DIAMOND VIEW ELEMENTARY
 
DIAMOND VIEW ELEMENTARY
5300 Haverhill Road
Greenacres, 33463
FISH Drill Down
 Campus Info.
 Buildings:4 Rooms:317
 Portables:23
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
415519 04/11/2018 476532 1 132B M Repair fan for kiln room, fan runs constantly and staff reports that the fan can not be turned off
415492 04/02/2018 476476 00 0000 M Remove plants growing from covered walk adjacent to portable classrooms
392871 04/02/2018 427730 1 0000 M Replace damaged signage indicating room name and number at appropriate height with raised and Braille characters for 4 exterior mechanical rooms 1-199G, 1-199H, 1-199F, 1-199K and boiler room 1-199J
415517 04/02/2018 476528 1 005 M Replace missing magnetic release hold open device for fire door adjacent to 1-132
415629 04/02/2018 476762 1 006 M Adjust door closer at 1-113 to control speed of closing door
415609 04/02/2018 476719 1 007 M Replace missing magnetic release hold open device for smoke door at 1-102A
415478 04/02/2018 476447 1 101 M Determine cause of water damaged ceiling tiles and replace tiles
415605 04/02/2018 476714 1 103A M Secure loose escutcheon on fire sprinkler head
415529 04/02/2018 476552 1 104 M Replace missing magnetic release hold open device for fire door adjacent to 1-142
415606 04/02/2018 476716 1 105 M Replace missing ceiling tiles
415612 04/02/2018 476726 1 106 M Provide current dated flame resistance label on stage curtain
415645 04/02/2018 476799 1 107 M Adjust door closer to control speed of closing door
415601 04/02/2018 476706 1 116A M Determine cause of water damaged ceiling tiles and replace tiles
415597 04/02/2018 476697 1 119 M Adjust door closer to control speed of closing door
415536 04/02/2018 476566 1 123 M Determine cause of water damaged ceiling tiles and replace tiles
415538 04/02/2018 476570 1 127 M Determine cause of water damaged ceiling tiles and replace tiles
415540 04/02/2018 476574 1 129 M Adjust door closer to control speed of closing door
415614 04/02/2018 476732 1 130 M Determine cause of water damaged ceiling tiles and replace tiles
415518 04/02/2018 476530 1 132 M Replace missing ceiling tiles
415520 04/02/2018 476534 1 134 M Adjust door closer to control speed of closing door
415521 04/02/2018 476536 1 135B M Repair exhaust fan in bathroom
415522 04/02/2018 476538 1 137 M Determine cause of water damaged ceiling tiles and replace tiles
415523 04/02/2018 476540 1 141B M Repair exhaust fan in bathroom
415524 04/02/2018 476542 1 142 M Adjust door closer to control speed of closing door
415525 04/02/2018 476544 1 144 M Determine cause of water damaged ceiling tiles and replace tiles
415527 04/02/2018 476548 1 147 M Determine cause of water damaged ceiling tiles and replace tiles
415528 04/02/2018 476550 1 147C M Determine cause of water damaged ceiling tiles and replace tiles
415530 04/02/2018 476554 1 151 M Determine cause of water damaged ceiling tiles and replace tiles
415531 04/02/2018 476556 1 151 M Repair damaged wall adjacent to exterior door
415533 04/02/2018 476560 1 152 M Determine cause of water damaged ceiling tiles and replace tiles
415532 04/02/2018 476558 1 153 M Repair exterior door to latch properly
415535 04/02/2018 476564 1 153 M Prohibit running electrical cord for projector directly into ceiling
415534 04/02/2018 476562 1 154 M Prohibit running electrical cord for projector directly into ceiling
415630 04/02/2018 476766 1 181 M Determine cause of water damaged ceiling tiles and replace tiles
415633 04/02/2018 476772 1 181 M Replace missing sign indicating the number of floor cleaning machines approved for charging in room
415641 04/02/2018 476785 1 181 M Repair or replace damaged drain pan for hot water heater
415642 04/02/2018 476791 1 181 M Provide edge protection for hot water heater drain pan which is below 6 feet 8 inches
415627 04/02/2018 476757 1 191 M Contain exposed wires at open junction box above electrical panel 1LA
415596 04/02/2018 476694 1 195 M Adjust door closer to control speed of closing door
415537 04/02/2018 476568 1 199D M Adjust door closer to control speed of closing door
415489 04/02/2018 476469 1 199F M Secure and contain exposed wires at junction boxes (x2) on north and west walls
415490 04/02/2018 476472 2 101 M Remove plants growing from gutters and downspouts
415491 04/02/2018 476474 2 101A M Adjust door closer to control speed of closing door
415618 04/02/2018 476739 3 191 M Replace missing guards for pump motors for CP-2, SP-1 and SP-2
415483 04/02/2018 476457 P 6155 M Adjust door closer on east door to control speed of closing door
415484 04/02/2018 476459 P 6155 M Repair emergency lighting at east door
415500 04/02/2018 476492 P 6156 M Repair emergency lighting (x2)
415479 04/02/2018 476449 P 9677 M Repair emergency lighting at west door
415481 04/02/2018 476453 P 9678 M Secure loose base on wall at east door
415482 04/02/2018 476455 P 9679 M Adjust door closer on east door to control speed of closing door
415486 04/02/2018 476463 P 9821 M Repair emergency lighting at west door
392747 04/02/2018 427450 P 9821 M Repair exhaust fan in bathroom
415488 04/02/2018 476467 P 9822 M Repair emergency lighting at west door
415503 04/02/2018 476499 P 9906 M Repair emergency lighting (x2)
415504 04/02/2018 476501 P 9907 M Replace missing base on east wall
415505 04/02/2018 476503 P 9908 M Adjust door closer on east door to control speed of closing door
415506 04/02/2018 476505 P 9908 M Repair emergency lighting at east door
415512 04/02/2018 476517 P 9911 M Adjust door closer on west door to control speed of closing door
415514 04/02/2018 476521 P 9911 M Repair or replace rusty, damaged east door
415513 04/02/2018 476519 P 9912 M Repair damaged wall finish adjacent to bathroom door
415498 04/02/2018 476488 P 9914 M Repair emergency lighting at west door
415496 04/02/2018 476484 P 9915 M Repair emergency lighting at west door
415497 04/02/2018 476486 P 9915 M Adjust door closer on east door to control speed of closing door
415495 04/02/2018 476482 P 9916 M Secure loose base on wall at west door
415493 04/02/2018 476478 P 9917 M Repair emergency lighting at east door
415494 04/02/2018 476480 P 9917 M Secure loose base on wall at west door
415613 04/02/2018 476730 1 101G O Keep area within 18 inches of fire sprinkler head clear and unobstructed
415646 04/02/2018 476801 1 107A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
415644 04/02/2018 476797 1 110 O Remove and prohibit decorative plastic sheets on walls
415643 04/02/2018 476794 1 111 O Keep area within 18 inches of fire sprinkler heads clear and unobstructed
415539 04/02/2018 476572 1 129 O Prohibit plugging surge protector into surge protector
415526 04/02/2018 476546 1 146 O Remove and prohibit air freshener, plug in style
415509 04/02/2018 476511 P 9911 O Remove and prohibit excessive flammable paper on walls, coverage may not exceed 20 percent of each wall in a room without fire sprinklers
415515 04/02/2018 476523 P 9912 O Prohibit use of white 13A extension cord at microwave
415604 04/02/2018 476712 1 104E MS Provide current inspection tag for fire extinguisher
415599 04/02/2018 476699 1 116C MS Repair thumb latch to enable door to be locked and unlocked properly
415603 04/02/2018 476709 1 190 MS Replace missing fire extinguisher
415501 04/02/2018 476494 P 6156 MS Repair bathroom door to unlock properly
415480 04/02/2018 476451 P 9678 MS Repair bathroom door to unlock properly
415616 04/02/2018 476736 1 009 OS Relocate shelves and chairs in corridor to maintain clear aisle to exit
415485 04/02/2018 476461 P 6153 OS Maintain clear aisle to east exit
415507 04/02/2018 476507 P 9909 OS Relocate table at east door to maintain clear aisle to exit
415508 04/02/2018 476509 P 9910 OS Relocate desk at east door to maintain clear aisle to exit
415510 04/02/2018 476513 P 9911 OS Relocate yellow shelf in bathroom to maintain clear aisle to exit
415511 04/02/2018 476515 P 9911 OS Relocate file cabinets at east door to maintain clear aisle to exit
415499 04/02/2018 476490 P 9913 OS Relocate bookshelf to maintain clear aisle to exit
261053 04/02/2018 143267 2 0000 N/A No violations observed
261054 04/02/2018 143268 3 0000 N/A No violations observed
261071 04/02/2018 143285 P 6153 N/A No violations observed
261073 04/02/2018 143287 P 6155 N/A No violations observed
261074 04/02/2018 143288 P 6156 N/A No violations observed
261056 04/02/2018 143270 P 9677 N/A No violations observed
261057 04/02/2018 143271 P 9678 N/A No violations observed
261058 04/02/2018 143272 P 9679 N/A No violations observed
303294 04/02/2018 232112 P 9821 N/A No violations observed
303295 04/02/2018 232114 P 9822 N/A No violations observed
261059 04/02/2018 143273 P 9906 N/A No violations observed
261060 04/02/2018 143274 P 9907 N/A No violations observed
261061 04/02/2018 143275 P 9908 N/A No violations observed
261062 04/02/2018 143276 P 9909 N/A No violations observed
261063 04/02/2018 143277 P 9910 N/A No violations observed
261064 04/02/2018 143278 P 9911 N/A No violations observed
261065 04/02/2018 143279 P 9912 N/A No violations observed
261066 04/02/2018 143280 P 9913 N/A No violations observed
261067 04/02/2018 143281 P 9914 N/A No violations observed
261068 04/02/2018 143282 P 9915 N/A No violations observed
261069 04/02/2018 143283 P 9916 N/A No violations observed
261070 04/02/2018 143284 P 9917 N/A No violations observed
392880 11/15/2017 427749 1 0000 M Trim trees overhanging roof of building 1 and covered walkways
392883 11/15/2017 427755 1 199F M Repair leaking air handler
415516 11/15/2017 476526 1 199K M Make repairs as noted on fire sprinkler inspection report
261052 11/15/2017 143266 1 0000 N/A No violations observed
261072 11/15/2017 143286 P 6154 N/A No violations observed
303296 11/15/2017 232116 P 9823 N/A No violations observed
303297 11/15/2017 232118 P 9824 N/A No violations observed
392841 05/03/2017 427665 1 160 M Post sign indicating primary and secondary evacuation routes in contrasting colors
392784 05/02/2017 427537 1 199J M Repair leaking copper plumbing at tee
392760 03/13/2017 427476 1 109C M Repair exhaust fan in bathroom
392887 03/13/2017 427764 1 129B M Repair exhaust fan in bathroom
392808 03/13/2017 427592 1 143B M Repair exhaust fan in bathroom
392757 03/13/2017 427470 2 101D M Repair exhaust fan in bathroom
392885 12/01/2016 427759 1 0000 M Repair panic bar on gate at 1-199F to latch. Latch is retracted and will not come out
392850 12/01/2016 427686 1 0000 M Caulk sink to wall in bathrooms 1-104D, 1-122C, 1-144B, 1-116D, 1-119D, 1-002A , 1-157B and 1-110B
392860 12/01/2016 427706 1 0000 M Seal bathroom wall at sink to provide impervious wall finish in bathrooms 1-116C, 1-119C, 1-137B, 1-139B, 1-140B, 1-151B, 1-152B and 1-154B
392863 12/01/2016 427713 1 0000 M Grind down uneven concrete at red stripe on walkway at 1-199H
392872 12/01/2016 427732 1 0000 M Take down sharp edges on screws on steel push pads on inside of doors for bathrooms 1-001B and 1-001C in corridor adjacent to Cafeteria
392864 12/01/2016 427715 1 005 M Adjust NE corridor door to exterior to latch properly
392754 12/01/2016 427464 1 101Q M Provide cover plate for data outlet at copier
392785 12/01/2016 427539 1 106D M Anchor toilet to floor
392759 12/01/2016 427474 1 110B M Replace missing screw for light switch plate
392866 12/01/2016 427719 1 123 M Determine cause of water damaged ceiling tiles and replace tiles
392867 12/01/2016 427721 1 124 M Determine cause of water damaged ceiling tiles and replace tiles
392868 12/01/2016 427723 1 125 M Determine cause of water damaged ceiling tiles and replace tiles
392838 12/01/2016 427660 1 125 M Secure loose door handle
392836 12/01/2016 427655 1 126C M Repair leaking flush valve on toilet
392843 12/01/2016 427672 1 135 M Repair inoperable drinking fountain
392761 12/01/2016 427478 1 135 M Secure loose faucet to sink
392873 12/01/2016 427735 1 138B M Finish bathroom wall at toilet to provide impervious wall finish
392807 12/01/2016 427587 1 143B M Seal bathroom wall at sink and grab rail to provide impervious wall finish
392878 12/01/2016 427745 1 144 M Determine cause of water damaged ceiling tiles and replace tiles
392800 12/01/2016 427570 1 145A M Repair door lock. Key will not go completely into lock and room cannot be locked
392804 12/01/2016 427582 1 145B M Paint repair on bathroom wall at sink to provide impervious wall finish
392890 12/01/2016 427770 1 147 M Adjust door to exterior to latch properly
392889 12/01/2016 427768 1 149 M Adjust door to exterior to latch properly
392879 12/01/2016 427747 1 151 M Determine cause of water damaged ceiling tiles and replace tiles
392842 12/01/2016 427669 1 152 M Provide new sign indicating primary and secondary evacuation routes in contrasting colors. School has changed evacuation route
392888 12/01/2016 427766 1 153 M Adjust door to exterior to latch properly
392891 12/01/2016 427772 1 157 M Determine cause of water damaged ceiling tiles and replace tiles
392839 12/01/2016 427662 1 162 M Secure evacuation map frame to wall
392848 12/01/2016 427682 1 181 M Determine cause of water damaged ceiling tiles and replace tiles
392849 12/01/2016 427684 1 181 M Repair drain leak on emergency eyewash
392869 12/01/2016 427725 1 186 M Repair or cover damaged wall at floor sink to provide impervious wall finish. Stainless steel, tile or lexan
392870 12/01/2016 427727 1 186 M Repair or cover damaged wall at floor sink to provide impervious wall finish. Stainless steel, tile or lexan. Plan indicates 2 rooms 1-186. One in Media center and 1 at 1-199
392845 12/01/2016 427676 1 192 M Provide certification that all student occupied spaces have emergency lights and all are operable. Last certification 6-26-15
392791 12/01/2016 427555 1 199A M Replace missing screws for covers of panels 1LD
392886 12/01/2016 427761 1 199G M Repair leaking air handler
392846 12/01/2016 427678 1 199K M Make necessary repairs to fire sprinkler system as indicated on inspection report
392881 12/01/2016 427751 2 0000 M Replace sand that fills eroded area at 2-180 with rock. Sand washes away and blows across covered play area
392756 12/01/2016 427468 2 101D M Adjust door to latch properly
392875 12/01/2016 427739 3 0000 M Re-caulk joints on exterior walls
392876 12/01/2016 427741 3 0000 M Remove vegetation growing in cooling tower enclosure
392877 12/01/2016 427743 3 0000 M Repair or replace rusted door frame for cooling tower enclosure
392874 12/01/2016 427737 3 191 M Re-insulate chilled water pump
392782 12/01/2016 427532 P 0000 M Modify or improve drainage from rear of concrete portables. Many drains are covered and filled with dirt resulting in storm water flowing out of stopped up downspouts. Remove black pipe and install splash blocks at bottom of downspouts to direct water away from portables
392735 12/01/2016 427425 P 6153 M Remove tree at rear of unit growing on sewer line
392736 12/01/2016 427427 P 6154 M Adjust rear door to latch properly
392737 12/01/2016 427429 P 6155 M Repair emergency lighting at front door
392738 12/01/2016 427431 P 6155 M Caulk bathroom sink to wall and seal wall to provide impervious finish
392740 12/01/2016 427436 P 6155 M Caulk and seal back splash at sink
392741 12/01/2016 427438 P 9677 M Provide new sign indicating Fire Alarm Pull Station Inside
392742 12/01/2016 427440 P 9678 M Repair emergency lighting at front door
392743 12/01/2016 427442 P 9678 M Replace missing screw for spout of drinking fountain
392744 12/01/2016 427444 P 9678 M Caulk sink to wall
392745 12/01/2016 427446 P 9679 M Replace missing screw for spout of drinking fountain
392746 12/01/2016 427448 P 9679 M Caulk sink to wall
392748 12/01/2016 427452 P 9822 M Exterior 12 X 12 junction box partially buried. Remove dirt from beneath box so that it no longer contacts ground
392749 12/01/2016 427454 P 9822 M Caulk sink to wall
392750 12/01/2016 427456 P 9822 M Anchor toilet to floor
392751 12/01/2016 427458 P 9823 M Repair emergency lighting at front door
392752 12/01/2016 427460 P 9823 M Seal wall to provide impervious finish at bathroom sink
392753 12/01/2016 427462 P 9824 M Adjust rear door to latch properly
392762 12/01/2016 427480 P 9906 M Exterior 12 X 12 junction box is partially buried. Remove dirt from beneath box so that it no longer contacts ground
392763 12/01/2016 427482 P 9907 M Caulk bathroom sink to wall and provide impervious wall finish
392764 12/01/2016 427486 P 9908 M Caulk bathroom sink to wall and provide impervious wall finish
392765 12/01/2016 427494 P 9909 M Replace missing impervious floor finish in bathroom
392766 12/01/2016 427496 P 9909 M Provide sign indicating Fire Alarm Pull Station Inside
392767 12/01/2016 427498 P 9910 M Caulk sink to wall in bathroom
392768 12/01/2016 427500 P 9911 M Caulk sink to wall and provide impervious wall finish in bathroom
392769 12/01/2016 427502 P 9912 M Repair emergency lighting X 2
392770 12/01/2016 427504 P 9913 M Exterior 12 X 12 junction box is partially buried. Remove dirt from beneath box so that it no longer contacts ground
392771 12/01/2016 427506 P 9913 M Reconnect downspout
392772 12/01/2016 427509 P 9914 M Exterior 12 X 12 junction box is partially buried. Remove dirt from beneath box so that it no longer contacts ground
392774 12/01/2016 427513 P 9915 M Repair emergency lighting at front door
392775 12/01/2016 427515 P 9915 M Secure loose base to wall at toilet
392776 12/01/2016 427517 P 9915 M Exterior 12 X 12 junction box is partially buried. Remove dirt from beneath box so that it no longer contacts ground
392777 12/01/2016 427519 P 9915 M Provide impervious wall finish at bathroom sink
392779 12/01/2016 427526 P 9916 M Repair emergency lighting at rear door
392780 12/01/2016 427528 P 9917 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they no longer contact ground
392781 12/01/2016 427530 P 9917 M Determine cause of water damaged ceiling tiles and replace tiles at AC unit
392861 12/01/2016 427709 1 005 O Remove and prohibit hanging green paper from ceiling of corridor
392755 12/01/2016 427466 1 109A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
392834 12/01/2016 427647 1 148 O Remove rug with curled edge or tape edge down to prevent tripping hazard
392826 12/01/2016 427635 1 149 O Remove and prohibit plug-in air freshener
392821 12/01/2016 427622 1 155 O Remove and prohibit attaching paper and decorations to blinds
392847 12/01/2016 427680 1 181 O Maintain clear access to emergency eye wash - shower
392739 12/01/2016 427433 P 6155 O Remove and prohibit paper covering window in door. allowable for code situation only
392773 12/01/2016 427511 P 9915 O Provide clear access to electrical panel
392865 12/01/2016 427717 1 007 MS Adjust fire door to cafeteria to latch properly
392811 12/01/2016 427595 1 133 MS Provide current inspection tag for fire extinguisher or remove un-needed extinguisher
392825 12/01/2016 427632 1 144C MS Provide current inspection tags for ABC and K fire extinguishers. Remove un-needed ABC Extinguisher
392824 12/01/2016 427626 1 147C MS Provide current inspection tags for ABC and K fire extinguishers. Remove un-needed ABC extinguisher
392822 12/01/2016 427624 1 151C MS Provide current inspection tags for ABC and K fire extinguishers. Remove un-needed ABC extinguisher
392884 12/01/2016 427757 1 190 MS Provide current inspection tag for fire extinguisher or remove un-needed extinguisher
392882 12/01/2016 427753 2 101F MS Provide current inspection tag for fire extinguisher
392783 12/01/2016 427535 1 191 OS Remove storage from electrical room
392837 12/01/2016 427658 1 197 OS Remove storage from electrical room
392778 12/01/2016 427522 P 9915 OS Maintain 3 foot clear aisle to rear exit
377665 08/25/2016 394859 1 199K M Make necessary repairs to fire sprinkler system as indicated on inspection report (system has red tag)
365448 01/06/2016 368225 1 0000 M Repair gates at each end of chain link fencing play area at E side of Bldg. to work properly - One gate drags on the floor, the other gate hinges are stiff
377656 01/06/2016 394839 1 001C M Replace missing toilet seat in girls bathroom
377634 01/06/2016 394794 1 101 M Determine cause of water damaged ceiling tiles in main office and replace tiles
377640 01/06/2016 394807 1 122C M Repair ventilation fan in girls restroom
377641 01/06/2016 394809 1 122D M Repair ventilation fan in boys restroom
377642 01/06/2016 394811 1 124 M Repair or replace leaking fire sprinkler plumbing around sprinkler head
377647 01/06/2016 394821 1 132 M Determine cause of water damaged ceiling tiles next to windows and replace tiles
377648 01/06/2016 394823 1 132B M Repair exhaust fan in kiln room
377650 01/06/2016 394827 1 137 M Secure faucet to sink
377653 01/06/2016 394833 1 141B M Repair ventilation fan in bathroom
377645 01/06/2016 394817 1 146 M Repair or replace leaking fire sprinkler plumbing at sprinkler head adjacent to bathroom
377646 01/06/2016 394819 1 146 M Determine cause of water damaged ceiling tiles at exterior exit door and replace tiles
377643 01/06/2016 394813 1 151 M Determine cause of water damaged ceiling tiles at windows and replace tiles
377637 01/06/2016 394800 1 163 M Repair or replace leaking fire sprinkler plumbing at sprinkler head next to entrance door
377659 01/06/2016 394846 1 190A M Replace missing ceiling tiles
377662 01/06/2016 394852 1 191 M Repair door on electric panel 1LA to close and latch properly
377663 01/06/2016 394854 1 192 M Provide current emergency generator and lighting certification (current certification expired 7-30-15)
377664 01/06/2016 394857 1 199K M Repair leaks in chilled water piping (water from leak is standing on floor)
377668 01/06/2016 394865 2 101F M Repair doors to close properly (doors hit against each other and do not close)
365464 01/06/2016 368263 3 0000 M Remove all vegetation growing along walls in exterior chillers room
377679 01/06/2016 394889 P 6153 M Repair emergency lighting at rear door
377677 01/06/2016 394885 P 9678 M Repair emergency lighting at rear door
377678 01/06/2016 394887 P 9679 M Repair emergency lighting at front door
365456 01/06/2016 368248 P 9821 M Repair exhaust fan in bathroom
377669 01/06/2016 394867 P 9906 M Repair rear door to close properly
377670 01/06/2016 394871 P 9907 M Repair emergency lighting at front door
377671 01/06/2016 394873 P 9907 M Repair rear door to close properly
377675 01/06/2016 394881 P 9916 M Repair emergency lighting at front door
377676 01/06/2016 394883 P 9917 M Repair emergency lighting at rear door
377635 01/06/2016 394796 1 101Q O Eliminate multi plug outlet adaptor (6-way adaptor) above counter top
377649 01/06/2016 394825 1 136 O Remove and prohibit combustible beanbag chairs (X2)
377651 01/06/2016 394829 1 137 O Remove and prohibit hanging drapery and paper decorations from ceiling
377652 01/06/2016 394831 1 139 O Prohibit plugging surge protector into surge protector at teachers desk
365435 01/06/2016 368203 1 142 O Secure electrical cord cover strips to flooring to eliminate trip hazard (X2) - you may tape to floor along both sides of cover strips
365438 01/06/2016 368209 1 151 O Prohibit plugging two white extension cords with multiple outlet end into surge protector under teacher desk and eliminate use of extension cords with multiple outlet end
377638 01/06/2016 394803 1 163A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
377660 01/06/2016 394848 1 181 O Remove and prohibit combustible (residential) furniture (overstuffed chair)
377667 01/06/2016 394863 2 101B O Replace bulbs in light fixture in coaches bathroom
377672 01/06/2016 394875 P 9913 O Remove and prohibit hanging paper and decorations from ceiling
377674 01/06/2016 394879 P 9913 O Eliminate use of white, multi plug outlet extension cord powering icicle lights on ceiling
377666 01/06/2016 394861 P 0000 C Provide impervious wall finish on bathroom walls in Portables 10, 12, 16, 18, 19 (there are no signs indicating walls have been made impervious)
377654 01/06/2016 394835 1 0000 MS Verify activation of fire alarm system accomplishes incidental functions (Horn/Strobes were not functioning in many parts of the building and portables when fire drill was conducted on August 26, 2015, many occupants were not aware there was a fire drill in progress until they were told to evacuate over the P.A. system)
377639 01/06/2016 394805 1 002 MS Replace missing parts on magnetic release hold open device for fire doors in corridor adjacent to 1-114
377644 01/06/2016 394815 1 003 MS Repair magnetic release hold open device for smoke door in corridor adjacent to 1-152 (adjustment screw and magnet keep falling off)
377636 01/06/2016 394798 1 003 MS Repair magnetic release hold open device for smoke door in corridor adjacent to 1-120 (parts missing from hold open device)
377655 01/06/2016 394837 1 005 MS Repair door hardware at north exit doors of corridor so doors will latch properly
377658 01/06/2016 394844 1 104E MS Provide current inspection tag for fire extinguisher inside kitchen manager's office
377657 01/06/2016 394842 1 106C MS Adjust west exit door going into corridor 1-007 to close and latch properly
377661 01/06/2016 394850 1 191 OS Remove storage from electrical room
377673 01/06/2016 394877 P 9913 OS Maintain clear aisle to exit (must maintain at least 3 ft. clear access to all exits)
351480 08/26/2015 337750 1 129B M Repair exhaust fan in bathroom
365466 08/26/2015 368268 1 141 O Prohibit plugging white extension cord into surge protector - eliminate use of extension cord with multiple outlet end
365487 11/21/2014 368306 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable. Old certificate in 1-192
365444 11/21/2014 368221 1 003 M Repair door hardware on smoke door adjacent to 1-152 to work properly - right leaf did not open
365470 11/21/2014 368274 1 103 M Provide insulated cover for exposed GFCI electrical outlet under registers in serving area
365442 11/21/2014 368217 1 122 M Repair drinking spout at sink to work porperly
365445 11/21/2014 368223 1 157 M Determine cause of water damaged ceiling tiles and replace tiles
365480 11/21/2014 368292 1 181 M Replace heavily rusted hot water heater in custodial receiving
365490 11/21/2014 368314 1 199H M Repair air handler to eliminate water leak
351486 11/21/2014 337762 2 101D M Repair exhaust fan in bathroom
351485 11/21/2014 337760 2 101E M Repair exhaust fan in bathroom
365451 11/21/2014 368237 2 101F M Replace damaged Braille signage indicating room name and number
365433 11/21/2014 368199 P 0000 M Keep dirt away from exterior junction boxes at all portables
365460 11/21/2014 368255 P 6153 M Repair emergency lighting above front door
365458 11/21/2014 368250 P 9821 M Secure toilet to floor and caulk gap between toilet and floor
365455 11/21/2014 368244 P 9822 M Adjust back door to latch properly
365453 11/21/2014 368241 P 9824 M Adjust water flow to drinking spout at sink
365440 11/21/2014 368213 P 9908 M Repair damaged vinyl base along wall adjacent to back door
365441 11/21/2014 368215 P 9911 M Repair emergency lighting above front door
365434 11/21/2014 368201 1 101M O Prohibit plugging extension cord into surge protector under desk and eliminate used of white extension cord with multiple outlet end
365477 11/21/2014 368289 1 111 O Eliminate string line below 6 feet 8 inches adjacent to sinks
365473 11/21/2014 368282 1 115 O Remove and prohibit air freshener
365472 11/21/2014 368280 1 115A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
365443 11/21/2014 368219 1 129 O Remove and prohibit hanging large anchor chart paper from ceiling
365436 11/21/2014 368205 1 144C O Remove all storage from stove burners to eliminate fire hazard
365437 11/21/2014 368207 1 146B O Remove all storage under and adjacent to bathroom sink
365462 11/21/2014 368259 P 9677 O Remove and prohibit combustible curtains on window
365439 11/21/2014 368211 P 9917 O Remove paper covering electrical outlet adjacent to writing board
365471 11/21/2014 368278 1 102 MS Remove hold open device from fire doors at south side of dining room (X4)
351494 11/21/2014 337781 1 102 MS Adjust NW fire door to latch properly
365482 11/21/2014 368298 1 191 MS Remove mechanical storage from electrical room
365475 11/21/2014 368285 1 107 OS Relocate desk adjacent to corridor door to maintain clear path to exit
365483 11/21/2014 368301 1 191 OS Remove operational storage from electrical room
365488 11/21/2014 368312 1 193 OS Remove custodial storage from main electrical room
351575 08/27/2014 337966 P 9908 M Repair unlock hardware on bathroom door to work properly
351581 08/27/2014 337978 P 9917 M Repair unlock hardware on bathroom door to work properly - lock sticks
351500 11/22/2013 337791 1 0000 M Trim low branches in playground at East side of Bldg.
351501 11/22/2013 337794 1 0000 M Repair pannic hardware to work properly on north gate in playground outside 1-144
351474 11/22/2013 337738 1 002 M Replace missing magnetic hold open hardware on fire door in corridor adjacent to 1-002
351472 11/22/2013 337734 1 101G M Secure ceiling tile in place
351496 11/22/2013 337783 1 103 M Secure loose divider railing in serving area
351493 11/22/2013 337777 1 106C M Repair door to open and close properly - West door facing stage ramp rubs on frame
351506 11/22/2013 337807 1 111 M Adjust water flow for drinking spout
351473 11/22/2013 337736 1 114 M Replace sagging ceiling tile adjacent to windows
351481 11/22/2013 337752 1 123B M Repair exhaust fan in bathroom
351476 11/22/2013 337742 1 124 M Secure ceiling tile in place adjacent to corridor door
351482 11/22/2013 337754 1 125B M Repair exhaust fan in bathroom
351479 11/22/2013 337748 1 129B M Patch hole in wall adjacent to bathroom light switch
351515 11/22/2013 337829 1 130G M Secure shelving to wall (x2)
351510 11/22/2013 337816 1 151 M Determine cause of water damaged ceiling tiles and replace tiles
351517 11/22/2013 337834 1 157B M Repair cracked caulk around bathroom sink
351516 11/22/2013 337831 1 159 M Secure loose faucet to sink
351508 11/22/2013 337812 1 162 M Secure ceiling tile in place
351484 11/22/2013 337758 2 101 M Repair undermined area in landscape at NW corner of PE pavilion - see PE teacher
351586 11/22/2013 337988 P 6154 M Repair emergency lighting above front door
351582 11/22/2013 337980 P 9677 M Repair emergency lighting above front door
351585 11/22/2013 337986 P 9678 M Repair cracked caulk around sink in bathroom
351488 11/22/2013 337766 P 9822 M Repair emergency lighting above back door
351574 11/22/2013 337964 P 9908 M Repair emergency lighting above front door
351573 11/22/2013 337962 P 9909 M Repair emergency lighting above front door
351572 11/22/2013 337960 P 9910 M Repair emergency lighting above front door
351577 11/22/2013 337970 P 9914 M Repair emergency lighting above front door
351579 11/22/2013 337974 P 9917 M Repair emergency lighting above front door
351580 11/22/2013 337976 P 9917 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to AC unit
351470 11/22/2013 337730 1 101 O Prohibit plugging surge protector into surge protector - plug each surge protector directly into wall outlet in main office under monitor screen
351471 11/22/2013 337732 1 101G O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
351483 11/22/2013 337756 1 123 O Remove and prohibit combustible beanbag chairs (x3)
351477 11/22/2013 337744 1 124 O Remove paper covering room name and number sign with Braille characters adjacent to corridor door
351475 11/22/2013 337740 1 124A O Remove cardboard above top shelf to keep area within 18 inches of fire sprinkler head clear and unobstructed
351478 11/22/2013 337746 1 126 O Remove paper cover electrical outlets - under writing board and at SW corner
351504 11/22/2013 337803 1 131 O Prohibit plugging surge protector into surge protector at teacher desk - plug each surge protector directly into wall outlet
351505 11/22/2013 337805 1 131A O Prohibit plugging microwave into cart electrical outlet strip - plug directly into permanent electrical outlet
351490 11/22/2013 337771 1 138 O Remove and prohibit paper on window blinds
351489 11/22/2013 337768 1 138A O Remove and prohibit combustible black beanbag chairs in closet (x2)
351491 11/22/2013 337775 1 140 O Remove and prohibit yellow flammable vinyl sheathing under sink
351509 11/22/2013 337814 1 143 O Remove and prohibit fabric covering window in door
351512 11/22/2013 337820 1 144C O Remove storage from stove burners to eliminate fire hazard - Trays covered with plastic were on burners
351514 11/22/2013 337827 1 159A O Remove and prohibit combustible beanbag chair
351502 11/22/2013 337797 1 181 O Prohibit plugging appliances (washing machine, microwave and toaster oven) into surge protector - plug directly into permanent electrical outlet
351587 11/22/2013 337990 P 6153 O Remove and prohibit flammable shower curtain adjacent to bathroom door
351590 11/22/2013 337996 P 9677 O Provide cover strip for electrical cords running across floor and secure cover strip to flooring to eliminte trip hazard
351583 11/22/2013 337982 P 9677 O Prohibit plugging surge protector into extension cord for projector - Replace with another surge (long enough cord to reach wall outlet)
351584 11/22/2013 337984 P 9678 O Remove and prohibit combustible shear curtains covering window
351576 11/22/2013 337968 P 9906 O Remove and prohibit air freshener under sink
351588 11/22/2013 337992 P 9909 O Provide cover strip for electrical cords running across floor and secure cover strip to flooring to eliminte trip hazard
351569 11/22/2013 337954 P 9911 O Remove paper in light fixtures to eliminate hazardous condition
351570 11/22/2013 337956 P 9911 O Remove and prohibit combustible residential couch
351571 11/22/2013 337958 P 9911 O Remove and prohibit combustible curtains covering window
351589 11/22/2013 337994 P 9914 O Provide cover strip for electrical cords running across floor and secure cover strip to flooring to eliminte trip hazard
351578 11/22/2013 337972 P 9915 O Eliminate black extension cord with multiple outlet end for projector or replace with a surge protector
351487 11/22/2013 337764 2 180 MS Provide current inspection tag for fire extinguisher
351507 11/22/2013 337809 1 163A OS Prohibit storage of flammable spray paint cans
337685 11/22/2013 307810 1 191 OS Remove desk stored in electrical room
337698 08/28/2013 307840 3 0000 M Repair double entrance doors at chiller room to close and latch properly
337700 08/28/2013 307844 P 9909 M Secure electrical junction box at rear of portable (something struck box and broke mounting bracket and also broke plastic conduit)
337701 08/28/2013 307848 P 9911 M Secure electrical junction box at rear of portable (something struck box and broke mounting bracket and also broke plastic conduit)
337689 08/28/2013 307822 1 111 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
337687 08/28/2013 307817 1 181 O Eliminate use of multiple outlet electrical adaptor (3-way) used in battery charging outlet
334297 08/28/2013 300320 P 9677 O Eliminate multiple outlet extension cord, replace with surge protector
337688 08/28/2013 307819 1 181 C Provide sign in room indicating number of floor machine or golf cart batteries are allowed to be charged inside room
334613 08/28/2013 301006 1 106 OS Prohibit hold open device on fire door adjacent to 1-106A (remove rope tied to door handle, preventing door from closing)
334457 11/09/2012 300666 00 0000 M Clean debris from storm drain adjacent to portable 1-D
337640 11/09/2012 307714 1 101C M Return missplaced ceiling tiles back into metal ceiling grid
337641 11/09/2012 307721 1 101C M Determine cause of water damaged ceiling tiles and replace tiles
337643 11/09/2012 307723 1 101S M Determine cause of water damaged ceiling tiles and replace tiles
337680 11/09/2012 307792 1 102 M Repair hole in wall around electrical outlet next to water cooler in Cafeteria
337671 11/09/2012 307780 1 137 M Determine cause of water damaged and missing ceiling tiles and replace tiles
337674 11/09/2012 307784 1 139 M Provide cover on electrical junction box in ceiling next to projector
337663 11/09/2012 307766 1 144 M Determine cause of water damaged ceiling tiles and replace tiles
337662 11/09/2012 307762 1 144C M Determine cause of water damaged ceiling tiles and replace tiles
337660 11/09/2012 307760 1 145B M Secure sink to wall
337658 11/09/2012 307756 1 148 M Determine cause of water damaged ceiling tiles and replace tiles
337659 11/09/2012 307758 1 148 M Repair exterior exit door to close and latch properly
337652 11/09/2012 307743 1 151 M Repair exterior exit door to close and latch properly
337656 11/09/2012 307750 1 153 M Repair exterior exit door to close and latch properly
337686 11/09/2012 307812 1 181 M Determine cause of water damaged ceiling tiles and replace tiles
334294 11/09/2012 300314 P 6156 M Exterior junction boxes are partially buried. Remove dirt from around boxes so boxes no longer contact ground
337712 11/09/2012 307870 P 9823 M Repair emergency lighting above rear door
337699 11/09/2012 307842 P 9906 M Repair emergency lighting at both exit doors
334317 11/09/2012 300361 P 9907 M Secure sink to wall
334321 11/09/2012 300369 P 9908 M Secure sink to wall
334322 11/09/2012 300371 P 9908 M Exterior junction boxes are partially buried. Remove dirt from around boxes so that boxes do not contact ground
337704 11/09/2012 307855 P 9909 M Repair emergency lighting above rear door
334388 11/09/2012 300513 P 9910 M Exterior junction boxes are partially buried. Remove dirt from around boxes so that boxes do not contact ground
334401 11/09/2012 300541 P 9912 M Exterior junction boxes are partially buried. Remove dirt from around boxes so that boxes do not contact ground
337708 11/09/2012 307862 P 9912 M Repair emergency lighting above both exit doors
334409 11/09/2012 300559 P 9913 M Exterior junction boxes are partially buried. Remove dirt from around boxes so that boxes do not contact ground
334411 11/09/2012 300563 P 9914 M Exterior junction boxes are partially buried. Remove dirt from around boxes so that boxes are not in contact with ground
337703 11/09/2012 307852 P 9914 M Secure sink to wall in bathroom
334449 11/09/2012 300646 P 9915 M Exterior junction boxes are partially buried. Remove dirt from around boxes so that boxes do not contact ground
334452 11/09/2012 300653 P 9916 M Exterior junction boxes are partially buried. Remove dirt from around boxes so that boxes do not contact ground
334454 11/09/2012 300657 P 9917 M Exterior junction boxes are partially buried. Remove dirt from around boxes so that boxes do not contact ground
337710 11/09/2012 307865 P 9917 M Repair emergency lighting above rear door
337648 11/09/2012 307729 1 126 O Remove and prohibit hanging paper and decorations from ceiling (imitation grass decoration hanging from string line attached to ceiling grid)
337669 11/09/2012 307778 1 134B O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
337657 11/09/2012 307753 1 151 O Remove and prohibit flammable paper hanging on window blinds
337651 11/09/2012 307737 1 159 O Remove and prohibit paper hanging from windows
334306 11/09/2012 300338 P 0000 O Provide evidence of flame proofing for fabric and fabric curtains in portables or remove fabric
337706 11/09/2012 307859 P 9911 O Prohibit plugging microwave oven and refrigerator into surge protector - plug directly into permanent electrical outlet
334578 11/09/2012 300931 1 0000 C Improve drainage from Art room (1-132) patio to eliminate standing on patio
303228 11/09/2012 231963 P 0000 C Modify or improve roof drainage from portables to drain away from the portables
337684 11/09/2012 307807 1 104E MS Provide current inspection tag for fire extinguisher
337668 11/09/2012 307775 1 133 MS Provide current inspection tag for fire extinguisher
337696 11/09/2012 307830 1 199K MS Provide current inspection tags for fire sprinkler systems (three systems inside room and all three have outdated quarterly inspection tags, dated 5-22-2012)
337697 11/09/2012 307838 3 191 MS Recharge fire extinguisher at entrance door
337666 11/09/2012 307768 1 009 OS Relocate projector carts from exit corridor at rear of Media Center and maintain clear aisle to exit
334603 08/30/2012 300985 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable. Last certification dated 6/2010
334617 08/30/2012 301015 1 104 M Provide current state inspection tag for Kitchen steamer
334615 08/30/2012 301010 1 106H M Replace 2 broken sinks
334598 08/30/2012 300973 1 111 M Repair damaged emergency eye wash
334621 08/30/2012 301023 1 132 M Replace GFCI outlet at end of counter top that will not trip
334461 08/30/2012 300674 1 194 M Close open boxes in room
334605 08/30/2012 300989 1 199J M Repair leaking tee on copper plumbing lines
321919 08/30/2012 272848 1 199K M Replace inoperable water pressure guage on fire sprinkler riser Zone 1
334314 08/30/2012 300355 P 9824 M Replace missing elbow at bottom of downspout
334315 08/30/2012 300357 P 9906 M Large exterior junction box is partially buried. Remove dirt from around box so that it does not contact ground
334597 08/30/2012 300971 1 109A O Prohibit plugging refrigerator into extension cord - plug directly into permanent electrical outlet
334490 08/30/2012 300737 1 153 O Remove and prohibit hanging paper on blinds
334500 08/30/2012 300760 1 160 O Remove and prohibit paper covering window in door
334609 08/30/2012 300997 1 181 O Prohibit plugging 3 microwave ovens and toaster oven into surge protector - plug directly into permanent electrical outlet
334303 08/30/2012 300332 P 9821 O Remove and prohibit hanging paper from string lines. String lines are acceptable against the wall
334324 08/30/2012 300375 P 9909 O Provide clear access to electrical panel
334585 08/30/2012 300947 00 0000 OS Custodian is holding doors open with a block or stick on the hinge side of the door between the door and frame. This will damage the door, hinges and door frame. Temporarily block the door open with a wedge between the bottom of the door and the floor
334593 04/23/2012 300963 1 006 M Secure loose hold open magnet for corridor door adjacent to 1-107
334587 04/23/2012 300951 1 101C M Anchor shelving to wall
334616 04/23/2012 301012 1 105 M Replace GFCI outlet adjacent to sink that will not trip
334614 04/23/2012 301008 1 106E M Anchor toilet to floor
334592 04/23/2012 300961 1 107 M Replace GFCI outlet at sink that will not trip
334594 04/23/2012 300965 1 110B M Secure loose door handle
334595 04/23/2012 300967 1 110B M Repair leaking toilet supply line
334596 04/23/2012 300969 1 110B M Repair damaged wall at sink. Make wall impervious
334599 04/23/2012 300975 1 112B M Secure sink to wall
334465 04/23/2012 300683 1 115 M Determine cause of water damaged ceiling tiles and replace tiles
334463 04/23/2012 300679 1 116B M Secure loose door handle
334462 04/23/2012 300676 1 116D M Secure sink to wall
334584 04/23/2012 300944 1 118 M Secure loose faucet on sink
334460 04/23/2012 300672 1 119C M Repair damaged wall at sink. Make wall impervious
334459 04/23/2012 300670 1 121D M Repair leaking toilet supply line
334583 04/23/2012 300941 1 124 M Secure loose faucet on sink
334579 04/23/2012 300933 1 127B M Repair damaged wall at sink. Make wall impervious
334582 04/23/2012 300939 1 128 M Secure loose faucet on sink
334580 04/23/2012 300935 1 129B M Repair leaking toilet supply line
334619 04/23/2012 301019 1 139B M Repair damaged wall at sink. Make wall impervious
334589 04/23/2012 300955 1 146A M Secure loose door check to door
334588 04/23/2012 300953 1 146B M Repair leaking toilet supply line
334590 04/23/2012 300957 1 147C M Secure loose faucet to sink
334591 04/23/2012 300959 1 148B M Secure sink to wall
334489 04/23/2012 300735 1 151 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to exterior door
334499 04/23/2012 300758 1 152B M Repair exhaust fan in bathroom
334498 04/23/2012 300753 1 154B M Repair exhaust fan in bathroom
334497 04/23/2012 300751 1 156 M Adjust door to latch properly. Latch sticks
334494 04/23/2012 300745 1 156 M Determine cause of water damaged ceiling tiles and replace tiles at SW corner of room
334495 04/23/2012 300747 1 156B M Secure sink to wall
334496 04/23/2012 300749 1 156B M Repair damaged wall at sink. Make wall impervious
334493 04/23/2012 300743 1 158 M Determine cause of water damaged ceiling tiles and replace tiles and replace missing tiles
334455 04/23/2012 300659 1 180 M Repair door to open and close properly
334606 04/23/2012 300991 1 181 M Determine cause of water damaged ceiling tiles and replace tiles
334607 04/23/2012 300993 1 181B M Replace GFCI outlet that will not trip
334581 04/23/2012 300937 1 183 M Secure loose door handle
334622 04/23/2012 301025 1 184 M Repair damaged wall at floor sink
334618 04/23/2012 301017 1 186 M Repair door to open and close properly
334608 04/23/2012 300995 1 190A M Determine cause of water damaged ceiling tiles and replace tiles adjacent to sprinkler head. Investigate possible sprinkler leak
334602 04/23/2012 300981 1 191 M Close open video box
334305 04/23/2012 300336 1 199F M Repair door to open and close properly
334307 04/23/2012 300340 1 199H M Repair circuit 10 in panel 1HMA. Breaker tripped
334309 04/23/2012 300345 3 0000 M Remove SCBA sign at cooling tower doors to 3-191
334308 04/23/2012 300343 3 190 M Remove hasp and catch on door
334289 04/23/2012 300303 P 6153 M Secure loose sink faucet
334290 04/23/2012 300305 P 6153 M Fill gap between rear landing and portable
334291 04/23/2012 300308 P 6154 M Determine cause of water damaged ceiling tiles and replace tiles
334292 04/23/2012 300310 P 6154 M Replace missing epoxy paint sign or provide impervious wall finish in bathroom
334293 04/23/2012 300312 P 6155 M Secure sink to wall
334295 04/23/2012 300316 P 9677 M Repair deteriorated wall finish at bathroom sink, make it impervious
334298 04/23/2012 300322 P 9678 M Repair emergency lighting
334299 04/23/2012 300324 P 9821 M Repair emergency lighting
334300 04/23/2012 300326 P 9821 M Secure sink to wall in bathroom
334301 04/23/2012 300328 P 9821 M Repair deteriorated wall finish at bathroom sink, make it impervious
334310 04/23/2012 300347 P 9823 M Secure sink to wall
334311 04/23/2012 300349 P 9823 M Repair deteriorated wall finish at bathroom sink. Make it impervious
334313 04/23/2012 300353 P 9824 M Repair emergency lighting
334316 04/23/2012 300359 P 9906 M Secure sink to wall
334318 04/23/2012 300363 P 9908 M Replace broken flush handle for toilet
334319 04/23/2012 300365 P 9908 M Repair emergency lighting
334320 04/23/2012 300367 P 9908 M Secure loose toilet seat
334323 04/23/2012 300373 P 9909 M Determine cause of water damaged ceiling tiles and replace tiles
334393 04/23/2012 300521 P 9911 M Secure sink to wall
334396 04/23/2012 300528 P 9911 M Repair damaged wall at bathroom sink. Make wall impervious
334397 04/23/2012 300533 P 9911 M Repair bathroom door to open and close properly
334400 04/23/2012 300536 P 9912 M Repair damaged wall at bathroom sink. Make wall impervious
334403 04/23/2012 300543 P 9913 M Exterior juinction boxes are partially buried. Remove dirt from around boxes so that boxes do not contact ground
334410 04/23/2012 300561 P 9914 M Repair damaged wall at bathroom sink. Make wall impervious
334413 04/23/2012 300566 P 9915 M Secure sink to wall in bathroom
334448 04/23/2012 300644 P 9915 M Repair damaged wall finish at bathroom sink. Make wall impervious
334450 04/23/2012 300649 P 9916 M Repair emergency lighting X 2
334451 04/23/2012 300651 P 9916 M Secure sink to wall in bathroom
334453 04/23/2012 300655 P 9916 M Replace broken clean out cover for portable sewer line at exterior. Nut broken off
334458 04/23/2012 300668 00 0000 O Remove old exposed plumbing pipes in play fields. See coach Kauf
334600 04/23/2012 300977 1 112 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
334601 04/23/2012 300979 1 113 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
334464 04/23/2012 300681 1 117 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
334620 04/23/2012 301021 1 138 O Remove and prohibit attaching papers to blinds
334491 04/23/2012 300739 1 152 O Remove and prohibit hanging paper on blinds
334492 04/23/2012 300741 1 155 O Remove and prohibit hanging paper on blinds
334326 04/23/2012 300379 P 9909 C Replace missing epoxy paint sign or provide impervious wall finish in bathroom
334466 04/23/2012 300685 1 002 MS Adjust fire door in corridor adjacent to 1-115 to latch properly
334610 04/23/2012 300999 1 102 MS Adjust corridor door adjacent to 1-190A to latch properly
334611 04/23/2012 301001 1 102 MS Adjust 2 corridor doors on south wall to latch properly
334604 04/23/2012 300987 1 193 MS Replace missing latch on fire door to 1-192
334304 04/23/2012 300334 1 199F MS Remove storage from mechanical room
334456 04/23/2012 300663 1 180 OS Prohibit using a stick or wedge on the hinge side of the door between the door and frame to hold the door open. This will split the door, pull out the hinge or damage the door frame. Use a wedge between the bottom of the door and floor to temporarily hold the door open.
334296 04/23/2012 300318 P 9677 OS Maintain clear aisle to rear exit
334302 04/23/2012 300330 P 9821 OS Maintain clear aisle to rear exit
334312 04/23/2012 300351 P 9823 OS Maintain 3 foot clear aisle to rear exit
334325 04/23/2012 300377 P 9909 OS Maintain 3 foot clear aisle to rear exit
334586 04/23/2012 300949 1 101 FS Repair punch list indicated on the fire alarm inspection report
303232 04/07/2011 231968 00 0000 M Provide impervious wall finish for minimum six foot height in single bathrooms in classrooms
321886 04/07/2011 272778 1 0000 M Repair damaged chain link fencing at south side of Kindergarten playground
321942 04/07/2011 272894 1 001C M Replace missing signage indicating room name and number
321925 04/07/2011 272859 1 106D M Secure loose handrail in stage ramp
303283 04/07/2011 232090 1 135 M Reconfigure evacuation map (Turn evacuation map right side up so directions on map correspond to proper direction of egress)
321908 04/07/2011 272822 1 138 M Turn evacuation route map right side up
321898 04/07/2011 272803 1 143A M Replace missing escutcheon on fire sprinkler head
321945 04/07/2011 272899 1 144C M Replace damaged ceiling tile with hole in it
321946 04/07/2011 272904 1 148 M Determine cause of water damaged ceiling tiles and replace tiles
321903 04/07/2011 272814 1 157 M Secure hanging escutcheon on fire sprinkler head
321899 04/07/2011 272807 1 158 M Determine cause of water damaged ceiling tiles and replace tiles
321895 04/07/2011 272796 1 181 M Determine cause of water damaged ceiling tiles and replace tiles
321901 04/07/2011 272809 1 187 M Anchor shelving to wall
321885 04/07/2011 272776 2 0000 M Remove rust from underside of metal roof structure and repaint to prevent further damage to metal structure
321912 04/07/2011 272832 P 9677 M Repair emergency lighting at rear door
321911 04/07/2011 272830 P 9679 M Repair emergency lighting at front door
321916 04/07/2011 272841 P 9822 M Repair emergency lighting at front door
321917 04/07/2011 272843 P 9823 M Repair emergency lighting at front door
321914 04/07/2011 272836 P 9907 M Repair emergency lighting at front and rear doors
321918 04/07/2011 272845 P 9915 M Repair emergency lighting at front door
321887 04/07/2011 272780 1 0000 O Remove and prohibit flammable paper and artwork hanging from cables in all classrooms and prohibit flammable articles hanging from ceilings
321890 04/07/2011 272786 1 101G O Keep area within 18" of fire sprinkler head clear
321935 04/07/2011 272879 1 106 O Eliminate multiple outlet extension cord powering Christmas lights on stage
321891 04/07/2011 272788 1 108A O Keep area within 18" of fire sprinkler head clear
321920 04/07/2011 272850 1 131B O Prohibit plugging microwave oven and refrigerator into surge protector - plug directly into permanent electrical outlet
321921 04/07/2011 272852 1 131B O Prohibit plugging surge protector into surge protector
321896 04/07/2011 272798 1 181 O Remove articles blocking clear access to emergency eye wash and shower
321894 04/07/2011 272794 1 181 O Prohibit plugging two (2) microwave ovens into surge protector - plug directly into permanent electrical outlet
321913 04/07/2011 272834 P 9908 O Provide clear access to electrical panel
321915 04/07/2011 272838 P 9910 O Relocate bookcase blocking clear access to electrical panel
321922 04/07/2011 272854 1 104E MS Provide current inspection tag for fire extinguisher
321888 04/07/2011 272782 1 132 MS Provide current inspection tag for fire extinguisher
321889 04/07/2011 272784 1 133 MS Provide current inspection tag for fire extinguisher
321905 04/07/2011 272818 1 151D MS Provide current inspection tag for Type K fire extinguisher
321940 04/07/2011 272885 1 102 OS Prohibit use of hold open devices (wedges) on corridor doors
321933 04/07/2011 272870 1 106 OS Prohibit string holding open exit door to stage ramp
321897 04/07/2011 272801 1 181 OS Prohibit storage of gasoline powered leaf blower
321892 04/07/2011 272790 1 191 OS Remove storage from electrical room
321893 04/07/2011 272792 1 193 OS Remove bicycles stored in electrical room
303259 01/31/2011 232038 P 9677 M Seal seam in bathroom flooring
303260 01/31/2011 232040 P 9678 M Seal seam in bathroom flooring
303262 01/31/2011 232045 P 9679 M Seal seam in bathroom flooring
303270 01/31/2011 232062 1 101S O Lower storage to keep area within 18" of fire sprinkler heads clear
303293 01/31/2011 232110 1 140A O Lower storage to keep area within 18" of fire sprinkler head clear
303234 01/31/2011 231978 00 0000 C Provide exterior signage indicating property address
303261 01/31/2011 232043 1 181 OS Prohibit charging batteries in room
303254 04/09/2010 232025 00 0000 M Secure sinks to walls in individual bathrooms in classrooms
303277 04/09/2010 232078 00 0000 M Secure loose trim piece above windows to wall outside of 1-146
303303 04/09/2010 232130 00 0000 M Provide cap on open 2 inch PVC pipe in slab in grassed area north of building 2
303271 04/09/2010 232064 1 001 M Secure loose escutcheon on fire sprinkler head in corridor adjacent to 1-102
303248 04/09/2010 232011 1 001 M Replace missing escutcheon on fire sprinkler head in corridor adjacent to 1-130
303243 04/09/2010 231998 1 004 M Replace missing escutcheon on fire sprinkler head in corridor adjacent to 1-153
303273 04/09/2010 232069 1 004 M Replace rusted escutcheon on fire sprinkler head in corridor adjacent to 1-004C and investigate sprinkler for possible leak
303265 04/09/2010 232051 1 103A M Replace missing escutcheon on fire sprinkler head
297374 04/09/2010 219275 1 104 M Provide current inspection tag for kitchen steamer
303236 04/09/2010 231981 1 106C M Secure loose green light fixture outside of door. Attachment nut missing
303240 04/09/2010 231991 1 106D M Anchor toilet to floor
303267 04/09/2010 232056 1 107 M Replace missing escutcheon on fire sprinkler head
303266 04/09/2010 232054 1 107A M Replace missing escutcheon on fire sprinkler head
303301 04/09/2010 232126 1 139B M Refinish damaged wall in bathroom
303285 04/09/2010 232094 1 141 M Repair electrical outlets that don't work. See teacher
303264 04/09/2010 232049 1 148 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to exterior wall
303241 04/09/2010 231995 1 155 M Repair or replace GFCI outlet adjacent to sink
303249 04/09/2010 232014 1 155B M Repair leaking supply line on toilet
303251 04/09/2010 232017 1 159B M Repair and refinish damaged wall adjacent to sink in bathroom
303233 04/09/2010 231974 1 163B M Repair exhaust fan in bathroom
303276 04/09/2010 232075 1 186 M Seal openings around pipe where it penetrates wall and refinish wall
297377 04/09/2010 219281 1 193 M Replace missing signage indicating room name and number
303253 04/09/2010 232022 3 190 M Seal open caulk joint on exterior wall adjacent to door
303227 04/09/2010 231960 P 0000 M Provide impervious wall finish for minimum six foot height in all restrooms in all portables
303258 04/09/2010 232036 P 9677 M Repair emergency lighting
303274 04/09/2010 232071 P 9677 M Repair or replace broken deck drain at rear door landing
303275 04/09/2010 232073 P 9678 M Repair or replace broken deck drain at rear door landing
303263 04/09/2010 232047 P 9679 M Repair emergency lighting
303286 04/09/2010 232096 P 9910 M Adjust both doors to latch properly
303287 04/09/2010 232098 P 9910 M Secure sink to wall in bathroom
303288 04/09/2010 232100 P 9911 M Secure sink to wall in bathroom
303289 04/09/2010 232102 P 9912 M Secure sink to wall in bathroom
303290 04/09/2010 232104 P 9914 M Secure sink to wall in bathroom
303252 04/09/2010 232020 1 127B O Keep shower drain filled with water
303291 04/09/2010 232106 1 131B O Prohibit plugging surge protector into surge protector
303292 04/09/2010 232108 1 131B O Prohibit plugging appliance into surge protector - plug directly into permanent electrical outlet
303284 04/09/2010 232092 1 135 O Prohibit plugging surge protector into surge protector
303282 04/09/2010 232088 1 136 O Reconfigure evacuation map
303279 04/09/2010 232082 1 137 O Reconfigure evacuation map
303278 04/09/2010 232080 1 138 O Reconfigure evacuation map
303281 04/09/2010 232086 1 139 O Reconfigure evacuation map
303280 04/09/2010 232084 1 141 O Reconfigure evacuation map
303257 04/09/2010 232033 00 0000 C Provide protective bollards around propane gas line where it enters room 1-199J
234224 04/09/2010 91205 00 9699 C Provide fencing around playground adjacent to bus loop/parking lot
303255 04/09/2010 232028 1 002 MS Adjust fire door in corridor adjacent to 1-114 to latch properly
297355 04/09/2010 219236 1 144C MS Provide current inspection tag for fire extinguisher
303268 04/09/2010 232058 1 147C MS Provide current inspection tag for fire extinguisher
303256 04/09/2010 232030 1 151C MS Provide current inspection tag for fire extinguisher
303299 04/09/2010 232122 2 101F MS Provide current inspection tag for fire extinguisher
303300 04/09/2010 232124 2 180 MS Provide current inspection tag for fire extinguisher
303238 04/09/2010 231989 1 106 OS Prohibit hold open devices on fire door
303302 04/09/2010 232128 1 132 OS Maintain clear aisle to rear exit
303298 04/09/2010 232120 1 141 OS Remove and prohibit storage outside of door
303269 04/09/2010 232060 1 147C OS Provide clear access to fire extinguisher
303272 04/09/2010 232066 1 101 FS Provide current inspection tag for fire alarm system and repair strobe light in dining room according to fire alarm inspection report
297361 11/05/2009 219248 3 190 M Repair hole in north concrete wall next to floor
297376 04/24/2009 219279 1 101G M Determine cause of water damaged ceiling tiles and replace tiles
297375 04/24/2009 219277 1 101U M Secure loose escutcheon on fire sprinkler head
297366 04/24/2009 219258 1 103A M Replace missing ceiling tiles
297367 04/24/2009 219260 1 103A M Replace missing signage indicating room name and number
297368 04/24/2009 219263 1 104F M Repair door on walk-in cooler to close properly (door drags on jamb preventing it from closing properly)
297369 04/24/2009 219265 1 106C M Adjust corridor door to close properly (door drags on jamb)
297373 04/24/2009 219273 P 6154 M Repair rear exit door to close properly
297372 04/24/2009 219271 P 9906 M Repair rear exit door to close properly
297371 04/24/2009 219269 P 9908 M Repair rear exit door to close properly
297364 04/24/2009 219254 1 004 O Remove flammable decorations from ceiling in corridor adjacent to 1-155 and 1-157
297378 04/24/2009 219283 1 181 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
297357 04/24/2009 219240 1 181 O Eliminate use of 13 amp extension cord to charge batteries
297358 04/24/2009 219242 2 101A O Eliminate multiple outlet electrical adaptor (three-way adaptor) at microwave oven
252171 04/24/2009 124746 1 106C C Provide signage indicating room name and number at appropriate height with raised and Braille characters
297362 04/24/2009 219250 1 199K MS Provide current inspection tag for fire extinguisher
297359 04/24/2009 219244 2 180 MS Provide current inspection tag for fire extinguisher
297360 04/24/2009 219246 3 191 MS Provide current inspection tag for fire extinguisher
297365 04/24/2009 219256 1 106 OS Prohibit use of twine to hold fire door open on north side of stage
297356 04/24/2009 219238 1 190A OS Remove storage from systems electrical room
297363 04/24/2009 219252 1 199K OS Remove storage from mechanical room
297370 04/24/2009 219267 P 9917 OS Maintain clear aisle to rear exit door
279623 02/19/2009 181437 1 102 M Replace missing escutcheon on fire sprinkler head adjacent to 1-102A
234275 02/19/2009 91306 1 144C M Relocate fire sprinkler head to provide minimum 18" clearance between sprinkler head and cabinet above sink counter. Sprinkler will not cover stove
264553 02/19/2009 148656 00 0000 C Provide covered walkway to portables
279650 02/19/2009 181492 00 0000 C Provide suitable area for storage and recharging floor cleaning machines
279653 02/19/2009 181500 1 190A C Provide adequate ventilation in electrical room - room is very hot
279654 02/19/2009 181502 1 196 C Provide adequate ventilation in electrical room - room is very hot
234227 07/17/2008 91212 1 003 C Provide edge protection at free edge of smoke stop doors adjacent to 1-123 to prevent door from accidentally being closed (No longer required)
234228 07/17/2008 91214 1 003 C Provide edge protection at free edge of smoke stop doors adjacent to 1-152 to prevent door from accidentally being closed (No longer required by Code)
279639 03/31/2008 181469 1 005 M Adjust exterior doors adjacent to 1-141 to latch properly
279612 03/31/2008 181411 1 127A M Remove top shelf of metal shelving to keep area within 18" of automatic fire sprinkler head clear and unobstructed
279648 03/31/2008 181488 1 142 M Repair lock on door - lock sticks
279622 03/31/2008 181435 1 146 M Adjust exterior door to latch properly
279646 03/31/2008 181484 2 101 M Repair leaking gutter at north side of pavilion - see PE teacher
279832 03/31/2008 181886 P 6154 M Adjust front door to latch properly
279817 03/31/2008 181855 P 9677 M Secure sink to wall
279818 03/31/2008 181857 P 9679 M Repair back door to open and close properly - Hard to open and rubs on frame
279833 03/31/2008 181888 P 9909 M Adjust back door to latch properly
279834 03/31/2008 181890 P 9909 M Secure sink to wall
279830 03/31/2008 181882 P 9911 M Secure sink to wall
279825 03/31/2008 181872 P 9916 M Adjust front door to latch properly
279606 03/31/2008 181397 1 101Q O Prohibit plugging surge protector into surge protector - plug each surge protector dircetly into electrical wall outlet
279635 03/31/2008 181461 1 109 O Remove and prohibit combustible residential chair
279633 03/31/2008 181457 1 113 O Eliminate 13A extension cord for document camera or replace with minimum 15A cord
279643 03/31/2008 181478 1 137 O Remove and prohibit combustible beanbag chairs (x4)
279642 03/31/2008 181475 1 138 O Remove and prohibit combustible beanbag chairs (x4)
279637 03/31/2008 181465 1 139 O Remove and prohibit combustible beanbag chair
279649 03/31/2008 181490 1 139 O Remove solid paper covering corridor door
279620 03/31/2008 181432 1 147 O Remove and prohibit combustible beanbag chairs (x2)
279619 03/31/2008 181429 1 148 O Remove and prohibit combustible beanbag chairs (x2)
279613 03/31/2008 181417 1 149A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
279618 03/31/2008 181426 1 155 O Remove and prohibit combustible beanbag chair
279615 03/31/2008 181420 1 158 O Eliminate extension cord with multiple outlet end under computer station
279616 03/31/2008 181423 1 159 O Prohibit plugging surge protector into surge protector adjacent to teacher's desk
279630 03/31/2008 181452 1 181 O Prohibit plugging microwave and toaster into surge protector - plug appliances directly into permanent electrical outlet
279652 03/31/2008 181496 1 181 O Remove and prohibit use of tape on latch hardware preventing custodial room door from latching - keep door locked and latched to prohibit student access
279820 03/31/2008 181861 P 6153 O Remove and prohibit paper covering window in door
279819 03/31/2008 181859 P 6155 O Remove and prohibit paper covering window in door (x2)
279829 03/31/2008 181880 P 9906 O Relocate bookcase to provide clear access to electrical panel
279823 03/31/2008 181867 P 9908 O Remove and prohibit paper covering window in door
279821 03/31/2008 181863 P 9909 O Remove and prohibit paper covering window in door
279822 03/31/2008 181865 P 9910 O Remove and prohibit paper covering window in door
279826 03/31/2008 181874 P 9915 O Remove and prohibit combustible beanbag chairs (x2)
279824 03/31/2008 181869 P 9917 O Remove and prohibit flammable fabric covering window in door (x2)
279608 03/31/2008 181402 1 002 MS Adjust fire doors in corridor adjacent to 1-115 to latch properly
279625 03/31/2008 181439 1 005 MS Adjust fire doors in corridor adjacent to 1-106G to latch properly
279627 03/31/2008 181444 1 103 MS Replace Type K fire extinguisher with an ABC fire extinguisher (x2)
279644 03/31/2008 181480 1 133 MS Provide current inspection tag for fire extinguisher
279628 03/31/2008 181448 1 193 MS Remove maintenance storage from electrical room
279655 03/31/2008 181505 1 196 MS Keep ceiling tile in place to prevent spread of fire or smoke
279831 03/31/2008 181884 P 6153 MS Recharge fire extinguisher
279610 03/31/2008 181408 1 124 OS Remove and prohibit use of toaster oven
279645 03/31/2008 181482 1 133B OS Remove and prohibit running extension cord above door
279647 03/31/2008 181486 1 147C OS Relocate storage blocking clear access to fire extinguisher (x2)
279651 03/31/2008 181494 1 181 OS Prohibit charging batteries for floor cleaning machines in room (exhaust fan has been installed in room to exhaust fumes to the outside)
279827 03/31/2008 181876 P 9915 OS Remove and prohibit use of toaster oven
252139 12/19/2007 124673 1 111 C Provide tempered or safety glazing in display cabinet
264512 03/28/2007 148569 1 106C M Replace missing ceiling tile
264517 03/28/2007 148578 1 110B M Replace fire sprinkler head with paint on it
264524 03/28/2007 148593 1 119B M Replace missing door stopper and repair hole in wall behind door to boy's restroom
234256 03/28/2007 91271 1 126C M Secure sink to wall
264528 03/28/2007 148603 1 129 M Repair non working electrical outlets in classroom and closet 1-129A, per teacher
264539 03/28/2007 148627 1 148 M Repair exterior door to close properly
264530 03/28/2007 148608 1 154 M Repair door to close properly
264531 03/28/2007 148611 1 156A M Replace missing ceiling tile
264576 03/28/2007 148709 P 6153 M Paint portable number on exterior wall to be visible to fire rescue personnel
264574 03/28/2007 148703 P 6154 M Paint portable number on exterior wall to be visible to fire rescue personnel
264572 03/28/2007 148699 P 6155 M Paint portable number on exterior wall to be visible to fire rescue personnel
264546 03/28/2007 148641 P 9156 M Paint portable number on exterior wall to be visible to fire rescue personnel
264569 03/28/2007 148693 P 9678 M Repair emergency lighting
264550 03/28/2007 148649 P 9910 M Determine cause of water damaged ceiling tiles and replace tiles
264520 03/28/2007 148583 1 114A O Prohibit use of extension cord to power refrigerator, plug refrigerator directly into wall outlet
264521 03/28/2007 148589 1 116 O Remove and prohibit combustible (residential) furniture
264522 03/28/2007 148591 1 118 O Remove and prohibit combustible beanbag chairs
264515 03/28/2007 148573 1 130C O Prohibit use of multi outlet extension cord, use only 15A single outlet cord
264544 03/28/2007 148635 1 133B O Prohibit 13A extension cord or replace with minimum 15A cord
264538 03/28/2007 148624 1 149 O Prohibit plugging microwave into surge protector, plug microwave directly into wall outlet
264535 03/28/2007 148620 1 153 O Post sign indicating evacuation routes
264536 03/28/2007 148622 1 153 O Remove and prohibit combustible beanbag chairs
264534 03/28/2007 148617 1 155 O Eliminate brown 13A extension cords or replace with minimum 15A cords
264575 03/28/2007 148707 P 6153 O Remove and prohibit paper covering window in door
264566 03/28/2007 148686 P 9678 O Prohibit use of white 13A extension cord or replace with minimum 15A cord
264571 03/28/2007 148696 P 9679 O Remove and prohibit paper covering window in door
264548 03/28/2007 148645 P 9909 O Prohibit 13A extension cord or replace with minimum 15A cord
264551 03/28/2007 148652 P 9910 O Remove and prohibit paper covering window in door
264554 03/28/2007 148659 P 9911 O Remove and prohibit paper covering window in door
264558 03/28/2007 148666 P 9917 O Prohibit plugging surge protector into surge protector, plug each directly into wall outlet
264562 03/28/2007 148669 P 9917 O Prohibit use of multi outlet extension cord, use 15A single outlet extension cord
264511 03/28/2007 148567 1 007 MS Replace missing magnet on smoke door adjacent to 1-102A
264510 03/28/2007 148565 1 104E MS Provide current inspection tag for fire extinguisher
264541 03/28/2007 148633 1 135 MS Provide current inspection tag for fire extinguisher
234283 03/28/2007 91323 1 191 MS Verify space between corrugated metal roof deck and support angle along wall is sealed to maintain 2-hour rating of wall
264529 03/28/2007 148606 1 127 OS Prohibit electrical cord from being run under carpet
264540 03/28/2007 148630 1 144C OS Remove storage from stove burners
264513 03/28/2007 148571 1 181 OS Prohibit charging batteries in room
264579 03/28/2007 148712 2 101C OS Prohibit storage of field marker paint
264573 03/28/2007 148701 P 6154 OS Keep area clear to east exit door
264564 03/28/2007 148682 P 9677 OS Keep area clear to rear (east) exit door
264567 03/28/2007 148689 p 9678 OS Keep area clear to rear(east)exit door
264557 03/28/2007 148661 P 9912 OS Keep area clear to rear (west) exit door
234244 12/01/2006 91247 1 125A M Relocate fire sprinkler heads to be minimum 4 inches away from walls
264526 12/01/2006 148596 1 128 O Remove and prohibit combustible beanbag chairs
234222 12/01/2006 91201 00 0000 C Replace wood frames for wired glass in all fire rated doors throughout campus with steel frames or provide documentation that wood frames meets UL listing for door assembly
264533 12/01/2006 148613 1 159 OS Keep area to exit door clear
252149 05/04/2006 124698 00 9699 M Repair damaged chain link fencing in field adjacent to bus loop
252154 05/04/2006 124710 1 004 M Replace missing escutcheon on fire sprinkler head adjacent to 1-153
252140 05/04/2006 124675 1 108 M Replace missing escutcheon on fire sprinkler head
252143 05/04/2006 124682 1 119B M Repair hole in wall adajcent to 1-119C
252147 05/04/2006 124690 1 126A M Determine cause of water damaged ceiling tiles and replace tiles
252156 05/04/2006 124714 1 144 M Repair exterior door to open/close properly
252157 05/04/2006 124716 1 144C M Determine cause of water damaged ceiling tiles and replace tiles
252155 05/04/2006 124712 1 146B M Secure loose cover on light fixture
252148 05/04/2006 124696 1 158 M Anchor plastic shelving to wall
252150 05/04/2006 124701 2 101E M Repair door to close properly
252152 05/04/2006 124706 2 180 M Mount fire extinguisher at maximum five feet above floor
252166 05/04/2006 124735 P 9913 M Repair emergency lighting
252142 05/04/2006 124680 1 107 O Post sign indicating evacuation routes
252144 05/04/2006 124684 1 124 O Prohibit toaster
252145 05/04/2006 124686 1 124 O Eliminate plugging microwave into extension cord, plug microwave directly into wall outlet
252146 05/04/2006 124688 1 124 O Remove and prohibit air freshener
252160 05/04/2006 124722 P 9917 O Remove and prohibit combustible beanbag chairs
252172 05/04/2006 124748 1 001 C Provide tempered or safety glazing in display cabinet across from 1-131
252141 05/04/2006 124677 1 006 C Provide tempered or safety glazing in display cabinet across from 1-107
252138 05/04/2006 124671 1 102 MS Adjust NW fire doors adjacent to 1-190A to latch properly
252170 05/04/2006 124743 3 0000 MS Provide current inspection tags for fire extinguishers
252153 05/04/2006 124708 1 159 OS Remove and prohibit candles
234313 05/04/2006 91388 2 101C OS Prohibit storage of flammable spray paint
252137 05/04/2006 124669 1 101 FS Repair problems with fire alarm system. Trouble indicated on panel
234308 05/04/2006 91377 2 101F FS Provide additional heat detector in storage room or verify single detector provides adequate coverage
234320 03/14/2006 91405 00 9699 M Replace broken valve box in field SE of building 3
234235 03/14/2006 91229 1 106 M Provide dated flame resistance label on all stage curtains
234292 03/14/2006 91342 1 159B M Repair exhaust fan in bathroom
234277 03/14/2006 91310 1 181B M Replace sprinkler head that is covered with plaster
234323 03/14/2006 91411 3 0000 M Replace 3 signs in building 3 that indicate breathing apparatus is located in 3-198. Breathing aparatus is located in 3-190. There is no 3-198
234248 03/14/2006 91255 1 147 O Remove and prohibit combustible bean bag chairs
252151 03/14/2006 124703 2 180 C Provide explosion proof light fixture for flammable storage room
234304 03/14/2006 91369 1 199K MS Provide current inspection tag for fire sprinkler riser
234309 03/14/2006 91379 2 101F OS Prohibit storage of flammable chafing fuel
234225 03/14/2006 91207 1 0000 CS Provide lock box to allow fire department access
234321 03/04/2005 91407 00 9699 M Replace broken collar around clean out in grass SW of P-1
234305 03/04/2005 91371 1 003 M Determine cause of crack in corridor wall, adjacent to exterior doors across from 1-161. Crack is visible on both sides of wall
234234 03/04/2005 91227 1 101F M Secure loose handicapped grabrail in bathroom
234233 03/04/2005 91225 1 101G M Determine cause of water damaged ceiling tiles and replace tiles. Water is leaking into light fixture
234236 03/04/2005 91231 1 106 M Provide cover on exposed electrical junction box on back wall
234237 03/04/2005 91233 1 106C M Repair damaged green light fixture on wall outside dressing room door
234274 03/04/2005 91304 1 106H M Secure loose door handle
234238 03/04/2005 91235 1 107A M Replace missing escutcheon on fire sprinkler head
234240 03/04/2005 91239 1 108A M Remove shelving within 18" of automatic fire sprinkler heads
234241 03/04/2005 91241 1 110A M Remove shelving within 18" of automatic fire sprinkler heads
234243 03/04/2005 91245 1 113B M Anchor toilet to floor
234239 03/04/2005 91237 1 114A M Replace missing escutcheon on fire sprinkler head
234253 03/04/2005 91268 1 116C M Secure sink to wall
234341 03/04/2005 91460 1 116C M Repair damaged wall finish at sink top make wall impervious
234254 03/04/2005 91269 1 119C M Secure sink to wall
234268 03/04/2005 91291 1 119C M Secure loose door handle
234255 03/04/2005 91270 1 119D M Secure sink to wall
234272 03/04/2005 91300 1 122D M Repair damaged wall finish at sink to make wall impervious
234263 03/04/2005 91282 1 127B M Secure sink to wall
234250 03/04/2005 91261 1 131A M Replace missing escutcheon on fire sprinkler head
234257 03/04/2005 91272 1 135B M Secure sink to wall
234258 03/04/2005 91273 1 139B M Secure sink to wall
234259 03/04/2005 91274 1 141B M Secure sink to wall
234265 03/04/2005 91284 1 148B M Secure sink to wall
234260 03/04/2005 91275 1 152B M Secure sink to wall
234290 03/04/2005 91338 1 154B M Repair wall finish at sink to make it impervious
234294 03/04/2005 91347 1 155B M Repair deteriorated wall finish at sink to make wall impervious
234287 03/04/2005 91332 1 156A M Anchor shelving to wall
234261 03/04/2005 91276 1 156B M Secure sink to wall
234262 03/04/2005 91277 1 159B M Secure sink to wall
234276 03/04/2005 91308 1 163B M Replace missing escutcheon on fire sprinkler head
234289 03/04/2005 91336 1 180 M Anchor shelving to wall
234279 03/04/2005 91314 1 182 M Close ceiling hatch
234271 03/04/2005 91298 1 183 M Anchor shelving to wall
234280 03/04/2005 91317 1 190A M Replace missing ceiling tiles
234293 03/04/2005 91344 1 192 M Provide certification that emergency generator is operable
234295 03/04/2005 91350 1 196 M Replace missing ceiling tiles
234299 03/04/2005 91358 1 199 M Remove white boards stored in mechanical room
234301 03/04/2005 91363 1 199B M Replace missing ceiling tiles
234312 03/04/2005 91386 2 101C M Anchor shelving to wall
234306 03/04/2005 91373 2 101D M Adjust door to latch properly
234307 03/04/2005 91375 2 101E M Seal holes in door from removed latch guard
234314 03/04/2005 91390 2 101E M Secure sink to wall
234310 03/04/2005 91383 2 101F M Repair door to open/close properly and latch
234322 03/04/2005 91409 3 0000 M Secure loose chain link fencing east of building 3
234316 03/04/2005 91395 3 0000 M Repair door of chiller compound to close and latch properly
234317 03/04/2005 91399 3 190 M Install breathing apparatus locker. Locker sitting on floor
234318 03/04/2005 91401 3 190 M Install cover on electric panel A
234319 03/04/2005 91403 3 190 M Adjust east door to close and latch properly
234325 03/04/2005 91415 P 9678 M Secure sink to wall
234324 03/04/2005 91413 P 9679 M Secure sink to wall
234267 03/04/2005 91288 1 130E O Keep area within 18" of automatic fire sprinkler heads clear and unobstructed
234273 03/04/2005 91302 1 151C O Prohibit storage on stove
234326 03/04/2005 91417 00 9699 C Lock up electrical enclosure north of portables
234245 03/04/2005 91249 1 130D C Provide auto closer on corridor door
234246 03/04/2005 91251 1 130E C Provide auto closer on corridor door
234247 03/04/2005 91253 1 130G C Provide auto closer on corridor door
234249 03/04/2005 91258 1 131 C Install maximum occupancy signage adjacent to main entry, inside room
234281 03/04/2005 91319 1 190A C Adjust fire sprinkler head to be minimum 1" below escutcheon
234230 03/04/2005 91219 1 199H C Replace damaged sign indicating room name and number
234270 03/04/2005 91295 1 007 MS Adjust fire doors in corridor at 1-105 to latch properly
234252 03/04/2005 91265 1 106A MS Adjust fire door to stage to latch properly
234251 03/04/2005 91263 1 147C MS Provide current inspection tag for type K fire extinguisher
234231 03/04/2005 91221 1 199H MS Replace missing fire extinguisher
234315 03/04/2005 91392 2 180 MS Provide current inspection tag for fire extinguisher
234242 03/04/2005 91243 1 144C OS Provide clear access to fire extinguisher
234288 03/04/2005 91334 1 181 OS Prohibit recharging batteries in room
234278 03/04/2005 91312 1 181B OS Prohibit storage of gas powered equipment
234286 03/04/2005 91329 1 190 CS Provide fire extinguisher in electrical room
234284 03/04/2005 91325 1 194 CS Provide fire extinguisher in mechanical room
234285 03/04/2005 91327 1 195 CS Provide fire extinguisher in electrical room
234296 03/04/2005 91352 1 197 CS Provide fire extinguisher in electric room
234297 03/04/2005 91354 1 198 CS Provide fire extinguisher in electric room
234298 03/04/2005 91356 1 199 CS Provide fire extinguisher in mechanical room
234300 03/04/2005 91361 1 199A CS Provide fire extinguisher in electric room
234302 03/04/2005 91365 1 199C CS Provide fire extinguisher in mechanical room
234303 03/04/2005 91367 1 199D CS Provide fire extinguisher in electric room
234226 03/04/2005 91210 1 0000 FS Immediately repair magnetic hold open for fire doors in corridor at 1-132. School is wedging open door because magnet is not working
234229 03/04/2005 91217 1 0000 FS Remove duct tape from heat detector in corridor at smoke stop doors adjacent to 1-123
234232 03/04/2005 91223 1 101 FS Make repairs to fire alarm system. Panel indicates trouble
234282 03/04/2005 91321 1 191 FS Immediately remove masking tape from heat detector