Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
419129 04/25/2018 484255 10 001 M Repair emergency lighting
419053 04/09/2018 484091 00 0000 M Make repairs as noted on fire sprinkler inspection report, red annual inspection tags
419130 04/09/2018 484257 10 001 M Adjust east door to latch properly
419132 04/09/2018 484261 10 003 M Provide cover on exposed electrical junction box at missing clock
419291 04/09/2018 484603 10 007 M Adjust door to latch properly
419292 04/09/2018 484605 10 011 M Repair emergency lighting
419055 04/09/2018 484096 2 202 M Adjust exterior door to latch properly
397095 04/09/2018 436797 3 308 M Repair exhaust fan in bathroom
419125 04/09/2018 484246 4 410 M Replace missing thermostat cover
419124 04/09/2018 484243 4 411 M Replace missing escutcheon on fire sprinkler head
419128 04/09/2018 484253 4 415 M Adjust door to latch properly
419058 04/09/2018 484103 5 501 M Provide cover on exposed electrical junction box at missing clock
419059 04/09/2018 484105 5 504 M Replace missing base on walls
419081 04/09/2018 484152 5 506 M Repair damaged base on wall at exterior door
419061 04/09/2018 484110 6 602 M Repair exhaust fan in bathroom
419062 04/09/2018 484112 6 605 M Adjust door to latch properly
419060 04/09/2018 484107 6 606 M Repair exhaust fan in bathroom
419063 04/09/2018 484114 6 607 M Repair and secure loose base on walls
419077 04/09/2018 484144 6 615 M Determine cause of water damaged ceiling tiles and replace tiles
419078 04/09/2018 484146 6 618 M Repair exhaust fan in bathroom
419079 04/09/2018 484148 6 619 M Provide cover for data outlet on wall adjacent to teachers desk
419080 04/09/2018 484150 6 620 M Repair exhaust fan in bathroom
419302 04/09/2018 484626 8 801 M Determine cause of water damaged ceiling tiles and replace tiles
419301 04/09/2018 484621 8 802 M Replace missing cover for cleanout
419296 04/09/2018 484612 9 910 M Determine cause of water damaged ceiling tiles and replace tiles
419294 04/09/2018 484609 9 912 M Repair emergency lighting
397081 04/09/2018 436768 9 913 M Repair exhaust fan in bathroom
419293 04/09/2018 484607 9 916A M Repair exhaust fan in bathroom
397080 04/09/2018 436766 9 917 M Repair exhaust fan in bathroom
397079 04/09/2018 436764 9 919 M Repair exhaust fan in bathroom
419299 04/09/2018 484617 9 920 M Adjust exterior door to latch properly
397077 04/09/2018 436760 9 921 M Repair exhaust fan in bathroom
419297 04/09/2018 484615 9 922 M Determine cause of water damaged ceiling tiles and replace tiles
419126 04/09/2018 484248 4 403 O Prohibit use of green multi outlet extension cord at refrigerator or replace with minimum 15A single outlet extension cord
419304 04/09/2018 484630 4 408 O Prohibit plugging surge protector into extension cord
419076 04/09/2018 484141 7 701 O Remove and prohibit solid paper covering wall, limit coverage area to 50 percent of each wall in a room with fire sprinklers
419131 04/09/2018 484259 10 003 MS Recharge fire extinguisher
419286 04/09/2018 484590 10 009 MS Provide type K fire extinguisher at stove
419303 04/09/2018 484628 4 406 MS Provide current inspection tag for fire extinguisher
419057 04/09/2018 484100 12 210 OS Relocate backpacks at 12-008 corridor door to maintain clear aisle to exit
419050 04/09/2018 484080 2 226 OS Remove storage from mechanical room
271685 04/09/2018 164411 10 0000 N/A No violations observed
271675 04/09/2018 164390 2 0000 N/A No violations observed
271676 04/09/2018 164393 3 0000 N/A No violations observed
271677 04/09/2018 164396 4 0000 N/A No violations observed
271680 04/09/2018 164401 6 0000 N/A No violations observed
271681 04/09/2018 164404 7 0000 N/A No violations observed
271683 04/09/2018 164406 8 0000 N/A No violations observed
271684 04/09/2018 164409 9 0000 N/A No violations observed
397105 01/11/2018 436819 2 203 M Adjust door to walk-in cooler to latch properly
397109 01/11/2018 436827 1 107 C Provide automatic fire sprinkler coverage for closet in room
397123 01/11/2018 436858 12 115 C Replace missing evacuation sign indicating primary and secondary evacuation routes in contrasting colors
397125 01/11/2018 436862 12 190 C Provide automatic fire sprinkler coverage for room. No label on door, no fire sprinkler heads, heat detector at ceiling and plan indicates 1 hour walls
397136 01/11/2018 436884 12 290 C Provide automatic fire sprinkler coverage for room. 20 minute door, heat detector at ceiling, no fire sprinkler head and plan indicates 1 hour walls
271686 01/11/2018 164414 11 0000 N/A No violations observed
381780 01/11/2018 403769 13 0000 N/A No violations observed
381781 01/11/2018 403771 14 0000 N/A No violations observed
271679 01/11/2018 164398 5 0000 N/A No violations observed
397108 01/10/2018 436825 1 122 M Repair exhaust fan in bathroom
397130 01/10/2018 436872 12 107A M Repair exhaust fan in bathroom
397054 01/10/2018 436713 12 204C M Repair exhaust fan in bathroom
397055 01/10/2018 436715 12 206A M Repair exhaust fan in bathroom
397052 01/10/2018 436707 12 210A M Repair exhaust fan in bathroom
397049 01/10/2018 436700 4 404 M Repair inoperable air conditioning system
271687 01/10/2018 164416 12 0000 N/A No violations observed
397039 05/01/2017 436683 00 0000 M Make necessary repairs to fire sprinkler system as indicated on inspection report
397116 05/01/2017 436842 2 202 M Repair supply fan for Kitchen hood
397089 03/16/2017 436785 00 0000 M Remove vegetation debris from storm north of building 11
397038 03/16/2017 436680 00 0000 M Clean out all gutters, downspouts and roof drains on campus
397067 03/16/2017 436739 00 0000 M Clean out overflowing drain at 7-704 and 6-612
397110 03/16/2017 436830 1 111 M Provide cover on exposed electrical contactor box
397032 03/16/2017 436667 1 112 M Provide cover on exposed gutter for security wiring
397031 03/16/2017 436665 1 113 M Adjust door to latch properly
397063 03/16/2017 436731 10 003 M Determine cause of water damaged ceiling tiles and replace tiles at projection screen
397061 03/16/2017 436726 10 007 M Provide signage indicating room name and number at appropriate height with raised and Braille characters
397062 03/16/2017 436729 10 008 M Provide signage indicating room name and number at appropriate height with raised and Braille characters
397044 03/16/2017 436693 10 011 M Anchor shelving to wall
397036 03/16/2017 436677 11 104 M Repair emergency lighting. No elite in storage room
397118 03/16/2017 436847 12 002 M Replace missing ceiling tiles in 1st floor corridor at 12-109
397119 03/16/2017 436850 12 003A M Secure lose base along wall at entry
397120 03/16/2017 436852 12 003A M Caulk toilet to wall
397134 03/16/2017 436880 12 003B M Caulk handicapped sink to wall
397035 03/16/2017 436674 12 009A M Repair leaking toilet supply line
397050 03/16/2017 436704 12 101A M Grout or caulk bathroom wall tile at hinge side of door
397126 03/16/2017 436864 12 106 M Replace damaged center light switch
397127 03/16/2017 436866 12 106 M Repair data outlet. See teacher Ms. Furlong
397128 03/16/2017 436868 12 106 M Repair drinking fountain that runs too long
397131 03/16/2017 436874 12 108 M Determine cause of water damaged ceiling tiles and replace tiles
397132 03/16/2017 436876 12 110 M Determine cause of water damaged ceiling tiles and replace tiles
397122 03/16/2017 436856 12 111 M Determine cause of water damaged ceiling tiles and replace tiles
397129 03/16/2017 436870 12 118A M Repair exhaust fan in bathroom
397056 03/16/2017 436717 12 206A M Grout or caulk bathroom wall tile at door frame
397121 03/16/2017 436854 12 207A M Replace missing 4 X 4 ceramic wall tile in bathroom
397057 03/16/2017 436719 12 209 M Replace missing ceiling tiles
397047 03/16/2017 436696 12 215 M Secure door handle to door
397135 03/16/2017 436882 12 290 M Repair electrical panel 12M2 to latch
397097 03/16/2017 436803 2 0000 M Provide chain and lock on gate of fencing around propane gas tank outside of 2-205
397098 03/16/2017 436805 2 0000 M Remove plants growing on beam outside of 2-208
397099 03/16/2017 436807 2 0000 M Provide grate on drain outside of rear door of Kitchen or fill with concrete
397106 03/16/2017 436821 2 203 M Provide protective cage around fire sprinkler head in walk-in cooler
397107 03/16/2017 436823 2 204 M Provide protective cage around fire sprinkler head in walk-in freezer
397115 03/16/2017 436840 2 207 M Replace damaged dryer vent line in Kitchen
397111 03/16/2017 436832 2 208 M Replace damaged light switch
397114 03/16/2017 436838 2 213 M Replace missing clean-out cover on wall
397096 03/16/2017 436799 2 220 M Determine cause of water damaged ceiling tiles and replace tiles at 2-226
397102 03/16/2017 436813 2 222 M Secure loose handicapped grabrail
397103 03/16/2017 436815 2 224 M Caulk and secure handicapped sink to wall
397104 03/16/2017 436817 3 305 M Replace fire sprinkler head with higher temperature rated head
397094 03/16/2017 436795 3 308 M Seal open joint on exterior wall outside of 3-308
397090 03/16/2017 436787 4 401 M Secure loose power pole at east side of Media Center
397093 03/16/2017 436793 4 410 M Provide cover on exposed electrical box on wall at entry
397091 03/16/2017 436789 4 416 M Replace missing light switch plate. Room numbered 4-415
397101 03/16/2017 436811 4 492A M Re-install belt guard on outside air intake motor
397088 03/16/2017 436783 5 0000 M Provide chain and lock on gate of fencing around electrical equipment outside of 5-501
397083 03/16/2017 436772 5 506 M Refinish bathroom walls to provide impervious finish
397069 03/16/2017 436743 6 0000 M Secure loose drinking fountain spout outside of 6-607
397084 03/16/2017 436774 6 602 M Repair exhaust fan in bathroom
397086 03/16/2017 436778 6 605 M Determine cause of water damaged ceiling tiles and replace tiles
397085 03/16/2017 436776 6 606 M Repair exhaust fan in bathroom
397066 03/16/2017 436737 6 617 M Provide cover on old clock box box
397068 03/16/2017 436741 6 618 M Seal opening in wall around toilet supply escutcheon
397065 03/16/2017 436735 7 701 M Eliminate cockroaches
397043 03/16/2017 436689 7 709 M Seal gap around toilet supply escutcheon
397064 03/16/2017 436733 7 711 M Anchor toilet to floor
397074 03/16/2017 436754 8 802 M Refinish bathroom wall to provide impervious finish
397072 03/16/2017 436749 9 908 M Repair exhaust fan in bathroom
397073 03/16/2017 436751 9 911 M Repair exhaust fan in bathroom
397071 03/16/2017 436747 9 911 M Refinish bathroom walls to provide impervious finish
397082 03/16/2017 436770 9 913 M Refinish bathroom walls to provide impervious finish
397087 03/16/2017 436781 9 914 M Install missing 3 quarter inch KO seal in side of electrical panel LD
397075 03/16/2017 436756 9 920 M Determine cause of water damaged ceiling tiles and replace tiles
397078 03/16/2017 436762 9 921 M Refinish bathroom walls to provide impervious finish
397076 03/16/2017 436758 9 922 M Determine cause of water damaged ceiling tiles and replace tiles
397026 03/16/2017 436652 00 0 O No access was available to 2-212-A, 4-411, 11-104, 12-112 and 12-113. Please provide access to these rooms during the report review meeting
397133 03/16/2017 436878 12 003C O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
397053 03/16/2017 436710 12 210A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
397070 03/16/2017 436745 10 001 MS Recharge fire extinguisher
397033 03/16/2017 436671 2 216 MS Provide current inspection tag for fire extinguisher
397112 03/16/2017 436834 2 226 MS Provide current inspection tag for fire extinguisher
397092 03/16/2017 436791 4 406 MS Provide current inspection tag for fire extinguisher
397041 03/16/2017 436687 4 421 MS Recharge fire extinguisher
397059 03/16/2017 436722 10 007 OS Remove storage from electrical room
397060 03/16/2017 436724 10 008 OS Remove storage from electrical room. Room is custodial closet
397124 03/16/2017 436860 12 190 OS Remove storage from electrical room
397100 03/16/2017 436809 4 492A OS Remove storage from mechanical room
381841 10/20/2016 403898 12 113 M Make necessary repairs to fire sprinkler system as indicated on inspection report (red tag dated 9-28-15)
397117 10/20/2016 436844 2 202 M Provide current inspection tag for Kitchen hood fire suppression system and make any necessary repairs if indicated on report. Dated 10-14-2015
271673 10/20/2016 164387 1 0000 N/A No violations observed
381865 02/02/2016 403952 00 0000 M Lock gate on fenced pump enclosure at east side of Building 12
357873 02/02/2016 351853 00 9599 M Turn barbs down on all fencing - cap installation is not complete
371593 02/02/2016 381618 00 9599 M Provide fill and sod edge of pre-K playground adjacent to drain to eliminate hazard - West side of Bldg. 10
381782 02/02/2016 403776 1 101 M Provide certification that fire alarm system has been tested and is fully operational and make any necessary repairs if indicated on report (date on last inspection report was 9-17-14)
381806 02/02/2016 403829 1 114 M Replace missing ceiling tiles
381809 02/02/2016 403836 11 103 M Adjust door on generator room to latch properly
381862 02/02/2016 403946 12 0000 M Secure loose guardrail on second floor walkway across from northwest stairway
381846 02/02/2016 403914 12 104 M Repair hole in wall adjacent to sink
381849 02/02/2016 403917 12 105 M Determine cause of water damaged ceiling tiles above sink and replace tiles
381852 02/02/2016 403926 12 108 M Determine cause of water damaged ceiling tiles and replace tiles
381851 02/02/2016 403922 12 109 M Determine cause of water damaged ceiling tiles and replace tiles
381863 02/02/2016 403948 12 201 M Determine cause of water damaged ceiling tiles in northwest corner of room and replace tiles
381864 02/02/2016 403950 12 202 M Determine cause of water damaged ceiling tiles at windows and replace tiles
381866 02/02/2016 403955 12 213 M Determine cause of water damaged ceiling tiles at windows and replace tiles
381835 02/02/2016 403883 2 201 M Repair southeast exit door of cafeteria to close properly (door drags on threshold)
381817 02/02/2016 403853 2 202 M Provide cleaning of kitchen hood (last cleaning was performed 6-12-14)
381830 02/02/2016 403872 2 207 M Replace dryer vent with new vent pipe (old vent pipe has holes and is kinked)
381838 02/02/2016 403896 3 303 M Determine cause of water damaged ceiling tiles and replace tiles
381867 02/02/2016 403957 4 427 M Provide cover on exposed electrical junction box on north wall
381876 02/02/2016 403975 6 615 M Provide cover on exposed electrical wiring in old clock enclosure on wall
381873 02/02/2016 403969 7 701 M Replace missing escutcheon on fire sprinkler head
381874 02/02/2016 403973 7 701 M Provide cover on exposed electrical wiring in old clock enclosure on wall
381870 02/02/2016 403963 8 801 M Determine cause of water damaged ceiling tiles above sink and replace tiles
381871 02/02/2016 403965 8 804 M Determine cause of water damaged ceiling tiles and replace tiles
381868 02/02/2016 403959 9 922 M Determine cause of water damaged ceiling tiles at door and replace tiles
381855 02/02/2016 403928 12 107 O Tape edges of rug to floor or remove rug (edges of rug are curled up, creating a tripping hazard)
381857 02/02/2016 403933 12 116 O Remove and prohibit combustible (residential) leather recliner chair
381813 02/02/2016 403846 2 220 O Prohibit plugging surge protector into surge protector
381872 02/02/2016 403967 8 907 O Remove and prohibit combustible (residential) upholstered white chair
381807 02/02/2016 403832 1 113 MS Replace missing fire extinguisher
381843 02/02/2016 403906 12 190 MS Recharge fire extinguisher in electric room
381823 02/02/2016 403858 2 202 MS Modify and re-adjust fire suppression nozzle covering two-burner stove in kitchen (stove has been relocated to accommodate more space for new steamer)
381837 02/02/2016 403894 2 216 MS Recharge fire extinguisher
381869 02/02/2016 403961 9 920 MS Recharge fire extinguisher
371592 02/02/2016 381614 2 201 CS Provide adequate egress to allow safe evacuation for west side of dining room - leads to enclosed fenced area
371610 10/14/2015 381655 12 113 M Provide current quarterly inspection tag for fire sprinkler system
371607 02/11/2015 381649 00 0000 M Remove all vegetation growing in chiller compound - south of Bldg. 12
371594 02/11/2015 381621 1 114 M Provide sign indicating room has been approved for charging 5 floor cleaning machines
371616 02/11/2015 381667 1 120 M Repair light in exit sign in corridor adjacent to custodial receiving
371608 02/11/2015 381651 12 112 M Replace missing ceiling tiles
371614 02/11/2015 381663 12 201 M Repair broken vinyl base along wall adjacent to corridor door
371613 02/11/2015 381661 12 215 M Repair damaged wall finish at corner adjacent to bathroom
371612 02/11/2015 381659 12 215B M Repair bathroom door hardware to work properly - lock sticks
371597 02/11/2015 381627 2 218 M Repair flickering light fixture
371598 02/11/2015 381629 2 219 M Secure loose cover for electrical outlet adjacent to microwave
371596 02/11/2015 381625 3 308 M Repair door to open and close properly - door rubs on frame
371605 02/11/2015 381643 5 506 M Provide sign indicating EMERGENCY EXIT above communicating door to 5-504
371603 02/11/2015 381639 6 601A M Secure loose edge of stainless steel mirror in bathroom
371604 02/11/2015 381641 6 604 M Secure loose metal cover to ceilings to prevent spread of fire or smoke - adjacent to 6-605
371601 02/11/2015 381635 6 612 M Adjust water flow for emergency eye wash
371617 02/11/2015 381669 12 104 O Eliminate (3) plug electrical outlet adaptor adjacent to teacher desk or replace with a surge protector
371618 02/11/2015 381671 12 105 O Remove and prohibit combustible residential Lazy Boy chair
371615 02/11/2015 381665 12 205 O Eliminate (3) plug electrical outlet adaptor used to power microwave or coffee maker
371611 02/11/2015 381657 12 211 O Eliminate orange (3) plug electrical outlet adaptor inside cabinet adjacent to teacher desk or replace with a surge protector
371606 02/11/2015 381647 12 292 O Remove and prohibit charging batteries for floor cleaning machines in mechanical room - The only approved location is custodial receiving 1-114
371599 02/11/2015 381631 9 918 O Remove paper covering electrical outlets under center of writing board
371609 02/11/2015 381653 12 113 MS Provide current inspection tag for fire extinguisher
371595 02/11/2015 381623 3 301 MS Remove dog leg hold open device from fire door
371602 02/11/2015 381637 4 420 MS Provide current inspection tag for fire extinguisher in closet or remove - room is inside 4-419
371600 02/11/2015 381633 11 192 OS Prohibit storage of gasoline and gas powered leaf blower - relocate to flammable storage room 11-104
321717 11/14/2014 272407 2 202 M Provide current inspection tag for kitchen steamer - steamer is out of service
343600 11/14/2014 320501 3 309 M Repair ventilation fan in girls bathroom
303462 11/14/2014 232492 00 0000 CS Provide suitable area for storage and recharging golf cart and floor cleaning machines
293354 11/14/2014 210729 2 201 CS Provide adequate egress to allow safe evacuation for west side of dining room - leads to enclosed fenced area
357867 02/12/2014 351841 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
357870 02/12/2014 351847 1 113 M Repair clogged floor drain
357868 02/12/2014 351843 1 114 M Determine cause of water damaged ceiling tiles and replace tiles
321747 02/12/2014 272470 12 0000 M Repair broken bottom rail at center guardrail at 2nd floor walkway - east end of Bldg. 12
357878 02/12/2014 351864 9 916A M Replace missing escutcheon on fire sprinkler head in bathroom
357869 02/12/2014 351845 1 110 O Prohibit plugging microwave and toaster oven into surge protector - plug each appliance directly into permanent electrical outlet
357871 02/12/2014 351849 12 106 O Prohibit plugging surge protector into surge protector at teacher desk - plug each surge protector directly into wall outlet
357879 02/12/2014 351866 10 009 MS Provide current inspection tag for fire extinguisher in kitchen between classrooms 10-005 and 10-011
357874 02/12/2014 351856 11 102 MS Provide current inspection tag for fire extinguisher
357872 02/12/2014 351851 12 211A OS Remove storage from bathroom vestibule
357875 02/12/2014 351858 2 226 OS Remove storage from mechanical room adjacent to music room
357877 02/12/2014 351862 6 604 OS Remove storage from electrical room adjacent to classroom 605
357876 02/12/2014 351860 8 801 OS Remove and prohibit use of toaster oven
343598 11/15/2013 320496 2 201 M Remove peeling paint from ceiling of cafeteria and repaint ceiling
335242 11/15/2013 302385 2 208 M Remove tree growing from wall above door of can wash room, 2-208
335244 11/15/2013 302389 2 208 M Repair holes in ceiling
343604 11/15/2013 320509 4 192A M Replace missing wrench from fire sprinkler spare heads box
203003 11/15/2013 76762 00 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for all rooms on campus (NA - on ADA report)
268197 11/15/2013 156567 2 222 C Provide solid, moisture resistant ceiling in group bathroom
268196 11/15/2013 156565 2 224 C Provide solid, moisture resistant ceiling in group bathroom
303454 11/15/2013 232476 7 706 C Provide automatic fire sprinkler coverage in custodial room
343603 11/15/2013 320507 4 192A MS Provide current annual and quarterly inspection tags for fire sprinkler system
343594 02/06/2013 320488 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
343596 02/06/2013 320492 1 114 M Determine cause of water damaged ceiling tiles and replace tiles
343595 02/06/2013 320490 1 115 M Provide cover for exposed electrical outlet at desk in office
343608 02/06/2013 320517 10 003 M Determine cause of water damaged ceiling tiles and replace tiles
343599 02/06/2013 320499 11 104 M Repair emergency lighting in generator room
343609 02/06/2013 320519 12 208 M Replace missing base along wall adjacent to north door
343611 02/06/2013 320523 12 213 M Repair non-working flourescent light fixture
343610 02/06/2013 320521 12 214 M Determine cause of water damaged ceiling tiles and replace tiles
343605 02/06/2013 320511 6 603 M Provide cover on exposed electrical junction box in ceiling
343607 02/06/2013 320515 9 912 M Determine cause of water damaged ceiling tiles and replace tiles
343606 02/06/2013 320513 9 920 M Determine cause of water damaged ceiling tiles and replace tiles
343601 02/06/2013 320503 4 403 O Prohibit plugging surge protector into surge protector in t.v. studio
190443 02/06/2013 15001 00 9599 C Turn barbs down on all fencing
343602 02/06/2013 320505 4 420 MS Provide current inspection tag for fire extinguisher
343597 02/06/2013 320494 1 114 OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
190471 11/12/2012 15014 2 215 M Provide dated flame resistance label on stage curtains
321714 11/12/2012 272401 2 215 C Provide records that stage rigging has been inspected and conforms to required safety standards
335247 04/11/2012 302394 00 0000 M Provide 3210 padlock for fenced area at building 11, lock on gate is not 3210
335294 04/11/2012 302496 10 003 M Adjust door closers (x2) to control speed of closing doors
335295 04/11/2012 302498 10 016 M Adjust door closer to control speed of closing door
335251 04/11/2012 302403 12 002 M Provide cover on exposed electrical junction box in ceiling adjacent to 12-115
335254 04/11/2012 302410 12 009B M Repair damaged ceiling finish
335252 04/11/2012 302406 12 102 M Replace missing ceiling tiles
335253 04/11/2012 302408 12 117A M Replace missing escutcheon on fire sprinkler head
335255 04/11/2012 302412 12 208 M Adjust door closer of door to 12-007 corridor to control speed of closing door
335256 04/11/2012 302415 12 292 M Pad and mark corners of ducts of SF 12-2 which are lower than 6 feet 8 inches
335237 04/11/2012 302374 2 201 M Repair damaged ceiling finish, paint is peeling
335240 04/11/2012 302380 2 203 M Repair door of walk-in refrigerator to close and latch properly
335243 04/11/2012 302387 2 208 M Repair door to close and latch properly
335238 04/11/2012 302376 2 212 M Adjust door closer on exterior door to control speed of closing door
335249 04/11/2012 302398 3 301 M Adjust door closer on east exterior door adjacent to 3-304 on to control speed of closing door
335276 04/11/2012 302460 4 425 M Repair door to close and latch properly
335277 04/11/2012 302462 4 425 M Provide cover on exposed electrical junction box at missing clock
335298 04/11/2012 302505 5 0000 M Provide certification that building 5 has emergency lighting
335272 04/11/2012 302450 5 506 M Adjust door closer to control speed of closing door
335273 04/11/2012 302453 5 508 M Anchor toilet to floor, bathroom located inside 5-509
335257 04/11/2012 302417 6 602 M Adjust door closer of bathroom door to control speed of closing door
335260 04/11/2012 302424 6 603 M Repair or replace damaged hot water heater
335261 04/11/2012 302426 6 606 M Adjust door closer for bathroom located inside 6-605 to control speed of closing door
335265 04/11/2012 302434 6 612 M Adjust door closer to control speed of closing door
335266 04/11/2012 302436 6 617 M Adjust door closer to control speed of closing door
335267 04/11/2012 302438 6 618 M Replace missing toilet seat for bathroom inside 6-617
335270 04/11/2012 302444 6 619 M Adjust door closer to control speed of closing door
335271 04/11/2012 302448 6 619 M Repair computer data box mounted on wall adjacent to microwave to close properly. Pad and mark corners of computer data box which are lower than 6 feet 8 inches
335282 04/11/2012 302472 7 707 M Adjust door closer to control speed of closing door
335281 04/11/2012 302470 8 801 M Repair door to close and latch properly
335291 04/11/2012 302490 9 910 M Adjust door closer to control speed of closing door
335292 04/11/2012 302492 9 911 M Replace missing escutcheon on fire sprinkler head
335290 04/11/2012 302488 9 912 M Provide cover on exposed electrical junction box at missing clock
335289 04/11/2012 302486 9 914 M Fill void in electrical panel HD1
335280 04/11/2012 302468 9 918 M Adjust door closer to control speed of closing door
335264 04/11/2012 302432 00 0000 O Clean moldly sidewalk adjacent to garden area and 6-610
335245 04/11/2012 302391 00 0000 O Remove debris pile from area adjacent to building 11
335239 04/11/2012 302378 2 202 O Prohibit plugging reach-in freezer into extension cord - plug directly into permanent electrical outlet
335248 04/11/2012 302396 2 220 O Prohibit plugging surge protector into surge protector at keyboards at back of risers
335274 04/11/2012 302455 5 508 O Prohibit flammable plastic purple tablecloth and green plastic grass decorations
335258 04/11/2012 302419 6 601 O Prohibit hanging papers on window blinds
335262 04/11/2012 302428 6 605 O Remove and prohibit hanging papers on window blinds
335268 04/11/2012 302440 6 617 O Prohibit hanging papers on window blinds
335269 04/11/2012 302442 6 619 O Prohibit hanging papers on window blinds
335283 04/11/2012 302474 8 812 O Prohibit plugging surge protector into orange extension cord
335285 04/11/2012 302478 9 916 O Prohibit plugging surge protector into surge protector at listening station
335286 04/11/2012 302480 9 916 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
335287 04/11/2012 302482 9 916 O Prohibit white 13A extension cords (x2) or replace with minimum 15A single outlet cords
335288 04/11/2012 302484 9 916 O Remove and prohibit umbrella and leaf decoration hanging from ceiling
335279 04/11/2012 302466 9 920 O Remove and prohibit hanging papers on window blinds
335278 04/11/2012 302464 9 922 O Prohibit brown multi outlet extension cord @ listening station or replace with minimum 15A single outlet cord
335259 04/11/2012 302421 6 603 F Replace missing heat detector
335284 04/11/2012 302476 12 113 MS Provide current inspection tag for fire extinguisher
335297 04/11/2012 302502 12 113 MS Provide current, complete inspection tag for fire sprinkler system, tag is missing information
335250 04/11/2012 302401 12 190 MS Replace missing fire extinguisher
335241 04/11/2012 302383 2 202 MS Provide current inspection tag for kitchen hood fire suppression system
335296 04/11/2012 302500 10 009 OS Prohibit running orange extension cord under door into 10-005
335263 04/11/2012 302430 6 607 OS Remove and prohibit use of toaster oven
335293 04/11/2012 302494 9 909 OS Prohibit storage of gas powered equipment
303468 02/08/2012 232505 12 0000 M Secure loose guardrails at 2nd floor walkway - west end of Bldg. 12 adjacent to stairs 12-004 (X2)
321718 04/01/2011 272409 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable (last report date: 10/17/09 in rm. 11-104)
321728 04/01/2011 272429 12 101 M Adjust water flow for drinking spout in classroom
303439 04/01/2011 232442 2 202 M Repair magnetic hold open device on fire doors between serving area and dining room to work properly
321716 04/01/2011 272405 2 204 M Repair warming element around freezer door to eliminate ice accumilation
321732 04/01/2011 272438 2 223 M Replace missing base tile adjacent to mop sink
321711 04/01/2011 272395 6 609 M Determine cause of water damaged ceiling tiles and replace tiles
321746 04/01/2011 272468 8 0000 M Replace missing escutcheon on fire sprinkler head at east end of covered walkway between Bldgs. 8 & 9
321720 04/01/2011 272413 12 007 O Remove and prohibit paper hanging from ceiling in corridor
321722 04/01/2011 272417 12 205 O Remove and prohibit paper hanging from ceiling in classroom
321730 04/01/2011 272433 3 307 O Remove glass mirror and broken mirror frame on door to 3-306 to eliminate hazardous condition
321712 04/01/2011 272397 4 403 O Prohibit plugging surge protector into extension cord - plug surge directly into wall outlet and eliminate use of extension cord
321710 04/01/2011 272393 6 605 O Remove and prohibit decorations hanging above exterior door
321709 04/01/2011 272391 6 615 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
321708 04/01/2011 272389 6 617 O Remove and prohibit combustible beanbag chair
321739 04/01/2011 272453 7 707 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
321740 04/01/2011 272456 7 707 O Remove and prohibit all flammable decorations hanging from ceiling
321745 04/01/2011 272466 7 707 O Prohibit plugging surge protector into extension cord at desk at SW corner of classroom and eliminate use of extension cord with multiple outlet end
321705 04/01/2011 272383 7 709 O Relocate storage to keep area within 18" of fire sprinkler head clear and unobstructed
321736 04/01/2011 272447 9 901 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
321738 04/01/2011 272450 9 906 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
321734 04/01/2011 272443 10 016 C Provide auto closer on door
321719 04/01/2011 272411 12 111 MS Provide current inspection tag for CO2 fire extinguisher
321729 04/01/2011 272431 12 113 MS Provide current inspection tag for fire extinguisher
321731 04/01/2011 272435 2 216 MS Provide current inspection tag for fire extinguisher
321713 04/01/2011 272399 2 226 MS Provide current inspection tag for fire extinguisher
321733 04/01/2011 272441 10 001 OS Relocate storage cart to provide clear access to fire alarm pull station
321727 04/01/2011 272427 12 001 OS Remove desk and chairs from corridor adjacent to 12-107
321726 04/01/2011 272425 12 115 OS Prohibit use of wedge to hold fire door in open position
321721 04/01/2011 272415 12 204A OS Remove all storage from bathroom vestibule
321723 04/01/2011 272419 12 207A OS Remove desks and stool from bathroom
321725 04/01/2011 272423 12 211 OS Prohibit use of wedge to hold fire door in open position
321724 04/01/2011 272421 12 215A OS Remove all storage from bathroom
321715 04/01/2011 272403 2 227 OS Prohibit charging batteries for floor cleaning machines in room
321707 04/01/2011 272387 7 703 OS Remove all storage from bathroom vestibule
321743 04/01/2011 272462 7 707 OS Relocate storage bag to provide clear access to fire alarm pull station adjacent to exterior door
321744 04/01/2011 272464 7 707 OS Rearrange furniture to maintain 3 ft clear aisle to exterior door
321706 04/01/2011 272385 7 708 OS Remove all storage from bathroom vestibule
321741 04/01/2011 272458 8 802 OS Remove all storage from bathroom
321742 04/01/2011 272460 8 803 OS Remove all storage from bathroom vestibule
321735 04/01/2011 272445 9 901 OS Remove and prohibit use of space heater
303463 01/31/2011 232494 00 9698 M Repair damaged concrete around sewer manhole and patch hole in north parking lot
303464 01/31/2011 232496 00 9698 M Make asphalt level with storm drain at north parking lot
293351 04/07/2010 210723 1 113A M Patch hole in ceiling around sprinkler head
303461 04/07/2010 232490 1 114 M Repair or replace damaged washing machine
303449 04/07/2010 232464 10 002 M Caulk gap around exhaust fan cover on ceiling
293347 04/07/2010 210715 11 102 M Provide cover on exposed electrical junction box on ceiling
303459 04/07/2010 232486 11 192 M Repair air handler to eliminate water leak
303436 04/07/2010 232435 12 117A M Repair water damaged ceiling
303467 04/07/2010 232503 3 0000 M Replace missing caulk at expansion joint on exterior wall at SE corner of Bldg. 3
303465 04/07/2010 232499 3 305 M Secure metal shelving to wall in kiln room (X2)
303466 04/07/2010 232501 3 305 M Provide cover for exposed electrical outlet adjacent to kiln
303457 04/07/2010 232481 4 424 M Patch hole around junction box adjacent to door
303456 04/07/2010 232479 5 0000 M Replace missing escutcheon on fire sprinkler head at west end of corridor between Bldgs. 5 & 6
293318 04/07/2010 210656 5 599 M Replace missing escutcheon on fire sprinkler head under covered walkway adjacent to 5-508
303438 04/07/2010 232439 6 606 M Replace missing escutcheon on fire sprinkler head in bathroom
271534 04/07/2010 164064 6 615 M Replace missing escutcheon on fire sprinkler head
303460 04/07/2010 232488 7 0000 M Make manhole cover level with sidewalk at south side of Bldg. adjacent to 7-706
303453 04/07/2010 232473 8 802 M Replace missing escutcheon on fire sprinkler head in bathroom
303451 04/07/2010 232469 9 912 M Determine cause of water damaged ceiling tiles and replace tiles
303443 04/07/2010 232446 10 001 O Prohibit plugging surge protector into surge protector behind "IBM Youth EXPLORER" computer station - plug each surge protector directly to wall outlet
303444 04/07/2010 232454 10 003 O Prohibit plugging surge protector into surge protector behind "IBM Youth EXPLORER" computer station - plug each surge protector directly to wall outlet
303447 04/07/2010 232458 10 005 O Prohibit plugging surge protector into surge protector behind "IBM Youth EXPLORER" computer station - plug each surge protector directly to wall outlet
303458 04/07/2010 232483 00 0000 C Provide exterior signage indicating property address
251599 04/07/2010 123531 2 223 C Provide auto closer on door
303450 04/07/2010 232467 10 009 MS Provide current inspection tag for fire extinguisher
303437 04/07/2010 232437 12 111 MS Adjust corridor door to latch properly
303452 04/07/2010 232471 9 906 OS Remove and prohibit use of toaster oven
271505 04/07/2010 164000 3 305 CS Provide fire extinguisher at kiln room door
271519 11/12/2009 164032 4 192A M Provide wrench for spare sprinkler heads box
271497 11/12/2009 163984 1 0000 MS Replace residential type knox box with commercial type knox box by office (current knox box not large enough to hold all keys)
293352 04/22/2009 210725 1 122 M Replace missing lens on light fixture
293288 04/22/2009 210594 10 005 M Adjust both exterior doors to latch properly
271502 04/22/2009 163994 11 103 M Repair auto closer on exterior door
284055 04/22/2009 190882 12 101 M Rotate evacuation sign - sign is installed upside down
284056 04/22/2009 190884 12 104 M Rotate evacuation sign - sign is installed upside down
284057 04/22/2009 190886 12 105 M Rotate evacuation sign - sign is installed upside down
284058 04/22/2009 190888 12 106 M Rotate evacuation sign - sign is installed upside down
284060 04/22/2009 190892 12 108 M Rotate evacuation sign - sign is installed upside down
284059 04/22/2009 190890 12 111 M Rotate evacuation sign - sign is installed upside down
293313 04/22/2009 210646 12 201 M Rotate evacuation sign - sign is installed upside down
293312 04/22/2009 210644 12 203 M Rotate evacuation sign - sign is installed upside down
284064 04/22/2009 190900 12 204 M Rotate evacuation sign - sign is installed upside down
284063 04/22/2009 190898 12 205 M Rotate evacuation sign - sign is installed upside down
284061 04/22/2009 190894 12 206 M Rotate evacuation sign - sign is installed upside down
293325 04/22/2009 210671 12 211 M Determine cause of water damaged ceiling tiles and replace tiles
293307 04/22/2009 210634 2 212 M Replace missing cover plate for electrical outlet under drinking fountain
293353 04/22/2009 210727 4 401 M Install maximum occupancy signage - sign indicating 85 occupants is with media specialist
293331 04/22/2009 210683 4 415 M Provide cover on exposed electrical junction box on ceiling
293342 04/22/2009 210705 4 418 M Replace missing lens on light fixture
293317 04/22/2009 210654 5 501 M Replace missing escutcheon on fire sprinkler head adjacent to bathroom
271539 04/22/2009 164074 6 603 M Patch hole in ceiling
293315 04/22/2009 210650 6 607 M Replace missing escutcheon on fire sprinkler head in bathroom
293334 04/22/2009 210689 6 615 M Adjust exterior door to latch properly
293316 04/22/2009 210652 6 619 M Replace missing escutcheon on fire sprinkler head
293293 04/22/2009 210603 7 704 M Mount fire extinguisher at maximum five feet above floor
293355 04/22/2009 210731 7 706 M Replace missing light fixture in custodial room
271527 04/22/2009 164050 9 909 M Patch hole in ceiling in janitors closet
293341 04/22/2009 210703 9 914 M Patch hole in ceiling
293339 04/22/2009 210699 9 918 M Mount fire extinguisher at maximum five feet above floor
293350 04/22/2009 210721 1 111 O Replace flickering light bulbs or have maintenance repair light fixture
293303 04/22/2009 210626 12 110 O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
293314 04/22/2009 210648 12 110 O Eliminate extension cord with multiple outlet end behind teacher's desk or replace with a surge protector
293301 04/22/2009 210623 12 116 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
293311 04/22/2009 210642 12 205 O Remove and prohibit combustible beanbag chair
293305 04/22/2009 210629 12 205 O Prohibit plugging microwave and refrigerator into extension cord with multiple outlet end - plug appliances directly into permanent electrical outlet and eliminate use of extension cord
293319 04/22/2009 210658 12 207 O Relocate storage to keep area within 18" of fire sprinkler head clear
293306 04/22/2009 210632 2 212 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
293309 04/22/2009 210638 2 220 O Prohibit plugging surge protector into surge protector adjacent to teacher's desk
293310 04/22/2009 210640 2 220 O Prohibit plugging surge protector into extension cord under projector screen
293299 04/22/2009 210619 6 619 O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
293297 04/22/2009 210615 7 701 O Remove mirror or provide mirror made of tempered glass, safety glass, or stainless steel
293298 04/22/2009 210617 7 701 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
293295 04/22/2009 210608 7 704 O Prohibit plugging surge protector into surge protector
293296 04/22/2009 210610 7 704 O Eliminate extension cord for desk lamp or replace with minimum 15A cord
293336 04/22/2009 210693 8 807 O Eliminate extension cord with multiple outlet end adjacent to teacher's desk or replace with a surge protector
293337 04/22/2009 210695 9 901 O Eliminate white extension cord or replace with minimum 15A cord
293308 04/22/2009 210636 2 220 F Remove dust cover on heat detector
293346 04/22/2009 210713 11 102 MS Provide current inspection tag for fire extinguisher
293345 04/22/2009 210711 11 103 MS Provide current inspection tag for fire extinguisher
293326 04/22/2009 210673 12 107 MS Adjust corridor door to latch properly
271510 04/22/2009 164011 2 208 MS Provide current inspection tag for fire extinguisher
293332 04/22/2009 210685 4 192A MS Provide current inspection tag for fire extinguisher
293333 04/22/2009 210687 6 615 MS Provide current inspection tag for fire extinguisher
293291 04/22/2009 210600 9 903 MS Provide current inspection tag for fire extinguisher
293344 04/22/2009 210709 1 104 OS Remove and prohibit use of space heater
293290 04/22/2009 210597 10 003 OS Relocate table to maintain 3 ft clear aisle to back exit door
293356 04/22/2009 210733 12 0000 OS Remove furniture from 2nd floor exterior walkway on east end of Bldg.
293320 04/22/2009 210660 12 008 OS Remove recycling bins from corridor adjacent to 12-207
294083 04/22/2009 212271 12 113 OS Relocate storage to provide clear access to fire extinguisher cabinet
293328 04/22/2009 210677 12 116 OS Remove and prohibit use of toaster oven
293327 04/22/2009 210675 12 190 OS Remove storage from electrical room
293324 04/22/2009 210669 12 213A OS Remove storage from bathroom vestibule
293322 04/22/2009 210664 12 214 OS Rearrange desks to maintain 3 ft clear aisle to corridor door
293323 04/22/2009 210666 12 215 OS Rearrange desks to maintain 3 ft clear aisle to corridor door
293321 04/22/2009 210662 12 215A OS Remove storage from bathroom
293330 04/22/2009 210681 4 415 OS Remove storage from electrical room
293343 04/22/2009 210707 4 421 OS Remove and prohibit use of space heater
293329 04/22/2009 210679 5 506 OS Remove and prohibit use of toaster oven
293335 04/22/2009 210691 6 610 OS Relocate desk to maintain 3ft clear aisle to exterior door
293340 04/22/2009 210701 9 916 OS Prohibit running electrical cord above ceiling tiles adjacent to bathroom door
293338 04/22/2009 210697 9 920 OS Rearrange desks to maintain 3 ft clear aisle to exit door
293348 04/22/2009 210717 11 102 FS Secure hanging heat detector
284062 12/18/2008 190896 12 208 M Rotate evacuation sign - sign is installed upside down
251604 12/18/2008 123542 2 202 M Provide current inspection tag for kitchen steamer - exp. 7/21/05
268194 12/18/2008 156561 2 208 M Replace missing escutcheon on fire sprinkler head
268187 12/18/2008 156547 2 227 M Replace missing escutcheon on fire sprinkler head and remove orange plastic guard from sprinkler head
271542 12/18/2008 164080 6 607 M Replace missing escutcheon on fire sprinkler heads above sink (X2)
271543 12/18/2008 164082 6 611 M Determine cause of water damaged ceiling tiles and replace tiles
271536 12/18/2008 164068 6 618 M Replace missing escutcheon on fire sprinkler head
271531 12/18/2008 164058 8 801 M Determine cause of water damaged ceiling tiles and replace tiles
190494 12/18/2008 15038 9 918 M Repair bubbled vinyl flooring
271514 12/18/2008 164020 12 117 O Remove and prohibit combustible beanbag chairs (X2)
271528 12/18/2008 164052 9 907 O Provide cover on extension cord on floor to prevent trip hazard or eliminate cord
268200 12/18/2008 156576 00 0000 C Complete Test and Balance of A/C system. Some rooms too hot and others too cold
268108 12/18/2008 156374 1 0000 C Replace missing sidewalk at handicappped ramp West of Bldg. 1. Repair or replace damaged conduit where sidewalk was removed
271520 12/18/2008 164034 4 401 C Provide sign indicating maximum occupancy adjacent to main entrance
271529 12/18/2008 164054 10 009 MS Provide current inspection tag for type-K fire extinguisher
271501 12/18/2008 163992 11 104 MS Provide current inspection tag for fire extinguisher
271518 12/18/2008 164028 4 415 MS Provide current inspection tag for fire extinguisher
268203 12/18/2008 156582 11 192 CS Provide fire extinguisher in Mechanical Room
268201 12/18/2008 156578 4 415 CS Remove construction storage from electrical room
271532 02/01/2008 164060 00 0000 M Secure lighted exit sign to ceiling in corridor between building 6 and 7
251580 02/01/2008 123493 00 9599 M Label fire department connections at bus loop to signify which buildings they supply
271499 02/01/2008 163988 1 107 M Provide cover on exposed electrical junction box
271500 02/01/2008 163990 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
271530 02/01/2008 164056 10 008 M Patch hole in ceiling
271512 02/01/2008 164015 12 104 M Determine cause of water damaged ceiling tiles and replace tiles
271513 02/01/2008 164017 12 108 M Determine cause of water damaged ceiling tiles and replace tiles
271516 02/01/2008 164024 12 201 M Determine cause of water damaged ceiling tiles and replace tiles
271508 02/01/2008 164006 2 201 M Repair inoperable drinking fountain @ N.W. corner of cafeteria
271511 02/01/2008 164013 2 202 M Repair exterior exit door to close properly
271509 02/01/2008 164009 2 205 M Replace missing escutcheons (X2) on fire sprinkler heads in food storage room
271504 02/01/2008 163998 2 222 M Provide cover on exposed electrical junction box on ceiling
268179 02/01/2008 156530 3 301 M Remove flaking paint and rust on ceiling and bar joists, prime and repaint
271506 02/01/2008 164002 3 306 M Determine cause of water damaged ceiling tiles and replace tiles
271521 02/01/2008 164036 4 405 M Replace missing ceiling tiles
271522 02/01/2008 164038 4 425 M Replace missing clock or provide cover on exposed electrical junction box
271537 02/01/2008 164070 5 506 M Determine cause of water damaged ceiling tiles and replace tiles
271538 02/01/2008 164072 5 599 M Provide cover on exposed electrical junction box in ceiling
268224 02/01/2008 156629 6 604 M Cover opening in ceiling where light fixture was removed
271541 02/01/2008 164078 6 605 M Replace missing clock or provide cover on exposed electrical junction box
271544 02/01/2008 164084 6 610 M Replace broken faucet on sink
271535 02/01/2008 164066 6 615 M Determine cause of water damaged ceiling tiles and replace tiles
271526 02/01/2008 164048 9 918 M Replace missing clock or provide cover on exposed electrical junction box
271525 02/01/2008 164046 9 920 M Secure faucet to sink
271523 02/01/2008 164040 9 922 M Secure faucet to sink
271524 02/01/2008 164042 9 922 M Determine cause of water damaged ceiling tiles and replace tiles
271503 02/01/2008 163996 1 118 O Eliminate 13 amp extension cord powering fan
271517 02/01/2008 164026 12 211 O Prohibit plugging microwave oven into extension cord - plug directly into permanent electrical outlet
271507 02/01/2008 164004 2 220 O Eliminate 13 amp extension cord powering electronic keyboard
271540 02/01/2008 164076 6 605 O Eliminate multiple outlet electrical adaptor
268205 02/01/2008 156586 00 0000 C Secure hanging soffit and fascia metal and complete installation of soffit and fascia metal through out campus
268158 02/01/2008 156482 12 114 C Provide illuminated exit signs at both exits or change maximum occupancy sign to read 49 max.
268249 02/01/2008 156686 12 210 C Provide illuminated exit signs at both exits or change occupancy sign to read 49 max
271739 02/01/2008 164536 12 113 MS Provide current inspection tag for fire sprinkler system
268153 02/01/2008 156472 4 192A MS Provide current inspection tag for fire sprinkler system
251577 02/01/2008 123487 6 603 MS Close ceiling hatch
271533 02/01/2008 164062 6 615 OS Remove and prohibit use of toaster oven
271498 02/01/2008 163986 1 101 FS Make repairs to fire alarm system, fire alarm panel indicated trouble during inspection
251616 09/12/2007 123567 11 102 M Repair door to close properly
268190 09/12/2007 156553 2 212A M Replace missing escutcheon on fire sprinkler head
268193 09/12/2007 156559 2 224 M Replace missing and broken ceramic wall tile
268182 09/12/2007 156537 3 306 M Relocate sprinkler heads or shelves to provide adequate fire sprinkler coverage for room
268183 09/12/2007 156539 3 306 M Replace missing escutcheon on fire sprinkler head
268141 09/12/2007 156447 4 406 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
268140 09/12/2007 156444 4 415 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
268202 09/12/2007 156580 4 427 M Provide covers on exposed electrical junction box and 2 gutters and provide missing light switch plate
268209 09/12/2007 156594 5 503 M Replace missing escutcheon on fire sprinkler head
268242 09/12/2007 156670 6 606 M Repair leak coming through wall adjacent to toilet
268225 09/12/2007 156631 7 701 M Replace missing escutcheon on fire sprinkler head
268222 09/12/2007 156625 8 0000 M Remove orange plastic guard on fire sprinkler head in corridor between Bldgs. 7 & 8
268162 09/12/2007 156492 1 113A C Provide automatic fire sprinkler coverage for room
268169 09/12/2007 156508 10 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for unnumbered room adjacent to 10-010
268170 09/12/2007 156510 10 0000 C Complete construction of room 10-010 and unnumbered room adjacent ot 10-010
268206 09/12/2007 156588 4 192A C Provide signage indicating correct FISH room number and name at appropriate height with raised and Braille characters
190448 09/12/2007 14851 1 0000 CS Modify gate outside 1-114 (between Bldgs. 2 & 11) to allow egress at all times and remove chains and padlock
268156 09/12/2007 156478 1 105 CS Provide automatic fire sprinkler coverage for closet
268210 09/12/2007 156597 4 406 CS Provide automatic fire sprinkler coverage for room
268144 04/27/2007 156453 00 0000 M Fill hole in ground where old portable lift station was removed (East of Bldg. 2)
268155 04/27/2007 156476 00 0000 M Regrade dirt that prevents gate from closing and provide padlock for irrigation pump enclosure East of Bldg. 12
268160 04/27/2007 156488 00 0000 M Provide handle for Post Indicator Valve at Bus Loop and lock handle in place
268113 04/27/2007 156386 00 0000 M Provide chain and padlock to lock valve handles open on fire main at bus loop. No tamper switches installed
251039 04/27/2007 122131 00 0000 M Repair damaged bench seat at parent dropoff
190444 04/27/2007 15000 00 9599 M Clean debris from storm drains throughout site
268159 04/27/2007 156486 1 102 M Provide cover for exposed electrical floor outlet
268177 04/27/2007 156526 1 102 M Provide electricity to power pole
268171 04/27/2007 156512 1 112 M Pad and mark hanging 1" copper pipe that is lower than 6'8"
268174 04/27/2007 156518 1 120 M Adjust door to exterior corridor to latch properly
268167 04/27/2007 156503 10 001 M Adjust both doors to latch properly
268168 04/27/2007 156506 10 003 M Remove unneeded CO2 fire extinguisher from room
268164 04/27/2007 156496 10 005 M Install fire extinguisher sitting on floor at maximum five feet above floor adjacent ot exit
268232 04/27/2007 156645 10 005 M Adjust door to latch properly
268161 04/27/2007 156490 10 009 M Install fire extinguisher sitting on counter at maximum five feet above floor adjacent to door
268165 04/27/2007 156498 10 011 M Install fire extinguisher sitting on floor at maximum five feet above floor adjacent to exit
268163 04/27/2007 156494 10 013 M Install fire extinguisher sitting on floor at maximum five feet above floor adjacent to exit
268176 04/27/2007 156523 11 103 M Install fire extinguisher sitting on floor at maximum five feet above floor adjacent ot door
268114 04/27/2007 156391 12 0000 M Secure loose escutcheon on toilet supply lines for all toilets in Building
268138 04/27/2007 156442 12 108 M Adjust South door to latch properly
268157 04/27/2007 156480 12 111 M Adjust door to latch properly
268137 04/27/2007 156438 12 114 M Replace missing escutcheon on fire sprinkler head and remove orange plastic guard on head
268123 04/27/2007 156411 12 170 M Provide certification that elevator has current inspection tag
268151 04/27/2007 156468 12 191 M Replace missing ceiling tiles
268247 04/27/2007 156680 12 206A M Replace missing ceramic tile on wall
268246 04/27/2007 156678 12 206B M Replace broken toilet seat
268248 04/27/2007 156684 12 210A M Repair damaged ceiling at light fixture
268251 04/27/2007 156690 12 215A M Cover opening in ceiling
268184 04/27/2007 156541 2 212 M Replace missing ceiling tiles
251596 04/27/2007 123525 2 212 M Provide cover on exposed electrical junction box at old clock
268189 04/27/2007 156551 2 212A M Determine cause of water damaged ceiling tiles and replace tiles adjacent to fire sprinkler head
251593 04/27/2007 123519 2 220 M Replace damaged electrical cord for electric piano
268186 04/27/2007 156545 2 221 M Anchor shelving to wall
268185 04/27/2007 156543 2 223 M Cover exposed wires and close open cover on water heater
268188 04/27/2007 156549 2 227 M Replace missing ceiling tiles
268180 04/27/2007 156532 3 305 M Provide controls on exhaust fan at kiln so that fan can be run as needed
268178 04/27/2007 156528 4 0000 M Provide electricity to power poles through out Media Center
268207 04/27/2007 156590 4 192A M Install fire extinguisher at maximum five feet above floor adjacent to exit
251591 04/27/2007 123515 4 402 M Replace missing cover plate on floor outlet
268214 04/27/2007 156606 4 409A M Secure loose door hinge
268181 04/27/2007 156534 4 411 M Determine cause of water damaged ceiling tiles and replace tiles in Dark Room vestibule
268145 04/27/2007 156455 5 0000 M Repair exhaust fans in all bathrooms in Building
269055 04/27/2007 158437 5 506 M Remove sign indicating "Emergency Exit" from door leading into 5-504
268213 04/27/2007 156603 5 508 M Replace safety pin on fire extinguisher
268199 04/27/2007 156574 6 601 M Repair communicating door to 6-619 to open and close properly
268147 04/27/2007 156459 6 602 M Repair exhaust fan in bathroom
251578 04/27/2007 123489 6 605 M Adjust clock to properly cover junction box
268148 04/27/2007 156461 6 606 M Repair exhaust fan in bathroom
268149 04/27/2007 156463 6 618 M Repair exhaust fan in bathroom
268146 04/27/2007 156457 6 620 M Repair exhaust fan in bathroom
268236 04/27/2007 156654 7 702 M Anchor toilet to floor
268221 04/27/2007 156622 7 708 M Replace missing ceiling tiles
268240 04/27/2007 156666 8 804 M Determine cause of water damaged ceiling tiles and replace tiles
268150 04/27/2007 156465 8 806 M Repair exhaust fan in bathroom
268223 04/27/2007 156627 8 807 M Adjust door to latch properly
268237 04/27/2007 156656 8 812 M Replace missing auto closer on door
268233 04/27/2007 156647 9 901 M Adjust door to latch properly
268218 04/27/2007 156616 9 904 M Anchor shelving to wall
268219 04/27/2007 156618 9 912 M Install fire extinguisher at maximum five feet above floor adjacent to door
268220 04/27/2007 156620 9 912 M Replace missing ceiling tiles
268227 04/27/2007 156635 9 914 M Close ceiling hatch
268228 04/27/2007 156637 9 914 M Adjust door to latch properly
268229 04/27/2007 156639 9 915 M Adjust door to latch properly
268230 04/27/2007 156641 9 916 M Adjust door to latch properly
268235 04/27/2007 156651 9 916 M Provide correct bracket for fire extinguisher
268234 04/27/2007 156649 9 918 M Adjust door to latch properly
268231 04/27/2007 156643 9 919 M Anchor toilet to floor
251561 04/27/2007 123455 9 920 M Adjust door to latch properly
268154 04/27/2007 156474 12 102 O Keep area within 18" of automatic fire sprinkler heads clear and unobstructed
268198 04/27/2007 156571 3 307 O Plug refrigerator directly into wall outlet not surge strip
251592 04/27/2007 123517 4 403 O Prohibit plugging surge protector to surge protector
268215 04/27/2007 156609 4 409A O Prohibit blocking door open by placing stick in hinge side of door. This has caused hinge to pull out of door
251575 04/27/2007 123483 5 501 O Eliminate orange extension cord or replace with minimum 15A cord
269057 04/27/2007 158443 6 619 O Remove and prohibit tent or provide evidence of flame proofing
268204 04/27/2007 156584 11 192 C Provide signage indicating correct FISH room number and name at appropriate height with raised and Braille characters
268172 04/27/2007 156514 1 111 MS Provide current inspection tag for fire extinguisher
268173 04/27/2007 156516 1 111 MS Remove storage from electrical room
268166 04/27/2007 156500 10 001 MS Provide current inspection tag for fire extinguisher and hang extinguisher at maximum five feet above floor adjacent to exit
268152 04/27/2007 156470 12 180 MS Close and seal large opening in ceiling
268125 04/27/2007 156414 12 190 MS Remove storage from electrical room
268250 04/27/2007 156688 12 209 MS Provide current inspection tag for fire extinguisher
268243 04/27/2007 156672 12 290 MS Remove storage from electrical room
269056 04/27/2007 158440 2 202 MS Provide current inspection for Kitchen Hood fire suppression system
251601 04/27/2007 123535 2 205 MS Replace missing fire extinguisher
268192 04/27/2007 156557 2 216 MS Provide current inspection tag for fire extinguisher
268191 04/27/2007 156555 2 226 MS Provide current inspection tag for fire extinguisher
251588 04/27/2007 123509 5 503 MS Close ceiling hatch
268212 04/27/2007 156601 6 604 MS Remove storage from electrical room
268226 04/27/2007 156633 7 701 MS Provide current inspection tag for fire extinguisher
268175 04/27/2007 156520 1 114 OS Prohibit storage of gasoline
268208 04/27/2007 156592 4 419 OS Keep door unlocked when facility is occupied to access fire extinguisher
268211 04/27/2007 156599 6 604 OS Remove storage from electrical room
268238 04/27/2007 156661 6 605 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station
268239 04/27/2007 156664 8 801 OS Provide clear access to fire alarm pull station
268217 04/27/2007 156614 8 801 OS Keep door unlocked when facility is occupied to access fire extinguisher
268216 04/27/2007 156612 8 804 OS Keep door unlocked when facility is occupied to access fire extinguisher
268244 04/27/2007 156674 12 290 CS Provide fire extinguisher in Electric Room
268245 04/27/2007 156676 12 292 CS Provide fire extinguisher in Electric Room
251038 01/19/2007 122129 00 0000 M Repair hurricane damage throughout campus
251541 01/19/2007 123413 00 0000 M Replace missing escutcheons on fire sprinkler heads in all newly sprinklered buildings
190438 01/19/2007 14889 00 0000 M Provide verification that all student occupied spaces have emergency lights and all are operable
251560 01/19/2007 123453 00 9599 M Secure plastic covering soffit of covered walkway outside 9-922
251547 01/19/2007 123425 00 9599 M Connect bottom of chain link fencing outside 9-907 to bottom support wire
251572 01/19/2007 123477 00 9599 M Relocate fencing between 9-907 & Bldg. 10 to follow sidewalk along parent loop to allow adequate egress from Bldg. 9
251540 01/19/2007 123411 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
251605 01/19/2007 123544 2 202 M Secure loose escutcheon on fire sprinkler head
251600 01/19/2007 123533 2 205A M Remove top shelf which is too close to fire sprinkler head
268195 01/19/2007 156563 2 208 M Remove inaccessible and unneeded fire extinguisher in room
251595 01/19/2007 123523 2 215 M Repair light in exit sign
251594 01/19/2007 123521 2 223 M Replace missing ceiling tiles
251612 01/19/2007 123558 3 308 M Replace missing cover on handicapped assistance call box
251614 01/19/2007 123562 3 308 M Replace missing cover plates on electrical outlet and light switch
251608 01/19/2007 123550 4 401 M Repair light in exit sign
251602 01/19/2007 123537 4 415 M Mount fire extinguisher bracket
251587 01/19/2007 123507 5 0000 M Repair inoperable drinking fountain outside 5-506
251586 01/19/2007 123505 5 506 M Repair door to close properly - sticks on sidewalk
251590 01/19/2007 123513 6 609 M Reverse door lock on door into 6-607 or replace with non-lockable door hardware
268241 01/19/2007 156668 6 609 M Determine cause of water damaged ceiling tiles and replace tiles
251509 01/19/2007 123348 P 3636 M Secure loose board at top of stair
251502 01/19/2007 123334 P 3772 M Replace weathered stair boards
251504 01/19/2007 123338 P 3772 M Repair emergency lighting or remove inoperable emergency light
251511 01/19/2007 123352 P 3772 M Repair or replace broken handrail along ramp
190543 01/19/2007 15059 P 387 M Adjust steps to make risers equal
190506 01/19/2007 14938 P 4258 M Provide certification of flame spread rating of wall paneling or remove paneling
190532 01/19/2007 15051 P 456 M Adjust steps to make risers equal
190534 01/19/2007 15052 P 456 M Adjust stair landing to be level with interior floor
251555 01/19/2007 123443 P 456 M Replace extremely deteriorated stair
251551 01/19/2007 123434 P 457 M Replace missing ceiling tiles
251552 01/19/2007 123436 P 457 M Determine cause of water damaged ceiling tiles and replace tiles
251553 01/19/2007 123438 P 457 M Replace missing handicapped hardware on outside face of stair door
190539 01/19/2007 57408 P 457 M Repair damaged boards on stair landing
190540 01/19/2007 15056 P 457 M Adjust stair landing to be level with interior floor
190537 01/19/2007 15055 P 457 M Adjust steps to make risers equal
251521 01/19/2007 123372 P 4781 M Anchor bottom of ramp to sidewalk to eliminate tripping hazard
251525 01/19/2007 123380 P 4781 M Repair short in light switch in bathroom
203172 01/19/2007 77078 P 510 M Adjust steps to make risers equal
251520 01/19/2007 123370 P 738 M Repair exhaust fan in bathroom
251530 01/19/2007 123390 P 744 M Repair exhaust fan in bathroom
190519 01/19/2007 15047 P 744 M Adjust steps to make risers equal
190526 01/19/2007 15050 P 745 M Adjust steps to make risers equal
251526 01/19/2007 123382 P 745 M Repair exhaust fan in bathroom
251527 01/19/2007 123384 P 745 M Replace worn stair
251609 01/19/2007 123552 4 401 O Prohibit plugging surge protector into extension cord
251603 01/19/2007 123539 4 414 O Remove and prohibit air freshener
251607 01/19/2007 123548 4 419 O Remove and prohibit bamboo curtains on windows
251583 01/19/2007 123499 5 506 O Eliminate extension cord or replace with minimum 15A cord
251585 01/19/2007 123503 6 601 O Prohibit plugging surge protector into extension cord
251581 01/19/2007 123495 6 612 O Prohibit powering refrigerator and microwave oven with surge protector
203147 01/19/2007 77030 6 612 O Prohibit use of surge protector to power refrigerator and microwave, plug appliances directly into wall outlet
190439 01/19/2007 14940 00 0000 C Modify all emergency lighting so that no room may be left in darkness if single bulb fails
203367 01/19/2007 77496 00 9500 C Provide covered walkway to portables
203144 01/19/2007 77025 4 421 C Provide electrical power pole in computer room to eliminate use of excessive extension cords
251579 01/19/2007 123491 7 701 C Provide sign indicating emergency exit ino 7-710
251576 01/19/2007 123485 7 707 C Provide sign indicating emergency exit at door into 7-704
251573 01/19/2007 123479 7 710 C Provide sign at opening into 7-701 to indicate emergency exit
251503 01/19/2007 123336 P 3772 C Provide bottom rail on stair landing guardrail at two inches above floor
190542 01/19/2007 14989 P 387 C Provide guardrails at stair landing at a minimum 42 inches high
190544 01/19/2007 14990 P 387 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
190507 01/19/2007 14996 P 4258 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190531 01/19/2007 14978 P 456 C Provide guardrails at stair landing at a minimum 42 inches high
190533 01/19/2007 14979 P 456 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
190536 01/19/2007 14984 P 457 C Provide guardrails at stair landing at a minimum 42 inches high
190538 01/19/2007 14985 P 457 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
251554 01/19/2007 123441 P 47 C Portable is currently used for storage and construction office - provide inspection by Bldg. Dept. prior to occupancy
190509 01/19/2007 14950 P 4781 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190508 01/19/2007 57357 P 510 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
251550 01/19/2007 123432 P 731 C Portable is currently used for storage only - provide inspection by Bldg. Dept. prior to occupancy
190520 01/19/2007 14968 P 744 C Provide graspable handrails on each side of ramp at between 34-38 inches high
190521 01/19/2007 14964 P 744 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
190522 01/19/2007 14965 P 744 C Provide handrails on each side of stair
190527 01/19/2007 14974 P 745 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
190528 01/19/2007 14970 P 745 C Provide handrails on each side of stair
251539 01/19/2007 123409 1 106 F Replace missing cover on heat detector
251597 01/19/2007 123527 2 202 F Repair magnetic hold open device on door at serving line
251538 01/19/2007 123407 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus (dated 5/04)
251618 01/19/2007 123572 10 009 MS Replace missing fire extinguisher
251617 01/19/2007 123570 10 010 MS Provide current inspection tag for fire extinguisher (3/00)
251574 01/19/2007 123481 5 501 OS Immediately discontinue use of frayed extension cord and prohibit use of extension cord to power a/c unit
251584 01/19/2007 123501 5 506 OS Provide minimum 3' clearance in front of emergency exit door or remove exit sign from door. Emergency exit no longer required as Building is sprinklered
251589 01/19/2007 123511 6 610 OS Relocate table blocking clear path to exterior door
251582 01/19/2007 123497 6 615 OS Prohibit wedging open exterior door
203149 01/19/2007 77034 7 704 CS Provide secondary egress
251615 01/19/2007 123565 00 0000 FS Repair all damage to fire alarm system, including hanging heat detectors, broken pull stations, etc. throughout campus (may be result of ongoing construction)
251535 01/19/2007 123400 1 102 FS Verify that fire alarm system provides adequate coverage for campus - panel indicates troubles, most of which are because of construction on campus - verify fire watch is not required
251606 01/19/2007 123546 4 422 FS Provide heat detector in storage room
261914 01/19/2007 144192 P 456 N/A No violations observed
261917 01/19/2007 144195 P 457 N/A No violations observed
261927 01/19/2007 144205 P 47 N/A No violations observed
261919 01/19/2007 144197 P 4781 N/A No violations observed
261924 01/19/2007 144202 P 510 N/A No violations observed
261916 01/19/2007 144194 P 731 N/A No violations observed
261923 01/19/2007 144201 P 738 N/A No violations observed
261925 01/19/2007 144203 P 744 N/A No violations observed
261921 01/19/2007 144199 P 745 N/A No violations observed
251542 04/24/2006 123415 1 120 M Remove lock from exit door into 1-114
251619 04/24/2006 123574 10 013 M Adjust rear door to latch properly
251610 04/24/2006 123554 2 216 M Cover hole in wall at stage
251611 04/24/2006 123556 2 216 M Repair door to close properly
251563 04/24/2006 123459 8 0000 M Repair light in exit sign between Bldgs. 8 & 9
251567 04/24/2006 123467 8 811 M Replace missing ceiling tiles
251506 04/24/2006 123342 P 3636 M Replace worn non-slip surface for ramp and stair
251565 04/24/2006 123463 P 3637 M Replace worn non-slip surface for ramp and stair
251505 04/24/2006 123340 P 3772 M Replace worn non-slip surface for ramp
251513 04/24/2006 123356 P 3773 M Replace weathered stair boards
251516 04/24/2006 123362 P 3773 M Replace worn non-slip surface for ramp
251510 04/24/2006 123350 P 4258 M Provide bracket for fire extinguisher and put extinguisher on bracket
251557 04/24/2006 123447 P 456 M Replace missing ceiling tiles
251558 04/24/2006 123449 P 456 M Replace worn sign indicating "Fire Alarm Pull Station Inside"
251522 04/24/2006 123374 P 4781 M Repair emergency lighting
251523 04/24/2006 123376 P 4781 M Replace missing handicapped hardware on outside face of ramp door
251529 04/24/2006 123388 P 744 M Repair stair door to close properly
251532 04/24/2006 123394 P 744 M Repair emergency lighting
251533 04/24/2006 123396 P 744 M Replace worn non-slip surface for ramp
251534 04/24/2006 123398 P 744 M Replace worn stair
190523 04/24/2006 15048 P 744 M Adjust steps to make treads level
251536 04/24/2006 123402 1 105 O Remove and prohibit air freshener
251544 04/24/2006 123419 1 114 O Clean lint from dryer vent - lint is stuck on outside vent cover
251537 04/24/2006 123404 1 122 O Remove and prohibit air freshener
251598 04/24/2006 123529 2 202 O Remove table from in front of electrical panels
251568 04/24/2006 123469 8 812 O Remove and prohibit air freshener
251569 04/24/2006 123471 8 813 O Remove and prohibit air freshener
251546 04/24/2006 123423 9 901 O Eliminate extension cord or replace with minimum 15A cord
251545 04/24/2006 123421 9 904 O Prohibit powering copy machine and microwave oven with surge protector
251571 04/24/2006 123475 9 909 O No access was available to this room. Please be prepared to access this room during the report review meeting.
251562 04/24/2006 123457 9 918 O Eliminate several extension cords or replace with minimum 15A cords
251507 04/24/2006 123344 P 3636 O Remove storage in front of electrical panel
251517 04/24/2006 123364 P 3773 O Remove excessive storage
251514 04/24/2006 123358 P 3773 O Relocate display board blocking clear access to electrical panel
251556 04/24/2006 123445 P 456 O Remove and prohibit air freshener in bathroom
251518 04/24/2006 123366 P 738 O Eliminate extension cord or replace with minimum 15A cord
251519 04/24/2006 123368 P 738 O Prohibit plugging extension cord into surge protector and surge protector to surge protector
251528 04/24/2006 123386 P 744 O Remove poster covering electrical panel
251531 04/24/2006 123392 P 744 O Remove and prohibit bamboo curtains covering windows and walls
190476 04/24/2006 57412 3 301 C Label the emergency exhaust fan switch and provide direction for operation
190502 04/24/2006 14993 P 3637 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190467 04/24/2006 15008 2 202 MS Verify activation of hood fire suppression system will initiate school fire alarm
190468 04/24/2006 15007 2 202 MS Verify that electricity and gas to appliances shuts off upon activation of hood suppression system
251543 04/24/2006 123417 1 114 OS Prohibit charging batteries in room
251564 04/24/2006 123461 8 801 OS Remove storage at fire extinguisher bracket and keep extinguisher on bracket
251570 04/24/2006 123473 8 812 OS Relocate table blocking clear path to emergency exit door into 8-801
251508 04/24/2006 123346 P 3636 OS Relocate desk blocking clear path to stair door
251515 04/24/2006 123360 P 3773 OS Relocate display board blocking clear view and access to fire extinguisher
251512 04/24/2006 123354 P 3773 OS Remove table at bottom of stairs
251559 04/24/2006 123451 P 387 OS Relocate desk blocking clear path to ramp door
251524 04/24/2006 123378 P 4781 OS Relocate table blocking clear path to stair door
190501 04/17/2006 14991 P 3636 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190504 04/17/2006 14994 P 3772 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190505 04/17/2006 14995 P 3773 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190541 04/17/2006 14986 P 387 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190530 04/17/2006 14975 P 456 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190535 04/17/2006 14981 P 457 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190516 04/17/2006 14960 P 738 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190518 04/17/2006 14962 P 744 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190524 04/17/2006 14969 P 745 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
251566 02/22/2006 123465 00 0000 M Repair exhaust fans in all bathrooms
190442 02/22/2006 57405 00 8087 M Repair or replace bent steel column at parent drop off west of Building 9
203008 02/22/2006 76771 1 113 M Repair air handler to eliminate water leak
190452 02/22/2006 57375 1 114 M Replace plastic dryer vent with a metal vent
203023 02/22/2006 76796 2 202 M Secure loose magnetic hold open hardware on west fire door between serving area and dining room
203139 02/22/2006 77015 2 207 M Replace plastic dryer vent with a metal vent
190477 02/22/2006 57338 3 301 M Remove peeling paint on the underside of metal roof deck and repaint
251613 02/22/2006 123560 3 309 M Replace missing cover on handicapped assistance call box
203171 02/22/2006 77074 P 3772 M Remove wood pallets on east side of portable unit
203153 02/22/2006 77040 7 710 O Prohibit use of extension cord to power refrigerator and microwave, plug appliances directly into wall outlet
203180 02/22/2006 77092 P 457 O Eliminate extension cord or replace with minimum 15A cord
190445 02/22/2006 57400 00 9599 C Modify drainage east of 6-610 to prevent standing water at sidewalk
190447 02/22/2006 57402 00 9699 C Modify site drainage to eliminate standing water on the play court, at the sidewalk, east of 3-301
203019 02/22/2006 76783 2 202 MS Adjust sweep on east fire door between serving area and dining room which prevents door from latching
203140 02/22/2006 77016 2 212 MS Replace frayed electrical cord for microwave
190440 02/22/2006 57345 00 0000 OS Keep doors unlocked when facility is occupied to allow access to fire alarm pull stations and fire extinguishers for rooms that are signed fire alarm or fire extinguisher inside
203143 02/22/2006 77023 3 306 OS Prohibit storage of flammable spray paint
203152 02/22/2006 77038 7 708 OS Remove storage from bathroom vestibule
203157 02/22/2006 77048 8 807 OS Remove storage from stove burners to prevent fire hazard
190441 02/22/2006 57380 00 0000 CS Provide "Knox" padlock on entry gate to allow fire department access
190453 02/22/2006 14852 1 114 CS Provide fire rated door and frame at door into corridor between Buildings 1 and 2
190454 02/22/2006 14853 1 117 CS Provide fire rated door and frame
190455 02/22/2006 14913 1 199 CS Provide protection for natural gas line in corridor
190457 02/22/2006 57349 10 009 CS Provide fire extinguisher within 15? of stove
190472 02/22/2006 14855 2 220 CS Provide fire rated door and frame at door into corridor between Buildings 1 and 2
190473 02/22/2006 14856 2 220A CS Provide fire rated door and frame at door into corridor between Buildings 2 and 3
190474 02/22/2006 14857 2 223 CS Provide fire rated door and frame
190475 02/22/2006 14858 2 226 CS Provide fire rated door and frame
190479 02/22/2006 14860 3 301 CS Replace door in corridor between Buildings 2 and 3 with a fire rated door and frame
190480 02/22/2006 14862 5 506 CS Provide fire rated door and frame
190481 02/22/2006 14863 5 508 CS Provide fire rated door and frame
190483 02/22/2006 14864 6 612 CS Replace door in corridor between Buildings 6 and 7 with a fire rated door and frame
190484 02/22/2006 14865 6 615 CS Provide fire rated door and frame at door into corridor between Buildings 6 and 7
190486 02/22/2006 14867 7 701 CS Provide fire rated door and frame
203148 02/22/2006 77033 7 701 CS Provide secondary egress
190487 02/22/2006 14868 7 704 CS Provide fire rated door and frame
190488 02/22/2006 14869 7 707 CS Provide fire rated door and frame
203150 02/22/2006 77035 7 707 CS Provide secondary egress
203151 02/22/2006 77036 7 710 CS Provide secondary egress
190489 02/22/2006 14870 7 710 CS Provide fire rated door and frame
190491 02/22/2006 14871 8 801 CS Provide fire rated door and frame
190492 02/22/2006 14873 8 804 CS Provide fire rated door and frame
190496 02/22/2006 14877 9 922 CS Provide fire rated door and frame
190449 02/22/2006 57367 1 107 FS Provide heat detector in room used for storage
190437 12/06/2004 63766 00 0000 M Eliminate rodents throughout campus
203005 12/06/2004 76764 1 105 M Repair noisy exhaust fan in bathroom
190450 12/06/2004 57343 1 109 M Anchor loose exhaust fan grill
203010 12/06/2004 76777 10 011 M Adjust exterior door to latch properly
203011 12/06/2004 76778 10 013 M Adjust exterior door to latch properly
190459 12/06/2004 15039 11 102 M Provide current inspection tag for boiler
190460 12/06/2004 57378 11 104 M Replace vapor proof lens on light fixture
190461 12/06/2004 57379 11 104 M Replace burned out light bulb or repair light fixture
190463 12/06/2004 15005 2 201 M Replace missing blades for ceiling fans
190464 12/06/2004 15006 2 202 M Provide current inspection tag for kitchen steamer
190465 12/06/2004 57369 2 202 M Move deep fryer so that it is directly under the suppression head and tighten loose nozzle for suppression head and paint line on floor to indicate proper location of cooking equipment under hood
203020 12/06/2004 76792 2 202 M Repair light in exit sign above exterior door
190469 12/06/2004 57344 2 213 M Repair exhaust fan
190470 12/06/2004 63767 2 214 M Determine cause of water damaged ceiling tiles and replace tiles
203142 12/06/2004 77021 2 216 M Repair clogged floor drain
190478 12/06/2004 57406 3 301 M Clean rust from, prime and repaint rusted steel girder joist
203145 12/06/2004 77027 5 501 M Provide signs indicating "Fire Alarm Pull Station Inside" and "Fire Extinguisher Inside"
190482 12/06/2004 57377 6 604 M Provide cover on exposed fire alarm junction box
203146 12/06/2004 77028 6 605 M Provide sign indicating "Fire Alarm Pull Station Inside"
190485 12/06/2004 57383 6 616 M Anchor toilet to floor
190490 12/06/2004 57386 7 711 M Anchor toilet to floor
203154 12/06/2004 77042 8 802 M Secure toilet to floor
203156 12/06/2004 77044 8 804 M Remove "Emergency Exit" sign adjacent to door into bathroom vestibule
190493 12/06/2004 57387 8 805 M Anchor toilet to floor
203159 12/06/2004 77052 8 899 M Repair light in exit sign adjacent to 8-804
203163 12/06/2004 77059 9 917 M Provide caulk to seal gap between toilet and floor
190503 12/06/2004 57376 P 3637 M Clean A/C vents
190545 12/06/2004 15060 P 387 M Adjust stair landing to be level with interior floor
203181 12/06/2004 77095 P 387 M Secure loose handrail for stairs
190500 12/06/2004 57418 P 47 M Repair or replace deteriorated wood siding
190512 12/06/2004 15043 P 4781 M Adjust steps to make risers equal
203174 12/06/2004 77081 P 4781 M Repair emergency lighting
190529 12/06/2004 57411 P 5 M Repair exhaust fan in bathroom
190498 12/06/2004 57417 P 731 M Repair or replace deteriorated wood siding
190517 12/06/2004 57419 P 738 M Repair deteriorated wood siding at SE corner
203176 12/06/2004 77085 P 738 M Provide sign indicating "Fire Alarm Pull Station Inside"
203178 12/06/2004 77089 P 744 M Repair emergency lighting
190525 12/06/2004 57420 P 745 M Repair or replace deteriorated wood siding
203158 12/06/2004 77050 8 812 O Eliminate extension cord or replace with minimum 15A cord
203160 12/06/2004 77054 9 911 O Replace burned out light bulb or have maintenance repair light fixture
190446 12/06/2004 57401 00 9699 C Fill the eroded area to the east of the pavilion. Use sod or gravel to prevent future erosion.
190462 12/06/2004 14949 11 8088 C Install weep holes for brickwork to allow moisture to escape
190499 12/06/2004 57356 P 47 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190513 12/06/2004 14959 P 4781 C Provide graspable handrails on each side of ramp at between 34-38 inches high
190514 12/06/2004 14951 P 4781 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
190515 12/06/2004 14958 P 4781 C Provide handrails on each side of stair
190510 12/06/2004 14957 P 4781 C Provide guardrails at stair landing at a minimum 42 inches high
190511 12/06/2004 14952 P 4781 C Provide guardrails at ramp landing at a minimum 42 inches high
190497 12/06/2004 57355 P 731 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
190458 12/06/2004 57347 10 010 MS Provide current inspection tag for fire extinguisher
190466 12/06/2004 14892 2 202 MS Provide current inspection tag for fire suppression system
203141 12/06/2004 77018 2 216 MS Provide current inspection tag for fire extinguisher
190495 12/06/2004 57348 9 922 MS Provide current inspection tag for fire extinguisher
203167 12/06/2004 77067 P 731 MS Replace missing fire extinguisher
203006 12/06/2004 76768 1 112 OS Remove storage from mechanical room
203009 12/06/2004 76775 10 007 OS Remove storage from electrical room
203013 12/06/2004 76781 2 201 OS Relocate chairs blocking access to fire extinguisher on east wall
203162 12/06/2004 77056 9 914 OS Remove storage from electrical room
203169 12/06/2004 77070 P 47 OS Relocate boxes to provide clear path of travel to stair door
203165 12/06/2004 77063 P 731 OS Relocate storage to provide clear access to fire alarm pull station
190436 12/06/2004 57346 00 0000 FS Verify that all portables are connected to the fire alarm panel (Pink sheets indicate only 10 portables are connected)
190451 12/06/2004 57368 1 113A FS Provide heat detector in normally unoccupied space (phone closet)
190456 06/30/2004 57358 10 001 M Anchor shelving to wall