SEMINOLE RIDGE HIGH
 
SEMINOLE RIDGE HIGH
This site is a Hurricane Shelter
4601 Seminole Pratt Whitney Road
Loxahatchee, 33470
FISH Drill Down
 Campus Info.
 Buildings:15 Rooms:593
 Portables:2
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
413063 04/30/2018 471306 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable - old certificate in 10-191
413143 04/30/2018 471474 12 170 M Provide current inspection tag for elevator to pressbox
412889 04/30/2018 470930 5 112A M Repair exhaust fan in bathroom
412890 04/30/2018 470932 5 112B M Repair exhaust fan in bathroom
412892 04/30/2018 470936 5 180 M Repair exhaust fan
262632 04/30/2018 145038 12 0000 N/A No violations observed
413108 04/20/2018 471404 00 9599 M Repair damaged pavement at end of bus loop adjacent to retention area - Large hole
413412 04/20/2018 472046 11 101 M Repair deteriorated wall finish adjacent to door
413413 04/20/2018 472048 11 190 M Replace missing signage indicating room name and number for electrical room at NW corner - sign reads 11-105
413407 04/20/2018 472035 14 0000 M Secure loose fence posts, repair damaged chain link fencing and replace missing top rail at fencing behind Bldg. 14 - east of home bleachers
413392 04/20/2018 472005 2 005 M Replace missing floor tiles adjacent to exit door at east end of corridor adjacent to 2-113H
413400 04/20/2018 472022 2 108A M Repair light in exit sign along west ramp at front of stage
413386 04/20/2018 471993 2 114 M Adjust SE exit doors to latch properly
394404 04/20/2018 431030 2 114 M Repair damaged fire extinguisher cabinet at southeast exit door of gym (unable to open door of cabinet)
413145 04/20/2018 471478 3 003 M Replace missing ceiling tile in corridor adjacent to 3-109
413126 04/20/2018 471440 3 104J M Repair deteriorated wall finish at bottom of partition wall
413172 04/20/2018 471535 4 0000 M Repair or replace auto closer on exit gates between Bldgs. 4 and 5 - most gates slam hard
412887 04/20/2018 470926 4 102 M Repair damaged wall finish behind desk
412888 04/20/2018 470928 4 104A M Repair exhaust fan in bathroom
412891 04/20/2018 470934 4 180 M Repair exhaust fan
412886 04/20/2018 470924 6 112B M Replace missing ceramic base tile in bathroom
412899 04/20/2018 470950 6 113 M Repair missing base along walls
413179 04/20/2018 471539 9 0000 M Repair exit gates between Bldgs. 9 and 10 to open and close properly and repair damaged auto closers. Some slam hard
413123 04/20/2018 471434 3 102 O Remove and prohibit flammable fabric on wall adjacent to 3-102A
413415 04/20/2018 472052 12 0000 MS Remove and prohibit storage of yellow plastic fencing caps under bleachers
413487 04/20/2018 472198 00 0000 OS Keep all recycle bins in corners or in recessed areas of corridors throughout facility
412883 04/20/2018 470918 1 140 OS Remove and prohibit use of space heater
413132 04/20/2018 471453 3 109 OS Relocate weight lift equipment to maintain a minimum 3 ft clear path to both exit doors
413489 04/20/2018 472209 4 102 OS Reduce number of student desks to maintain clear path to exits - 29 desks is the limit
262621 04/20/2018 145016 1 0000 N/A No violations observed
262631 04/20/2018 145036 11 0000 N/A No violations observed
320768 04/20/2018 270368 14 0000 N/A No violations observed
262623 04/20/2018 145020 3 0000 N/A No violations observed
262629 04/20/2018 145032 9 0000 N/A No violations observed
413406 03/12/2018 472033 00 9599 M Repair leaning speed sign along driveway east of Bldg. 2
412884 03/12/2018 470920 1 143B M Secure loose lens cover to light fixture in girls bathroom - clinic
412882 03/12/2018 470916 1 190 M Determine cause of water damaged ceiling tiles and replace tiles
413102 03/12/2018 471391 10 101A M Secure loose lens on light fixture
413101 03/12/2018 471389 10 101B M Repair problems with fire alarm system - Troubles indicated on panel
413064 03/12/2018 471308 10 101D M Remove over grown vegetation outside exterior door of south serving area to maintain safe egress
413103 03/12/2018 471393 10 101E M Secure loose lens on light fixture
413104 03/12/2018 471396 10 180A M Provide cover for exposed electrical outlet behind desk
413105 03/12/2018 471398 10 195 M Chain cylinders to wall
413106 03/12/2018 471400 10 195 M Secure machinery in use to flooring. NA - Machinery not in use
413410 03/12/2018 472041 11 0000 M Provide insulated cover for exposed electrical outlet on east wall adjacent to 11-105
413411 03/12/2018 472044 11 0000 M Provide insulated cover for exposed electrical outlet on west wall of Bldg. 11
413416 03/12/2018 472054 12 0000 M Determine cause of water damaged ceiling tiles and replace tiles
394416 03/12/2018 431057 12 0000 M Repair or replace rusted window frame in north entrance door of press box
413408 03/12/2018 472037 14 0000 M Repair uneven concrete walkway between Bldgs. 11 and 14 to eliminate trip hazard - adjacent to home bleachers
413409 03/12/2018 472039 14 0000 M Provide insulated cover for exposed electrical outlet on west wall of Bldg. 14
413401 03/12/2018 472024 2 101 M Replace missing operating button on drinking fountain in gymnasium corridor
413403 03/12/2018 472028 2 101 M Adjust NE exit door to latch properly at end of corridor adjacent to 2-102
413397 03/12/2018 472017 2 108 M Adjust SE exterior doors to latch properly
413399 03/12/2018 472019 2 108A M Adjust east exterior door on stage to latch properly
413396 03/12/2018 472015 2 108C M Mount evacuation map indicating primary and secondary evacuation routes in contrasting colors at 5 ft above floor adjacent to stage door - girls dressing room
413391 03/12/2018 472003 2 113J M Replace missing lens on light fixture
413390 03/12/2018 472001 2 180 M Determine cause of water damaged ceiling tiles and replace tiles
413152 03/12/2018 471490 3 008 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to 3-210
413131 03/12/2018 471451 3 108C M Determine cause of water damaged ceiling tiles and replace tiles
413130 03/12/2018 471448 3 108D M Secure loose cover on electrical outlet under writing board
413136 03/12/2018 471459 3 215 M Anchor metal shelving to wall
412898 03/12/2018 470948 6 101 M Replace missing ceiling tiles
412900 03/12/2018 470952 6 103 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to 6-103A
412901 03/12/2018 470954 6 103 M Adjust right leaf of exterior door to latch properly
412904 03/12/2018 470960 6 108 M Replace missing appliance light bulb above cook range
412895 03/12/2018 470942 6 114B M Determine cause of water damaged ceiling tiles and replace tiles
412896 03/12/2018 470944 6 114B M Clean surface mold on wall
413052 03/12/2018 471284 6 208 M Determine cause of water damaged ceiling tiles and replace tiles
413492 03/12/2018 472211 6 211 M Post sign inside classroom limiting occupancy to maximum 5 students - designed after Oct. 18, 1994. Remove sign of 9 occupants outside classroom door
413026 03/12/2018 471230 7 110B M Determine cause of water damaged ceiling tiles and replace tiles
413025 03/12/2018 471227 7 112 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to windows
413037 03/12/2018 471252 7 116 M Secure loose lens cover on light fixture in girls bathroom
413055 03/12/2018 471290 7 203A M Replace missing lens on light fixture
413046 03/12/2018 471270 7 205 M Replace burned light bulbs in emergency light fixture
413051 03/12/2018 471282 7 206 M Determine cause of water damaged ceiling tiles and replace tiles
413050 03/12/2018 471280 7 210 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to windows
412874 03/12/2018 470900 8 102A M Provide emergency lighting in classroom space or verify room has emergency lighting
413038 03/12/2018 471254 9 001 M Determine cause of water damaged ceiling tiles and replace tiles above lockers in corridor facing 9-105
413042 03/12/2018 471262 9 107 M Turn barbs down on fencing section facing 9-107M
413043 03/12/2018 471264 9 107 M Replace all burned out light bulbs in construction shop
413044 03/12/2018 471266 9 107 M Secure machinery to floor or table top - see Mr. Terkovich
413402 03/12/2018 472026 2 104 O Remove broken glass from certificate frame adjacent to corridor door to eliminate hazard - concession room
413124 03/12/2018 471436 3 102 O Remove florescent light fixture off floor to eliminate hazard
413155 03/12/2018 471500 4 201 O Remove paper covering electrical outlets under writing board - (2) locations
413158 03/12/2018 471502 4 201 O Remove and prohibit excessive flammable black vinyl sheathing used for display in back of classroom
413159 03/12/2018 471508 4 202 O Remove red black paper covering electrical outlets at corner along corridor wall and red gray paper covering electrical outlets on back wall
412893 03/12/2018 470938 5 110A O Relocate boxes to keep area within 18 inches of fire sprinkler heads clear and unobstructed - 2 locations
413121 03/12/2018 471430 5 210 O Prohibit piggy backed surge protectors and surge into extension cord under computer stations back to back - plug each surge protector directly into wall outlet and eliminate use of extension cord
413112 03/12/2018 471412 5 219 O Remove and prohibit fabric covering ceiling light fixtures
412897 03/12/2018 470946 6 101 O Eliminate orange (3) plug electrical outlet adaptor adjacent to west corridor door or replace with a surge protector
412902 03/12/2018 470956 6 106 O Provide cover strip for electrical cords running across floor adjacent to teacher station and secure cover strip to flooring to eliminate trip hazard
412894 03/12/2018 470940 6 114 O Remove and prohibit plug in air freshener adjacent to corridor door
413054 03/12/2018 471288 6 202 O Remove and prohibit paper covering window in corridor door
413059 03/12/2018 471298 6 215 O Eliminate black power outlet strip adjacent to refrigerator or replace with a surge protector
413057 03/12/2018 471294 6 220 O Prohibit plugging surge protector into surge protector under (5) rows of computer stations - plug each surge protector directly into wall outlet
413053 03/12/2018 471286 7 203 O Remove and prohibit paper covering window in corridor door
413045 03/12/2018 471268 7 215A O Relocate storage to keep area within 18 inches of fire sprinkler heads clear and unobstructed
412872 03/12/2018 470896 8 104 O Remove glass mirror or provide mirror made of tempered glass, safety glass, or stainless steel
413039 03/12/2018 471256 9 102 O Eliminate orange extension cord with multiple outlet end adjacent to writing board or replace with a surge protector
413040 03/12/2018 471258 9 103 O Prohibit plugging surge protector into surge protector under 2nd and 3rd rows of computer stations on left side of classroom
413387 03/12/2018 471995 P 6462 O Remove and prohibit flammable curtain on window
413393 03/12/2018 472007 2 108E C Post sign indicating primary and secondary evacuation routes in contrasting colors
413685 03/12/2018 472633 3 0000 C Post sign indicating primary and secondary evacuation routes in contrasting colors in classrooms: 3-206, 3-207, 3-209, 3-210 and 3-213
413114 03/12/2018 471416 4 0000 C Post sign indicating primary and secondary evacuation routes in contrasting colors in classrooms 4-202 and 4-203
413113 03/12/2018 471414 5 0000 C Post sign indicating primary and secondary evacuation routes in contrasting colors in classrooms: 5-205 and 5-215
412903 03/12/2018 470958 6 0000 C Post sign indicating primary and secondary evacuation routes in contrasting colors in classrooms: 6-107, 6-202, 6-203, 6-213, 6-214 and 6-215
413028 03/12/2018 471234 7 0000 C Post sign indicating primary and secondary evacuation routes in contrasting colors in classrooms: 7-102, 7-111, 7-204 and 7-213
413029 03/12/2018 471236 9 107K C Post sign indicating primary and secondary evacuation routes in contrasting colors
412879 03/12/2018 470910 1 005 MS Provide current inspection tag for fire extinguisher in corridor adjacent to 1-132
413062 03/12/2018 471304 10 193 MS Provide current inspection tag for fire extinguisher
413107 03/12/2018 471402 10 194 MS Repair door hardware to work properly to exterior chiller area - door lock does not work
413389 03/12/2018 471999 2 006 MS Provide current inspection tag for fire extinguisher in corridor facing bathroom 2-110
413395 03/12/2018 472012 2 108A MS Provide current inspection tag for fire extinguisher at stage catwalk
413388 03/12/2018 471997 2 109 MS Provide current inspection tag for fire extinguisher
413404 03/12/2018 472030 2 191 MS Provide current inspection tag for fire extinguisher in exterior electrical room
413394 03/12/2018 472009 2 294 MS Provide current inspection tag for fire extinguisher in electrical room at west loft above stage
413125 03/12/2018 471438 3 104H MS Provide current inspection tag for fire extinguisher or remove from office
413128 03/12/2018 471444 3 108 MS Secure loose lock hardware on corridor door to boys locker
413133 03/12/2018 471455 3 212 MS Adjust corridor door to latch properly
413122 03/12/2018 471432 5 209A MS Repair door hardware to work properly - latch hardware sticks
413109 03/12/2018 471406 5 215 MS Adjust corridor door to latch properly
413147 03/12/2018 471483 5 290 MS Repair door hardware to work properly - latch hardware sticks
413056 03/12/2018 471292 6 202 MS Adjust corridor door to latch properly
413058 03/12/2018 471296 6 292 MS Repair door hardware to work properly - latch hardware sticks
412871 03/12/2018 470894 7 171 MS Provide current inspection tag for fire extinguisher
413041 03/12/2018 471260 9 107 MS Adjust corridor door to latch properly - adjacent to 9-107M
412881 03/12/2018 470914 1 118 OS Clean dirty toaster over or prohibit use to eliminate fire hazard - Athletic director office
412880 03/12/2018 470912 1 134 OS Remove and prohibit use of space heater
413414 03/12/2018 472050 12 0000 OS Remove and prohibit storage of vinyl foam mat under bleachers
412878 03/12/2018 470908 3 0000 OS Remove all seats from center of 1st floor covered walkway to maintain safe egress
413127 03/12/2018 471442 3 104E OS Remove clothes racks from exit vestibule in girls locker room
413129 03/12/2018 471446 3 108B OS Remove all storage from exit vestibule in boys locker room
412876 03/12/2018 470904 3 193 OS Remove storage from hot water heater room
413110 03/12/2018 471408 5 215 OS Relocate shelf unit adjacent to corridor door to maintain safe egress
412885 03/12/2018 470922 7 191 OS Remove custodial storage from electrical room
413047 03/12/2018 471273 7 205 OS Clean dirty toaster over or prohibit use to eliminate fire hazard
412875 03/12/2018 470902 8 102 OS Remove and prohibit use of toaster oven and toaster - location facing 8-104
412873 03/12/2018 470898 8 104 OS Remove and prohibit use of toaster oven and toaster in classroom
262628 03/12/2018 145030 8 0000 N/A No violations observed
320770 03/12/2018 270372 P 6462 N/A No violations observed
352154 11/06/2017 339251 00 0000 M Repair damaged, bent poles for covered walk at bus loop
413496 11/06/2017 472224 00 0000 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report dated 4.20.17
413497 11/06/2017 472227 00 0000 M Repair bleachers as instructed in the Bleacher Structural Inspection Report. Contact Patrick Joyce if questions occur.
394276 11/06/2017 430756 00 0000 M Make necessary repairs to fire sprinkler systems as indicated on inspection report (systems due for 5 year inspection)
394290 11/06/2017 430783 00 0000 M Repair damaged roof panel on covered walkway at bus loop
379342 11/06/2017 398491 10 195 M Repair heavily rusted door frame
394407 11/06/2017 431036 14 0000 M Repair damaged chain link fencing in front of ticket booth
394486 11/06/2017 431199 3 006 M Repair drinking fountains in 2nd floor corridor adjacent to 3-216
412877 11/06/2017 470906 4 0000 M Repair damaged concrete edge of 8th riser at bottom run of stairs in interior courtyard
413163 11/06/2017 471518 5 0000 M Secure loose handrail at intermediate landing for stairs in courtyard
413169 11/06/2017 471528 5 0000 M Secure loose handrail at 2nd floor covered walkway
413060 11/06/2017 471300 6 0000 M Secure loose handrail at intermediate landing for stairs in courtyard
413061 11/06/2017 471302 7 0000 M Secure loose handrail at 2nd floor covered walkway between Bldgs. 6 and 7 - few railing sections are loose
413048 11/06/2017 471275 7 205A M Repair exhaust fan in bathroom
413049 11/06/2017 471277 7 205B M Repair exhaust fan in bathroom
394468 11/06/2017 431163 7 217 M Replace missing mirrors in boys restroom and in handicap stall
394372 11/06/2017 430964 2 113H O Remove lightweight partition walls forming storage space (X2) from piano lab (structures do not meet code and design requirements, contact FMC for assistance if needed)
413495 11/06/2017 472218 6 211 O Limit occupancy to maximum 5 students - designed after Oct. 18, 1994 or facilitate a project through M&PO to change door to swing in direction of egress
394424 11/06/2017 431073 P 0000 O Clean mold from underside of covered walkway at portables to eliminate health hazard
330072 11/06/2017 291204 00 0000 C Modify or improve site drainage at tennis courts and softball field
262630 11/06/2017 145034 10 0000 N/A No violations observed
262633 11/06/2017 145040 13 0000 N/A No violations observed
262622 11/06/2017 145018 2 0000 N/A No violations observed
262624 11/06/2017 145022 4 0000 N/A No violations observed
262625 11/06/2017 145024 5 0000 N/A No violations observed
262626 11/06/2017 145026 6 0000 N/A No violations observed
262627 11/06/2017 145028 7 0000 N/A No violations observed
320769 11/06/2017 270370 P 6461 N/A No violations observed
367768 03/27/2017 373330 2 108A M Repair stage lights. Staff reports that lights directly over stage are not working, switch located at door to 2-108J
379135 03/17/2017 398045 00 0000 M Repair or replace rusted goal post uprights at football field
379234 03/17/2017 398262 00 0000 M Provide anchors for shipping containers west of building 14
394498 03/17/2017 431223 00 0000 M Remove mold and mildew from visitor's bleachers at football stadium to prevent slip and fall hazard
330066 03/17/2017 291189 00 0000 M Secure gaps at bottom of fence along retention pond at north side of football field and adjacent to visitors bleachers. There are large gaps between the ground and the bottom of the fence
379237 03/17/2017 398269 1 103 M Repair damaged wall at window
394365 03/17/2017 430948 1 113 M Determine cause of water damaged ceiling tiles and replace tiles
394367 03/17/2017 430952 1 190 M Determine cause of water damaged ceiling tiles and replace tiles
394369 03/17/2017 430956 1 192 M Repair deteriorated wall finish at doors
394457 03/17/2017 431140 10 101 M Provide security padlock on fire sprinkler riser enclosure at southeast corner of cafeteria
394452 03/17/2017 431130 10 101B M Make any necessary repairs as indicated on fire alarm report dated 8-23-16
394456 03/17/2017 431138 10 102A M Repair damaged wall finish in women's restroom
394455 03/17/2017 431136 10 102B M Secure loose toilet seat in men's restroom
394453 03/17/2017 431132 10 106 M Secure loose toilet seat in staff restroom
394417 03/17/2017 431059 11 0000 M Replace missing cover on electrical outlet on exterior wall on south side of building adjacent to 11-103
394410 03/17/2017 431045 11 0000 M Replace missing cover on GFCI outlet on exterior north wall of Building 11
394411 03/17/2017 431047 11 102 M Replace missing mirror above sink in men's restroom
394412 03/17/2017 431049 11 102 M Secure hanging exit sign in men's restroom
394413 03/17/2017 431051 11 102 M Repair faucet in sink in men's restroom
394408 03/17/2017 431038 11 104 M Repair out-of-service toilet in women's restroom
394414 03/17/2017 431053 12 0000 M Replace missing cover on electric outlet on west exterior wall of building adjacent to 12-190
394415 03/17/2017 431055 12 0000 M Determine cause of water damaged ceiling tiles in press box and replace tiles
394445 03/17/2017 431116 13 0000 M Repair or remove damaged chain link fencing on west side of Building 13
394446 03/17/2017 431118 13 101 M Replace burned out bulbs in light fixtures inside flammable storage room
394409 03/17/2017 431041 14 0000 M Replace deteriorated and rotting wood facia board on roof at west side of building
394406 03/17/2017 431034 14 0000 M Repair damaged exterior wall at ticket window
379295 03/17/2017 398390 14 0000 M Replace missing hurricane shutter anchors in exterior wall
394385 03/17/2017 430993 2 004 M Determine cause of water damaged ceiling tiles at south end of ramp behind stage and replace tiles
394383 03/17/2017 430988 2 005 M Replace missing ceiling tiles above drinking fountains in corridor
394392 03/17/2017 431007 2 101 M Determine cause of water damaged ceiling tiles in corridor north of gym and replace tiles
394388 03/17/2017 430998 2 102 M Repair hole in wall at ticket booth window
394389 03/17/2017 431001 2 107 M Make repair to out-of-service urinal in men's restroom
394390 03/17/2017 431003 2 107 M Replace missing mirror above sink in men's restroom
394391 03/17/2017 431005 2 107 M Replace missing soap dispenser in men's restroom
394384 03/17/2017 430990 2 108C M Replace missing globe in light fixture at exit door in corridor
394381 03/17/2017 430984 2 108D M Secure loose toilet seat in girls dressing room bathroom
394382 03/17/2017 430986 2 108E M Replace damaged ceiling tiles in boys dressing room2
394379 03/17/2017 430980 2 110 M Secure loose toilet seat in handicap stall
394370 03/17/2017 430960 2 113 M Secure hanging light fixture lens in band room
394399 03/17/2017 431021 2 114 M Secure hanging exit sign at northeast doors of gym
394402 03/17/2017 431024 2 114 M Repair crack in wall at entrance to 2-114A gym storage room
394403 03/17/2017 431028 2 114 M Repair crack in wall at entrance to 2-114B gym storage room
394405 03/17/2017 431032 2 114 M Repair damaged wall above southeast exit doors of gym
394380 03/17/2017 430982 2 180 M Determine cause of water damaged ceiling tiles and replace tiles
394490 03/17/2017 431207 3 101C M Replace corroded fire sprinkler head inside kiln room
394494 03/17/2017 431215 3 102 M Replace missing and damaged ceiling tiles
394496 03/17/2017 431219 3 102C M Replace damaged ceiling tiles
394418 03/17/2017 431061 3 104G M Replace moldy ceiling tiles
394420 03/17/2017 431065 3 108 M Secure hanging exit sign in boy's locker room
394421 03/17/2017 431067 3 108B M Replace missing floor tile
394422 03/17/2017 431069 3 109 M Repair east corridor exit door to close properly
394487 03/17/2017 431201 3 201A M Secure loose toilet seat
394458 03/17/2017 431143 3 216 M Repair out of service toilet in girls restroom
394484 03/17/2017 431195 3 292 M Replace missing floor drain cover in mechanical room
394363 03/17/2017 430942 4 101 M Determine cause of water damaged ceiling tiles at windows on east wall and replace tiles
394364 03/17/2017 430946 4 102 M Determine cause of water damaged ceiling tiles at exit door and replace tiles
394361 03/17/2017 430939 4 107 M Determine cause of water damaged ceiling tiles and replace tiles
394480 03/17/2017 431187 4 201 M Secure hanging lens on light fixture
394481 03/17/2017 431189 4 201A M Repair or replace bent metal grill on ventilation fan in ceiling
394478 03/17/2017 431183 4 215B M Secure loose toilet seat in men's restroom
394482 03/17/2017 431191 4 291 M Replace missing signage indicating room name and number on electric room
394475 03/17/2017 431177 5 0000 M Repair peeling paint on outside wall above classroom door at 5-211
394430 03/17/2017 431086 5 112A M Secure hanging lens on light fixture in staff restroom
394431 03/17/2017 431088 5 192 M Place cover on floor drain at entrance door
394476 03/17/2017 431179 5 216A M Secure loose toilet seat
394477 03/17/2017 431181 5 218 M Replace missing ceramic base tile in entrance to boy's restroom
394428 03/17/2017 431082 6 103 M Determine cause of water damaged ceiling tiles and replace tiles
394426 03/17/2017 431078 6 105 M Secure hanging light fixture lens
394427 03/17/2017 431080 6 105 M Determine cause of water damaged ceiling tiles and replace tiles
394472 03/17/2017 431171 6 218 M Replace broken ceramic base tile at entrance of boy's bathroom
394473 03/17/2017 431173 6 218 M Replace missing mirror in boy's bathroom
394471 03/17/2017 431169 6 280 M Repair deteriorated wall finish above mop sink
394465 03/17/2017 431157 7 007 M Repair loose vinyl base along wall in corridor next to smoke doors
394434 03/17/2017 431094 7 116 M Repair damaged wall in entrance to girl's restroom
394432 03/17/2017 431090 7 117 M Replace missing soap dispenser in handicap stall in boy's restroom
394433 03/17/2017 431092 7 117 M Repair damaged wall next to floor at entrance to boy's restroom
394438 03/17/2017 431102 7 170 M Replace missing floor tiles in elevator
394437 03/17/2017 431100 7 191 M Provide cover on electrical panel next to floor
394466 03/17/2017 431159 7 205B M Secure loose toilet seat
394467 03/17/2017 431161 7 217 M Secure loose toilet seat in boy's restroom
394444 03/17/2017 431114 8 108 M Secure hanging lighted exit sign adjacent to 8-109
394442 03/17/2017 431110 8 109 M Replace ceiling tiles that have holes in them
394440 03/17/2017 431106 8 111 M Replace missing wall tile at towel dispenser
394449 03/17/2017 431124 9 103 M Anchor shelving to wall next to exit door
394450 03/17/2017 431126 9 191 M Repair air conditioning unit above door (room is very hot)
394423 03/17/2017 431071 P 6461 M Repair emergency lighting at rear door
394425 03/17/2017 431075 P 6462 M Eliminate termites nesting at rear door
394366 03/17/2017 430950 1 113 O Keep area within 18 inches of fire sprinkler head clear and unobstructed (storage on top shelf of storage rack)
394493 03/17/2017 431213 3 101A O Replace burned out bulbs in light fixture
394497 03/17/2017 431221 3 102A O Replace burned out bulbs in light fixture
394488 03/17/2017 431203 3 102A O Remove and prohibit combustible (residential) furniture) (Sofa)
394495 03/17/2017 431217 3 102D O Replace burned out bulbs in light fixtures
394485 03/17/2017 431197 3 215 O Replace burned out bulbs in light fixtures in textbook storage room
394479 03/17/2017 431185 4 202 O Remove and prohibit flammable curtains hanging from ceiling
394429 03/17/2017 431084 6 102 O Eliminate 3-way multi plug outlet adaptor on east wall
394474 03/17/2017 431175 6 202 O Remove and prohibit paper covering window in door
352210 03/17/2017 339376 6 211 O Post sign limiting occupancy to maximum 6 students or create workorder requesting to change the swing of door to swing in direction of travel
394435 03/17/2017 431096 7 110 O Replace missing evacuation map showing primary and secondary emergency exit routes
394436 03/17/2017 431098 7 110 O Remove and prohibit banner hanging from ceiling
394464 03/17/2017 431155 7 206 O Remove and prohibit hanging paper and decorations from ceiling
394463 03/17/2017 431153 7 210 O Prohibit plugging surge protector into surge protector at teachers desk
394462 03/17/2017 431151 7 211 O Eliminate white, light duty multi outlet extension cord at teachers desk
394460 03/17/2017 431147 7 213 O Remove and prohibit hanging paper and decorations from ceiling
394461 03/17/2017 431149 7 214 O Remove and prohibit hanging paper from lighted exit sign
394447 03/17/2017 431120 9 101A O Remove and prohibit combustible (residential) furniture (sofa sleeper) (Sofa has been sprayed with a flame retardant, certificate is stapled to back of sofa)
330080 03/17/2017 291222 00 0000 C Modify gate adjacent to Bldg. 14 ticket booth to allow Fire Department Access. Gate needs to be larger to allow emergency vehicle access. Relocate sign (facing parking lot adjacent to bike rack) indicating FD access road to be adjacent to east driveway (adjacent to Bldg. 14) with curb cut
394454 03/17/2017 431134 10 101 MS Provide current inspection tag for fire extinguisher at southwest exit door of cafeteria
394451 03/17/2017 431128 10 195 MS Provide current inspection tag for fire extinguisher
394374 03/17/2017 430969 2 005 MS Recharge fire extinguisher at east exit door of corridor
394375 03/17/2017 430971 2 005 MS Recharge fire extinguisher in corridor at band room door
394387 03/17/2017 430995 2 192 MS Provide current inspection tag for fire extinguisher
394394 03/17/2017 431010 2 290 MS Provide current inspection tag for fire extinguisher in mechanical room vestibule
394395 03/17/2017 431012 2 291 MS Provide current inspection tag for fire extinguisher in electrical room
394396 03/17/2017 431014 2 292 MS Provide current inspection tag for fire extinguisher in Data room
394397 03/17/2017 431016 2 293 MS Provide current inspection tag for fire extinguisher in mechanical room
394489 03/17/2017 431205 3 101 MS Replace missing fire extinguisher in cabinet at southeast corner of room
394491 03/17/2017 431209 3 101 MS Provide current inspection tag for fire extinguisher next to kiln room door
394419 03/17/2017 431063 3 104F MS Provide current inspection tag for fire extinguisher at exterior door
394441 03/17/2017 431108 8 003 MS Recharge fire extinguisher in corridor at south entrance doors
394443 03/17/2017 431112 8 108 MS Recharge fire extinguisher on east wall next to tire changing machine
394439 03/17/2017 431104 8 191 MS Provide current inspection tag for fire extinguisher
394368 03/17/2017 430954 1 192 OS Remove storage from mechanical room (cafeteria tables)
394373 03/17/2017 430966 2 005 OS Remove storage from exit corridor to maintain clear aisle to exit at all times
394398 03/17/2017 431019 2 006 OS Remove and prohibit storage at bottom of stairway
394492 03/17/2017 431211 3 101B OS Prohibit storage of flammable fluorescent spray paint (store inside flammable storage cabinet)
394483 03/17/2017 431193 3 292 OS Remove storage from mechanical room
394470 03/17/2017 431167 6 291 OS Remove storage from electrical room
394469 03/17/2017 431165 6 292 OS Remove storage from mechanical room
394459 03/17/2017 431145 7 292 OS Remove storage from mechanical room
394448 03/17/2017 431122 9 103A OS Prohibit storage of flammable field marker spray paint (store inside flammable storage cabinet)
379148 09/14/2016 398076 2 192 M Make necessary repairs to fire sprinkler system as indicated on inspection report
379130 09/14/2016 398033 00 0 O No access was available to 2-103 (elevator), 6-219, 12-170 (elevator), and metal storage building west of building 14. Please provide access to these rooms during the report review meeting
340914 09/14/2016 314741 00 0000 C Modify or improve drainage in interior courtyard to eliminate standing water (NA per Pat Joyce, very small puddles of standing water after heavy rain, evaporates within 24 hours)
379233 05/05/2016 398260 00 0000 C Modify or improve site drainage to eliminate standing water at 3rd baseline of baseball field
379257 05/05/2016 398315 00 0000 C Modify or improve site drainage to eliminate standing water on sidewalk west of building 11
379344 05/03/2016 398498 10 194 M Repair door to open and close properly
379288 05/02/2016 398378 11 190 M Repair or replace surge suppressor for panel 11H. Not illuminated
379291 05/02/2016 398381 11 190 M Repair or replace surge suppressor for panel 11LSH. Not illuminated
379356 05/02/2016 398523 2 291 M Repair or replace surge suppressor for panel 2H2. Not illuminated
379357 05/02/2016 398525 2 291 M Repair or replace surge suppressor for panel 2QH2. Not illuminated
379248 05/02/2016 398294 3 190 M Repair or replace surge suppressor for panel 3LSH1. Not illuminated
379139 05/02/2016 398053 4 191 M Repair or replace surge suppressor for panel 4H1, not illuminated
379140 05/02/2016 398055 4 191 M Repair or replace surge suppressor for panel 4LSH1, not illuminated
379403 05/02/2016 398628 4 291 M Repair or replace surge suppressor for panel 4H2. Not illuminated
379401 05/02/2016 398624 4 293 M Repair or replace surge suppressor for panel 4EQH2. Not illuminated
379376 05/02/2016 398569 6 191 M Repair or replace surge suppressor for panel 6LSH1. Not illuminated
379390 05/02/2016 398598 9 191 M Repair or replace surge suppressor for panel 9LSH. Not illuminated
379451 05/02/2016 398736 3 102 O Replace missing ceiling tiles
379134 05/02/2016 398043 10 195 MS Remove and prohibit storing old motors and compressors in chiller room
379132 03/10/2016 398039 00 0000 M Eliminate bees on ceiling of dug outs at softball field
379149 03/10/2016 398079 00 0000 M Eliminate ants in play fields
379298 03/10/2016 398396 00 0000 M Repair irrigation leaks at building 14. See Coach Parks
379445 03/10/2016 398722 00 0000 M Remove old base for bollard that is sitting on ground west of P-2
379389 03/10/2016 398596 00 0000 M Provide chains and locks on gates of fencing around underground propane gas tanks behind building 13
379323 03/10/2016 398453 1 108 M Repair damaged wall finish behind toilet
379326 03/10/2016 398460 1 141 M Refinish wall behind toilet
379324 03/10/2016 398456 1 143A M Secure and caulk sink to wall
379325 03/10/2016 398458 1 143B M Secure and caulk sink to wall
379236 03/10/2016 398267 1 190 M Determine cause of water damaged ceiling tiles and replace tiles
379332 03/10/2016 398469 10 101 M Adjust door to corridor 10-001 to latch properly
379141 03/10/2016 398057 10 101B M Fire alarm panel has 1 trouble and 1 device disabled. Repair these and any other repairs as indicated on report to AHJ
379338 03/10/2016 398483 10 102 M Repair deteriorated wall finish at door to Kitchen
379345 03/10/2016 398500 10 102A M Caulk sink to wall
379346 03/10/2016 398502 10 102A M Refinish wall at toilet
379131 03/10/2016 398036 10 103G M Secure loose exhaust fan grate
379347 03/10/2016 398504 10 104 M Secure loose faucet
379348 03/10/2016 398506 10 104 M Replace missing push button for faucet
379349 03/10/2016 398508 10 104 M Repair inoperable toilet
379350 03/10/2016 398510 10 105 M Repair inoperable toilet
379351 03/10/2016 398512 10 105 M Secure loose toilet seat
379352 03/10/2016 398514 10 105 M Replace missing push button for faucet
379145 03/10/2016 398069 10 190 M Replace leaking over pressure valve on water heater
379143 03/10/2016 398062 10 191 M Provide certification that all student occupied spaces have emergency lights and all are operable. Last certification dated 7/14
379340 03/10/2016 398488 10 191 M Replace missing strike plate on door to 10-192
379138 03/10/2016 398051 10 192 M Replace missing screws for cover of electric panel 10L
379343 03/10/2016 398496 10 194 M Secure loose lock to door
379333 03/10/2016 398475 10 195 M Chain cylinder to wall
379335 03/10/2016 398477 10 195 M Replace missing strike plate for door to 10-194
379133 03/10/2016 398041 10 195 M Repair leaking strainer on chemical pump plumbing
379256 03/10/2016 398313 11 102 M Repair inoperable toilet
379260 03/10/2016 398321 11 105 M Chain cylinders to wall
379258 03/10/2016 398317 12 171 M Replace missing strike plate on door frame
379299 03/10/2016 398400 12 190 M Replace missing screws for cover of electric panel 11LA
379300 03/10/2016 398402 12 190 M Secure loose lock to door and replace missing strike plate on door frame
379235 03/10/2016 398265 12 201 M Determine cause of water damaged ceiling tiles and replace tiles in Football Field pressbox
379313 03/10/2016 398430 2 005 M Secure loose corner guard to wall in corridor at 2-113H
379316 03/10/2016 398435 2 005 M Secure loose spout for drinking fountain in corridor at 2-108E
379310 03/10/2016 398427 2 103 M Secure loose handrail for stairs in control room
379262 03/10/2016 398325 2 108 M Replace missing escutcheons on 7 fire sprinkler heads
379146 03/10/2016 398071 2 108F M Caulk sink to wall
379147 03/10/2016 398073 2 109A M Repair light fixture
379318 03/10/2016 398442 2 110 M Repair or replace damaged paper towel dispenser in handicapped stall
379320 03/10/2016 398447 2 110 M Repair inoperable urinal
379284 03/10/2016 398371 2 112 M Repair door to corridor 2-004 to open and close properly
379321 03/10/2016 398450 2 113D M Replace missing ceiling tiles
379355 03/10/2016 398521 2 290 M Repair leaking air handler 2-4
379450 03/10/2016 398734 3 102 M Repair hole in wall from 3-102C door handle. Provide door stop to prevent further damage
379252 03/10/2016 398304 3 104 M Relocate maximum occupancy sign from corridor to inside of room adjacent to exit
379452 03/10/2016 398738 3 104A M Caulk sink and handicapped sink to wall
379448 03/10/2016 398730 3 108 M Repair fire extinguisher cabinet at entry. Cannot open
379449 03/10/2016 398732 3 108 M Secure loose spouts on drinking fountains at entry
379250 03/10/2016 398300 3 108F M Caulk handicapped toilet to wall
379251 03/10/2016 398302 3 108H M Secure loose faucet
379245 03/10/2016 398287 3 113 M Repair inoperable urinal
379255 03/10/2016 398311 3 114 M Cap open pipes at SW exterior corner of building
379253 03/10/2016 398306 3 116 M Replace missing escutcheon on fire sprinkler head
379247 03/10/2016 398292 3 190 M Panel 3L1-2 breaker 72 tripped. Repair circuit
379249 03/10/2016 398297 3 190 M Label all circuits on electrical panel 3L1-2
379137 03/10/2016 398049 3 206 M Repair broken window blinds
379410 03/10/2016 398646 3 216 M Repair inoperable toilet
379411 03/10/2016 398648 3 290 M Secure loose large grounds to ground bar
379408 03/10/2016 398642 3 291 M Repair or replace surge suppressor for panel 3L2-2. Not illuminated
379406 03/10/2016 398638 3 292 M Install floor drain grate
379136 03/10/2016 398047 4 104 M Remove occupancy sign that reads 109
379453 03/10/2016 398740 4 170 M Provide current inspection tag for elevator
379413 03/10/2016 398653 4 207 M Refinish damaged wall
379412 03/10/2016 398651 4 208 M Refinish wall
379414 03/10/2016 398655 4 215B M Repair or replace button lock on bathroom door. Hard to get door to lock
379405 03/10/2016 398636 4 293 M Outside air intake motor belt is hitting housing. Replace belt
379358 03/10/2016 398527 5 003 M Adjust corridor door to exterior to latch properly
379246 03/10/2016 398290 5 101 M Adjust flow for emergency eye wash
379370 03/10/2016 398553 5 103 M Adjust flow of emergency eye wash - shower
379372 03/10/2016 398557 5 113 M Small piece of ceramic wall tile at sink is missing. Replace tile or grout opening
379373 03/10/2016 398559 5 191 M Secure loose ground to ground bar. Large ground on top with black tape
379379 03/10/2016 398575 5 192 M Install floor drain grate
379417 03/10/2016 398663 5 216B M Repair inoperable toilet
379415 03/10/2016 398659 5 218 M Replace missing ceramic base tile at entry
379400 03/10/2016 398622 5 218 M Repair hole in bathroom vestibule wall at base
379419 03/10/2016 398668 5 290 M Replace floor drain grate
379421 03/10/2016 398672 5 290 M Pad and mark corners of ductwork at door which are lower than 6 feet 8 inches
379418 03/10/2016 398666 5 291 M Replace missing screws for cover of panel 5L2
379446 03/10/2016 398725 6 008 M Secure loose spout for drinking fountain in corridor at 6-214
379384 03/10/2016 398585 6 110 M Repair handicapped toilet that runs too long
379374 03/10/2016 398561 6 111 M Secure loose faucet to handicapped sink
367745 03/10/2016 373279 6 112A M Repair deteriorated wall finish
367746 03/10/2016 373281 6 112B M Repair deteriorated wall finish
379380 03/10/2016 398577 6 114B M Determine cause of water damaged ceiling tiles and replace tiles
379368 03/10/2016 398548 6 192 M Repair or replace 3 surge suppressors. Not illuminated
379369 03/10/2016 398550 6 192 M Secure loose lock to door
379423 03/10/2016 398676 6 202 M Secure loose bracket for projector screen
379424 03/10/2016 398678 6 215A M Repair exhaust fan in bathroom
379426 03/10/2016 398682 6 215A M Repair wall behind toilet. Perhaps cover with aluminum diamond plate
379425 03/10/2016 398680 6 215B M Repair exhaust fan in bathroom
379437 03/10/2016 398705 6 216 M Replace missing escutcheon on fire sprinkler head
379428 03/10/2016 398686 6 292 M Install floor drain grate
379429 03/10/2016 398688 6 292 M Standing water on floor from condensate or leaking air handler. Repair air conditioning system to ensure it operates as designed
379361 03/10/2016 398533 7 116 M Repair or replace damaged toilet paper dispenser
379360 03/10/2016 398531 7 117 M Secure loose handicapped grabrail
379359 03/10/2016 398529 7 119B M Seal crack in corner of shower stall wall
379364 03/10/2016 398539 7 180 M Determine cause of water damaged ceiling tiles and replace tiles. Check for possible fire sprinkler leak
379367 03/10/2016 398546 7 190 M Repair or replace surge suppressor for panel EQH1. Red light is illuminated
379435 03/10/2016 398701 7 205 M Repair electrical outlets. No power. See teacher
379432 03/10/2016 398694 7 205A M Repair exhaust fan in bathroom
379433 03/10/2016 398697 7 205B M Repair exhaust fan in bathroom
379434 03/10/2016 398699 7 206 M Repair electrical outlet on counter top. No power
379436 03/10/2016 398703 7 215 M Repair or replace leaking faucet
379431 03/10/2016 398692 7 216 M Repair inoperable toilet
379430 03/10/2016 398690 7 217 M Replace missing push button for faucet
379438 03/10/2016 398707 7 280 M Replace missing escutcheon on fire sprinkler head
379439 03/10/2016 398709 7 280 M Repair damaged wall at floor sink
379443 03/10/2016 398717 7 292 M Install floor drain grate
367476 03/10/2016 372689 7 292 M Replace rusty areas of AHU EF7-2-3
379385 03/10/2016 398587 8 102 M Adjust door to exterior to latch properly
379392 03/10/2016 398602 8 112 M Secure loose faucet
379387 03/10/2016 398591 9 001 M Adjust corridor door to interior courtyard to latch properly
379395 03/10/2016 398608 9 105 M Repair toilet
379388 03/10/2016 398593 9 107 M Secure loose lock cylinder on door at 9-106
379399 03/10/2016 398619 9 108 M Caulk handicapped sink to wall
379398 03/10/2016 398616 9 109 M Caulk handicapped sink to wall
379396 03/10/2016 398611 9 109 M Replace missing ceramic base tile at entry
379238 03/10/2016 398272 P 6461 M Repair condensate leak for A-C and remove mold and algae from exterior wall
379239 03/10/2016 398274 P 6462 M Repair emergency lighting X 2
379240 03/10/2016 398276 P 6462 M Determine cause of water damaged ceiling tiles and replace tiles
379444 03/10/2016 398720 00 0000 O Sheeted roof sections for houses constructed in building 9 are stored outside. Provide temporary hurricane anchorage for roof assemblies. Roof sections gone
379142 03/10/2016 398059 10 180 O Post sign indicating number of machines allowed to be charged in room or prohibit charging batteries in room
379261 03/10/2016 398323 14 101 O Provide clear access to electrical panel
379243 03/10/2016 398283 3 192 O Provide clear access to electrical panel
379244 03/10/2016 398285 3 192 O Prohibit charging batteries in room
379409 03/10/2016 398644 3 218B O Keep area within 18 inches of fire sprinkler head clear and unobstructed
379377 03/10/2016 398571 5 106 O Uncover window in door. Acceptable for code red situation only
379416 03/10/2016 398661 5 206 O Post sign indicating primary and secondary evacuation routes in contrasting colors
379381 03/10/2016 398579 6 103 O Uncover window in door. Acceptable for code red situation only
379382 03/10/2016 398581 6 105A O Maintain clear access to emergency eye wash - shower
379375 03/10/2016 398567 6 108 O Remove trash from behind washer and dryer
379365 03/10/2016 398541 7 111 O Post sign indicating primary and secondary evacuation routes in contrasting colors
379393 03/10/2016 398604 9 102C O Store corrosive chemicals in corrosive storage cabinet
379394 03/10/2016 398606 9 103 O Prohibit plugging surge protector into surge protector
379329 03/10/2016 398467 10 101 MS Provide current inspection tag for fire extinguisher at NW corner of room
379266 03/10/2016 398332 2 002 MS Adjust Auditorium doors to corridor 2-101 to latch properly
379268 03/10/2016 398337 2 108A MS Adjust stage door to corridor 2-004 to latch properly
379286 03/10/2016 398374 2 113 MS Adjust north door to corridor to latch properly
379263 03/10/2016 398327 2 114 MS Adjust north fire door to interior corridor to latch properly
379242 03/10/2016 398280 3 192 MS Remove storage from mechanical room
379404 03/10/2016 398632 4 208 MS Adjust corridor door to latch properly
379371 03/10/2016 398555 5 104 MS Recharge fire extinguisher
379422 03/10/2016 398674 6 201 MS Provide current inspection tag for fire extinguisher
379363 03/10/2016 398537 7 191 MS Recharge fire extinguisher
379441 03/10/2016 398713 7 291 MS Remove storage from electrical room
379386 03/10/2016 398589 8 108 MS Provide current inspection tag for fire extinguisher in corridor to interior courtyard
379144 03/10/2016 398067 10 190 OS Remove storage from boiler room
379259 03/10/2016 398319 11 101 OS Provide clear access to fire extinguisher and fire alarm pull station
379354 03/10/2016 398519 2 010 OS Prohibit hold open device on fire door in corridor at top of stairs
379283 03/10/2016 398366 2 108 OS Remove and prohibit storage at north Auditorium exit to 2-004 to maintain clear aisle to exit
379454 03/10/2016 398742 2 294 OS Prohibit hold open devices on fire doors. Door to room and door in adjacent corridor
379254 03/10/2016 398308 3 111 OS Remove and prohibit storage at exit to maintain clear aisle to exit
379241 03/10/2016 398278 3 192 OS Remove storage from mechanical room
379407 03/10/2016 398640 3 292 OS Remove and prohibit storing old light tubes in mechanical room
379447 03/10/2016 398727 4 104 OS Remove and prohibit storage at exit
379402 03/10/2016 398626 4 293 OS Remove storage from mechanical room
379378 03/10/2016 398573 5 192 OS Remove storage from mechanical room
379420 03/10/2016 398670 5 290 OS Remove storage from mechanical room
379383 03/10/2016 398583 6 105A OS Provide clear access to fire extinguisher
379427 03/10/2016 398684 6 292 OS Remove storage from mechanical room
379366 03/10/2016 398544 7 190 OS Remove storage from mechanical room
379362 03/10/2016 398535 7 191 OS Remove storage from electrical room
379440 03/10/2016 398711 7 291 OS Remove storage from electrical room
379442 03/10/2016 398715 7 292 OS Remove storage from mechanical room
379391 03/10/2016 398600 8 191 OS Remove storage from mechanical room
367421 03/10/2016 372564 9 107C OS Remove hasp locks from exit doors, interior and exterior
379397 03/10/2016 398613 9 192 OS Remove storage from mechanical room
367380 09/17/2015 372473 00 9699 M Replace missing top rails of fence on south side of bike rack and at driveway adjacent to football field
340978 09/17/2015 314877 10 103B M Provide protective cage around fire sprinkler head in walk-in freezer
340979 09/17/2015 314879 10 103C M Provide protective cage around fire sprinkler head in walk-in cooler
379353 09/17/2015 398516 10 192 M Cover exposed connections on unit DX10-3. NA low voltage at 10 feet above floor
367378 09/17/2015 372469 00 9699 O Repair or remove rotting, deteriorated wood trailer and pieces of wood stored adjacent to storage container at tennis courts
352206 09/17/2015 339368 6 220 O Prohibit plugging surge protector into surge protector
340922 08/11/2015 314762 3 101 CS Provide automatic fire sprinkler coverage for outside kiln room. NA not required per Mark Lodge
341023 02/04/2015 314980 00 0000 C Provide bottom rail on guardrail on raised platform in interior courtyard at 2 inches above floor
330073 01/05/2015 291210 00 0000 M Replace missing gate for retention pond at SW corner of property near softball fields
330094 01/05/2015 291262 00 0000 M Repair damaged concrete on exterior stairs at classroom buildings
367558 01/05/2015 372872 00 0000 M Repair damaged, broken concrete on ramp for exterior stage
367400 01/05/2015 372517 00 8087 M Remove wasp nests at covered walk south of 10-101 and north of 1-101
367379 01/05/2015 372471 00 9599 M Replace missing cover plate at base of light pole south of 11-180
367373 01/05/2015 372458 00 9699 M Replace deteriorated wood cover for in ground box south of baseball dugouts
367374 01/05/2015 372461 00 9699 M Replace rotting, deteriorated areas of wood deck located between baseball and softball dugouts
367375 01/05/2015 372463 00 9699 M Replace missing cover for in ground control box south of softball backstop
367376 01/05/2015 372465 00 9699 M Replace missing base support on bench south of baseball field
367377 01/05/2015 372467 00 9699 M Replace rusty, damaged control box covers located in fenced area between baseball and softball fields
367386 01/05/2015 372487 1 109 M Secure loose cover on light fixture
367385 01/05/2015 372485 1 190 M Determine cause of water damaged ceiling tiles and replace tiles
367401 01/05/2015 372519 10 101 M Repair deteriorated wall finish at vending machine adjacent to 10-102
367403 01/05/2015 372523 10 101 M Adjust door closers on south exit doors to control speed of closing doors
352164 01/05/2015 339273 10 101 M Replace missing signage on west exterior wall indicating room name and number at appropriate height with raised and Braille characters
367382 01/05/2015 372478 10 183 M Replace bulbs in light fixture
367384 01/05/2015 372483 10 184 M Replace missing covers on light fixtures
367405 01/05/2015 372527 10 191 M Remove wasp nest in window louvers
367381 01/05/2015 372475 10 195 M Repair east door to open and close properly
352152 01/05/2015 339246 10 195 M Re-attach gauge to water supply CWP3
352184 01/05/2015 339318 11 102 M Determine cause of damaged ceiling adjacent to south door and make necessary repairs
367368 01/05/2015 372446 11 105 M Repair door to open and close properly
367370 01/05/2015 372451 12 201 M Repair lights in exit signs in pressbox
367371 01/05/2015 372453 12 201 M Determine cause of water damaged ceiling tiles and replace tiles in pressbox
367372 01/05/2015 372455 12 201 M Repair emergency lighting in pressbox
367399 01/05/2015 372515 2 005 M Repair hole in wall at east exterior doors
367390 01/05/2015 372495 2 101 M Repair damaged wall at 2-102, 2-104 and east exterior doors
367394 01/05/2015 372505 2 108E M Secure mirror to wall
367397 01/05/2015 372511 2 108J M Secure band saw to counter top surface
367392 01/05/2015 372499 2 109 M Repair door hardware on north door
367557 01/05/2015 372870 2 111 M Replace missing sink faucet handle
367367 01/05/2015 372444 2 8088 M Replace missing box cover for electrical outlet on exterior wall adjacent to 2-005 corridor doors
341230 01/05/2015 315413 3 0000 M Repair roof on 1 story section of building. Several large bubbles in membrane (Approved as is per manufacturer via B. Pinto January 2015)
367388 01/05/2015 372491 3 101 M Replace missing protective cover for electrical outlet on east exterior wall
367389 01/05/2015 372493 3 101 M Replace missing signage on exterior wall indicating room name and number at appropriate height with raised and Braille characters
367562 01/05/2015 372881 3 101A M Determine cause of water damaged ceiling tiles and replace tiles
367583 01/05/2015 372929 3 102 M Adjust exterior door to close and latch properly
352322 01/05/2015 339624 3 102 M Replace missing signage at exterior door indicating room name and number at appropriate height with raised and Braille characters
367561 01/05/2015 372879 3 103 M Replace broken mirror in dance studio
352312 01/05/2015 339604 3 104 M Replace missing sign indicating maximum occupancy, adjacent to main corridor entrance (Max Occ 193)
367585 01/05/2015 372932 3 104A M Determine cause of water damaged ceiling tiles and replace tiles
367587 01/05/2015 372938 3 104C M Anchor toilet to floor, accessible stall
367594 01/05/2015 372951 3 109 M Adjust door closer on corridor door to control speed of closing door
367595 01/05/2015 372954 3 109 M Repair deteriorated wall finish
367591 01/05/2015 372946 3 191 M Prohibit storage of expelled fire extinguisher
367553 01/05/2015 372860 3 218 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to window
367551 01/05/2015 372858 3 218B M Replace missing cover for light fixture
367555 01/05/2015 372866 3 292 M Replace missing fire sprinkler heads in spare heads box
341225 01/05/2015 315401 4 0000 M Repair roof on 1 story section of building. Several large bubbles in membrane (Approved as is per manufacturer via B. Pinto Jan. 2015)
352197 01/05/2015 339345 4 005 M Replace damaged sign at east door indicating room name and number at appropriate height with raised and Braille characters
367764 01/05/2015 373322 4 101 M Determine cause of water damaged ceiling tiles and replace tiles, at east windows
367765 01/05/2015 373324 4 101 M Repair deteriorated wall finish at east door
367761 01/05/2015 373316 4 102 M Replace missing signage, adjacent to exterior door, indicating room name and number at appropriate height with raised and Braille characters
367763 01/05/2015 373320 4 104 M Replace missing cover for light at exterior door
367766 01/05/2015 373326 4 107 M Determine cause of water damaged ceiling tiles and replace tiles
352305 01/05/2015 339585 4 111 M Replace missing signage at exterior door indicating room name and number at appropriate height with raised and Braille characters
367539 01/05/2015 372823 4 212A M Replace missing cover for light fixture
367483 01/05/2015 372703 4 291 M Repair door to close and latch properly
367482 01/05/2015 372701 4 8088 M Replace missing protective cover for electrical outlet on exterior wall adjacent to 4-212
367760 01/05/2015 373314 4 8088 M Replace missing protective cover for outlet on exterior wall adjacent to 4-192
367762 01/05/2015 373318 4 9599 M Repair damaged concrete walk adjacent to 4-171
341246 01/05/2015 315447 5 0000 M Repair roof on 1 story section of building. Membrane has several large bubbles in it (Approved as is per manufacturer via B. Pinto Jan. 2015)
367601 01/05/2015 372967 5 101 M Repair emergency eye wash
367602 01/05/2015 372969 5 104 M Determine cause of water damaged ceiling tiles and replace tiles
367610 01/05/2015 372984 5 111 M Adjust flow of emergency eye wash
352299 01/05/2015 339573 5 116 M Replace missing signage at exterior door indicating room name and number at appropriate height with raised and Braille characters
367733 01/05/2015 373255 5 191 M Mount fire extinguisher at maximum five feet above floor
367480 01/05/2015 372697 5 203 M Adjust door closer to control speed of closing door
352203 01/05/2015 339360 5 219 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
367478 01/05/2015 372693 5 280 M Replace missing threshold
367479 01/05/2015 372695 5 280 M Repair deteriorated wall finish at sink
367735 01/05/2015 373259 6 101 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to window
367738 01/05/2015 373265 6 103 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to emergency eye wash
367747 01/05/2015 373284 6 105 M Replace missing base on wall adjacent to 6-105B
367740 01/05/2015 373269 6 105 M Adjust door closer on exterior door to control speed of closing door
367741 01/05/2015 373271 6 105 M Remove wasp nests on light fixtures in patio
367742 01/05/2015 373273 6 105 M Replace missing cover for light fixture
367743 01/05/2015 373275 6 105 M Determine cause of water damaged ceiling tiles and replace tiles
367744 01/05/2015 373277 6 105 M Secure loose light cover on fixture adjacent to wet ceiling tile
367739 01/05/2015 373267 6 105A M Determine cause of water damaged ceiling tiles and replace tiles
367737 01/05/2015 373263 6 114 M Adjust door closer on exterior door to control speed of closing door
367759 01/05/2015 373312 7 0000 M Secure loose center handrail on stairs, lower run
367423 01/05/2015 372568 7 008 M Adjust north exterior corridor doors to control speed of closing doors
367753 01/05/2015 373297 7 107 M Adjust door closer to control speed of closing door
367756 01/05/2015 373304 7 111 M Remove grounding plug from electrical outlet adjacent to door
367751 01/05/2015 373293 7 116 M Repair deteriorated wall finish at entrance vestibule
367752 01/05/2015 373295 7 116 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
367749 01/05/2015 373289 7 117 M Repair deteriorated wall finish at entrance vestibule
367754 01/05/2015 373299 7 191 M Repair inoperable air conditioner in electrical room
367426 01/05/2015 372574 7 206 M Adjust door closer to control speed of closing door
367425 01/05/2015 372572 7 210 M Determine cause of water damaged ceiling tiles and replace tiles
367409 01/05/2015 372535 8 102B M Adjust door closer to control speed of closing door
367414 01/05/2015 372549 8 104 M Adjust door closer for door to 8-102 to control speed of closing door
367415 01/05/2015 372551 8 191 M Repair chilled water line at air handler to eliminate water leak
367416 01/05/2015 372553 8 191 M Repair deteriorated wall finish adjacent to hot water heater
367758 01/05/2015 373310 9 102 M Secure trim pieces to bottom of cubicles to prevent tripping hazard
352226 01/05/2015 339410 9 107 M Replace missing signage at corridor door indicating room name and number at appropriate height with raised and Braille characters
367422 01/05/2015 372566 9 107C M Repair doors, both interior and exterior, to close and latch properly
367418 01/05/2015 372558 9 109 M Repair deteriorated wall finish at entrance to boys bathroom
367419 01/05/2015 372560 9 109 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
367420 01/05/2015 372562 9 191 M Repair deteriorated wall finish under fire extinguisher
367597 01/05/2015 372956 P 6461 M Adjust door closer on west door to control speed of closing door
367598 01/05/2015 372960 00 0000 O Prohibit parking on grass area adjacent to portables
367387 01/05/2015 372489 1 129 O Replace bulbs in light fixture
367383 01/05/2015 372480 10 184 O Replace bulbs in light fixture
367369 01/05/2015 372448 11 105 O Provide clear access to electrical panel
367406 01/05/2015 372529 13 101 O Maintain storage room in an orderly manner
367407 01/05/2015 372531 13 101 O Arrange for pick up and proper disposal of used motor oil
367391 01/05/2015 372497 2 101 O Repair bent, damaged trim piece protruding from door frame at east exterior doors
367769 01/05/2015 373332 2 104 O Prohibit plugging drink cooler into surge protector - plug directly into permanent electrical outlet
367767 01/05/2015 373328 2 108B O Prohibit grey multi outlet extension cord or replace with minimum 15A single outlet cord
352125 01/05/2015 339176 2 108C O Replace missing sign indicating primary and secondary evacuation routes
367398 01/05/2015 372513 2 108H O Relocate storage to provide access to this room
367395 01/05/2015 372507 2 108J O Keep sawdust cleaned from surfaces
352126 01/05/2015 339179 2 108J O Replace missing sign indicating primary and secondary evacuation routes
367393 01/05/2015 372502 2 112A O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
352193 01/05/2015 339337 2 113H O Replace missing sign indicating primary and secondary evacuation routes
352323 01/05/2015 339626 3 101 O Prohibit plugging surge protector into surge protector at teachers desk
367581 01/05/2015 372926 3 101A O Remove and prohibit light hanging from ceiling grid
367590 01/05/2015 372944 3 106 O Remove and prohibit air freshener (plug in)
367548 01/05/2015 372846 3 202 O Treat cloth wall coverings with flame retardant and provide certification of treatment or remove and prohibit flammable wall coverings
367484 01/05/2015 372705 4 007 O Remove and prohibit flags hanging in second floor corridor
352239 01/05/2015 339438 5 108 O Replace missing sign indicating primary and secondary evacuation routes
367609 01/05/2015 372971 5 111 O Replace missing sign indicating primary and secondary evacuation routes
367600 01/05/2015 372962 5 115A O Prohibit plugging reach-in freezer into extension cord, plug directly into permanent electrical outlet
367481 01/05/2015 372699 5 219B O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
367748 01/05/2015 373287 6 107 O Replace missing sign indicating primary and secondary evacuation routes
367477 01/05/2015 372691 6 201 O Prohibit plugging surge protector into surge protector at computer adjacent to window
352209 01/05/2015 339374 6 212 O Replace missing sign indicating primary and secondary evacuation routes
341264 01/05/2015 315489 6 213 O Replace missing sign indicating primary and secondary evacuation routes
367750 01/05/2015 373291 7 106 O Prohibit plugging microwave into orange extension cord, plug microwave directly into permanent electrical outlet
367755 01/05/2015 373301 7 111 O Prohibit white 13A extension cord at decorative blue lights or replace with minimum 15A single outlet cord
352228 01/05/2015 339415 7 111 O Prohibit use of multi outlet electrical adaptor (at refrigerator)
367427 01/05/2015 372577 7 203 O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
341269 01/05/2015 315499 7 213 O Replace missing sign indicating primary and secondary evacuation routes
367424 01/05/2015 372570 7 214 O Prohibit plugging surge protectors into surge protectors
352215 01/05/2015 339386 8 102A O Prohibit plugging surge protector into surge protector into surge protector
352160 01/05/2015 339265 8 103 O Prohibit plugging yellow extension cord into surge protector
367410 01/05/2015 372539 8 105 O Replace bulbs in light fixture
367413 01/05/2015 372547 8 108 O Prohibit plugging full sized refrigerator into surge protector - plug directly into permanent electrical outlet
367412 01/05/2015 372545 8 109 O Remove and prohibit eye bolts in double doors. Create work order requesting holes in doors to be repaired
367757 01/05/2015 373308 9 102C O Prohibit light hanging from ceiling grid
352224 01/05/2015 339406 9 107C O Prohibit plugging microwave and refrigerators (2 full size refrigerators) into surge protector - plug directly into permanent electrical outlets
367396 01/05/2015 372509 2 108J C Provide dust collection and exhaust system
352198 01/05/2015 339347 4 201 C Provide signage (x2) indicating roof access, with raised and Braille characters, mounted at appropriate height. Mount one sign on wall at exterior door, mount second sign at 4-201B door
341202 01/05/2015 315349 7 190 C Provide shield for sprinkler line above panel 7-EQH1
367586 01/05/2015 372935 3 104 MS Recharge fire extinguisher located adjacent to 3-104A sign
367734 01/05/2015 373257 5 191 MS Provide current inspection tag for fire extinguisher
367408 01/05/2015 372533 8 001 MS Recharge fire extinguisher in corridor across from to 8-190
352191 01/05/2015 339333 00 0000 OS Prohibit recycle bins and desks in classroom corridors, store in recessed areas of corridors, to maintain clear aisle to exits
367402 01/05/2015 372521 10 101 OS Relocate tables to maintain clear aisle to exit doors
340996 01/05/2015 314919 10 101B OS Prohibit charging batteries in room
367404 01/05/2015 372525 10 101D OS Relocate table to maintain clear aisle to exterior exit
340994 01/05/2015 314915 10 180 OS Prohibit charging batteries in room
367593 01/05/2015 372948 3 110 OS Maintain clear aisle to exit
341149 01/05/2015 315240 3 192 OS Remove storage from mechanical room
367550 01/05/2015 372856 3 201 OS Maintain clear aisle to(exterior) exit
367544 01/05/2015 372842 4 212 OS Maintain clear aisle to exit doors
367736 01/05/2015 373261 6 114 OS Maintain clear aisle to exterior exit door
367411 01/05/2015 372542 8 109 OS Remove hasp lock from corridor exit door
367417 01/05/2015 372555 8 191 OS Remove storage from mechanical room
340987 09/15/2014 314900 1 191 M 2 concrete beams were notched where they attach to larger concrete beam. Contact Building Department for necessary repairs (NA inspected and accepted by A. Morse Jan. 2015)
352219 09/15/2014 339395 8 108 O Prohibit use of orange multi outlet extension cord at wheel allignment machine or replace with minimum 15A single outlet cord
341022 09/15/2014 314978 00 0000 C Provide balusters on guardrail at raised platform in interior courtyard at 4 inches apart (NA per T. Hogarth Sept. 2014)
340934 09/12/2014 314785 00 0000 M Provide hurricane anchors for containers at tennis court and building 11
352167 09/12/2014 339280 00 0000 M Provide current inspection tags for elevators (including pressbox and theater control booth)
352181 09/12/2014 339312 1 110 M Secure loose water faucet for sink
352150 09/12/2014 339240 10 194 M Replace rusty bracket for ladder at cooling tower adjacent to 10-195 door
352185 09/12/2014 339321 11 102 M Repair or replace damaged door handle at north door
329974 09/12/2014 290986 12 190 M Repair uneven concrete floor
352303 09/12/2014 339581 4 0000 M Secure loose center handrail on lower run of stairs
352173 09/12/2014 339294 6 192 M Mount fire extinguisher at maximum five feet above floor
352321 09/12/2014 339622 3 102 O Prohibit covering sign for 3-102B, sign needs to be visible
352318 09/12/2014 339616 3 102 O Remove and prohibit excessive flammable decorations (papers on walls and hanging from ceiling) coverage area is limited to 50 percent of each wall
352196 09/12/2014 339343 3 201 O Prohibit plugging surge protector into surge protector at teachers desk
352201 09/12/2014 339356 4 211 O Provide certification that brown curtains and green wall covering have been treated with flame retardant or prohibit curtains and wall covering
352294 09/12/2014 339563 5 112 O Prohibit plugging microwave into media cart - plug directly into permanent electrical outlet
352208 09/12/2014 339372 6 202 O Remove and prohibit (orange) plastic sheet on bulletin board, cloth or paper is permitted
352171 09/12/2014 339290 7 106 OS Relocate bookshelf at corridor door to maintain clear aisle to exit
352188 02/18/2014 339327 00 0000 M Replace missing protective cover for electrical outlet and missing cover for junction box on southside of baseball dugout
340991 02/18/2014 314908 1 006 M Repair loose door handle on corridor door adjacent to 1-143. Handle comes off when pulled
352149 02/18/2014 339238 1 101B M Make repairs as noted on fire alarm report
340989 02/18/2014 314904 1 135 M Repair damaged wall behind toilet
352165 02/18/2014 339275 10 101 M Replace missing protective cover for electrical outlet on west exterior wall adjacent to missing sign
352166 02/18/2014 339278 10 102 M Provide cover on exposed electrical junction box on wall with ocean scene
352146 02/18/2014 339231 10 182 M Determine cause of water damaged ceiling tiles and replace tiles
352151 02/18/2014 339244 10 195 M Verify that chiller units (3) without anchor bolts are acceptable or provide anchor bolts (acceptable without bolts unless support legs are splayed per T. Hogarth Jan. 2014)
352153 02/18/2014 339248 10 195 M Provide cover on exposed electrical junction box on east wall adjacent to 10-194 door
352163 02/18/2014 339271 10 8087 M Repair raised area of (covered) concrete walk to prevent tripping hazard, at intersection from buildings 9 and 10 adjacent to Adult and Community Education Sign
352182 02/18/2014 339314 12 101 M Determine cause of water damaged ceiling tiles and replace tiles
352156 02/18/2014 339256 13 101 M Repair light fixture, lights do not turn on
352113 02/18/2014 339149 2 101 M Repair east exterior doors to close and latch properly
352114 02/18/2014 339152 2 101 M Replace missing cover on light fixture adjacent to east exterior doors
352127 02/18/2014 339182 2 108 M Adjust door closer on SE exterior door to control speed of closing door (too fast)
352122 02/18/2014 339172 2 110 M Replace missing soap dispenser
352120 02/18/2014 339166 2 114 M Repair damaged exit sign at exterior door
352121 02/18/2014 339169 2 114 M Repair holes in south wall above top row of bleachers
352136 02/18/2014 339200 2 180 M Repair leaking hot water heater
352118 02/18/2014 339162 2 290 M Repair air handler (AHU 2-4) to eliminate water leak
352195 02/18/2014 339341 3 0000 M Repair damaged concrete on east stair adjacent to handrail, lower run. Damaged concrete and nosing are raised creating a tripping hazard
352320 02/18/2014 339620 3 102B M Determine cause of water damaged ceiling tiles and replace tiles
352319 02/18/2014 339618 3 102C M Replace missing ceiling tiles
352324 02/18/2014 339629 3 103 M Verify that mirrors are tempered or have safety backing or provide safety glazing for mirrors
352313 02/18/2014 339606 3 104 M Repair corridor door to close and latch properly
352316 02/18/2014 339612 3 104F M Repair exterior door to close and latch properly
352310 02/18/2014 339599 3 108 M Repair exit sign at exterior door
352311 02/18/2014 339601 3 108 M Repair damaged bench
352306 02/18/2014 339587 3 109 M Repair deteriorated wall finish, holes in walls
352309 02/18/2014 339593 3 111 M Replace missing doorstop in corridor
352187 02/18/2014 339325 3 111 M Replace missing signage at exterior door indicating room name and number at appropriate height with raised and Braille characters
352180 02/18/2014 339310 3 192 M Replace missing protective cover for electrical outlet on exterior wall of 3-192
352190 02/18/2014 339331 4 101 M Repair SE exterior door to close and latch properly
352300 02/18/2014 339575 4 102 M Adjust door closer on exterior to control speed of closing door (too fast)
352301 02/18/2014 339577 4 102 M Determine cause of water damaged ceiling tiles and replace tiles
352304 02/18/2014 339583 4 102B M Replace missing cover for electrical outlet on exterior wall of 4-102B
352178 02/18/2014 339306 4 104 M Replace missing signage at exterior door indicating room name and number at appropriate height with raised and Braille characters
352176 02/18/2014 339300 4 191 M Repair door to close and latch properly
352177 02/18/2014 339304 4 192 M Repair air handler to eliminate water leak
352199 02/18/2014 339352 4 204 M Replace missing base on wall below window
341238 02/18/2014 315431 4 218 M Repair faucet missing push button
352200 02/18/2014 339354 4 290 M Replace missing electrical outlet cover
352295 02/18/2014 339565 5 103 M Determine cause of water damaged ceiling tiles and replace tiles
352297 02/18/2014 339569 5 115 M Determine cause of water damaged ceiling tiles and replace tiles
352175 02/18/2014 339298 5 192 M Repair door to close and latch properly
352204 02/18/2014 339364 5 218 M Replace missing soap dispenser in accessible stall
352237 02/18/2014 339433 6 103 M Repair loose handle for emergency eye wash
352235 02/18/2014 339429 6 106 M Adjust door closers on exterior doors to control speed of closing doors (too fast)
352233 02/18/2014 339425 6 107 M Adjust door closer to control speed of closing door (too fast)
352234 02/18/2014 339427 6 111 M Replace missing soap dispenser
352238 02/18/2014 339435 6 113 M Determine cause of water damaged ceiling tiles and replace tiles
352207 02/18/2014 339370 6 201 M Repair exterior door to close and latch properly
352231 02/18/2014 339421 7 103 M Repair door to close and latch properly
352232 02/18/2014 339423 7 103 M Replace missing thermostat cover
330128 02/18/2014 291330 7 191 M Repair inoperable air conditioner
352214 02/18/2014 339384 7 208 M Adjust door closer to control speed of closing door (too fast)
341270 02/18/2014 315501 7 291 M Repair inoperable DX air conditioning unit
352158 02/18/2014 339260 8 101 M Adjust door closer to control speed of closing door
352159 02/18/2014 339262 8 102 M Replace missing door handle on corridor door
352162 02/18/2014 339269 9 001 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to 9-106
352155 02/18/2014 339254 9 107C M Replace missing protective cover for electrical outlet on north exterior wall of 9-107C
352314 02/18/2014 339608 P 6461 M Repair emergency lighting
352315 02/18/2014 339610 P 6462 M Determine cause of water damaged ceiling tiles and replace tiles
352325 02/18/2014 339631 1 121 O Remove and prohibit air freshener
352327 02/18/2014 339635 1 124 O No access was available to these rooms, 1-124 and 1-126. Please provide access to these rooms during the report review meeting
352329 02/18/2014 339639 1 127 O Prohibit plugging freezer into extension cord - plug directly into permanent electrical outlet
352123 02/18/2014 339174 2 108B O Prohibit grey multi outlet extension cord or replace with minimum 15A cord
352194 02/18/2014 339339 2 109A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
352192 02/18/2014 339335 2 113B O Prohibit use of red plastic table covering, replace with cloth or paper
352202 02/18/2014 339358 4 212 O Remove and prohibit curtain covering window in door
352240 02/18/2014 339440 5 111 O Remove and prohibit air freshener
352241 02/18/2014 339442 5 111 O Replace missing sign indicating primary and secondary evacuation routes
352230 02/18/2014 339419 7 106 O Prohibit plugging microwave into orange multi outlet extension cord, plug directly into permanenet electrical outlet
352229 02/18/2014 339417 7 109 O Remove and prohibit air freshener
352169 02/18/2014 339286 7 180 O Keep area within 18 inches of fire sprinkler head clear and unobstructed
352212 02/18/2014 339380 7 218 O Prohibit white 13A extension cord at tea kettle or replace with minimum 15A cord
352216 02/18/2014 339389 8 102 O Prohibit charging batteries in room or provide certification that room has been evaluated and approved for battery charging
352157 02/18/2014 339258 8 104 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
352218 02/18/2014 339393 8 108A O Keep floor clean and free of oil
352222 02/18/2014 339401 9 103A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
352220 02/18/2014 339397 8 108 C Provide additional light switches adjacent to corridor door, only switches are adjacent to exterior door
340986 02/18/2014 314897 00 0000 MS Provide current quarterly inspection tags for fire sprinkler systems
352147 02/18/2014 339233 10 180 MS Recharge fire extinguisher adjacent to exterior door
352183 02/18/2014 339316 12 190 MS Recharge fire extinguisher
352189 02/18/2014 339329 3 001 MS Replace missing fire extinguisher in corridor adjacent to 3-115
352317 02/18/2014 339614 3 104 MS Recharge fire extinguisher adjacent to 3-104A
352174 02/18/2014 339296 5 192 MS Recharge fire extinguisher
352236 02/18/2014 339431 6 105 MS Recharge fire extinguisher at exterior door
352225 02/18/2014 339408 9 107C MS Remove and prohibit hasp lock on exit door
352326 02/18/2014 339633 1 125 OS Remove and prohibit use of candles
352328 02/18/2014 339637 1 132 OS Remove and prohibit use of candles
352186 02/18/2014 339323 14 102 OS Prohibit storage of flammable materials (boxes of field marker paint) store in flammable storage cabinet or room
352117 02/18/2014 339154 2 101 OS Prohibit storage (racks of chairs) adjacent to 2-114 corridor doors to maintain clear aisle to exits
352307 02/18/2014 339589 3 109 OS Maintain clear aisle to corridor exit
352308 02/18/2014 339591 3 110 OS Maintain clear aisle to corridor exit
352302 02/18/2014 339579 4 102B OS Relocate storage to maintain clear aisle to both exit doors
352296 02/18/2014 339567 5 102 OS Remove and prohibit use of candles
352298 02/18/2014 339571 5 116 OS Remove and prohibit use of candles
352205 02/18/2014 339366 5 211 OS Maintain clear aisle to corridor exit
352172 02/18/2014 339292 7 106 OS Prohibit hold open device on classroom door
352170 02/18/2014 339288 7 109 OS Prohibit hold open device on classroom door
352168 02/18/2014 339284 7 115 OS Prohibit hold open device on classroom door
352213 02/18/2014 339382 7 208 OS Relocate table to maintain clear aisle to corridor exit
352161 02/18/2014 339267 8 107 OS Prohibit hold open device on classroom door
352217 02/18/2014 339391 8 108A OS Prohibit storage of used oil, arrange pick up and removal on regular basis
352221 02/18/2014 339399 9 102 OS Prohibit storage adjacent to exterior door to maintain clear aisle to exit
352223 02/18/2014 339404 9 107 OS Prohibit storage of (flammable materials) boxes of liquid nails, store in flammable storage cabinet or room
352227 02/18/2014 339413 9 107 OS Provide clear access to fire extinguisher adjacent to grinder at exterior door
341211 09/05/2013 315368 00 0000 M Repair or replace extremely rusted lower bracket for football field scoreboard
341003 09/05/2013 314933 00 0000 M Seal open joint between tilt up panels in interior courtyard at 2nd floor between buildings 6 and 7
329968 09/05/2013 290971 14 101 M Provide signage indicating room name and number at appropriate height with raised and Braille characters
329969 09/05/2013 290973 14 102 M Provide signage indicating room name and number at appropriate height with raised and Braille characters
341219 09/05/2013 315387 2 109 M Replace missing signage indicating room name and number
341217 09/05/2013 315383 2 192 M Replace missing signage indicating room name and number
341148 09/05/2013 315238 3 112 M Pipes rattle when toilet is flushed. Secure pipes or provide hammer arrestor
330104 09/05/2013 291282 3 201 M Replace missing signage for exterior door indicating room name and number at appropriate height with raised and Braille characters
330103 09/05/2013 291280 3 211 M Replace missing signage for exterior door indicating room name and number at appropriate height with raised and Braille characters
341223 09/05/2013 315397 4 206 M Repair or replace damaged projection screen that will not stay down
330102 09/05/2013 291278 5 008 M Replace missing signage for exterior door indicating room name and number at appropriate height with raised and Braille characters
341169 09/05/2013 315281 5 106 M Repair or replace video screen. Will not stay down
341157 09/05/2013 315257 5 191 M Repair DX unit, not running and room very hot
330099 09/05/2013 291272 5 291 M Repair broken A/C unit in electrical room, control panel for A/C unit is missing
330084 09/05/2013 291239 9 107 M Replace missing sign at north exterior door at appropriate height with raised and Braille characters
340974 09/05/2013 314869 00 0 O No access was available to 12-170 (elevator). Please provide access to this room during the report review meeting
341263 09/05/2013 315487 00 0000 O Indicate primary and secondary routes on evacuation maps in all classrooms (will cite rooms individually)
341013 09/05/2013 314957 3 202 O Remove and prohibit hanging paper or plastic from ceiling
341172 09/05/2013 315287 5 107 O Eliminate multiple outlet adapter plugged into electric outlet. Use surge suppressor
341198 09/05/2013 315341 7 109 O Post sign indicating evacuation routes
341171 09/05/2013 315285 5 107 OS Maintain 3 foot clear aisle to rear exit
341271 09/05/2013 315503 7 280 OS Prohibit charging batteries in room
341216 03/07/2013 315379 00 0000 M Install cap on fire department standpipe connection east of 2-192
341167 03/07/2013 315277 00 0000 M Provide signage indicating emergency gas disconnect valve inside on front of teachers station for rooms 5-101, 5-102, 5-103, 5-107, 5-108, 5-109, 5-116, 6-105 and 6-106
340972 03/07/2013 314865 00 0000 M Provide hurricane anchors for shed south of home bleachers
340973 03/07/2013 314867 00 0000 M Exterminate ants throughout campus
340920 03/07/2013 314755 00 0000 M Provide chain and lock on gate of fencing around gas valve west of building 5
340939 03/07/2013 314797 1 108 M Replace missing push button on faucet
340990 03/07/2013 314906 1 190 M Determine cause of water damaged ceiling tiles and replace tiles
340981 03/07/2013 314883 10 102A M Repair damaged wall behind toilet
340980 03/07/2013 314881 10 103 M Repair inoperable food warming box. See kitchen manager
340997 03/07/2013 314921 10 104 M Caulk toilets to wall
340998 03/07/2013 314923 10 105 M Caulk toilets to wall
340988 03/07/2013 314902 10 180 M Repair damaged wall at floor sink
340977 03/07/2013 314875 10 182A M Repair door to open and close properly. Door rubs on frame
340995 03/07/2013 314917 10 190 M Replace missing screw that holds lockset to door
340918 03/07/2013 314747 10 191 M Repair emergency generator. Leaking oil and water
340937 03/07/2013 314793 10 193 M Repair leaking air handler 10-2
340992 03/07/2013 314910 10 194 M Remove ficus tree growing in frieze band on exterior wall at NE corner
340993 03/07/2013 314912 10 195 M Repair rusted door frame for east door
341221 03/07/2013 315392 11 102 M Secure loose faucet to sink
341212 03/07/2013 315370 11 104 M Secure loose faucet for sink 2 and handicapped sink
341213 03/07/2013 315373 11 104 M Repair sink faucet that runs continually
340982 03/07/2013 314886 2 110 M Caulk toilets to wall
340983 03/07/2013 314888 2 111 M Caulk toilets to wall
340985 03/07/2013 314895 2 112 M Relocate fire extinguisher to be adjacent to exit
341014 03/07/2013 314959 3 0000 M Provide chain and lock on gate of fencing around electrical equipment adjacent to 3-114
341015 03/07/2013 314961 3 0000 M Provide chain and lock on gate of fencing around gas valve adjacent to 3-193
341004 03/07/2013 314936 3 101 M Clean out clay traps for all sinks
341005 03/07/2013 314938 3 101 M Replace GFCI outlet at triple sink that will not trip
341006 03/07/2013 314940 3 101 M Adjust rear door to latch properly
330156 03/07/2013 291387 3 101 M Provide signage indicating purge fan (adjacent to corridor door)
341007 03/07/2013 314944 3 101A M Anchor single shelf to wall
341011 03/07/2013 314952 3 104F M Caulk toilets to wall
341117 03/07/2013 315174 3 105 M Secure loose faucet to sink
341008 03/07/2013 314946 3 108 M Replace missing ceramic floor tile in corridor to 3-108D
341009 03/07/2013 314948 3 108F M Repair high urinal to flush
341152 03/07/2013 315247 3 108F M Replace missing clean-out cover in handicapped stall
341010 03/07/2013 314950 3 108H M Secure loose faucet
341121 03/07/2013 315184 3 192 M Complete concrete floor around floor drain
341120 03/07/2013 315179 3 193 M Complete concrete floor around floor drain
341229 03/07/2013 315409 3 214B M Secure loose faucet to sink
341227 03/07/2013 315405 3 216 M Secure loose faucet to sink
341226 03/07/2013 315403 3 217 M Replace missing ceramic base tile along wall
341231 03/07/2013 315415 3 292 M Replace missing floor drain grate
341234 03/07/2013 315423 4 005 M Repair hole in corridor wall adjacent to 4-220
341026 03/07/2013 314986 4 104 M Repair damaged and sharp weatherstripping on door to interior courtyard
341027 03/07/2013 314988 4 104A M Secure loose faucet to sink
341028 03/07/2013 314989 4 104A M Seal wall at sink, make repair impervious
341024 03/07/2013 314982 4 192 M Seal access door in air handler, large air leak
341236 03/07/2013 315427 4 201A M Secure sink to wall
341224 03/07/2013 315399 4 206 M Secure loose cabinet door, see teacher
341222 03/07/2013 315395 4 212 M Remove pencil sharpener without cover adjacent to door
341239 03/07/2013 315433 4 218 M Caulk toilets to wall
341240 03/07/2013 315435 4 292 M Cover opening in panel 4EQH2
341266 03/07/2013 315493 5 0000 M Secure loose guardrail on intermediate landing for stairs adjacent to 5-003
341241 03/07/2013 315437 5 006 M Repair hole in corridor wall between 5-218 and 5-219
341178 03/07/2013 315300 5 101 M Secure several loose outlet boxes and replace several GFCI outlets that will not trip on table tops
341187 03/07/2013 315319 5 102 M Replace GFCI outlet on top of table 2 that will not trip
341188 03/07/2013 315321 5 103 M Replace GFCI outlet on top of table 1 that will not trip
341168 03/07/2013 315279 5 106 M Replace GFCI outlet on side of last table
341166 03/07/2013 315275 5 106 M Secure loose sockets for ring stands on lab tables. See teacher
341170 03/07/2013 315283 5 107 M Adjust flow of emergency eye wash. Low flow
341173 03/07/2013 315289 5 107 M Secure loose electrical outlet to table top
341175 03/07/2013 315294 5 108 M Replace GFCI outlet on top of table next to north most table
341176 03/07/2013 315296 5 108 M Secure loose outlet box and replace 1 GFCI outlet that will not trip on south table top
341153 03/07/2013 315249 5 108A M Repair door to 5-109 to open and close properly. Door rubs on frame
341154 03/07/2013 315251 5 109 M Secure loose electrical outlet adjacent to south table
341155 03/07/2013 315253 5 109 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to door to courtyard. Check sprinkler system for possible leak
341156 03/07/2013 315255 5 110 M Secure loose electrical outlet on north table top
341191 03/07/2013 315327 5 111 M Replace GFCI outlet on top of north table that will not trip
341185 03/07/2013 315314 5 113 M Caulk toilets to wall
341186 03/07/2013 315317 5 114 M Replace broken ceramic base tile adjacent to entry
341184 03/07/2013 315312 5 114 M Caulk toilets to wall
341183 03/07/2013 315310 5 115 M Determine cause of water damaged ceiling tiles and replace tiles
341182 03/07/2013 315308 5 115A M Replace GFCI outlet left of 1st sink that will not trip
341179 03/07/2013 315302 5 116 M Secure several loose outlet boxes to table tops
341180 03/07/2013 315304 5 116 M Replace GFCI outlet at end of table 2 and top of table 3 that will not trip
341181 03/07/2013 315306 5 116 M Adjust door to exterior to latch properly
341000 03/07/2013 314927 5 116 M Adjust flow of emergency eye wash. Hits ceiling
341190 03/07/2013 315325 5 180 M Repair damaged wall finish at floor sink. Provide ceramic tile or stainless steel for back splash to prevent further damage
341243 03/07/2013 315441 5 201 M Determine cause of water damaged ceiling tiles and replace tiles
341244 03/07/2013 315443 5 201 M Replace door lock. Laundry room has bathroom lock on it and cannot be secured. Provide keyed lock
341245 03/07/2013 315445 5 207 M Replace missing projection screen bracket
341249 03/07/2013 315453 5 211A M Replace missing light switch plate
341242 03/07/2013 315439 5 217 M Repair 1st toilet to flush and caulk it to wall
341163 03/07/2013 315269 6 002 M Determine cause of water damaged ceiling tiles in corridor and replace tiles adjacent to 6-112
341159 03/07/2013 315261 6 101A M Adjust door to courtyard to latch properly
341161 03/07/2013 315265 6 102 M Adjust door to latch properly
341162 03/07/2013 315267 6 103A M Adjust door to latch properly
341001 03/07/2013 314929 6 105 M Replace GFCI outlet on NW table at west end that will not trip
341164 03/07/2013 315271 6 110 M Caulk toilet to wall
341165 03/07/2013 315273 6 111 M Caulk toilet to wall
341251 03/07/2013 315457 6 217 M Repair inoperable handicapped toilet
341250 03/07/2013 315455 6 218 M Replace missing ceramic base tile along wall at entry
341262 03/07/2013 315485 6 280 M Replace missing escutcheon on fire sprinkler head
341197 03/07/2013 315339 7 106A M Repair deteriorated wall finish behind tiolet
341196 03/07/2013 315337 7 116 M Caulk toilets to wall
341194 03/07/2013 315333 7 117 M Repair inoperable toilet and urinal
341195 03/07/2013 315335 7 117 M Caulk toilets to wall
341200 03/07/2013 315345 7 192 M Secure loose ground to ground bar, large wire
341277 03/07/2013 315516 7 216 M Caulk toilets to wall
341276 03/07/2013 315514 7 217 M Caulk toilets to wall
330115 03/07/2013 291304 7 290 M Provide signage at corridor door indicating room name and number at appropriate height with raised and Braille characters
341205 03/07/2013 315355 8 102 M Secure loose electrical outlet for refrigerator adjacent to 8-102A
341019 03/07/2013 314972 8 113 M Secure loose toilet seat
341018 03/07/2013 314970 9 102 M Repair sticky latch on panic hardware to interior corridor
341036 03/07/2013 315009 9 103 M Relocate fire extinguisher at center of room to rear exit
341033 03/07/2013 315001 9 103 M Adjust door to interior corridor to latch properly
341032 03/07/2013 314999 9 107 M Secure cord restraints on Eaton box on wall adjacent to 9-107H
341016 03/07/2013 314964 9 107 M Repair damaged floor electrical outlet. See teacher.
341017 03/07/2013 314967 9 107 M Repair damaged ceiling drop cord. See teacher
341206 03/07/2013 315357 9 107 M Adjust south door to interior courtyard to latch properly
341031 03/07/2013 314997 9 107J M Seal opening around electrical outlet box in north wall
341207 03/07/2013 315359 9 107M M Repair toilet that runs continually. I shut it off.
340999 03/07/2013 314925 00 0000 O Prohibit custodian from blocking open doors with a wedge or stick at the top, hinge side of the door between the door and frame. This will damage the door, frame and hinges
340975 03/07/2013 314871 00 0000 O Remove and prohibit combustible storage under bleachers
341215 03/07/2013 315377 2 190 O Remove glue pad with dead mouse on it
341228 03/07/2013 315407 3 0000 O Remove and prohibit hanging flammable decorations from ceiling on 2nd floor interior corridor
341150 03/07/2013 315242 3 192 O Provide clear access to electrical panel
341233 03/07/2013 315421 4 0000 O Remove and prohibit hanging flammable decorations from 2nd floor corridor ceiling
341235 03/07/2013 315425 4 201A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
341237 03/07/2013 315429 4 203 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
341174 03/07/2013 315292 5 003 O Remove props from and remove and prohibit hanging decorations from ceiling in corridor
341012 03/07/2013 314955 6 108 O Remove rags behind dryer
341177 03/07/2013 315298 6 108A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
341160 03/07/2013 315263 6 114A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
341201 03/07/2013 315347 7 003 O Remove and prohibit hanging flammable decorations from corridor ceiling
341199 03/07/2013 315343 7 110A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
341002 03/07/2013 314931 7 114 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
341193 03/07/2013 315331 7 118 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
341192 03/07/2013 315329 7 119B O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
341020 03/07/2013 314974 8 113 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
341021 03/07/2013 314976 8 114 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
341210 03/07/2013 315365 9 104 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
341209 03/07/2013 315363 9 105 O Keep floor drain and all fixture drains filled with water. Room used for storage
341208 03/07/2013 315361 9 107M O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
340976 03/07/2013 314873 10 103 MS Remove type K fire extinguisher adjacent to door to exterior and replace with ABC fire extinguisher
341218 03/07/2013 315385 2 192 MS Provide current inspection tag for fire sprinkler system. Tag marked as quarterly, provide annual tag
321257 03/07/2013 271406 2 192 MS Make repairs listed on Fire Pump report dated 5/17/10, report says transfer switch not working
341151 03/07/2013 315245 3 192 MS Provide current inspection tag for fire sprinkler system. Tag marked as quarterly, provide annual tag
341232 03/07/2013 315419 3 292 MS Provide current inspection tag for fire sprinkler system. Tag marked as quarterly, provide annual tag
341189 03/07/2013 315323 5 104 MS Recharge fire extinguisher
341158 03/07/2013 315259 5 192 MS Provide current inspection tag for fire sprinkler system. Tag marked as quarterly, provide annual tag
341248 03/07/2013 315451 6 292 MS Provide current inspection tag for fire sprinkler system. Tag marked as quarterly, provide annual tag
341204 03/07/2013 315353 7 190 MS Provide current inspection tag for fire sprinkler system. Tag marked as quarterly, provide annual tag
341267 03/07/2013 315495 7 292 MS Provide current inspection tag for fire sprinkler system. Tag is marked as quarterly, provide annual tag
340926 03/07/2013 314770 8 191 MS Provide current inspection tag for fire sprinkler system. Tag marked as quarterly, provide annual tag.
341220 03/07/2013 315390 11 105 OS Prohibit storage of flammable spray paint. Store in flammable storage cabinet
341029 03/07/2013 314991 13 101 OS Provide clear access to fire extinguisher
340984 03/07/2013 314891 14 102 OS Prohibit storage of flammable spray paint. Store in flammable storage room or flammable storage cabinet
341214 03/07/2013 315375 2 108J OS Keep flammable cabinet closed and latched
341025 03/07/2013 314984 4 102B OS Maintain clear aisle to exit to interior courtyard
341247 03/07/2013 315449 5 210 OS Prohibit hold open device on corridor door
341265 03/07/2013 315491 6 292 OS Remove storage from mechanical room
341268 03/07/2013 315497 7 008 OS Remove and prohibit storage in corridor
341203 03/07/2013 315351 7 190 OS Remove storage from mechanical room
341275 03/07/2013 315512 7 201 OS Prohibit hold open devices on corridor door
341274 03/07/2013 315510 7 204 OS Prohibit hold open devices on corridor door
341273 03/07/2013 315508 7 206 OS Prohibit hold open devices on corridor door
341272 03/07/2013 315506 7 210 OS Prohibit hold open devices on corridor door
341278 03/07/2013 315518 7 292 OS Remove storage from mechanical room
341034 03/07/2013 315003 9 103 OS Maintain clear aisle to rear exit
341035 03/07/2013 315005 9 103 OS Provide clear access to fire extinguisher at center of room
341030 03/07/2013 314993 9 192 OS Remove storage from mechanical room
330151 10/05/2012 291377 4 102B C Provide records that CCTV studio rigging has been inspected and conforms to required safety standards
330070 09/28/2012 291202 00 0000 M Turn barbs down on Fire Department Access gate adjacent to bike racks
330091 09/28/2012 291255 00 0000 M Repair bent, damaged chain link fencing for retention pond near greenhouse, bottom of fence has been lifted and will allow animal access to school property
291935 09/28/2012 207692 2 108 M Replace missing foldaway desktops on chairs in auditorium. Brackets for missing desks protrude into aisles
330037 09/28/2012 291122 2 108A M Provide dated flame resistance label on stage curtain
330150 09/28/2012 291375 4 102B M Provide dated flame resistance label on CCTV studio curtain
330068 09/28/2012 291196 00 0000 O Clean mold from bleachers at softball and baseball fields
329970 09/28/2012 290977 14 101 OS Prohibit storage of flammable materials (spray paint)
329966 03/26/2012 290967 00 0000 M Install cap on fire department standpipe connection adjacent to 2-192
330064 03/26/2012 291185 00 0000 M Secure loose electrical outlet box under front of football bleachers near track. Box and conduit are laying on the ground
330065 03/26/2012 291187 00 0000 M Secure loose grounding wire on scoreboard at football field
330095 03/26/2012 291264 00 0000 M Repair damaged concrete ramps from exterior stage in courtyard
330082 03/26/2012 291233 00 0000 M Repair damaged concrete area adjacent to covered walk at busloop
330109 03/26/2012 291292 00 0000 M Remove one latch from emergency rescue windows, 3-204, 3-208, 4-205, 4-209, 5-208, 5-204, 6-207, 7-209, 7-205
330092 03/26/2012 291258 10 193 M Provide covers on exposed electrical junction boxes on SW and North walls
329973 03/26/2012 290984 11 102 M Repair deteriorated ceiling finish adjacent to south exit door
329976 03/26/2012 290990 11 105 M Fill void in panel 11H
330063 03/26/2012 291183 12 170 M Provide current inspection tag for elevator
330090 03/26/2012 291253 13 101 M Mount fire extinguisher at maximum five feet above floor
330067 03/26/2012 291194 14 9599 M Repair damaged chain link fencing at Bldg. 14 adjacent to ticket booth
330031 03/26/2012 291110 2 101 M Repair deteriorated wall finish and loose base on wall at east exterior door
330074 03/26/2012 291217 2 101 M Repair hole in wall adjacent to 2-106
330035 03/26/2012 291117 2 108 M Determine cause of water leak on SE side of auditorium, the carpet and wall are both wet
330032 03/26/2012 291112 2 114A M Repair door to open and close properly
330033 03/26/2012 291114 2 114A M Repair deteriorated wall finish
330050 03/26/2012 291156 3 104 M Repair leaking drinking fountain adjacent to corridor door
330049 03/26/2012 291154 3 111 M Replace missing ceiling tiles
330052 03/26/2012 291161 3 114 M Secure out of place ceiling tile
330054 03/26/2012 291165 4 104A M Lock on door not functioning properly, see Media Specialist for details
321239 03/26/2012 271371 4 217 M Repair faucet in accessible stall, no water
330096 03/26/2012 291266 4 291 M Fill voids in panel 4H2
330134 03/26/2012 291342 5 101 M Secure loose electrical/GFCI outlet at counter top work station closest to fire extinguisher
330138 03/26/2012 291350 5 102 M Adjust flow of emergency eye wash
330139 03/26/2012 291352 5 103 M Replace missing cover for GFCI outlet at counter top work station closest to corridor door
330140 03/26/2012 291354 5 103 M Adjust flow of emergency eye wash
330141 03/26/2012 291356 5 104 M Secure loose GFCI outlets at counter top work stations
330142 03/26/2012 291358 5 107 M Secure loose GFCI outlets at counter top work stations
330143 03/26/2012 291360 5 108 M Repair clogged drain at emergency eye wash
330144 03/26/2012 291362 5 108 M Secure loose GFCI outlets at counter top work stations
330146 03/26/2012 291366 5 110 M Secure loose GFCI outlets at counter top work stations
330147 03/26/2012 291368 5 111 M Adjust flow of emergency eye wash
330133 03/26/2012 291340 5 116 M Repair emergency shut off button
330113 03/26/2012 291300 6 202 M Repair door to close and latch properly
330114 03/26/2012 291302 6 205 M Repair door to close and latch properly
330110 03/26/2012 291294 6 215A M Replace missing escutcheon on fire sprinkler head
330101 03/26/2012 291276 6 8088 M Replace missing protective cover for electrical outlet in second floor covered walk adjacent to 6-008 exterior wall
321145 03/26/2012 271171 7 003 M Repair drinking fountain adjacent to 7-110, no water
330132 03/26/2012 291338 7 119 M Adjust door closer on exterior door to control speed of closing door
330116 03/26/2012 291306 7 206 M Replace missing thermostat cover
330127 03/26/2012 291328 8 102A M Adjust door closer to control speed of closing door
330124 03/26/2012 291322 8 108 M Replace or remove damaged plastic window in fire extinguisher cabinet adjacent to 8-108A
330125 03/26/2012 291324 8 108 M Verify capacity indicated on maximum occupancy sign
330123 03/26/2012 291320 8 108A M Replace damaged ceiling tiles
330060 03/26/2012 291177 9 001 M Determine cause of water damaged ceiling tiles and replace tiles, across from 9-106
330122 03/26/2012 291318 9 102 M Replace missing ceiling tiles
330059 03/26/2012 291175 9 103 M Replace missing ceiling tiles
330061 03/26/2012 291179 9 106 M Replace missing ceiling tiles
330083 03/26/2012 291237 9 8088 M Replace missing protective cover for outlets on exterior wall at 9-107 north door
330069 03/26/2012 291198 P 6461 M Replace missing floor tile adjacent to A/C unit
329972 03/26/2012 290982 11 101 O Prohibit plugging refrigerator into green multi outlet extension cord - plug directly into permanent electrical outlet
330105 03/26/2012 291284 2 112 O Prohibit brown 13A extension cord plugged into green extension cord (for train and strands of lights). Replace with minimum 15A single outlet extension cord or surge protector plugged directly into permanent electrical outlet
330107 03/26/2012 291288 2 112C O Prohibit multi outlet electrical adaptor on media cart
330106 03/26/2012 291286 2 112D O Prohibit plugging surge protector into surge protector, prohibit plugging refrigerator into surge protector, plug each into permanent electrical outlets
330155 03/26/2012 291385 3 101 O Prohibit plugging surge protector into surge protector at teacher's desk
330047 03/26/2012 291147 3 102 O Remove and prohibit excessive flammable decorations on walls, prohibit hanging decorations from ceiling. Coverage area is 50% of each wall in room with fire sprinklers
330108 03/26/2012 291290 3 202 O Prohibit use of umbrella which dislocates ceiling tile, ceiling tile must be kept in place
330135 03/26/2012 291344 5 101A O Store chemicals properly
330136 03/26/2012 291346 5 102 O Remove and prohibit air freshener (sticks in oil)
330153 03/26/2012 291381 5 102A O Prohibit plugging orange extension cord into surge protector
330145 03/26/2012 291364 5 108 O Replace missing sign indicating primary and secondary evacuation routes
330154 03/26/2012 291383 5 110 O Prohibit grey multi outlet power strip at wall mounted CD changer, use single outlet 15A extension cord or surge protector
330148 03/26/2012 291370 5 111 O Prohibit plugging surge protectors into surge protectors at fish tanks in corner of room
330149 03/26/2012 291372 5 112 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
330056 03/26/2012 291169 6 106 O Prohibit plugging surge protector into surge protector adjacent to grow lights
330057 03/26/2012 291171 6 112 O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
330112 03/26/2012 291298 6 201 O Prohibit plugging surge protector into surge protector at computers adjacent to exterior door
330111 03/26/2012 291296 6 220 O Prohibit plugging surge protector into surge protector in computer lab
330131 03/26/2012 291336 7 106 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
330130 03/26/2012 291334 7 112 O Remove and prohibit air freshener (scented wax warmer)
330126 03/26/2012 291326 8 102A O Remove and prohibit net hanging from ceiling
330121 03/26/2012 291316 9 102 O Prohibit white multi outlet extension cord at teacher's desk or replace with minimum 15A single outlet cord
330118 03/26/2012 291310 9 107 O Keep dust collection hoses connected to equipment (saws, drill)
330119 03/26/2012 291312 9 107C O Relocate storage to provide access to this room during the report review meeting
330157 03/26/2012 291391 00 0000 C Provide NFPA 704 placard which identifies hazard at fenced area for under ground propane tanks adjacent to Bldg. 13
261951 03/26/2012 144242 12 201 C Provide emergency lights in pressbox (emergency lights are part of lighting in ceiling,test button is identified by red sticker)
330030 03/26/2012 291108 10 101C MS Provide current inspection tag for fire extinguisher in serving line adjacent to 10-102
329967 03/26/2012 290969 14 101 MS Replace missing fire extinguisher
330029 03/26/2012 291106 2 103 MS Provide current inspection tag for fire extinguisher
330041 03/26/2012 291127 2 108J MS Provide current inspection tag for fire extinguisher
330158 03/26/2012 291395 2 192 MS Water control 1/4 turn valve on Standpipe is in closed position. Immediately return to open position to allow water flow from standpipe connection on exterior wall if necessary
330120 03/26/2012 291314 8 108 MS Repair panic hardware on double corridor door to allow proper egress
330058 03/26/2012 291173 9 001 MS Recharge fire extinguisher adjacent to 9-101
329975 03/26/2012 290988 00 0000 OS Remove and prohibit storage under bleachers
330093 03/26/2012 291260 1 130 OS Prohibit storage of tires, store in flammable storage room
291810 03/26/2012 207434 10 180 OS Prohibit charging batteries in room
329971 03/26/2012 290979 11 105 OS Prohibit storage of flammable materials (propane, spray paint)
330089 03/26/2012 291251 13 101 OS Provide clear access to fire extinguisher
330051 03/26/2012 291159 3 108C OS Prohibit storage of flammable materials (field marker paint)
330048 03/26/2012 291152 3 111 OS Maintain clear aisle to corridor exit door
330053 03/26/2012 291163 3 193 OS Remove storage from boiler room
330097 03/26/2012 291268 4 292 OS Remove storage from mechanical room
330137 03/26/2012 291348 5 102 OS Remove and prohibit use of candles
330152 03/26/2012 291379 5 102B OS Maintain clear aisle to exterior exit
330055 03/26/2012 291167 5 192 OS Remove storage from mechanical room
330098 03/26/2012 291270 5 292 OS Remove storage from mechanical room
330100 03/26/2012 291274 6 292 OS Remove storage from mechanical room
330129 03/26/2012 291332 7 112 OS Maintain clear aisle to corridor exit door
330117 03/26/2012 291308 7 205 OS Keep area clear at emergency escape window
330062 03/26/2012 291181 9 192 OS Remove storage from mechanical room
321150 11/23/2011 271185 10 103B M Replace damaged release handle
321237 11/23/2011 271366 4 007 M Replace damaged spout on drinking fountain
321089 11/23/2011 271053 5 101 M Repair loose exterior door handle
321090 11/23/2011 271057 5 114 M Secure sink to wall in accessible stall
321230 11/23/2011 271352 5 218 M Secure loose faucet in accessible stall
321106 11/23/2011 271089 6 105A M Determine cause of water damaged ceiling tiles and replace tiles
321119 11/23/2011 271116 6 111 M Secure loose faucet
321197 11/23/2011 271280 7 216 M Repair faucet
258342 11/23/2011 138069 2 108C C Provide tempered glass, safety glass, or stainless steel for mirrors
258343 11/23/2011 138072 2 108E C Provide tempered glass, safety glass, or stainless steel for mirrors
261956 11/23/2011 144252 2 108J C Provide suitable dust collection system for woodworking equipment or prohibit use of wood working equipment in room
321213 04/04/2011 271317 1 006 M Repair damaged tile flooring, N.W. corner, tile missing under desk
321255 04/04/2011 271403 1 190 M Determine cause of water damaged ceiling tiles and replace tiles
321224 04/04/2011 271339 11 101 M Mount fire extinguisher at maximum five feet above floor adjacent to exit
321220 04/04/2011 271328 11 104 M Repair 2nd sink on South side, no water
321223 04/04/2011 271336 11 105 M Mount fire extinguisher at maximum five feet above floor adjacent to west door
321217 04/04/2011 271325 2 105 M Repair 8th sink, runs too long
321216 04/04/2011 271323 2 107 M Repair 3rd sink, no water
321215 04/04/2011 271320 2 110 M Repair sink, no water
306216 04/04/2011 238477 3 104 M Provide permanent number on maximum occupancy sign, Maximum Occupancy = 193
321040 04/04/2011 270945 3 108 M Repair damaged ceramic floor tile
321075 04/04/2011 271020 3 108 M Repair broken bench
321076 04/04/2011 271022 3 108D M Repair damaged ceramic tile flooring
321036 04/04/2011 270931 3 108F M Repair plumbing at two sinks, no water
321244 04/04/2011 271381 3 214A M Repair sink, no water
321245 04/04/2011 271383 3 215 M Replace missing flourescent light cover
321247 04/04/2011 271387 3 217 M Replace missing signage indicating room name and number
321248 04/04/2011 271389 3 217 M Repair two sinks, no water
321250 04/04/2011 271393 3 218A M Anchor shelving to wall
321088 04/04/2011 271050 4 101 M Determine cause of water damaged ceiling tiles and replace tiles
321084 04/04/2011 271035 4 102B M Provide dated flame resistance label on stage curtain, current date 4/04 has expired
321078 04/04/2011 271025 4 104 M Determine cause of water damaged ceiling tiles and replace tiles
321079 04/04/2011 271033 4 104 M Eliminate ants at rear exterior door
321085 04/04/2011 271044 4 191 M No access available to panel 4LSH1
321238 04/04/2011 271369 4 204 M Determine cause of water damaged ceiling tiles and replace tiles
321235 04/04/2011 271362 4 215 M Replace two missing flourescent light covers
321241 04/04/2011 271374 4 218 M Repair doorstop at accessible stall door
321099 04/04/2011 271074 5 003 M Replace insert in exit sign
321093 04/04/2011 271063 5 105 M Replace missing fluorescent light cover
321091 04/04/2011 271059 5 113 M Repair loose faucet
321102 04/04/2011 271081 5 116 M Repair exterior door to close properly
321227 04/04/2011 271347 5 207 M Determine cause of water damaged ceiling tiles and replace tiles
321226 04/04/2011 271343 5 210 M Repair door hardware, latch and handle loose
321231 04/04/2011 271354 5 217 M Repair doorstop at accessible stall door
321228 04/04/2011 271349 5 218 M Repair doorstop at accessible stall door
321225 04/04/2011 271341 5 291 M Replace missing signage indicating room name and number
321104 04/04/2011 271085 6 101 M Determine cause of water damaged ceiling tiles and replace tiles
321125 04/04/2011 271130 6 103 M Replace missing thermostat cover
321105 04/04/2011 271087 6 105 M Determine cause of water damaged ceiling tiles and replace tiles
321122 04/04/2011 271124 6 108 M Determine cause of water damaged ceiling tiles and replace tiles
321107 04/04/2011 271091 6 110 M Secure sink to wall in accessible stall
321120 04/04/2011 271118 6 111 M Repair doorstop at accessible stall door
321123 04/04/2011 271126 6 190 M Repair door to close properly
321203 04/04/2011 271293 6 201 M Repair exterior door to close properly
321210 04/04/2011 271308 6 217 M Repair doorstop at accessible stall door
321208 04/04/2011 271304 6 218 M Repair doorstop at accessible stall door
321211 04/04/2011 271312 6 220 M Replace missing signage indicating room name and number
321201 04/04/2011 271290 6 8088 M Repair or replace exterior outlet cover adjacent to 6-191
321124 04/04/2011 271128 7 001 M Secure hanging escutcheon on fire sprinkler head in corridor
321127 04/04/2011 271134 7 105 M Secure data outlet cover in SW corner
321128 04/04/2011 271136 7 110 M Determine cause of water damaged ceiling tiles and replace tiles
321129 04/04/2011 271138 7 110A M Secure sink to wall
321126 04/04/2011 271132 7 117 M Repair inoperable urinal
321198 04/04/2011 271284 7 217 M Repair faucet in accessible stall
321199 04/04/2011 271286 7 217 M Repair doorstop at accessible stall door
321200 04/04/2011 271288 7 219 M Secure hanging escutcheon on fire sprinkler head
321193 04/04/2011 271272 7 290 M Replace missing flourescent light covers
321195 04/04/2011 271277 7 290 M Replace missing escutcheon on fire sprinkler head
321184 04/04/2011 271255 8 108 M Replace missing signage indicating room name and number, north exterior
321180 04/04/2011 271246 8 111 M Repair door stop at accessible stall door
321190 04/04/2011 271268 8 191 M Replace missing signage indicating room name and number
321187 04/04/2011 271260 9 102 M Replace missing signage indicating room name and number, north exterior
321175 04/04/2011 271236 9 103A M Provide cover on exposed electrical junction box
321170 04/04/2011 271225 9 107M M Repair loose faucet
321171 04/04/2011 271227 9 109 M Repair loose faucet
321172 04/04/2011 271229 9 109 M Repair doorstop in accessible stall
321151 04/04/2011 271187 9 110 M Replace missing signage indicating room name and number
321153 04/04/2011 271190 9 110 M Repair deteriorated wall
321252 04/04/2011 271397 1 124 O No access was available to this room. Please be prepared to access this room during the report review meeting.
321253 04/04/2011 271399 1 126 O No access was available to this room. Please be prepared to access this room during the report review meeting.
321254 04/04/2011 271401 1 129 O No access was available to this room. Please be prepared to access this room during the report review meeting.
321249 04/04/2011 271391 3 201B O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
321246 04/04/2011 271385 3 206 O Replace missing sign indicating evacuation routes
321243 04/04/2011 271379 3 207 O Replace missing sign indicating evacuation routes
321233 04/04/2011 271357 5 219B O Prohibit plugging refrigerator and microwave into surge protector - plug directly into permanent electrical outlet
321121 04/04/2011 271122 6 107 O Replace missing sign indicating evacuation routes
321206 04/04/2011 271299 6 201 O Prohibit plugging surge protector into surge protector at computer desk
321146 04/04/2011 271178 7 118 O No access was available to this room. Please be prepared to access this room during the report review meeting.
321174 04/04/2011 271233 9 103A O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
321161 04/04/2011 271201 9 107E O Remove storage above caged area to allow proper coverage of fire sprinkler heads
321164 04/04/2011 271212 9 107F O Remove storage above caged area to allow proper coverage of fire sprinkler heads
321165 04/04/2011 271215 9 107G O Remove storage above caged area to allow proper coverage of fire sprinkler heads
261949 04/04/2011 144238 10 184 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for storage room next to kitchen rear door
321148 04/04/2011 271181 10 103 MS Provide current inspection tag for type "K" fire extinguisher
321251 04/04/2011 271395 2 212 MS Provide current inspection tag for fire extinguisher
321168 04/04/2011 271220 9 107 MS Provide current inspection tag for fire extinguisher, west wall adjacent to 9-107M
321173 04/04/2011 271231 9 190 MS Seal penetration in enclosure wall to prevent spread of fire or smoke
321017 04/04/2011 270898 P 6461 MS Provide current inspection tag for fire extinguisher
321019 04/04/2011 270901 P 6462 MS Provide current inspection tag for fire extinguisher
321149 04/04/2011 271183 10 180 OS Prohibit charging batteries in room, floor machines
306019 04/04/2011 238069 10 184 OS Prohibit charging batteries in room, Golf Cart and Floor Machines
306090 01/05/2011 238217 7 210 M Replace broken window glass, S.W. corner
306273 01/05/2011 238602 12 170 O No access was available to Press Box elevator. Please be prepared to access this area during the report review meeting.
306107 01/05/2011 238253 6 101A O Prohibit plugging ice machine and coffee machine into surge protector - plug directly into permanent electrical outlet
272769 01/05/2011 166778 00 0000 C Replace sliding door with side hinged door at greenhouse
291809 01/05/2011 207431 10 001 C Provide magnetic release hold open device for fire door leading into cafeteria
306267 01/05/2011 238592 11 105 MS Provide current inspection tag for fire extinguisher, and mount fire extiinguisher to wall
306002 01/05/2011 238034 10 101B FS Provide certification that fire alarm system has been tested and is fully operational, latest test report dated 2008
306245 03/26/2010 238546 00 0000 M Repair doors to open/close properly, courtyard doors between bldngs 4 & 5
306246 03/26/2010 238548 00 0000 M Repair doors to open/close properly, courtyard doors between bldngs 3 & 2
306258 03/26/2010 238572 00 0000 M Modify temporary fencing and gates to allow access to fire hydrant by new portables at all times
306050 03/26/2010 238135 1 190 M Determine cause of water damaged ceiling tiles and replace tiles
305993 03/26/2010 238012 10 101A M Provide cover for exposed electrical outlet, 220V
305997 03/26/2010 238022 10 104 M Repair loose faucets, sink #1 & sink #3
305976 03/26/2010 237983 10 191 M Repair emergency lighting
306033 03/26/2010 238083 10 195 M Repair exterior door to close properly
306034 03/26/2010 238102 10 195 M Chain refrigerant cylinders to wall
306259 03/26/2010 238575 11 101 M Mount fire extinguisher at maximum five feet above floor
306265 03/26/2010 238577 11 104 M Secure sink in the accessible stall to wall
306270 03/26/2010 238597 12 190 M Provide cover for exposed exterior electrical outlet
291937 03/26/2010 207696 2 103 M Provide additional outlets for lighting equipment, per theater teacher. Lighting draws too much power causing breakers to trip
306065 03/26/2010 238165 2 105 M Repair damage stall door, 3rd stall in womens bathroom
306064 03/26/2010 238163 2 108 M Eliminate ants at exit door adjacent to 2-192
258432 03/26/2010 138255 2 108 M Replace missing caps on fire sprinkler heads
306059 03/26/2010 238153 2 108A M Repair stage door to close properly
306062 03/26/2010 238159 2 113 M Provide dated flame resistance label on stage curtain, "Should be retested four years from date - 4/04", as stated on tag
306066 03/26/2010 238167 2 191 M Eliminate insect infestation, ants
306165 03/26/2010 238380 3 104A M Determine cause of water damaged ceiling tiles and replace tiles
306163 03/26/2010 238375 3 106 M Determine cause of water damaged ceiling tiles and replace tiles
306189 03/26/2010 238415 3 108D M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters at exterior door
306203 03/26/2010 238457 3 108F M Repair broken toilet paper dispenser
306210 03/26/2010 238470 3 108F M Repair loose faucet on sink
306226 03/26/2010 238502 3 112 M Repair sink in girls bathroom, no water at faucet
306255 03/26/2010 238566 3 202 M Repair electrical outlets
306256 03/26/2010 238568 3 208 M Determine cause of water damaged ceiling tiles and replace tiles
306257 03/26/2010 238570 3 211A M Determine cause of water damaged ceiling tiles and replace tiles
306196 03/26/2010 238439 3 8088 M Repair exterior drinking fountain adjacent to 3-104F
306233 03/26/2010 238513 4 102B M Provide dated flame resistance label on curtain, "Curtain should be retested 4 years from date - 11/04" as stated on tag
306239 03/26/2010 238531 4 104 M Replace missing ceiling tile adjacent to T.V. conduit
306243 03/26/2010 238542 4 107 M Determine cause of water damaged ceiling tiles and replace tiles
306254 03/26/2010 238564 4 202 M Determine cause of water damaged ceiling tiles and replace tiles
306248 03/26/2010 238552 4 214C M Replace missing ceiling tile
306249 03/26/2010 238554 4 217 M Repair toilet
306250 03/26/2010 238556 4 217 M Repair loose faucet
306251 03/26/2010 238558 4 218 M Repair toilet
306138 03/26/2010 238320 5 104 M Determine cause of water damaged ceiling tiles and replace tiles
306134 03/26/2010 238312 5 111 M Replace missing ceiling tiles
306136 03/26/2010 238315 5 116 M Replace missing ceiling tiles
306161 03/26/2010 238369 5 218 M Repair broken soap dispenser
306100 03/26/2010 238241 6 003 M Repair exterior corridor door to close properly
306093 03/26/2010 238224 6 008 M Repair damaged water fountain spout
306104 03/26/2010 238248 6 190 M Adjust ceiling tiles
306082 03/26/2010 238201 7 001 M Repair drinking fountain
306080 03/26/2010 238195 7 116 M Replace missing toilet seat in second stall
306081 03/26/2010 238199 7 117 M Repair leaking faucet, first lavatory
306083 03/26/2010 238203 7 119 M Repair exterior door to close properly
306084 03/26/2010 238205 7 119 M Repair deteriorated wall, corner bead damaged
306087 03/26/2010 238211 7 215A M Adjust ceiling tiles
306089 03/26/2010 238215 7 219 M Repair exterior door to close properly
306045 03/26/2010 238125 8 002 M Repair drinking fountain
306044 03/26/2010 238123 8 109 M Repair door to cooridor 003 to open/close properly
306042 03/26/2010 238118 9 105 M Repair escutcheon on fire sprinkler head
306039 03/26/2010 238112 9 107 M Secure Band Saw to floor
306053 03/26/2010 238141 1 105 O Remove and prohibit combustible (residential) furniture or treat with flame retardant and provide certification of that treatment
306052 03/26/2010 238139 1 116 O Remove and prohibit combustible (residential) furniture or treat with flame retardant and provide certification of that treatment
306051 03/26/2010 238137 1 117 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
306055 03/26/2010 238145 1 124 O No access was available to this room. Please be prepared to access this room during the report review meeting.
306056 03/26/2010 238147 1 126 O No access was available to this room. Please be prepared to access this room during the report review meeting.
306049 03/26/2010 238133 1 138 O Prohibit plugging microwave appliance into surge protector - plug directly into permanent electrical outlet
306054 03/26/2010 238143 1 139 O Prohibit plugging appliances into multi outlet electrical adapter - plug directly into permanent electrical outlet - Prohibit multi outlet adapter
306005 03/26/2010 238038 10 180A O Remove and prohibit combustible (residential) furniture or treat with flame retardent and provide certification of treatment
306009 03/26/2010 238045 10 180A O Eliminate 13A extension cord on cart or replace with minimum 15A cord
306022 03/26/2010 238076 10 184 O Keep area within 18" of fire sprinkler head clear
306061 03/26/2010 238157 2 113 O Post sign indicating evacuation routes
306060 03/26/2010 238155 2 113G O No access was available to this room. Please be prepared to access this room during the report review meeting.
306253 03/26/2010 238562 4 201 O Remove and prohibit paper covering window in door
306252 03/26/2010 238560 4 201A O Keep shower drain filled with water
306247 03/26/2010 238550 4 215 O Prohibit plugging microwave appliance into surge protector - plug directly into permanent electrical outlet
306153 03/26/2010 238351 5 108 O Post sign indicating evacuation routes
306131 03/26/2010 238298 5 110A O Keep area within 18" of fire sprinkler head clear
306133 03/26/2010 238308 5 111 O Remove and prohibit combustible beanbag chairs, toy shark
306108 03/26/2010 238259 6 108 O Remove and prohibit combustible beanbag chair
306094 03/26/2010 238226 6 215 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
306086 03/26/2010 238209 7 109 O Post sign indicating evacuation routes
306092 03/26/2010 238220 7 212 O Prohibit plugging surge protector into surge protector
306046 03/26/2010 238127 8 101 O Remove mirror or provide mirror made of tempered glass, safety glass, or stainless steel
306047 03/26/2010 238129 8 102A O Remove mirror or provide mirror made of tempered glass, safety glass, or stainless steel
306048 03/26/2010 238131 8 102A O Prohibit plugging surge protector into surge protector
306043 03/26/2010 238121 9 101A O Remove and prohibit combustible (residential) furniture or treat with flame retardant and provide certification of treatment
306037 03/26/2010 238108 9 103 O Eliminate multi-outlet extension cord
306040 03/26/2010 238114 9 107C O No access was available to this room. Please be prepared to access this room during the report review meeting.
291985 03/26/2010 207798 00 0000 C Provide exterior signage indicating property address
261959 03/26/2010 144258 2 190 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for room across from 2-108B
262432 03/26/2010 144824 3 101 C Eliminate floor outlets in potter's wheel area and provide wall or ceiling outlets
272755 03/26/2010 166749 3 291 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
272398 03/26/2010 165962 5 203 C Post sign indicating evacuation routes
262014 03/26/2010 144370 6 190 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for data room adjacent to 6-192
306096 03/26/2010 238229 6 201 C Provide signage indicating room name and number at appropriate height with raised and Braille characters at exterior door
258283 03/26/2010 137945 6 206 C Provide sign indicating evacuation routes
262018 03/26/2010 144378 7 110B C Provide cover for inspector's test cabinet - sprinkler system
262019 03/26/2010 144381 7 114 C Post sign indicating evacuation routes
258279 03/26/2010 137936 7 214 C Provide sign indicating evacuation routes
306063 03/26/2010 238161 2 101 MS Provide current inspection tag for fire extinguisher adjacent to concession stand
291936 03/26/2010 207694 2 103 MS Provide current inspection tag for fire extinguisher
306167 03/26/2010 238385 3 104F MS Provide current inspection tag for fire extinguisher
306244 03/26/2010 238544 4 191 MS Provide current inspection tag for fire extinguisher
306139 03/26/2010 238324 5 105 MS Provide current inspection tag for fire extinguisher
306124 03/26/2010 238290 5 191 MS Provide current inspection tag for fire extinguisher
306102 03/26/2010 238244 6 192 MS Recharge fire extinguisher
306057 03/26/2010 238149 1 192 OS Prohibit desk storage in Mechanical room
305986 03/26/2010 237985 10 103A OS Remove and prohibit combustible (residential) furniture or treat with flame retardent and provide certification of treatment
306036 03/26/2010 238106 13 101 OS Tires to be relocated to the flammable storage room or removed from property
306058 03/26/2010 238151 2 113C OS Prohibit storage of flammable spray paint
306199 03/26/2010 238449 3 114 OS Prohibit storage of flammable spray paint
306222 03/26/2010 238489 3 116 OS Prohibit storage of flammable spray paint
306147 03/26/2010 238336 5 106A OS Prohibit storage of flammable materials, store MAPP gas in flammable storage cabinet
306085 03/26/2010 238207 7 001 OS Remove and prohibit boxes in exit corridor outside 7-104
306077 03/26/2010 238192 7 190 OS Remove desks stored in mechanical room
306088 03/26/2010 238213 7 280 OS Prohibit charging batteries in room, floor cleaner
306038 03/26/2010 238110 9 107 OS Prohibit storage of flammable materials (gasoline, mineral spirits and paint thinner)
306041 03/26/2010 238116 9 191 OS Remove storage from mechanical room
262029 03/26/2010 144401 8 102B CS Provide appropriate cover for opening in ceiling for paint spray booth
291816 01/04/2010 207446 3 104 M Secure loose escutcheon on fire sprinkler head
291967 01/04/2010 207762 3 202 M Secure escutcheon on fire sprinkler head
291941 01/04/2010 207706 5 103 M Adjust flow of emergency eye wash
291911 01/04/2010 207643 9 107H M Replace missing section of whiteboard frame, exposed edges are sharp
291970 01/04/2010 207768 3 206 O Mount and secure sign indicating evacuation routes, sign has fallen off the wall
258266 01/04/2010 137910 5 111 O Prohibit piggy backed surge protectors behind aquarium, plug each surge protector directly into wall outlet
258314 01/04/2010 138013 6 220 O Prohibit plugging one surge protector into another under computer stations, plug each surge protector directly into wall outlet
258243 01/04/2010 137882 7 115 O Prohibit plugging surge protectors into extension cords at computer stations, plug each surge protector directly into wall outlet
262431 01/04/2010 144822 00 0000 C Provide additional outlets in computer labs to eliminate use of excessive extension cords and surge protectors
261961 01/04/2010 144262 3 0000 C Post sign indicating evacuation routes for each classroom indicating primary and secondary means of egress - some signs indicate both routes as primary and others do not show secondary route
261980 01/04/2010 144300 5 0000 C Post sign indicating evacuation routes for each classroom indicating primary and secondary means of egress - some signs indicate both routes as primary and others do not show secondary route
262005 01/04/2010 144352 6 0000 C Post sign indicating evacuation routes for each classroom indicating primary and secondary means of egress - some signs indicate both routes as primary and others do not show secondary route
258480 01/04/2010 138351 4 102 OS Arrange desks to maintain 3 ft clear aisle to exterior door - reduce number of desks as necessary
291957 04/23/2009 207742 00 0000 M Provide chain and padlock for backflow preventor south of 2-114
291813 04/23/2009 207440 10 184 M Replace missing ceiling tiles
291896 04/23/2009 207592 10 192 M Label interior walls of electrical room to indicate 2 hour fire rating
291954 04/23/2009 207736 11 101 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
291956 04/23/2009 207740 12 170 M Provide certification that inspection tag for elevator is current
291938 04/23/2009 207698 2 004 M Repair hole in wall behind door to 2-113
291931 04/23/2009 207684 2 108A M Reset smoke hatch releases
291929 04/23/2009 207680 2 108G M Secure loose escutcheon on fire sprinkler head
291928 04/23/2009 207678 2 112 M Provide stickers above fire extinguishers (x2) indicating their location
291910 04/23/2009 207641 2 114B M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
291990 04/23/2009 207810 3 101B M Relocate permanent power source plug from inside 3-101B to 3-101. Current installation creates a hazard because equipment it is powering is used in classroom, not in storage closet. See teacher
291822 04/23/2009 207458 3 103 M Replace missing sign on exterior wall indicating room name and number
291819 04/23/2009 207452 3 110 M Repair hole in wall
291821 04/23/2009 207456 4 102 M Determine cause of water damaged ceiling tiles and replace tiles
293121 04/23/2009 210233 4 104 M Remove maximum occupancy sign
291984 04/23/2009 207795 4 104 M Verify capacity indicated on maximum occupancy sign, map indicates 109 as maximum occupancy but sign reads 60
291940 04/23/2009 207704 4 107 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
291973 04/23/2009 207773 4 212 M Replace missing sign by exterior door indicating room name and number at appropriate height with raised and Braille characters
291962 04/23/2009 207752 4 216 M Replace missing ceiling tiles
291942 04/23/2009 207708 5 104 M Replace missing ceiling tiles
291944 04/23/2009 207712 5 107 M Adjust flow of emergency eye wash
291945 04/23/2009 207715 5 109 M Adjust flow of emergency eye wash
291946 04/23/2009 207717 5 110 M Adjust flow of emergency eye wash
291943 04/23/2009 207710 5 110 M Replace missing ceiling tiles
291983 04/23/2009 207793 5 116 M Provide security cover for emergency shut off button to prevent student access
291974 04/23/2009 207775 5 201 M Replace missing maximum occupancy sign(max. occ. 95)
291975 04/23/2009 207777 5 201 M Determine cause of water damaged ceiling tiles and replace tiles
291982 04/23/2009 207791 6 101C M Chain helium cylinder to wall
291980 04/23/2009 207787 6 105A M Determine cause of water damaged ceiling tiles and replace tiles
291976 04/23/2009 207779 7 215 M Replace ceiling tile with hole above NW door
291959 04/23/2009 207746 7 290 M Replace missing ceiling tiles in vestibule for 7-290
291922 04/23/2009 207665 8 101 M Repair door to close and latch properly
291953 04/23/2009 207734 9 002 M Determine cause of water damaged ceiling tiles and replace tiles in corridor across from 9-105
291952 04/23/2009 207731 9 106 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
291912 04/23/2009 207645 9 107 M Repair hole in column across from 9-107H
291914 04/23/2009 207649 9 107 M Connect vacuum hoses to dust collection system
291927 04/23/2009 207675 9 191 M Repair leaking water line
291949 04/23/2009 207725 1 146 O Remove and prohibit air freshener
291933 04/23/2009 207688 2 108B O Prohibit multi outlet extension cord, use 15A single outlet extension cord
291939 04/23/2009 207700 3 111 O Remove and prohibit paper covering window in door
291965 04/23/2009 207758 3 201A O Remove and prohibit air freshener
291966 04/23/2009 207760 3 201A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
291963 04/23/2009 207754 3 201B O Remove and prohibit air freshener
291969 04/23/2009 207766 3 205 O Mount and secure sign indicating evacuation routes, sign has fallen off the wall
291981 04/23/2009 207789 6 106 O Prohibit hanging class projects (decorations) on emergency eye wash
291961 04/23/2009 207750 6 215 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
291978 04/23/2009 207783 7 119 O Post sign indicating evacuation routes
291917 04/23/2009 207655 8 108A O Maintain storage room in an orderly manner
291951 04/23/2009 207729 9 101B O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
291915 04/23/2009 207651 9 107 O Maintain classroom in an orderly manner
258291 04/23/2009 137963 7 217 C Provide signage for boys bathroom indicating room name and number at appropriate height with raised and Braille characters
291926 04/23/2009 207673 00 0000 MS Provide current inspection tag for fire extinguisher in greenhouse
291955 04/23/2009 207738 12 201 MS Provide current inspection tag for fire extinguisher
291934 04/23/2009 207690 2 0000 MS Provide current inspection tag for fire extinguishers on catwalk and adjoining room
291930 04/23/2009 207682 2 108A MS Provide current inspection tag for fire extinguisher
291908 04/23/2009 207619 2 114 MS Replace missing section of wall above SE doors
291909 04/23/2009 207638 2 114 MS Provide current inspection tag for fire extinguisher adjacent to SW doors
291823 04/23/2009 207460 2 290 MS Provide current inspection tag for fire extinguisher
291824 04/23/2009 207462 2 291 MS Provide current inspection tag for fire extinguisher
291825 04/23/2009 207464 2 292 MS Provide current inspection tag for fire extinguisher
291826 04/23/2009 207466 2 293 MS Provide current inspection tag for fire extinguisher
291818 04/23/2009 207450 3 104H MS Provide current inspection tag for fire extinguisher
291950 04/23/2009 207727 3 108 MS Provide current inspection tag for fire extinguisher
291968 04/23/2009 207764 3 218 MS Provide current inspection tag for fire extinguisher
291925 04/23/2009 207671 8 192 MS Provide current inspection tag for fire extinguisher
291913 04/23/2009 207647 9 107 MS Replace missing fire extinguisher adjacent to 9-107G
291814 04/23/2009 207442 10 103D OS Prohibit storage of sterno fuel
291811 04/23/2009 207436 10 184 OS Prohibit storage of golf cart
291812 04/23/2009 207438 10 184 OS Prohibit charging batteries in room
291916 04/23/2009 207653 13 9698 OS Prohibit storage of tires outside of building 13, store tires inside flammable storage room
291817 04/23/2009 207448 3 104G OS Prohibit storage of flammable field marker paint
291964 04/23/2009 207756 3 201A OS Remove and prohibit use of toaster oven
291820 04/23/2009 207454 4 102B OS Maintain clear aisle to exit
291972 04/23/2009 207771 4 211 OS Remove and prohibit candles
291977 04/23/2009 207781 7 105 OS Remove and prohibit candles
291958 04/23/2009 207744 7 280 OS Prohibit charging batteries in room
291924 04/23/2009 207669 8 102 OS Prohibit storage of golf cart tires, store in flammable storage room
291923 04/23/2009 207667 8 102B OS Prohibit charging batteries in room
291921 04/23/2009 207663 8 105 OS Relocate desks to maintain clear aisle to exit
291918 04/23/2009 207657 8 108 OS Properly store used fluids (oil, antifreeze)
291919 04/23/2009 207659 8 108A OS Properly store used fluids (oil, antifreeze)
291920 04/23/2009 207661 8 109 OS Prohibit storage of flammable materials, store in flammable storage cabinet
284861 12/04/2008 192601 00 0000 M Provide screen on ventilation fans on Greenhouse to prevent contact with fan blades
261940 12/04/2008 144219 00 0000 M Label all interior walls of electrical rooms to indicate 2 hour fire rating
291932 12/04/2008 207686 2 108A O Relocate pulley on green stage curtain rod or relocate curtain rod which impedes movement of adjacent curtain
291979 12/04/2008 207785 6 107 O Post sign indicating evacuation routes
258287 12/04/2008 137955 6 208 O Prohibit plugging one surge protector into another at computer stations, plug each surge protector directly into wall outlet
272394 12/04/2008 165954 7 209 O Prohibit plugging surge protector into surge protector under computer stations on north wall
258204 12/04/2008 137798 3 206 C Post sign indicating evacuation routes
258422 12/04/2008 138237 2 192 MS Repair water leak at fire pump
261974 12/04/2008 144288 3 280 MS Replace missing ceiling hatch cover
272770 01/18/2008 166780 00 0000 M Remove sliding barrel lock on north door of greenhouse
272371 01/18/2008 165906 1 005 M Replace safety pin on fire extinguisher in corridor adjacent to 1-132
272368 01/18/2008 165900 1 180 M Adjust door to latch properly
272383 01/18/2008 165932 1 191 M Repair air conditioner in electrical room to work properly - room is very hot
261945 01/18/2008 144230 10 103 M Adjust two burner cook top to be under hood fire suppression nozzle
272753 01/18/2008 166745 11 102 M Replace missing illuminated exit sign adjacent to south door
272754 01/18/2008 166747 12 201 M Repair water damaged flooring and subflooring in pressbox adjacent to south exit door
261952 01/18/2008 144244 12 201 M Repair illuminated exit signs in football field pressbox
272387 01/18/2008 165940 2 005 M Replace missing globe on light fixture in corridor outside girls dressing room (2-108C)
261957 01/18/2008 144254 2 108J M Anchor woodworking equipment and paint safety lines around all equipment
255991 01/18/2008 133129 3 104J M Replace plastic flexible exhaust duct for dryer with a metal duct
272374 01/18/2008 165912 3 111 M Remove or repair fire extinguisher cabinet door adjacent to exterior door
272389 01/18/2008 165944 3 218 M Replace missing ceiling tiles
272376 01/18/2008 165916 4 101 M Replace missing ceiling tiles adjacent to circulation desk
272378 01/18/2008 165921 4 103 M Replace missing ceiling tiles
272391 01/18/2008 165948 4 213 M Replace broken sign indicating room name and number at appropriate height with raised and Braille characters
272400 01/18/2008 165966 5 101 M Adjust water flow for emergency eye wash
272399 01/18/2008 165964 5 108 M Adjust water flow for emergency eye wash
272402 01/18/2008 165970 5 110 M Adjust water flow for emergency eye wash
272404 01/18/2008 165975 5 110 M Secure loose electrical junction box on science table adjacent to emergency eye wash
272403 01/18/2008 165972 5 116 M Secure loose electrical junction box at end of science table adjacent to fire door
272757 01/18/2008 166753 6 114A M Replace missing escutcheon on fire sprinkler head
272397 01/18/2008 165960 6 208 M Repair broken window
272395 01/18/2008 165956 7 291 M Repair air conditioner unit to work properly in electrical room
272771 01/18/2008 166782 00 0000 O Maintain housekeeping in greenhouse - clean spider webs/cobwebs from walls, doors and ceiling, etc...
272369 01/18/2008 165902 1 114 O Prohibit plugging surge protector into surge protector under desk
272406 01/18/2008 165979 10 101B O Remove and prohibit use of tape to prevent door from latching
272752 01/18/2008 166742 12 170 O No access was available to this room. Please be prepared to access this room during the report review meeting.
272766 01/18/2008 166771 12 190 O Maintain housekeeping in room - clean spider web / cobwebs from ceiling, doors, electrical equipment, etc....
272388 01/18/2008 165942 2 108A O Relocate mats to provide clear access to fire hose cabinet on stage adjacent to boys & girls locker rooms
272773 01/18/2008 166786 3 101 O Remove and prohibit use of bandsaw in room or have room modified to meet woodshop requirements ( emergency electrical disconnect button, safety lines, bolt machinery to floor, dust collector, etc....)
272382 01/18/2008 165930 3 104J O Remove clothes on dryer duct
272373 01/18/2008 165910 3 106 O Prohibit plugging microwave into surge protector. Plug microwave directly into wall outlet (X3)
258212 01/18/2008 137818 3 201 O Remove and prohibit paper covering window in door
272390 01/18/2008 165946 3 210 O Eliminate extension cord for christmas lights next to teacher's desk or replace with minimum 15A cord
272380 01/18/2008 165925 4 102B O Remove broken mirror on floor adjacent to exterior door
272381 01/18/2008 165927 5 110A O Remove and prohibit excessive flammable stuffed aquatic decorations
272401 01/18/2008 165968 5 112 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
258316 01/18/2008 138018 5 210 O Prohibit plugging one surge protector into another at computer stations, plug each surge protector directly into wall outlet
272758 01/18/2008 166755 6 103 O Prohibit plugging microwave into surge protector along exterior wall - plug directly into permanent electrical outlet
258245 01/18/2008 137886 6 108 O Remove paper inside light fixture on ceiling
272764 01/18/2008 166767 7 103 O Prohibit removing ceiling tiles in classroom - have maintenance adjust air flow
272760 01/18/2008 166759 7 114 O Prohibit plugging microwave into surge protector under teacher's desk - plug directly into permanent electrical outlet
272765 01/18/2008 166769 7 119 O Prohibit removing ceilings tiles in classroom - have maintenance adjust air flow
272396 01/18/2008 165958 7 214 O Prohibit plugging surge protector into surge protector under teacher's desk
272761 01/18/2008 166761 8 107 O Prohibit plugging surge protector into surge protector under teacher's desk
262031 01/18/2008 144406 9 101B O Eliminate and prohibit use of multiple outlet adaptor to power microwave and refrigerator - plug appliances directly into wall outlet
272763 01/18/2008 166765 9 103 O Eliminate extension cord with multiple outlet end or replace with a surge protector
272762 01/18/2008 166763 9 107K O Prohibit plugging surge protector into surge protector under computer stations
272767 01/18/2008 166773 6 103 C Modify emergency disconnect valves under teacher's station to completely shut-off with (1/4) turn
272768 01/18/2008 166775 00 0000 MS Provide current inspection tag for fire extinguisher in greenhouse
272385 01/18/2008 165936 2 113 MS Remove dog leg hold open devices from west double fire doors
272372 01/18/2008 165908 3 108A MS Provide current inspection tag for fire extinguisher
272370 01/18/2008 165904 1 192 OS Remove custodial storage from mechanical room
272405 01/18/2008 165977 10 101B OS Relocate storage to keep a minimum 3 ft clear path to panels ( elecrtical, fire alarm, etc...) in storage room
272386 01/18/2008 165938 2 113 OS Remove storage and musical instruments to maintain clear aisle to west exit doors
272772 01/18/2008 166784 3 101 OS Remove bandsaw to maintain clear aisle to exterior door
272375 01/18/2008 165914 3 193 OS Remove storage from boiler room
258211 01/18/2008 137812 3 201 OS Relocate teacher's desk to maintain a minimum 3 ft clear aisle to exterior door
272392 01/18/2008 165950 4 220 OS Relocate table to maintain clear aisle to exterior door
258273 01/18/2008 137921 5 103 OS Arrange desks to maintain a minimum 3 ft clear aisle to emergency eye wash and exterior door
272759 01/18/2008 166757 6 105A OS Prohibit storage of flammable rubber cement or relocate to flammable storage cabinet in adjacent room 6-105B
272756 01/18/2008 166751 6 292 OS Remove storage from mechanical room
272393 01/18/2008 165952 7 206 OS Remove and prohibit use of space heater
258388 01/18/2008 138164 12 201 CS Provide fire extinguisher in pressbox
258352 09/28/2007 138092 10 101E M Replace missing escutcheon on fire sprinkler head
261947 09/28/2007 144234 10 191 M Provide current inspection log and certification that emergency generator is operable
258387 09/28/2007 138162 12 170 M Provide certification that elevator has current inspection tag
258321 09/28/2007 138027 2 103 M Provide certification that lift has current inspection tag
262000 09/28/2007 144341 5 113 M Replace damaged sign indicating room name and number - Sign was replaced but does not indicate room number
258323 09/28/2007 138033 9 107C M Replace missing escutcheon on fire sprinkler head (x4)
262034 09/28/2007 144412 9 192 M Repair air conditioner to work properly, electrical room is too hot
255990 09/28/2007 133126 3 102C O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
258208 09/28/2007 137801 3 218 O Prohibit plugging one surge protector into another at computer stations, plug each surge protector directly into wall outlet
258222 09/28/2007 137837 4 220 O Prohibit plugging one surge protector into another at computer stations, plug each surge protector directly into wall outlet
261996 09/28/2007 144332 5 110 O Remove and prohibit excessive flammable decorations hanging from ceiling
261999 09/28/2007 144338 5 111 O Remove and prohibit excessive flammable decorations hanging from ceiling
258311 09/28/2007 138007 6 201 O Prohibit plugging one surge protector into another under computer stations and at teacher's desk, plug each surge protector directly into wall outlet
258391 09/28/2007 138170 9 103 O Prohibit plugging one surge protector into another at computer stations, plug each surge protector directly into wall outlet
262010 09/28/2007 144362 6 191 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
262012 09/28/2007 144366 6 192 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
258430 09/28/2007 138253 1 192 MS Provide current inspection tag for fire sprinkler system
258429 09/28/2007 138250 10 101D MS Provide current inspection tag for fire sprinkler system
258421 09/28/2007 138233 2 192 MS Provide current inspection tag for fire sprinkler system
258423 09/28/2007 138239 3 192 MS Provide current inspection tag for fire sprinkler system
258417 09/28/2007 138227 3 292 MS Provide current inspection tag for fire sprinkler system
258426 09/28/2007 138245 5 192 MS Provide current inspection tag for fire sprinkler system
258419 09/28/2007 138230 5 290 MS Provide current inspection tag for fire sprinkler system
258425 09/28/2007 138243 7 190 MS Provide current inspection tag for fire sprinkler system
258415 09/28/2007 138221 7 292 MS Provide current inspection tag for fire sprinkler system
258424 09/28/2007 138241 9 191 MS Provide current inspection tag for fire sprinkler system
261975 09/28/2007 144290 4 102B OS Keep curtain away from exterior door when not in use
262032 09/28/2007 144408 9 102 OS Remove storage from hallway adjacent to exterior door
261970 09/28/2007 144280 3 115 CS Provide auto closer on door
262429 10/20/2006 144813 1 143 M Repair or replace emergency eye wash to be functional at nurse's sink - emergency eye wash sprays on floor
258334 10/20/2006 138052 10 101 M Change number on maximum occupancy sign to 718 occupants
261944 10/20/2006 144228 10 101E M Replace missing ceiling tiles
258340 10/20/2006 138065 10 182A M Determine cause of water damaged ceiling tiles and replace tiles
261946 10/20/2006 144232 10 183 M Replace bulbs in explosion proof light fixtures
261948 10/20/2006 144236 10 195 M Repair air handler to eliminate water leak
258386 10/20/2006 138160 11 105 M Remove hasp and padlock from door
258345 10/20/2006 138075 2 108H M Determine cause of water damaged ceiling tiles and replace tiles
258351 10/20/2006 138087 2 114 M Repair damaged door to fire extinguisher cabinet adjacent to 2-114B
261958 10/20/2006 144256 2 114 M Repair illuminated exit sign adjacent to 2-006
261966 10/20/2006 144272 3 111 M Cover hole in corridor door at location of uninstalled lock cylinder
261967 10/20/2006 144274 3 111 M Replace damaged weatherstripping at exterior door
261968 10/20/2006 144276 3 112 M Replace missing wrench for fire sprinkler heads box
255989 10/20/2006 133124 3 113 M Replace missing escutcheon on fire sprinkler head
261969 10/20/2006 144278 3 115 M Seal gap between fire sprinkler escutcheon and ceiling
261971 10/20/2006 144282 3 180 M Anchor metal shelving to wall
258214 10/20/2006 137820 3 217 M Replace missing toilet paper dispenser in handicapped stall
258377 10/20/2006 138143 4 192 M Mount fire extinguisher at maximum five feet above floor
258230 10/20/2006 137849 4 201B M Provide padlock for roof hatch to prohibit unauthorized access
258233 10/20/2006 137859 4 218 M Replace missing signage for boys bathroom indicating room name and number at appropriate height with raised and Braille characters
258269 10/20/2006 137916 5 102 M Adjust water flow for emergency eye wash
261991 10/20/2006 144322 5 106A M Replace missing cover on electrical outlet
262002 10/20/2006 144345 5 116 M Replace missing nozzles for emergency eye wash
262003 10/20/2006 144347 5 180 M Anchor metal shelving to wall
262004 10/20/2006 144349 5 8088 M Replace missing cover on GFCI outlet on exterior wall in courtyard adjacent to 5-211
258294 10/20/2006 137970 6 216 M Secure loose threshold
262013 10/20/2006 144368 6 8088 M Replace missing cover on GFCI outlet on exterior wall in courtyard adjacent to 6-191
262016 10/20/2006 144374 7 001 M Remove or replace broken glazing in door for fire extinguisher cabinet in corridor adjacent to 7-101
262020 10/20/2006 144383 7 115B M Seal gap between fire sprinkler escutcheon and ceiling
262023 10/20/2006 144389 7 208 M Secure missing cover for auto closer on fire door - cover is lying above wall cabinet
262027 10/20/2006 144397 7 291 M Repair water damage to wall below DX 7-2
262030 10/20/2006 144403 8 108A M Replace missing ceiling tiles
262033 10/20/2006 144410 9 102 M Replace damaged weatherstripping at exterior door
258322 10/20/2006 138030 9 107 M Adjust water flow for emergency eye wash (see teacher)
258481 10/20/2006 138361 9 107 M Secure machinery to floor
258482 10/20/2006 138363 9 107 M Paint safety lines around equipment
262035 10/20/2006 144414 9 8088 M Replace missing cover on GFCI outlet on exterior wall in courtyard adjacent to 9-001
262036 10/20/2006 144416 9 8088 M Replace missing cover on GFCI outlet on exterior wall in courtyard adjacent to 9-192
261941 10/20/2006 144221 00 9599 O Remove storage in fenced transformer enclosure adjacent to kitchen dumpsters
261942 10/20/2006 144223 1 116 O Prohibit use of surge protector to power microwave and toaster oven , plug appliances directly into wall outlet
258339 10/20/2006 138062 10 103A O Prohibit plugging one surge protector into another, plug each surge protector directly into wall outlet
258200 10/20/2006 137788 2 104 O Remove and prohibit combustible residential couch
261955 10/20/2006 144250 2 108G O Maintain room in an orderly manner
258331 10/20/2006 138040 2 108J O Relocate wooden boards blocking access to emergency electrical disconnect and fire extinguisher
262430 10/20/2006 144820 3 101 O Keep tables, surface areas and floor clean of clay dust-follow cleaning instructions of ECO report
255992 10/20/2006 133131 3 104J O Prohibit plugging washer into an extension cord, plug appliances directly into wall outlet
258217 10/20/2006 137826 3 203 O Remove mirror adjacent to door or provide mirror made of tempered glass, safety glass, or stainless steel
261972 10/20/2006 144284 3 214 O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
261976 10/20/2006 144292 4 104 O Remove tires outside S. exterior door - store tires in flammable storage room
258224 10/20/2006 137842 4 201B O Remove and prohibit combustible residential couches
258460 10/20/2006 138315 4 210 O Prohibit use of 13A brown extension cord with multi-outlet end adjacent to teacher's desk
261977 10/20/2006 144294 4 215 O Eliminate and prohibit use of multiple outlet adaptor to power coffee maker and refrigerator - replace multiple outlet adaptor with a surge protector
261987 10/20/2006 144314 5 103A O Remove plywood boards which causes excessive fuel load - Relocate plywood to flammable storage room
258241 10/20/2006 137870 5 201 O Remove inappropriate sign ( Do not use this door to exit classroom)on exterior door - You may re-word to read " Emergency Exit Only "
258451 10/20/2006 138290 5 209C O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
258452 10/20/2006 138300 6 201 O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
258309 10/20/2006 137976 6 203 O Prohibit plugging one surge protector into another at computer stations, plug each surge protector directly into wall outlet
258457 10/20/2006 138308 6 205 O Prohibit plugging surge protector into an extension cord at teacher's desk, plug surge protector directly into wall outlet and prohibit use of 13A extension cord
258244 10/20/2006 137884 7 109 O Replace burned out light bulbs in emergency light fixture
258392 10/20/2006 138173 9 101 O Prohibit plugging one surge protector into another at computer stations, plug each surge protector directly into wall outlet
258427 10/20/2006 138247 10 101C C Provide signage indicating room name and number at appropriate height with raised and Braille characters
258355 10/20/2006 138098 10 104 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
258353 10/20/2006 138094 10 106 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
261953 10/20/2006 144246 13 101 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for flammable storage room
261960 10/20/2006 144260 2 291 C Label walls to indicate 2 hour fire rating
261963 10/20/2006 144266 3 104F C Provide sign indicating maximum occupancy
258202 10/20/2006 137793 3 104J C Install GFCI outlet next to washer
261964 10/20/2006 144268 3 106A C Install GFCI outlet at ice machine and at water line for future washing machine
261965 10/20/2006 144270 3 108D C Provide sign indicating maximum occupancy
258397 10/20/2006 138184 4 209 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
261981 10/20/2006 144302 5 101 C Provide sign in front of teacher's desk indicating emergency shut off valves inside
261983 10/20/2006 144306 5 102 C Provide sign in front of teacher's desk indicating emergency shut off valves inside
261985 10/20/2006 144310 5 103 C Provide sign in front of teacher's desk indicating emergency shut off valves inside
261988 10/20/2006 144316 5 104 C Provide sign in front of teacher's desk indicating emergency shut off valves inside
261992 10/20/2006 144324 5 107 C Provide sign in front of teacher's desk indicating emergency shut off valves inside
261993 10/20/2006 144326 5 108 C Provide sign in front of teacher's desk indicating emergency shut off valves inside
261994 10/20/2006 144328 5 109 C Provide sign in front of teacher's desk indicating emergency shut off valves inside
261995 10/20/2006 144330 5 110 C Provide sign in front of teacher's desk indicating emergency shut off valves inside
261998 10/20/2006 144336 5 111 C Provide sign in front of teacher's desk indicating emergency shut off valves inside
262001 10/20/2006 144343 5 116 C Provide sign in front of teacher's desk indicating emergency shut off valves inside
262006 10/20/2006 144354 6 105 C Provide sign in front of teacher's desk indicating emergency shut off valves inside
262008 10/20/2006 144358 6 106 C Provide sign in front of teacher's desk indicating emergency shut off valves inside
262011 10/20/2006 144364 6 192 C Label doors to indicate that fixed leaf is to remain latched except when moving equipment - Sign provided indicates " this door to remain locked except when moving equipment" and is located on the operable leaf of the double doors
262015 10/20/2006 144372 6 210 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for storage room adjacent to 6-212
262021 10/20/2006 144385 7 190 C Label doors to indicate that fixed leaf is to remain latched except when moving equipment - Sign provided indicates " this door to remain locked except when moving equipment" and is located on the operable leaf of the double doors
262022 10/20/2006 144387 7 191 C Label walls to indicate 2 hour fire rating
262024 10/20/2006 144391 7 215 C Replace missing threshold or floor tile at door
262025 10/20/2006 144393 7 215A C Replace missing glazing in door
262026 10/20/2006 144395 7 291 C Label walls to indicate 2 hour fire rating
262028 10/20/2006 144399 7 292 C Label doors to indicate that fixed leaf is to remain latched except when moving equipment - Sign provided indicates " this door to remain locked except when moving equipment" and is located on the operable leaf of the double doors
258326 10/20/2006 138038 2 113 MS Adjust fire doors adjacent to 2-113A to latch properly
258198 10/20/2006 137781 3 108C MS Remove hasp and padlock from door
255993 10/20/2006 133133 3 108D MS Relocate bench blocking clear access to exterior door - bench is currently bolted to floor
258383 10/20/2006 138154 3 192 MS Provide current inspection tag for fire extinguisher
258393 10/20/2006 138178 3 291 MS Provide current inspection tag for fire extinguisher
258394 10/20/2006 138180 3 292 MS Provide current inspection tag for fire extinguisher
258337 10/20/2006 138058 4 180 MS Close hatch on ceiling
258267 10/20/2006 137912 5 105 MS Provide current inspection tag for fire extinguisher
258268 10/20/2006 137914 5 115 MS Provide current inspection tag for fire extinguisher - tag not punched
258373 10/20/2006 138133 10 190 OS Remove storage from boiler room
261950 10/20/2006 144240 11 101 OS Prohibit storage of propane gas can
258385 10/20/2006 138158 11 105 OS Remove storage from electrical room
261954 10/20/2006 144248 2 108G OS Remove light pole extending above ceiling tile to prevent spread of fire and smoke
258412 10/20/2006 138217 3 110 OS Prohibit use of wedge to hold fire door in open position
258384 10/20/2006 138156 3 192 OS Remove storage from mechanical room
258402 10/20/2006 138192 3 210 OS Prohibit use of wedge to hold fire door in open position
258403 10/20/2006 138199 3 213 OS Prohibit use of wedge to hold fire door in open position
261973 10/20/2006 144286 3 214 OS Remove and prohibit use of toaster oven
258395 10/20/2006 138182 3 292 OS Remove storage from mechanical room
258335 10/20/2006 138055 4 107 OS Arrange desks to maintain a minimum 3 ft clear aisle to exterior door
261978 10/20/2006 144296 4 292 OS Prohibit recharging batteries for floor cleaning machines in room
261979 10/20/2006 144298 4 292 OS Remove storage from mechanical room
258411 10/20/2006 138213 5 103 OS Prohibit use of wedge to hold fire door in open position
258374 10/20/2006 138136 5 191 OS Remove storage from electrical room
258376 10/20/2006 138141 5 192 OS Remove storage from mechanical room
258406 10/20/2006 138203 5 209 OS Prohibit use of wedge to hold fire door in open position
258398 10/20/2006 138188 5 291 OS Remove storage from mechanical room
258375 10/20/2006 138139 6 191 OS Remove storage from electrical room
258389 10/20/2006 138166 6 192 OS Prohibit charging golf cart batteries in room
258409 10/20/2006 138211 7 105 OS Prohibit use of wedge to hold fire door in open position
262017 10/20/2006 144376 7 106 OS Remove and prohibit use of toaster oven
258242 10/20/2006 137880 7 112 OS Relocate table and desks to maintain a minimum 3 ft clear aisle to corridor door
258408 10/20/2006 138209 7 115 OS Prohibit use of wedge to hold fire door in open position
258390 10/20/2006 138168 7 190 OS Remove storage from mechanical room
258407 10/20/2006 138206 7 203 OS Prohibit use of wedge to hold fire door in open position
261962 10/20/2006 144264 3 101C CS Provide new fire extinguisher in kiln area
258382 10/20/2006 138151 4 171 CS Provide fire extinguisher in elevator machine room
258379 10/20/2006 138145 4 191 CS Provide fire extinguisher in electrical room
261943 10/20/2006 144226 10 101B FS Repair problems with fire alarm system - Troubles indicated on panel