CRESTWOOD MIDDLE
 
CRESTWOOD MIDDLE
64 SPARROW DR
ROYAL PALM BEACH, 33411
FISH Drill Down
 Campus Info.
 Buildings:3 Rooms:352
 Portables:13
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
402684 11/30/2017 448818 00 0000 M Anchor or remove 2 shipping containers at track
416567 11/30/2017 478784 1 101 M Repair damaged corner wall finish adjacent to Multi Com 2000 unit
402675 11/30/2017 448796 1 101G M Repair exhaust fan in bathroom
416449 11/30/2017 478527 1 102 M Repair or replace broken floor tiles on north side of room at 1-102B and 1-002 corridor
402666 11/30/2017 448778 1 103A M Repair exhaust fan in bathroom
402667 11/30/2017 448780 1 103B M Repair exhaust fan in bathroom
416447 11/30/2017 478523 1 104 M Fill void in electrical panels LK and HK
416448 11/30/2017 478525 1 104H M Adjust door of walk in refrigerator to close properly
402680 11/30/2017 448808 1 109M M Repair exhaust fan in bathroom
402679 11/30/2017 448805 1 109P M Repair exhaust fan in bathroom
416460 11/30/2017 478550 1 112 M Refinish or repaint peeling walls adjacent to window and 1-113
416489 11/30/2017 478622 1 113 M Repair peeling wall finish at windows, 1-113A and 1-112 door
416492 11/30/2017 478628 1 113B M Refinish peeling wall finish
416490 11/30/2017 478624 1 113C M Repair exhaust fan in bathroom
416491 11/30/2017 478626 1 113C M Repair damaged ceiling
416457 11/30/2017 478544 1 121E M Provide cover on exposed electrical junction box on wall
416564 11/30/2017 478780 1 153 M Adjust exterior doors to latch properly
402682 11/30/2017 448812 1 153 M Repair inoperable purge fan
416514 11/30/2017 478676 1 160 M Adjust door closer on exterior door to control speed of closing door
416515 11/30/2017 478679 1 160 M Replace missing ceiling tiles
416453 11/30/2017 478536 1 180 M Provide cover on exposed electrical junction box on wall
416563 11/30/2017 478778 1 182 M Repair damaged wall finish
416446 11/30/2017 478521 1 183 M Repair damaged wall finish
416451 11/30/2017 478531 1 190 M Chain cylinder to wall
416452 11/30/2017 478534 1 190 M Provide current certification that all student occupied spaces have emergency lights and all are operable
416561 11/30/2017 478774 1 199C M Repair leaking air conditioning system to ensure it operates as designed
416559 11/30/2017 478770 2 104 M Repair or replace damaged bathroom stall partitions
416560 11/30/2017 478772 2 190 M Repair leaking air conditioning system to ensure it operates as designed
416528 11/30/2017 478705 3 002 M Determine cause of water damaged ceiling tiles adjacent to 3-120 and replace tiles
416557 11/30/2017 478764 3 005 M Adjust door closer to control speed of closing door
416539 11/30/2017 478728 3 009 M Repair damaged wall at 2nd floor landing
416520 11/30/2017 478689 3 108 M Determine cause of water damaged ceiling tiles and replace tiles
416525 11/30/2017 478700 3 115 M Determine cause of water damaged ceiling tiles and replace tiles
416530 11/30/2017 478709 3 120 M Determine cause of water damaged ceiling tiles and replace tiles
416533 11/30/2017 478714 3 122 M Repair damaged wall finish adjacent to teachers desk
416538 11/30/2017 478721 3 124 M Repair or replace damaged vent on AC unit
416534 11/30/2017 478718 3 125 M Determine cause of water damaged ceiling tiles and replace tiles
416558 11/30/2017 478767 3 180 M Make repairs as noted on fire sprinkler inspection report
416517 11/30/2017 478683 3 207 M Adjust door to latch properly
416551 11/30/2017 478749 3 207A M Replace door lock cylinder to be on the A key, not construction key
416547 11/30/2017 478743 3 212A M Repair or replace damaged wall tile behind accessible stall door
402835 11/30/2017 449138 3 214 M Repair exhaust fan in bathroom
402836 11/30/2017 449140 3 216 M Repair exhaust fan in bathroom
416544 11/30/2017 478739 3 219 M Determine cause of water damaged ceiling tiles and replace tiles
416545 11/30/2017 478741 3 219A M Determine cause of water damaged ceiling tiles and replace tiles
416541 11/30/2017 478730 3 225 M Repair or replace damaged vent on AC unit
416554 11/30/2017 478759 3 9599 M Repair gate west of Bldg. 3 to open properly
416458 11/30/2017 478546 1 123 O Prohibit plugging refrigerator into orange multi outlet extension cord, prohibit use of multi outlet extension cord. Plug refrigerator directly into permanent electrical outlet
416513 11/30/2017 478673 1 144 O Prohibit white 13A extension cord at teachers desk or replace with minimum 15A single outlet extension cord
416518 11/30/2017 478685 3 103 O Prohibit hanging lights above exit door
416519 11/30/2017 478687 3 105 O Prohibit black mult outlet extension cord under teachers desk or replace with minimum 15A single outlet extension cord
416522 11/30/2017 478693 3 113 O Maintain clear access to emergency eye wash - shower
416456 11/30/2017 478542 1 130 C Post sign indicating primary and secondary evacuation routes in contrasting colors
416527 11/30/2017 478702 3 118 C Replace missing sign indicating primary and secondary evacuation routes in contrasting colors
416531 11/30/2017 478711 3 122 C Replace missing sign indicating primary and secondary evacuation routes in contrasting colors
402823 11/30/2017 449112 3 125 C Post sign indicating primary and secondary evacuation routes in contrasting colors
416565 11/30/2017 478782 1 101G MS Repair bathroom door lock to operate properly
416450 11/30/2017 478529 1 105A MS Provide current inspection tag for fire extinguisher
416455 11/30/2017 478540 1 107A MS Replace missing thumb latch to on bathroom stall door
416493 11/30/2017 478630 1 114A MS Repair thumb latch to enable door to be unlocked
416516 11/30/2017 478681 1 169A MS Replace missing thumb latch to enable door to be unlocked
416494 11/30/2017 478632 1 194 MS Provide Co2 fire extinguisher for computer lab
416495 11/30/2017 478634 1 195 MS Provide current inspection tag for fire extinguisher
416454 11/30/2017 478538 1 197 MS Provide current inspection tag for fire extinguisher
416552 11/30/2017 478754 3 292 MS Recharge fire extinguisher
416459 11/30/2017 478548 1 121 OS Maintain clear aisle to secondary exit
416496 11/30/2017 478636 1 141 OS Remove and prohibit use of space heater
402671 11/30/2017 448788 1 190 OS Remove storage blocking electrical disconnects (recycle bins)
260034 11/30/2017 141683 1 0000 N/A No violations observed
327838 11/30/2017 286399 2 0000 N/A No violations observed
327839 11/30/2017 286401 3 0000 N/A No violations observed
402676 11/02/2017 448798 1 101P M Repair exhaust fan in bathroom
402677 11/02/2017 448800 1 101Q M Repair exhaust fan in bathroom
402692 11/02/2017 448837 1 107A M Replace cracked handicapped sink
402804 11/02/2017 449072 2 190 M Re-insulate hot water lines
402662 11/02/2017 448770 3 180 M Make necessary repairs to fire sprinkler system as indicated on inspection report. Red annual and yellow quarterly tags
402833 05/05/2017 449134 3 291A M Remove sign indicating COMBUSTIBLE STORAGE. Remove that verbiage from sign but leave room number
402695 04/28/2017 448843 1 113C M Secure faucet to sink
402802 04/28/2017 449068 2 105 M Repair inoperable urinal
402803 04/28/2017 449070 2 105 M Cover urinal screens with plastic laminate to provide impervious finish or remove urinal screens. Not required
402830 04/28/2017 449127 3 009 M Repair hole in wall at top of stairs from door handle. Provide door stop to prevent further damage to wall. Magnetic hold open may need to be extended
402694 04/28/2017 448841 1 108 MS Provide current inspection tag for fire extinguisher
402797 04/28/2017 449057 1 199C MS Provide current inspection tag for fire extinguisher. No date punched
402816 04/28/2017 449098 3 002 MS Provide current inspection tag for fire extinguisher in corridor at 3-122
402685 04/04/2017 448821 00 0000 M Large lip where red clay meets grass at both softball fields. Either grade to remove lip or fill infield with red clay to raise elevation and eliminate lip
402686 04/04/2017 448823 00 0000 M Clean out all gutters, downspouts and roof drains on campus
402789 04/04/2017 449040 1 002 M Secure spout to drinking fountain in corridor at 1-115A
402712 04/04/2017 448877 1 006 M Secure loose T-stat to corridor wall across from 1-190
402792 04/04/2017 449047 1 011 M Secure loose box and plate on corridor wall at 5 feet above floor at 1-151
402796 04/04/2017 449055 1 013 M Caulk loose glass in north corridor door to exterior
402788 04/04/2017 449038 1 102 M Secure spout on drinking fountain at 1-102A
402674 04/04/2017 448794 1 102 M Provide permanent number on maximum occupancy sign. MO = 745
402711 04/04/2017 448875 1 105 M Secure loose hinge on Stage right exit door to corridor
402693 04/04/2017 448839 1 107A M Secure faucet to handicapped sink
402691 04/04/2017 448835 1 107A M Repair exhaust fan in bathroom
402690 04/04/2017 448833 1 107B M Replace damaged paper towel dispenser
402805 04/04/2017 449074 1 109 M Secure data outlets to power poles
402696 04/04/2017 448845 1 114A M Repair damaged wall finish at toilet to provide impervious finish
402665 04/04/2017 448776 1 116 M Determine cause of water damaged ceiling tiles and replace tiles
402790 04/04/2017 449043 1 120 M Repair damaged flooring at north door. Perhaps install threshold
402787 04/04/2017 449036 1 122 M Secure loose handrail for stairs. Has been repaired several times in the past. Perhaps install a backer board and attach the brackets to it
402705 04/04/2017 448863 1 122 M Repair light fixtures at 16 feet above floor
402703 04/04/2017 448859 1 124 M Repair exhaust fan in bathroom
402704 04/04/2017 448861 1 125 M Repair damaged wall finish to provide impervious finish
402702 04/04/2017 448857 1 125 M Repair exhaust fan in bathroom
402700 04/04/2017 448853 1 126 M Secure faucet to sink
402891 04/04/2017 449261 1 127 M Repair exhaust fan in bathroom
402699 04/04/2017 448851 1 128D M Secure door knob to door
402698 04/04/2017 448849 1 128H M Secure door knob to door
402706 04/04/2017 448865 1 130 M Secure faucet to sink
402795 04/04/2017 449053 1 145 M Caulk loose glass in door to exterior
402807 04/04/2017 449078 1 149A M Seal gap in wall at top of base tile to provide impervious finish
402678 04/04/2017 448803 1 149B M Repair exhaust fan in bathroom
402806 04/04/2017 449076 1 149C M Secure faucet to sink
402793 04/04/2017 449049 1 152 M Adjust door to 1-153 to latch properly
402707 04/04/2017 448867 1 152 M Adjust door to corridor to latch properly
402683 04/04/2017 448815 1 153 M Adjust flow of emergency eye wash
402799 04/04/2017 449062 1 159A M Repair damaged wall in bathroom to provide impervious finish
402794 04/04/2017 449051 1 159C M Repair damaged wall at entry to bathroom
402800 04/04/2017 449064 1 165 M Adjust door to exterior to latch properly
402663 04/04/2017 448772 1 165 M Repair fume hood exhaust fan. Not working. No hood in room
402681 04/04/2017 448810 1 169A M Repair damaged wall finish at base
402808 04/04/2017 449080 1 169C M Repair damaged wall finish in 2 stalls to provide impervious finish
402809 04/04/2017 449082 1 169C M Replace broken toilet seat
402670 04/04/2017 448786 1 190 M Chain cylinders to wall or remove from room
402673 04/04/2017 448792 1 190 M Replace missing screws for covers of electrical panels XL and XH
402672 04/04/2017 448790 1 190A M Repair or replace leaking union on water supply to cooling tower
402668 04/04/2017 448782 1 193 M Repair stopped up floor drain
402697 04/04/2017 448847 1 195 M Replace missing spacers for electrical panel L6B
402687 04/04/2017 448825 1 196 M Secure transformer to electrical box on mezzanine and cover exposed wires
402688 04/04/2017 448828 1 197 M Install belt guard for motor on mechanical mezzanine
402689 04/04/2017 448830 1 197 M Cover open Neptronic box on mechanical mezzanine
402708 04/04/2017 448869 1 199 M Provide cover on exposed electrical junction box at ceiling at door
402709 04/04/2017 448871 1 199 M Repair leaking air handler
402798 04/04/2017 449059 1 199C M Repair leaking air handler
402801 04/04/2017 449066 2 103 M Room too cold,adjust A-C. See Coach
402811 04/04/2017 449087 3 001 M Adjust north corridor door to exterior to latch properly
402812 04/04/2017 449089 3 001 M Repair damaged corridor wall at north door to exterior. Perhaps install corner guard
402817 04/04/2017 449100 3 006 M Secure outside handrail at 1st run of stairs. One anchor stripped another missing nut
402814 04/04/2017 449094 3 006 M Adjust stair door to exterior to latch properly
402815 04/04/2017 449096 3 009 M Adjust stair door to exterior to latch properly
402825 04/04/2017 449117 3 103 M Repair light fixture
402826 04/04/2017 449119 3 106 M Repair damaged wall at closet. Perhaps install corner guard
402813 04/04/2017 449091 3 108 M Determine cause of water damaged ceiling tiles and replace tiles
402827 04/04/2017 449121 3 110A M Repair leaking supply line for 1st urinal
402820 04/04/2017 449106 3 117 M Determine cause of water damaged ceiling tiles and replace tiles
402822 04/04/2017 449110 3 122 M Repair holes in wall
402824 04/04/2017 449114 3 125 M Breaker 8 tripped on electrical panel. Repair circuit
402828 04/04/2017 449123 3 201 M Determine cause of water damaged ceiling tiles and replace tiles
402840 04/04/2017 449148 3 205 M Repair door to open and close properly. Drags on floor
402838 04/04/2017 449144 3 216A M Replace damaged paper towel dispenser in handicapped stall
402832 04/04/2017 449131 3 221 M Repair light fixture
402834 04/04/2017 449136 3 291 M Repair or replace surge protector for electrical panel 2M. Surge in fault
402664 04/04/2017 448774 1 166 O Remove and prohibit paper covering window in door. Acceptable for CODE situation only
402821 04/04/2017 449108 3 117A O Provide clear access to electrical panel
402839 04/04/2017 449146 3 213 O Maintain clear access to emergency eye wash - shower
402713 04/04/2017 448879 1 116 MS Blinds stack across exit to exterior. Provide stop on blinds or replace with blinds of appropriate size
402831 04/04/2017 449129 3 006 MS Adjust fire door at top of stairs to latch properly
402810 04/04/2017 449084 3 107 MS Adjust corridor door to latch properly
402819 04/04/2017 449104 3 113A MS Secure fire extinguisher bracket to wall
402710 04/04/2017 448873 1 105 OS Prohibit hold open device on Stage right exit door to corridor
402791 04/04/2017 449045 2 001A OS Remove and prohibit storage in exit vestibule from Girls locker room to maintain clear aisle to exit
402818 04/04/2017 449102 3 110A OS Prohibit hold open device on door to 3-113
402829 04/04/2017 449125 3 201 OS Prohibit hold open device on corridor door
402837 04/04/2017 449142 3 217A OS Prohibit hold open device on fire door
387006 12/19/2016 414981 1 104 M Repair damaged ceiling around ceiling hatch and air vent in ceiling of kitchen
387009 12/19/2016 414990 1 116 M Repair damaged laminate tops on tables in art room or replace tables
402669 12/19/2016 448784 1 180 M Repair trouble indicated on fire alarm panel. Trouble repaired
387052 12/19/2016 415077 3 291A M Repair damaged drywall ceiling in plumbing chase room
387029 03/02/2016 415031 1 0000 M Remove trees and vegetation growing inside chiller compound
387005 03/02/2016 414979 1 104 M Provide cover on exposed electrical junction box in ceiling of kitchen next to Ansul system tanks
387003 03/02/2016 414975 1 104 M Repair or replace rusted door frame between kitchen and serving line (metal frame has rusted through at floor)
387004 03/02/2016 414977 1 104E M Secure loose toilet seat in kitchen staff restroom
387012 03/02/2016 414996 1 112 M Repair seams in vinyl flooring between two power drop poles at rear of room
386997 03/02/2016 414963 1 122 M Repair loose handrail on stairs in band room
386999 03/02/2016 414967 1 122 M Replace burned out bulbs in light fixtures in band room (ceilings are too tall for custodians to access changing bulbs)
386998 03/02/2016 414965 1 122B M Secure hanging lens on light fixture
387000 03/02/2016 414969 1 125 M Secure loose toilet seat in women's staff restroom
386993 03/02/2016 414955 1 133 M Replace electrical outlet which is within three feet of sink with GFCI outlet
386994 03/02/2016 414957 1 135 M Replace damaged ceiling tile (one ceiling tile with hole cut in it)
386986 03/02/2016 414941 1 149A M Repair damaged wall behind stool in boys bathroom
386985 03/02/2016 414939 1 149B M Secure loose toilet seat
386982 03/02/2016 414933 1 149C M Repair two (2) stall doors in girl's restroom to close properly
386991 03/02/2016 414951 1 150 M Provide covers on exposed electrical wiring in old clock enclosures on wall (X2)
386992 03/02/2016 414953 1 152 M Provide cover on exposed electrical wiring in old clock enclosure on wall
386990 03/02/2016 414949 1 153A M Determine cause of water damaged ceiling tiles and replace tiles
386988 03/02/2016 414945 1 169A M Repair damaged wall behind stool in boy's bathroom
387002 03/02/2016 414973 1 180 M Provide certification that fire alarm system has been tested (records show last date of inspection was 11-30-14)
387020 03/02/2016 415013 2 004 M Determine cause of water damaged ceiling tiles in exit vestibule and replace tiles
387022 03/02/2016 415017 2 101 M Repair hanging light fixture in gymnasium above door at 2-102C
387015 03/02/2016 415002 2 102 M Provide cover on exposed electrical wiring in old clock enclosure
387018 03/02/2016 415009 2 103 M Provide cover on exposed electrical wiring in old clock enclosure on wall
387019 03/02/2016 415011 2 103A M Secure loose toilet seat in staff restroom
387016 03/02/2016 415005 2 104 M Secure loose toilet seat in girls bathroom
387027 03/02/2016 415027 3 0000 M Provide inspection log to certify that emergency generator located in fence enclosure at the north side of Building 3 is operable
387036 03/02/2016 415045 3 001 M Replace missing and broken ceramic wall tiles on half wall in front of 3-110A bathroom
387054 03/02/2016 415081 3 013 M Anchor toilet to floor in men's bathroom
387030 03/02/2016 415033 3 101 M Repair damaged wall finish adjacent to 3-101D
387034 03/02/2016 415041 3 106 M Make repair and paint damaged corner of wall at storage room
387037 03/02/2016 415047 3 112A M Secure loose toilet seat in handicap stall of girl's bathroom
387042 03/02/2016 415057 3 114 M Repair out-of-service toilet
387039 03/02/2016 415051 3 115 M Replace missing escutcheon on fire sprinkler head in ceiling adjacent to emergency shower
387041 03/02/2016 415055 3 116 M Secure loose toilet seat in staff restroom
387028 03/02/2016 415029 3 192 M Provide emergency lighting and generator certification that all student occupied spaces have emergency lights and all are operable
387060 03/02/2016 415095 3 209 M Replace missing escutcheon on fire sprinkler head
387059 03/02/2016 415093 3 213 M Determine cause of water damaged ceiling tiles (X2)and replace tiles
387053 03/02/2016 415079 3 214 M Anchor toilet to floor in women's bathroom
387048 03/02/2016 415069 3 218 M Repair inoperable light fixtures (X3)
387049 03/02/2016 415071 3 219 M Determine cause of water damaged ceiling tiles and replace tiles
387051 03/02/2016 415075 3 291 M Replace cover on electric panel Node 5
387064 03/02/2016 415103 3 292 M Provide cover on exposed electrical junction box
386996 03/02/2016 414961 1 122C O Replace burned out bulbs in light fixture
387001 03/02/2016 414971 1 123 O Prohibit charging golf cart batteries in room (room has no exhaust fan)
386995 03/02/2016 414959 1 132 O Remove and prohibit paper covering window in door
386983 03/02/2016 414935 1 144 O Remove storage to maintain clear access to emergency eye wash
386989 03/02/2016 414947 1 169B O Replace burned out bulbs in light fixture in center stall of girl's bathroom
387031 03/02/2016 415035 3 103 O Remove paper covering emergency evacuation route map at entrance door
387032 03/02/2016 415037 3 103 O Remove and prohibit hanging paper and inflatable plastic skeleton from ceiling
387035 03/02/2016 415043 3 111 O Remove and prohibit paper covering window in door
387046 03/02/2016 415065 3 122 O Remove and prohibit paper covering window in door
387045 03/02/2016 415063 3 123 O Remove paper covering emergency evacuation map at front door
387047 03/02/2016 415067 3 124 O Remove and prohibit hanging paper and decorations from ceiling
387026 03/02/2016 415025 3 180 O Replace burned out bulbs in light fixture
387062 03/02/2016 415099 3 201 O Remove and prohibit air freshener
387061 03/02/2016 415097 3 206 O Prohibit use of light duty gray multi-outlet extension cord used to power refrigerator (use surge protector instead)
387056 03/02/2016 415085 3 215 O Remove and prohibit paper covering window in door
387057 03/02/2016 415088 3 215 O Prohibit plugging surge protector into surge protector (under teacher's desk)
387008 03/02/2016 414988 1 0000 MS Adjust fire doors in corridor next to 1-105B at back of stage to close and latch properly
387010 03/02/2016 414992 1 113 MS Provide current inspection tag for fire extinguisher
386981 03/02/2016 414930 1 142 MS Provide current inspection tag for fire extinguisher
386987 03/02/2016 414943 1 161 MS Repair loose panic hardware on exterior exit door
387013 03/02/2016 414998 1 195 MS Provide current inspection tag for fire extinguisher
387017 03/02/2016 415007 2 002 MS Remove thumb latch from secondary exit door from girls locker room and install panic hardware, and remove sign reading "Do Not Use" taped to door ("paer sign has been removed, maximum occupancy sign says MO=49, not requiring panic hardware)
387021 03/02/2016 415015 2 004 MS Adjust fire doors in exit vestibule to close and latch properly
387033 03/02/2016 415039 3 105 MS Adjust entrance door to close and latch properly
387038 03/02/2016 415049 3 113A MS Provide current inspection tag for fire extinguisher
387040 03/02/2016 415053 3 117A MS Provide current inspection tag for fire extinguisher
387024 03/02/2016 415021 3 127 MS Provide current inspection tag for fire extinguisher
387058 03/02/2016 415091 3 215A MS Provide current inspection tag for fire extinguisher
387055 03/02/2016 415083 3 217A MS Provide current inspection tag for fire extinguisher
387063 03/02/2016 415101 3 292 MS Provide current inspection tag for fire extinguisher
387011 03/02/2016 414994 1 113 OS Remove and prohibit use of space heater (located under teachers desk)
386984 03/02/2016 414937 1 144 OS Prohibit hanging decorations and articles from fire extinguisher
387007 03/02/2016 414983 1 196 OS Remove storage of old light tube cartons from bottom of mechanical room vestibule stairs
352407 03/02/2016 339811 2 004 OS Remove all storage from exit vesibule adjacent to boys locker to maintain clear egress
387023 03/02/2016 415019 2 190 OS Remove storage from hot water heater room
387044 03/02/2016 415061 3 120A OS Remove and prohibit storage of flammable chafing fuel cans (store flammable materials inside flammable storage room)
387025 03/02/2016 415023 3 180 OS Prohibit storage of flammable propane tank (store propane tanks in flammable storage room)
387043 03/02/2016 415059 3 191 OS Remove storage from mechanical room
387050 03/02/2016 415073 3 291 OS Remove storage from mechanical room (floor machine stored in mechanical room)
352432 12/08/2015 339865 1 0000 M Repair or replace damaged and rusted metal siding at soffit east of art classrooms 1-116 and 1-117
367579 12/08/2015 372922 1 102A M Repair or replace rippled carpeting
367588 01/13/2015 372936 00 9599 M Repair damaged concrete adjacent to sewer manholes outside kitchen exterior door
367607 01/13/2015 372979 00 95999 M Repair uneven sidewalk at west side of school entrance - Adjacent to mechanical room 1-199D
367431 01/13/2015 372586 1 128A M Secure hanging heat detector
367432 01/13/2015 372588 1 128B M Secure loose knob on closet door
367568 01/13/2015 372897 1 153A M Determine cause of water damaged ceiling tiles and replace tiles
367438 01/13/2015 372600 1 163 M Adjust exterior door to latch properly
367442 01/13/2015 372608 1 165 M Remove illuminated exit sign above door to 1-167. Door has a key lock and it is not a required exit
367440 01/13/2015 372604 1 183 M Replace rusted hot water heater
367584 01/13/2015 372927 1 190 M Repair clogged drain under relief valves on north wall
367574 01/13/2015 372909 2 001 M Adjust east exit doors in vestibule adjacent to girls locker to latch properly
367578 01/13/2015 372920 2 101 M Provide cover on exposed electrical junction box adjacent to NW exit doors
367571 01/13/2015 372903 2 102D M Secure loose cylinder lock on door to girls laundry room
367428 01/13/2015 372580 00 0000 O Keep evacuation maps clearly visible in all classrooms - most maps were covered with paper
367608 01/13/2015 372981 00 9599 O Pressure clean basketball court adjacent to storage room to eliminate slipping caused by mold
367599 01/13/2015 372959 1 105A O Relocate storage to provide clear access to all electrical panels
367603 01/13/2015 372966 1 105A O Prohibit charging floor cleaning machine - relocate to designated custodial receiving room which is an approved location
367589 01/13/2015 372941 1 105B O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
367592 01/13/2015 372943 1 109 O Prohibit running electrical cord across floor in front of west exit door in media center
367436 01/13/2015 372596 1 144 O Eliminate 13A brown extension cord adjacent to aquarium or replace with a surge protector
367437 01/13/2015 372598 1 160 O Eliminate black extension cord with multiple outlet end under teacher desk for document camera or replace with a surge protector
367439 01/13/2015 372602 1 164A O Keep chemicals in chemical storage cabinet when not in use (alcohol, ammonia)
367441 01/13/2015 372606 1 166 O Eliminate black extension cord with multiple outlet end under 1st row of computer stations or replace with a surge protector
367580 01/13/2015 372924 1 180C O Prohibit plugging refrigerator into extension cord - plug directly into permanent electrical outlet
367575 01/13/2015 372912 2 102C O Relocate bookcases to provide clear access to all electrical breakers and panels
367605 01/13/2015 372975 3 211 O Relocate shelf unit to provide clear access to electrical panel
367606 01/13/2015 372977 3 213 O Remove paper covering room name and number with Braille characters
327950 01/13/2015 286636 1 194 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
328174 01/13/2015 287120 3 291A C Provide signage indicating room name and number at appropriate height with raised and Braille characters
367429 01/13/2015 372582 1 108 MS Remove dog leg hold open device from fire door
367430 01/13/2015 372584 1 134 MS Recharge fire extinguisher
367566 01/13/2015 372887 1 135 MS Remove lock from communicating door to 1-134
367435 01/13/2015 372594 1 144 MS Provide current inspection tag for fire extinguisher adjacent to eye wash
367604 01/13/2015 372973 3 001 MS Replace missing fire extinguisher in corridor adjacent to boys bathroom 3-110
367596 01/13/2015 372952 1 105 OS Remove recycling bin and easel at intermediate landing of exit ramp at west side of stage
367433 01/13/2015 372590 1 131 OS Relocate table adjacent to teacher desk to keep area clear to secondary exit door
367434 01/13/2015 372592 1 140 OS Replace sign DO NOT USE THIS DOOR with EMERGENCY EXIT ONLY on secondary escape door to 1-141
367570 01/13/2015 372899 1 168 OS Relocate table to maintain clear access to exterior door
367577 01/13/2015 372916 2 101 OS Replace sign DO NOT USE THIS DOOR with sign that reads EMERGENCY EXIT ONLY on NW exit doors
352408 09/30/2014 339813 1 123D M Repair door lock to work properly - lock did not work
288403 09/30/2014 200237 00 0000 C Provide suitable area for storage and recharging batteries for floor cleaning machines
352391 09/30/2014 339778 1 140 MS Remove key lock from secondary exit door to 1-141
190604 09/30/2014 20797 1 132 CS Provide double acting door into 1-133 to provide secondary egress from 1-132 (door into 1-134 is too close to corridor door)
190603 09/30/2014 20796 1 135 CS Provide secondary exit to separate atmosphere - BCS interpretation
352435 12/13/2013 339871 00 0000 M Remove all heavily rusted electrical boxes and conduits in storage room at basketball court. Also remove and cap disconnected GFCI outlet on exterior wall
352436 12/13/2013 339873 1 0000 M Provide insulated cover for exposed GFCI electrical outlet on west exterior wall facing mechanical room 1-199C
352417 12/13/2013 339832 1 0000 M Make clean out cover level with sidewalk adjacent to center door of 1-101 (main office)
352418 12/13/2013 339834 1 0000 M Repair uneven sidewalk at NE end of Bldg. 1 (facing mechanical room 1-195)
352431 12/13/2013 339862 1 102 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to serving area
352413 12/13/2013 339824 1 104 M Replace rusted hatch on kitchen ceiling
352414 12/13/2013 339826 1 104 M Repair roof leaks
352415 12/13/2013 339828 1 104 M Repair water damaged ceiling finish at south west corner
352416 12/13/2013 339830 1 104F M Patch hole in exterior brick wall
352412 12/13/2013 339821 1 104F M Close hatch on ceiling
352437 12/13/2013 339875 1 109R M Replace missing certificate indicating curtain in CCTV studio is IFR
352402 12/13/2013 339801 1 116 M Repair exterior door to open and close properly - lock sticks
352403 12/13/2013 339803 1 121 M Secure loose lever on corridor door
352404 12/13/2013 339805 1 123 M Adjust water flow for emergency eye wash
352390 12/13/2013 339776 1 143 M Remove (6) plug multiple outlet adaptor and replace missing cover plate adjacent to exterior door
352392 12/13/2013 339780 1 144A M Replace missing ceiling tiles
328168 12/13/2013 287107 1 182 M Repair exhaust fan in custodial room
328169 12/13/2013 287109 1 183 M Repair exhaust fan in custodial room
352409 12/13/2013 339815 1 190 M Repair chillers to eliminate water leaks
352434 12/13/2013 339869 1 195 M Provide proper installation for hot water heater - Remove wood boards and extend relief valve to be adjacent to floor drain
352433 12/13/2013 339867 3 0000 M Anchor metal shelving to wall in all Bldg. 3 closets - very few were anchored
352425 12/13/2013 339850 3 002 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to 3-191
341629 12/13/2013 316283 3 180 M Provide current quarterly inspection tag for fire sprinkler system
352426 12/13/2013 339852 3 190 M Adjust air conditioning unit above door to work properly
352428 12/13/2013 339856 3 201D M Replace missing escutcheon on fire sprinkler head in bathroom
352386 12/13/2013 339768 1 101L O Eliminate 13A white extension cord with multiple outlet end under desk on east side (adj. to 1-101H) or replace with a surge protector
352405 12/13/2013 339807 1 109 O Prohibit plugging surge protector into green extension cord at computer stations - plug surge protector directly into wall outlet
352387 12/13/2013 339770 1 135 O Prohibit plugging surge protector into surge protector behind teacher printer - plug each surge protector directly into wall outlet
352389 12/13/2013 339774 1 143 O Prohibit plugging microwave into multiple outlet adaptor - plug directly into permanent electrical outlet
352393 12/13/2013 339782 1 144 O Prohibit plugging surge protector into surge protector under teacher desk - plug each surge protector directly into wall outlet
352395 12/13/2013 339787 1 145 O Prohibit plugging surge protector into surge protector at teacher desk - plug each surge protector directly into wall outlet
352396 12/13/2013 339789 1 148 O Prohibit plugging surge protector into surge protector adjacent to printer - plug each surge protector directly into wall outlet
352394 12/13/2013 339784 1 148 O Eliminate 13A white extension cord with multiple outlet end behind teacher desk or replace with a surge protector
352397 12/13/2013 339791 1 161 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
352398 12/13/2013 339793 1 161 O Eliminate brown 13A extension cord with multiple outlet end under teacher desk or replace with a surge protector
352399 12/13/2013 339795 1 161 O Eliminate white 13A white extension cord with multiple outlet end adjacent to microwave
352400 12/13/2013 339797 1 164 O Eliminate and prohibit use of 13A white extension cord with multiple outlet end plugged into surge under teacher desk
352401 12/13/2013 339799 1 164 O Keep electrical cord away from path to exterior door to eliminate trip hazard
352410 12/13/2013 339817 1 180C O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet (x2)
352411 12/13/2013 339819 1 181 O Provide caps on all gas containers to eliminate spread of fumes
352406 12/13/2013 339809 2 102B O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
352420 12/13/2013 339840 3 101 O Eliminate multiple outlet adaptor or replace with a surge protector
352421 12/13/2013 339842 3 105 O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet and prohibit use of extension cord with multiple outlet end
352422 12/13/2013 339844 3 111 O Remove and prohibit air freshener at teacher desk
352423 12/13/2013 339846 3 115 O Remove paper covering electrical panel adjacent to teacher desk
352424 12/13/2013 339848 3 117 O Remove paper covering electrical panel adjacent to teacher desk
352427 12/13/2013 339854 3 204 O Remove and prohibit excessive flammable blue vinyl table cover
352429 12/13/2013 339858 3 211 O Relocate file cabinet to provide clear access to electrical panel
341612 12/13/2013 316248 3 192 MS Remove maintenance storage from electrical room
352388 12/13/2013 339772 1 141 OS Remove and prohibit use of space heater at teacher desk
352430 12/13/2013 339860 3 291 OS Remove and prohibit charging and storing floor claening machines in mechanical room
319042 09/12/2013 266633 1 153 M Repair purge fan
328175 09/12/2013 287122 2 101 M Repair broken concrete floor at transition between wood and tile adjacent to 2-102C
327958 02/11/2013 286653 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable (expired ceretification located in 1-190, dated 6-17-10)
341630 02/11/2013 316285 00 0000 M Replace missing chain and padlock on water supply control valves for sprinkler system inside fence enclosure on the east side of Building 3
341602 02/11/2013 316228 1 007 M Replace missing ceiling tiles in corridor adjacent to 1-192
341606 02/11/2013 316236 1 102 M Determine cause of water damaged ceiling tiles in cafeteria and replace tiles
341589 02/11/2013 316202 1 109F M Replace missing ceiling tiles
319027 02/11/2013 266597 1 109R M Provide dated flame resistance label on CCTV studio curtain
341599 02/11/2013 316222 1 113 M Replace sagging ceiling tiles
341604 02/11/2013 316232 1 121E M Replace broken wire glass in window of office
341592 02/11/2013 316208 1 144 M Repair damaged vinyl flooring at exit door
341594 02/11/2013 316212 1 145 M Secure loose ceiling tiles
341591 02/11/2013 316206 1 149A M Repair loose door knob on boys bathroom door
341596 02/11/2013 316216 1 163 M Repair exterior exit door to close properly (door rubs on threshold, preventing it from closing)
341597 02/11/2013 316218 1 164 M Place label on emergency shut-off switch
341598 02/11/2013 316220 1 165 M Repair exterior exit door to close properly
341600 02/11/2013 316224 1 180C M Replace missing ceiling tiles
341611 02/11/2013 316246 2 101 M Repair lighted exit sign at southwest exit door (face plate is hanging)
341607 02/11/2013 316238 2 102C M Provide cover on exposed electrical junction box in ceiling
341616 02/11/2013 316256 3 002 M Replace broken plexiglass in door of fire extinguisher cabinet in corridor adjacent to 3-191
341613 02/11/2013 316250 3 102 M Replace missing escutcheon on fire sprinkler head
341615 02/11/2013 316254 3 190 M Provide covers on exposed junction boxes in telecommunications room
341628 02/11/2013 316281 3 201 M Replace missing ceiling tiles adjacent to 3-201D
341627 02/11/2013 316279 3 201D M Replace missing escutcheon on fire sprinkler head
341623 02/11/2013 316270 3 213 M Determine cause of water damaged ceiling tiles and replace tiles
341631 02/11/2013 316287 00 0000 O Provide padlock on gate of fence enclosure for water control valves on east side of Building 3
341585 02/11/2013 316194 1 101J O Prohibit plugging extension cord into surge protector
341603 02/11/2013 316230 1 123 O Remove and prohibit paper covering window in door
341586 02/11/2013 316196 1 132 O Remove and prohibit paper covering window in door
341587 02/11/2013 316198 1 132 O Remove and prohibit hanging paper and decorations from ceiling
341588 02/11/2013 316200 1 132 O Prohibit plugging appliance into surge protector - plug directly into permanent electrical outlet
341593 02/11/2013 316210 1 143 O Prohibit plugging surge protector into extension cord
341595 02/11/2013 316214 1 148 O Prohibit plugging surge protector into extension cord
341608 02/11/2013 316240 2 102D O Clean lint from bottom lint trap on clothes dryer
341609 02/11/2013 316242 2 103C O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
341625 02/11/2013 316274 3 207 O Remove and prohibit hanging paper and decorations from ceiling
341626 02/11/2013 316276 3 207 O Remove and prohibit opaque film covering window in door
341624 02/11/2013 316272 3 211 O Remove and prohibit hanging paper and decorations from ceiling
341621 02/11/2013 316266 3 218 O Remove and prohibit opaque film covering window in door
341622 02/11/2013 316268 3 218 O Remove and prohibit paper attached to window blinds
341619 02/11/2013 316262 3 220 O Remove and prohibit opaque film covering window in door
341620 02/11/2013 316264 3 223 O Remove and prohibit opaque film covering window in door
341605 02/11/2013 316234 1 105 C Provide non-slip surface for stage ramp
328166 02/11/2013 287103 1 144 C Label emergency electrical disconnect switch on wall adjacent to electrical disconnect button - currently label is on electrical box
328167 02/11/2013 287105 1 153 C Label emergency electrical disconnect switch on wall adjacent to electrical disconnect button - currently label is on electrical box
341590 02/11/2013 316204 1 109F MS Seal around conduit penetrations in ceiling to prevent spread of fire or smoke
341610 02/11/2013 316244 2 101 MS Recharge fire extinguisher on southwest wall at exit door
341614 02/11/2013 316252 3 104A OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
341618 02/11/2013 316260 3 220A OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
341617 02/11/2013 316258 3 224A OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
341601 02/11/2013 316226 1 180 FS Provide certification that fire alarm system has been tested and is fully operational (last date of inspection was 5-21-2011)
190565 10/16/2012 20913 1 113 C Provide ventilation to exterior for cooking equipment (X6)- work in progress - no hood cover, switches not labeled
341584 10/16/2012 316192 00 0000 MS Provide current inspection tags for fire extinguishers throughout campus (all tags have expired date)
328179 10/16/2012 287130 3 0000 MS Remove metal shelf within 18" of fire sprinkler head and label edge of shelf under sprinkler head "No Storage Above" in classroom closets
328177 10/16/2012 287126 3 191A CS Provide automatic fire sprinkler coverage for plumbing chase
328176 10/16/2012 287124 3 291A CS Provide automatic fire sprinkler coverage for plumbing chase
328171 02/10/2012 287113 1 102 C Install maximum occupancy signage in cafeteria
328173 01/27/2012 287118 1 011 M Repair broken concrete outside exterior corridor door at west side of main office
328178 01/27/2012 287128 3 0000 M Anchor all metal shelving to wall throughout all classroom closets, 3-101B, 3-182, 3-201B and 3-281
327854 01/27/2012 286433 1 132 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
327873 01/27/2012 286471 1 142 O Remove and prohibit paper covering window in door (X2)
327841 01/27/2012 286405 1 120 OS Relocate teacher's desk to maintain 3 ft clear aisle to secondary exit door
327898 01/27/2012 286527 1 121C OS Immediately remove and prohibit use of fryer and electrical skillet
327840 01/27/2012 286403 1 123D OS Prohibit storage of propane gas cylinders - relocate to flammable storage room
251200 01/27/2012 122501 2 004 OS Remove storage in corridor
327956 01/20/2012 286649 1 001A M Replace missing ceiling tiles adjacent to 1-105C
328172 01/20/2012 287115 1 011 M Adjust door closer to control speed of closing for exterior corridor door at west side of main office
327869 01/20/2012 286463 1 101D M Adjust door to latch properly
327955 01/20/2012 286647 1 106 M Replace missing ceiling tiles
327954 01/20/2012 286644 1 111 M Replace missing ceiling tiles
327872 01/20/2012 286468 1 144 M Secure ceiling tile in place above eye wash
327876 01/20/2012 286477 1 160 M Cover or patch hole in wall adjacent to thermostat
327880 01/20/2012 286485 1 164A M Replace missing ceiling tiles
327962 01/20/2012 286662 1 168 M Chain helium cylinder to wall
327960 01/20/2012 286657 2 004 M Replace missing ceiling tiles adjacent to boys locker room
327842 01/20/2012 286407 3 003 M Adjust exterior doors at bottom of stairwell to latch properly
327899 01/20/2012 286529 1 116 O Eliminate 13A extension cord with multiple outlet end under cabinet behind teacher's desk
327897 01/20/2012 286525 1 121 O Remove all plastic sheathing hanging from roof trusses
319016 01/20/2012 266571 1 123 O Repair or replace safety goggles/disinfectant cabinet
327861 01/20/2012 286444 1 130 O Eliminate white extension cord with multiple outlet end under teacher's desk or replace with a surge protector
327858 01/20/2012 286440 1 132 O Remove and prohibit paper covering window in door
327964 01/20/2012 286666 1 133 O Eliminate white extension cord with multiple outlet end for stereo adjacent to teacher's desk or replace with a surge protector
327852 01/20/2012 286430 1 135 O Prohibit plugging surge protector into surge protector at teacher's desk - plug each surge protector directly into wall outlet
327870 01/20/2012 286466 1 143 O Eliminate (6) plug adaptor adjacent to teacher's desk
327874 01/20/2012 286473 1 146 O Secure cover strip for electrical cords to flooring - place tape along both sides to eliminate slip hazard
327875 01/20/2012 286475 1 148 O Eliminate black extension cord with multiple outlet end for projector or replace with a surge protector
327965 01/20/2012 286668 1 154 O Provide cover strip for electrical cord running across floor for projector and secure cover strip to flooring
327879 01/20/2012 286483 1 160 O Secure electrical cord cover strip to flooring to eliminate slip hazrad
327877 01/20/2012 286479 1 162 O Provide cover strip for electrical cords running across floor and secure cover strip to flooring
327963 01/20/2012 286664 1 166 O Remove and prohibit paper covering window in corridor door
327847 01/20/2012 286418 3 104 O Remove and prohibit plug in air freshener under writing board
327865 01/20/2012 286452 3 105 O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet and prohibit use of extension cord with multiple outlet end
327848 01/20/2012 286420 3 111 O Relocate bookcase to provide clear access to electrical panel
327846 01/20/2012 286416 3 207 O Remove and prohibit hanging paper from ceiling
327849 01/20/2012 286422 3 215 O Remove poster covering electrical panel adjacent to teacher's desk
190549 01/20/2012 21048 00 9599 C Turn barbs down on all fencing
327961 01/20/2012 286659 1 102B C Provide heat detector in storage room
328390 01/20/2012 287584 1 109 C Relocate illuminated exit sign from above entrance bar east to egress path as indicated on construction plans
327952 01/20/2012 286640 1 193 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
327951 01/20/2012 286638 1 195 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
328180 01/20/2012 287134 3 191A MS Re-key lock to master key - still on construction key
327867 01/20/2012 286460 1 101C OS Remove and prohibit use of space heater
327957 01/20/2012 286651 1 105A OS Prohibit charging batteries in room
327900 01/20/2012 286531 1 116 OS Prohibit storage of flammable spray cans on shelf adjacent to exterior door
319019 01/20/2012 266578 1 123 OS Keep sawdust cleaned from surfaces in shop room
327878 01/20/2012 286481 1 162 OS Relocate desk blocking access to secondary exit door
328170 01/20/2012 287111 1 164 OS Prohibit running electrical cord for surge protector under file cabinet - run cord behind file cabinet and you may tape the cord to the back of the cabinet
327959 01/20/2012 286655 1 180 OS Prohibit charging batteries in room
327851 01/20/2012 286426 3 204A OS Relocate box to keep area within 18" of fire sprinkler head clear and unobstructed
327843 01/20/2012 286410 3 213 OS Prohibit use of wedge to hold fire door in open position
327844 01/20/2012 286412 3 217 OS Prohibit use of wedge to hold fire door in open position
327850 01/20/2012 286424 3 218A OS Relocate storage to keep area within 18" of fire sprinkler head clear and unobstructed
327845 01/20/2012 286414 3 291 OS Remove custodial storage from mechanical room
327953 01/20/2012 286642 1 111 FS Secure hanging heat detector
288439 11/02/2011 200311 1 120 M Verify that room has emergency lighting
288440 11/02/2011 200313 1 122 M Verify that room has emergency lighting
259664 11/02/2011 140906 1 500B M Replace plywood in window frames with non-combustible construction
190679 11/02/2011 21021 P 3573 M Modify existing foundations and anchorage to comply with engineering requirements
190547 11/02/2011 20934 00 9500 C Provide covered walkway to portables - portables relocated
190552 11/02/2011 20905 1 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
190609 11/02/2011 20923 1 800A C Provide emergency disconnects for electricity and water
259898 11/02/2011 141405 1 820B C Provide emergency shut-off for electrical
260049 11/02/2011 141698 P 2130 N/A No violations observed
260062 11/02/2011 141711 P 2131 N/A No violations observed
260057 11/02/2011 141706 P 2134 N/A No violations observed
260054 11/02/2011 141703 P 2135 N/A No violations observed
260053 11/02/2011 141702 P 2136 N/A No violations observed
260050 11/02/2011 141699 P 492 N/A No violations observed
260058 11/02/2011 141707 P 498 N/A No violations observed
260063 11/02/2011 141712 P 536 N/A No violations observed
260065 11/02/2011 141714 P 537 N/A No violations observed
260066 11/02/2011 141715 P 538 N/A No violations observed
260035 11/02/2011 141684 P 9930 N/A No violations observed
260036 11/02/2011 141685 P 9931 N/A No violations observed
259187 11/02/2011 139908 P 9932 N/A No violations observed
251443 11/02/2011 123202 P 9933 N/A No violations observed
259755 11/02/2011 141104 P 9934 N/A No violations observed
251444 11/02/2011 123204 P 9935 N/A No violations observed
260041 11/02/2011 141690 P 9936 N/A No violations observed
260042 11/02/2011 141691 P 9937 N/A No violations observed
260043 11/02/2011 141692 P 9938 N/A No violations observed
260044 11/02/2011 141693 P 9939 N/A No violations observed
260045 11/02/2011 141694 P 9940 N/A No violations observed
260046 11/02/2011 141695 P 9941 N/A No violations observed
260047 11/02/2011 141696 P 9942 N/A No violations observed
319123 03/15/2011 266809 00 0000 M Install caps on fire department standpipe connection in bus loop area
319125 03/15/2011 266813 1 107 M Secure cover on electrical panel H1
319126 03/15/2011 266815 1 107 M Replace missing section of wall
319127 03/15/2011 266817 1 118 M Provide cover for exposed electrical outlet
319117 03/15/2011 266793 1 202F M Replace missing ceiling tiles
319111 03/15/2011 266781 1 209 M Repair damaged flooring adjacent to teacher's desk
319113 03/15/2011 266785 1 210 M Replace missing ceiling tiles
319114 03/15/2011 266787 1 213 M Provide CO2 fire extinguisher in computer lab
319119 03/15/2011 266797 1 300 M Determine cause of water damaged ceiling tiles and replace tiles
318985 03/15/2011 266508 1 300 M Replace missing ceiling tiles
319004 03/15/2011 266547 1 400 M Provide cover on exposed electrical junction box @ missing clock
319023 03/15/2011 266587 1 403 M Secure loose transition strip on floor in center of room. Repair damaged, cracked floor
319011 03/15/2011 266561 1 500 M Secure cage on light fixture adjacent to time out room
319005 03/15/2011 266549 1 500A M Determine cause of water damaged ceiling tiles and replace tiles
319008 03/15/2011 266555 1 500B M Provide cover for exposed electrical junction box located above door
319015 03/15/2011 266569 1 502 M Repair dust collection and exhaust system, system does not appear to be operating at full strength. See teacher for details
319018 03/15/2011 266576 1 502A M Repair light fixture, lights do not work
319026 03/15/2011 266595 1 503 M Remove and prohibit cardboard sheets stored above transformer
319028 03/15/2011 266599 1 700C M Determine cause of water damaged ceiling tiles and replace tiles
319031 03/15/2011 266605 1 809A M Replace missing ceiling tiles
319041 03/15/2011 266631 1 820B M Replace missing ceiling tiles
319039 03/15/2011 266627 1 851C M Keep water to sinks turned on
319048 03/15/2011 266649 1 900 M Provide cover on exposed electrical junction box on north wall under protective cage
319049 03/15/2011 266651 1 900 M Replace missing ceiling tiles adjacent to 1-999A
319050 03/15/2011 266653 1 999A M Replace missing ceiling tiles
318997 03/15/2011 266533 P 2131 M Repair ramp door to latch properly
318998 03/15/2011 266535 P 2131 M Repair or replace damaged door frame for ramp door
319000 03/15/2011 266539 P 538 M Repair emergency lighting
318990 03/15/2011 266519 P 9938 M Repair rear door to close properly
319012 03/15/2011 266563 1 404 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
319021 03/15/2011 266583 1 502B O Change filters in spray booth
319055 03/15/2011 266663 1 601 O Prohibit plugging surge protector into surge protector
319056 03/15/2011 266665 1 603 O Chain cylinder to wall
319047 03/15/2011 266647 1 604 O Mount sign indicating evacuation routes
319030 03/15/2011 266603 1 700 O Prohibit 4 gang outlet box @ media center desk adjacent to Christmas Tree, or replace with minimum 15A cord or surge protector
319033 03/15/2011 266611 1 800A O Maintain clear access to emergency eye wash/shower
319034 03/15/2011 266613 1 800A O Prohibit multi outlet electrical adaptor adjacent to fish tank
319046 03/15/2011 266643 1 803 O Remove and prohibit paper covering window in door
319054 03/15/2011 266661 1 902B O Prohibit plugging microwave and coffee maker into surge protector - plug directly into permanent electrical outlet
319003 03/15/2011 266545 1 300 C Verify capacity indicated on maximum occupancy sign
318984 03/15/2011 266506 1 303 C Provide records that stage rigging has been inspected and conforms to required safety standards
319032 03/15/2011 266607 1 800A MS Provide current inspection tag for CO2 fire extinguisher
318988 03/15/2011 266515 P 534 MS Provide current inspection tag for fire extinguisher
319116 03/15/2011 266791 1 202 OS Prohibit running electrical cords across floor or provide approved rubber cover strip to prevent tripping hazard
318987 03/15/2011 266513 1 312 OS Prohibit charging batteries in room
319013 03/15/2011 266565 1 401 OS Maintain clear aisle to exits
319024 03/15/2011 266590 1 403 OS Maintain clear aisle to exits
319025 03/15/2011 266592 1 403 OS Prohibit sign on secondary exit door, sign may read "emergency exit only"
319121 03/15/2011 266803 1 504 OS Prohibit storage of propane
319029 03/15/2011 266601 1 700 OS Arrange bookshelves adjacent to computers to allow egress at all times. Current arrangement creates a dead end
319044 03/15/2011 266639 1 801A OS Provide approved rubber cover strip for electrical and data cords on floor to prevent tripping hazard and damaging cords
319038 03/15/2011 266622 1 806A OS Prohibit hold open devices on fire door
319040 03/15/2011 266629 1 840C OS Prohibit hold open devices on fire door
319052 03/15/2011 266657 1 902 OS Prohibit do not use signs on exit doors, sign may read "emergency exit only"
319053 03/15/2011 266659 1 902F OS Keep exit doors unlocked to provide clear access to exit
319001 03/15/2011 266541 P 2130 OS Provide clear access to fire extinguisher
319002 03/15/2011 266543 P 2130 OS Prohibit running electrical cord under rug
251428 03/15/2011 123074 P 9932 OS Maintain clear aisle to exit
318986 03/15/2011 266511 1 312 FS Provide certification that fire alarm system has been tested and is fully operational, report indicates that repairs are needed
319022 03/15/2011 266585 1 403M FS Secure hanging heat detector
319010 03/15/2011 266559 1 500 FS Provide heat detector in old time out room/storage room
288441 03/14/2011 200315 1 403 M Verify that room has emergency lighting
319043 03/14/2011 266635 1 802A M Adjust door closer on exterior door to control speed of closing door
318989 03/14/2011 266517 P 9936 M Repair rear door to close properly
319057 03/14/2011 266667 1 100 O Prohibit black multi outlet extension cord or replace with minimum 15A single outlet extension cord or surge protector, located adjacent to copy machine
319124 03/14/2011 266811 1 109 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
319110 03/14/2011 266779 1 208 O No access was available to this room. Please be prepared to access this room during the report review meeting
319112 03/14/2011 266783 1 209 O Prohibit plugging surge protector into orange extension cord
319118 03/14/2011 266795 1 310 O Remove and prohibit flammable plastic table coverings (cloth is acceptable)
319014 03/14/2011 266567 1 403C O Relocate instruments to provide access to these rooms, no access was available to this room and adjoining practice rooms. Please be prepared to access these rooms during the report review meeting
319020 03/14/2011 266580 1 502 O Maintain shop and adjoining storage rooms in an orderly manner
319045 03/14/2011 266641 1 801A O Prohibit plugging surge protector into multi outlet electric adaptor, prohibit multi outlet electrical adaptor
319037 03/14/2011 266620 1 806A O Prohibit plugging surge protector into yellow extension cord
319035 03/14/2011 266615 1 808A O Remove and prohibit flammable plastic decorative sheet on wall(skeleton picture)
319036 03/14/2011 266618 1 808A O Remove and prohibit excessive flammable wall coverings, limit coverage area to 20% of each wall
319051 03/14/2011 266655 1 901A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
318995 03/14/2011 266529 P 536 O Remove excessive flammable wall coverings, limit coverage area to 20% of each wall
318996 03/14/2011 266531 P 538 O Remove excessive flammable wall coverings, limit coverage area to 20% of each wall
318992 03/14/2011 266523 P 9933 O Remove and prohibit paper covering door and wood covering window in door
318993 03/14/2011 266525 P 9935 O Provide clear access to electrical panel
319115 03/14/2011 266789 1 202 OS Maintain clear aisle to exterior exit
319007 03/14/2011 266553 1 500B OS Remove and prohibit candles
319017 03/14/2011 266574 1 502 OS Prohibit storage of flammable materials, keep flammables stored in flammable storage cabinet or room
319122 03/14/2011 266806 1 901D OS Prohibit storage of flammable materials (field marker paint)
318991 03/14/2011 266521 P 9930 OS Maintain clear aisle to exits
260056 03/14/2011 141705 P 1147 N/A No violations observed
260060 03/14/2011 141709 P 1447 N/A No violations observed
260064 03/14/2011 141713 P 1517 N/A No violations observed
260052 03/14/2011 141701 P 3573 N/A No violations observed
260061 03/14/2011 141710 P 476 N/A No violations observed
303896 12/14/2010 233432 00 9599 M Repair broken sidewalk between P-17 & P-18
303961 12/14/2010 233572 1 300 M Repair magnetic hold open device to work properly on exit doors adjacent to 1-306 . Magnetic hardware did not release
303931 12/14/2010 233505 P 1261 M Make bottom of ramp level with sidewalk
303953 12/14/2010 233550 P 2130 M Repair missing window blinds
303903 12/14/2010 233446 P 492 M Repair or replace deteriorated wood siding along ramp
303905 12/14/2010 233450 P 492 M Repair or replace rusted ramp door
303951 12/14/2010 233547 P 535 M Repair or replace broken concrete stoop outside back door
190614 12/14/2010 20927 1 840C C Provide emergency disconnects for electricity and water
190615 12/14/2010 20799 1 841C CS Provide exit directly to the exterior (cannot enter room without passing through another room)
190619 12/14/2010 20801 1 845C CS Provide exit directly to the exterior (cannot enter room without passing through another room)
260051 12/14/2010 141700 P 534 N/A No violations observed
303960 03/24/2010 233570 1 033 M Repair magnetic hold open device to work properly on fire doors in corridor facing 1-503
304164 03/24/2010 234014 1 111 M Replace cracked wire glazing in door adjacent to 1-110
303862 03/24/2010 233359 1 210 M Replace cracked wired glass in door leading to dining room
303937 03/24/2010 233508 P 1261 M Make flooring even adjacent to ramp door - piece of plywood was placed over rotted subflooring. This is not an acceptable solution and can cause tripping
303938 03/24/2010 233520 P 1261 M Provide adequate support under ramp posts to prevent bounciness along ramp
303940 03/24/2010 233522 P 1261 M Secure loose door knob on inside face of closet door adjacent to stair door
303941 03/24/2010 233526 P 1447 M Replace rusted metal flashing above east windows
303929 03/24/2010 233502 P 1517 M Secure loose metal siding under north window
303963 03/24/2010 233576 P 2130 M Replace missing auto closer on stair door
303964 03/24/2010 233578 P 2130 M Repair water damaged wall finish at stair door
303965 03/24/2010 233580 P 2130 M Adjust soffit edge above stair door - top of door rubs on sofit when open
303948 03/24/2010 233538 P 2131 M Replace damaged handicapped accessible ramp door hardware
303915 03/24/2010 233471 P 2134 M Secure bottom of ramp to sidewalk
303922 03/24/2010 233487 P 2136 M Repair emergency lighting
303926 03/24/2010 233490 P 2136 M Replace rotted window sill adjacent to electrical panel
303927 03/24/2010 233497 P 2136 M Replace broken window blinds
303928 03/24/2010 233500 P 2136 M Repair roof leak - Water drips form AC vent (see teacher for exact location)
303910 03/24/2010 233456 P 492 M Secure exhaust fan grille to ceiling in bathroom
303912 03/24/2010 233464 P 492 M Determine cause of water damaged ceiling tiles and replace tiles
303874 03/24/2010 233383 P 9936 M Adjust front door to latch properly
303878 03/24/2010 233391 P 9941 M Adjust front door to latch properly
304163 03/24/2010 234012 1 108 O Prohibit plugging toaster oven into surge protector - plug directly into permanent electrical outlet
303863 03/24/2010 233361 1 202F O Eliminate (3) plug electrical outlet adaptor behind computer stations adjacent to teacher's desk
303957 03/24/2010 233560 1 502B O Replace burned out light bulbs in explosion proof light fixtures
303857 03/24/2010 233347 1 603 O Prohibit plugging microwave into surge protector behind teacher's desk - plug directly into permanent electrical outlet
303854 03/24/2010 233343 1 808A O Secure electrical cord cover strip to floor to eliminate slipping
303855 03/24/2010 233345 1 822B O Prohibit plugging surge protector into surge protector under teacher's desk adjacent to exterior door - plug each surge protector directly into permanent electrical outlet
303962 03/24/2010 233574 P 2130 O Relocate flag covering electrical panel
303919 03/24/2010 233474 P 2134 O Prohibit plugging surge protector into surge protector under projector station - plug each surge protector directly into wall outlet
303949 03/24/2010 233544 P 535 O Eliminate brown extension cord with multiple outlet end adjacent to desk lamp or replace with a surge protector
303945 03/24/2010 233534 P 536 O Remove paper covering electrical panel
303893 03/24/2010 233423 P 9934 O Eliminate (3) plug electrical outlet adaptor adjacent to microwave
303880 03/24/2010 233396 P 9934 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
303876 03/24/2010 233387 P 9937 O Eliminate white extension cord with multiple outlet end for projector or replace with a surge protector
303882 03/24/2010 233400 P 9940 O Relocate bookcase to provide clear access to electrical panel
303887 03/24/2010 233406 P 9940 O Prohibit plugging surge protector into extension cord at projector cart - plug surge directly into permanent electrical outlet
288401 03/24/2010 200234 00 0000 C Provide exterior signage indicating property address
190555 03/24/2010 20793 1 0000 C Provide illuminated exit sign on each side of smoke stop doors between 700 and 800 wings (near 1-851C)
190556 03/24/2010 20805 1 0000 C Provide illuminated exit signs on each side of smoke stop doors between 100 and 600 wings
259136 03/24/2010 139800 1 201 C Install GFCI outlets next to sinks
303959 03/24/2010 233568 1 502 C Provide emergency eye wash in woodshop
190616 03/24/2010 20800 1 841C C Provide illuminated exit signs into 1-840C and 1-842C
190620 03/24/2010 20802 1 845C C Provide illuminated exit signs into 1-846C and 1-840C
259795 03/24/2010 141185 P 2135 C Provide bottom rail on stair landing guardrail at two inches above floor
303853 03/24/2010 233340 1 202C MS Provide current inspection tag for fire extinguisher
303852 03/24/2010 233338 1 202F MS Provide current inspection tag for fire extinguisher adjacent to exterior door
288390 03/24/2010 200206 1 307 MS Adjust fire doors into serving areas to latch properly (X2)
288414 03/24/2010 200259 1 314 MS Remove maintenance storage from mechanical room
303955 03/24/2010 233557 1 701 MS Provide current inspection tag for fire extinguisher adjacent to 1-701A
303851 03/24/2010 233336 1 800A MS Provide current inspection tag for fire extinguisher adjacent to exterior door (x2)
303850 03/24/2010 233334 1 808A MS Provide current inspection tag for fire extinguisher
304162 03/24/2010 234010 1 830B MS Provide current inspection tag for fire extinguisher in mechanical room
303864 03/24/2010 233363 1 403 OS Remove storage blocking clear path to both exit doors and maintain room in an orderly manner
303954 03/24/2010 233554 1 902B OS Prohibit running electrical cord through door to gymnasium
259629 03/24/2010 140828 1 703 CS Modify hardware on door at corridor so door latches automatically
288438 11/17/2009 200309 00 9599 M Make manhole cover level with sidewalk at east side of exterior mechanical room 1-810A
190576 11/17/2009 34289 1 307 M Provide current inspection tag for kitchen steamer (expired 7/05)
288480 11/17/2009 200398 P 1261 M Repair soft spot in subflooring adjacent to ramp door
288465 11/17/2009 200366 P 538 O Remove and prohibit flammable fabric covering windows
288466 11/17/2009 200371 P 538 O Remove and prohibit excessive flammable decorations and cardboard on wall adjacent to front door blocking clear view of fire extinguisher and fire alarm pull station
288391 11/17/2009 200208 1 701A C Provide partitions between urinals
260048 11/17/2009 141697 P 535 N/A No violations observed
288446 03/26/2009 200325 1 033 M Repair magnetic release hold open device for fire door facing 1-503 to work properly - magnet does not hold well
288448 03/26/2009 200332 1 102 M Repair emergency lighting
288451 03/26/2009 200338 1 112 M Provide cover on exposed electrical junction box adjacent to clock
288408 03/26/2009 200247 1 303 M Determine cause of water damaged ceiling tiles and replace tiles
259686 03/26/2009 140952 1 303 M Repair or replace torn black curtains on stage and provide dated flame resistance label on stage curtains
288428 03/26/2009 200289 1 400 M Repair open seam in vinyl flooring
288442 03/26/2009 200317 1 400 M Replace bulbs in light fixture
288443 03/26/2009 200319 1 401 M Replace bulbs in light fixtures
288444 03/26/2009 200321 1 401 M Repair electrical light switch to work properly - see teacher
288416 03/26/2009 200263 1 500B M Replace missing ceiling tiles
288417 03/26/2009 200266 1 500C M Replace missing ceiling tiles
288415 03/26/2009 200261 1 501 M Determine cause of water damaged ceiling tiles and replace tiles
288427 03/26/2009 200287 1 603 M Replace missing ceiling tiles above corridor door
288431 03/26/2009 200295 1 605 M Secure electrical outlet box to wall adjacent to teacher's desk
288396 03/26/2009 200219 1 700D M Provide additional electrical outlets to eliminate use of multiple extension cords
288457 03/26/2009 200348 1 8088 M Provide cover on exposed electrical junction box where speaker was or replace missing speaker on exterior wall above SW entrance to gymnasium
288397 03/26/2009 200222 1 999D M Replace missing ceiling tiles
288460 03/26/2009 200356 P 0000 M Raise exterior electrical boxes so bottom of boxes is at least 8 inches above grade for portables 8-16 & 28-31 (not required per Terry Summerell)
288468 03/26/2009 200375 P 2131 M Replace missing window blinds (X2)
288477 03/26/2009 200392 P 2135 M Repair emergency lighting
190680 03/26/2009 21149 P 3573 M Provide hurricane anchors for portable
288475 03/26/2009 200389 P 492 M Repair emergency lighting
288467 03/26/2009 200373 P 534 M Adjust front door to latch properly
290454 03/26/2009 204539 P 537 M Determine cause of water damaged ceiling tiles and replace tiles
288389 03/26/2009 200204 1 307D O Prohibit plugging surge protector into surge protector
288432 03/26/2009 200297 1 821B O Prohibit plugging surge protector into surge protector under teacher's station adjacent to writing board
288481 03/26/2009 200403 P 1517 O Prohibit use of shower curtain as a projector screen
288471 03/26/2009 200379 P 2131 O Remove and prohibit flammable fabric covering windows
288462 03/26/2009 200361 P 537 O Remove and prohibit excessive flammable decorations and wall covering
288445 03/26/2009 200323 1 033 MS Adjust fire door facing 1-503 to latch properly
288447 03/26/2009 200330 1 102 MS Provide current inspection tag for fire extinguisher
288405 03/26/2009 200242 1 202C MS Provide current inspection tag for fire extinguisher
288388 03/26/2009 200202 1 204 MS Provide current inspection tag for fire extinguisher
288409 03/26/2009 200249 1 212 MS Provide current inspection tag for fire extinguisher
288407 03/26/2009 200245 1 303A MS Provide current inspection tag for fire extinguisher
288412 03/26/2009 200255 1 312 MS Adjust corridor doors to latch properly
288393 03/26/2009 200212 1 700F MS Provide current inspection tag for fire extinguisher
288474 03/26/2009 200382 P 2131 FS Provide heat detector in portable - Heat detector is not visible. It might be above new ceiling tiles
288450 11/14/2008 200336 1 105 O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
288449 11/14/2008 200334 1 118 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
288411 11/14/2008 200253 1 202F O Prohibit plugging surge protector into extension cord under writing board
288423 11/14/2008 200280 1 403 O Prohibit plugging surge protector into TV cart outlet - plug directly into permanent electrical outlet
288422 11/14/2008 200276 1 404 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
288394 11/14/2008 200214 1 700C O Prohibit plugging surge protector into surge protector (school # 700B)
288395 11/14/2008 200216 1 700D O Prohibit piggy backed surge protectors in CCTV control room - plug each surge protector directly into permanent electrical outlet
288436 11/14/2008 200305 1 802A O Prohibit plugging surge protector into extension cord adjacent to teacher's desk
288437 11/14/2008 200307 1 802A O Eliminate (3) plug electrical adaptor adjacent to teacher's desk - plug surge directly into wall outlet
288435 11/14/2008 200303 1 803A O Remove and prohibit paper covering window in door
288430 11/14/2008 200293 1 824B O Remove and prohibit paper covering window in door
288433 11/14/2008 200299 1 825B O Prohibit plugging surge protector into extension cord under teacher's desk
288434 11/14/2008 200301 1 825B O Remove and prohibit garbage bags covering windows in exterior door
288429 11/14/2008 200291 1 842C O Remove and prohibit excessive wall covering - limit paper covering to 20% of wall area
288398 11/14/2008 200224 1 901A O Prohibit plugging microwave into surge protector in boys coach office - plug directly into permanent electrical outlet
288399 11/14/2008 200230 1 902A O Prohibit plugging microwave into surge protector in girls coach office - plug directly into permanent electrical outlet
288485 11/14/2008 200407 P 476 O Prohibit use of extension cord with multiple outlet end for document camera or replace with a surge protector
288494 11/14/2008 200430 P 9933 O Relocate file cabinet to provide clear access to electrical panel
288413 11/14/2008 200257 1 312 OS Prohibit charging batteries in room
288418 11/14/2008 200269 1 500C OS Remove and prohibit use of space heater
288420 11/14/2008 200271 1 500C OS Remove and prohibit use of toaster oven
288392 11/14/2008 200210 1 701C OS Prohibit running electrical cord for surge protector under door
273652 10/21/2008 168667 1 314 M Provide certification that all student occupied spaces have emergency lights and all are operable
259851 10/21/2008 141308 1 900 M Replace cracked wire glass in door at 1-999D
251237 10/21/2008 122576 P 1517 C Provide ramp for portable
190722 10/21/2008 20953 P 2131 C Provide ramp for portable
263081 10/21/2008 145771 1 100A MS Modify hardware on doors at corridor to latch automatically
260055 10/21/2008 141704 P 1261 N/A No violations observed
259803 02/08/2008 141205 00 9599 M Replace broken cover for electrical pull box in grass area between P-7 & P-9
259759 02/08/2008 141111 00 9599 M Replace inoperable 3210 padlock on gate for fence enclosure behind P-11
273683 02/08/2008 168731 1 102 M Secure loose wall bracket for fire extinguisher
273643 02/08/2008 168649 1 119A M Provide cover on exposed electrical junction box
273648 02/08/2008 168659 1 213 M Patch hole in wall adjacent to clock
273661 02/08/2008 168687 1 400 M Determine cause of water damaged ceiling tiles and replace tiles
273708 02/08/2008 168784 1 500D M Remove plywood covering storage fencing
273658 02/08/2008 168680 1 503 M Replace bulbs in light fixtures in mechanical room
273705 02/08/2008 168778 1 801A M Remove (6) electrical plug adaptors and replace cover for exposed electrical outlets - adjacent to exterior door and above counter adjacent to TV cart
273680 02/08/2008 168725 1 998 M Repair auto closer on door
273674 02/08/2008 168713 P 1517 M Repair north door to open and close properly - door rubs on stair landing
273687 02/08/2008 168740 P 2130 M Secure loose handle on ramp door
273678 02/08/2008 168721 P 2134 M Repair emergency lighting
273706 02/08/2008 168780 P 2134 M Replace missing aluminum handrail for stairs or seal wide gap between stairs and portable siding
273707 02/08/2008 168782 P 2135 M Replace missing aluminun handrail for stairs or seal wide gap between stairs and portable siding
273677 02/08/2008 168719 P 2136 M Repair emergency lighting
273676 02/08/2008 168717 P 3573 M Remove ramp and stair sections on south side of portable
273695 02/08/2008 168757 P 535 M Determine cause of water damaged ceiling tile around heat detector and replace tiles
273696 02/08/2008 168759 P 535 M Repair emergency lighting
273689 02/08/2008 168744 P 538 M Determine cause of water damaged ceiling tiles and replace tiles
273691 02/08/2008 168748 P 538 M Repair back door to open and close properly
273688 02/08/2008 168742 P 538 O Limit flammable wall covering to 20% of wall area
259800 02/08/2008 141200 P 2134 C Provide bottom rail on ramp landing guardrail at two inches above floor
259716 02/08/2008 141020 P 492 C Provide handrails along stair at 34-38" high with continuous graspable surface
273668 02/08/2008 168701 1 803A MS Adjust fire door to latch properly
273681 02/08/2008 168727 1 998 MS Seal penetration around conduits in wall
273692 02/08/2008 168750 P 2131 MS Provide current inspection tag for fire extinguisher
273660 02/08/2008 168685 1 403F FS Secure hanging heat detector
190693 01/25/2008 21033 P 1147 M Modify existing foundations and anchorage to comply with engineering requirements
190701 01/25/2008 21040 P 1261 M Modify existing foundations and anchorage to comply with engineering requirements
190697 01/25/2008 21035 P 1447 M Modify existing foundations and anchorage to comply with engineering requirements
190689 01/25/2008 21029 P 1517 M Modify existing foundations and anchorage to comply with engineering requirements
190627 01/25/2008 20941 P 2130 M Modify existing foundations and anchorage to comply with engineering requirements
190721 01/25/2008 20952 P 2131 M Modify existing foundations and anchorage to comply with engineering requirements
190666 01/25/2008 21013 P 2134 M Modify existing foundations and anchorage to comply with engineering requirements
190654 01/25/2008 21008 P 2135 M Modify existing foundations and anchorage to comply with engineering requirements
190672 01/25/2008 21019 P 2136 M Modify existing foundations and anchorage to comply with engineering requirements
259711 10/12/2007 141005 P 498 M Replace worn non-slip surface on ramp and stair
259644 10/12/2007 140864 1 812A C Provide tempered glass, safety glass, or stainless steel for mirrors
259739 10/12/2007 141068 P 476 C Provide bottom rail on ramp landing guardrail at two inches above floor
190581 10/12/2007 34288 1 312 OS Prohibit charging batteries in room
259128 10/12/2007 139781 1 312A OS Prohibit charging batteries in room
259653 10/12/2007 140876 1 207 FS Provide heat detector in communications/storage room
260059 10/12/2007 141708 P 2127 N/A No violations observed
259666 03/30/2007 140910 1 045 M Remove left arrow from illuminated exit sign at fire doors adjacent to 1-400
250967 03/30/2007 121988 1 301 M Adjust door to Kitchen to latch properly
190678 03/30/2007 21147 P 2136 M Adjust ramp landing to be level with interior floor
259862 03/30/2007 141330 1 0000 O Highlight specific evacuation routes for evacuation signs in every student space
259137 03/30/2007 139802 1 112 O Eliminate extension cord or replace with minimum 15A cord
259138 03/30/2007 139804 1 112 O Remove and prohibit air freshener
259633 03/30/2007 140840 1 200 O No access was available to this room. Please be prepared to access this room during the report review meeting.
259182 03/30/2007 139898 1 303B O No access was available to this room. Please be prepared to access this room during the report review meeting.
259129 03/30/2007 139785 1 312B O No access was available to this room. Please be prepared to access this room during the report review meeting.
259130 03/30/2007 139787 1 313 O No access was available to this room. Please be prepared to access this room during the report review meeting.
259660 03/30/2007 140898 1 502 O Keep sawdust cleaned off all surfaces, including equipment, floors, ledges, etc.
259661 03/30/2007 140902 1 502C O Keep sawdust cleaned off all surfaces, including equipment, floors, ledges, etc.
259658 03/30/2007 140894 1 504 O Keep sawdust cleaned off all surfaces, including equipment, floors, ledges, etc.
259892 03/30/2007 141392 1 602 O Eliminate extension cord or replace with minimum 15A cord
259630 03/30/2007 140830 1 700D O No access was available to this room. Please be prepared to access this room during the report review meeting.
259891 03/30/2007 141390 1 700F O No access was available to this room. Please be prepared to access this room during the report review meeting.
259631 03/30/2007 140832 1 702 O No access was available to this room. Please be prepared to access this room during the report review meeting.
259871 03/30/2007 141350 1 800A O Remove storage blocking clear access to emergency eye wash
259872 03/30/2007 141352 1 800A O Prohibit plugging surge protector into extension cord
259863 03/30/2007 141333 1 801A O Remove and prohibit paper covering window in exterior door
259864 03/30/2007 141335 1 801A O Prohibit plugging surge protector into extension cord
259865 03/30/2007 141337 1 801A O Eliminate extension cord or replace with minimum 15A cord
259877 03/30/2007 141362 1 805A O Eliminate extension cord or replace with minimum 15A cord
259878 03/30/2007 141364 1 807A O Eliminate extension cord with multi-outlet end or replace with minimum 15A cord with single outlet end
259874 03/30/2007 141356 1 808A O Prohibit plugging surge protector into extension cord
259875 03/30/2007 141358 1 808A O Eliminate extension cord or replace with minimum 15A cord
259647 03/30/2007 140872 1 814A O Keep storage off hot water heater
259899 03/30/2007 141407 1 821B O Remove and prohibit use of crock pot for heating water and cinnamon
259887 03/30/2007 141382 1 825B O Eliminate extension cord or replace with minimum 15A cord
259885 03/30/2007 141378 1 826B O Prohibit plugging surge protector into extension cord
259886 03/30/2007 141380 1 826B O Eliminate extension cord or replace with minimum 15A cord
259881 03/30/2007 141370 1 827B O Prohibit storage of chemicals in cabinets
259882 03/30/2007 141372 1 827B O Prohibit plugging surge protector into extension cord
259883 03/30/2007 141374 1 827B O Eliminate extension cord or replace with minimum 15A cord
259889 03/30/2007 141386 1 829B O Prohibit storage of chemicals in cabinets
259636 03/30/2007 140846 1 832B O Remove and prohibit air freshener and air freshener spray
259879 03/30/2007 141366 1 840C O Eliminate extension cord with multi-outlet end or replace with minimum 15A cord with single outlet end
259880 03/30/2007 141368 1 840C O Prohibit plugging surge protector into extension cord
259829 03/30/2007 141257 1 847C O Remove paper covering wall - maximum amount of wall area that can be covered is 20%
259834 03/30/2007 141270 1 901E O No access was available to this room. Please be prepared to access this room during the report review meeting.
259853 03/30/2007 141312 1 902E O Remove and prohibit air freshener
259855 03/30/2007 141315 1 902E O Remove bleach from bathroom or keep in locked cabinet to prohibit access by students
259852 03/30/2007 141310 1 903 O Replace bulbs in light fixture
259824 03/30/2007 141246 P 1447 O Provide verification that written permission from principal has been provided to keep snake in the classroom and that all required safety precautions are being followed. Animal may only be in room as part of a particular curriculum and removed when that curriculum is complete.
259184 03/30/2007 139902 P 2131 O Eliminate extension cord or replace with minimum 15A cord
259722 03/30/2007 141031 P 2136 O Eliminate extension cord or replace with minimum 15A cord
259712 03/30/2007 141009 P 498 O Remove and prohibit paper covering window in door
259811 03/30/2007 141219 P 536 O Prohibit plugging surge protector to extension cord
259813 03/30/2007 141226 P 536 O Eliminate extension cord or replace with minimum 15A cord
259709 03/30/2007 141003 P 537 O Eliminate extension cord or replace with minimum 15A cord
259704 03/30/2007 140994 P 538 O Prohibit plugging surge protector to extension cord
259619 03/30/2007 140808 P 9933 O Remove and prohibit paper covering windows in doors
259741 03/30/2007 141073 P 9936 O Remove and prohibit combustible (residential) chair
259620 03/30/2007 140810 P 9938 O Remove and prohibit paper covering windows in doors
259626 03/30/2007 140821 P 9941 O Relocate bookcase blocking clear access to electrical panel
190574 03/30/2007 20918 1 304 C Provide partitions between urinals
190623 03/30/2007 20932 1 901C C Provide partitions between urinals
259735 03/30/2007 141058 P 3573 C Provide non-slip surface for stairs
259643 03/30/2007 140861 1 202F OS Relocate storage cabinet blocking clear path to exterior door
259655 03/30/2007 140889 1 210 OS Provide minimum 3' wide clear path from door at 1-209 to door into 1-300
259688 03/30/2007 140957 1 303 OS Remove tables blocking clear path from emergency exit door out of 1-401
259133 03/30/2007 139793 1 303 OS Remove chairs from exit corridor outside 1-303B
259178 03/30/2007 139890 1 303C OS Prohibit wedging open fire door
259689 03/30/2007 140960 1 303E OS Prohibit wedging open fire door
259691 03/30/2007 140963 1 303F OS Remove storage at bottom of steps leading to mechanical mezzanine
263100 03/30/2007 145813 1 305 OS Prohibit blocking open corridor door
263102 03/30/2007 145819 1 312 OS Prohibit blocking open corridor door
259140 03/30/2007 139808 1 314 OS Remove storage from mechanical room
259677 03/30/2007 140934 1 401 OS Remove instuments from steps at emergency exit door
259679 03/30/2007 140938 1 401 OS Provide minimum 3' wide clear path to emergency exit door
259684 03/30/2007 140949 1 403 OS Provide clear path to emergency exit door
259662 03/30/2007 140904 1 502 OS Remove ladders blocking clear path from exit door leading from 1-500
259893 03/30/2007 141394 1 600 OS Prohibit wedging open corridor door
259896 03/30/2007 141399 1 600 OS Relocate copy machine blocking clear path from emergency exit door leading from 1-601
259894 03/30/2007 141397 1 601 OS Relocate teacher's desk and storage blocking clear path to emergency exit door into 1-600
259897 03/30/2007 141402 1 603 OS Remove and prohibit toaster
259181 03/30/2007 139894 1 807A OS Prohibit wedging open corridor door
259873 03/30/2007 141354 1 809A OS Keep doors to storage room closed to provide clear visibility of and access to fire extinguishers and fire alarm pull stations
259888 03/30/2007 141384 1 825B OS Relocate computer table blocking clear path to exterior door
259884 03/30/2007 141376 1 827B OS Relocate bookcase blocking clear access to secondary egress door
259713 03/30/2007 141011 1 998 OS Prohibit storage of gas can
259825 03/30/2007 141251 P 1447 OS Provide and maintain minimum 3' wide clear path to stair door
259618 03/30/2007 140804 P 9933 OS Remove and prohibit candle in bathroom
259750 03/30/2007 141092 P 9935 OS Arrange desks to provide minimum 3' wide clear path to rear door
259753 03/30/2007 141097 P 9935 OS Keep fire extinguisher on bracket - relocate lockers so extinguisher does not interfere
259745 03/30/2007 141082 P 9937 OS Relocate file cabinet blocking clear path to rear door
259748 03/30/2007 141085 P 9937 OS Remove extension cord run through wall into storage room to power refrigerator
259625 03/30/2007 140819 P 9941 OS Relocate storage cabinet blocking clear path to rear door
259183 03/19/2007 139900 00 9599 M Replace inoperable 3210 padlock on gate for fence enclosure between P-1 & the gym
259668 03/19/2007 140914 1 046 M Remove left arrow from illuminated exit sign at end of corridor adjacent to fire doors at 400/500 wing
259670 03/19/2007 140918 1 065 M Remove illuminated exit sign at fire doors that lead into 400/500 wing
259673 03/19/2007 140922 1 065 M Remove right arrow in illuminated exit sign at smoke doors between 600 wing and exterior wall
263097 03/19/2007 145803 1 205A M Change number on staff bathroom adjacent to 1-205 from 1-207 to 1-205A
263093 03/19/2007 145798 1 206A M Change sign on staff bathroom adjacent to 1-206 from 1-208 to 1-206A
259648 03/19/2007 140874 1 206A M Secure loose door knob on staff bathroom
259642 03/19/2007 140859 1 306 M Modify lock on bathroom door so door can be unlocked from the outside without a key
259171 03/19/2007 139873 1 314A M Remove lock from outside face of door to allow reentry into building
259675 03/19/2007 140928 1 401 M Secure loose handrail at stair
259683 03/19/2007 140947 1 403 M Change sign at corridor door to indicate EXIT - not secondary exit
259682 03/19/2007 140942 1 403F M Remove out-of-date fire extinguisher
259131 03/19/2007 139789 1 503 M Provide permanent power source to eliminate anchoring surge protector to wall
259635 03/19/2007 140844 1 700 M Replace CO2 fire extinguisher with ABC extinguisher
259868 03/19/2007 141341 1 800A M Remove label indicating, "In Case of Fire...." from security cover on switch for emergency exhaust system
259859 03/19/2007 141323 1 802A M Determine cause of water damaged ceiling tiles and replace tiles
259645 03/19/2007 140868 1 812A M Replace lock on bathroom door to unlock from the outside
259870 03/19/2007 141348 1 820B M Remove label indicating, "In Case of Fire...." from security cover on switch for emergency exhaust system
259639 03/19/2007 140853 1 831B M Repair exhaust fan in bathroom
259640 03/19/2007 140855 1 833B M Repair exhaust fan in bathroom
259869 03/19/2007 141346 1 840C M Remove label indicating, "In Case of Fire...." from security cover on switch for emergency exhaust system
190617 03/19/2007 21088 1 843C M Replace wood paneling with finish material that meets required flame spread rating
190618 03/19/2007 20928 1 845C M Replace wood paneling with finish material that meets required flame spread rating
190621 03/19/2007 20929 1 847C M Replace wood paneling with finish material that meets required flame spread rating (labeled 846C)
259857 03/19/2007 141318 1 900 M Relocate maximum occupancy sign to be inside gym adjacent to exit
259850 03/19/2007 141304 1 900 M Repair broken exit sign at 1-999D
251198 03/19/2007 122497 1 901 M Determine cause of water damaged ceiling and replace or repair hard ceiling
251199 03/19/2007 122499 1 998 M Replace rusted and leaking boiler tank
190624 03/19/2007 21094 1 998 M Provide current state inspection tag for boiler
259831 03/19/2007 141263 P 1147 M Replace broken cover plate for light switch adjacent to stair door
259832 03/19/2007 141266 P 1147 M Replace broken floor tiles at stair door
259817 03/19/2007 141231 P 1261 M Provide correct bracket for fire extinguisher
259820 03/19/2007 141239 P 1261 M Repair stair door to close properly - metal threshold is bent and keeps door from closing properly
259822 03/19/2007 141242 P 1447 M Repair stair door to close properly
259828 03/19/2007 141254 P 1447 M Repair ramp door to close and latch properly
251236 03/19/2007 122574 P 1517 M Adjust steps to make risers and treads equal
259185 03/19/2007 139904 P 2130 M Replace extremely worn stair
259797 03/19/2007 141191 P 2134 M Replace worn boards along ramp
259799 03/19/2007 141197 P 2134 M Replace missing metal siding at end of portable
190671 03/19/2007 21143 P 2134 M Adjust ramp and stair landing to be level with interior floor
259794 03/19/2007 141183 P 2135 M Replace worn ramp boards
259796 03/19/2007 141188 P 2135 M Provide support under stair stringer
259720 03/19/2007 141027 P 2136 M Replace worn non-slip surface for ramp
259736 03/19/2007 141061 P 3573 M Determine cause of water damaged ceiling tiles and replace tiles
259737 03/19/2007 141064 P 3573 M Replace worn boards along ramp
259718 03/19/2007 141023 P 492 M Replace worn non-slip surface for stair
259715 03/19/2007 141016 P 492 M Replace worn boards along ramp
259801 03/19/2007 141202 P 534 M Adjust front door to latch properly
259806 03/19/2007 141210 P 535 M Repair rear door to close and latch properly
259808 03/19/2007 141215 P 535 M Repair emergency lighting
259814 03/19/2007 141229 P 536 M Replace missing handicapped hardware at rear door
259705 03/19/2007 140996 P 538 M Replace missing ceiling tiles
259708 03/19/2007 141000 P 538 M Repair rear door to close and latch properly
259703 03/19/2007 140992 P 538 M Repair emergency lighting
259627 03/19/2007 140823 P 9931 M Repair holes in walls at bathroom and at teacher's computer table
259743 03/19/2007 141078 P 9936 M Adjust rear door to latch properly
259622 03/19/2007 140812 P 9938 M Adjust rear door to latch properly
259623 03/19/2007 140815 P 9939 M Adjust rear door to latch properly
259624 03/19/2007 140817 P 9940 M Adjust rear door to close and latch properly
259186 03/19/2007 139906 P 9942 M Adjust rear door to latch properly
230804 03/19/2007 84535 1 403 C Install maximum occupancy signage (max. occupancy = 41)
190626 03/19/2007 20938 P 2130 C Modify or replace stair with stair minimum 44" wide
259638 03/19/2007 140851 1 202 MS Provide current inspection tag for fire extinguisher (dated 12/04)
259646 03/19/2007 140870 1 202C MS Provide current inspection tag for fire extinguisher (dated 6/04)
259641 03/19/2007 140857 1 204 MS Provide current inspection tag for fire extinguisher (dated 6/04)
259177 03/19/2007 139879 1 303 MS Remove hook hold open device from corridor door adjacent to 1-303B
259132 03/19/2007 139791 1 303D MS Provide current inspection tag for fire extinguisher (dated 1/05)
259890 03/19/2007 141388 1 305 MS Remove dog leg hold open device from corridor door
259134 03/19/2007 139795 1 312 MS Remove dog leg hold open device from corridor door
259139 03/19/2007 139806 1 502 MS Provide current inspection tag for fire extinguisher
250979 03/19/2007 122006 1 700F MS Provide current inspection tag for fire extinguisher
259632 03/19/2007 140838 1 701 MS Remove locks from doors leading into 1-700A to allow egress at all times
259861 03/19/2007 141327 1 803A MS Provide current inspection tag for fire extinguisher (dated 1/05)
259876 03/19/2007 141360 1 808A MS Provide current inspection tag for fire extinguisher (dated 5/04)
259637 03/19/2007 140849 1 832B MS Adjust corridor door to close and latch properly
259819 03/19/2007 141236 P 1261 MS Replace missing inspection tag for fire extinguisher
259756 03/19/2007 141107 P 9933 MS Provide current inspection tag for fire extinguisher
259135 03/19/2007 139798 1 201A FS Provide heat detector in laundry/storage room
259634 03/19/2007 140842 1 700E FS Provide heat detector in storage room (room is labeled 1-700D)
250962 11/01/2006 121977 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
250971 11/01/2006 121996 1 314 M Repair NE door to exterior to open and close properly
251169 11/01/2006 122431 1 825B M Secure loose glazing in exterior door
251170 11/01/2006 122434 1 826B M Secure loose glazing in exterior door
251175 11/01/2006 122446 1 827B M Replace broken glass in door
251216 11/01/2006 122528 P 1147 M Repair broken weld on handrail along ramp
230783 11/01/2006 84494 P 1261 M Adjust ramp landing to be level with interior floor
190709 11/01/2006 21167 P 1261 M Adjust ramp and stair landing to be level with interior floor
190663 11/01/2006 21141 P 2135 M Adjust ramp and stair landing to be level with interior floor
190681 11/01/2006 21148 P 3573 M Adjust steps to make risers equal
251360 11/01/2006 122910 P 476 M Adjust steps to make risers equal
190550 11/01/2006 20904 00 9599 C Install drain pipes under existing sidewalks to facilitate drainage in portable area
230799 11/01/2006 84525 1 803A C Provide signage indicating room name and number at appropriate height with raised and Braille characters
190670 11/01/2006 21012 P 2134 C Provide handrails on each side of stair
190667 11/01/2006 21009 P 2134 C Provide balusters on stair landing guardrail at six inches apart
190661 11/01/2006 21007 P 2135 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
190656 11/01/2006 21005 P 2135 C Provide balusters on stair landing guardrail at six inches apart
190658 11/01/2006 21003 P 2135 C Provide balusters at six inches apart on ramp landing guardrail
251351 11/01/2006 122880 P 2135 C Provide handrails on each side of stair
250966 11/01/2006 121985 1 118A F Provide heat detector in electrical closet
251188 11/01/2006 122455 1 504 F Relocate heat detector to high point of ceiling
230777 02/16/2006 84471 00 9500 M Complete repairs on missing roofing on portables
251386 02/16/2006 122969 00 9599 M Repair broken sidewalk adjacent to P-1 & P-5
250960 02/16/2006 121973 00 9698 M Replace missing cover on clean out in parking lot east of 1-310 (at car stop)
251389 02/16/2006 122972 00 9699 M Fill trench cut for fire line at portables. Fill hole at Fire Department connection and fill adjacent to and below sidewalk
250963 02/16/2006 121979 1 107 M Provide cover on exposed electrical junction box behind air handler
250964 02/16/2006 121981 1 115B M Anchor toilet to floor
250965 02/16/2006 121983 1 121C M Repair exhaust fan in bathroom
230709 02/16/2006 84342 1 201A M Replace plastic dryer vent pipe with metal vent pipe
250986 02/16/2006 122016 1 213 M Seal open seam in vinyl flooring
190573 02/16/2006 34281 1 302 M Replace missing magnetic hold open device on door
250972 02/16/2006 121998 1 303F M Provide cover on exposed A/C control box on mechanical mezzanine above 1-303E
250968 02/16/2006 121990 1 304 M Secure loose handicapped grabrail
250987 02/16/2006 122019 1 305 M Provide bracket for fire extinguisher and install fire extinguisher at maximum five feet above floor adjacent to exit
251422 02/16/2006 123060 1 307 M Adjust location of tilting skillet or adjust suppression heads to provide proper coverage for tilting skillet
190577 02/16/2006 21065 1 307 M Verify activation of hood fire suppression system will initiate school fire alarm
190578 02/16/2006 21064 1 307 M Verify that electricity and gas to appliances shuts off upon activation of hood suppression system
230716 02/16/2006 84356 1 312 M Replace plastic dryer vent pipe with metal vent pipe
190600 02/16/2006 21074 1 500A M Repair or replace torn carpeting
251178 02/16/2006 122452 1 605 M Seal open seam in vinyl flooring
251195 02/16/2006 122490 1 703 M Provide cover on exposed Neptronic control box
251196 02/16/2006 122492 1 807A M Secure loose cover plate on TV outlet box on wall at 7 feet
251193 02/16/2006 122487 1 813A M Repair auto closers on 2 stall doors
251202 02/16/2006 122506 1 821B M Provide cover for exposed electrical outlet on south wall
251197 02/16/2006 122494 1 847C M Adjust door to exterior to latch properly
251192 02/16/2006 122484 1 852C M Anchor shelving to wall
230738 02/16/2006 84401 P 1126 M Replace bent grill on A.C. duct on south wall
190733 02/16/2006 21113 P 1126 M Adjust steps to make risers equal
230736 02/16/2006 84397 P 1126 M Repair exterior siding on the north side of portable
190695 02/16/2006 21157 P 1147 M Adjust steps to make risers equal
251217 02/16/2006 122536 P 1147 M Repair emergency lighting
251220 02/16/2006 122541 P 1147 M Replace damaged stair door
190702 02/16/2006 21168 P 1261 M Secure and protect insulation on portable unit
190706 02/16/2006 21166 P 1261 M Adjust steps to make risers equal (P-116)
190700 02/16/2006 21163 P 1447 M Adjust steps to make risers equal
230785 02/16/2006 84498 P 1447 M Repair exterior siding on south side of portable
230786 02/16/2006 84500 P 1447 M Secure loose ramp walkway boards
190698 02/16/2006 21164 P 1447 M Secure and protect insulation on portable unit
251233 02/16/2006 122568 P 1447 M Repair emergency lighting
251234 02/16/2006 122571 P 1517 M Repair emergency lighting
251223 02/16/2006 122553 P 2130 M Repair emergency lighting
230720 02/16/2006 84365 P 2130 M Replace metal exterior siding @ S.E. corner of portable
230725 02/16/2006 84375 P 2131 M Replace exterior wall siding
251228 02/16/2006 122558 P 2134 M Repair emergency lighting
251226 02/16/2006 122556 P 2135 M Repair emergency lighting
251357 02/16/2006 122901 P 2135 M Repair or replace door that is damaged at latch
190662 02/16/2006 21140 P 2135 M Secure loose handrail for stairs
251225 02/16/2006 122555 P 2136 M Repair emergency lighting
190713 02/16/2006 34276 P 227 M Repair all damaged rain downspouts
190715 02/16/2006 34294 P 227 M Replace missing guardrails and balusters on stairs.
190637 02/16/2006 21123 P 2942 M Remove interior partition walls between two ends of portable which create two separate classrooms
251366 02/16/2006 122928 P 476 M Provide lock on fuse box to prohibit student access
251368 02/16/2006 122934 P 476 M Repair or replace leaking auto closer on door
251373 02/16/2006 122942 P 492 M Replace popped nails on stairs with screws
251224 02/16/2006 122554 P 534 M Repair emergency lighting
251384 02/16/2006 122966 P 536 M Adjust south door to latch properly
251381 02/16/2006 122961 P 538 M Replace missing handicapped accessible door handle outside of south door
251230 02/16/2006 122560 P 538 M Repair emergency lighting
251429 02/16/2006 123077 P 9931 M Replace missing paint/coating on exterior of unit
251393 02/16/2006 122982 00 0 O No access was available to 1-202G, 1-303A, 1-303B, 1-313, 1-901D and 1-901E. Please be prepared to access these rooms during the report review meeting.
251191 02/16/2006 122477 1 500A O Eliminate extension cord or replace with minimum 15A cord. Plug refrigerator directly into outlet
251173 02/16/2006 122439 1 835B O Replace light tubes in light fixture
251435 02/16/2006 123094 P 9936 O Remove storage to provide clear access to electrical panel
251433 02/16/2006 123090 P 9939 O Prohibit plugging surge suppressor into surge suppressor
251432 02/16/2006 123088 P 9940 O Clean out toilet. No water to unit, bathroom not connected
190548 02/16/2006 20903 00 9599 C Provide fencing around electrical panels adjacent to P-12
190575 02/16/2006 34250 1 307 C Provide magnetic release hold open devices for fire doors leading to 1-301 and 1-302
190605 02/16/2006 34256 1 700 C Provide additional electrical outlets to run computer equipment to eliminate the need for multiple extension cords
190730 02/16/2006 20964 P 1126 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190731 02/16/2006 20960 P 1126 C Provide balusters on stair landing guardrail at six inches apart
190736 02/16/2006 20965 P 1126 C Provide ramp for portable
190696 02/16/2006 21032 P 1147 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
190694 02/16/2006 21031 P 1147 C Provide balusters on stair landing guardrail at six inches apart
190707 02/16/2006 21039 P 1261 C Provide handrails along stair at 34-38 inches high with continuous graspable surface (P-116)
190705 02/16/2006 21037 P 1261 C Provide bottom rail on stair landing guardrail at two inches above floor (P-116)
190699 02/16/2006 21034 P 1447 C Provide bottom rail on ramp landing guardrail at two inches above floor
190630 02/16/2006 20970 P 147 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190633 02/16/2006 20973 P 200 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190636 02/16/2006 20975 P 2127 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190629 02/16/2006 20942 P 2130 C Provide ramp for portable
190669 02/16/2006 21011 P 2134 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
190659 02/16/2006 21004 P 2135 C Provide bottom rail on ramp landing guardrail at two inches above floor
190657 02/16/2006 21006 P 2135 C Provide guardrails at stair landing at a minimum 42 inches high
190673 02/16/2006 21014 P 2136 C Provide balusters on stair landing guardrail at six inches apart
190674 02/16/2006 21016 P 2136 C Provide guardrails at stair landing at a minimum 42 inches high
190676 02/16/2006 21017 P 2136 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
190677 02/16/2006 21018 P 2136 C Provide handrails on each side of stair
190712 02/16/2006 21047 P 227 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
230749 02/16/2006 84423 P 228 C Provide balusters on stair landing guardrail at six inches apart
190644 02/16/2006 20977 P 228 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190638 02/16/2006 20979 P 2942 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190640 02/16/2006 20980 P 2942 C Provide bottom rail on stair landing guardrail at two inches above floor
190682 02/16/2006 21020 P 3573 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
230768 02/16/2006 84461 P 3694 C Provide balusters on stair landing guardrail at six inches apart
190710 02/16/2006 21045 P 3694 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190648 02/16/2006 20991 P 498 C Provide guardrails at stair landing at a minimum 42 inches high
190649 02/16/2006 20992 P 498 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
251379 02/16/2006 122956 P 535 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
251380 02/16/2006 122958 P 538 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190717 02/16/2006 20988 P 748 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190719 02/16/2006 20987 P 748 C Provide bottom rail on stair landing guardrail at two inches above floor
230752 02/16/2006 84429 P 748 C Provide balusters on stair landing guardrail at six inches apart
190642 02/16/2006 20985 P 759 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190641 02/16/2006 20982 P 794 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
251431 02/16/2006 123081 P 9941 C Provide non-slip impervious floor surface and install base in bathroom
251430 02/16/2006 123079 P 9942 C Provide non-slip impervious floor surface and install base in bathroom
190571 02/16/2006 34279 1 301 F Replace missing magnetic hold open device on door
190572 02/16/2006 34280 1 301A F Replace missing magnetic hold open device on door
251206 02/16/2006 122512 1 087 MS Adjust fire door adjacent to 1-823B to latch properly. Could not get door to release from hold open device.
250973 02/16/2006 122000 1 212 MS Provide current inspection tag for fire extinguisher
230713 02/16/2006 84350 1 303A MS Provide current inspection tag for fire extinguisher
250984 02/16/2006 122012 1 303D MS Provide current inspection tag for fire extinguisher
250985 02/16/2006 122014 1 303F MS Provide current inspection tag for fire extinguisher
250974 02/16/2006 122001 1 303H MS Provide current inspection tag for fire extinguisher
251421 02/16/2006 123056 1 307 MS Provide current inspection tag for Kitchen hood fire suppression system
250975 02/16/2006 122002 1 310A MS Provide current inspection tag for fire extinguisher
250976 02/16/2006 122003 1 311 MS Provide current inspection tag for fire extinguisher
250977 02/16/2006 122004 1 312 MS Provide current inspection tag for fire extinguisher
250978 02/16/2006 122005 1 314 MS Provide current inspection tag for fire extinguisher
190583 02/16/2006 20874 1 314 MS Remove storage from mechanical room
250980 02/16/2006 122007 1 810A MS Provide current inspection tag for fire extinguisher
250981 02/16/2006 122008 1 830B MS Provide current inspection tag for fire extinguisher
250982 02/16/2006 122009 1 840C MS Provide current inspection tag for fire extinguisher
250983 02/16/2006 122010 1 850C MS Provide current inspection tag for fire extinguisher
250970 02/16/2006 121994 1 314 OS Remove storage from mechanical room
251201 02/16/2006 122504 1 901D OS Prohibit storage of flammable spray paint
251377 02/16/2006 122951 P 534 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station
251383 02/16/2006 122964 P 536 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station
251434 02/16/2006 123092 P 9937 OS Prohibit electrical cord from running through bathroom door opening
230730 02/16/2006 84385 P 200 CS Remove desks blocking egress to allow safe evacuation
250961 02/16/2006 121975 1 207 FS Provide heat detector in room used for storage
250969 02/16/2006 121992 1 312 FS Provide certification that fire alarm system has been tested and is fully operational (tagged 8/04)
230796 02/16/2006 84519 1 832B FS Provide heat detector in janitor's closet
190632 02/16/2006 20835 P 200 FS Secure heat detector hanging by wires
190650 01/26/2006 21000 P 492 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190647 01/26/2006 20993 P 498 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190728 01/26/2006 20958 P 534 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190726 01/26/2006 20956 P 535 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190724 01/26/2006 20954 P 536 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190725 01/26/2006 20955 P 536 C Provide engineer's verification that anchorage system is adequate or provide suitable anchorage
190664 01/26/2006 20943 P 537 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190665 01/26/2006 20944 P 537 C Provide engineer's verification that anchorage system is adequate or provide suitable anchorage
190716 01/26/2006 20945 P 538 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190553 01/25/2005 34292 1 0000 M Repair vandalized water fountain (adjacent to 832B)
190558 01/25/2005 29593 1 0000 M Remove expandable gate at exit doors at end of corridor near 1-836B
230797 01/25/2005 84521 1 087 M Provide cover on exposed electrical junction box in corridor @ 1-832B
190559 01/25/2005 21054 1 100 M Repair or replace carpeting
190560 01/25/2005 21055 1 102A M Repair exhaust fan in bathroom
190561 01/25/2005 34295 1 106 M Replace missing threshold
190564 01/25/2005 21056 1 117 M Repair or replace worn and rippled carpeting along corridor
230706 01/25/2005 84336 1 119A M Provide cover on exposed electrical junction box on south wall
230708 01/25/2005 84340 1 201 M Determine cause of water damaged ceiling tiles and replace tiles
230710 01/25/2005 84344 1 202F M Provide cover on exposed electrical junction box @ 1-202C
230711 01/25/2005 84346 1 213 M Determine cause of water damaged ceiling tiles and replace tiles
190570 01/25/2005 21061 1 300 M Determine cause of water damaged ceiling tiles and replace tiles
190579 01/25/2005 21066 1 307A M Repair or replace water damaged ceiling
230712 01/25/2005 84348 1 307E M Replace plastic dryer vent with metal vent pipe
230702 01/25/2005 84327 1 312A M Determine cause of water damaged ceiling tiles and replace tiles
230717 01/25/2005 84358 1 400 M Determine cause of water damaged ceiling tiles and replace tiles
190602 01/25/2005 34234 1 500C M Replace missing a/c grille
230718 01/25/2005 84360 1 502 M Pad and mark corners of TV shelf which are lower than 6'8"
230790 01/25/2005 84508 1 601 M Determine cause of water damaged ceiling tiles and replace tiles
230791 01/25/2005 84509 1 603 M Determine cause of water damaged ceiling tiles and replace tiles above teacher's desk
230792 01/25/2005 84511 1 603 M Replace glazing in corridor door with fire rated glazing or wired glass
190610 01/25/2005 34237 1 802A M Determine cause of water damaged ceiling tiles and replace tiles
230801 01/25/2005 84529 1 813A M Repair broken base tile along wall in boy's bathroom
230793 01/25/2005 84513 1 820B M Repair base along wall @ 1-829B
230795 01/25/2005 84517 1 820B M Repair damaged cabinet below and beside sink on north wall
190611 01/25/2005 21084 1 820B M Adjust flow of eye wash and clear drain
190612 01/25/2005 34286 1 820B M Eliminate mold and mildew in cabinet under eye wash and replace damaged cabinet bottom
230794 01/25/2005 84515 1 829B M Determine cause of water damaged ceiling tiles and replace tiles
230798 01/25/2005 84523 1 831B M Repair broken base tile along wall in boy's bathroom
230737 01/25/2005 84399 P 1126 M Determine cause of water damaged ceiling tiles and replace tiles
230784 01/25/2005 84496 P 1147 M Repair stair door to close properly
230782 01/25/2005 84492 P 1261 M Repair damaged awning by ramp door
230787 01/25/2005 84502 P 1447 M Determine cause of water damaged ceiling tiles and replace tiles
230789 01/25/2005 84506 P 1447 M Repair light in exit sign
230739 01/25/2005 84403 P 147 M Repair stair door to close properly
230740 01/25/2005 84405 P 147 M Repair emergency lighting
230741 01/25/2005 84407 P 147 M Repaint bare spots on N.E. exterior wall
230781 01/25/2005 84490 P 1517 M Determine cause of water damaged ceiling tiles and replace tiles
230743 01/25/2005 84411 P 200 M Determine cause of water damaged ceiling tiles and replace tiles
230744 01/25/2005 84413 P 2127 M Repair stair door to close properly
190628 01/25/2005 21098 P 2130 M Adjust arm of door closer at stair door so that it does not stick into room
230726 01/25/2005 84377 P 2131 M Determine cause of water damaged ceiling tiles and replace tiles
190655 01/25/2005 21139 P 2135 M Adjust arm of door closer at ramp door so that it does not stick into room
230780 01/25/2005 84486 P 2136 M Determine cause of water damaged ceiling tiles and replace tiles
230753 01/25/2005 84431 P 227 M Determine cause of water damaged ceiling tiles and replace tiles
230756 01/25/2005 84434 P 227 M Repair hole in exterior wall by ramp
230763 01/25/2005 84448 P 227 M Repair two rotted exterior window frames on ramp side
230750 01/25/2005 84425 P 228 M Repair front door to close properly
230751 01/25/2005 84427 P 228 M Determine cause of water damaged ceiling tiles and replace tiles
190686 01/25/2005 21150 P 228 M Adjust steps to make risers equal
230747 01/25/2005 84419 P 2942 M Determine cause of water damaged ceiling tiles and replace tiles
230764 01/25/2005 84456 P 3694 M Determine cause of water damaged ceiling tiles and replace tiles
190651 01/25/2005 21138 P 492 M Adjust uneven boards at bottom of ramp and make boards even with sidewalk
230735 01/25/2005 84395 P 534 M Repair rear door to close properly
230734 01/25/2005 84393 P 535 M Determine cause of water damaged ceiling tiles and replace tiles
230722 01/25/2005 84369 P 537 M Repair or replace rotted door
230723 01/25/2005 84371 P 537 M Determine cause of water damaged ceiling tiles and replace tiles
230724 01/25/2005 84373 P 538 M Adjust rear door to close properly
230748 01/25/2005 84421 P 759 M Repair hole in exterior wall on ramp side of portable
230745 01/25/2005 84415 P 794 M Determine cause of water damaged ceiling tiles and replace tiles
230703 01/25/2005 84329 1 105 O Eliminate extension cord powering microwave oven
230714 01/25/2005 84352 1 303A O Provide clear access to electrical panel
190585 01/25/2005 61675 1 402 O Prohibit running extension cord through door
230719 01/25/2005 84362 1 502C O Maintain storage room in an orderly manner
230805 01/25/2005 84537 1 700 O Eliminate multi-outlet adaptor plugged into electric outlet behind information desk
230729 01/25/2005 84383 1 902F O Remove sign that indicates "Stop, Do Not Use This Door" which exits into corridor 1-999D
230742 01/25/2005 84409 P 200 O Eliminate extension cord powering refrigerator in storage room
230727 01/25/2005 84379 P 2131 O Install cover strip on electric cord on floor
230728 01/25/2005 84381 P 536 O Eliminate 6-way adaptor plugged into electric outlet
190723 01/25/2005 61676 P 536 O Prohibit running extension cord through ceiling
190737 01/25/2005 20967 00 154 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190554 01/25/2005 20792 1 0000 C Provide illuminated exit sign on each side of smoke stop doors between 600 wing and exterior wall (near 1-604)
190557 01/25/2005 20836 1 0000 C Provide labels for all doors and frames indicating fire rating
190551 01/25/2005 20794 1 0000 C Provide panic hardware on fire doors at end of corridor across from 1-503 and adjust doors to latch properly
230707 01/25/2005 84338 1 201 C Install GFCI outlet next to all sinks
190569 01/25/2005 34293 1 300 C Provide sign indicating maximum occupancy adjacent to main entrance
230800 01/25/2005 84527 1 812A C Provide tempered glass, safety glass, or stainless steel for mirrors
190613 01/25/2005 20925 1 829B C Provide or verify exhaust to exterior for chemical storage room
190622 01/25/2005 20803 1 900 C Provide sign indicating maximum occupancy adjacent to main entrance
190732 01/25/2005 20961 P 1126 C Provide guardrails at stair landing at a minimum 42 inches high
190734 01/25/2005 20963 P 1126 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
190735 01/25/2005 20962 P 1126 C Provide handrails on each side of stair
190708 01/25/2005 21038 P 1261 C Provide handrails on each side of stair (P-116)
190703 01/25/2005 21042 P 1261 C Replace threshold with one at maximum 1/2 inch high (P-116)
190704 01/25/2005 21036 P 1261 C Provide balusters on stair landing guardrail at six inches apart (P-116)
190631 01/25/2005 20968 P 147 C Provide bottom rail on stair landing guardrail at two inches above floor
190690 01/25/2005 21027 P 1517 C Provide guardrails at stair landing at a minimum 42 inches high
190691 01/25/2005 21028 P 1517 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
190692 01/25/2005 21030 P 1517 C Provide ramp for portable
190738 01/25/2005 20966 P 154 C Provide bottom rail on ramp landing guardrail at two inches above floor
190634 01/25/2005 20971 P 200 C Provide bottom rail on stair landing guardrail at two inches above floor
190635 01/25/2005 20972 P 200 C Provide bottom rail on ramp landing guardrail at two inches above floor
190720 01/25/2005 20949 P 2131 C Modify or replace stair with stair minimum 44" wide
190668 01/25/2005 21010 P 2134 C Provide bottom rail on ramp landing guardrail at two inches above floor
190660 01/25/2005 21002 P 2135 C Provide guardrails at ramp landing at a minimum 42 inches high
190675 01/25/2005 21015 P 2136 C Provide bottom rail on ramp landing guardrail at two inches above floor
190714 01/25/2005 21046 P 227 C Provide bottom rail on stair landing guardrail at two inches above floor
190645 01/25/2005 20976 P 228 C Provide bottom rail on ramp landing guardrail at two inches above floor
190639 01/25/2005 20978 P 2942 C Provide bottom rail on stair landing guardrail at two inches above floor
190711 01/25/2005 21044 P 3694 C Provide bottom rail on stair landing guardrail at two inches above floor
190683 01/25/2005 21025 P 476 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190684 01/25/2005 21022 P 476 C Provide balusters on stair landing guardrail at six inches apart
190685 01/25/2005 21023 P 476 C Provide guardrails at stair landing at a minimum 42 inches high
190687 01/25/2005 21024 P 476 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
190688 01/25/2005 21026 P 476 C Provide ramp for portable
190652 01/25/2005 20997 P 492 C Provide bottom rail on ramp landing guardrail at two inches above floor
190653 01/25/2005 20999 P 492 C Provide handrails along stair at 34-38? high with continuous graspable surface
190646 01/25/2005 20990 P 498 C Replace worn non-slip surface for ramp
190729 01/25/2005 20959 P 534 C Provide engineer's verification that anchorage system is adequate or provide suitable anchorage
190727 01/25/2005 20957 P 535 C Provide engineer's verification that anchorage system is adequate or provide suitable anchorage
190643 01/25/2005 20984 P 759 C Provide bottom rail on stair landing guardrail at two inches above floor
190562 01/25/2005 20809 1 115A F Provide fire alarm strobe light
190563 01/25/2005 20810 1 115B F Provide fire alarm strobe light
190607 01/25/2005 20833 1 701A F Provide fire alarm strobe light
190608 01/25/2005 20834 1 701B F Provide fire alarm strobe light
230704 01/25/2005 84332 1 0000 MS Adjust fire doors to release from hold open devices and latch properly. Staff reports that during fire drill conducted 01-20-05 none of the fire or smoke doors closed properly
190599 01/25/2005 34268 1 500 MS Repair light in exit sign
230705 01/25/2005 84334 1 107 OS Remove storage from mechanical room
230715 01/25/2005 84354 1 312 OS Prohibit storage of flammable spray paint
230802 01/25/2005 84531 1 840C OS Prohibit electrical cord from running under doorway between 8-840C and 8-849C
230732 01/25/2005 84389 1 999A OS Remove storage blocking corridor and maintain clear aisle to exit
230788 01/25/2005 84504 P 1447 OS Maintain clear aisle to stair exit
230803 01/25/2005 84533 1 065 CS Remove expandable gate @ fire doors in corridor to allow egress from campus at all times
230721 01/25/2005 84367 P 2130 CS Provide adequate egress to allow safe evacuation
190546 01/25/2005 20808 00 0000 FS Verify all new heat detectors have been connected to fire alarm control panel and all are fully functional
190566 01/25/2005 20811 1 202D FS Provide heat detector in storage room (X2)
190567 01/25/2005 20812 1 202E FS Provide heat detector in storage room (X2)
190568 01/25/2005 20813 1 206 FS Provide heat detector in custodial storage room
190580 01/25/2005 20815 1 311 FS Provide heat detector in boiler room
190582 01/25/2005 20816 1 312A FS Provide heat detector in storage room
190625 01/25/2005 34282 1 314 FS Relocate heat detector to ceiling
190584 01/25/2005 34283 1 401B FS Secure heat detector to ceiling
190586 01/25/2005 20817 1 403B FS Provide heat detector in storage room
190587 01/25/2005 20818 1 403D FS Provide heat detector in storage room
190588 01/25/2005 20819 1 403E FS Provide heat detector in storage room
190589 01/25/2005 20820 1 403F FS Provide heat detector in storage room
190590 01/25/2005 20821 1 403G FS Provide heat detector in storage room
190591 01/25/2005 20822 1 403H FS Provide heat detector in storage room
190592 01/25/2005 20823 1 403I FS Provide heat detector in storage room
190593 01/25/2005 20824 1 403J FS Provide heat detector in storage room
190594 01/25/2005 20825 1 403K FS Provide heat detector in storage room
190595 01/25/2005 20826 1 403L FS Provide heat detector in storage room
190596 01/25/2005 20827 1 403M FS Provide heat detector in storage room
190597 01/25/2005 20828 1 403N FS Provide heat detector in storage room
190598 01/25/2005 20829 1 406B FS Provide heat detector in storage room
190601 01/25/2005 20831 1 500C FS Provide heat detector in storage room
190606 01/25/2005 20832 1 700F FS Provide heat detector in storage room
230746 01/25/2005 84417 P 2942 FS Secure heat detector to ceiling
190718 01/25/2005 21128 P 748 FS Provide heat detector in bathroom used for storage