Repair leak in irrigation system at SE corner of playground outside of 2-126 and 2-128
356275 03/18/2014 348335 2 127A M Repair toilet with excessive flush length
356276 03/18/2014 348337 2 128B M Anchor single shelving unit to wall
356285 03/18/2014 348355 2 129 M Replace GFCI outlet at NE corner of room that will not reset
356270 03/18/2014 348325 2 134A M Repair leaking supply line for toilet
356265 03/18/2014 348314 2 140A M Seal opening in ceiling adjacent to fire sprinkler head
356277 03/18/2014 348339 2 190 M Replace leaking elbow on fire sprinkler line adjacent to door
356263 03/18/2014 348310 2 190 M Anchor air handlers at 4 corners. Legs are bending
356264 03/18/2014 348312 2 190 M Close and lock or latch open cabinets
356281 03/18/2014 348347 2 193 M Anchor air handlers at 4 corners
356282 03/18/2014 348349 2 193 M Repair leaking tee on fire sprinkler line adjacent to RF 2-1
356284 03/18/2014 348353 2 194 M Anchor 4 corners of air handlers. Legs are bending
356271 03/18/2014 348327 2 197 M Anchor air handlers at 4 corners. Legs are bending
356273 03/18/2014 348331 3 0000 M Seal open joint on exterior wall between 3-190 and 3-116
356268 03/18/2014 348321 3 102A M Repair door to open and close properly. Drags on frame
356272 03/18/2014 348329 3 110D M Repair leaking supply line for toilet
356266 03/18/2014 348317 3 190 M Replace rusted and leaking elbow on fire sprinkler line behind air handler
356267 03/18/2014 348319 3 190 M Anchor air handlers at 4 corners. Legs are bending
356287 03/18/2014 348359 4 107D M Adjust door to walk-in cooler in Kitchen to latch properly
356279 03/18/2014 348343 4 190 M Anchor air handlers at 4 corners. Legs are bending
356280 03/18/2014 348345 4 190 M Close and lock or latch all open cabinets
356262 03/18/2014 348308 4 193 M Provide cover on exposed electrical junction box adjacent to door
356260 03/18/2014 348301 6 190 M Repair leaking valve on small grey tank in chiller compound
356286 03/18/2014 348357 4 107A MS Provide current inspection tag for fire extinguisher
356261 03/18/2014 348306 4 192 MS Provide current inspection tag for fire extinguisher
356288 03/18/2014 348361 4 002 OS Remove and prohibit storing carts on stage exit ramp
327486 07/31/2013 285644 2 190 M Bottom chord brace for bar joist has been cut and removed to facilitate installation of roof access ladder. Replace missing brace. See Building Department for repair
327487 07/31/2013 285646 2 193 M Bottom chord brace for bar joist has been cut and removed to facilitate installation of outside air intake. Replace brace. See Building Department for repair
327488 07/31/2013 285648 2 197 M Bottom chord brace for bar joist has been cut and removed to facilitate installation of outside air intake. Replace brace. See Building Department for repair
345675 03/19/2013 324937 00 0000 M Remove unnecessary fire extinguishers located in classroom closets in buildings 2 and 3. Placement of fire extinguishers in corridors meet code requirements
345681 03/19/2013 324949 1 008 M Adjust door closer on exterior corridor door adjacent to 2-101 to control speed of closing door
345682 03/19/2013 324951 1 129 M Provide protective cover for fire alarm pull station to prevent student tampering
345680 03/19/2013 324947 2 004 M Adjust door closers on doors to 2-001 corridor to control speed of closing doors
345679 03/19/2013 324945 2 106A M Repair damaged light switch
345677 03/19/2013 324941 2 110A M Repair damaged light switch
345676 03/19/2013 324939 2 110B M Repair damaged door lock
345678 03/19/2013 324943 2 111C M Repair damaged light switch
345674 03/19/2013 324935 2 119A M Repair damaged light switch
345660 03/19/2013 324907 2 120A M Repair damaged light switch
345659 03/19/2013 324905 2 134A M Repair damaged light switch
345670 03/19/2013 324927 2 137 M Determine cause of water damaged ceiling tiles and replace tiles
345669 03/19/2013 324925 2 139B M Determine cause of water damaged ceiling tiles and replace tiles
345665 03/19/2013 324917 2 144A M Repair damaged light switch
345666 03/19/2013 324919 2 151A M Repair damaged light switch
345668 03/19/2013 324923 2 192 M Fill void in electrical panel 2LA
345661 03/19/2013 324909 2 197 M Adjust door closer to control speed of closing door
345690 03/19/2013 324967 2 199 M Adjust door closer to control speed of closing door
345689 03/19/2013 324965 4 005 M Adjust door closer on exterior door adjacent to 4-108 to control speed of closing door
345691 03/19/2013 324969 4 105B M Repair damaged light switch
345686 03/19/2013 324959 4 106 M Adjust door closer on exterior door to control speed of closing door
345688 03/19/2013 324963 4 108 M Determine cause of water damaged ceiling tiles and replace tiles
345687 03/19/2013 324961 4 108B M Repair broken door lock
327458 03/19/2013 285581 5 0000 M Bar joist closest to building appears corroded. Clean off corrosion and refinish bar joist
345673 03/19/2013 324933 2 123 O Remove and prohibit air freshener
345672 03/19/2013 324931 2 130 O Remove and prohibit air freshener
345667 03/19/2013 324921 2 142 O Prohibit use of flammable black plastic sheet on table
345663 03/19/2013 324913 2 144 O Prohibit use of damaged blue bean bag chair (hole in bean bag)
345664 03/19/2013 324915 2 144 O Provide tag from red bean bag chair manufacturer certifying that bean bag meets California TB 117 standards or prohibit use of bean bag
345662 03/19/2013 324911 3 116 O Provide minimum one foot blank wall space on lock side of corridor door
345685 03/19/2013 324957 4 101A O Prohibit plugging surge protector into surge protector in cardboard box at walkie talkies
345684 03/19/2013 324955 4 101B O Post sign indicating primary and secondary evacuation routes
345683 03/19/2013 324953 4 101B C Provide emergency lighting in student occupied area
345692 03/19/2013 324971 1 104 MS Recharge fire extinguisher
345671 03/19/2013 324929 2 130 OS Remove and prohibit use of candle
327460 11/29/2012 285585 2 196 M Repair surge suppressors. The indicator lights on 2 surge suppressors are off and another is in fault
327476 11/29/2012 285622 4 107 MS Provide current inspection tag for kitchen hood fire suppression system
327475 11/29/2012 285620 4 106 OS Prohibit charging batteries in room
327473 03/26/2012 285615 00 0000 M Unband trees north of building 1 and 2
327459 03/26/2012 285583 00 0000 M Remove 1" PVC pipe in ground at north end of west fence line adjacent to bike rack
327485 03/26/2012 285642 00 0000 M Provide bollards around electrical outlet in field north of basketball court. Outlet approx. 8 inches high
327461 03/26/2012 285587 1 111 M Replace GFI outlet to right of sink that won't trip
327462 03/26/2012 285589 2 002 M Adjust auto closer on smoke doors in corridor adjacent to 2-114 so that doors close completely
327482 03/26/2012 285636 2 108A M Patch hole in ceiling adjacent to fire sprinkler head and verify sprinkler leak has been repaired
327481 03/26/2012 285634 2 125A M Patch hole in ceiling adjacent to fire sprinkler head and verify sprinkler leak has been repaired
327478 03/26/2012 285627 2 132A M Repair light switch. Lights will not come on
327480 03/26/2012 285631 2 137 M Secure liquid tight conduit to wall close to box to prevent conduit being pulled out of box
327468 03/26/2012 285603 2 139B M Repair hole cut in ceiling adjacent to fire sprinkler head and verify sprinkler leak repaired
327489 03/26/2012 285650 2 183 M Provide current inspection log for hot water heater
327464 03/26/2012 285594 2 193 M Provide current inspection log for hot water heater
327467 03/26/2012 285601 3 109B M Adjust door to 3-109 to latch properly
327469 03/26/2012 285605 4 107M M Adjust door to latch properly
327466 03/26/2012 285599 4 191 M Repair surge suppressor. No indicator light lit
327477 03/26/2012 285624 4 195 M Provide certification that all student occupied spaces have emergency lights and all are operable. Last certification dated 7/2010
327463 03/26/2012 285592 6 190 M Repair surge suppressor. No indicator light is lit
327479 03/26/2012 285629 00 0000 O Keep shower drains filled with water. Every 2 months pour 1 quart of water down drains
327470 03/26/2012 285609 3 110 O Remove and prohibit hanging papers from string line
327471 03/26/2012 285611 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus
327474 03/26/2012 285617 4 106 MS Provide current inspection tag for fire sprinkler system. Tags marked as quarterly and dated 5/2011
327465 03/26/2012 285597 4 190 MS Verify automatic fire sprinkler coverage for all of room. No sprinklers visible in east side of room
327472 03/26/2012 285613 3 115A OS Keep area within 18" of fire sprinkler head clear and unobstructed
310602 11/10/2011 248088 2 193 C Provide handrail along steps outside of mechanical room at 30-38" high (Requirement waived by Tom Hogarth)
310604 11/10/2011 248095 2 194 C Provide handrail along steps outside of mechanical room at 30-38" high (Requirement waived by Tom Hogarth)
310605 11/10/2011 248098 2 197 C Provide handrail along steps outside of mechanical room at 30-38" high (Requirement waived by Tom Hogarth)
319078 03/31/2011 266712 00 0000 M Adjust all smoke doors in corridors to close properly
319067 03/31/2011 266689 1 102 M Determine cause of water damaged ceiling tiles and replace tiles
319077 03/31/2011 266710 1 129 M Determine cause of water damaged ceiling tiles and replace tiles
310600 03/31/2011 248084 2 190 M Replace missing bottom chord bracing on bar joists. Contact Building Department for necessary repairs. (Approved by Building Department Inspectors, and CO was issued)
310603 03/31/2011 248092 2 194 M Relocate bottom chord brace for bar joists that interferes with roof access ladder. Replace missing bottom chord bracing. Contact Building Department for necessary repairs.(Approved by Building Department inspector and CO was issued)
319081 03/31/2011 266718 2 196 M Provide cover on blank circuit inside electrical panel 216 Sec.2
319079 03/31/2011 266714 2 102 O Eliminate multiple outlet extension cords
319080 03/31/2011 266716 2 107 O Remove and prohibit flammable decorations hanging from ceiling
319084 03/31/2011 266724 2 129 O Remove and prohibit paper covering windows
319086 03/31/2011 266728 2 147 O Remove and prohibit flammable decorations hanging from ceiling
319082 03/31/2011 266720 2 221 O Remove and prohibit paper covering windows
319072 03/31/2011 266700 4 106 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
319075 03/31/2011 266706 5 105 O Prohibit plugging microwave oven and refrigerator into surge protector - plug directly into permanent electrical outlet
310649 03/31/2011 248196 00 0000 C Repair/fill low areas of play courts to eliminate standing water
319073 03/31/2011 266702 4 103 F Secure hanging fire alarm strobe/horn on cafeteria wall next to stage
319068 03/31/2011 266691 3 105A MS Provide current inspection tag for fire extinguisher
319070 03/31/2011 266696 4 106 MS Seal around sprinkler riser piping penetrating ceiling to prevent spread of fire or smoke
319071 03/31/2011 266698 4 106 MS Provide current inspection tag for fire extinguisher
319069 03/31/2011 266693 6 191 MS Provide current inspection tag for fire extinguisher
319076 03/31/2011 266708 1 128 OS Provide clear access to fire extinguisher at south exit doors
319085 03/31/2011 266726 2 182 OS Relocate buckets of floor stripper to flammable storage room (by order of Palm Beach Gardens Fire Inspector)
319083 03/31/2011 266722 2 119 CS Provide ABC type fire extinguisher to replace type BC extinguisher
319074 03/31/2011 266704 5 105 CS Provide ABC type fire extinguisher to replace a BC type
310450 12/14/2010 247751 00 0000 M Install chain and lock on valve handles of 8" fire main at east exit from parking lot
310589 12/14/2010 248061 2 141 M Provide verification that space has emergency lights and lights are operable (all areas have emergency lighting according to generator report)
310617 12/14/2010 248123 00 0000 C Verify with Palm Beach Gardens Fire Rescue that the fire department access road is acceptable.(verified o.k. by inspector Andrea Santa)
310471 12/14/2010 247797 1 128 C Provide additional fire sprinkler heads along raised ceiling or along dropped soffit at west wall of Media Center to provide adequate coverage under dropped soffit (adequate coverage is provided by what is currently in place as per Mark Lodge)
310618 12/14/2010 248125 3 190 C Provide automatic fire sprinkler coverage under duct if duct is greater than 4' in width
310438 12/14/2010 247725 00 0000 MS Verify wall openings along exterior courtyard area between Bldgs. 1 & 3 meet protection requirements of FBC, table 600 (not applicable as per Architect Angel Goitia)
310446 04/23/2010 247743 00 0000 M Unband palms in preserve
310490 04/23/2010 247842 2 108C M Repair door lock to lock
310506 04/23/2010 247879 2 109 M Relocate cabinet blocking room name and number sign for room 2-109B
310525 04/23/2010 247922 2 110 M Determine cause of water damaged ceiling tiles and replace tiles
310601 04/23/2010 248086 2 192 M Repair sticky door latch
310607 04/23/2010 248102 3 001 M Adjust smoke doors in corridor adjacent to 4-103 to close properly
310612 04/23/2010 248112 3 101 M Repair/replace electrical outlet adjacent to 3-101C. See teacher
310634 04/23/2010 248164 3 109C M Repair/replace damaged light switch
310635 04/23/2010 248166 3 109D M Repair/replace damaged light switch
310633 04/23/2010 248161 3 110C M Repair/replace damaged light switch
310631 04/23/2010 248157 3 110D M Repair/replace damaged light switch
310623 04/23/2010 248139 4 106 M Attach dryer vent to dryer
310648 04/23/2010 248193 5 101 M Provide cover on exposed electrical junction box and cover exposed wires to NW at ceiling
310527 04/23/2010 247926 00 0000 O Keep all shower drains throughout campus filled with water
310444 04/23/2010 247739 1 112 O Lower storage to keep area within 18" of fire sprinkler heads clear
310448 04/23/2010 247747 1 127 O Remove and prohibit plug in air freshener
310595 04/23/2010 248073 1 127B O Lower storage to keep area within 18" of fire sprinkler heads clear
310447 04/23/2010 247745 1 128C O Lower storage to keep area within 18" of fire sprinkler head clear
310451 04/23/2010 247754 1 129D O Keep storage away from motorized damper to allow damper to operate
310473 04/23/2010 247808 2 102 O Remove mirror or provide mirror made of tempered glass, safety glass, or stainless steel
310486 04/23/2010 247834 2 106 O Remove and prohibit combustible beanbag chairs
310488 04/23/2010 247837 2 106B O Lower storage to keep area within 18" of fire sprinkler heads clear
310485 04/23/2010 247830 2 107C O Lower storage to keep area within 18" of fire sprinkler heads clear
310475 04/23/2010 247812 2 109 O Remove and prohibit combustible beanbag chairs
310507 04/23/2010 247881 2 111 O Remove and prohibit combustible beanbag chairs
310520 04/23/2010 247911 2 112B O Lower storage to keep area within 18" of fire sprinkler heads clear
310516 04/23/2010 247903 2 112C O Lower storage to keep area within 18" of fire sprinkler heads clear
310518 04/23/2010 247907 2 114C O Lower storage to keep area within 18" of fire sprinkler heads clear
310517 04/23/2010 247905 2 116 O Lower storage to keep area within 18" of fire sprinkler heads clear
310522 04/23/2010 247916 2 116B O Remove and prohibit use of deep fryer (in box on shelf)
310519 04/23/2010 247909 2 118B O Lower storage ot keep area within 18" of fire sprinkler heads clear
310596 04/23/2010 248075 2 125B O Lower storage to keep area within 18" of fire sprinkler heads clear
310592 04/23/2010 248067 2 128 O Remove and prohibit combustible beanbag chairs
310585 04/23/2010 248052 2 130 O Remove and prohibit combustible beanbag chairs
310586 04/23/2010 248054 2 131 O Remove and prohibit combustible beanbag chairs
310587 04/23/2010 248057 2 138 O Remove and prohibit combustible beanbag chairs
310593 04/23/2010 248069 2 138C O Lower storage to keep area within 18" of fire sprinkler heads clear
310588 04/23/2010 248059 2 140B O Lower storage to keep area within 18" of fire sprinkler heads clear
310594 04/23/2010 248071 2 142 O Lower storage to keep area within 18" of fire sprinkler heads clear
310613 04/23/2010 248114 2 151B O Lower storage to keep area within 18" of fire sprinkler heads clear
310608 04/23/2010 248104 3 102 O Remove and prohibit combustible beanbag chairs
310610 04/23/2010 248108 3 102C O Lower storage to keep area within 18" of fire sprinkler heads clear
310616 04/23/2010 248120 3 104A O Lower storage to keep area within 18" of fire sprinkler heads clear
310609 04/23/2010 248106 3 106 O Remove and prohibit combustible beanbag chairs
310615 04/23/2010 248118 3 106A O Lower storage to keep area within 18" of fire sprinkler heads clear
310614 04/23/2010 248116 3 108A O Lower storage ot keep area within 18" of fire sprinkler heads clear
310626 04/23/2010 248149 3 109A O Lower storage ot keep area within 18" of fire sprinkler heads clear
310628 04/23/2010 248151 3 111A O Lower storage to keep area within 18" of fire sprinkler heads clear
310629 04/23/2010 248154 3 116A O Lower storage to keep area within 18" of fire sprinkler heads clear
310624 04/23/2010 248141 4 102 O Lower storage to keep area within 18" of fire sprinkler heads clear
310625 04/23/2010 248146 4 105A O Lower storage to keep area within 18" of fire sprinkler heads clear
310620 04/23/2010 248132 4 106 O Remove chain and padlock from gate for caged storage area
310638 04/23/2010 248173 4 105 F Repair broken fire alarm strobe/horn
310440 04/23/2010 247729 1 104 MS Provide current inspection tag for fire extinguisher
310445 04/23/2010 247741 1 120 MS Provide current inspection tag for fire extinguisher
310524 04/23/2010 247920 2 116C MS Provide current inspection tag for fire extinguisher
310591 04/23/2010 248065 2 125B MS Provide current inspection tag for fire extinguisher
310611 04/23/2010 248110 2 149B MS Provide current inspection tag for fire extinguisher
310606 04/23/2010 248100 2 199 MS Provide current inspection tag for fire extinguisher
310622 04/23/2010 248137 3 110A MS Provide current inspection tag for fire extinguisher
310647 04/23/2010 248191 4 195 MS Adjust fire door to 4-194 to latch properly
310642 04/23/2010 248178 6 190 MS Provide current inspection tag for fire extinguisher
310643 04/23/2010 248183 6 191 MS Provide current inspection tag for fire extinguisher
310441 04/23/2010 247731 1 104 OS Prohibit hold open devices on fire door
310443 04/23/2010 247737 1 118 OS Remove and prohibit candles
310651 04/23/2010 248201 1 193 OS Prohibit storage of gasoline or gas powered equipment
310474 04/23/2010 247810 2 107 OS Relocate table to provide 12" clearance on latch side of door
310482 04/23/2010 247824 2 109B OS Provide clear access to fire extinguisher
310526 04/23/2010 247924 2 117B OS Provide clear access to fire extinguisher
310598 04/23/2010 248080 2 124 OS Relocate file cabinet to provide minimum 12" clearance on latch side of door
310597 04/23/2010 248077 2 127B OS Provide clear access to fire extinguisher
310590 04/23/2010 248063 2 140B OS Provide clear access to fire extinguisher
310599 04/23/2010 248082 2 147 OS Relocate table to provide minimum 12" clearance on latch side of door
310636 04/23/2010 248169 4 105 OS Keep area clear to secondary exit
310619 04/23/2010 248127 4 105 OS Relocate bookcase to provide minimum 12" clearance on latch side of door
310621 04/23/2010 248135 4 106 OS Prohibit charging batteries in room
310645 04/23/2010 248187 4 194 OS Remove storage from electrical room
310442 04/23/2010 247735 00 0000 CS Immediately change gate swing at preserve area to allow people inside preserve a way to exit. Currently panic bars are on the outside of the gates. When gate closes you are locked inside of preserve
310521 04/23/2010 247913 2 113 CS Arrange furniture to provide minimum 3' wide clear path to corridor door
310639 04/23/2010 248176 4 195 CS Provide ABC fire extinguisher, not type K
310449 04/23/2010 247749 1 101 FS Provide fire alarm log book at fire alarm panel
203623 03/02/2010 77996 00 9599 M Repair damaged chain link fencing at bus loop
249802 03/02/2010 119555 00 9599 M Repair broken sidewalk at bus loop
249866 03/02/2010 119659 00 9699 M Repair damaged chain link fencing along south property line
249842 03/02/2010 119608 12 005 M Repair garage door lock to be able to be unlocked
203779 03/02/2010 78297 2 102 M Provide current inspection tag for kitchen steamer
249864 03/02/2010 119655 P 4821 M Secure and protect insulation on portable unit
260119 03/02/2010 141827 4 101A O Prohibit use of outlet box to power copier, plug copier directly into wall outlet
260120 03/02/2010 141829 4 101A O Eliminate and prohibit use of (6 plug) multi outlet adaptor adjacent to counter table
259167 03/02/2010 139866 5 101 O Prohibit plugging one surge protector into another under computer stations, plug each surge protector directly into wall outlet
259161 03/02/2010 139851 P 4086 O Remove and prohibit combustible residential children foam seats
260126 03/02/2010 141841 P 4086 O Prohibit plugging surge protector into an extension cord under writing board, plug surge protector directly into wall outlet and prohibit use of 13A extension cord
260125 03/02/2010 141839 P 42 O Prohibit plugging surge protector into an extension cord, plug surge protector directly into wall outlet and prohibit use of 13A extension cord
187722 03/02/2010 22003 00 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
187724 03/02/2010 22032 00 9599 C Turn barbs down on all fencing (east property line/bus loop)
187728 03/02/2010 22005 1 108A C Provide exhaust fan in bathroom
203615 03/02/2010 77980 1 111 C Provide emergency lighting
187738 03/02/2010 22006 2 101A C Provide handrail on one side of stage steps
187739 03/02/2010 22008 2 101A C Provide handicapped accessibility to stage
203626 03/02/2010 78002 2 101C C Provide emergency lighting along path of egress
187744 03/02/2010 22007 2 105 C Provide fire rated door for boiler room
187746 03/02/2010 22012 4 101B C Provide exhaust fan in bathroom (4-102B)
187747 03/02/2010 22013 4 102A C Provide exhaust fan in bathroom (4-104A)
187748 03/02/2010 22014 4 103A C Provide exhaust fan in bathroom (4-101A)
187749 03/02/2010 22015 4 104A C Provide exhaust fan in bathroom (4-103A)
203780 03/02/2010 78299 5 107 C Provide emergency lighting in student space
259147 03/02/2010 139825 6 107 C Provide partitions between urinals
187758 03/02/2010 22019 6 108 C Provide exhaust ventilation in janitor's closet
187759 03/02/2010 22021 6 110 C Provide partitions between urinals
187760 03/02/2010 22023 7 108 C Provide exhaust ventilation in janitor's closet
187761 03/02/2010 22024 7 109 C Make exterior walkway level with interior floor
249863 03/02/2010 119653 P 4821 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
259159 03/02/2010 139849 P 4086 OS Arrange furniture to maintin a minimum 3 ft clear aisle to stair door
260141 03/02/2010 141872 00 9599 CS Modify gate between Bldg. 8 & bus loop to allow egress at all times and remove chain and padlock
260142 03/02/2010 141874 00 9599 CS Modify gate between Bldg. 7 & P-21 to allow egress at all times and remove chain and padlock
260115 03/02/2010 141818 2 101C FS Provide heat detector in storage room
259149 03/02/2010 139828 7 101A FS Provide heat detector in storage room
260303 03/02/2010 142209 10 0000 N/A No violations observed
260301 03/02/2010 142205 8 0000 N/A No violations observed
260302 03/02/2010 142207 9 0000 N/A No violations observed
260308 03/02/2010 142219 P 4163 N/A No violations observed
260304 11/06/2006 142211 12 0000 N/A No violations observed
260300 11/06/2006 142203 7 0000 N/A No violations observed
260305 11/06/2006 142215 P 4086 N/A No violations observed
260112 11/03/2006 141812 1 110 M Determine cause of water damaged ceiling tiles and replace tiles
260111 11/03/2006 141810 1 110 MS Provide current inspection tag for fire extinguisher
249852 11/01/2006 119628 00 0000 M Provide certification that emergency generator is operable
259179 11/01/2006 139891 1 101 M Repair emergency lighting
259180 11/01/2006 139895 1 108 M Repair emergency lighting
259163 11/01/2006 139858 12 004 M Repair emergency lighting
187734 11/01/2006 30932 12 005 M Repair leaking air handler (No Access to Room)
249849 11/01/2006 119622 4 104A M Anchor toilet to floor
249851 11/01/2006 119626 5 101A M Provide cover for exposed floor electrical outlet
259146 11/01/2006 139823 6 101 M Repair emergency lighting
259143 11/01/2006 139816 6 102 M Repair emergency lighting
259142 11/01/2006 139814 6 104 M Repair emergency lighting
259145 11/01/2006 139818 6 110 M Repair emergency lighting
187762 11/01/2006 21737 8 0000 M Provide verification that all student occupied spaces have emergency lights and all are operable
249872 11/01/2006 119674 8 103A M Repair exhaust fan in bathroom
260122 11/01/2006 141833 8 103B M Determine cause of water damaged ceiling tiles and replace tiles in closet
260138 11/01/2006 141866 8 109 M Provide cover on exposed electrical junction box where clock was
259170 11/01/2006 139875 8 109 M Determine cause of water damaged ceiling tiles and replace tiles
260113 11/01/2006 141814 8 113A M Provide cover for exposed electrical outlet adjacent to door
249873 11/01/2006 119676 8 113A M Anchor toilet to floor
249877 11/01/2006 119684 8 115 M Secure loose interior door knob that comes off of door
187770 11/01/2006 21739 9 0000 M Provide verification that all student occupied spaces have emergency lights and all are operable
249867 11/01/2006 119662 9 101B M Repair exhaust fan in bathroom
249870 11/01/2006 119669 9 109 M Install TV cable in fittings that allow cable to enter gutter correctly not through open front of gutter and install cover on open gutter
249883 11/01/2006 119697 P 4086 M Reshingle roof
259158 11/01/2006 139847 P 4086 M Determine cause of water damaged ceiling tiles and replace tiles
259155 11/01/2006 139840 P 4163 M Determine cause of water damaged ceiling tiles and replace tiles
259157 11/01/2006 139844 P 4163 M Provide correct bracket for fire extinguisher and mount at maximum five feet above floor
249857 11/01/2006 119641 P 4163 M Reshingle roof
260140 11/01/2006 141870 00 0 O No access was available to 7-108 & 10-101. Please be prepared to access these rooms during the report review meeting.
259165 11/01/2006 139862 12 001A O Prohibit plugging surge protector into an extension cord, plug surge protector directly into wall outlet and prohibit use of 13A extension cord
259166 11/01/2006 139864 12 001C O Maintain storage room in an orderly manner
260114 11/01/2006 141816 4 102 O Remove and prohibit combustible beanbag chair
259168 11/01/2006 139868 6 102 O Provide certification that carpet meets flame spread requirement or remove carpet
259150 11/01/2006 139831 6 105 O Remove and prohibit combustible beanbag chairs (x2)
259151 11/01/2006 139833 6 106 O Remove and prohibit combustible beanbag chairs(x2)
259153 11/01/2006 139836 6 106 O Eliminate 13A extension cord for table lamp or replace with minimum 15A cord
259164 11/01/2006 139860 7 103 O Remove and prohibit paper covering window in door
260128 11/01/2006 141846 8 101 O Eliminate multiple outlet adaptor above sink counter
259172 11/01/2006 139877 8 103 O Eliminate 13A extension cord or replace with minimum 15A cord
260121 11/01/2006 141831 8 106 O Eliminate 13A extension cord under TV or replace with minimum 15A cord
260139 11/01/2006 141868 8 107 O Eliminate multiple outlet adaptor behind TV
260129 11/01/2006 141848 8 109 O Eliminate multiple outlet adaptor behind refrigerator
260130 11/01/2006 141850 9 102 O Eliminate multiple outlet adaptor behind TV
260131 11/01/2006 141852 9 103 O Eliminate (6 plug) multiple outlet adaptor behind TV
260133 11/01/2006 141856 9 103 O Prohibit plugging one surge protector into another under computer stations, plug each surge protector directly into wall outlet
260136 11/01/2006 141862 9 104 O Remove and prohibit combustible residential red foam couch
260127 11/01/2006 141844 9 105 O Prohibit plugging surge protector into an extension cord, plug surge protector directly into wall outlet and prohibit use of 13A extension cord
260132 11/01/2006 141854 9 105 O Eliminate multiple outlet adaptor
260124 11/01/2006 141837 9 105 O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
260137 11/01/2006 141864 9 106 O Remove and prohibit combustible beanbag chairs (x2)
259169 11/01/2006 139870 9 108 O Provide certification that carpet remnant meets flame spread requirement or remove carpet
260123 11/01/2006 141835 9 108B O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
203630 11/01/2006 78010 00 9599 C Provide auto closer on door of vinyl storage shed beside playground by Bldg. 10
249847 11/01/2006 119618 12 003 MS Provide current inspection tag for fire extinguisher
187735 11/01/2006 21740 12 005 MS Provide current inspection tag for fire extinguisher
249845 11/01/2006 119614 12 006 MS Provide current inspection tag for fire extinguisher
250239 11/01/2006 120454 2 102 MS Provide current inspection tag for Kitchen hood fire suppression system
249812 11/01/2006 119566 5 103 MS Provide current inspection tag for fire extinguisher
249816 11/01/2006 119570 6 108 MS Provide current inspection tag for fire extinguisher
259162 11/01/2006 139856 7 101 MS Provide current inspection tag for fire extinguisher
260135 11/01/2006 141860 P 42 MS Immediately repair stair door to open and close properly. Stair door did not open
260118 11/01/2006 141824 1 111 OS Arrange furniture to maintain a minimum 3 ft clear aisle to exit door
260116 11/01/2006 141820 2 101C OS Remove storage on steps to maintain clear aisle from stage
260117 11/01/2006 141822 2 102A OS Relocate table blocking clear access to exterior door
259176 11/01/2006 139887 4 104 OS Remove and prohibit use of toaster oven
259174 11/01/2006 139883 8 102 OS Remove and prohibit use of toaster oven
259173 11/01/2006 139881 8 103 OS Remove and prohibit use of toaster oven
259175 11/01/2006 139885 8 104D OS Remove and prohibit use of toaster oven
260134 11/01/2006 141858 9 103 OS Arrange storage to maintain a minimum 3 ft clear aisle to exterior door
249838 11/01/2006 119597 1 101 FS Provide certification that fire alarm system has been tested and is fully operational - Report was not available for review
260310 11/01/2006 142228 P 42 N/A No violations observed
260312 11/01/2006 142232 P 4821 N/A No violations observed
236065 02/28/2006 92204 P 4163 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
249860 02/28/2006 119647 P 42 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
249865 02/03/2006 119657 00 0000 M Provide lock on lift station enclosure at P-Clinic
203629 02/03/2006 78008 00 9599 M Provide thumblatch on inside face of door at vinyl storage shed beside playground by Bldg. 10 so door can be unlocked from the inside
249839 02/03/2006 119599 1 101 M Repair emergency lighting
249801 02/03/2006 119553 1 101 M Secure loose door handle
249826 02/03/2006 119584 1 109 M Repair emergency lighting
249824 02/03/2006 119579 1 110 M Repair door to open and close properly
249878 02/03/2006 119686 10 101 M Remove signs indicating "Fire Alarm Inside" and "Fire Extinguisher Inside"
203648 02/03/2006 78046 12 002 M Determine cause of water damaged ceiling tiles and replace tiles
203647 02/03/2006 78044 12 006 M Replace missing ceiling tiles
203620 02/03/2006 77990 2 101A M Repair or replace torn black stage curtains on side of stage and provide dated flame resistance label on curtains
203622 02/03/2006 77994 2 101C M Label door leading into 2-101C as an exit door
249827 02/03/2006 119585 4 101 M Repair emergency lighting
249828 02/03/2006 119586 4 103 M Repair emergency lighting
236064 02/03/2006 92202 4 104 M Remove toaster oven from room
203797 02/03/2006 78335 5 101 M Revise sign indicating maximum occupancy - posted number is 41 but should be 134
249829 02/03/2006 119587 5 101B M Repair emergency lighting
249830 02/03/2006 119588 5 106 M Repair emergency lighting
249853 02/03/2006 119630 6 101A M Adjust door to 6-102 to latch properly
249831 02/03/2006 119589 6 102 M Repair emergency lighting
249832 02/03/2006 119590 6 103 M Repair emergency lighting
249850 02/03/2006 119624 6 103 M Determine cause of water damaged ceiling tiles and replace tiles
249833 02/03/2006 119591 6 104 M Repair emergency lighting
249834 02/03/2006 119592 6 105 M Repair emergency lighting
249835 02/03/2006 119593 7 102 M Repair emergency lighting
249836 02/03/2006 119594 7 103 M Repair emergency lighting
249854 02/03/2006 119632 7 103 M Secure loose power pole
249837 02/03/2006 119595 7 107 M Repair emergency lighting
249855 02/03/2006 119635 7 110 M Secure loose toilet partition upright
249879 02/03/2006 119688 8 102 M Remove or repair ceiling drop cord with frayed end at cord cap
249880 02/03/2006 119690 8 104 M Secure loose cord cap on ceiling drop cord
249841 02/03/2006 119603 8 106B M Secure loose handicapped grabrail
249840 02/03/2006 119601 8 110B M Secure loose handicapped grabrail
249881 02/03/2006 119692 8 111 M Remove sign indicating "Fire Extinguisher Inside"
203689 02/03/2006 78131 8 113B M Replace broken wall tiles adjacent to door
187771 02/03/2006 22064 9 102A M Determine cause of water damaged ceiling tiles and replace tiles
249869 02/03/2006 119666 9 108 M Adjust door to latch properly
249884 02/03/2006 119699 P 4086 M Determine cause of water damaged ceiling tiles and replace tiles
249858 02/03/2006 119643 P 4163 M Determine cause of water damaged ceiling tiles and replace tiles
249859 02/03/2006 119645 P 4163 M Adjust steps to make risers equal
249861 02/03/2006 119649 P 42 M Adjust stair door to latch properly
249862 02/03/2006 119651 P 42 M Adjust steps to make risers equal
249885 02/03/2006 119701 00 0 O No access was available to 1-107A, 7-108 and Bldg. 10. Please be prepared to access these rooms during the report review meeting.
203675 02/03/2006 78102 4 102 O Remove paper covering wall - limit decorations to max. 20% of wall area
203676 02/03/2006 78104 4 104 O Remove paper covering wall - limit decorations to max. 20% of wall area
203672 02/03/2006 78096 6 102 O Remove paper covering wall - limit decorations to max. 20% of wall area
203678 02/03/2006 78108 6 103 O Remove paper covering wall - limit decorations to max. 20% of wall area
203673 02/03/2006 78098 6 104 O Remove paper covering wall - limit decorations to max. 20% of wall area
203677 02/03/2006 78106 6 105 O Remove paper covering wall - limit decorations to max. 20% of wall area
203674 02/03/2006 78100 7 101 O Remove paper covering wall - limit decorations to max. 20% of wall area
249882 02/03/2006 119695 8 111 O Keep door unlocked when facility is occupied to allow access to fire alarm pull station
249856 02/03/2006 119637 9 102A O Keep storage away from heat detector
203621 02/03/2006 77992 2 101A C Provide emergency lighting on stage
203777 02/03/2006 78293 2 102 C Provide tempered glazing, safety glass, or safety plastic in windows within 48 inches of doors at serving line
203653 02/03/2006 78056 P 4163 C Provide bottom rail on ramp landing guardrail at two inches above floor
203650 02/03/2006 78050 P 42 C Provide bottom rail on stair landing guardrail at two inches above floor
203664 02/03/2006 78080 P 42 C Provide bottom rail on ramp landing guardrail at two inches above floor
249803 02/03/2006 119557 1 101 MS Provide current inspection tag for fire extinguisher
249804 02/03/2006 119558 1 113 MS Provide current inspection tag for fire extinguisher
249846 02/03/2006 119616 12 001 MS Provide current inspection tag for fire extinguisher in cabinet or remove fire extinguisher and fire extinguisher sign on cabinet
249848 02/03/2006 119620 12 004 MS Provide current inspection tag for fire extinguisher
249805 02/03/2006 119559 2 101A MS Provide current inspection tag for fire extinguisher
249806 02/03/2006 119560 2 101B MS Provide current inspection tag for fire extinguisher
203778 02/03/2006 78295 2 102 MS Provide current inspection for fire (hood) suppression system (dated 7/03)
249807 02/03/2006 119561 2 104 MS Provide current inspection tag for fire extinguisher
249808 02/03/2006 119562 3 102 MS Provide current inspection tag for fire extinguisher
203788 02/03/2006 78316 3 104 MS Immediately replace missing vent duct for dryer
249809 02/03/2006 119563 4 104 MS Provide current inspection tag for fire extinguisher
249810 02/03/2006 119564 5 101 MS Provide current inspection tag for fire extinguisher
249811 02/03/2006 119565 5 101B MS Provide current inspection tag for fire extinguisher
249813 02/03/2006 119567 5 106 MS Provide current inspection tag for fire extinguisher
249814 02/03/2006 119568 6 102 MS Provide current inspection tag for fire extinguisher
249815 02/03/2006 119569 6 106 MS Provide current inspection tag for fire extinguisher
249817 02/03/2006 119571 7 104 MS Provide current inspection tag for fire extinguisher
249818 02/03/2006 119572 7 105 MS Provide current inspection tag for fire extinguisher
249819 02/03/2006 119573 8 102 MS Provide current inspection tag for fire extinguisher
249820 02/03/2006 119574 8 103 MS Provide current inspection tag for fire extinguisher
249821 02/03/2006 119575 8 105 MS Provide current inspection tag for fire extinguisher
249822 02/03/2006 119576 8 110 MS Provide current inspection tag for fire extinguisher
249823 02/03/2006 119577 9 107 MS Provide current inspection tag for fire extinguisher
249825 02/03/2006 119581 1 113 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station and fire extinguisher
249843 02/03/2006 119610 2 101C OS Maintain clear aisle to exit
249844 02/03/2006 119612 3 105 OS Remove storage in exit corridor
203789 02/03/2006 78318 3 105 OS Remove and prohibit golf cart from exit corridor
249874 02/03/2006 119678 9 101 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station and fire extinguisher
249876 02/03/2006 119682 9 103 OS Keep door unlocked when facility is occupied to access fire extinguisher
249868 02/03/2006 119664 9 106 OS Provide clear access to fire extinguisher
249875 02/03/2006 119680 9 108 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station and fire extinguisher
249871 02/03/2006 119672 8 107B FS Secure heat detector to ceiling
236066 02/02/2006 92206 P 4821 N/A No violations observed
203611 04/20/2005 77971 1 101 M Repair emergency lighting in corridor outside 1-104
203614 04/20/2005 77977 1 103 M Determine cause of water damaged ceiling tiles and replace tiles
203618 04/20/2005 77986 1 108 M Repair emergency lighting
203619 04/20/2005 77988 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
203617 04/20/2005 77984 1 113 M Repair emergency lighting
203649 04/20/2005 78048 12 001B M Determine cause of water damaged ceiling tiles and replace tiles
203632 04/20/2005 78015 12 004A M Determine cause of water damaged ceiling tiles and replace tiles
203613 04/20/2005 77975 2 101 M Determine cause of water damaged ceiling tiles and replace tiles
203625 04/20/2005 78000 2 101C M Replace missing ceiling tiles
203785 04/20/2005 78310 2 102 M Repair door for exterior walk-in freezer to close properly
203782 04/20/2005 78303 2 102B M Replace plastic dryer vent with metal vent
203793 04/20/2005 78327 4 104 M Replace missing ceiling tiles
203784 04/20/2005 78308 5 101C M Repair emergency lighting
203786 04/20/2005 78312 5 101C M Repair damaged vinyl base along steps of seating pit
187751 04/20/2005 63043 5 103 M Reinstall room number sign - sign is inside on light switch
203686 04/20/2005 78125 6 110 M Caulk around all urinals
203683 04/20/2005 78118 7 101 M Determine cause of water damaged ceiling tiles and replace tiles
203706 04/20/2005 78166 7 102 M Repair emergency lighting
203704 04/20/2005 78162 7 103 M Replace damaged sign indicating "Fire Alarm Pull Station Inside"
203708 04/20/2005 78170 7 104 M Repair emergency lighting
203707 04/20/2005 78168 7 105 M Repair emergency lighting
203705 04/20/2005 78164 7 107 M Repair emergency lighting
203699 04/20/2005 78152 7 108 M Repair lock on door so custodial room can be kept locked
203695 04/20/2005 78143 7 110 M Repair emergency lighting
187763 04/20/2005 30943 8 101 M Determine cause of water damaged ceiling tiles and replace tiles
203642 04/20/2005 78034 8 101B M Remove hook and eye lock device on inside of bathroom door
203694 04/20/2005 78141 8 102 M Rehang fire extinguisher bracket and mount extinguisher on bracket
203709 04/20/2005 78172 8 102 M Replace missing ceiling tiles
203710 04/20/2005 78174 8 102 M Repair water damaged wall finish adjacent to closet and behind computers
203696 04/20/2005 78145 8 102B M Remove slidebolt lock from inside of bathroom door
203697 04/20/2005 78147 8 103B M Replace missing ceiling tiles
203638 04/20/2005 78027 8 104A M Remove hook and eye lock device on inside of bathroom door
203643 04/20/2005 78036 8 105B M Remove hook and eye lock device on inside of bathroom door
203639 04/20/2005 78029 8 106B M Remove hook and eye lock device on inside of bathroom door
203688 04/20/2005 78129 8 107 M Adjust clock to cover junction box
203687 04/20/2005 78127 8 107A M Repair exhaust fan in bathroom
187764 04/20/2005 22061 8 107B M Determine cause of water damaged ceiling tiles and replace tiles
187766 04/20/2005 63044 8 108A M Caulk gap on wall at light switch
203640 04/20/2005 78031 8 110B M Remove hook and eye lock device on inside of bathroom door
203681 04/20/2005 78114 8 111 M Determine cause of water damaged ceiling tiles and replace tiles
203682 04/20/2005 78116 8 113A M Repair damaged metal shelf
187767 04/20/2005 22057 8 113B M Replace missing laminate on countertop and partition
203684 04/20/2005 78120 8 115A M Repair leaking chilled water line
203635 04/20/2005 78021 9 101B M Remove hook and eye lock device on inside of bathroom door
203636 04/20/2005 78023 9 102B M Remove hook and eye lock device on inside of bathroom door
203644 04/20/2005 78038 9 103 M Remove air freshener from ceiling outlet
203634 04/20/2005 78019 9 103A M Remove hook and eye lock device from inside bathroom door
203637 04/20/2005 78025 9 104A M Remove hook and eye lock device on inside of bathroom door
203655 04/20/2005 78061 P 4163 M Repair emergency lighting
203656 04/20/2005 78063 P 4163 M Replace missing ceiling tiles
203661 04/20/2005 78074 P 42 M Replace missing ceiling tiles
203662 04/20/2005 78076 P 42 M Replace missing ceiling tiles in bathroom
187774 04/20/2005 22070 P 4821 M Repair cove base in bathroom to be impervious
203645 04/20/2005 78040 00 0000 O Prohibit air fresheners throughout campus
203787 04/20/2005 78314 00 9599 O Prohibit parking in fire lane behind kitchen
203616 04/20/2005 77982 1 113 O Remove and prohibit combustible beanbag chairs
203670 04/20/2005 78092 12 001 O Provide certification of flame spread rating of carpeting and repair frayed edges or remove carpeting
203612 04/20/2005 77973 2 101 O Eliminate extension cord or replace with minimum 15A cord
203627 04/20/2005 78004 2 101B O Eliminate extension cord or replace with minimum 15A cord and prohibit use of cord with multi-outlet end
203795 04/20/2005 78331 4 101 O Prohibit plugging surge protector into another surge protector
203796 04/20/2005 78333 4 102 O Eliminate extension cords or replace with minimum 15A cords (x2)
203794 04/20/2005 78329 4 104 O Eliminate extension cord or replace with minimum 15A cord and prohibit use of cord with multi-outlet end
203781 04/20/2005 78301 5 107A O Remove and prohibit paper covering window in door
203776 04/20/2005 78291 6 101A O Eliminate extension cord or replace with minimum 15A cord and prohibit plugging copy machine into extension cord
203701 04/20/2005 78156 8 101 O Prohibit use of multi-outlet power strip or verify strip has operable surge suppression
203702 04/20/2005 78158 8 101 O Prohibit plugging power strip into extension cord
203711 04/20/2005 78176 8 102 O Eliminate extension cord at computers or replace with minimum 15A cord
203712 04/20/2005 78178 8 102 O Prohibit plugging extension cord into surge protector
203713 04/20/2005 78180 8 102 O Eliminate extension cord at microwave oven or replace with minimum 15A cord and prohibit use of cord with multi-outlet end
203698 04/20/2005 78150 8 103B O Remove cables on floor that prevent door from opening properly
203679 04/20/2005 78110 8 111 O Eliminate extension cord or replace with minimum 15A cord and prohibit cords with multi-outlet ends
203646 04/20/2005 78042 9 106 O Eliminate extension cord or replace with minimum 15A cord and prohibit running electrical cord through ceiling
203633 04/20/2005 78017 9 107 O Remove and prohibit combustible beanbag chairs
203657 04/20/2005 78066 P 4163 O Remove and prohibit flammable curtains on windows
203659 04/20/2005 78070 P 4163 O Remove and prohibit paper covering window in ramp door
203663 04/20/2005 78078 P 42 O Eliminate extension cord or replace with minimum 15A cord and prohibit use of extension cord with multi-outlet end
203652 04/20/2005 78054 P 42 O Prohibit covering electrical panel and remove all storage in front of panel
203665 04/20/2005 78082 P 4821 O Remove and prohibit flammable curtains on windows
203666 04/20/2005 78084 P 4821 O Eliminate extension cord or replace with minimum 15A cord at microwave oven
187768 04/20/2005 22025 8 113B C Provide partition at urinal
203668 04/20/2005 78088 P 4821 C Provide bottom rail on stair landing guardrail at two inches above floor
203609 04/20/2005 77967 1 106 F Provide fire alarm strobe light
203790 04/20/2005 78321 5 103 F Clean or replace heat detector
187752 04/20/2005 21731 5 103 MS Provide current inspection tag for fire extinguisher (12/96)
203685 04/20/2005 78122 8 115A MS Remove storage from mechanical room
203658 04/20/2005 78068 P 4163 MS Provide fire extinguisher with minimum 4A capacity in portable
203610 04/20/2005 77969 1 106A OS Prohibit use of candles
203669 04/20/2005 78090 12 001 OS Relocate all storage and instruments blocking clear access to emergency escape window
203671 04/20/2005 78094 12 001 OS Relocate table and storage blocking clear access to fire alarm pull station
203624 04/20/2005 77998 2 101C OS Remove storage blocking clear path to exterior door
203792 04/20/2005 78325 3 102 OS Remove storage from electrical room
203631 04/20/2005 78012 5 101A OS Arrange tables, storage, etc. to provide a minimum 5' wide clear path from computer area to exterior doors
203791 04/20/2005 78323 6 101 OS Arrange tables to provide minimum 3' wide clear path to exterior door
203703 04/20/2005 78160 8 101 OS Prohibit running electrical cord under rug
203700 04/20/2005 78154 8 101 OS Arrange furniture and storage to provide and maintain minimum 3' wide clear path to exterior door
203692 04/20/2005 78137 8 105 OS Arrange furniture and storage to provide and maintain minimum 3' wide clear path to exterior door
203691 04/20/2005 78135 8 105A OS Prohibit storage of flammable spray paint
203680 04/20/2005 78112 8 111 OS Relocate tree blocking clear path to exterior door
203693 04/20/2005 78139 8 112 OS Prohibit use of candles
203690 04/20/2005 78133 8 115 OS Remove storage from electrical room and keep door to room locked to prohibit unauthorized access
203660 04/20/2005 78072 P 4163 OS Prohibit occupancy of portable until construction blocking stair door is completed
203651 04/20/2005 78052 P 42 OS Remove and prohibit all storage at stair door
203667 04/20/2005 78086 P 4821 OS Remove storage cart and storage blocking clear path to stair door
187737 04/20/2005 21706 2 101 CS Provide ABC fire extinguisher near north pull station
203628 04/20/2005 78006 00 9599 FS Provide heat detector in vinyl storage building adjacent to playground beside Bldg. 10
187732 04/20/2005 21725 10 101 FS Provide heat detector in storage room (No Access to Room)
203783 04/20/2005 78306 2 102D FS Provide heat detector in storage room
187723 12/22/2004 30928 00 0000 M School must have gate locked. Other gate with panic bar is sufficient for exiting. If chain and lock stay then the panic bar must be removed. ( Fenced play area at bldg. 10)
187733 12/22/2004 22067 12 001 M Secure loose base
187736 12/22/2004 21708 2 101 M Provide number indicating maximum occupancy on sign adjacent to main entrance
187741 12/22/2004 63042 2 102 M Install k.o. seal on gas shut off box
187754 12/22/2004 22045 5 107A M Repair or replace damaged ceiling - finish is coming off
187757 12/22/2004 30938 6 108 M Repair termite damage to door frame
187769 12/22/2004 30948 8 115A M Insulate exposed chilled water lines
187775 12/22/2004 30956 P 1 M Adjust steps to make risers equal
187773 12/22/2004 30955 P 1 M Repair or replace damaged ceiling
187780 12/22/2004 22073 P 2 M Repair or replace rusted ramp door
187776 12/22/2004 30957 P 2 M Repair broken/deteriorated base along bathroom wall
187777 12/22/2004 22072 P 2 M Repair or replace crushed downspout on gutter
187778 12/22/2004 22071 P 2 M Adjust steps to make risers equal
187750 12/22/2004 21709 5 101 C Provide sign indicating maximum occupancy adjacent to main entrance
187779 12/22/2004 22028 P 2 C Land the ground wire on the panel
203654 12/22/2004 78059 P 4163 C Provide handicapped accessible door hardware for both doors
187725 12/22/2004 21717 1 101 F Install fire alarm pull station near main exit doors
187740 12/22/2004 21721 2 102 F Install fire alarm pull station near kitchen exit door and hood extinguishing actuator device
187772 12/22/2004 30953 9 108 F Relocate fire alarm pull station to be at main exit
187756 12/22/2004 21732 6 103 MS Recharge fire extinguisher
187765 12/22/2004 30945 8 108 MS Provide current inspection tag for fire extinguisher, no year punched
187726 12/22/2004 21713 1 104A FS Provide heat detector in storage room
187727 12/22/2004 21714 1 107A FS Provide heat detector in storage room
187729 12/22/2004 21715 1 109A FS Provide heat detector in storage room
187730 12/22/2004 21716 1 109B FS Provide heat detector in storage room
187731 12/22/2004 30931 1 114A FS Provide heat detector in storage room
187742 12/22/2004 21720 2 104 FS Provide heat detector in storage room
187743 12/22/2004 21718 2 105 FS Provide heat detector in boiler room
187745 12/22/2004 21722 3 104 FS Provide heat detector in storage room
187753 12/22/2004 21723 5 107A FS Provide heat detector in storage room
187755 12/22/2004 21724 5 107B FS Provide heat detector in storage room