PLUMOSA SCHOOL OF THE ARTS
 
PLUMOSA SCHOOL OF THE ARTS
1712 N.E. 2nd Ave
DELRAY BEACH, 33435
FISH Drill Down
 Campus Info.
 Buildings:0 Rooms:0
 Portables:0
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
409706 04/26/2018 464059 00 0000 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report 8.28.17
373828 04/26/2018 386462 3 103 M Repair or replace rusty, damaged exterior door
397020 04/26/2018 436639 5 106 M Repair broken chair lift and provide current inspection tag in auditorium
397018 04/26/2018 436635 5 108B M Repair noisy exhaust fan in boy's dressing room bathroom
409718 04/26/2018 464080 5 192 M Make necessary repairs to fire pump system as indicated on annual inspection report dated 1.27.17
409746 01/11/2018 464143 1 122B M Repair ventilation fan in kiln room - see teacher Ms. Davis
409744 01/11/2018 464141 1 126 M Secure loose light switch cover plate
409735 01/11/2018 464123 1 141 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to windows
409736 01/11/2018 464125 1 141 M Adjust water flow for drinking spout
409734 01/11/2018 464121 1 145 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to windows
409749 01/11/2018 464152 1 148 M Secure loose escutcheon on fire sprinkler head
409753 01/11/2018 464157 1 149 M Determine cause of water damaged ceiling tiles and replace tiles in PE storage room
409743 01/11/2018 464138 1 170 M Provide current inspection tag for elevator
409765 01/11/2018 464184 1 281 M Repair exhaust fan in custodial room
409762 01/11/2018 464178 13 0000 M Secure cover on exposed electrical junction box on north exterior wall of electrical building west of auditorium
409748 01/11/2018 464148 2 001 M Repair auto closer on door to bathroom vestibule
409757 01/11/2018 464166 3 102N M Determine cause of water damaged ceiling tiles and replace tiles
409761 01/11/2018 464176 3 192 M Repair water leak from chiller lines in back of room
409760 01/11/2018 464174 3 193 M Repair air conditioning unit above door to ensure it operates as designed. Water drips
409764 01/11/2018 464182 4 0000 M Remove damaged tree blocking sidewalk at south side of custodial receiving
409763 01/11/2018 464180 5 0000 M Remove vegetation growing around glass dome in front of auditorium lobby
409733 01/11/2018 464118 1 016 O Remove and prohibit excessive flammable red vinyl sheathing used as curtain on corridor wall adjacent to 1-201
409723 01/11/2018 464092 1 127B O Prohibit plugging surge protectors on camera stands into surge protector behind teacher desk . Plug each surge protector directly into wall outlet
409726 01/11/2018 464101 1 127B O Prohibit plugging surge protector into extension cord with multiple outlet end. Plug surge protector directly into wall outlet and prohibit use of extension cord with multiple outlet end
409741 01/11/2018 464130 1 129 O Keep electrical cords inside vinyl cover strips and secure cover strips to flooring to eliminate slip hazard
409737 01/11/2018 464127 1 137 O Remove and prohibit paper covering window in corridor door
409732 01/11/2018 464114 1 201 O Remove and prohibit excessive flammable red vinyl sheathing used as curtain on wall adjacent to corridor door and adjacent to closet
409730 01/11/2018 464112 1 205 O Remove paper covering electrical outlets under writing board and adjacent to bathroom (X3)
409758 01/11/2018 464169 3 102K O Remove rags behind clothes dryer to eliminate hazardous condition
396998 01/11/2018 436594 1 127 MS Recharge fire extinguisher at front desk
409729 01/11/2018 464110 1 213 MS Adjust corridor door to latch properly
409755 01/11/2018 464162 3 101 MS Provide current inspection tag for fire extinguisher adjacent to SE corner
409759 01/11/2018 464171 3 180 MS Repair door hardware - lock hard to operate
333154 01/11/2018 297849 1 0000 N/A No violations observed
333155 01/11/2018 297851 2 0000 N/A No violations observed
333157 01/11/2018 297855 4 0000 N/A No violations observed
396992 10/02/2017 436581 1 198 M Make necessary repairs to fire sprinkler system as indicated on inspection report
396993 10/02/2017 436583 5 192 M Make necessary repairs to fire pump system as indicated on inspection report. Red tag on fire pump
347862 10/02/2017 329612 00 0000 C Prevent storm water drainage from running across sidewalk of covered walkway north of 1-135 and 1-137 and at bus loop. COR - No signs or mold or stains
388617 10/02/2017 418443 3 193 C Provide automatic fire sprinkler coverage for room. Plans indicate 1 hour wall. No fire sprinkler head visible. Room has heat detector
388638 10/02/2017 418487 5 108 C Provide automatic fire sprinkler coverage for storage mezzanine at rear of stage. Blocked by ductwork
333156 10/02/2017 297853 3 0000 N/A No violations observed
333158 10/02/2017 297857 5 0000 N/A No violations observed
397009 04/03/2017 436616 1 015 M Secure loose handrail at bottom of stairs
396996 04/03/2017 436590 1 122B M Determine cause of water damaged ceiling tiles and replace tiles
388548 04/03/2017 418297 1 127B M Provide dated flame resistance label on grey curtain in CCTV studio
397000 04/03/2017 436598 1 133 M Determine cause of water damaged ceiling tiles and replace tiles
397001 04/03/2017 436600 1 134 M Determine cause of water damaged ceiling tiles and replace tiles
397002 04/03/2017 436602 1 137 M Determine cause of water damaged ceiling tiles and replace tiles
397003 04/03/2017 436604 1 140 M Determine cause of water damaged ceiling tiles at exterior exit door and replace tiles
397004 04/03/2017 436606 1 142 M Determine cause of water damaged ceiling tiles above teacher's desk and replace tiles
397005 04/03/2017 436608 1 145 M Determine cause of water damaged ceiling tiles at windows and replace tiles
396999 04/03/2017 436596 1 170 M Provide current inspection tag for elevator (Expired 8-1-16)
397016 04/03/2017 436631 1 201A M Secure loose light switch in restroom
397015 04/03/2017 436629 1 203A M Secure loose light switch in restroom
397013 04/03/2017 436625 1 222B M Secure loose light switch in girl's restroom
397011 04/03/2017 436620 1 225C M Repair non-working faucet in boy's bathroom
397012 04/03/2017 436623 1 225C M Secure loose light switch in boy's restroom
397010 04/03/2017 436618 1 281 M Provide cover on exposed electrical junction box on east wall
397007 04/03/2017 436612 2 001 M Repair emergency lighting in bathroom vestibule
397006 04/03/2017 436610 2 101 M Provide cover for exposed electrical outlet on exterior wall adjacent to 2-103
397058 04/03/2017 436711 3 0000 M Repair broken lawn sprinkler irrigation head along sidewalk at end of retainer wall on the west side of Building 3 (creating a wash-out along sidewalk)
397045 04/03/2017 436692 3 102A M Repair wall damage around south exit door
397040 04/03/2017 436681 3 102A M Place ceiling tiles back into metal ceiling grid at south end of serving line
388628 04/03/2017 418467 3 190 M Shield electrical panel L20A from sprinkler line above it
388630 04/03/2017 418471 3 191 M Insulate hot water lines
397051 04/03/2017 436705 3 191 M Repair or replace rusted louvers on metal entrance door
397030 04/03/2017 436661 4 192 M Provide current emergency lighting and generator certificate (last certificate was dated 7-13-15)
397034 04/03/2017 436669 4 194 M Remove vegetation growing inside chiller yard
397023 04/03/2017 436645 5 0000 M Remove trees growing from above and underneath glass canopy at west entrance to Auditorium
397017 04/03/2017 436633 5 004 M Determine cause of water damaged ceiling tiles in exit corridor from stage and replace tiles
397019 04/03/2017 436637 5 108 M Repair two emergency lights on center catwalk at rear of stage
373824 04/03/2017 386453 5 190 M Make necessary repairs to rusty areas of air handler unit
397024 04/03/2017 436647 00 0000 O Remove pile of debris from open field west of Building 4 to prevent rodent infestation and flying debris during high winds
397014 04/03/2017 436627 1 219B O Replace burned out bulbs in light fixture inside closet
397042 04/03/2017 436686 3 102K O Clean area behind cloths dryer to prevent fire hazard
396994 04/03/2017 436586 1 190 MS Provide current inspection tag for fire extinguisher
396997 04/03/2017 436592 1 195 MS Provide current inspection tag for fire extinguisher
396995 04/03/2017 436588 1 222B MS Provide current inspection tag for fire extinguisher
397008 04/03/2017 436614 2 001 MS Provide current inspection tag for fire extinguisher
397046 04/03/2017 436697 3 190 MS Provide current inspection tag for fire extinguisher
397048 04/03/2017 436701 3 191 MS Provide current inspection tag for fire extinguisher
397037 04/03/2017 436675 3 194 MS Provide current inspection tag for fire extinguisher located inside telecom room
397025 04/03/2017 436649 4 180A MS Provide current inspection tag for fire extinguisher in custodial locker room
397027 04/03/2017 436655 4 181 MS Provide current inspection tag for fire extinguisher in golf cart storage room
397028 04/03/2017 436657 4 182 MS Provide current inspection tag for fire extinguisher in equipment storage room
397029 04/03/2017 436659 4 183 MS Provide current inspection tag for fire extinguisher in flammable storage room
397021 04/03/2017 436641 5 201 MS Replace missing fire extinguisher
397022 04/03/2017 436643 5 002 OS Remove and prohibit storage from bottom landing of stairway
388559 10/24/2016 418320 1 198 M Make necessary repairs to fire sprinkler system as indicated on inspection report
373833 10/24/2016 386472 2 0000 M Refinish rusty areas of PE pavilion
388635 10/24/2016 418481 5 192 M Make necessary repairs to fire pump system as indicated on inspection report. Red tag on fire pump
347902 06/02/2016 329695 5 180 C Provide automatic fire sprinkler coverage for custodial closet, no head visible
388552 05/06/2016 418305 4 0000 MS Provide current inspection tags for all fire extinguishers throughout building
388553 05/06/2016 418307 5 0000 MS Provide current inspection tags for all fire extinguishers throughout building
388586 05/04/2016 418377 1 290 M Replace missing latch for electrical panel 1MA2-2
388574 04/12/2016 418351 1 014 M Adjust corridor door to exterior to latch properly
388578 04/12/2016 418360 1 144A M Determine cause of water damaged ceiling tiles and replace tiles
388596 04/12/2016 418401 4 194 M Remove trees growing in chiller compound
388637 04/12/2016 418485 5 108 M Repair emergency lighting at ladder on pin rail and at ladder on loading rail
388551 04/12/2016 418303 5 180 M Provide cover on 2 exposed electrical junction boxes above ceiling to north
388554 04/12/2016 418309 5 194 M Replace missing ceiling tiles
388570 04/12/2016 418343 1 123 C Provide illuminated exit sign at corridor door. Room is assembly space
388639 04/06/2016 418489 1 0000 M Replace broken and sharp plexiglass panel on exit gate west of 1-127
388640 04/06/2016 418491 1 0000 M Replace broken green cover for box in grassed area north of 1-139
388555 04/06/2016 418311 1 009 M Replace broken hold open magnet on corridor door to stairs 1-010
388566 04/06/2016 418334 1 122 M Secure loose faucet to double sink
388568 04/06/2016 418338 1 122B M Greenfield conduit has pulled out of fitting on control box of west kiln. Secure conduit to fiting
388562 04/06/2016 418326 1 122D M Adjust gate to latch properly
388567 04/06/2016 418336 1 122E M Replace missing light switch plate
388561 04/06/2016 418324 1 127B M Adjust door to exterior to latch properly
388549 04/06/2016 418299 1 132A M Replace missing escutcheon on fire sprinkler head
388572 04/06/2016 418347 1 140 M Adjust door to exterior to latch properly
388573 04/06/2016 418349 1 142 M Adjust door to exterior to latch properly
388577 04/06/2016 418357 1 142B M Repair OUT OF ORDER toilet
388571 04/06/2016 418345 1 195 M Secure 2 loose grounds to terminal bar
388588 04/06/2016 418382 1 204A M Replace missing light switch plate
388589 04/06/2016 418384 1 213A M Repair leaking toilet supply line
388590 04/06/2016 418386 1 216 M Secure loose drinking fountain
388593 04/06/2016 418392 1 221A M Repair door to open and close properly. Door hits frame
388591 04/06/2016 418388 1 281 M Repair damaged wall at corridor. Cover exposed corner bead and install corner guard to prevent further damage to wall
388601 04/06/2016 418411 3 0000 M Adjust gate east of 3-001 to latch properly. Sticky latch
388631 04/06/2016 418473 3 102 M Nozzle for wash down spray at 2 compartment sink leaks when shut off. Repair valve
388629 04/06/2016 418469 3 190 M Replace missing screws for cover of electrical panel L20A
388620 04/06/2016 418450 3 192 M Provide cover on exposed electrical junction box at light switch
388632 04/06/2016 418475 3 193 M Replace missing screws for cover of panel P20
388633 04/06/2016 418477 3 193 M Replace missing screws for cover of panel 3D
388595 04/06/2016 418397 4 180 M Adjust double door to exterior to latch properly
388636 04/06/2016 418483 5 108E M Replace missing ceiling tiles
388546 04/06/2016 418293 00 0 O No access was available to 1-121. Please provide access to this room during the report review meeting
388550 04/06/2016 418301 1 137A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
388576 04/06/2016 418355 1 140B O Keep area within 18 inches of fire sprinkler head clear and unobstructed
388547 04/06/2016 418295 1 191 O Prohibit charging batteries in room
388587 04/06/2016 418380 1 205 O Remove and prohibit attaching paper to blinds. Paper can be attached to walls, windows or on string lines against the wall or in front of the windows
388594 04/06/2016 418394 1 220A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
388592 04/06/2016 418390 1 225A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
388600 04/06/2016 418409 2 103 O Provide clear access to electrical panel
388597 04/06/2016 418404 4 182 O Prohibit charging batteries in room
388563 04/06/2016 418328 1 101 MS Adjust corridor door to latch properly
388565 04/06/2016 418332 1 124 MS Adjust corridor door to latch properly
388556 04/06/2016 418313 1 134 MS Adjust corridor door to latch properly
388557 04/06/2016 418315 1 135 MS Adjust corridor door to latch properly
388575 04/06/2016 418353 1 145 MS Adjust corridor door to latch properly
388564 04/06/2016 418330 1 192 MS Adjust corridor door to latch properly
388558 04/06/2016 418317 1 199 MS Adjust corridor door to latch properly
388579 04/06/2016 418363 1 207 MS Adjust corridor door to latch properly
388582 04/06/2016 418369 1 211 MS Adjust corridor door to latch properly
388580 04/06/2016 418365 1 217 MS Adjust corridor door to latch properly
388581 04/06/2016 418367 1 219 MS Adjust corridor door to latch properly
388583 04/06/2016 418371 1 223 MS Adjust corridor door to latch properly
388584 04/06/2016 418373 1 225 MS Adjust corridor door to latch properly
388585 04/06/2016 418375 1 227 MS Adjust corridor door to latch properly
388599 04/06/2016 418406 2 001 MS Provide current inspection tag for fire extinguisher
388618 04/06/2016 418448 3 195 MS Provide current inspection tag for fire extinguisher
388569 04/06/2016 418340 1 123 OS Maintain 3 foot clear aisle to rear exit
388560 04/06/2016 418322 1 198 OS Remove storage (computer monitors) from mechanical room
388634 04/06/2016 418479 5 108 OS Remove cord laying on stairs at stage right
373811 12/21/2015 386424 00 0000 C Provide fencing around transformers east of building 4
347905 12/21/2015 329701 5 108A C Provide automatic fire sprinkler coverage for closet, no head visible
347911 04/10/2015 329714 00 0000 M Fill and stabilize banks of retention pond at bus loop and pond to south
373825 04/10/2015 386455 00 9599 M Fill hole in ground at sidewalk west of 4-190
373823 04/10/2015 386451 00 9599 M Repair broken in ground landscape sprinkler south of 5-190
373846 04/10/2015 386498 1 001 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to 1-190
373808 04/10/2015 386418 1 007 M Adjust door closer to control speed of closing door
373809 04/10/2015 386420 1 007 M Repair corridor doors to close properly, doors drag on floor
373841 04/10/2015 386488 1 009 M Determine cause of water damaged ceiling tiles and replace tiles
373845 04/10/2015 386496 1 010 M Replace damaged floor tiles at exterior door
373840 04/10/2015 386486 1 011 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to 1-198
373835 04/10/2015 386476 1 014 M Replace missing escutcheon on fire sprinkler head at exterior door
373836 04/10/2015 386478 1 014 M Adjust door closer on exterior door to control speed of closing door
373820 04/10/2015 386445 1 015 M Repair doors at second floor landing to close properly
373842 04/10/2015 386490 1 122 M Make repairs to broken concrete threshold at exterior door
373843 04/10/2015 386492 1 126A M Make repairs to non functioning toilet
373844 04/10/2015 386494 1 128 M Adjust auto opener on corridor door, staff reports that door can be difficult to open
373838 04/10/2015 386482 1 140 M Repair loose corridor door handle
373837 04/10/2015 386480 1 141 M Determine cause of water damaged ceiling tiles and replace tiles
373806 04/10/2015 386414 1 194 M Repair exterior door to close and latch properly
373839 04/10/2015 386484 1 199A M Repair door to close and latch properly
373812 04/10/2015 386426 1 201 M Repair door to close and latch properly
373814 04/10/2015 386430 1 210C M Replace missing escutcheon on fire sprinkler head
373815 04/10/2015 386432 1 210C M Determine cause of water damaged ceiling tiles and replace tiles
373816 04/10/2015 386437 1 211A M Repair non functioning toilet
373817 04/10/2015 386439 1 221 M Adjust door closer to control speed of closing door
373818 04/10/2015 386441 1 222B M Repair non functioning toilet
373819 04/10/2015 386443 1 227A M Repair door to open and close properly
373807 04/10/2015 386416 11 193 M Repair exterior door to close and latch properly
373834 04/10/2015 386474 2 0000 M Repair damaged rain gutter - downspout on south side of pavilion
373830 04/10/2015 386466 3 002 M Replace missing escutcheon on fire sprinkler head
373829 04/10/2015 386464 3 103 M Replace missing escutcheons on fire sprinkler heads (x2)
373832 04/10/2015 386470 3 192 M Repair door to close and latch properly
363370 04/10/2015 363724 3 194 M Provide correct signage indicating room name at appropriate height with raised and Braille characters, sign incorrectly reads Mechanical Room, is actually a Telecommunications Room
373827 04/10/2015 386459 4 193 M Repair leak and replace missing insulation at unit PP-1
373826 04/10/2015 386457 4 194 M Remove trees growing in chiller yard
373822 04/10/2015 386449 5 106 M Provide current inspection tag for chairlift elevator
363362 04/10/2015 363708 5 191 M Provide correct signage indicating room name at height with raised and Braille characters, sign incorrectly reads Electrical Room, is actually a storage room
373810 04/10/2015 386422 1 201B O Prohibit use of multi outlet electrical adaptor
373813 04/10/2015 386428 1 206A O Remove and prohibit air freshener
373847 04/10/2015 386500 00 0000 C Repair and secure bent, loose pieces of trim on columns at covered walk at parent drop off
363371 04/10/2015 363726 2 001 MS Provide current inspection tag for fire extinguisher, recharge fire extingiusher
373831 04/10/2015 386468 3 192 MS Provide current inspection tag for fire extinguisher
373821 04/10/2015 386447 5 194 MS Provide current inspection tag for fire extinguisher
347922 04/10/2015 329738 13 0000 N/A Building Not in Use, Utilities Disconnected
363326 12/15/2014 363627 1 190 M Provide correct signage indicating room name at appropriate height with raised and Braille characters. Current sign incorrectly reads Electrical Room, is actually a Telecommunications room
363327 12/15/2014 363629 1 191 M Provide correct signage indicating room name at appropriate height with raised and Braille characters. Current sign incorrectly reads Telecommunications room, is actually a storage room
363325 05/12/2014 363625 1 007 M Repair corridor doors to close properly
363388 05/12/2014 363765 1 007 M Repair door at second floor landing to close properly
363320 05/12/2014 363615 1 009 M Repair or replace damaged floor tile at exterior door
363386 05/12/2014 363761 1 010 M Repair door at second floor landing to close properly (adjacent to 1-292)
363287 05/12/2014 363542 1 011 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to 1-198
363288 05/12/2014 363544 1 011 M Adjust door closer on west exterior doors adjacent to 1-198 to control speed of closing doors
363319 05/12/2014 363613 1 015 M Secure loose handrail on stairs, lower run
363328 05/12/2014 363631 1 124 M Adjust door closer to control speed of closing door
363329 05/12/2014 363634 1 124A M Secure loose light switch
363289 05/12/2014 363546 1 134C M Repair out of order toilet
363290 05/12/2014 363548 1 135 M Determine cause of water damaged ceiling tiles and replace tiles
363291 05/12/2014 363550 1 140 M Adjust door closer on exterior door to control speed of closing door
363292 05/12/2014 363552 1 141 M Determine cause of water damaged ceiling tiles and replace tiles
363293 05/12/2014 363555 1 142 M Adjust door closer on exterior door to control speed of closing door
363296 05/12/2014 363565 1 144 M Adjust door closer on exterior door to control speed of closing door
363298 05/12/2014 363567 1 144A M Determine cause of water damaged ceiling tiles and replace tiles
363317 05/12/2014 363609 1 146 M Adjust door closer on exterior door to control speed of closing door
363315 05/12/2014 363605 1 147 M Replace missing ceiling tiles
363316 05/12/2014 363607 1 147 M Determine cause of water damaged ceiling tiles and replace tiles
363324 05/12/2014 363623 1 193 M Adjust exterior door to close and latch properly
363323 05/12/2014 363621 1 194 M Repair exterior door to close properly
363384 05/12/2014 363757 1 210C M Determine cause of water damaged ceiling tiles and replace tiles
363382 05/12/2014 363752 1 213A M Make repairs to toilet per out of order sign
363383 05/12/2014 363755 1 213A M Repair loose light switch
363381 05/12/2014 363750 1 219A M Make repairs to toilet per out of order sign
363379 05/12/2014 363743 1 221B M Make repairs to toilet per out of order sign
363373 05/12/2014 363730 1 225B M Repair non-functioning toilet
363374 05/12/2014 363732 1 293 M Adjust door closer to control speed of closing door
363333 05/12/2014 363642 13 101 M Repair broken emergency lighting (N/A building not in use, utilities to building disconnected)
363334 05/12/2014 363644 13 101 M Repair light fixture, lights do not work (N/A building not in use, utilities to building disconnected)
363335 05/12/2014 363646 13 101 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters (N/A building not in use, utilities to building disconnected)
363336 05/12/2014 363648 13 101 M Replace missing panel schedule for electrical panel (N/A building not in use, utilities to building disconnected)
363243 05/12/2014 363437 3 101 M Adjust door closer on north exterior doors at 3-103 to control speed of closing door
363284 05/12/2014 363536 3 102 M Provide current inspection tag for kitchen hood cleaning
363285 05/12/2014 363538 3 102 M Adjust east exterior door to close properly
363275 05/12/2014 363508 3 102G M Adjust door so that lock is properly alligned
363283 05/12/2014 363532 3 102N M Determine cause of water damaged ceiling tiles and replace tiles
363286 05/12/2014 363540 3 180 M Replace missing ceiling hatch
333004 05/12/2014 297519 3 180 M Replace heavily rusted louver on door
363330 05/12/2014 363636 4 194 M Remove trees growing in chiller yard
363367 05/12/2014 363718 5 004 M Repair north exterior door to close and latch properly
363338 05/12/2014 363654 5 102A M Secure hanging light fixture
363339 05/12/2014 363657 5 106 M Repair lights in exit signs
363369 05/12/2014 363722 5 108 M Verify that all stage lights are secured with a safety cable. Due to height of lights not all are visible from stage level
363368 05/12/2014 363720 5 180 M Prohibit storage of expired fire extinguisher
363340 05/12/2014 363659 5 191 M Remove and prohibit storage of expired fire extinguisher
363364 05/12/2014 363712 5 193 M Provide cover on exposed electrical junction box above door
363365 05/12/2014 363714 5 193 M Prohibit storage of expired fire extinguisher
363366 05/12/2014 363716 5 193 M Repair door to close and latch properly
363363 05/12/2014 363710 5 194 M No access was available to this room, sign on door states active alarm. Please provide access to this room during the report review meeting
363322 05/12/2014 363619 1 127B O Prohibit running electrical cords under carpet
363295 05/12/2014 363560 1 140 O Relocate paper covering 1-140B sign so that sign is visible
363294 05/12/2014 363558 1 143A O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
363318 05/12/2014 363611 1 149 O Relocate and prohibit storage blocking roof access ladder
363387 05/12/2014 363763 1 207 O Relocate anchor chart to maintain clear view of 1-207B sign
363375 05/12/2014 363734 1 223 O Prohibit blocking view of 1-223A and 1-020 signs
363372 05/12/2014 363728 2 102 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
363245 05/12/2014 363443 3 101A O Prohibit charging floor cleaning machine (batteries) in room
363274 05/12/2014 363503 5 202 O Prohibit storing 9V batteries so that contacts touch, creating a fire hazard. Cover contacts with electrical tape to eliminiate hazard
333000 05/12/2014 297509 3 003 C Change signage indicating room name and number with raised and Braille characters from 3-103A to 3-003 (bathroom vestibule)
363273 05/12/2014 363493 3 101 C Provide illuminated exit sign in covered walk north of 3-101 with chevron directing egress traffic to the west (left) when exiting building (to the north)
363268 05/12/2014 363490 3 193 C Verify that walls of electrical room are two hour rated walls and label walls or provide automatic fire sprinkler coverage for room
363385 05/12/2014 363759 1 210 MS Provide current inspection tag for fire extinguisher (located in cabinet)
363332 05/12/2014 363640 4 180A MS Provide current inspection tag for fire extinguisher
363331 05/12/2014 363638 4 191 MS Provide current inspection tag for fire extinguisher
363321 05/12/2014 363617 1 127B OS Maintain clear aisle to exterior exit
363378 05/12/2014 363740 1 220 OS Prohibit hold open device (door stop) on fire door
363380 05/12/2014 363748 1 221 OS Remove and prohibit use of space heater
363377 05/12/2014 363738 1 222 OS relocate desk to maintain clear aisle to exit
363337 05/12/2014 363652 5 190 CS Verify width of ducts (high locations) and if in excess of 4 feet wide provide automatic fire sprinkler coverage for areas under ducts which are in excess of 4 feet wide
347898 05/12/2014 329683 5 192 CS Provide automatic fire sprinkler coverage under duct in excess of 4 feet wide at north side of room (NA per M. Lodge, current coverage is sufficient)
347909 05/12/2014 329709 5 194 FS Provide fire alarm system inspection report
333088 01/24/2014 297705 00 9599 M Replace missing wrench and padlock for PIV at SE corner of Bldg. 5 - facing 5-192
347820 01/24/2014 329522 1 101 FS Repair punch list as indicated on fire alarm inspection report
332999 04/29/2013 297507 00 0000 CS Provide suitable area for recharging floor cleaning machines
347824 04/24/2013 329531 00 0000 M Replace lock on gate of fencing around ITV tower
347833 04/24/2013 329548 3 002 M Secure loose light sensor
347906 04/24/2013 329703 5 108 M Repair emergency lighting X 3 on mezzanine behind stage
347907 04/24/2013 329705 5 108 M Repair emergency lighting on 1st rail above stage
333153 04/24/2013 297846 5 202 M Repair latch hardware on top of ladder to work properly - hatch did not latch
347917 04/24/2013 329726 1 015 MS Adjust fire doors at top of stairs to latch properly. Doors hit, adjust hinges
347908 04/24/2013 329707 5 108 MS Provide current inspection tags for fire extinguishers on 2nd rail above stage and on grid iron
347854 04/24/2013 329593 5 202 OS Prohibit running electrical cord through catwalk access hatch
347877 04/19/2013 329640 00 0000 M Provide lock on fiberglass enclosure for pump outside of 1-128
347819 04/19/2013 329520 00 0000 M Unband all trees and remove bracing and stakes
332998 04/19/2013 297505 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
347871 04/19/2013 329629 1 122B M Determine cause of water damaged ceiling tiles and replace tiles
347872 04/19/2013 329631 1 122B M Finish interior wall at door frame
347823 04/19/2013 329528 1 123 M Adjust door to exterior to latch properly
347875 04/19/2013 329636 1 124B M Repair door handle, latch sticks and will not retract
347836 04/19/2013 329553 1 127 M Repair leaking backflow device. Wrong room number
347850 04/19/2013 329584 1 127B M Provide lock for drawers at teachers station
347837 04/19/2013 329556 1 127E M Repair electric faucet not working
347838 04/19/2013 329558 1 127H M Repair electric faucet, not working
347882 04/19/2013 329650 1 128 M Remove and reinstall door closer correctly. Closer arm is damaging door
347839 04/19/2013 329560 1 131 M Repair electric faucet, not working
347840 04/19/2013 329562 1 132A M Repair electric faucet, not working
332852 04/19/2013 297193 1 133A M Secure loose light switch
347848 04/19/2013 329578 1 136 M Replace missing ceiling tiles
347841 04/19/2013 329564 1 138A M Repair electric faucet, not working
347832 04/19/2013 329546 1 141 M Determine cause of water damaged ceiling tiles and replace tiles
347842 04/19/2013 329566 1 144C M Repair electric faucet, not working
347889 04/19/2013 329667 1 148 M Provide covers on 2 exposed electrical junction boxes
347831 04/19/2013 329544 1 149 M Determine cause of water damaged ceiling tiles and replace tiles
347884 04/19/2013 329656 1 170 M Provide current inspection tag for elevator
347852 04/19/2013 329588 1 181 M Anchor shelving to wall
347822 04/19/2013 329526 1 191 M Secure loose ground on ground bar, 2nd from left
347826 04/19/2013 329535 1 192 M Secure loose ground to ground bar, right side
347849 04/19/2013 329580 1 195 M Secure loose ground to ground bar, 2nd from top
347887 04/19/2013 329663 1 199B M Determine cause of water damaged ceiling tiles and replace tiles
347912 04/19/2013 329716 1 204A M Repair leaking toilet supply line
347921 04/19/2013 329735 1 208 M Repair damaged intercom button
347914 04/19/2013 329720 1 210 M Determine cause of water damaged ceiling tiles and replace tiles
347915 04/19/2013 329722 1 210 M Replace missing escutcheon on fire sprinkler head
347910 04/19/2013 329711 1 211B M Change out lock in door. Appears to be construction lock and teacher has no key
347845 04/19/2013 329572 1 212A M Repair electric faucet, not working
347920 04/19/2013 329732 1 215B M Repair door handle, will not retract latch
347919 04/19/2013 329730 1 218B M Secure loose light sensor
347918 04/19/2013 329728 1 218C M Replace missing strainer for faucet
347829 04/19/2013 329540 1 280 M Repair damaged wall at floor sink and provide splash guard
347900 04/19/2013 329690 13 101 M Repair emergency lighting in small electrical building SW of building 5. No electricity to building, building not in use
347870 04/19/2013 329625 2 101 M Repair NE downspout. Downspout strap is loose and sticking out
347844 04/19/2013 329570 2 101A M Repair electric faucet, not working
347890 04/19/2013 329670 3 104A M Repair 2nd toilet to flush
347892 04/19/2013 329675 3 105A M Repair 2nd toilet to flush
347843 04/19/2013 329568 3 105C M Repair electric faucet, not working
333002 04/19/2013 297515 3 180 M Repair damaged wall finish around plumbing valves
333003 04/19/2013 297517 3 180 M Secure exhaust fan cover to ceiling
347865 04/19/2013 329618 4 193 M Anchor chemical feed pumps
347828 04/19/2013 329538 4 194 M Remove trees growing in cooling tower compound
347846 04/19/2013 329574 5 105 M Repair electric faucet in handicapped stall, not working
347899 04/19/2013 329688 5 106 M Provide current inspection tag for wheel chair lift
347904 04/19/2013 329699 5 108C M Determine cause of water damaged ceiling tiles and replace tiles. Check for possible fire sprinkler leak
347903 04/19/2013 329697 5 193 M Secure covers for panels H and L2
347834 04/19/2013 329550 5 193 M Repair chilled water pump, bad bearing
347835 04/19/2013 329552 5 193 M Repair leaking backflow device.
347853 04/19/2013 329590 5 202 M Replace missing ceiling tiles
347818 04/19/2013 329518 00 0 O No access was available to 1-121. Please provide access to this room during the report review meeting
347847 04/19/2013 329576 1 131 O Keep shower drain filled with water, every 2 months pour 1 quart of water down drain
347817 04/19/2013 329516 1 138 O Uncover electrical outlets
347867 04/19/2013 329622 2 103 O Provide clear access to electrical panel
347830 04/19/2013 329542 3 103A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
347864 04/19/2013 329616 3 190 O Flush floor drain with water. Every month pour 1 quart of water down drain. Room smelled of sewer gas
347861 04/19/2013 329610 5 202 O Safety cable all lights to rail of catwalk above audience
333089 04/19/2013 297707 5 193 C Verify whether ventilation in electrical room is adequate - room is hot
347851 04/19/2013 329586 1 010 MS Adjust fire door at top of stairs to latch properly. Drags on floor
347863 04/19/2013 329614 1 015 MS Adjust fire door at bottom of stairs to latch properly
347825 04/19/2013 329533 1 180 MS Provide current inspection tag for fire extinguisher
347913 04/19/2013 329718 1 207 MS Adjust corridor door to latch properly
333001 04/19/2013 297512 3 180 MS Replace missing hatch on ceiling to prevent spread of fire or smoke
347866 04/19/2013 329620 4 193 MS Remove 2 boxes of construction close out documents from room
347894 04/19/2013 329679 5 192 MS Provide current inspection tag for fire extinguisher
332991 04/19/2013 297491 5 201 MS Relocate fire extinguisher from behind door to be on wall adjacent to door latch
347880 04/19/2013 329645 1 007 OS Prohibit storing recycle bins in stair enclosure
347916 04/19/2013 329724 1 017 OS Remove and prohibit storage in corridor adjacent to 1-212
347886 04/19/2013 329660 1 137A OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
347821 04/19/2013 329524 1 190 OS Prohibit charging batteries in room
347901 04/19/2013 329692 5 108F OS Provide clear access to fire extinguisher
332844 12/21/2012 297178 2 0000 MS Provide current inspection tag for fire sprinkler system behind Bldg. 2
332995 12/21/2012 297499 5 192 MS Provide current inspection tag for fire pump
332973 03/30/2012 297454 1 104 M Repair door to open and close properly - door rubs on frame
332864 03/30/2012 297218 1 141 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to windows
332866 03/30/2012 297221 1 143 M Secure ceiling tile in place
332868 03/30/2012 297225 1 148 M Replace missing cover plate for light switch
332871 03/30/2012 297231 1 180 M Repair door to open and close properly - door rubs on frame
332873 03/30/2012 297235 1 195 M Secure ceiling tile in place
332969 03/30/2012 297447 1 203B M Replace missing escutcheon on fire sprinkler head
332970 03/30/2012 297449 1 212A M Replace missing escutcheon on fire sprinkler head
332849 03/30/2012 297187 3 102A M Replace missing ceiling tiles
332982 03/30/2012 297473 3 102D M Remove old room number above door (20-102C)
332851 03/30/2012 297190 3 102N M Provide door stop on floor in fornt of fire extinguisher to prohibit door from slamming into the fire extinguisher
332983 03/30/2012 297475 5 103A M Remove old room number (1102)
332986 03/30/2012 297481 5 108A M Replace missing ceiling tiles
332987 03/30/2012 297483 5 108C M Repair emergency escape window to open properly
332985 03/30/2012 297479 5 108C M Replace missing ceiling tiles
332984 03/30/2012 297477 5 108E M Replace missing ceiling tiles
332994 03/30/2012 297497 5 192 M Patch holes in masonry walls
332971 03/30/2012 297451 1 115 O Prohibit plugging surge protector into surge protector under desk - plug each surge protector directly into wall outlet
332857 03/30/2012 297198 1 127B O Eliminate (3) plug adaptors plugged into extension cord then plugged into surge protector - replace with a surge protector that can be plugged directly into wall outlet (X2)
332863 03/30/2012 297208 1 127B O Provide electrical cord cover strips for cords running across floor and secure cover strips to floor to eliminate trip hazard
332945 03/30/2012 297400 1 129 O Eliminate brown extension cord with multiple outlet end between pianos adjacent to closet or replace with a surge protector
332950 03/30/2012 297404 1 129 O Secure electrical cord cover strip to flooring to eliminate slip hazard - adjacent to closet
332966 03/30/2012 297440 1 206 O Eliminate white extension cord with multiple outlet end under teacher's desk or replace with a surge protector
332967 03/30/2012 297444 1 227 O Eliminate white extension cord with multiple outlet end under teacher's desk or replace with a surge protector
332981 03/30/2012 297468 00 0000 C Modify all corners of block columns along west covered walkway of Bldg. 1 to eliminate sharp edges
332847 03/30/2012 297182 3 101 C Install maximum occupancy signage of 487 occupants
332874 03/30/2012 297238 1 195 MS Replace missing fire extinguisher
332843 03/30/2012 297176 2 001 MS Provide current inspection tag for fire extinguisher
332830 03/30/2012 297146 3 190 MS Provide current inspection tag for fire extinguisher
332997 03/30/2012 297503 3 192 MS Provide current inspection tag for fire sprinkler system
332990 03/30/2012 297489 5 0000 MS Provide current inspection tag for fire extinguisher on catwalk above 5-202
332989 03/30/2012 297487 5 102A MS Close hatch on ceiling
332988 03/30/2012 297485 5 108 MS Replace missing fire extinguisher on stage adjacent to hallway 5-004
332996 03/30/2012 297501 5 192 MS Require DP Plumbing and Fire Protection to fill information on inspection tag for fire sprinkler system
332993 03/30/2012 297495 5 193 MS Replace missing hatch on ceiling to prevent spread of fire or smoke
332992 03/30/2012 297493 5 194 MS Provide current inspection tag for fire sprinkler system
332867 03/30/2012 297223 1 145A OS Remove and prohibit use of toaster
332869 03/30/2012 297227 1 149 OS Relocate storage to keep area within 18" of fire sprinkler head clear and unobstructed
332872 03/30/2012 297233 1 191 OS Prohibit charging batteries for floor cleaning machines in room
332964 03/30/2012 297438 1 207 OS Prohibit use of wedge as hold open device on corridor door
332870 03/30/2012 297229 1 210C OS Relocate storage to keep area within 18" of fire sprinkler head clear and unobstructed
332963 03/30/2012 297435 1 212 OS Prohibit use of wedge as hold open device on corridor door
332961 03/30/2012 297429 1 223 OS Prohibit use of wedge as hold open device on corridor door
332978 03/30/2012 297464 00 0000 FS Provide certification that fire alarm system has been tested and is fully operational - Alarm panel indicated trouble and inspection report was not available for review