Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
416039 04/09/2018 477655 1 198G M Patch hole in ceiling and repair water damaged ceiling finish - custodial room adjacent to 1-180
416059 04/09/2018 477697 2 104 M Patch hole in ceiling - girls bathroom
416073 04/09/2018 477721 2 105 M Replace broken lens on light fixture in vestibule to boys locker room
416101 04/09/2018 477785 P 9281 M Repair emergency lighting above front door
415965 04/09/2018 477494 1 157 O Eliminate white extension cord with multiple outlet end under teacher desk or replace with a surge protector
416038 04/09/2018 477653 1 168 O Remove and prohibit excessive flammable white vinyl sheathing on bulletin board in staff dining
416050 04/09/2018 477678 1 172A O Store chemicals properly in flammable storage cabinet
416121 04/09/2018 477830 P 9833 O Remove or replace floor mat with rolled up edges to eliminate trip hazard
416112 04/09/2018 477808 P 6458 MS Repair mechanical room door hardware to work properly - hard to open. Located inside boys bathroom
416044 04/09/2018 477666 1 0000 OS Remove plants and silk tree from corridor adjacent to media center to maintain safe egress
416037 04/09/2018 477651 1 164A OS Remove all chairs along stage ramp to maintain safe egress
309310 04/09/2018 245213 P 6458 N/A No violations observed
260596 04/09/2018 142731 P 9281 N/A No violations observed
309215 04/09/2018 245016 P 9833 N/A No violations observed
415952 03/15/2018 477468 00 0000 M Provide current certification that fire alarm system has been tested and is fully operational and make any necessary repairs if indicated on report - last tag date 11.30.16
416051 03/15/2018 477680 00 9599 M Repair gate in chain link fencing between gymnasium building and P-12 to open and close properly. Gate with panic hardware is stuck
416124 03/15/2018 477836 00 9599 M Trim over grown tree branches rubbing against south side of Bldg. 1 facing P-11, P-9 and P-1 (X3)
416127 03/15/2018 477842 00 9599 M Repair damaged concrete finish at covered walkway base columns between P-7 and P-8 (X2)
416042 03/15/2018 477662 1 0000 M Repair light in exit sign in corridor adjacent to 1-191
415953 03/15/2018 477470 1 108 M Replace missing cover for cleanout under sink
415955 03/15/2018 477474 1 116 M Repair clinic door to open and close properly - east door rubs on frame
416046 03/15/2018 477670 1 120 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to media center entrance doors
416047 03/15/2018 477672 1 120 M Repair light in exit sign above east and west exit doors (X2)
416048 03/15/2018 477674 1 126 M Determine cause of water damaged ceiling tiles and replace tiles
415958 03/15/2018 477480 1 148A M Repair exhaust fan in bathroom
416049 03/15/2018 477676 1 170 M Repair light in exit sign
415969 03/15/2018 477502 1 177 M Determine cause of water damaged ceiling tiles and replace tiles above cooking ranges
415970 03/15/2018 477504 1 177 M Replace missing grille for exhaust fan above cooking range (X4)
416045 03/15/2018 477668 1 198B M Provide current inspection log for hot water heater
416054 03/15/2018 477686 2 101 M Replace missing handle for fire extinguisher cabinet door adjacent to NW exit doors in gymnasium
416055 03/15/2018 477688 2 101 M Adjust NE exit door to latch properly. Door latch hardware need to be adjusted to make door secure
416056 03/15/2018 477690 2 101 M Repair light in exit sign above SE exit doors
416058 03/15/2018 477694 2 101 M Adjust panic hardware on SW exit door to work properly. Hardware sticks
416061 03/15/2018 477700 2 103A M Patch hole in ceiling adjacent to exterior door - girls locker room
416063 03/15/2018 477705 2 103A M Change maximum occupancy sign to read 65 - currently marked 650 in girls locker room
416076 03/15/2018 477733 2 105B M Repair water damaged ceiling finish in bathroom - boys locker room
416074 03/15/2018 477730 2 105E M Determine cause of water damaged ceiling tiles and replace tiles in coach office - boys locker room
416052 03/15/2018 477682 2 190 M Replace burned out light bulbs in communications room
416097 03/15/2018 477779 P 6452 M Repair emergency lighting above front door
416122 03/15/2018 477832 P 6452 M Determine cause of water damaged ceiling tiles and replace tiles
416096 03/15/2018 477777 P 6453 M Repair emergency lighting above front door
416095 03/15/2018 477775 P 6455 M Repair emergency lighting above front door
416094 03/15/2018 477770 P 6456 M Repair emergency lighting above front door
416110 03/15/2018 477804 P 6458 M Repair emergency lighting in girls bathroom
416111 03/15/2018 477806 P 6458 M Repair emergency lighting in boys bathroom
416128 03/15/2018 477844 P 9276 M Repair broken vinyl base along wall adjacent to wall cabinets
416099 03/15/2018 477781 P 9277 M Repair emergency lighting above front door
416123 03/15/2018 477834 P 9305 M Secure loose front cover on exit sign above front door
416125 03/15/2018 477838 P 9307 M Repair or replace emergency lighting with broken test button above front door
416126 03/15/2018 477840 P 9307 M Repair damaged wall finish adjacent to front door
416088 03/15/2018 477759 P 9309 M Repair emergency lighting above front door
416086 03/15/2018 477754 P 9311 M Repair or replace emergency lighting with damaged test button above front door
416109 03/15/2018 477802 P 9402 M Repair electrical outlets under AC unit to work properly
416091 03/15/2018 477762 P 9407 M Repair emergency lighting above front door
416031 03/15/2018 477639 1 138A O Relocate shelf unit in front of electrical panel. Panel door should be kept shut
416029 03/15/2018 477634 1 147 O Remove and prohibit excessive flammable black vinyl sheathing on bulletin board behind computers
416462 03/15/2018 478556 1 150 O Secure all machinery in use to table top before use to eliminate hazard - Request assistance from maintenance if needed
416463 03/15/2018 478559 1 150 O Remove all storage within safety lines around machinery bolted to floor to eliminate hazard
416028 03/15/2018 477632 1 151 O Remove and prohibit combustible residential chair and ottoman
415963 03/15/2018 477490 1 154B O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet or into a surge protector
415964 03/15/2018 477492 1 156 O Remove and prohibit combustible residential green chair
415966 03/15/2018 477496 1 167 O Remove and prohibit paper covering window in corridor door
415967 03/15/2018 477498 1 169 O Eliminate white extension cord with multiple outlet end behind aquarium or replace with a surge protector
415968 03/15/2018 477500 1 175 O Remove and prohibit combustible residential mattress and box spring from drama classroom (X2)
415971 03/15/2018 477507 1 177 O Clean dirty ovens and dirty grille for exhaust fan above range burners
416027 03/15/2018 477630 1 178 O Remove black paper covering electrical outlets in back of classroom
416116 03/15/2018 477816 P 6453 O Prohibit plugging surge protector into extension cord under teacher desk - plug surge protector directly into wall outlet and eliminate use of extension cord
416114 03/15/2018 477812 P 6455 O Remove and prohibit paper covering window in front door
416130 03/15/2018 477848 P 9279 O Remove black paper covering electrical outlets adjacent to front door
416131 03/15/2018 477850 P 9281 O Remove and prohibit excessive flammable black vinyl sheathing on table adjacent to teacher desk and at front side of teacher desk (X2)
416108 03/15/2018 477800 P 9402 O Prohibit plugging surge protector into surge protector under computer stations adjacent to electrical panel
416107 03/15/2018 477798 P 9404 O Remove and prohibit excessive flammable vinyl sheathing on 2 tables, window and bathroom door (X4)
416106 03/15/2018 477795 P 9407 O Remove paper touching bulb shade on floor lamp to eliminate hazardous condition or relocate floor lamp
416115 03/15/2018 477814 P 9833 O Remove and prohibit paper covering window in front door
415954 03/15/2018 477472 1 112 MS Repair door lock hardware to work properly - lock spins
415960 03/15/2018 477484 1 148 MS Provide current inspection tag for fire extinguisher
415961 03/15/2018 477486 1 199G MS Provide current inspection tag for fire extinguisher
416057 03/15/2018 477692 2 101 MS Recharge fire extinguisher adjacent to SE exit doors
416113 03/15/2018 477810 P 6456 MS Secure loose door lever
415962 03/15/2018 477488 1 146 OS Relocate storage to maintain 3 ft clear path to exterior door
416036 03/15/2018 477649 1 164 OS Relocate storage in back of stage to maintain clear access to exterior exit door
416026 03/15/2018 477628 1 184 OS Remove and prohibit use of toaster oven
416025 03/15/2018 477626 1 185 OS Remove and prohibit use of toaster oven
416129 03/15/2018 477846 P 9276 OS Relocate 2 carts to maintain 3 ft clear path to back exit door
309212 03/15/2018 245009 P 6452 N/A No violations observed
309216 03/15/2018 245018 P 6453 N/A No violations observed
309218 03/15/2018 245022 P 6455 N/A No violations observed
309219 03/15/2018 245024 P 6456 N/A No violations observed
260601 03/15/2018 142741 P 9276 N/A No violations observed
260600 03/15/2018 142739 P 9277 N/A No violations observed
260598 03/15/2018 142735 P 9279 N/A No violations observed
260606 03/15/2018 142753 P 9305 N/A No violations observed
260615 03/15/2018 142770 P 9307 N/A No violations observed
260612 03/15/2018 142764 P 9309 N/A No violations observed
236036 03/15/2018 92151 P 9311 N/A No violations observed
260625 03/15/2018 142790 P 9402 N/A No violations observed
260622 03/15/2018 142785 P 9404 N/A No violations observed
236039 03/15/2018 92157 P 9407 N/A No violations observed
348055 12/05/2017 330025 00 0000 M Replace rusted, missing valve stems for valves on chilled water lines in chiller compound
416043 12/05/2017 477664 00 0000 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report dated 10.31.17
416083 12/05/2017 477744 00 9599 M Adjust latch hardware of gate in chain link fencing adjacent to P-12 back door to latch properly
383152 12/05/2017 406752 1 0000 M Repair leaking rain gutters and downspouts
416032 12/05/2017 477641 1 142A M Provide correct signage indicating room name and number for boys bathroom facing 1-144. Sign reads 1-144 and it should read 1-142A
416030 12/05/2017 477637 1 144 M Repair exhaust fan above cooking range to vent to the exterior - fan blows back into room. The exhaust duct is visible above the range
415957 12/05/2017 477478 1 144B M Repair exhaust fan in bathroom
415959 12/05/2017 477482 1 146A M Repair exhaust fan in bathroom
416041 12/05/2017 477660 1 185B M Repair exhaust fan in bathroom
416040 12/05/2017 477658 1 185C M Repair exhaust fan in bathroom
383426 12/05/2017 407356 1 197A M Repair exhaust fan in bathroom
399985 12/05/2017 443009 1 197B M Repair ventilation fan in men's bathroom
416035 12/05/2017 477647 1 198E M Repair exhaust fan in custodial room
416053 12/05/2017 477684 2 106 M Repair exhaust fan in boys bathroom in gymnasium and secure loose exhaust fan grille
416034 12/05/2017 477645 1 0000 C Provide emergency disconnect valve for water in all science rooms (1-131, 1-134, 1-146, 1-158, 1-162, 1-182 and 1-190)
415956 12/05/2017 477476 1 0000 C Post sign indicating primary and secondary evacuation routes in contrasting colors for all student occupied space in Building 1
416033 12/05/2017 477643 1 142A MS Repair unlock thumb latch on boys bathroom door to work properly . Thumb latch spins - labeled 1-144
260594 12/05/2017 142727 2 0000 N/A No violations observed
260595 12/05/2017 142729 3 0000 N/A No violations observed
281969 12/05/2017 186397 P 3683 N/A No violations observed
260619 12/05/2017 142777 P 3760 N/A No violations observed
309217 12/05/2017 245020 P 6454 N/A No violations observed
309309 12/05/2017 245211 P 6457 N/A No violations observed
260599 12/05/2017 142737 P 9278 N/A No violations observed
260597 12/05/2017 142733 P 9280 N/A No violations observed
260608 12/05/2017 142755 P 9304 N/A No violations observed
260605 12/05/2017 142750 P 9306 N/A No violations observed
260613 12/05/2017 142767 P 9308 N/A No violations observed
260611 12/05/2017 142762 P 9310 N/A No violations observed
260623 12/05/2017 142787 P 9403 N/A No violations observed
260621 12/05/2017 142780 P 9405 N/A No violations observed
260617 12/05/2017 142773 P 9406 N/A No violations observed
309213 12/05/2017 245012 P 9831 N/A No violations observed
309214 12/05/2017 245014 P 9832 N/A No violations observed
399979 03/16/2017 442999 1 123 M Replace ceiling tile with hole in it at east wall
399980 03/16/2017 443001 1 126 M Determine cause of water damaged ceiling tiles and replace tiles
399933 03/16/2017 442898 1 136 M Repair light fixture
399934 03/16/2017 442902 1 137 M Replace missing ceiling tiles
399938 03/16/2017 442910 1 143 M Determine cause of water damaged ceiling tiles at windows and replace tiles
399937 03/16/2017 442908 1 144 M Repair crack in wall at exit door
399936 03/16/2017 442906 1 144A M Determine cause of water damaged ceiling tiles and replace tiles
399939 03/16/2017 442912 1 145 M Remove old speaker wiring coming from ceiling on west wall
383308 03/16/2017 407097 1 146A M Repair exhaust fan in bathroom
383309 03/16/2017 407100 1 148A M Repair exhaust fan in bathroom
399949 03/16/2017 442934 1 155 M Replace broken ceiling tiles along north wall
399948 03/16/2017 442931 1 155A M Determine cause of water damaged and broken ceiling tiles and replace tiles
399983 03/16/2017 443006 1 160A M Replace missing escutcheon on fire sprinkler head
399989 03/16/2017 443018 1 164 M Determine cause of water damaged ceiling tiles on stage and replace tiles
399990 03/16/2017 443020 1 165A M Replace missing soap dispenser in handicap stall of women's bathroom
399951 03/16/2017 442937 1 167 M Remove old speaker wiring coming from ceiling next to bathroom
399912 03/16/2017 442855 1 170A M Repair light fixture (X3) in instrument storage room
399917 03/16/2017 442862 1 171 M Replace missing ceramic base tile in boy's restroom
399919 03/16/2017 442869 1 171 M Replace missing towel dispenser in boy's restroom
399923 03/16/2017 442873 1 171 M Replace broken wall tile at corner next to sinks
383247 03/16/2017 406959 1 175C M Label all circuits on electrical panel LPP1C2
399927 03/16/2017 442886 1 179 M Determine cause of water damaged ceiling tiles above sink and replace tiles
399929 03/16/2017 442890 1 185 M Determine cause of water damaged ceiling tiles and replace tiles
399903 03/16/2017 442836 1 188 M Replace ceiling tile with hole in it next to speaker
399930 03/16/2017 442892 1 189 M Place ceiling tiles back into metal ceiling grid
399941 03/16/2017 442916 1 199G M Replace missing insulation around valve in chilled water supply pipe
383372 03/16/2017 407230 1 199H M Replace 2 missing screws for covers of electrical panels HLP4 and LDP4
399931 03/16/2017 442894 1 199L M Repair or replace badly rusted door
399901 03/16/2017 442833 1 199P M Make necessary repairs to fire sprinkler system as indicated on inspection report
399995 03/16/2017 443032 2 0000 M Repair damaged downspout on north side of Gymnasium
399992 03/16/2017 443025 2 103F M Anchor toilet to floor in handicap stall
399993 03/16/2017 443028 2 105C M Replace damaged faucet controls on showers in boy's locker room
399994 03/16/2017 443030 2 105E M Determine cause of water damaged and missing ceiling tiles and replace tiles
383386 03/16/2017 407260 2 106 M Repair exhaust fan in bathroom
371059 03/16/2017 380470 P 0000 M Repair deteriorated wall finish, peeling paint, at exterior mate lines of P-9, P-10 and P-11
399999 03/16/2017 443040 P 3683 M Repair emergency lighting at both doors
399964 03/16/2017 442968 P 3760 M Repair emergency lighting at both exit doors
399966 03/16/2017 442971 P 3760 M Replace damaged soffit - roof edge above stair door
399968 03/16/2017 442973 P 3760 M Place ceiling tiles back into metal ceiling grid at southwest corner
399975 03/16/2017 442991 P 6453 M Repair emergency lighting at rear door
399976 03/16/2017 442993 P 6453 M Determine cause of water damaged ceiling tiles and replace tiles
399974 03/16/2017 442988 P 6454 M Repair emergency lighting at rear door
399972 03/16/2017 442983 P 6457 M Repair emergency lighting at front door
399973 03/16/2017 442985 P 6457 M Determine cause of water damaged ceiling tiles and replace tiles
383199 03/16/2017 406855 P 6458 M Repair exhaust fan in boys bathroom
399997 03/16/2017 443036 P 9276 M Repair emergency lighting at rear door
399998 03/16/2017 443038 P 9276 M Repair rear door to close properly
399996 03/16/2017 443034 P 9277 M Repair emergency lighting at rear door
400004 03/16/2017 443051 P 9304 M Fill dirt around hole below foundation at rear of portable
400006 03/16/2017 443056 P 9304 M Repair rear door to close properly
400000 03/16/2017 443043 P 9307 M Repair emergency lighting at front door
400001 03/16/2017 443046 P 9307 M Repair rear door to close properly
399962 03/16/2017 442964 P 9308 M Repair emergency lighting at front door
399963 03/16/2017 442966 P 9308 M Repair rear door to close properly (drags on exterior concrete landing)
399960 03/16/2017 442945 P 9309 M Repair or replace electric outlet below white board with prong sticking out of it (electric shock hazard)
399961 03/16/2017 442962 P 9309 M Provide cover for exposed electrical outlet below whiteboard
383269 03/16/2017 407008 P 9310 M Repair emergency lighting at front door
399954 03/16/2017 442943 P 9311 M Repair emergency lighting at front door
383278 03/16/2017 407031 P 9406 M Repair emergency lighting at front door
399978 03/16/2017 442997 P 9831 M Repair emergency lighting at front door
399977 03/16/2017 442995 P 9833 M Repair damaged interior wall finish around front door
383284 03/16/2017 407044 P 9833 M Repair missing exterior wall finish at entry
399895 03/16/2017 442816 1 104 O Eliminate light duty multi outlet extension cord at desk in principal's office
399981 03/16/2017 443003 1 120 O Prohibit plugging surge protector into surge protector at circulation desk
399932 03/16/2017 442896 1 136C O Replace burned out bulbs in light fixture inside storage room
399935 03/16/2017 442904 1 140 O Prohibit plugging surge protector into surge protector at teacher's desk
399953 03/16/2017 442940 1 162 O Eliminate multi plug outlet adaptor in teacher planning room
399986 03/16/2017 443013 1 164D O Replace burned out bulbs in light fixture
399910 03/16/2017 442846 1 174 O Eliminate use of multi outlet electrical adaptor (three-way) at microwave oven (use surge protector instead)
399925 03/16/2017 442881 1 175 O Replace burned out bulbs in emergency light fixture
399905 03/16/2017 442841 1 178 O Remove and prohibit hanging decorations from ceiling
399926 03/16/2017 442884 1 179 O Replace burned out bulbs in light fixtures (X5)
399928 03/16/2017 442888 1 181 O Replace burned out bulbs in light fixture
399899 03/16/2017 442829 1 194 O Eliminate light duty multi outlet extension cord located on east wall
399897 03/16/2017 442825 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus
399970 03/16/2017 442978 P 6458 MS Repair broken latch on door of handicap stall in boy's restroom
399940 03/16/2017 442914 1 152C OS Prohibit storage of flammable paints (store flammables in flammable storage cabinet or flammable storage room)
399988 03/16/2017 443016 1 164G OS Remove storage blocking clear access to fire extinguisher
399991 03/16/2017 443023 2 192 OS Prohibit storage of gas powered pressure washer in mechanical room
260593 03/16/2017 142725 1 0000 N/A No violations observed
383151 11/17/2016 406749 00 0000 M Re-insulate chilled water pump in chiller compound
383330 11/17/2016 407142 1 142 M Replace missing laminate on countertop
383391 11/17/2016 407272 1 161 M Replace missing escutcheon on fire sprinkler head
383183 11/17/2016 406812 1 164 M Provide illuminated exit sign at rear door
383340 11/17/2016 407164 1 199B M Make necessary repairs to fire sprinkler system as indicated on inspection report
383253 11/17/2016 406975 1 199R M Replace missing cover on damper actuator on AHU 2 operates as designed
383367 11/17/2016 407219 1 199T M Leak at vent pipe through ceiling. Repair leak and repair ceiling
383393 11/17/2016 407276 2 103F M Replace missing back splash on counter top
383176 11/17/2016 406796 2 105B M Caulk back splash on countertop
383429 11/17/2016 407358 2 191 M Cover for electrical panel HEP5 is missing 2 screws. Replace missing screws
383177 11/17/2016 406808 1 164 O Provide clear access to stage smoke vent controls
383255 03/08/2016 406978 00 0000 M Eliminate ants in play fields
383306 03/08/2016 407092 1 0000 M Caulk loose glass in corridor door at 1-124A
360164 03/08/2016 356837 1 0000 M Clean rain gutters and downspouts for building 1
383390 03/08/2016 407268 1 0000 M Provide chain and lock on gate of fencing around A-C equipment in interior courtyard at 1-199L
383402 03/08/2016 407296 1 0000 M Replace missing cover plate for panic hardware on gate at 1-198M
383337 03/08/2016 407155 1 0000 M Replace damaged cover for cleanout outside of 1-194
383364 03/08/2016 407214 1 0000 M Provide handle on fire extinguisher cabinet in corridor at 1-161
383332 03/08/2016 407148 1 0000 M Repair corridor door at 1-189 to open and close properly. Drags on floor
383324 03/08/2016 407125 1 0000 M Eliminate wasp nest at exit sign at door from interior courtyard at 1-143
383316 03/08/2016 407111 1 101 M Make repairs to fire alarm as indicated on report to AHJ and provide copy of report to AHJ. Not attached to inspection report
383327 03/08/2016 407134 1 126 M Determine cause of water damaged ceiling tiles and replace tiles
383185 03/08/2016 406825 1 126A M Repair exhaust fan in bathroom
383317 03/08/2016 407116 1 131 M Repair emergency eye wash - low flow
383318 03/08/2016 407119 1 131 M Repair sink that will not drain. Sink taped off
383331 03/08/2016 407146 1 138A M Label all circuits on electrical panel LPP3D
383299 03/08/2016 407075 1 140 M Repair emergency eye wash - low flow
383311 03/08/2016 407103 1 142A M Secure loose faucet. Room signed 1-144
383312 03/08/2016 407106 1 146 M Adjust door to exterior to latch properly
383154 03/08/2016 406757 1 147 M Replace missing cabinet door handle
383190 03/08/2016 406836 1 149 M Replace damaged ceiling tile at 1-147A
383380 03/08/2016 407244 1 163 M Repair air conditioning system to ensure it operates as designed. Teacher complained that it is always hot
383178 03/08/2016 406810 1 164 M Determine cause of water damaged ceiling tiles and replace tiles
383365 03/08/2016 407217 1 165 M Repair light in exit sign at SE doors
383150 03/08/2016 406747 1 166 M Repair Kitchen hood exhaust fan, noisey
383384 03/08/2016 407255 1 166F M Provide protective cage around fire sprinkler head
383382 03/08/2016 407253 1 166G M Provide protective cage around fire sprinkler head
383169 03/08/2016 406788 1 169 M Determine cause of water damaged ceiling tiles and replace tiles
383155 03/08/2016 406759 1 170 M Secure and repair torn and loose nosings and riser covers
383158 03/08/2016 406763 1 171 M Secure loose faucets
383159 03/08/2016 406769 1 171 M Caulk 2 urinals to wall
383226 03/08/2016 406918 1 175 M Repair emergency eye wash. Missing diverter piece
383333 03/08/2016 407151 1 181 M Adjust door to latch exterior to properly
383248 03/08/2016 406966 1 188 M Repair broken window blinds
383256 03/08/2016 406981 1 198C M Replace missing signage indicating room name and number
383258 03/08/2016 406983 1 199G M Replace missing cover for damper actuator on AHU 6
383404 03/08/2016 407299 1 199J M Remove large piece of visqueen on top of ductwork at NE corner of room
383303 03/08/2016 407082 1 199L M Panel schedule and numbers on panel do not correspond. Revise schedule
383360 03/08/2016 407197 1 199S M Numbers on electrical panel schedule do not correspond with numbers on panel. Revise schedule
383370 03/08/2016 407225 1 199T M Replace missing strike plate on door frame
383388 03/08/2016 407263 2 0000 M Seal open joints on exterior wall
383432 03/08/2016 407366 2 103C M Repair exhaust fan in bathroom
383376 03/08/2016 407240 2 104 M Anchor toilet to floor
383156 03/08/2016 406761 3 101 M Repair door to open and close properly. Drags on landing
383162 03/08/2016 406775 P 6452 M Repair emergency lighting at rear door
383164 03/08/2016 406777 P 6453 M Repair damaged wall and cover exposed corner bead at bathroom-closet
383166 03/08/2016 406781 P 6454 M Repair emergency lighting at front door
383167 03/08/2016 406785 P 6455 M Repair emergency lighting at rear door
383197 03/08/2016 406852 P 6457 M Repair emergency lighting at rear door
383203 03/08/2016 406861 P 6458 M Caulk toilet to wall in single bathroom at boys restroom
383204 03/08/2016 406868 P 6458 M Caulk sink to wall in single bathroom at girls restroom
383207 03/08/2016 406874 P 9276 M Eliminate wasp nest outside of rear door
383208 03/08/2016 406876 P 9276 M Repair emergency lighting at front door
383209 03/08/2016 406879 P 9277 M Repair emergency lighting at rear door
383211 03/08/2016 406882 P 9277 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
383216 03/08/2016 406889 P 9278 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
383217 03/08/2016 406898 P 9278 M Repair emergency lighting at rear door
383230 03/08/2016 406923 P 9304 M Repair holes in floor at mate line
383234 03/08/2016 406929 P 9305 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they no longer contact ground
383238 03/08/2016 406938 P 9305 M Eliminate wasp nest outside of rear door
383244 03/08/2016 406948 P 9307 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they no longer contact ground
383262 03/08/2016 406993 P 9309 M Replace missing exterior wall finish
383266 03/08/2016 406998 P 9310 M Replace missing exterior wall finish
383271 03/08/2016 407013 P 9403 M Seal wall at bathroom sink to provide impervious wall finish
383276 03/08/2016 407026 P 9404 M Repair emergency lighting at front door
383277 03/08/2016 407029 P 9404 M Repair roof leaks at front of unit at mate line
383272 03/08/2016 407017 P 9405 M Replace damaged rear window screen
383261 03/08/2016 406989 P 9405 M Repair or replace leaking closer on rear door
383279 03/08/2016 407033 P 9406 M Repair broken fire alarm strobe - horn
383280 03/08/2016 407036 P 9407 M Replace missing exterior wall finish at rear of unit
383281 03/08/2016 407038 P 9407 M Repair rear door to open and close properly
383283 03/08/2016 407042 P 9833 M Repair emergency lighting at rear door
383149 03/08/2016 406745 00 0 O No access was available to 1-154C. Please provide access to this room during the report review meeting
383224 03/08/2016 406912 00 0000 O Prohibit parking on grass area at SE campus. NA, not School District property
383153 03/08/2016 406754 1 130 O Provide certification that residential couch meets required California TB 117 flame spread rating or remove and prohibit residential furniture
371229 03/08/2016 380842 1 143 O Provide certification that residential couch and two chairs meet required California TB 117 flame spread rating or remove and prohibit residential furniture
371230 03/08/2016 380844 1 147 O Provide certification that residential couch and two chairs meet required California TB 117 flame spread rating or remove and prohibit residential furniture
383338 03/08/2016 407161 1 147 O Post sign indicating primary and secondary evacuation routes in contrasting colors
383398 03/08/2016 407287 1 162 O Prohibit plugging surge protector into extension cord at lighted growing rack
383400 03/08/2016 407292 1 162 O Maintain clear access to emergency eye wash - shower
383170 03/08/2016 406791 1 172A O Store chemicals properly on shelves not on countertop
383171 03/08/2016 406794 1 172A O Provide clear access to electrical panel
383341 03/08/2016 407167 1 192A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
383250 03/08/2016 406968 1 198L O Keep area within 18 inches of fire sprinkler head clear and unobstructed. Remove top shelf
383161 03/08/2016 406771 P 3760 O Provide clear access to electrical panel
371064 03/08/2016 380486 P 9276 O Provide certification that residential couch meets required California TB 117 flame spread rating or remove and prohibit residential furniture
383282 03/08/2016 407040 P 9831 O Eliminate non 15 amp multi-outlet extension cord or replace with a surge protector
383362 03/08/2016 407211 1 0000 MS Adjust corridor door at 1-160 to latch properly
383396 03/08/2016 407281 1 166 MS Adjust fire door from serving line to Kitchen at 1-166A to latch properly
383313 03/08/2016 407109 1 111 OS Prohibit hold open device on fire door
383188 03/08/2016 406831 1 146 OS Relocate 2 carts at exit door to maintain clear aisle to exit
383252 03/08/2016 406973 1 199R OS Remove old light tubes stored in mechanical room
383430 03/08/2016 407363 2 191 OS Remove old light tubes stored in electrical room
371237 10/29/2015 380858 P 9308 M Make concrete landing at north door level with interior of portable
371244 10/29/2015 380872 P 9402 M Make concrete landing at west door level with interior of portable
371242 10/29/2015 380868 P 9406 M Make concrete landing at north door level with interior of portable
318956 10/29/2015 266441 P 9831 M Repair emergency lighting
371051 10/29/2015 380454 P 9307 O Provide certification that residential couch meets required California TB 117 flame spread rating or remove and prohibit residential furniture
371049 02/20/2015 380449 1 0000 M Repair fire extinguisher cabinet in corridor adjacent to 1-196
371039 02/20/2015 380430 1 0000 M Repair light in exit sign in corridor adjacent to 1-110
371040 02/20/2015 380432 1 0000 M Repair fire extinguisher cabinet in corridor adjacent to 1-198B
371233 02/20/2015 380850 1 0000 M Repair damaged fire extinguisher cabinet in corridor adjacent to 1-198D
371074 02/20/2015 380507 1 0000 M Repair light in exit sign in corridor between 1-182 and 1-199L
371228 02/20/2015 380839 1 0000 M Repair lights in exit signs in corridor at 1-140 and 1-142
371226 02/20/2015 380833 1 101 M Repair lights in exit signs (x2)
371046 02/20/2015 380443 1 120 M Repair lights in exit signs (x3)
371044 02/20/2015 380439 1 124A M Repair light in exit sign
371043 02/20/2015 380437 1 125 M Determine cause of water damaged ceiling tiles and replace tiles
371042 02/20/2015 380435 1 126 M Determine cause of water damaged ceiling tiles and replace tiles
371231 02/20/2015 380846 1 146 M Determine cause of water damaged ceiling tiles and replace tiles
371232 02/20/2015 380848 1 152A M Replace missing floor tile
371234 02/20/2015 380852 1 155 M Determine cause of water damaged ceiling tiles and replace tiles
371097 02/20/2015 380559 1 156 M Adjust door closer to control speed of closing door
371235 02/20/2015 380854 1 160 M Adjust door closer to control speed of closing door
371201 02/20/2015 380780 1 164 M Determine cause of water damaged ceiling tiles and replace tiles
371223 02/20/2015 380826 1 165 M Repair or replace damaged SW corridor door
371224 02/20/2015 380829 1 166 M Update and correctly label all circuits on electrical panel KPP1A
371086 02/20/2015 380538 1 170 M Repair light in exit sign
371085 02/20/2015 380536 1 170A M Repair exterior door to close and latch properly
371081 02/20/2015 380524 1 172 M Repair exterior door to close and latch properly
371073 02/20/2015 380505 1 179 M Adjust exterior door to close and latch properly
371071 02/20/2015 380501 1 179D M Remove malfunctioning kiln
371072 02/20/2015 380503 1 181 M Adjust door closer on exterior door to control speed of closing door
371070 02/20/2015 380499 1 181 M Repair door into 1-179C to close and latch properly
371069 02/20/2015 380497 1 183 M Adjust door closer to control speed of closing door, repair damaged door
371068 02/20/2015 380495 1 185A M Determine cause of water damaged ceiling tiles and replace tiles
371047 02/20/2015 380445 1 198A M Repair damaged ceiling, paint is peeling
371082 02/20/2015 380528 1 199I M Replace bulbs in light fixture
371050 02/20/2015 380451 1 199P M Repair door to close and latch properly
348008 02/20/2015 329924 1 199R M Provide covers on 4 open valve actuator motor boxes
371197 02/20/2015 380772 2 101 M Replace missing base on south wall and at NW exterior doors
371198 02/20/2015 380774 2 101 M Repair fire extinguisher cabinet on SE wall
371199 02/20/2015 380776 2 103B M Determine cause of water damaged ceiling tiles and replace tiles
371103 02/20/2015 380564 2 105A M Replace missing signage at exterior door indicating room name and number at appropriate height with raised and Braille characters
371219 02/20/2015 380820 2 105E M Secure loose data outlet box
371060 02/20/2015 380475 3 0000 M Secure loose fence rails for fence enclosure at 3-101
371095 02/20/2015 380555 3 101 M Repair door to close and latch properly
371061 02/20/2015 380477 P 3683 M Adjust door closer on ramp door to control speed of closing door
371062 02/20/2015 380479 P 3683 M Repair or replace deteriorated wood siding
371065 02/20/2015 380489 P 3683 M Provide bottom rail on stair landing guardrail at 2 inches above floor
371243 02/20/2015 380870 P 3760 M Repair emergency lighting at north door
371245 02/20/2015 380874 P 3760 M Provide bottom rail on stair landing guardrail at 2 inches above floor
371254 02/20/2015 380892 P 6453 M Repair emergency lighting at west door
371255 02/20/2015 380894 P 6454 M Repair emergency lighting at west door
371256 02/20/2015 380896 P 6455 M Repair emergency lighting at west door
371257 02/20/2015 380899 P 6458 M Provide thumb latches on bathroom door to enable door to be unlocked from the outside without the use of a special tool
371258 02/20/2015 380901 P 6458 M Repair emergency lighting
371252 02/20/2015 380888 P 6458 M Repair emergency lighting
371253 02/20/2015 380890 P 6458 M Repair door to close and lock properly
371063 02/20/2015 380482 P 9276 M Adjust door closer on exterior door to control speed of closing door
371066 02/20/2015 380491 P 9279 M Repair damaged flooring at mate line
371067 02/20/2015 380493 P 9280 M Repair emergency lighting at south door
371057 02/20/2015 380466 P 9304 M Repair emergency lighting at north door
371058 02/20/2015 380468 P 9304 M Adjust door closer on south door to control speed of closing door
371056 02/20/2015 380464 P 9305 M Adjust door closer on entrance door to control speed of closing door
371053 02/20/2015 380458 P 9305 M Repair emergency lighting at south door
371054 02/20/2015 380460 P 9305 M Repair damaged flooring at mate line
371052 02/20/2015 380456 P 9306 M Repair south door to close and latch properly
371240 02/20/2015 380864 P 9310 M Repair emergency lighting at north door
371238 02/20/2015 380860 P 9311 M Repair emergency lighting at north door
371239 02/20/2015 380862 P 9311 M Repair north door to close and latch properly
371247 02/20/2015 380878 P 9404 M Repair north door to close and latch properly
371246 02/20/2015 380876 P 9405 M Repair or replace rusty, damaged north door
371249 02/20/2015 380882 P 9831 M Repair emergency lighting at west door
371250 02/20/2015 380884 P 9832 M Repair emergency lighting at east door
371251 02/20/2015 380886 P 9832 M Repair west door to close and latch properly
371227 02/20/2015 380837 1 140 O Maintain clear access to emergency eye wash - shower
371236 02/20/2015 380856 1 160 O Prohibit orange 13A extension cord or replace with minimum 15A single outlet extension cord
371221 02/20/2015 380822 1 164F O Replace bulbs in light fixture
371078 02/20/2015 380515 1 172A O Store chemicals properly on shelves with one half inch lip in vented, designated chemical storage room
371076 02/20/2015 380512 1 198F O Prohibit charging batteries (floor cleaning machine) in room
371055 02/20/2015 380462 P 9305 O Prohibit plugging surge protector into multi outlet electrical box, plug surge protector directly into permanent electrical outlet
371241 02/20/2015 380866 P 9407 O Prohibit plugging surge protector into surge protector at computers
371089 02/20/2015 380541 00 0000 C Provide bollards around gas lines at 1-199S and 2-192
371225 02/20/2015 380831 1 0000 MS Adjust fire doors at 1-161 to latch properly
371045 02/20/2015 380441 1 123 MS Provide current inspection tag for fire extinguisher
371084 02/20/2015 380531 1 170 MS Provide current inspection tag for fire extinguisher on east wall
371106 02/20/2015 380577 1 197A,B MS Provide thumb latches on bathroom doors to enable doors to be unlocked from the outside without the use of a special tool
371202 02/20/2015 380782 1 164 OS Maintain clear aisle to exterior exit door
371200 02/20/2015 380778 1 164A OS Prohibit storage on ramp to maintain clear aisle to exit
371094 02/20/2015 380550 1 198K OS Prohibit storage of gas powered leaf blowers
371091 02/20/2015 380545 1 198L OS Prohibit storage of gas powered pressure cleaner
371248 02/20/2015 380880 P 9403 OS Maintain clear aisle to north exit
324833 10/31/2014 279857 1 170 M Adjust fire sprinkler head so deflector projects a minimum 1 inch below escutcheon in band room
348007 10/31/2014 329922 1 199R M Replace belt guard for outside air intake motor at door
347940 10/31/2014 329778 P 3760 M Replace rotted wood siding at north windows and east end
360330 10/31/2014 357188 P 9831 M Repair damaged wall finish (peeling paint) on exterior wall at entrance door
360331 10/31/2014 357190 P 9831 M Replace damaged, missing louvers for AC intake
371048 10/31/2014 380447 1 130 O Provide certification that residential couch meets required California TB 117 flame spread rating or remove and prohibit residential furniture
360360 03/26/2014 357252 1 0000 M Repair light in exit sign in corridor adjacent to 1-195
360296 03/26/2014 357118 1 0000 M Repair light in exit sign in corridor adjacent to 1-105
360293 03/26/2014 357112 1 0000 M Replace missing cover on exit sign in corridor NE of media center
347932 03/26/2014 329760 1 0000 M Provide finish on smoke stop doors in corridor adjacent to main entry to 1-120
360325 03/26/2014 357178 1 120 M Repair light in exit sign at west exit
360326 03/26/2014 357180 1 120 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to 1-125
360327 03/26/2014 357182 1 126 M Determine cause of water damaged ceiling tiles and replace tiles
360132 03/26/2014 356768 1 134 M Replace missing drain cover for drain at emergency eye wash - shower
360135 03/26/2014 356774 1 146 M Adjust door closer to control speed of closing door
360137 03/26/2014 356778 1 152B M Determine cause of water damaged ceiling tiles and replace tiles
360138 03/26/2014 356780 1 156 M Adjust door closer to control speed of closing door
360139 03/26/2014 356782 1 157 M Adjust door closer to control speed of closing door
360141 03/26/2014 356786 1 158 M Adjust door closer to control speed of closing door
360140 03/26/2014 356784 1 159 M Repair door to open and close properly, repair loose hinge plate
360142 03/26/2014 356788 1 160 M Adjust door closer to control speed of closing door
360143 03/26/2014 356790 1 160A M Replace missing escutcheon on fire sprinkler head
348106 03/26/2014 330135 1 162 M Label emergency gas disconnect valve at teachers station
360145 03/26/2014 356794 1 164 M Determine cause of water damaged ceiling tiles and replace tiles
347934 03/26/2014 329765 1 164 M Replace plastic zip ties on lighting fixtures with safety cables
360149 03/26/2014 356802 1 164A M Adjust door closer on ramp door for 1-165 to control speed of closing door
360151 03/26/2014 356809 1 165 M Replace missing maximum occupancy sign (occupancy is 444)
360162 03/26/2014 356833 1 166 M Provide updated panel schedule for electrical panel KPP1A
360161 03/26/2014 356831 1 166A M Replace missing protective cover for outlet on wall adjacent to door
360159 03/26/2014 356827 1 166G M Adjust door of walk in freezer to close and latch properly
360152 03/26/2014 356811 1 169 M Adjust door closers on corridor and exterior doors to control speed of closing doors
360153 03/26/2014 356813 1 169 M Determine cause of water damaged ceiling tiles and replace tiles
360304 03/26/2014 357135 1 175A M Connect dryer duct to back of clothes dryer
360309 03/26/2014 357145 1 176 M Determine cause of water damaged ceiling tiles and replace tiles
360305 03/26/2014 357137 1 177 M Adjust door closer on corridor door to control speed of closing door
360306 03/26/2014 357139 1 178 M Adjust door closer on corridor door to control speed of closing door
360308 03/26/2014 357143 1 178 M Determine cause of water damaged ceiling tiles and replace tiles
360303 03/26/2014 357132 1 181 M Adjust door closer to control speed of closing door
360301 03/26/2014 357128 1 181A M Mount sign for emergency eye wash adjacent to 1-181A sign
360302 03/26/2014 357130 1 181A M Adjust flow of emergency eye wash
360290 03/26/2014 357106 1 183 M Adjust door closer on corridor door to control speed of closing door
360300 03/26/2014 357126 1 185A M Determine cause of water damaged ceiling tiles and replace tiles
360299 03/26/2014 357124 1 191 M Adjust door closer to control speed of closing door
360297 03/26/2014 357120 1 196 M Repair light in exit sign
360312 03/26/2014 357151 1 198E M Repair or replace rusty hot water heater
360281 03/26/2014 357085 1 198F M Repair door to close properly, rubs on frame
360288 03/26/2014 357101 1 198F M Secure loose electrical outlet cover
360155 03/26/2014 356817 1 198L M Repair door to close and latch properly
360295 03/26/2014 357116 1 199 M Replace bulbs in light fixture
360294 03/26/2014 357114 1 199C M Repair loose door handle
360292 03/26/2014 357110 1 199D M Repair door to close and latch properly
360148 03/26/2014 356800 1 199H M Adjust door closer to control speed of closing door
360279 03/26/2014 357082 1 199P M Repair door to close and latch properly
360154 03/26/2014 356815 1 199R M Repair door to open and close properly
360157 03/26/2014 356822 1 199S M Provide certification that all student occupied spaces have emergency lights and all are operable, certificate is expired
360158 03/26/2014 356825 1 199T M Replace missing cover plate on hot water heater
360271 03/26/2014 357067 2 0000 M Clean rain gutters for building 2
360328 03/26/2014 357184 P 6452 M Repair emergency lighting at entrance door
360329 03/26/2014 357186 P 6452 M Adjust door closer on west door to control speed of closing door
360333 03/26/2014 357194 P 6453 M Repair emergency lighting at entrance door
360334 03/26/2014 357196 P 6453 M Adjust door closer on west (rear) door to control speed of closing door
360336 03/26/2014 357200 P 6453 M Determine cause of water damaged ceiling tiles and replace tiles
360338 03/26/2014 357205 P 6454 M Adjust door closer on entrance door to control speed of closing door
360339 03/26/2014 357207 P 6454 M Repair emergency lighting at east (rear) door
360340 03/26/2014 357209 P 6456 M Repair emergency lighting (x2)
360341 03/26/2014 357211 P 6457 M Repair emergency lighting at entrance door
360342 03/26/2014 357213 P 6458 M Adjust door closer on girls bathroom door to control speed of closing door
360317 03/26/2014 357162 P 9276 M Adjust door closer on rear door to control speed of closing door
360314 03/26/2014 357155 P 9281 M Repair emergency lighting (x2)
360324 03/26/2014 357176 P 9304 M Repair south (rear) door to close properly
360323 03/26/2014 357174 P 9305 M Repair damaged flooring
360320 03/26/2014 357168 P 9306 M Repair emergency lighting at south (rear) door
360321 03/26/2014 357170 P 9306 M Repair south (rear) door to close and latch properly
360353 03/26/2014 357238 P 9308 M Repair emergency lighting (x2)
360354 03/26/2014 357240 P 9308 M Adjust door closer on north door to control speed of closing door
360355 03/26/2014 357242 P 9309 M Anchor shelving (adjacent to door) to wall
360356 03/26/2014 357244 P 9310 M Repair emergency lighting
360357 03/26/2014 357246 P 9310 M Adjust door closer on rear (north) door to control speed of closing door
360359 03/26/2014 357250 P 9311 M Repair rear (north) door to close and latch properly
360343 03/26/2014 357215 P 9403 M Adjust door closer on rear door to control speed of closing door
360345 03/26/2014 357219 P 9404 M Anchor shelving (located adjacent to window) to wall
360346 03/26/2014 357221 P 9404 M Secure cover on exhaust fan in bathroom
360347 03/26/2014 357223 P 9405 M Repair deteriorated wall finish under white board on west wall
360350 03/26/2014 357231 P 9406 M Secure loose base on west wall
360351 03/26/2014 357233 P 9407 M Repair emergency lighting at rear (north) door
360352 03/26/2014 357236 P 9407 M Adjust door closer on rear (north) to control speed of closing door
360332 03/26/2014 357192 P 9833 M Adjust door closer on entrance door to control speed of closing door
360133 03/26/2014 356770 1 136D O Prohibit plugging surge protector into orange extension cord
360134 03/26/2014 356772 1 140 O Prohibit use of 13A extension cords (white, brown) use 15A single outlet extension cords or surge protectors
360136 03/26/2014 356776 1 152A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
360144 03/26/2014 356792 1 162 O Prohibit use of multi outlet electrical adaptor box on wall at 1-160A
360150 03/26/2014 356804 1 168 O Prohibit plugging chilled salad serving table into surge protector - plug directly into permanent electrical outlet
360310 03/26/2014 357147 1 172 O Prohibit use of brown 13A extension cord adjacent to teachers desk or replace with minimum 15A single outlet extension cord
360307 03/26/2014 357141 1 178 O Prohibt use of (flammable) purple plastic table skirt
360298 03/26/2014 357122 1 193 O Prohibit plugging surge protector into surge protector at west power poles
360289 03/26/2014 357104 1 198F O Prohibit charging batteries in room
360349 03/26/2014 357227 P 3760 O Prohibit plugging surge protector into surge protector
360337 03/26/2014 357203 P 6453 O Prohibit plugging surge protector into green extension cord at teachers computer, plug surge protector directly into permanent electrical outlet
360335 03/26/2014 357198 P 6453 O Prohibit use of brown 13A extension cord adjacent to teachers desk or replace with minimum 15A single outlet cord
360318 03/26/2014 357164 P 9276 O Prohibit plugging surge protector into surge protector
360315 03/26/2014 357158 P 9280 O Prohibit use of multi outlet electrical adaptor behind refrigerator
360322 03/26/2014 357172 P 9305 O Prohibit plugging microwave into multi outlet electrical adaptor, plug directly into permanent electrica outlet
360319 03/26/2014 357166 P 9306 O Prohibit use of multi outlet electrical adaptor adjacent to hole punch
360358 03/26/2014 357248 P 9311 O Prohibit plugging surge protector into surge protector
360344 03/26/2014 357217 P 9402 O Prohibit plugging surge protector into surge protector adjacent to computers
360348 03/26/2014 357225 P 9405 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
360156 03/26/2014 356820 00 0000 C Provide placard indicating in ground LP tanks adjacent to chillers on SW side of Bldg. 1
360277 03/26/2014 357080 1 8088 C Provide bollards around gas line on north exterior wall of 1-163
348047 03/26/2014 330007 P 0000 C Modify or improve storm drainage from portables P-1-11 and P-14-21 to prevent storm water from going under units
360160 03/26/2014 356829 1 189 MS Provide current inspection tag for fire extinguisher
360291 03/26/2014 357108 1 189 MS Provide current inspection tag for fire extinguisher
360147 03/26/2014 356798 1 199H MS Provide current inspection tag for fire extinguisher
360272 03/26/2014 357069 2 101 MS Recharge fire extinguisher adjacent to SE door
360313 03/26/2014 357153 1 162 OS Prohibit hold open devices on fire doors
360146 03/26/2014 356796 1 164G OS Provide clear access to fire extinguisher
360311 03/26/2014 357149 1 9698 OS Prohibit parking cars adjacent to exterior door of 1-172 to maintain clear aisle to exit
360316 03/26/2014 357160 P 9277 OS Maintain clear aisle to (rear) exit
347960 12/06/2013 329825 1 138A M Provide schedule for electrical panel LPP3D
348082 12/06/2013 330086 1 146 M Adjust rear door to latch properly
348105 12/06/2013 330133 1 160A M Repair emergency exhaust fan. Switch turned and fan does not come on
347931 12/06/2013 329758 1 164A M Repair light in exit sign
348045 12/06/2013 330003 1 173 M Repair or replace damaged laminate on countertop
348056 12/06/2013 330027 1 198A M Repair non-working ventilation fan
347936 12/06/2013 329769 1 199G M Provide cover on open damper actuator box on AHU-6
348052 12/06/2013 330019 1 199K M Provide cover on open damper actuator box on OAU-4
348041 12/06/2013 329995 1 199S M Provide schedules for electrical panels LDP1 and HEP1
348103 12/06/2013 330129 2 0000 M Seal open expansion joints on exterior brick
348017 12/06/2013 329943 P 9402 M Replace missing epoxy flooring in bathroom
347926 12/06/2013 329748 1 131 O Maintain clear access to emergency eye wash - shower
347946 12/06/2013 329794 1 175A O Remove rags behind washer and dryer
348086 12/06/2013 330093 1 180A O Prohibit plugging microwave oven into extension cord - plug directly into permanent electrical outlet and eliminate non 15 amp multiple outlet extension cord
347999 12/06/2013 329905 1 182A O Provide clear access to electrical panel
348039 12/06/2013 329990 1 185 O Eliminate multiple outlet electrical adapter. Plug refrigerator directly into wall electrical outlet
347977 12/06/2013 329860 P 9280 O Provide clear access to electrical panel
347993 12/06/2013 329892 P 9306 O Provide clear access to electrical panel
348079 12/06/2013 330078 1 150 C Provide illuminated exit signs and panic hardware on both doors or limit occupancy to 49 maximum. Max occupancy sign reads 133 (corrected Dec. 2013 Max Occ changed to 49)
348050 12/06/2013 330014 1 172 OS Maintain 3 foot clear aisle to rear exit
347998 12/06/2013 329902 1 177B OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
347945 12/06/2013 329792 1 198F OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
348010 12/06/2013 329929 1 198L OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
347975 12/06/2013 329856 P 9279 OS Relocate bookshelf to maintain 3 foot clear aisle to rear exit
347979 12/06/2013 329864 P 9281 OS Maintain clear aisle to rear exit
348013 12/06/2013 329935 P 9310 OS Maintain clear aisle to rear exit
348016 12/06/2013 329941 P 9402 OS Maintain clear aisle to rear exit
348027 12/06/2013 329964 P 9406 OS Maintain clear aisle to rear exit
348030 12/06/2013 329970 P 9407 OS Maintain clear aisle to rear exit
348051 05/01/2013 330017 00 0000 M Replace cleanout cover for storm drain outside of 1-138. Damaged by lawnmower
348108 05/01/2013 330139 00 0000 M Install cap on fire department standpipe connection between building 2 and portables
348109 05/01/2013 330141 00 0000 M Repair gate to latch properly. Latch on panic bar not secure. Pulling on gate will release latch. Gate between buildings 1 and 2
348110 05/01/2013 330143 00 0000 M Provide chain and lock on gate of fencing around lift station north of 1-144
348111 05/01/2013 330145 00 0000 M Provide new lock on gate of fencing around electrical equipment adjacent to P-7
348054 05/01/2013 330023 1 0000 M Secure loose fire extinguisher cabinet in corridor adjacent to 1-194
347958 05/01/2013 329820 1 131 M Label emergency electrical disconnect switch
347957 05/01/2013 329818 1 134 M Label emergency electrical disconnect switch
347956 05/01/2013 329816 1 136 M Label emergency electrical disconnect switch
347955 05/01/2013 329814 1 140 M Label emergency electrical disconnect switch
347950 05/01/2013 329803 1 144 M Label emergency electrical disconnect switch
348059 05/01/2013 330033 1 144B M Replace GFCI outlet that will not trip
347962 05/01/2013 329830 1 154C M Determine cause of water damaged ceiling tiles and replace tiles
347949 05/01/2013 329801 1 158 M Label emergency electrical disconnect switch
347948 05/01/2013 329799 1 160 M Label emergency electrical disconnect switch
348104 05/01/2013 330131 1 164 M Paint warning stripe along edge of exterior stage
348089 05/01/2013 330100 1 165A M Repair leaking supply line for toilet 2 and low urinal
348087 05/01/2013 330095 1 165B M Anchor toilet to floor
347930 05/01/2013 329756 1 166 M Provide schedule for electrical panel KPP1B
348042 05/01/2013 329997 1 170A M Repair light in exit sign
348043 05/01/2013 329999 1 171 M Caulk sinks to countertop
348044 05/01/2013 330001 1 173 M Caulk sinks to countertop
348046 05/01/2013 330005 1 173 M Replace broken seat on handicapped toilet
348001 05/01/2013 329909 1 175A M Secure loose door handle on door to 1-177
347988 05/01/2013 329882 1 177 M Replace damaged GFCI outlet at west sink
347989 05/01/2013 329884 1 177 M Secure loose faucet on 2nd sink from east
347990 05/01/2013 329886 1 177 M Replace 2 GFCI outlets at east sink-kitchen
347991 05/01/2013 329888 1 177 M Label emergency electrical disconnect switch
348084 05/01/2013 330090 1 178 M Determine cause of water damaged ceiling tiles and replace tiles
348004 05/01/2013 329915 1 179 M Label emergency electrical disconnect switch
348003 05/01/2013 329913 1 180 M Label emergency electrical disconnect switch. No dissconect in room, wrong room number
348005 05/01/2013 329917 1 181 M Label emergency electrical disconnect switch
348077 05/01/2013 330074 1 185C M Anchor and caulk toilet
348011 05/01/2013 329931 1 190 M Repair GFCI outlets, no power to them
348002 05/01/2013 329911 1 190 M Label emergency electrical disconnect switch
348048 05/01/2013 330009 1 198M M Repair door hardware. Latch will not retract and door cannot be opened
348064 05/01/2013 330047 1 199B M A piece of flat aluminum has been screwed to the door frame inside of room. Remove it
348040 05/01/2013 329992 1 199E M Determine cause of water damaged ceiling tiles and replace tiles
347937 05/01/2013 329771 1 199G M Repair leaking air handler AHU-5
347929 05/01/2013 329754 1 199H M Provide schedule for electrical panel HLP4
348075 05/01/2013 330071 1 199L M Provide schedule for electrical panel LDP2
348009 05/01/2013 329927 1 199R M Repair door lock on door to 1-199S. Construction pin may be in cylinder
348006 05/01/2013 329920 1 199S M Provide certification that all student occupied spaces have emergency lights and all are operable. Last certification 1/2011
348092 05/01/2013 330107 2 101 M Replace GFCI outlet at drinking fountain adjacent to girls locker room door that will not trip
348097 05/01/2013 330117 2 103A M Adjust rear door to latch properly
347961 05/01/2013 329828 2 103F M Anchor 2nd toilet to floor
348098 05/01/2013 330119 2 105 M Secure loose door handle
348100 05/01/2013 330123 2 105A M Repair light in exit sign at rear door
348101 05/01/2013 330125 2 105A M Secure loose spout for drinking fountain
348099 05/01/2013 330121 2 105B M Anchor loose toilet partition between sink and 1st toilet
347953 05/01/2013 329809 2 191 M Provide schedules for electrical panels HLP5, HDP5, LPP5A and LPP5
348091 05/01/2013 330105 2 193 M Eliminate wasps above louver inside room
348000 05/01/2013 329907 P 0000 M Provide chain and lock on gate of fencing around fire main adjacent to P-8
347987 05/01/2013 329880 P 0000 M Provide chain and lock on gate of fencing around electrical equipment adjacent to P-22
347935 05/01/2013 329767 P 3683 M Provide covers on exposed electrical junction boxes under ramp
347938 05/01/2013 329773 P 3760 M Repair emergency lighting
347939 05/01/2013 329775 P 3760 M Adjust both doors to latch properly
347941 05/01/2013 329781 P 6453 M Remove pencil sharpener without cover adjacent to entry
347964 05/01/2013 329834 P 6458 M Repair emergency lighting in mens and womens single bathrooms
347965 05/01/2013 329836 P 6458 M Repair toilet 3 in girls bathroom, not working
347967 05/01/2013 329840 P 9276 M Exterior junction boxes are in contact with ground. Remove dirt from under boxes so that they do not contact ground
347968 05/01/2013 329842 P 9276 M Provide cover on exposed electrical junction box at exterior
347969 05/01/2013 329844 P 9277 M Adjust rear door to latch properly
347970 05/01/2013 329846 P 9277 M Provide cover on 2 exposed electrical junction boxes at exterior
347972 05/01/2013 329850 P 9277 M Exterior junction boxes are in contact with ground. Remove dirt from under boxes so that boxes do not contact ground
347973 05/01/2013 329852 P 9278 M Remove damaged pencil sharpener at rear door
347974 05/01/2013 329854 P 9278 M Adjust rear door to latch properly
347976 05/01/2013 329858 P 9279 M Exterior junction boxes are in contact with ground. Remove dirt from under boxes so that they do not contact ground
347980 05/01/2013 329866 P 9281 M Adjust rear door to latch properly
347981 05/01/2013 329868 P 9281 M Provide cover on exposed electrical junction box at exterior
347983 05/01/2013 329872 P 9304 M Adjust rear door to latch properly
347984 05/01/2013 329874 P 9305 M Adjust rear door to latch properly
347985 05/01/2013 329876 P 9305 M Provide cover on exposed electrical junction box at exterior
347994 05/01/2013 329894 P 9307 M Repair emergency lighting at front of room
347995 05/01/2013 329896 P 9307 M Remove damaged pencil sharpener at entry
348012 05/01/2013 329933 P 9309 M Adjust rear door to latch properly
348014 05/01/2013 329937 P 9310 M Repair rear door to open and close properly, adjust closer
348018 05/01/2013 329946 P 9403 M Replace missing base along wall in bathroom
348021 05/01/2013 329952 P 9405 M Provide schedule for electrical panel
348022 05/01/2013 329954 P 9405 M Remove damaged pencil sharpener at rear door
348024 05/01/2013 329958 P 9405 M Adjust rear door to latch properly
348025 05/01/2013 329960 P 9406 M Install KO seal in top of exterior junction box
348026 05/01/2013 329962 P 9406 M Caulk sink to wall in bathroom
348031 05/01/2013 329972 P 9407 M Adjust rear door to latch properly
348032 05/01/2013 329974 P 9407 M Secure loose base along wall in bathroom
348033 05/01/2013 329976 P 9407 M Seal wall at sink to provide impervious wall finish in bathroom
348036 05/01/2013 329983 P 9831 M Repair emergency lighting at rear door
348037 05/01/2013 329985 P 9832 M Repair emergency lighting x 2
348038 05/01/2013 329987 P 9833 M Repair emergency lighting at front door
347923 05/01/2013 329741 00 0 O No access was available to 1-164C, 1-166F, 1-166G and 1-187. Please provide access to these rooms during the report review meeting
348062 05/01/2013 330039 1 116A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
348063 05/01/2013 330041 1 116B O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
347925 05/01/2013 329745 1 130A O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
347924 05/01/2013 329743 1 133A O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
347927 05/01/2013 329750 1 136A O Provide clear access to electrical panel
347928 05/01/2013 329752 1 136D O Prohibit plugging surge protector into surge protector
348058 05/01/2013 330031 1 144A O Post sign indicating evacuation routes
347947 05/01/2013 329796 1 144B O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain and reinstall drain grate
348083 05/01/2013 330088 1 146 O Maintain clear access to emergency eye wash - shower
348107 05/01/2013 330137 1 169A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
348088 05/01/2013 330098 1 198G O Remove and prohibit storage on water heater
348095 05/01/2013 330113 2 103C O Keep shower drains filled with water. Every 2 months pour 1 quart of water down drains
348102 05/01/2013 330127 2 105E O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
348096 05/01/2013 330115 2 105F O Keep shower drains filled with water. Every 2 months pour 1 quart of water down drains
348015 05/01/2013 329939 P 9311 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
348049 05/01/2013 330011 1 172A C Provide appropriate area or room for storing chemicals
348093 05/01/2013 330109 2 103A C Provide illuminated exit sign at Gym entry
348094 05/01/2013 330111 2 105A C Provide illuminated exit sign at Gym entry
348028 05/01/2013 329966 P 9406 C Provide impervious wall finish in bathroom and if already painted with epoxy provide sign indicating when painted
348029 05/01/2013 329968 P 9407 C Provide impervious wall finish in bathroom or if already epoxy painted provide sign indicating date when painted
348053 05/01/2013 330021 1 0000 MS Adjust fire door in corridor adjacent to 1-191 to latch properly
348057 05/01/2013 330029 1 0000 MS Adjust fire door in corridor adjacent to 1-144 to latch
347933 05/01/2013 329762 1 0000 MS Provide handle for fire extinguisher cabinet in corridor adjacent to 1-165
348090 05/01/2013 330103 1 0000 MS Adjust fire doors in corridor adjacent to 1-160 to latch properly
347959 05/01/2013 329822 1 135 MS Remove paper clip from fire sprinkler head above teachers station
347942 05/01/2013 329783 P 6453 MS Provide current inspection tag for fire extinguisher
348081 05/01/2013 330084 1 148 OS Maintain clear aisle to rear exit
348080 05/01/2013 330082 1 150 OS Maintain clear aisle to west exit
347963 05/01/2013 329832 1 152A OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
347997 05/01/2013 329900 1 177A OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
348060 05/01/2013 330035 1 192A OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
348061 05/01/2013 330037 1 198 OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
347943 05/01/2013 329785 P 6453 OS Maintain clear aisle to rear exit
347966 05/01/2013 329838 P 9276 OS Maintain clear aisle to rear exit
347971 05/01/2013 329848 P 9277 OS Maintain clear aisle to rear exit
347978 05/01/2013 329862 P 9280 OS Maintain clear aisle to rear exit
347982 05/01/2013 329870 P 9281 OS Maintain 3 foot clear aisle to front exit
347986 05/01/2013 329878 P 9305 OS Relocate chairs to maintain clear aisle to rear exit
347992 05/01/2013 329890 P 9306 OS Maintain clear aisle to rear exit
347996 05/01/2013 329898 P 9308 OS Maintain clear aisle to rear exit
348019 05/01/2013 329948 P 9403 OS Maintain clear aisle to rear exit
348020 05/01/2013 329950 P 9404 OS Maintain clear aisle to rear exit
348023 05/01/2013 329956 P 9405 OS Maintain clear aisle to rear exit
348034 05/01/2013 329978 P 9831 OS Maintain clear aisle to rear exit. Exit sign removed, ESE room
347944 05/01/2013 329789 1 198F CS Provide auto closer on door
348035 05/01/2013 329980 P 9831 FS Secure hanging heat detector in closet-bathroom
324837 01/03/2013 279865 1 179 M Adjust patio door to latch properly
324820 01/03/2013 279828 1 0000 C Provide evacuation route maps which indicate primary and secondary evacuation routes from classrooms (current maps only show hand drawn primary routes, no secondary routes)
324829 01/03/2013 279849 1 164 C Provide records that stage rigging has been inspected and conforms to required safety standards
324840 11/29/2011 279871 00 0000 M Install cap on fire department standpipe connection on east side of P-12
324849 11/29/2011 279889 00 0000 M Replace missing wrench on Post Indicator Valve on south side of Building 1 adjacent to 1-199P
324823 11/29/2011 279837 1 144 M Determine cause of water damaged ceiling tiles and replace tiles
324824 11/29/2011 279839 1 146 M Adjust exterior exit door to close properly
324828 11/29/2011 279847 1 164B M Repair damaged floor tile in girls dressing room
324830 11/29/2011 279851 1 165 M Replace missing ceiling tile at northeast exterior exit door of cafeteria
324831 11/29/2011 279853 1 166 M Repair exterior exit door adjacent to dishwashing room to close properly (door drags on jamb)
324822 11/29/2011 279835 1 198C M Close ceiling hatch in janitors closet
324832 11/29/2011 279855 1 198M M Replace missing escutcheon on fire sprinkler head
324843 11/29/2011 279877 2 103E M Secure hanging lens on light fixture in first shower stall
324842 11/29/2011 279875 2 107 M Repair or replace damged air conditioner vent grill
324841 11/29/2011 279873 3 101 M Repair door to open and close properly (drags on concrete slab)
324848 11/29/2011 279887 P 6452 M Repair emergency lighting at rear door
324852 11/29/2011 279895 P 9279 M Repair auto closer on front door (closer arm is not attached to door)
324851 11/29/2011 279893 P 9280 M Adjust rear door to latch properly
324850 11/29/2011 279891 P 9281 M Adjust rear door to latch properly
324844 11/29/2011 279879 P 9311 M Repair emergency lighting at front door
324847 11/29/2011 279885 P 9404 M Repair loose vinyl base along wall at rear door
324854 11/29/2011 279899 00 0000 O Prohibit vehicle parking on grass area east of P-1
324817 11/29/2011 279824 1 124A O Prohibit plugging surge protector into surge protector at computer table
324816 11/29/2011 279816 1 130A O Prohibit plugging microwave oven and refrigerator into surge protector - plug directly into permanent electrical outlet
324835 11/29/2011 279861 1 133 O Remove and prohibit flammable decorations from ceilings or windows
324825 11/29/2011 279841 1 158 O Remove and prohibit flammable decorations hanging from ceilings or windows
324826 11/29/2011 279843 1 162 O Remove and prohibit flammable decorations from ceilings or windows
324838 11/29/2011 279867 1 190 O Remove and prohibit flammable decorations from ceilings or windows
324853 11/29/2011 279897 P 9304 O Prohibit plugging microwave oven and refrigerator into surge protector - plug directly into permanent electrical outlet
324845 11/29/2011 279881 P 9310 O Prohibit plugging microwave oven and refrigerator into surge protector - plug directly into permanent electrical outlet
324846 11/29/2011 279883 P 9310 O Prohibit use of plug in air freshners
324836 11/29/2011 279863 P 0000 C Provide impervious wall finish in bathrooms of portables
324839 11/29/2011 279869 1 0000 MS Adjust fire door in corridor adjacent to 1-192 to close and latch properly
324827 11/29/2011 279845 1 198J MS Recharge fire extinguisher
324834 11/29/2011 279859 1 0000 OS Remove storage from exterior courtyard exit adjacent to 1-167
324821 11/29/2011 279833 1 0000 OS Prohibit hold open devices (wedges) on corridor doors of classrooms
318837 03/24/2011 266168 1 0000 M Replace missing escutcheon on fire sprinkler head in corridor east of 1-120
318818 03/24/2011 266128 1 0000 M Adjust fire doors adjacent to 1-176 door to close properly
318842 03/24/2011 266179 1 130A M Repair electrical outlet, grounding plug is broken off in outlet
318839 03/24/2011 266172 1 136D M Replace missing ceiling tiles
318835 03/24/2011 266163 1 144 M Determine cause of water damaged ceiling tiles and replace tiles
318831 03/24/2011 266155 1 155 M Determine cause of water damaged ceiling tiles and replace tiles
318832 03/24/2011 266157 1 155 M Exterminate ants in classroom, see teacher for location
318829 03/24/2011 266151 1 158 M Replace ceiling tile with hole in it
318828 03/24/2011 266149 1 162 M Repair emergency power shut off button. Teacher states that emergency power button also used to operate a purge fan. Verify proper function of purge fan and locaton of fan on/off button
318824 03/24/2011 266141 1 173 M Patch hole in ceiling
318816 03/24/2011 266125 1 177 M Determine cause of water damaged ceiling tiles and replace tiles
318836 03/24/2011 266166 1 199B M Repair light fixture, lights do not work
318834 03/24/2011 266161 1 199G M Fill void in electrical panel HPP3
318826 03/24/2011 266145 1 199I M Provide panel schedule for electrical panel HLP1
318851 03/24/2011 266198 1 199S M Adjust exterior door to close properly
318940 03/24/2011 266407 1 199S M Provide certification that all student occupied spaces have emergency lights and all are operable, inspection certificate is expired
318944 03/24/2011 266417 2 101 M Provide cover on exposed electrical junction boxes on north wall
318947 03/24/2011 266423 2 103B M Determine cause of water damaged ceiling tiles and replace tiles
318946 03/24/2011 266420 2 104 M Anchor toilet to floor
235693 03/24/2011 17480 2 193 M Provide state certification for boiler or verify BTU output of heater is less than 400,000
318961 03/24/2011 266452 P 3683 M Repair emergency lighting
318957 03/24/2011 266444 P 6456 M Repair emergency lighting
318958 03/24/2011 266446 P 9304 M Repair rear door to close properly
318959 03/24/2011 266448 P 9305 M Repair emergency lighting
318848 03/24/2011 266192 P 9308 M Repair door to close properly
318846 03/24/2011 266188 P 9309 M Repair emergency lighting
318847 03/24/2011 266190 P 9309 M Repair door to close/latch properly
318849 03/24/2011 266194 P 9407 M Secure sink to wall in bathroom
318830 03/24/2011 266153 1 159 O Prohibit white 13A extension cord or replace with minimum 15A cord
318827 03/24/2011 266147 1 168 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
318825 03/24/2011 266143 1 169 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
318823 03/24/2011 266139 1 172B O Relocate flammable storage cabinet to allow door to close
318812 03/24/2011 266115 1 185 O Prohibit white 13A extension cord plugged into surge protector @ teacher's desk. 15A single outlet extension cord plugged directly into a permanent electrical outlet is permitted
318949 03/24/2011 266426 2 105E O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
318954 03/24/2011 266436 P 9405 O Prohibit plugging microwave into surge protector box on wall- plug directly into permanent electrical outlet
318955 03/24/2011 266439 P 9405 O Prohibit plugging surge protector into surge protector box mounted on wall
318792 03/24/2011 266077 00 0000 C Provide exterior signage indicating property address
318820 03/24/2011 266132 1 172B C Verify that room has adequate ventilation for storage of chemicals (N/A, room is not acceptable, school is moving cabinets to flammable storage room until proper storage area is identified or provided)
318833 03/24/2011 266159 1 198D C Provide auto closer on door
318808 03/24/2011 266107 1 0000 MS Recharge fire extinguisher in corridor adjacent to 1-192
318838 03/24/2011 266170 1 0000 MS Adjust fire doors in corridor adjacent to 1-142 to latch properly
318841 03/24/2011 266177 1 135 MS Provide current inspection tag for fire extinguisher
318815 03/24/2011 266123 1 186 MS Repair auto closer on fire door
318845 03/24/2011 266186 1 198L MS Provide current inspection tag for fire extinguisher, mount fire extinguisher
318943 03/24/2011 266410 2 101 MS Recharge fire extinguisher adjacent to NE exit doors
318950 03/24/2011 266429 P 3760 MS Recharge fire extinguisher
318844 03/24/2011 266183 1 170 OS Remove and prohibit sign reading "Do not open door" hanging on exit door. Sign may read "Emergency Exit Only"
318843 03/24/2011 266181 1 170A OS Remove and prohibit sign reading "Do not open door" hanging on exit door. Sign may read "Emergency Exit Only"
318814 03/24/2011 266121 1 181 OS Maintain clear aisle to exterior exit
318813 03/24/2011 266119 1 190 OS Prohibit hold open devices on fire door
318810 03/24/2011 266112 1 191 OS Prohibit hold open devices on fire door
318840 03/24/2011 266175 1 198A OS Prohibit storage of flammable materials (WD-40)
318963 03/24/2011 266456 P 9276 OS Maintain clear aisle to exit
318960 03/24/2011 266450 P 9305 OS Maintain clear aisle to exit
318850 03/24/2011 266196 P 9406 OS Relocate furniture to maintain clear aisle to exit
235664 03/24/2011 17406 1 0000 CS Install fire sprinklers for exterior stage and assembly area (Not required, verified by Mark Lodge 2/2011. Alyson Snowfleet has email info from Carey Kelly)
318962 03/24/2011 266454 P 3683 FS Secure hanging heat detector
309140 12/08/2010 244851 00 0000 C Provide detectable warning texture along sidewalk at drop-off area where there is no curb between the intersection of the sidewalk and the driveway, as required by ADA
191149 12/08/2010 61087 2 193 MS Lower fire sprinkler head to be minimum 1" below ceiling
281629 05/06/2010 185709 00 0000 M Replace missing covers on refrigeration units adjacent to 1-199T
281709 05/06/2010 185879 00 0000 M Keep PIV valve open, replace missing wrench for PIV Valve adjacent to P-8
309106 05/06/2010 244785 00 0000 M Install cap on fire department standpipe connection adjacent to P-12
309003 05/06/2010 244547 1 0000 M Secure loose escutcheon on fire sprinkler head adjacent to main (west)corridor entrance doors
309072 05/06/2010 244697 1 0000 M Repair lights in courtyard exit signs
309101 05/06/2010 244775 1 101 M Repair light in exit sign
298545 05/06/2010 221830 1 120 M Replace number on maximum occupancy sign in media center to indicate maximum occupancy = 262(per Angel Goitia, 6/15/09)
309180 05/06/2010 244941 1 120 M Repair light in exit sign
309178 05/06/2010 244937 1 124A M Repair light in exit sign
298549 05/06/2010 221838 1 150 M Replace number on maximum occupancy sign in tech lab to indicate maximum occupancy = 133(per Angel Goitia, 6/15/09)
309187 05/06/2010 244956 1 152 M Secure machinery to floor, (3 saws, 1 drill) see teacher for location
309189 05/06/2010 244960 1 152 M Paint safety lines around equipment (3 saws, 1 drill)
309090 05/06/2010 244752 1 153 M Replace missing ceiling tile
309104 05/06/2010 244781 1 164A M Adjust fire sprinkler head so deflector projects a minimum 1" below escutcheon, in ramp adjacent to 1-164B
298546 05/06/2010 221832 1 165 M Replace number on maximum occupancy sign in cafeteria to indicate maximum occupancy = 444(per Angel Goitia, 6/15/09)
309155 05/06/2010 244882 1 166E M Repair damaged ceiling
309069 05/06/2010 244691 1 167 M Repair light in exit sign
309070 05/06/2010 244693 1 169 M Repair light in exit sign
309064 05/06/2010 244680 1 170 M Secure escutcheon on fire sprinkler head
309065 05/06/2010 244682 1 170 M Replace missing escutcheon on fire sprinkler head
309066 05/06/2010 244684 1 170 M Repair light in exit sign
298548 05/06/2010 221836 1 170 M Replace number on maximum occupancy sign in band room to indicate maximum occupancy = 84(per Angel Goitia, 6/15/09)
309063 05/06/2010 244678 1 172 M Repair light in exit sign
249221 05/06/2010 118326 1 172 M Modify number on maximum occupancy sign from 88 to 78
309008 05/06/2010 244557 1 181 M Prohibit storage in cabinet under window with electrical outlets inside
309009 05/06/2010 244559 1 181 M Remove cabinet door for section of cabinet with electrical outlets inside or provide cutout in door for electrical cords
309062 05/06/2010 244675 1 198F M Close ceiling hatch
309005 05/06/2010 244551 1 199E M Replace damaged ceiling tiles
309006 05/06/2010 244553 1 199F M Replace missing ceiling tiles
309107 05/06/2010 244787 1 199S M Provide certification that all student spaces have operable emergency lights, last inspection 9/20/08
309156 05/06/2010 244890 2 103E M Repair light fixtures (loose, missing covers)and replace missing bulbs for lights in shower area
309157 05/06/2010 244893 2 105C M Secure loose escutcheon on fire sprinkler head in shower area
309159 05/06/2010 244896 2 105E M Repair light fixtures (loose, missing covers) and replace missing bulbs for lights in shower area
309142 05/06/2010 244862 P 9276 M Repair emergency lighting
309143 05/06/2010 244865 P 9277 M Repair emergency lighting
309145 05/06/2010 244868 P 9278 M Repair deteriorated wall finish adjacent to entrance door
309165 05/06/2010 244911 P 9309 M Repair emergency lighting
309162 05/06/2010 244904 P 9311 M Remove and prohibit makeshift suppport for projector hung from ceiling
226097 05/06/2010 68625 1 0000 O Provide safety goggles/disinfectant cabinets in all science labs
309182 05/06/2010 244944 1 120 O Prohibit plugging surge protector into orange extension cord @ projector
309183 05/06/2010 244947 1 120 O Prohibit plugging large flat screen TV into orange extension cord, plug directly into permanent electrical outlet
309100 05/06/2010 244773 1 136C O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
309099 05/06/2010 244771 1 140 O Remove and prohibit air freshener (apple air freshner sticks)
309097 05/06/2010 244767 1 143 O Remove and prohibit paper on ceiling
309098 05/06/2010 244769 1 143 O Treat furniture with flame retardant spray and provide certification of treatment or remove and prohibit combustible (residential) furniture
309094 05/06/2010 244760 1 148 O Prohibit plugging surge protector into surge protector @ fish tanks
309095 05/06/2010 244762 1 148 O Treat residential furniture with flame retardant and provide certification of treatment or remove and prohibit combustible (residential) furniture
309092 05/06/2010 244756 1 148A O Remove and prohibit air freshener
309173 05/06/2010 244927 1 152 O Prohibit plugging surge protector into surge protector @ teacher's desk
309089 05/06/2010 244750 1 156 O Prohibit use of damaged surge protector, adjacent to white board
249228 05/06/2010 118340 1 156 O Eliminate extension cord or replace with minimum 15A cord and prohibit running cord through ceiling
309011 05/06/2010 244563 1 181 O Prohibit plugging surge protector into surge protector
309010 05/06/2010 244561 1 181A O No access was available to this room. Please be prepared to access this room during the report review meeting
309059 05/06/2010 244668 1 184 O Remove and prohibit flammable plastic sheet covering corridor door
309004 05/06/2010 244549 1 192A O Prohibit plugging refrigerator into extension cord - plug directly into permanent electrical outlet
309161 05/06/2010 244900 2 180 O Keep floor drain filled with water to prevent sewer gas smell
309174 05/06/2010 244929 P 0000 O Remove and prohibit plastic (shower) privacy curtains in north portables
309177 05/06/2010 244935 P 6456 O Remove and prohibit flammable plastic decorative sheets on walls
309151 05/06/2010 244877 P 9280 O Prohibit storage/papers on electrical panel to provide clear access to electrical panel
309167 05/06/2010 244913 P 9309 O Prohibit plugging surge protector into surge protector @ teacher's desk
309164 05/06/2010 244909 P 9311 O Prohibit plugging surge protector into surge protector
309170 05/06/2010 244920 P 9406 O Prohibit orange multi outlet extension cord or replace with minimum 15A single outlet cord
309171 05/06/2010 244923 P 9406 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
309172 05/06/2010 244925 P 9406 O Remove and prohibit air freshener
260461 05/06/2010 142512 1 0000 C Provide suitable wiring or electrical drops for projectors in all classrooms (wiring currently consists of unprotected extension cords running along floors)
249241 05/06/2010 118366 1 120 C Provide panic hardware on corridor door adjacent to 1-122 (occupancy = 205)
309184 05/06/2010 244949 1 120 C Provide additional electrical outlet for flat screen TV to prevent use of extension cord to power TV
249223 05/06/2010 118330 1 172 C Provide illuminated exit sign at corridor door
226193 05/06/2010 61051 1 198M C Provide a vent at the high point of the exhaust duct for the flammable/chemical storage room. The openings in the duct should be 1' from the floor and 1' from the ceiling and an equal amount of air should be exhausted from each opening
309096 05/06/2010 244764 1 145 MS Provide current inspection tag for fire extinguisher
309091 05/06/2010 244754 1 152 MS Remove surplus, expelled fire extinguisher
309068 05/06/2010 244689 1 167 MS Provide current inspection tag for fire extinguisher
309071 05/06/2010 244695 1 168 MS Provide current inspection tag for fire extinguisher
309067 05/06/2010 244687 1 169 MS Provide current inspection tag for fire extinguisher
309103 05/06/2010 244779 1 199H MS Provide current inspection tag for fire extinguisher
309141 05/06/2010 244860 P 9304 MS Provide current inspection tag for fire extinguisher
309168 05/06/2010 244916 P 9406 MS Recharge fire extinguisher
309102 05/06/2010 244777 1 0000 OS Prohibit hold open devices on fire doors
309093 05/06/2010 244758 1 148A OS Prohibit storage in restroom to maintain clear aisle to exit
309088 05/06/2010 244748 1 158 OS Prohibit running electrical cord for projector through ceiling
309073 05/06/2010 244703 1 162 OS Immediately remove and prohibit makeshift support for projector hung from ceiling grid
309074 05/06/2010 244705 1 162 OS Prohibit running electrical cord for projector through ceiling tiles
309105 05/06/2010 244783 1 164 OS Prohibit attaching extension cord to lighting grid on stage
309060 05/06/2010 244670 1 174 OS Prohibit electrical cord under carpet
309007 05/06/2010 244555 1 183 OS Prohibit hold open devices on fire door
309061 05/06/2010 244672 1 198F OS Prohibit charging batteries in room
309176 05/06/2010 244933 P 6455 OS Maintain clear aisle to rear exit door
309148 05/06/2010 244870 P 9280 OS Maintain clear aisle to rear exit door
309163 05/06/2010 244906 P 9311 OS Prohibit running extension cord for projector through ceiling
309169 05/06/2010 244918 P 9406 OS Maintain clear aisle to exit
309175 05/06/2010 244931 P 9831 OS Prohibit running electrical cord through wall (into bathroom)
281603 05/06/2010 185659 1 189 CS Provide auto closer on door
249256 05/06/2010 118396 1 198A CS Provide auto closer on corridor door
298547 02/04/2010 221834 1 166 M Replace number on maximum occupancy sign in chorus room to indicate maximum occupancy = 66(per Angel Goitia, 6/15/09)
249191 02/04/2010 118263 1 198B CS Provide auto closer on door
297080 04/28/2009 218651 1 0000 M Adjust smoke doors in corridor adjacent to east side of 1-120 to close properly
297081 04/28/2009 218653 1 125A M Repair light in exit sign
297097 04/28/2009 218685 1 161 M Eliminate ant infestation
297046 04/28/2009 218577 1 164A M Adjust fire sprinkler head in ramp adjacent to 1-164B so deflector projects a minimum 1" below escutcheon
297041 04/28/2009 218565 1 170 M Re-number inappropriate occupancy sign, correct occupancy is 68
297043 04/28/2009 218571 1 170 M Repair light in exit sign above north door
297094 04/28/2009 218679 1 177 M Secure lens on light fixture
297093 04/28/2009 218677 1 190A M Replace missing escutcheon on fire sprinkler head
297092 04/28/2009 218675 1 195 M Repair light in exit sign
297091 04/28/2009 218673 1 196 M Repair light in exit sign
297054 04/28/2009 218595 1 198M M Repair door to close properly
297083 04/28/2009 218657 1 199 M Repair leaking air handler (AHU#9)
297079 04/28/2009 218649 1 199D M Repair door to close properly
281787 04/28/2009 186010 1 199K M Provide cover on exposed electrical junction box (neptronic unit) @ AHU12
297052 04/28/2009 218589 1 199S M Notes on emergency lighting/generator report note that line breaker to transformer will not reset. Verify repair and proper function
297059 04/28/2009 218605 2 101 M Replace missing safety pin on fire extinguisher in NE corner of gym
297060 04/28/2009 218607 2 105A M Re-number occupancy sign, correct occupancy is 66
297062 04/28/2009 218611 2 105C M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
297075 04/28/2009 218641 P 3760 M Repair emergency lighting
297106 04/28/2009 218703 P 9276 M Repair emergency lighting
297107 04/28/2009 218706 P 9277 M Repair emergency lighting
297108 04/28/2009 218708 P 9281 M Repair door to close properly
297072 04/28/2009 218635 P 9308 M Repair emergency lighting
297068 04/28/2009 218627 P 9310 M Repair emergency lighting
297076 04/28/2009 218643 P 9402 M Provide cover on exposed electrical junction box on north wall
260483 04/28/2009 142551 P 9407 M Replace vinyl flooring in bathroom (seam is coming apart)
281532 04/28/2009 185513 00 0000 O Highlight primary and secondary routes on evacuation maps in all student occupied areas
297082 04/28/2009 218655 1 123 O Prohibit plugging laminator into surge protector - plug directly into permanent electrical outlet
297090 04/28/2009 218671 1 136D O Prohibit white 13A extension cord plugged into surge protector or replace with minimum 15A cord. Prohibit plugging extension cord into surge protector, plug into permanent electrical outlet
297048 04/28/2009 218581 1 164 O Prohibit green multi outlet extension cord adjacent to 1-164G or replace with minimum 15A single outlet cord
297044 04/28/2009 218573 1 168 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
297087 04/28/2009 218665 1 169 O Prohibit plugging surge protector into surge protector
297042 04/28/2009 218569 1 170 O Reword sign to read "Emergency Exit Only" prohibit sign reading "Use only in dire emergency"
297039 04/28/2009 218561 1 170A O Reword sign to read "Emergency Exit Only", prohibit sign reading "Use only in dire emergency"
297040 04/28/2009 218563 1 172 O Treat couch with flame retardant or remove and prohibit combustible (residential) furniture
297096 04/28/2009 218683 1 174 O Prohibit orange 13A extension cord or replace with minimum 15A cord
281702 04/28/2009 185865 1 193 O Prohibit plugging surge protector into surge protector
281703 04/28/2009 185867 1 194 O Prohibit plugging surge protector into surge protector
297056 04/28/2009 218599 1 198J O Prohibit running surge protector cord through cabinet door
297053 04/28/2009 218591 1 198L O No access was available to this room. Please be prepared to access this room during the report review meeting
297045 04/28/2009 218575 1 199H O No access was available to this room. Please be prepared to access this room during the report review meeting
297104 04/28/2009 218699 P 3683 O Prohibit brown 13A extension cord or replace with minimum 15A cord
297101 04/28/2009 218693 P 9307 O Provide clear access to electrical panel
297069 04/28/2009 218629 P 9310 O Provide clear access to electrical panel
297067 04/28/2009 218625 P 9311 O Provide clear access to electrical panel
297078 04/28/2009 218647 P 9402 O Prohibit plugging mircowave into surge protector - plug directly into permanent electrical outlet
297074 04/28/2009 218639 P 9406 O Prohibit plugging microwave into multi outlet electrical adaptor - plug directly into permanent electrical outlet. Prohibit multi outlet electrical adaptor
235673 04/28/2009 17444 1 177 C Provide ventilation to exterior for stove adjacent to 1-177A
297055 04/28/2009 218597 1 198J C Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
297086 04/28/2009 218663 00 8088 MS Provide current inspection tag for fire extinguisher in courtyard adjacent to NE corridor doors, north exterior wall of 1-167
297085 04/28/2009 218661 1 0000 MS Adjust fire doors in corridor adjacent to 1-176 to latch properly
297099 04/28/2009 218689 1 156 MS Provide current inspection tag for fire extinguisher
297050 04/28/2009 218585 1 164 MS Provide current inspection tag for fire extinguisher
297051 04/28/2009 218587 1 166 MS Recharge fire extinguisher adjacent to south exterior doors
297058 04/28/2009 218603 2 101 MS Recharge fire extinguisher
297063 04/28/2009 218613 2 107 MS Provide current inspection tag for fire extinguisher
297070 04/28/2009 218631 P 9309 MS Recharge fire extinguisher
297077 04/28/2009 218645 P 9402 MS Provide current inspection tag for fire extinguisher
297089 04/28/2009 218669 1 140 OS Prohibit hold open devices on corridor door
297088 04/28/2009 218667 1 147 OS Prohibit hold open devices on corridor door
281570 04/28/2009 185591 1 158 OS Prohibit running electrical cord into ceiling to power projector
281575 04/28/2009 185601 1 162 OS Prohibit runnning extension cord into ceiling to power projector
297047 04/28/2009 218579 1 164 OS Prohibit hanging (green)extension cord from ceiling grid and stage curtain, adjacent to 1-164G
297095 04/28/2009 218681 1 175 OS Remove and prohibit use of toaster oven
297084 04/28/2009 218659 1 179 OS Prohibit hold open devices on corridor door
191142 04/28/2009 61078 1 198F OS Prohibit recharging batteries in room
297102 04/28/2009 218695 1 199P OS Remove storage from fire sprinkler room
297057 04/28/2009 218601 2 103A OS Relocate Pepsi machine to provide clear access to fire extinguisher
297061 04/28/2009 218609 2 105E OS Prohibit storage of flammable materials(degreaser)
297103 04/28/2009 218697 P 3683 OS Maintain clear aisle to exits
297105 04/28/2009 218701 P 9277 OS Remove and prohibit paper chains from ceiling
297100 04/28/2009 218691 P 9305 OS Remove and prohibit use of toaster oven
281545 02/02/2009 185538 1 120 O Prohibit plugging surge protector into surge protector (@computers)
249265 02/02/2009 118415 1 120 O Eliminate extension cord or replace with minimum 15A cord (at media spec. desk)
249266 02/02/2009 118417 1 120 O Prohibit plugging extension cord to surge protector (at media spec. desk)
281641 04/16/2008 185736 00 0000 M Install caps on fire department standpipe connection adjacent to P-9311 (P-12)
281800 04/16/2008 186036 00 0000 M Repair damaged latch for gate at fence enclosure adjacent to P-1
281554 04/16/2008 185557 1 141B M Repair damaged toilet, not flushing
281567 04/16/2008 185584 1 152A M Determine cause of water damaged ceiling tiles and replace tiles
249218 04/16/2008 118320 1 165 M Replace missing covers for high hat lights near exterior doors
281618 04/16/2008 185688 1 169 M Determine cause of water damaged ceiling tiles and replace tiles
281610 04/16/2008 185671 1 177 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
226173 04/16/2008 68554 1 179 M Relocate electrical outlet at teacher's desk to be above counter instead of inside cabinet to eliminate need for electrical cords to be run into cabinet
281639 04/16/2008 185732 2 101 M Repair fire extinguisher cabinet adjacent to North doors and 2-106
281640 04/16/2008 185734 2 101 M Provide cover on exposed electrical junction box, North wall
281711 04/16/2008 185886 P 3683 M Repair stair door to open properly
281790 04/16/2008 186016 P 9277 M Repair rear door to close properly
281789 04/16/2008 186014 P 9278 M Repair front door to close properly
281646 04/16/2008 185746 P 9308 M Repair emergency lighting
281645 04/16/2008 185744 P 9309 M Seal rear door to prevent frogs, see teacher
281644 04/16/2008 185742 P 9310 M Repair rear door to close properly
281700 04/16/2008 185861 P 9403 M Repair hanging exhaust fan in bathroom
281698 04/16/2008 185856 P 9404 M Repair damaged toilet seat
281699 04/16/2008 185858 P 9404 M Repair rear door to close properly
281697 04/16/2008 185854 P 9405 M Repair hanging exhaust fan in bathroom
191120 04/16/2008 61085 00 0000 O Prohibit parking on grass area at bus loop - limit parking to paved areas
281578 04/16/2008 185609 1 114 O Remove and prohibit air freshener
281550 04/16/2008 185551 1 124A O Prohibit plugging surge protector into surge protector
281542 04/16/2008 185534 1 131 O Prohibit white multi outlet extension cord or replace with minimum 15A single outlet cord
281540 04/16/2008 185531 1 136 O Prohibit plugging surge protector into surge protector
281536 04/16/2008 185520 1 136A O Prohibit plugging orange extension cord into surge protector
281538 04/16/2008 185527 1 136A O Prohibit plugging surge protector into surge protector
281557 04/16/2008 185565 1 143 O Remove and prohibit paper on ceiling
281562 04/16/2008 185572 1 148 O Prohibit plugging surge protector into surge protector
281568 04/16/2008 185588 1 154E O Remove and prohibit air freshener
281577 04/16/2008 185605 1 162 O Prohibit white 13A extension cord or replace with minimum 15A single outlet cord
281615 04/16/2008 185682 1 174 O Prohibit orange 13A extension cord or replace with minimum 15A cord
260464 04/16/2008 142520 1 175 O Post sign indicating evacuation routes
281605 04/16/2008 185662 1 188 O Prohibit white 13A extension cord or replace with minimum 15A single outlet cord
281607 04/16/2008 185665 1 198L O No access was available to this room. Please be prepared to access this room during the report review meeting
281712 04/16/2008 185888 P 3683 O Prohibit multi outlet electrical adaptor @ TV set
281713 04/16/2008 185890 P 3683 O Prohibit plugging media cart into surge protector, plug directly into permanent electrical outlet
281714 04/16/2008 185892 P 3683 O Remove and prohibit paper covering window in door
281795 04/16/2008 186028 P 9280 O Prohibit multi outlet electrical adaptor (plugged into surge protector)
281801 04/16/2008 186041 P 9281 O Prohibit plugging surge protector into surge protector
281705 04/16/2008 185871 P 9305 O Prohibit plugging surge protector into 13A extension cord, prohibit 13A extension cord
281706 04/16/2008 185873 P 9306 O Prohibit plugging surge protector into surge protector
281708 04/16/2008 185877 P 9307 O Provide clear access to electrical panel
281642 04/16/2008 185738 P 9311 O Prohibit plugging surge protector into surge protector
281647 04/16/2008 185748 P 9406 O Prohibit multi outlet electrical adaptor
281648 04/16/2008 185750 P 9406 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
281527 04/16/2008 185504 1 131 MS Provide current inspection tag for fire extinguisher
281608 04/16/2008 185669 1 199G MS Provide current inspection tag for fire extinguisher
281625 04/16/2008 185703 1 199H MS Provide current inspection tag for fire extinguisher
281802 04/16/2008 186043 1 199N MS Provide current inspection tag for fire extinguisher
281710 04/16/2008 185884 1 199P MS Provide current inspection tag for fire sprinkler system
281634 04/16/2008 185722 2 193 MS Provide current inspection tag for fire sprinkler system
281803 04/16/2008 186045 3 101 MS Provide current inspection tag for fire extinguisher
281649 04/16/2008 185752 P 3760 MS Provide current inspection tag for fire extinguisher
281624 04/16/2008 185695 00 0000 OS Maintain clear aisle to NE corridor exit doors from interior courtyard
281530 04/16/2008 185509 1 133 OS Prohibit hold open devices on fire door
281565 04/16/2008 185580 1 145 OS Prohibit hold open devices on fire door
281559 04/16/2008 185569 1 146 OS Maintain clear aisle to exterior exit
281563 04/16/2008 185577 1 148 OS Maintain clear aisle to exterior exit
281619 04/16/2008 185691 1 169 OS Remove and prohibit candles
281616 04/16/2008 185685 1 174 OS Prohibit hold open devices on fire door
281614 04/16/2008 185679 1 175 OS Prohibit hold open devices on fire door
260475 04/16/2008 142541 1 199P OS Remove storage from mechanical room
260582 04/16/2008 142706 P 9277 OS Maintain clear aisle to rear exit door
281792 04/16/2008 186022 P 9279 OS Relocate chair to maintain clear aisle to rear exit
281798 04/16/2008 186031 P 9281 OS Maintain clear aisle to rear exit
281704 04/16/2008 185869 P 9305 OS Prohibit running extension cord under carpet
260589 04/16/2008 142716 P 9306 OS Maintain clear aisle to rear exit door
281701 04/16/2008 185863 P 9402 OS Maintain clear aisle to exit doors
226220 03/05/2008 61063 P 3760 M Modify existing foundations and anchorage to comply with engineering requirements
249230 01/11/2008 118344 1 157 M Replace plywood in window frame with glass
281626 01/11/2008 185705 1 165 M Replace missing escutcheon on fire sprinkler head on east side of room
249217 01/11/2008 118318 1 166 M Provide current inspection tag for kitchen steamer
260458 01/11/2008 142498 1 166G M Loosen emergency release knob inside walk-in freezer to operate properly (emergency release knob cannot be turned by hand)
235692 01/11/2008 17478 2 101 M Cover the exposed fiberglass insulation @ ceiling
281636 01/11/2008 185727 2 103E M Secure loose escutcheon on fire sprinkler head
281635 01/11/2008 185725 2 103F M Replace missing escutcheon on fire sprinkler head
281638 01/11/2008 185729 2 106 M Remove bracket mounted on inside of door, creates hazard
281631 01/11/2008 185714 2 191 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
226216 01/11/2008 68624 3 101 M Secure hanging roof insulation
249245 01/11/2008 118374 1 124A O Remove and prohibit combustible beanbag chairs
260443 01/11/2008 142470 1 133 O Eliminate extension cord powering projector
260454 01/11/2008 142493 1 152A O Keep area within 18" of automatic fire sprinkler heads clear and unobstructed
249269 01/11/2008 118424 1 152C O Prohibit use of woodworking equipment or submit change of use request to Bldg. Dept. and provide adequate safety features for use of equipment
281612 01/11/2008 185677 1 175 O Prohibit plugging surge protector into extension cord
281643 01/11/2008 185740 P 9310 O Prohibit plugging surge protector into extension cord
235674 01/11/2008 17447 00 9500 C Provide covered walkway to portables
226139 01/11/2008 68627 1 152 C Provide sign indicating maximum occupancy adjacent to main entrance (max. occ.=92 for 1-150/1-152 combined)
226202 01/11/2008 68628 2 101 C Provide sign indicating maximum occupancy adjacent to main entrance (max. occ.=814)
260452 01/11/2008 142490 1 146 OS Remove and prohibit hold open device (wedge) from corridor door
281611 01/11/2008 185674 1 175 OS Remove and prohibit candles
260469 01/11/2008 142529 1 179B OS Prohibit storage of flammable spray paint
260583 01/11/2008 142708 P 9276 OS Remove and prohibit use of toaster oven
260591 01/11/2008 142720 P 9304 OS Maintain clear aisle to rear exit door
235665 01/11/2008 17407 1 144 CS Provide fire extinguisher within 15' of stove
260435 03/23/2007 142454 1 0000 M Remove surface mounted knox box without cover which is not being used (recessed knox box next to this one is being used)
260437 03/23/2007 142456 1 0000 M Repair light in exit sign in administrative corricor @ 1-110
260438 03/23/2007 142462 1 113 M Determine cause of water damaged ceiling tiles and replace tiles
260441 03/23/2007 142467 1 122 M Replace missing escutcheon on fire sprinkler head
260439 03/23/2007 142464 1 125 M Replace missing escutcheon on fire sprinkler head
249249 03/23/2007 118382 1 126A M Replace missing escutcheon on fire sprinkler head
235672 03/23/2007 17442 1 162 M Verify that emergency exhaust system for chemistry lab was installed per the contract documents- ducted above the ceiling to a roof exhaust vent. (As per teacher,exhaust is vented just above ceiling only)
260455 03/23/2007 142496 1 164 M Determine cause of water damaged ceiling tiles and replace tiles
260470 03/23/2007 142532 1 184 M Replace missing escutcheon on fire sprinkler head
260471 03/23/2007 142534 1 185 M Replace missing escutcheon on fire sprinkler head (X2)
260473 03/23/2007 142536 1 191 M Replace missing escutcheon on fire sprinkler head
249235 03/23/2007 118354 1 199E M Replace missing escutcheon on fire sprinkler head
226199 03/23/2007 69580 1 199P M Provide wrench for spare fire sprinkler heads
249209 03/23/2007 118301 2 105C M Replace missing escutcheon on fire sprinkler head in shower area
226219 03/23/2007 68589 P 3683 M Replace worn non-slip surface on stair
260570 03/23/2007 142682 P 3760 M Determine cause of water damaged ceiling tiles and replace tiles
260590 03/23/2007 142718 P 9305 M Repair rear door to close and latch properly
249232 03/23/2007 118348 1 115 O Remove and prohibit air freshener
249243 03/23/2007 118370 1 120 O Prohibit taping extension cord to floor - provide appropriate electrical cord protective cover strip
249271 03/23/2007 118428 1 131 O Remove multi-outlet electrical adaptors at aquariums
260450 03/23/2007 142484 1 136A O Provide clear access to electrical panel on north wall adjacent to 1-136C
260465 03/23/2007 142522 1 177 O Eliminate 13 amp extension cord powering projector
249168 03/23/2007 118213 P 9306 O Prohibit taping electrical cords to floor - cover with appropriate electrical cord protective cover strip
249147 03/23/2007 118170 P 9310 O Prohibit taping extension cord to floor - cover cord with appropriate electrical cord protective cover
260476 03/23/2007 142544 1 123 MS Provide current inspection tag for fire extinguisher
260592 03/23/2007 142722 P 9304 MS Provide current inspection tag for fire extinguisher
260447 03/23/2007 142476 1 135 OS Remove and prohibit hold open device (wedge) on corridor door
260576 03/23/2007 142694 P 9310 OS Maintain clear aisle to rear exit door
260537 03/23/2007 142614 P 9403 OS Remove and prohibit use of toaster in classroom
260572 03/23/2007 142686 P 9407 OS Remove and prohibit use of toaster in classroom
260573 03/23/2007 142688 P 9407 OS Maintain clear aisle to rear exit door
191141 03/23/2007 65084 1 177 CS Provide a type "K" fire extinguisher within 15' of all cooking equipment
226082 11/07/2006 61050 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
249149 11/07/2006 118175 1 102A M Replace missing escutcheon on fire sprinkler head
235691 11/07/2006 17468 1 166G M Adjust freezer door to close and latch properly - frozen around edge
249224 11/07/2006 118332 1 172C M Adjust fire sprinkler head to project a minimum 1" below escutcheon
226171 11/07/2006 68633 1 177B M Remove shelf below fire sprinkler head to provide minimum 18" clearance from head
249213 11/07/2006 118309 1 199H M Relocate light fixture away from fire sprinkler head to provide proper fire sprinkler coverage
226223 11/07/2006 68639 P 3760 M Adjust steps to make risers equal
249233 11/07/2006 118350 1 114 O Remove and prohibit air freshener
235668 11/07/2006 17425 1 124A O Remove and prohibit combustible residential furniture in CCTV studio
249253 11/07/2006 118390 1 168 O Remove and prohibit toaster oven
226189 11/07/2006 68617 1 198F O Replace bulbs in light fixture
249169 11/07/2006 118215 P 9306 O Eliminate extension cord or replace with minimum 15A cord
249146 11/07/2006 118168 P 9310 O Eliminate extension cord or replace with minimum 15A cord
249159 11/07/2006 118195 P 9405 O Remove and prohibit combustible beanbag chairs
249268 11/07/2006 118422 1 120 C Modify hardware on corridor doors to allow entrance into media center without dog down devices on panic hardware
235671 11/07/2006 17441 1 140 C If room is used as a chemistry lab, provide or verify that room has emergency exhaust system (all chemicals removed from this room and stored in proper space)
226204 11/07/2006 68570 2 103A C Provide illuminated exit sign at door into gym (occ. = 65)
226206 11/07/2006 68571 2 105A C Provide illuminated exit sign at door into gym (occ. = 66)
226218 11/07/2006 68623 P 3683 C Provide bottom rail on ramp landing guardrail at two inches above floor
226221 11/07/2006 61086 P 3760 C Provide graspable handrails on each side of ramp at between 34-38" high
249267 11/07/2006 118420 1 120 MS Remove dog down devices on corridor doors so doors latch properly
249170 11/07/2006 118217 2 193 MS Provide current inspection tag for fire extinguisher
249144 11/07/2006 118164 3 101 MS Provide current inspection tag for fire extinguisher
249248 11/07/2006 118380 1 124A OS Remove and prohibit use of extension cord with missing ground plug
249137 11/07/2006 118145 1 152 OS Remove and prohibit running extension cord through ceiling
249174 11/07/2006 118225 P 3760 OS Remove tables blocking clear path to stair door
249211 05/11/2006 118305 00 0000 M Repair or replace damaged column for covered walkway near 2-190
249204 05/11/2006 118291 00 9599 M Repair damaged chain link fencing at chiller compound
249259 05/11/2006 118402 1 0000 M Adjust door closer for smoke doors adjacent to 1-120 to control speed of closing door
249261 05/11/2006 118406 1 0000 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to 1-154
226102 05/11/2006 68620 1 116 M Remove button lock from door
226103 05/11/2006 68520 1 120 M Determine cause of water damaged ceiling tiles and replace tiles at fire sprinkler head
249264 05/11/2006 118413 1 120 M Remove button locks from all smaller rooms within media center so doors cannot be locked from inside rooms
249239 05/11/2006 118362 1 122 M Determine cause of water damaged ceiling tiles and replace tiles
249270 05/11/2006 118426 1 131 M Adjust water flow for emergency eye wash
249231 05/11/2006 118346 1 132 M Remove button lock so door cannot be locked from inside room
226121 05/11/2006 68523 1 136C M Replace missing ceiling tiles
226135 05/11/2006 61045 1 150 M Label emergency disconnect switch
249139 05/11/2006 118150 1 162 M Provide Off switch for emergency exhaust fan - switch in 1-160A does not work and breaker must be tripped to turn fan off
249140 05/11/2006 118153 1 162 M Provide directions for operation of emergency exhaust fan adjacent to control button
226152 05/11/2006 68638 1 164 M Provide warning strip along edge of exterior stage
226155 05/11/2006 68524 1 164B M Patch hole in ceiling adjacent to fire sprinkler head
249206 05/11/2006 118295 1 165 M Adjust corridor door adjacent to 1-165A to latch properly
249199 05/11/2006 118280 1 165 M Secure loose handle for fire extinguisher cabinet near serving line
249226 05/11/2006 118336 1 170 M Repair light in exit sign
249225 05/11/2006 118334 1 171 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
249222 05/11/2006 118328 1 172 M Repair light in exit sign
249220 05/11/2006 118324 1 197B M Replace missing toilet seat
249190 05/11/2006 118261 1 198B M Repair or replace rusted water heater tank - standing water on floor
249236 05/11/2006 118356 1 199E M Determine cause of water damaged ceiling tiles and replace tiles
249205 05/11/2006 118293 1 199R M Repair exterior door to close properly
249200 05/11/2006 118282 1 199T M Secure loose fire extinguisher bracket and mount extinguisher on bracket
249201 05/11/2006 118285 1 199T M Remove unused fire extinguishers
249215 05/11/2006 118313 2 101 M Repair or replace water damaged wood flooring at water fountain adjacent to 2-103
249212 05/11/2006 118307 3 0000 M Repair damaged chain link fencing at Bldg. 3
249177 05/11/2006 118231 P 3683 M Replace missing ceiling tiles
249175 05/11/2006 118227 P 3760 M Replace missing joint cover strip on wall adjacent to sink
226222 05/11/2006 68590 P 3760 M Replace worn non-slip surface on ramp and stair
249179 05/11/2006 118235 P 9276 M Repair light in exit sign/emergency light
249182 05/11/2006 118241 P 9277 M Provide cover on exposed electrical junction box on exterior wall by rear door
249186 05/11/2006 118249 P 9278 M Remove out-of-date fire extinguisher
249164 05/11/2006 118205 P 9404 M Adjust front door to latch properly
249151 05/11/2006 118179 1 109 O No access was available to this room. Please be prepared to access this room during the report review meeting.
249242 05/11/2006 118368 1 120 O Prohibit plugging surge protector to extension cord
249238 05/11/2006 118360 1 121A O Prohibit plugging surge protector to surge protector and surge protector to extension cord - plug each directly into electrical outlet
249240 05/11/2006 118364 1 123 O No access was available to this room. Please be prepared to access this room during the report review meeting.
249250 05/11/2006 118384 1 130A O Remove and prohibit toaster oven
249251 05/11/2006 118386 1 130A O Remove excessive storage and maintain storage room in an orderly manner
249252 05/11/2006 118388 1 131 O Remove and prohibit air freshener
249254 05/11/2006 118392 1 133A O Remove and prohibit toaster oven
249257 05/11/2006 118398 1 136 O Prohibit plugging surge protector to extension cord
249258 05/11/2006 118400 1 136B O Remove storage blocking clear access to fire sprinkler system test valve
249262 05/11/2006 118408 1 147A O Eliminate extension cord or replace with minimum 15A cord
249263 05/11/2006 118410 1 147A O Prohibit powering refrigerator with extension cord - plug refrigerator directly into electrical outlet
226143 05/11/2006 68616 1 152C O Replace bulbs in light fixture
249227 05/11/2006 118338 1 169A O Remove and prohibit air freshener spray
249196 05/11/2006 118274 1 199L O Remove cobwebs from room
249202 05/11/2006 118287 1 199S O Replace bulbs in light fixture
249207 05/11/2006 118297 2 180 O Remove storage within 18" of fire sprinkler head
249208 05/11/2006 118299 2 181 O Remove storage within 18" of fire sprinkler head
249176 05/11/2006 118229 P 3760 O Remove and prohibit Raid bug spray
249180 05/11/2006 118237 P 9276 O Remove and prohibit air freshener spray
249184 05/11/2006 118245 P 9278 O Relocate bookcase blocking clear access to electrical panel
226237 05/11/2006 68557 P 9308 O Relocate tables blocking clear access to electrical panel
249162 05/11/2006 118201 P 9404 O Remove and prohibit toaster oven
249198 05/11/2006 118278 1 0000 MS Adjust smoke stop doors outside cafeteria to close properly
249244 05/11/2006 118372 1 124 MS Provide current inspection tag for fire extinguisher (2/04)
249255 05/11/2006 118394 1 134 MS Provide current inspection tag for fire extinguisher
249234 05/11/2006 118352 1 145 MS Provide current inspection tag for fire extinguisher
249219 05/11/2006 118322 1 164G MS Provide current inspection tag for fire extinguisher
249216 05/11/2006 118315 1 166H MS Provide current inspection tag for fire extinguisher
249203 05/11/2006 118289 1 198M MS Replace missing tag for fire extinguisher
249192 05/11/2006 118265 1 199D MS Provide current inspection tag for fire extinguisher
249194 05/11/2006 118269 1 199G MS Provide current inspection tag for fire extinguisher
249193 05/11/2006 118267 1 199L MS Provide current inspection tag for fire extinguisher
249195 05/11/2006 118271 1 199N MS Provide current inspection tag for fire extinguisher
249188 05/11/2006 118255 1 199P MS Provide current inspection tag for fire sprinkler system - dated 9/28/04
249210 05/11/2006 118303 2 101 MS Replace missing inspection tag on fire extinguisher near NE exit doors
249214 05/11/2006 118311 2 102 MS Close ceiling hatch
249171 05/11/2006 118219 2 191 MS Provide current inspection tag for fire extinguisher
249185 05/11/2006 118247 P 9278 MS Replace missing inspection tag for fire extinguisher
249197 05/11/2006 118276 1 0000 OS Remove all storage at exit doors leading from interior courtyard near cafeteria
249152 05/11/2006 118181 1 0000 OS Remove storage carts in front of exit doors from interior courtyard - near media center
249150 05/11/2006 118177 1 102A OS Prohibit wedging open fire door
226099 05/11/2006 68594 1 111 OS Prohibit wedging open fire door
249237 05/11/2006 118358 1 120 OS Prohibit hold open devices on corridor door
249246 05/11/2006 118376 1 124A OS Remove furniture blocking clear path to corridor exit door
249247 05/11/2006 118378 1 124A OS Prohibit running cords through door opening - run cords through designed openings in wall
249260 05/11/2006 118404 1 130 OS Prohibit running electrical cords under rug
251204 05/11/2006 122508 1 134 OS Prohibit wedging open corridor door
249135 05/11/2006 118143 1 148 OS Relocate table and chairs blocking clear path to exterior door
249229 05/11/2006 118342 1 156 OS Prohibit wedging open corridor door
249178 05/11/2006 118233 P 9276 OS Remove table and storage blocking clear path to rear door
249181 05/11/2006 118239 P 9277 OS Arrange desks to provide and maintain minimum 3' wide clear path to doors
249183 05/11/2006 118243 P 9278 OS Remove table and storage blocking clear path to rear door
249187 05/11/2006 118251 P 9279 OS Remove file cabinet and storage blocking clear access to rear door
249172 05/11/2006 118221 P 9281 OS Relocate table to provide minimum 3' wide clear path to rear door
249173 05/11/2006 118223 P 9281 OS Remove table and storage blocking clear path to rear door
249153 05/11/2006 118183 P 9304 OS Remove file cabinet and storage blocking clear access to rear door
249154 05/11/2006 118185 P 9305 OS Arrange desks to provide and maintain minimum 3' wide clear path to rear door
249166 05/11/2006 118209 P 9306 OS Relocate desk and study corral blocking clear path to front door
249167 05/11/2006 118211 P 9306 OS Remove storage and file cabinet blocking clear path to rear door
249156 05/11/2006 118189 P 9308 OS Remove file cabinet blocking clear path to rear door
249155 05/11/2006 118187 P 9309 OS Remove table and refrigerator blocking clear access to rear door
249145 05/11/2006 118166 P 9310 OS Remove storage blocking clear path to rear door
249142 05/11/2006 118158 P 9311 OS Relocate table blocking clear path to rear door and arrange desks to provide minimum 3' wide clear path to rear door
226244 05/11/2006 68551 P 9402 OS Relocate table blocking clear path to rear door
249165 05/11/2006 118207 P 9403 OS Remove study corral and chair blocking clear path to rear door
249163 05/11/2006 118203 P 9404 OS Relocate table to be minimum 3' from front door
249161 05/11/2006 118199 P 9404 OS Relocate file cabinet, refrigerator and storage blocking clear path to rear door
249160 05/11/2006 118197 P 9405 OS Remove file cabinet and refrigerator blocking clear path to rear door
249158 05/11/2006 118193 P 9406 OS Relocate table blocking clear path to rear door
249157 05/11/2006 118191 P 9407 OS Remove file cabinet, refrigerator, microwave oven, etc. blocking clear path to rear door
226100 02/02/2006 68619 1 112 M Remove button lock from door
226131 02/02/2006 68521 1 146 M Determine cause of water damaged ceiling tiles and replace tiles
226145 02/02/2006 68577 1 154 M Replace safety pin on fire extinguisher
226180 02/02/2006 68540 1 195 M Repair exterior door to close and latch properly
226110 02/02/2006 68517 1 131 O Provide verification that written permission from principal has been provided to keep animal in the classroom and that all required safety precautions are being followed
226116 02/02/2006 68518 1 134 O Provide verification that written permission from principal has been provided to keep animal in the classroom and that all required safety precautions are being followed
226129 02/02/2006 68591 1 144 O Remove and prohibit combustible beanbag chairs (adjacent to dryer)
226141 02/02/2006 68566 1 152 O Eliminate extension cord or replace with minimum 15A cord and prohibit running extension cord through ceiling
226147 02/02/2006 61036 1 156 O Provide verification that written permission from principal has been provided to keep gerbil in the classroom and that all required safety precautions are being followed
226196 02/02/2006 68618 1 199H O Replace bulbs in light fixture
235670 02/02/2006 17440 1 116 C Provide separate cots and cot areas for male/female (requirement waived by Tom Hogarth)
226117 02/02/2006 68626 1 136 C Provide sign indicating maximum occupancy adjacent to main entrance
226093 02/02/2006 68578 1 0000 MS Recharge fire extinguisher in corridor between 1-147 & 1-145
226094 02/02/2006 68579 1 0000 MS Recharge fire extinguisher in corridor between 1-120 & 1-199B
226088 02/02/2006 68541 1 0000 MS Remove sandbags blocking exit doors from courtyard near media center
226168 02/02/2006 68583 1 177 MS Provide current inspection tag for fire extinguisher
226179 02/02/2006 68584 1 193 MS Provide current inspection tag for fire extinguisher
226200 02/02/2006 68580 1 199S MS Recharge fire extinguisher
191145 02/02/2006 61058 2 103A MS Provide current inspection tag for fire extinguisher
235667 02/02/2006 17417 2 105A MS Provide current inspection tag for fire extinguisher (1/00)
226232 02/02/2006 68581 P 9304 MS Recharge fire extinguisher
226233 02/02/2006 68574 P 9305 MS Replace missing fire extinguisher
226080 02/02/2006 61083 00 0000 CS Provide lid for "Knox" box and keys in box to allow fire department access
226084 03/15/2005 65085 00 9599 M Fill holes in ground adjacent to sidewalk west of P-7
226089 03/15/2005 68567 1 0000 M Repair light in exit sign in corridor between 1-136 & 1-136A
226090 03/15/2005 68568 1 0000 M Repair light in exit sign in courtyard adjacent to 1-199N
226091 03/15/2005 68569 1 0000 M Repair or replace damaged exit sign in courtyard adjacent to 1-199D
226092 03/15/2005 68576 1 0000 M Replace safety pin on fire extinguisher in corridor adjacent to 1-198B
226095 03/15/2005 68588 1 0000 M Replace cracked vinyl floor tiles on corridor floor between 1-182 & 1-184
226108 03/15/2005 69576 1 125 M Replace missing escutcheon on fire sprinkler head
226128 03/15/2005 68519 1 144 M Connect vent duct for dryer
226137 03/15/2005 68582 1 151 M Remove out of date fire extinguisher under computer table
226153 03/15/2005 69578 1 164 M Repair light in exit sign
226154 03/15/2005 68609 1 164A M Replace missing screws in door light at door onto stage
226156 03/15/2005 68610 1 164D M Replace missing screws in door light
226158 03/15/2005 68516 1 166 M Keep bug screen air curtains at doors turned on when kitchen is in use
226167 03/15/2005 68522 1 177 M Determine cause of water damaged ceiling tiles adjacent to vent duct for stove and replace tiles
226170 03/15/2005 68632 1 177A M Remove shelf below fire sprinkler head to provide minimum 18" clearance from head
226183 03/15/2005 68634 1 198 M Remove shelf below fire sprinkler head to provide minimum 18" clearance from head
226184 03/15/2005 68635 1 198A M Remove shelf below fire sprinkler head to provide minimum 18" clearance from head
226186 03/15/2005 68612 1 198D M Pad and mark corner of wood shelf which is lower than 6'8" or round off corner
226191 03/15/2005 68613 1 198G M Pad and mark corner of wood shelf which is lower than 6'8" or round off corner
226198 03/15/2005 68575 1 199J M Remove Type K fire extinguishers from floor and relocate to appropriate locations
226209 03/15/2005 68608 2 191 M Adjust door to latch properly
226214 03/15/2005 68614 2 8088 M Replace broken lens on light fixture on exterior wall facing basketball courts
226229 03/15/2005 68585 P 9279 M Remove out of date fire extinguisher at rear of room
226236 03/15/2005 68560 P 9308 M Repair emergency lighting
226241 03/15/2005 69590 P 9310 M Adjust rear door to latch properly
226250 03/15/2005 68622 P 9407 M Secure sink to wall in bathroom
214285 03/15/2005 68515 O No access was available to 1-109, 1-123, 1-192A, 1-198L. Please be prepared to access these rooms during the report review meeting.
226104 03/15/2005 68564 1 120 O Prohibit use of unlabeled extension cords - cords must have UL rating, min. 15A
226105 03/15/2005 68615 1 123 O Replace bulbs in light fixture
226107 03/15/2005 68565 1 124A O Prohibit use of unlabeled extension cords - cords must have UL rating, min. 15A
226109 03/15/2005 68555 1 130A O Relocate storage blocking clear access to electrical panel
226111 03/15/2005 68525 1 131 O Remove and prohibit paper covering window in door
226112 03/15/2005 68558 1 131 O Provide and maintain clear path to emergency eye wash
226118 03/15/2005 68556 1 136A O Relocate marker board blocking clear access to electrical panel
226120 03/15/2005 68629 1 136B O Relocate storage blocking clear access to inspector's test valve for fire sprinkler system
226124 03/15/2005 68630 1 139A O Relocate storage within 18" of fire sprinkler head to keep area around head clear
226126 03/15/2005 68559 1 140 O Provide and maintain clear path to emergency eye wash
226134 03/15/2005 68526 1 149 O Remove and prohibit paper covering window in door
226136 03/15/2005 68527 1 150 O Remove and prohibit paper covering window in door
226142 03/15/2005 68631 1 152A O Relocate storage within 18" of fire sprinkler head to keep area around head clear
226146 03/15/2005 68528 1 154 O Remove and prohibit paper covering window in door
226148 03/15/2005 68529 1 160 O Remove and prohibit paper covering window in door
226150 03/15/2005 68530 1 162 O Remove and prohibit paper covering window in door
226163 03/15/2005 68531 1 172 O Remove and prohibit paper covering window in door
226169 03/15/2005 68532 1 177 O Remove and prohibit paper covering window in door
226172 03/15/2005 68533 1 178 O Remove and prohibit paper covering window in door
226176 03/15/2005 68534 1 182 O Remove and prohibit paper covering window in door
226178 03/15/2005 68561 1 187A O Prohibit plugging extension cord into surge protector
226182 03/15/2005 68535 1 196 O Remove and prohibit paper covering window in door
226187 03/15/2005 68636 1 198D O Keep area within 18" of automatic fire sprinkler heads clear and unobstructed
226192 03/15/2005 68643 1 198L O Clean cobwebs from room and electrical equipment
226194 03/15/2005 69579 1 199B O Eliminate extension cord or replace with minimum 15A cord
226208 03/15/2005 69581 2 190 O Remove storage blocking clear access to electrical panel
226211 03/15/2005 68644 2 191 O Clean cobwebs from room and electrical equipment
226226 03/15/2005 68536 P 9276 O Remove and prohibit curtains on door lights
226240 03/15/2005 69589 P 9310 O Eliminate extension cord or replace with minimum 15A cord
226243 03/15/2005 68537 P 9402 O Remove and prohibit paper covering window in door
226248 03/15/2005 68538 P 9406 O Remove and prohibit paper covering window in door
226252 03/15/2005 68562 P 9407 O Prohibit plugging extension cord into surge protector
226130 03/15/2005 69577 1 144 C Provide ventilation to exterior for stove
226144 03/15/2005 68604 1 154 C Provide auto closer on corridor door
226185 03/15/2005 68605 1 198C C Provide auto closer on door
226190 03/15/2005 68606 1 198G C Provide auto closer on door
226195 03/15/2005 68607 1 199E C Provide auto closer on door
235690 03/15/2005 17463 P 9407 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
226085 03/15/2005 68637 00 9599 MS Immediately determine why PIV outside 1-199P is half open and half shut
226087 03/15/2005 68539 1 0000 MS Adjust fire door outside 1-161 to latch properly
226140 03/15/2005 68592 1 152 MS Immediately remove makeshift support for projector hung from ceiling and provide adequate support and electrical outlet for use of projector
226096 03/15/2005 68611 1 0000 OS Immediately remove broken light bulbs in courtyard adjacent to 1-199N
226098 03/15/2005 68593 1 103 OS Prohibit wedging open corridor door
226113 03/15/2005 68595 1 131 OS Prohibit wedging open corridor door
226114 03/15/2005 68596 1 132 OS Prohibit wedging open corridor door
226115 03/15/2005 68597 1 133 OS Prohibit wedging open corridor door
226119 03/15/2005 68573 1 136A OS Relocate storage cart blocking clear access to fire extinguisher adjacent to 1-136D
226122 03/15/2005 68598 1 139 OS Prohibit wedging open corridor door
226123 03/15/2005 68599 1 139A OS Prohibit wedging open fire door
226132 03/15/2005 68542 1 146 OS Relocate file cabinet blocking clear path to exterior door
226133 03/15/2005 68600 1 147 OS Prohibit wedging open corridor door
226138 03/15/2005 68543 1 151 OS Arrange desks and computer table to provide minimum 3' wide clear path to corridor door
226151 03/15/2005 68601 1 163 OS Prohibit wedging open corridor door
226160 03/15/2005 68544 1 167 OS Relocate teacher's desk blocking clear path to exterior door
226161 03/15/2005 68545 1 169 OS Relocate table and chair blocking clear path to exterior door
226162 03/15/2005 68563 1 170 OS Prohibit running extension cord under door into 1-170C
226164 03/15/2005 68587 1 175 OS Remove empty gas can from custodial cart
226174 03/15/2005 68602 1 179 OS Prohibit wedging open corridor door
226175 03/15/2005 68586 1 179C OS Prohibit storage of flammable spray paint
226177 03/15/2005 68603 1 187 OS Prohibit wedging open corridor door
226181 03/15/2005 68546 1 195 OS Relocate teacher's desk blocking clear path to exterior door
226197 03/15/2005 68640 1 199H OS Remove storage from electrical room
226201 03/15/2005 68641 1 199S OS Remove storage from electrical room
226210 03/15/2005 68642 2 191 OS Remove storage from electrical room
226227 03/15/2005 68547 P 9276 OS Relocate desks blocking clear path to rear door
226230 03/15/2005 69585 P 9279 OS Provide clear path to both doors
226234 03/15/2005 68548 P 9306 OS Relocate file cabinet blocking clear path to door
226239 03/15/2005 68549 P 9310 OS Relocate teacher's podium blocking clear path to door
226242 03/15/2005 68550 P 9311 OS Relocate table blocking clear path to rear door and arrange desks to provide minimum 3' wide clear path to door
226245 03/15/2005 68552 P 9403 OS Relocate table blocking clear path to door
226251 03/15/2005 68553 P 9407 OS Remove storage blocking clear path to door
226157 03/15/2005 65083 1 166 CS Provide a type "K" fire extinguisher within 15' of all cooking equipment (2 located on floor of 1-199T)
226081 03/15/2005 68572 00 0000 FS Provide current inspection tag for fire alarm system - tag on panel is dated 11/02 and paperwork is dated 10/03
235666 03/15/2005 17414 3 101 FS Provide heat detector in storage room (PE storage)
226276 10/15/2004 61091 00 9599 M Repair or remove damaged fence gate adjacent to Bleacher D at north play fields
191147 10/15/2004 61052 2 191 M Clean the screen at the door louver to provide make up air for the exhaust fan
226277 10/15/2004 61082 P 9279 M Provide cover on exposed electrical junction box at exterior
226278 10/15/2004 61035 P 9306 M Adjust air conditioning unit to operate correctly (see teacher)
226281 10/15/2004 61077 P 9404 O Prohibit use of plug in air freshener
235669 10/15/2004 17439 1 0000 C Install closers on all corridor doors
226254 10/15/2004 61055 1 101 C Provide fire extinguisher in office area
235681 10/15/2004 17454 P 3683 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235678 10/15/2004 17451 P 9273 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235680 10/15/2004 17453 P 9276 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235679 10/15/2004 17452 P 9277 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235677 10/15/2004 17450 P 9279 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235676 10/15/2004 17449 P 9280 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235675 10/15/2004 17448 P 9281 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235685 10/15/2004 17458 P 9304 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235684 10/15/2004 17457 P 9305 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235683 10/15/2004 17456 P 9306 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235682 10/15/2004 17455 P 9307 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235689 10/15/2004 17462 P 9308 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235688 10/15/2004 17461 P 9309 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235687 10/15/2004 17460 P 9310 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
235686 10/15/2004 17459 P 9311 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
226275 10/15/2004 61067 P 9402 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
226274 10/15/2004 61066 P 9403 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
226273 10/15/2004 61065 P 9404 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
226272 10/15/2004 61064 P 9405 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
226271 10/15/2004 61062 P 9406 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
226279 10/15/2004 61038 00 0000 OS Remove storage blocking exits from interior courtyard
191139 10/15/2004 61039 1 172 OS Remove storage blocking clear access to exit to exterior
226255 10/15/2004 61041 1 147 CS Replace frayed cord for T.V. cart