WEST GATE ELEMENTARY
 
WEST GATE ELEMENTARY
This site is a Hurricane Shelter
1545 LOXAHATCHEE DRIVE
WEST PALM BEACH, 33409
FISH Drill Down
 Campus Info.
 Buildings:4 Rooms:316
 Portables:18
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
412237 03/08/2018 469518 00 0000 M Repair loose basketball backboard column at basketball courts (support column twists in loose base)
412252 03/08/2018 469551 1 002 M Determine cause of water damaged ceiling tiles in corridor adjacent to 1-182 and replace tiles
412241 03/08/2018 469527 1 009 M Determine cause of water damaged ceiling tiles in first floor corridor adjacent to 1-184 and replace tiles
412221 03/08/2018 469485 1 101 M Determine cause of water damaged ceiling tiles and replace tiles
412222 03/08/2018 469487 1 101J M Determine cause of water damaged ceiling tiles at windows and replace tiles
412223 03/08/2018 469489 1 101L M Replace missing ceiling tiles
412264 03/08/2018 469575 1 104B M Determine cause of water damaged ceiling tiles in locker room and replace tiles
412257 03/08/2018 469561 1 106A M Repair damaged wall at bottom of stage ramp
412255 03/08/2018 469557 1 106B M Mount fire extinguisher at maximum five feet above floor (bracket has fallen from wall and needs to be re-attached)
412256 03/08/2018 469559 1 106B M Repair door to close properly (door hits on jamb when closing(
412225 03/08/2018 469494 1 107D M Secure hanging light fixture lens
412228 03/08/2018 469500 1 107G M Provide current date for flame resistance certification on CCTV curtain (date on current certificate is April 30, 2012)
412226 03/08/2018 469496 1 107N M Replace missing ceiling tiles
412250 03/08/2018 469547 1 111 M Replace missing ceiling tiles
412254 03/08/2018 469555 1 115 M Repair out of service urinal in boy's restroom
412230 03/08/2018 469504 1 120 M Determine cause of water damaged ceiling tiles at windows and replace tiles
412232 03/08/2018 469508 1 126 M Replace missing ceiling tiles next to windows
412239 03/08/2018 469523 1 128 M Determine cause of water damaged ceiling tiles and replace tiles
412238 03/08/2018 469520 1 128A M Secure loose cover plate on light switch
412243 03/08/2018 469531 1 130 M Repair entrance door to close properly
412244 03/08/2018 469533 1 138 M Replace missing vinyl base on wall next to projector screen
412245 03/08/2018 469535 1 138B M Replace missing ceiling tiles in storage room
412246 03/08/2018 469537 1 140 M Determine cause of water damaged ceiling tiles and replace tiles
412229 03/08/2018 469502 1 170 M Provide current inspection tag for elevator (expiration date 8-1-17)
412240 03/08/2018 469525 1 184 M Replace missing ceiling tile around exhaust fan in ceiling of custodial closet
412263 03/08/2018 469573 1 185 M Determine cause of water damaged ceiling tiles adjacent to fire sprinkler riser and replace tiles
412262 03/08/2018 469571 1 185B M Determine cause of water damaged ceiling tile around exhaust fan and replace tiles
412231 03/08/2018 469506 1 193 M Repair leaky water valves (X2) above AHU 3 and AHU 4 to prevent rust forming on duct work
412261 03/08/2018 469569 1 197 M Secure hanging emergency light in generator room
412249 03/08/2018 469545 1 199 M Replace missing cover on floor drain to prevent tripping hazard
412234 03/08/2018 469512 1 199A M Repair leak in chilled water supply piping above AHU 5
412280 03/08/2018 469608 1 203 M Determine cause of water damaged ceiling tiles at windows and replace tiles
412278 03/08/2018 469604 1 207 M Determine cause of water damaged ceiling tiles above sink and replace tiles
412277 03/08/2018 469602 1 207B M Replace missing escutcheon on fire sprinkler head
412267 03/08/2018 469581 1 208 M Repair holes in wall next to window
412266 03/08/2018 469579 1 210 M Determine cause of water damaged ceiling tiles at windows and replace tiles
412268 03/08/2018 469583 1 211 M Determine cause of water damaged ceiling tiles at windows and replace tiles
412269 03/08/2018 469585 1 212 M Replace missing escutcheon on fire sprinkler head
412276 03/08/2018 469600 1 213 M Secure loose faucet to sink
412272 03/08/2018 469591 1 219 M Determine cause of water damaged ceiling tiles at teachers desk and replace tiles
412273 03/08/2018 469593 1 222B M Repair ventilation fan in restroom
412274 03/08/2018 469595 1 226B M Repair ventilation fan in restroom
372501 03/08/2018 383596 1 290 M Repair exhaust fan
372506 03/08/2018 383607 1 293 M Repair exhaust fan
412271 03/08/2018 469589 1 293 M Mount fire extinguisher at maximum five feet above floor (bracket has fallen from the wall)
412235 03/08/2018 469514 2 101 M Repair loose cover on electrical outlet on wall next to drinking fountain
412236 03/08/2018 469516 2 101 M Fill drop off in ground at walkway at south side of Building 2
412300 03/08/2018 469649 P 9134 M Repair emergency lighting at front door
412301 03/08/2018 469651 P 9134 M Determine cause of water damaged ceiling tiles and replace tiles
412302 03/08/2018 469653 P 9135 M Place ceiling tile back into ceiling grid
412293 03/08/2018 469635 P 9136 M Repair emergency lighting at rear door
412287 03/08/2018 469623 P 9343 M Repair emergency lighting at both front and rear doors
412288 03/08/2018 469625 P 9343 M Place ceiling tile back into ceiling grid
412291 03/08/2018 469631 P 9345 M Repair emergency lighting at both front and rear doors
412289 03/08/2018 469627 P 9408 M Repair emergency lighting at rear door
412290 03/08/2018 469629 P 9408 M Repair rear door to close properly
412285 03/08/2018 469619 P 9409 M Repair emergency lighting at both front and rear doors
412286 03/08/2018 469621 P 9411 M Replace missing face plate on lighted exit sign at front door
412282 03/08/2018 469612 P 9412 M Place ceiling tiles back into ceiling grid
412283 03/08/2018 469615 P 9412 M Repair rear door to close properly
412284 03/08/2018 469617 P 9413 M Repair emergency lighting at both front and rear doors
412281 03/08/2018 469610 P 9479 M Repair emergency lighting at rear door
412297 03/08/2018 469643 P 9480 M Determine cause of water damaged ceiling tiles and replace tiles
412298 03/08/2018 469645 P 9480 M Repair emergency lighting at rear door
412299 03/08/2018 469647 P 9480 M Repair emergency lighting at rear door
412295 03/08/2018 469639 P 9481 M Determine cause of water damaged ceiling tiles and replace tiles
412296 03/08/2018 469641 P 9481 M Repair rear door to close properly
412220 03/08/2018 469483 1 0000 O Provide name of Lead Crowd Manager who successfully completed the Crowd Management course as indicated in Bulletin # P-14808
412251 03/08/2018 469549 1 110 O Remove and prohibit hanging paper and decorations from ceiling
412242 03/08/2018 469529 1 130B O Keep area within 18 inches of fire sprinkler head clear and unobstructed
412248 03/08/2018 469541 1 142B O Keep area within 18 inches of fire sprinkler head clear and unobstructed
412279 03/08/2018 469606 1 203 O Remove and prohibit hanging paper and decorations from ceiling
412265 03/08/2018 469577 1 210A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
412275 03/08/2018 469598 1 221 O Remove and prohibit hanging paper and decorations from ceiling
412270 03/08/2018 469587 1 281 O Prohibit charging floor machine batteries in room (there is no ventilation in this room)
412292 03/08/2018 469633 P 9136 O Remove and prohibit hanging decorations (flags)from ceiling (Place on walls instead)
412258 03/08/2018 469563 1 106D MS Provide current inspection tag for fire extinguisher
412227 03/08/2018 469498 1 107J MS Provide current inspection tag for fire extinguisher
412233 03/08/2018 469510 1 126 MS Provide current inspection tag for fire extinguisher next to kiln room 1-126B
412259 03/08/2018 469565 1 195 MS Provide current inspection tag for fire extinguisher
412294 03/08/2018 469637 P 9481 MS Recharge fire extinguisher
412224 03/08/2018 469492 1 190 OS Remove storage from electrical room
412253 03/08/2018 469553 1 191 OS Remove storage from mechanical room
412260 03/08/2018 469567 1 197A OS Remove storage from electrical room
265748 03/08/2018 151259 1 0000 N/A No violations observed
265749 03/08/2018 151262 2 0000 N/A No violations observed
265755 03/08/2018 151274 P 9133 N/A No violations observed
261216 03/08/2018 143462 P 9134 N/A No violations observed
234661 03/08/2018 91992 P 9135 N/A No violations observed
265759 03/08/2018 151282 P 9136 N/A No violations observed
265760 03/08/2018 151284 P 9341 N/A No violations observed
265761 03/08/2018 151286 P 9342 N/A No violations observed
265762 03/08/2018 151288 P 9343 N/A No violations observed
265763 03/08/2018 151292 P 9344 N/A No violations observed
265764 03/08/2018 151294 P 9345 N/A No violations observed
265765 03/08/2018 151296 P 9408 N/A No violations observed
265766 03/08/2018 151298 P 9409 N/A No violations observed
265767 03/08/2018 151300 P 9410 N/A No violations observed
265768 03/08/2018 151302 P 9411 N/A No violations observed
265769 03/08/2018 151304 P 9412 N/A No violations observed
265770 03/08/2018 151306 P 9413 N/A No violations observed
265771 03/08/2018 151308 P 9479 N/A No violations observed
265772 03/08/2018 151310 P 9480 N/A No violations observed
265773 03/08/2018 151312 P 9481 N/A No violations observed
384380 10/24/2017 409414 00 0000 M Repair damaged basketball court surface to eliminate exposed concrete and tripping hazards
412219 10/24/2017 469481 1 0000 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report dated 4-26-17
400165 10/24/2017 443393 1 0000 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report dated 3.4.2016
400166 10/24/2017 443396 1 184 M Repair exhaust fan in custodial room
372419 10/24/2017 383415 00 0000 C Evacuation maps in classrooms have only primary evacuation routes. Indicate secondary evacuation routes in contrasting color on all evacuation maps
359090 10/24/2017 354500 P 0000 C Modify or improve storm drainage at all portables units to prevent storm water from going under units and undermining front and or rear landings
359091 10/24/2017 354503 P 0000 C Provide covered walkway to all portables
400111 02/14/2017 443277 1 102A M Patch hole in wall above fire extinguisher
400101 02/14/2017 443255 2 101 M Replace rusted soffit - roof edge at west end of pavilion
400170 02/14/2017 443404 P 9345 M Replace broken lens on light fixture in bathroom
400075 02/14/2017 443198 1 207A O Relocate two plastic storage units to oposite side of closet to keep area within 18 inches of fire sprinkler head clear and unobstructed
400171 02/14/2017 443406 P 9410 O Prohibit plugging surge protectors into extension cords under computer stations in center of room
400164 02/14/2017 443391 1 013 MS Adjust fire door to latch properly at top of stairwell adjacent to 1-227. Bottom of door rubs on flooring
400162 02/14/2017 443387 1 292 MS Provide current inspection tag for fire extinguisher
372476 01/26/2017 383544 1 126B M Repair inadequate kiln fan. Teacher indicates kiln room gets excessively hot when kiln is on
400169 01/26/2017 443402 1 132 M Secure drinking spout to sink
400114 01/26/2017 443285 1 183 M Secure loose escutcheon on fire sprinkler head
400167 01/26/2017 443398 1 184 M Secure loose escutcheon on fire sprinkler head
384359 01/26/2017 409370 1 193 M Repair leaking air conditioning system to ensure it operates as designed
400157 01/26/2017 443376 1 197A M Adjust door closer to control speed of closing door - door slams hard
400054 01/26/2017 443157 1 206 M Repair broken vinyl base along wall under writing board
400072 01/26/2017 443194 1 210C M Remove hook off bathroom door
400070 01/26/2017 443191 1 214 M Secure loose drinking spout to sink
400068 01/26/2017 443187 1 216 M Repair broken vinyl base along wall under writing board
400078 01/26/2017 443208 2 105 M Adjust door closer to control speed of closing door - PE coach office slams hard
400081 01/26/2017 443214 P 9133 M Repair emergency lighting above front door
400083 01/26/2017 443219 P 9134 M Repair emergency lighting above front door
400085 01/26/2017 443221 P 9135 M Repair emergency lighting above front door
400086 01/26/2017 443225 P 9136 M Repair emergency lighting above front door
400096 01/26/2017 443246 P 9136 M Repair broken vinyl base along wall adjacent to front door
400093 01/26/2017 443241 P 9342 M Repair emergency lighting above front door
400092 01/26/2017 443238 P 9408 M Repair emergency lighting above front door
400172 01/26/2017 443408 P 9410 M Adjust door closer to control speed of closing door - back door slams hard
400173 01/26/2017 443410 P 9412 M Repair or replace damaged floor tile with a hole
400090 01/26/2017 443234 P 9480 M Repair emergency lighting above front door
400088 01/26/2017 443229 P 9481 M Repair emergency lighting above front door
400099 01/26/2017 443250 P 9481 M Repair cracked floor tiles
400159 01/26/2017 443381 1 0000 O Remove and prohibit excessive flammable pink vinyl sheathing on corridor wall adjacent to 1-110
400163 01/26/2017 443389 1 0000 O Keep door to all custodial rooms locked and latched to prohibit student access to chemicals
400051 01/26/2017 443151 1 101K O Remove and prohibit excessive flammable yellow vinyl sheathing on table
400113 01/26/2017 443282 1 102A O Prohibit plugging surge protector into extension cord under desk facing door - plug surge protector directly into wall outlet
400160 01/26/2017 443383 1 107M O Eliminate brown extension cord with multiple outlet end for Christmas lights on cabinet or replace with a surge protector
400107 01/26/2017 443270 1 109 O Remove and prohibit hanging anchor charts from ceiling. You can place along wall or up to 2 inches away from wall
400106 01/26/2017 443267 1 110 O Remove and prohibit hanging anchor charts from ceiling. You can place along wall or up to 2 inches away from wall
400103 01/26/2017 443261 1 142 O Remove and prohibit hanging anchor charts from ceiling. You can place along wall or up to 2 inches away from wall
400057 01/26/2017 443164 1 203 O Remove and prohibit excessive flammable vinyl scenery on back wall adjacent to closet
400058 01/26/2017 443166 1 205 O Remove and prohibit paper covering window in door
400059 01/26/2017 443168 1 213 O Remove paper covering electrical outlets under writing board
400065 01/26/2017 443171 1 221 O Remove and prohibit hanging anchor charts from ceiling. You can place along wall or up to 2 inches away from wall
400066 01/26/2017 443184 1 226 O Remove and prohibit hanging anchor charts from ceiling. You can place along wall or up to 2 inches away from wall
400052 01/26/2017 443154 1 101Q MS Provide current inspection tag for fire extinguisher
400108 01/26/2017 443272 1 106D MS Provide current inspection tag for fire extinguisher
400161 01/26/2017 443385 1 107J MS Provide current inspection tag for fire extinguisher
400109 01/26/2017 443275 1 185 MS Provide current inspection tag for fire extinguisher
400095 01/26/2017 443243 P 9136 MS Secure loose latch guard on front door
400158 01/26/2017 443378 1 0000 OS Remove chains and padlock from exit gate between chillers and kitchen
400168 01/26/2017 443400 1 132B OS Remove storage from bathroom
400056 01/26/2017 443161 1 203 OS Relocate charging cart and student desk to maintain 3 ft clear path to corridor door
384336 11/18/2016 409321 1 0000 M Make necessary repairs as indicated on fire sprinkler inspection report. Tag in 1-014 stair is hanging too high to read date
384322 03/10/2016 409293 00 0000 M Repair or replace rusty, deteriorated bases for benches at bus loop
384405 03/10/2016 409469 00 0000 M Remove plants and trees growing from covered walk at portables and parent drop off
384382 03/10/2016 409416 00 0000 M Remove wasp nest on basketball hoop backstop
384338 03/10/2016 409326 1 001 M Repair damaged flooring at exterior east (bus loop) and west (parent drop off) entrance doors
384340 03/10/2016 409330 1 001 M Determine cause of water damaged ceiling tiles at west (parent drop off) entrance doors and replace tiles
384361 03/10/2016 409373 1 002 M Repair exterior doors at 1-126 to close and latch properly
384352 03/10/2016 409354 1 002 M Determine cause of water damaged ceiling tiles in corridor adjacent to 1-191 and replace tiles
384323 03/10/2016 409295 1 010 M Repair or replace damaged door at 1st floor
384365 03/10/2016 409382 1 013 M Adjust door closer on 1st floor corridor door to control speed of closing door
384326 03/10/2016 409301 1 015 M Replace missing doorstop at 1-281
384330 03/10/2016 409309 1 015 M Determine cause of water damaged ceiling tiles adjacent to 1-219 and replace tiles
384343 03/10/2016 409338 1 102A M Make necessary repairs as indicated on Fire Alarm Inspection report
384344 03/10/2016 409340 1 102A M Mount fire extinguisher at maximum five feet above floor
384347 03/10/2016 409346 1 103A M Replace missing escutcheons on fire sprinkler heads
384350 03/10/2016 409350 1 104 M Remove grounding plug prong from electrical outlet adjacent to 1-104D
384412 03/10/2016 409483 1 104 M Secure loose screen on side of kitchen hood
384348 03/10/2016 409348 1 104D M Secure cables and loose cover on data junction box
384341 03/10/2016 409333 1 106C M Repair door to close and latch properly, door handle loose
384355 03/10/2016 409362 1 111A M Repair inoperable thumb latch
384342 03/10/2016 409336 1 115 M Repair or replace damaged laminate on countertop
384356 03/10/2016 409365 1 117 M Determine cause of water damaged ceiling tiles and replace tiles
384320 03/10/2016 409289 1 119 M Determine cause of water damaged ceiling tiles and replace tiles
384318 03/10/2016 409285 1 123 M Repair holes in walls
384363 03/10/2016 409377 1 128 M Secure loose base on wall under white board and at 1-128A
384379 03/10/2016 409411 1 130 M Repair rusty, damaged exterior door
384369 03/10/2016 409390 1 132 M Provide type K fire extinguisher at kitchen area, remove ABC fire extinguisher
384364 03/10/2016 409380 1 133 M Repair hole in wall finish at north corridor door
384367 03/10/2016 409386 1 136 M Provide type K fire extinguisher at kitchen area, remove ABC fire extinguisher
384368 03/10/2016 409388 1 136 M Provide cover on exposed data junction box at teachers desk
384409 03/10/2016 409479 1 136 M Repair rusty, damaged exterior door
384366 03/10/2016 409384 1 140 M Provide type K fire extinguisher at kitchen area, remove ABC fire extinguisher
384346 03/10/2016 409344 1 185 M Replace missing ceiling tiles
384378 03/10/2016 409399 1 194 M Properly secure cover for Altronix unit
384345 03/10/2016 409342 1 195 M Mount fire extinguisher at maximum five feet above floor
384353 03/10/2016 409357 1 198 M Repair or replace damaged, split hot water heater cases (N/A split cases inspected by zone team plumber, cosmetic, not a hazard at this time March 2016)
384404 03/10/2016 409467 1 199C M Repair leaking air conditioning system to ensure it operates as designed
384331 03/10/2016 409311 1 280 M Replace missing cover on light fixture
384324 03/10/2016 409297 1 293 M Adjust door to open and close properly
384325 03/10/2016 409299 1 293 M Mount fire extinguisher at maximum five feet above floor
384383 03/10/2016 409420 2 101 M Secure loose siding on drinking fountain adjacent to 2-105
372522 03/10/2016 383644 P 0000 M Trim Oak trees off of covered walkway north of portables
384390 03/10/2016 409433 P 9408 M Repair rusty, damaged entrance door
384403 03/10/2016 409464 P 9409 M Repair inoperable bathroom door lock
384399 03/10/2016 409453 P 9411 M Anchor toilet to floor
384407 03/10/2016 409472 P 9413 M Provide cover on exposed electrical junction box at south door
384408 03/10/2016 409476 P 9413 M Anchor toilet to floor
384319 03/10/2016 409287 1 123 O Replace missing sign indicating primary and secondary evacuation routes in contrasting colors
384334 03/10/2016 409319 1 204 O Remove and prohibit hanging paper (anchor charts) from ceiling in center of room. Anchor charts may hang from ceiling no more than 2 inches from wall surface
384333 03/10/2016 409315 1 208 O Remove and prohibit hanging paper (anchor charts) from ceiling in center of room. Anchor charts may hang from ceiling no more than 2 inches from wall surface
384327 03/10/2016 409303 1 224 O Prohibit white 13A multi outlet extension cord at microwave or replace with minimum 15A single outlet extension cord
384329 03/10/2016 409307 1 226 O Prohibit brown 13A multi outlet extension cord at teachers desk or replace with minimum 15A single outlet extension cord
384328 03/10/2016 409305 1 226A O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
384388 03/10/2016 409428 P 9345 O Prohibit black multi outlet extension cord at desk adjacent to west exterior door or replace with minimum 15A single outlet extension cord or surge protector
384394 03/10/2016 409439 P 9408 O Provide certification that residential chair meets NFPA 701 or TB 117 standards or remove and prohibit combustible (residential) chair
384402 03/10/2016 409461 P 9410 O Prohibit plugging surge protector into orange extension cord
384386 03/10/2016 409425 2 190 MS Adjust door to latch properly
384398 03/10/2016 409451 P 9341 MS Recharge fire extinguisher, replace with fire extinguisher without rust and peeling paint
384357 03/10/2016 409367 1 193 OS Remove storage from mechanical room
384321 03/10/2016 409291 1 199 OS Remove storage from mechanical room
384397 03/10/2016 409449 P 9343 OS Maintain clear aisle to west exit
384400 03/10/2016 409457 P 9410 OS Relocate shelf at east door to maintain clear aisle to exit
359172 11/12/2015 354684 1 0000 M Remove rust from and refinish rusting canopy over east entry
372481 11/12/2015 383554 1 101J M Plumbing pipes water hammer when cold water faucet is closed at sink. Eliminate water hammer
372422 11/12/2015 383423 P 9344 M Connect downspout to storm drainage system
372521 04/22/2015 383641 1 0000 M Remove sod, dirt and weeds from parking spaces west of east retention pond. Provide channels to drain to retention area
372379 04/17/2015 383325 1 191 M Run water pump and check for leaks. Rust on impeller housing
372421 04/07/2015 383420 00 0000 M Eliminate ant infestation in play fields
372440 04/07/2015 383463 00 0000 M Remove Palmettos growing in chiller compound
359241 04/07/2015 354831 00 0000 M Fill around pull boxes in fenced play area SE of 1-199B
372477 04/07/2015 383546 1 0000 M Cover or remove exposed steel mesh in sidewalk that runs north and south. West of 1-101
372485 04/07/2015 383563 1 0000 M Repair hole in floor of 2nd floor corridor outside of room 1-213
372488 04/07/2015 383569 1 014 M Provide current quarterly inspection tag for fire sprinkler system in stair tower
372417 04/07/2015 383411 1 101E M Repair leaking toilet supply line
372413 04/07/2015 383403 1 104 M Panel 1LKA breaker 5 tripped. Panel 1LK breaker 41 tripped. Repair circuits
372404 04/07/2015 383384 1 104 M Clean Kitchen hood and provide tag with date of cleaning. Last cleaning 4-2-13
372408 04/07/2015 383393 1 105C M Repair leaking toilet supply line
372472 04/07/2015 383535 1 106D M Make light switch plate flush with wall, sharp edges are exposed.
372441 04/07/2015 383465 1 109A M Repair leaking toilet supply line
372446 04/07/2015 383475 1 112B M Repair leaking toilet supply line
372407 04/07/2015 383391 1 115 M Replace cracked urinal
372473 04/07/2015 383537 1 116B M Caulk bathroom sink to wall
372480 04/07/2015 383552 1 119A M Plumbing pipes water hammer when toilet is flushed. Eliminate water hammer
372444 04/07/2015 383471 1 120B M Repair leaking toilet supply line
372445 04/07/2015 383473 1 120B M Replace missing escutcheon on fire sprinkler head
372442 04/07/2015 383467 1 122A M Repair leaking toilet supply line
372443 04/07/2015 383469 1 122A M Secure and caulk sink to wall
372450 04/07/2015 383483 1 124 M Secure loose handicapped grabrail
372411 04/07/2015 383399 1 132B M Secure and caulk sink to wall
372479 04/07/2015 383550 1 134A M Repair leaking toilet supply line
372418 04/07/2015 383413 1 135B M Repair leaking toilet supply line
372410 04/07/2015 383397 1 136 M Repair damaged wall at rear door and refinish wall
372447 04/07/2015 383477 1 138 M Secure loose and replace missing base along wall at rear door
372482 04/07/2015 383557 1 181 M Repair or replace leaking water heater. Standing water in drain pan
372474 04/07/2015 383539 1 185 M Provide current annual inspection tag for fire sprinkler system. Riser not in room
372414 04/07/2015 383405 1 194 M Panel 1LB breaker 29 tripped. Repair circuit.
372409 04/07/2015 383395 1 196 M Panel 1L breaker 77 tripped. Repair circuit
372377 04/07/2015 383320 1 197 M Provide certification that all student occupied spaces have emergency lights and all are operable. Last certification 1-10-13
372454 04/07/2015 383491 1 197A M Repair door to 1-197 to open and close properly. Drags on top of frame
372439 04/07/2015 383461 1 198 M Repair or replace leaking water heater
372514 04/07/2015 383627 1 201 M Secure loose base along wall under white board
372515 04/07/2015 383629 1 202C M Secure and caulk sink to wall
372513 04/07/2015 383624 1 203B M Caulk sink to wall
372517 04/07/2015 383633 1 204A M Secure and caulk sink to wall
372518 04/07/2015 383635 1 204A M Secure faucet to sink
372519 04/07/2015 383637 1 204A M Determine cause of water damaged ceiling tiles and replace tiles
372520 04/07/2015 383639 1 204A M Repair leaking toilet supply line
372487 04/07/2015 383567 1 205 M Determine cause of water damaged ceiling tiles and replace tiles in raised soffit at windows
372490 04/07/2015 383573 1 206C M Caulk sink to wall
372486 04/07/2015 383565 1 207 M Determine cause of water damaged ceiling tiles and replace tiles
372509 04/07/2015 383614 1 207 M Secure power pole to floor
372516 04/07/2015 383631 1 208A M Secure and caulk sink to wall
372498 04/07/2015 383590 1 210A M Anchor shelving to wall
372494 04/07/2015 383582 1 211A M Repair leaking toilet supply line
372492 04/07/2015 383577 1 211B M Determine cause of water damaged ceiling tiles and replace tiles
372497 04/07/2015 383588 1 211B M Secure and caulk sink to bathroom wall
372491 04/07/2015 383575 1 212C M Caulk sink to wall
372496 04/07/2015 383586 1 213B M Repair leaking toilet supply line
372493 04/07/2015 383579 1 218 M Repair leaking toilet supply line
372495 04/07/2015 383584 1 224A M Repair leaking toilet supply line
372499 04/07/2015 383592 1 280 M Repair exhaust fan, not running
372503 04/07/2015 383600 1 281 M Repair damaged wall at floor sink and cover with tile, stainless steel, plastic
372500 04/07/2015 383594 1 290 M Panel 2LA breaker tripped. Repair circuit
372505 04/07/2015 383605 1 293 M Install bracket and hang fire extinguisher sitting on floor at maximum five feet above floor
372391 04/07/2015 383353 P 9133 M Repair auto closer on front door
372385 04/07/2015 383339 P 9133 M Secure and caulk bathroom sink to wall
372386 04/07/2015 383341 P 9133 M Replace missing epoxy flooring in bathroom
372394 04/07/2015 383361 P 9134 M Secure and caulk bathroom sink to wall
372396 04/07/2015 383363 P 9134 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they no longer contact ground
372400 04/07/2015 383372 P 9135 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they no longer contact ground
372402 04/07/2015 383378 P 9136 M Provide cover on exterior electrical junction box
372403 04/07/2015 383380 P 9136 M Repair leaking toilet supply line
359099 04/07/2015 354525 P 9136 M Refinish bathroom floor. Epoxy flooring not bonded and coming up
372406 04/07/2015 383388 P 9342 M Secure bottom of base to floor. Bottom of base has been pushed under drywall and wall is no longer impervious
372424 04/07/2015 383429 P 9345 M Anchor 2 metal shelves to wall
372425 04/07/2015 383431 P 9345 M Make repair at bathroom sink impervious
372426 04/07/2015 383434 P 9408 M Anchor projector screen backboard to wall
372427 04/07/2015 383436 P 9408 M Secure loose base along wall in bathroom
372430 04/07/2015 383442 P 9410 M Adjust rear door to latch properly
372432 04/07/2015 383446 P 9410 M Determine cause of water damaged ceiling tiles and replace tiles at mate line
372431 04/07/2015 383444 P 9411 M Repair emergency lighting X 2
372434 04/07/2015 383450 P 9412 M Repair emergency lighting at rear of unit
372436 04/07/2015 383455 P 9479 M Adjust rear door to latch properly
372438 04/07/2015 383459 P 9481 M Secure and caulk sink to wall in bathroom. Make repair impervious
372478 04/07/2015 383548 00 0000 O Provide name of Lead Crowd Manager who successfully completed the Crowd Management course as indicated in Bulletin # P-14808
372416 04/07/2015 383409 1 101R O Keep area within 18 inches of fire sprinkler head clear and unobstructed
372451 04/07/2015 383485 1 124 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
372420 04/07/2015 383418 1 130 O 10 to 12 large sheets of paper are hanging from ceiling. This is too much. Reduce amount of paper hanging from ceiling to 5 sheets. Paper is acceptable against wall or on string lines close to wall
372449 04/07/2015 383481 1 140A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
372483 04/07/2015 383559 1 181 O Prohibit charging batteries in room
372484 04/07/2015 383561 1 183 O Prohibit charging batteries in room
372475 04/07/2015 383542 1 185 O Remove trash from behind dryer
372512 04/07/2015 383621 1 204B O Keep area within 18 inches of fire sprinkler head clear and unobstructed
372510 04/07/2015 383616 1 205A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
372511 04/07/2015 383618 1 205B O Keep area within 18 inches of fire sprinkler head clear and unobstructed
372508 04/07/2015 383612 1 207A O Maintain storage room in an orderly manner
372502 04/07/2015 383598 1 281 O Remove and prohibit plug-in air freshener
372433 04/07/2015 383448 P 9412 O Provide clear access to electrical panel
372437 04/07/2015 383457 P 9481 O Remove and prohibit paper covering window in front door
372415 04/07/2015 383407 1 101Q MS Provide current inspection tag for fire extinguisher
372452 04/07/2015 383487 1 117 MS Adjust door to corridor 1-002 to latch properly
372453 04/07/2015 383489 1 197A MS Prohibit hold open device on door to 1-197
372507 04/07/2015 383610 1 221B MS Repair thumb latch to enable door to be unlocked from outside of room
372393 04/07/2015 383356 P 9133 MS Replace missing fire extinguisher
372489 04/07/2015 383571 1 0000 OS Relocate trash and recycle cans adjacent to doors to stairs 1-014 and 1-013
372448 04/07/2015 383479 1 140 OS Maintain clear aisle to rear exit. Remove storage
372504 04/07/2015 383603 1 293 OS Remove old light tubes stored in electrical room. Store in custodial closet or custodial storage
372388 04/07/2015 383348 P 9133 OS Maintain clear aisle to rear exit
372398 04/07/2015 383369 P 9135 OS Maintain clear aisle to rear exit
372412 04/07/2015 383401 P 9343 OS Maintain clear aisle to rear exit
372423 04/07/2015 383425 P 9345 OS Maintain clear aisle to rear exit. Relocate file cabinets
372428 04/07/2015 383438 P 9408 OS Maintain clear aisle to rear exit
372429 04/07/2015 383440 P 9410 OS Maintain clear aisle to rear exit
372435 04/07/2015 383452 P 9412 OS Maintain clear aisle to rear exit
359080 01/06/2015 354479 00 0000 M Repair roof. Large bubbles in membrane on low roof. Membrane is cracking. NA, roof not leaking per Jim Bowen
359237 12/01/2014 354819 1 191 M Replace missing drywall
359140 12/01/2014 354615 P 9480 M Refinish exterior of unit. Paint is loose, missing and bubbling up
359178 04/02/2014 354696 00 0000 M Replace broken irrigation head east of SE covered play area
359176 04/02/2014 354692 00 0000 M Label 2 fire department connections at SE campus.
359242 04/02/2014 354833 1 101E M Replace GFCI outlet that will not trip
359245 04/02/2014 354839 1 101J M Determine cause of water damaged ceiling tiles and replace tiles adjacent to exterior wall
359218 04/02/2014 354782 1 102 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to NW exit to exterior. Check for possible fire sprinkler leak
359110 04/02/2014 354551 1 104 M Replace missing spacer in panel 1LKA
359227 04/02/2014 354800 1 104E M Provide protective cage around fire sprinkler head in walk-in freezer
359228 04/02/2014 354803 1 104F M Provide protective cage around fire sprinkler head in walk-in cooler
359230 04/02/2014 354806 1 108B M Secure handicapped sink to wall
359128 04/02/2014 354589 1 110 M Remove pencil sharpener without cover adjacent to door
359120 04/02/2014 354573 1 110B M Caulk sink to wall
359122 04/02/2014 354578 1 111 M Determine cause of water damaged ceiling tiles and replace tiles
359124 04/02/2014 354580 1 111A M Caulk sink to wall
359121 04/02/2014 354575 1 112B M Caulk sink to wall
359238 04/02/2014 354823 1 113 M Caulk backsplash
359239 04/02/2014 354827 1 113 M Repair leaking supply lines for toilets 1,2 and 4
359088 04/02/2014 354495 1 114 M Secure loose drinking fountain
359089 04/02/2014 354497 1 114A M Caulk sink to wall
359240 04/02/2014 354829 1 115 M Repair leaking supply line for toilet 2
359232 04/02/2014 354810 1 117 M Relocate maximum occupancy signage outside of south door to be inside room adjacent to exit
359087 04/02/2014 354493 1 118 M Replace GFCI outlet that will not trip
359085 04/02/2014 354489 1 120B M Refinish patched wall
359086 04/02/2014 354491 1 120B M Caulk sink to wall
359084 04/02/2014 354487 1 122 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to teachers station
359083 04/02/2014 354485 1 124 M Secure loose handicapped grabrail
359082 04/02/2014 354483 1 125 M Secure loose handicapped grabrail
359081 04/02/2014 354481 1 126B M Adjust door to latch properly
359266 04/02/2014 354883 1 130A M Repair leaking supply line for toilet
359268 04/02/2014 354887 1 130B M Keep area within 18 inches of fire sprinkler head clear and unobstructed. Remove top shelf
359265 04/02/2014 354881 1 134 M Remove pencil sharpener without cover adjacent to door
359263 04/02/2014 354877 1 134A M Secure loose cleanout cover under sink
359244 04/02/2014 354835 1 181 M Replace GFCI outlet that will not trip
359281 04/02/2014 354914 1 184 M Anchor shelving to wall
359282 04/02/2014 354916 1 184 M Replace missing ceiling tiles
359113 04/02/2014 354557 1 185 M Repair damaged drywall adjacent to door and provide corner guard to prevent further damage
359234 04/02/2014 354814 1 191 M Close and lock open EMS box
359248 04/02/2014 354847 1 193 M Close and lock open EMS cabinet
359249 04/02/2014 354849 1 193 M Anchor air handler 4 at 4 corners
359284 04/02/2014 354919 1 194 M Room very hot, in excess of 100 degrees. 3 transformers in room. Improve ventilation to reduce temperature
359111 04/02/2014 354553 1 195 M Close and lock open Altronix cabinet
359119 04/02/2014 354571 1 196 M Panel 1L breaker 1 tripped. Repair circuit
359171 04/02/2014 354682 1 199 M Close and lock open EMS cabineet
359173 04/02/2014 354686 1 199A M Repair badly rusted door frame and reattach closer to frame
359174 04/02/2014 354688 1 199A M Anchor air handler at 4 corners
359175 04/02/2014 354690 1 199A M Close and lock open EMS cabinet
359264 04/02/2014 354879 1 199B M Close and lock EMS cabinet
359255 04/02/2014 354862 1 199C M Anchor air handler at 4 corners
359256 04/02/2014 354864 1 199C M Close and lock open EMS cabinet
359169 04/02/2014 354677 1 202C M Secure sink to wall
359297 04/02/2014 354946 1 203B M Repair leaking plumbing fixture in bathroom. Floor flooded
359168 04/02/2014 354675 1 204A M Secure sink to wall
359296 04/02/2014 354944 1 205 M Remove damaged pencil sharpener adjacent to door
359294 04/02/2014 354940 1 205A M Repair exhaust fan in bathroom
359293 04/02/2014 354938 1 207B M Repair exhaust fan in bathroom
359148 04/02/2014 354633 1 210C M Determine cause of water damaged ceiling tiles and replace tiles
359149 04/02/2014 354635 1 210C M Repair exhaust fan in bathroom
359150 04/02/2014 354637 1 210C M Replace missing screw in switch plate
359152 04/02/2014 354641 1 211A M Repair exhaust fan in bathroom
359153 04/02/2014 354644 1 211A M Secure sink to wall in bathroom
359154 04/02/2014 354647 1 212C M Secure sink to wall in bathroom
359155 04/02/2014 354649 1 214 M Replace GFCI outlet that will not trip
359289 04/02/2014 354930 1 215A M Repair exhaust fan in bathroom
359290 04/02/2014 354933 1 215A M Repair thumb latch lock release on door. Hard to operate
359156 04/02/2014 354651 1 216B M Caulk sink to wall
359157 04/02/2014 354653 1 216B M Repair exhaust fan in bathroom
359159 04/02/2014 354657 1 219B M Secure sink to wall in bathroom
359160 04/02/2014 354659 1 219B M Repair exhaust fan in bathroom
359162 04/02/2014 354661 1 220A M Caulk sink to wall in bathroom
359163 04/02/2014 354664 1 220A M Repair exhaust fan in bathroom
359164 04/02/2014 354667 1 220B M Anchor plastic shelving to wall
359288 04/02/2014 354927 1 221B M Caulk sink to wall
359165 04/02/2014 354669 1 222B M Caulk sink to wall in bathroom
359166 04/02/2014 354671 1 223A M Caulk sink to wall in bathroom
359167 04/02/2014 354673 1 224A M Replace damaged toilet seat
359286 04/02/2014 354925 1 225B M Caulk sink to wall
359104 04/02/2014 354538 1 280 M Anchor shelving to wall
359292 04/02/2014 354935 1 291 M Close and lock EMS cabinet
359270 04/02/2014 354890 2 104 M Secure lid for outside lighting contactor box
359179 04/02/2014 354698 P 0000 M Provide chain and lock on gate of fencing around electrical equipment south of P-418
359180 04/02/2014 354700 P 0000 M Provide chain and lock on gate of fencing around pump enclosure SW of P-418
359214 04/02/2014 354773 P 0000 M Replace missing frame and grate for top of storm drainage pipe SW of P-418
359216 04/02/2014 354778 P 0000 M Provide chain and lock on gate of fencing around lift station W of P-413
359092 04/02/2014 354506 P 9134 M Replace damaged drywall at rear door and secure lose base
359093 04/02/2014 354509 P 9135 M Adjust auto closer on front door. Closes too fast
359096 04/02/2014 354515 P 9135 M Caulk sink to wall in bathroom
359098 04/02/2014 354521 P 9136 M Caulk sink to wall in bathroom
359101 04/02/2014 354529 P 9136 M Fill hole in floor at mate line
359102 04/02/2014 354531 P 9341 M Secure loose base along wall in bathroom
359105 04/02/2014 354540 P 9344 M Repair emergency lighting at rear door
359170 04/02/2014 354680 P 9344 M Connect downspout to storm sewer line
359106 04/02/2014 354542 P 9345 M Repair emergency lighting at rear door
359107 04/02/2014 354544 P 9345 M Refinish bathroom floor at toilet. New toilet installed and unfinished floor exposed
359108 04/02/2014 354547 P 9409 M Replace short ceiling tile that does not fill the opening in the ceiling grid
359109 04/02/2014 354549 P 9409 M Repair bathroom door to open and close properly. Rubs on frame
359132 04/02/2014 354598 P 9410 M Adjust rear door to latch properly. Adjust or replace closer
359133 04/02/2014 354601 P 9410 M Secure loose base along wall in bathroom
359135 04/02/2014 354604 P 9410 M Secure loose ground to building or bury it. At rear of unit
359136 04/02/2014 354607 P 9411 M Exterminate ants in classroom
359137 04/02/2014 354609 P 9413 M Secure loose base along wall in bathroom
359138 04/02/2014 354611 P 9413 M Secure loose ground to building or bury it At rear of unit
359141 04/02/2014 354618 P 9480 M Secure loose base along wall adjacent to rear door
359142 04/02/2014 354620 P 9480 M Secure loose ground to building or bury it. At rear of unit
359143 04/02/2014 354622 P 9480 M Caulk sink to wall in bathroom
359144 04/02/2014 354624 P 9481 M Caulk sink to wall in bathroom
359145 04/02/2014 354626 P 9481 M Replace damaged drywall adjacent to rear door and replace base
359146 04/02/2014 354628 P 9481 M Secure loose ground to building or bury it. At rear of unit
359130 04/02/2014 354595 1 110A O Keep area within 18 inches of fire sprinkler head clear and unobstructed. Remove top shelf from shelving unit
359126 04/02/2014 354584 1 114 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
359262 04/02/2014 354875 1 136 O Remove and prohibit storage on cook top
359254 04/02/2014 354859 1 137 O Prohibit plugging mocrowave oven into surge protector - plug directly into permanent electrical outlet
359258 04/02/2014 354868 1 140A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
359112 04/02/2014 354555 1 185 O Remove trash from behind dryer
359295 04/02/2014 354942 1 205A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
359147 04/02/2014 354631 1 210A O Keep area within 18 inches of fire sprinkler head clear and unobstructed
359158 04/02/2014 354655 1 281 O Prohibit charging batteries in room
359097 04/02/2014 354517 P 9135 O Provide clear access to electrical panel
359139 04/02/2014 354613 P 9479 O Provide clear access to electrical panel
359177 04/02/2014 354694 00 0000 C Provide lock on gate of fencing around retention pond at extreme SE campus
359116 04/02/2014 354565 1 0000 C Provide bollards around gas meter and valve outside of 1-198
359247 04/02/2014 354844 1 001 C Provide or verify tempered or safety glazing in display cabinet
359253 04/02/2014 354856 1 005 MS Recharge fire extinguisher in corridor adjacent to 1-133
359219 04/02/2014 354786 1 106B MS Recharge fire extinguisher
359117 04/02/2014 354567 1 197 MS Prohibit hold open devices on fire doors
359118 04/02/2014 354569 1 197A MS Prohibit hold open devices on fire doors
359094 04/02/2014 354511 P 9135 MS Replace missing fire extinguisher and mounting hook
359285 04/02/2014 354923 1 003 OS Prohibit hold open device on fire door at top of stairs
359224 04/02/2014 354794 1 106 OS Remove and prohibit storage on stage exit stairs
359222 04/02/2014 354788 1 106A OS Remove and prohibit storing cart on stage ramp exit.
359261 04/02/2014 354872 1 138 OS Maintain clear aisle to rear exit
359259 04/02/2014 354870 1 140 OS Maintain clear aisle to rear exit
359095 04/02/2014 354513 P 9135 OS Maintain clear aisle to rear exit
359100 04/02/2014 354527 P 9136 OS Maintain clear aisle to front exit. Remove chairs
359103 04/02/2014 354533 P 9342 OS Maintain 3 foot clear aisle to rear exit
319246 12/04/2013 267068 1 104 M Provide current inspection tag for boiler (kitchen steamer). Tankless steamer installed
345973 03/22/2013 325567 00 0000 M Repair uneven concrete at transition from basketball court to sidewalk leading SW to portables
346090 03/22/2013 325814 1 001A M Adjust door closer on exterior door adjacent to 1-101T to control speed of closing door
345956 03/22/2013 325531 1 002 M Adjust door closer on west exterior door adjacent to 1-182 to control speed of closing door
346088 03/22/2013 325810 1 008 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to 1-107L
345796 03/22/2013 325200 1 009 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to 1-010 stairs
345962 03/22/2013 325544 1 102A M Replace missing base on wall
345963 03/22/2013 325546 1 106A M Repair damaged wall at intermediate landing for stage ramp
345961 03/22/2013 325542 1 106D M Determine cause of water damaged ceiling tiles and replace tiles
346086 03/22/2013 325806 1 107 M Provide cover for electrical outlet in ceiling at projector
346087 03/22/2013 325808 1 107J M Secure loose fire extinguisher bracket
345807 03/22/2013 325221 1 114A M Replace missing escutcheon on fire sprinkler head
345773 03/22/2013 325149 1 119A M Repair hole in wall tile
345804 03/22/2013 325216 1 122 M Determine cause of water damaged ceiling tiles and replace tiles
345801 03/22/2013 325209 1 129 M Determine cause of water damaged ceiling tiles and replace tiles
345802 03/22/2013 325212 1 129 M Repair leaking toilet, leaks when flushed
345778 03/22/2013 325161 1 134 M Anchor grey plastic shelving to wall
346078 03/22/2013 325790 1 170 M Provide current inspection tag for elevator
345774 03/22/2013 325151 1 183 M Repair exhaust fan
345798 03/22/2013 325203 1 184 M Determine cause of water damaged ceiling tiles and replace tiles
345958 03/22/2013 325537 1 185 M Determine cause of water damaged ceiling tiles and replace tiles
345960 03/22/2013 325539 1 185B M Determine cause of water damaged ceiling tiles and replace tiles
345957 03/22/2013 325535 1 191 M Adjust door closer to control speed of closing door
345800 03/22/2013 325206 1 194 M Repair door to close and latch properly
345785 03/22/2013 325176 1 199A M Repair door to close and latch properly
346073 03/22/2013 325780 1 199C M Repair door to latch properly
346084 03/22/2013 325802 1 206 M Repair damaged corridor door handle
346082 03/22/2013 325798 1 207 M Secure loose base along wall
346083 03/22/2013 325800 1 207 M Provide cover on exposed electrical junction box adjacent to emergency shut off
309294 03/22/2013 245180 1 216B M Replace missing escutcheon on fire sprinkler head
346080 03/22/2013 325794 1 293 M Mount fire extinguisher at maximum five feet above floor
345966 03/22/2013 325552 2 101 M Repair damaged concrete sidewalk at adjoining sections of concrete on north side of covered pavilion adjacent to 2-102.
345965 03/22/2013 325550 2 103 M Adjust door closer to control speed of closing door
345964 03/22/2013 325548 2 105 M Adjust door closer to control speed of closing door
346056 03/22/2013 325744 P 0000 M Verify epoxy wall finish in bathrooms of portables P-401, P-402, P-403, P-404, P-405, P-406, P-407, P-408, P-409, P-410, P-417, P-418
346058 03/22/2013 325748 P 9133 M Repair damaged bathroom door lock
346059 03/22/2013 325750 P 9134 M Adjust door closer on south door to control speed of closing door
346060 03/22/2013 325752 P 9135 M Repair emergency lighting at south door
346068 03/22/2013 325770 P 9341 M Repair emergency lighting a east door
346069 03/22/2013 325772 P 9341 M Repair west door to close properly
346067 03/22/2013 325768 P 9343 M Adjust door closer on west door to control speed of closing door
346064 03/22/2013 325761 P 9344 M Adjust door closer on west door to control speed of closing door
346066 03/22/2013 325765 P 9345 M Adjust door closer on west door to control speed of closing door
346071 03/22/2013 325776 P 9411 M Adjust door closer on east door to control speed of closing door
346076 03/22/2013 325786 P 9412 M Anchor two grey and one wood shelf (adjacent to bathroom) to wall
346074 03/22/2013 325782 P 9479 M Adjust door closer on north door to control speed of closing door
346075 03/22/2013 325784 P 9479 M Repair emergency lighting
346061 03/22/2013 325754 P 9481 M Mount fire extinguisher at maximum five feet above floor
346089 03/22/2013 325812 1 101 O Prohibit plugging surge protector into surge protector at desks adjacent to 1-101B
345805 03/22/2013 325218 1 114 O Provide minimum one foot blank wall space on lock side of door
345777 03/22/2013 325159 1 138 O Provide minimum one foot blank wall space on lock side of door of exterior door
345775 03/22/2013 325153 1 142 O Provide minimum one foot blank wall space on lock side of door exterior door
346085 03/22/2013 325804 1 202 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
346070 03/22/2013 325774 P 9341 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
346063 03/22/2013 325759 P 9344 O Remove and prohibit excessive paper coverage on walls, maximum coverage is 20 percent of each wall
251801 03/22/2013 123966 1 193A C Provide signage indicating room name and number at appropriate height with raised and Braille characters
346057 03/22/2013 325746 P 0000 C Modify or improve drainage at portables P-412, P-413, P-414, P-415, P-416. Water from rain gutters is eroding areas under concrete landings. Areas under landings for P-408, P-309 and P-410 are eroding. Make necessary repairs to prevent further erosion and fill missing dirt from under landings
345809 03/22/2013 325224 1 110A OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
345803 03/22/2013 325214 1 128A OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
345782 03/22/2013 325167 1 130B OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
345779 03/22/2013 325163 1 132 OS Relocate table to maintain clear aisle to (exterior) exit
345780 03/22/2013 325165 1 132A OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
345776 03/22/2013 325157 1 142B OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
230489 03/22/2013 83869 1 183 OS Prohibit recharging batteries in janitor closet
346081 03/22/2013 325796 1 216A OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
346079 03/22/2013 325792 1 219 OS Remove and prohibit use of toaster
346062 03/22/2013 325756 P 9344 OS Maintain clear aisle to west exit
346072 03/22/2013 325778 P 9411 OS Maintain clear aisle to east exit
346077 03/22/2013 325788 P 9412 OS Maintain clear aisle to south exit
346304 03/22/2013 326284 1 199B CS Provide automatic fire sprinkler coverage for area under duct which is in excess of four feet wide (NA current coverage is adequate)
319248 12/04/2012 267072 1 106 M Provide dated flame resistance label on stage curtain
319253 12/04/2012 267082 1 107G M Provide dated flame resistance label on CCTV studio curtain
201413 12/04/2012 9816 00 0000 C Provide fence around eastern retention pond
251759 12/04/2012 123865 00 0000 C Provide fence around west retention pond
319249 12/04/2012 267074 1 106 C Provide records that stage rigging has been inspected and conforms to required safety standards
346301 12/04/2012 326278 1 199A CS Provide automatic fire sprinkler coverage for area under duct which is in excess of four feet wide (NA, current coverage is adequate)
331109 04/03/2012 293433 1 009 M Replace missing escutcheon on fire sprinkler head in first floor corridor adjacent to stairway 1-010
331108 04/03/2012 293431 1 010 M Immediately replace missing fire door in corridor at bottom of stairway
331093 04/03/2012 293401 1 101J M Mount fire extinguisher at maximum five feet above floor (mounting bracket has become loose and needs to be secured to wall)
331111 04/03/2012 293438 1 197 M Provide current certification that all student occupied spaces have emergency lights and all are operable (date on certification is not current)
331113 04/03/2012 293442 1 207 M Replace missing escutcheon on fire sprinkler head
331097 04/03/2012 293409 P 0000 M Fill dirt along sidewalks in front of P-417 and P-418 to prevent tripping hazard
331105 04/03/2012 293425 P 9133 M Prevent exposed electrical wiring on emergency light at rear door
331104 04/03/2012 293423 P 9134 M Determine cause of water damaged ceiling tiles and replace tiles
331102 04/03/2012 293419 P 9135 M Determine cause of water damaged ceiling tiles adjacent to front door and replace tiles
331099 04/03/2012 293413 P 9136 M Mount fire extinguisher at maximum five feet above floor (extinguisher is currently sitting on floor)
331100 04/03/2012 293415 P 9136 M Repair emergency lighting at both exit doors
331098 04/03/2012 293411 P 9344 M Repair emergency lighting at front door
331096 04/03/2012 293407 P 9479 M Repair rear exit door to close properly (door drags on threshold
331106 04/03/2012 293427 P 9480 M Replace broken cover for exposed electrical outlet next to front door
331107 04/03/2012 293429 P 9480 M Repair emergency lights at both exit doors
331103 04/03/2012 293421 P 9481 M Provide cover on exposed electrical junction box on exterior wall next to front door
319252 04/03/2012 267080 1 107G C Provide records that CCTV studio rigging has been inspected and conforms to required safety standards
331112 04/03/2012 293440 1 102A MS Provide current inspection tag for fire extinguisher
331094 04/03/2012 293403 1 140 MS Provide current inspection tag for fire extinguisher
331101 04/03/2012 293417 P 9135 MS Replace missing fire extinguisher
331095 04/03/2012 293405 1 130B OS Keep area within 18" of fire sprinkler head clear and unobstructed
331110 04/03/2012 293436 1 191 OS Remove storage from mechanical room
201432 04/03/2012 9791 1 199 CS Provide automatic fire sprinkler coverage
201433 04/03/2012 9792 1 199A CS Provide automatic fire sprinkler coverage
201434 04/03/2012 62460 1 199B CS Provide automatic fire sprinkler coverage
201435 04/03/2012 62467 1 199C CS Provide automatic fire sprinkler coverage
319298 03/10/2011 267178 00 0000 M Keep gate at lift station east of bldg. 2 closed and locked
319315 03/10/2011 267213 1 002 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to 1-191
319282 03/10/2011 267145 1 005 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to 1-142
319251 03/10/2011 267078 1 008 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to 1-107L
319059 03/10/2011 266672 1 010 M Determine cause of water damaged ceiling tiles and replace tiles @ second floor landing
319066 03/10/2011 266686 1 014 M Replace missing escutcheon on fire sprinkler head adjacent to 1-217
319317 03/10/2011 267217 1 101D M Provide cover and secure exposed data cables in wall
319247 03/10/2011 267070 1 102A M Provide sign indicating FACP inside (Fire alarm control panel)
319250 03/10/2011 267076 1 106 M Repair secure loose base along wall adjacent to stage
319254 03/10/2011 267084 1 107G M Repair broken/deteriorated base along wall
319243 03/10/2011 267061 1 108B M Secure light fixture cover
319314 03/10/2011 267211 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
319310 03/10/2011 267203 1 116 M Secure light fixture cover
319297 03/10/2011 267175 1 130 M Provide cover for exposed electrical outlet in ceiling adjacent to projector
319294 03/10/2011 267170 1 138 M Provide cover for exposed electrical outlet in ceiling adjacent to protector
319292 03/10/2011 267166 1 138A M Repair ventilation fan
319290 03/10/2011 267162 1 140B M Secure sink to wall
319283 03/10/2011 267147 1 142A M Repair ventilation fan
319245 03/10/2011 267065 1 195 M Replace missing ceiling tiles
319244 03/10/2011 267063 1 197A M Repair door between 1-197 and 1-197A to close properly
319277 03/10/2011 267132 1 208A M Secure sink to wall
319276 03/10/2011 267129 1 210 M Remove excessive flammable wall coverings, limit coverage area to 50% of each wall in building with fire sprinklers
319242 03/10/2011 267059 1 211B M Determine cause of water damaged ceiling tiles and replace tiles
319065 03/10/2011 266684 1 216B M Secure sink to wall
319060 03/10/2011 266674 1 222A M Secure loose escutcheon on fire sprinkler head
319274 03/10/2011 267125 1 280 M Secure cover on light fixture
319300 03/10/2011 267182 2 104 M Mount fire extinguisher at maximum five feet above floor
319269 03/10/2011 267116 P 9133 M Mount fire extinguisher at maximum five feet above floor
319271 03/10/2011 267119 P 9133 M Repair emergency lighting
319272 03/10/2011 267123 P 9133 M Repair south door to close properly
319267 03/10/2011 267111 P 9134 M Mount fire extinguisher at maximum five feet above floor
319268 03/10/2011 267113 P 9134 M Repair south door to close properly
319266 03/10/2011 267109 P 9135 M Repair deteriorated wall and ceiling finish in portable and bathroom
319264 03/10/2011 267105 P 9135 M Mount fire extinguisher at maximum five feet above floor
309224 03/10/2011 245035 P 9135 M Determine cause of water damaged ceiling tiles and replace tiles
319265 03/10/2011 267107 P 9136 M Secure cover on exposed electrical junction box on south exterior wall
319263 03/10/2011 267103 P 9344 M Secure hanging exhaust fan in bathroom
319262 03/10/2011 267101 P 9345 M Repair emergency lighting
319255 03/10/2011 267086 P 9479 M Repair emergency lighting
319278 03/10/2011 267135 1 0000 O Remove and prohibit hanging papers in front of (classroom) windows
319313 03/10/2011 267209 1 109 O Relocate furniture to a maintain a minimum one foot blank wall space on lock side of door
319312 03/10/2011 267207 1 111 O Prohibit plugging microwave and refrigerator into surge protector and extension cord - plug directly into permanent electrical outlet
319311 03/10/2011 267205 1 112 O Relocate furniture to maintain a minimum one foot blank wall space on lock side of door
319280 03/10/2011 267140 1 123 O Prohibit plugging microwave and refrigerator into surge protector box on wall - plug directly into permanent electrical outlet
319295 03/10/2011 267172 1 136 O Relocate furniture to maintain a minimum one foot blank wall space on lock side of door
319293 03/10/2011 267168 1 138 O Relocate furniture to maintain a minimum one foot blank wall space on lock side of door
319286 03/10/2011 267154 1 139 O Prohibit white 13A extension cord adjacent to teacher's desk or replace with minimum 15A cord
319288 03/10/2011 267158 1 139 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
319285 03/10/2011 267152 1 139A O Keep area within 18" of fire sprinkler head clear
319289 03/10/2011 267160 1 140 O Relocate furniture to maintain a minimum one foot blank wall space on lock side of door
319291 03/10/2011 267164 1 140A O Keep area within 18" of fire sprinkler head clear
319279 03/10/2011 267137 1 202C O Maintain separate bathroom facilities for males and females, prohibit designating per teacher
319240 03/10/2011 267055 1 214 O Relocate furniture to maintain a minimum one foot blank wall space on lock side of door
319063 03/10/2011 266680 1 215 O Relocate furniture @ north door to maintain a minimum one foot blank wall space on lock side of door
319064 03/10/2011 266682 1 216 O Remove and prohibit air freshener
319061 03/10/2011 266676 1 225 O Prohibit plugging surge protector into surge protector adjacent to teacher's desk
319062 03/10/2011 266678 1 225 O Remove and prohibit air freshener (sticks in oil)
319299 03/10/2011 267180 2 104 O Prohibit plugging extension cord into surge protector
319301 03/10/2011 267184 2 104 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
319261 03/10/2011 267099 P 9342 O Remove and prohibit air freshener
319258 03/10/2011 267093 P 9410 O Provide clear access to electrical panel
319256 03/10/2011 267089 P 9480 O Prohibit hanging papers on electrical panel to provide clear access to electrical panel
285380 03/10/2011 193768 00 0000 C Provide exterior signage indicating property address
230570 03/10/2011 84040 00 9500 C Provide covered walkway to portables
271891 03/10/2011 164860 00 9698 C Provide sign indicating entrance to bus loop and restricting access to bus loop during student pick-up and drop-off times
319305 03/10/2011 267193 1 129 C Provide auto closer on door
319304 03/10/2011 267191 1 131 C Provide auto closer on door
319303 03/10/2011 267189 1 184 C Provide auto closer on door
319308 03/10/2011 267196 1 001 F Repair magnetic hold open device on fire door adjacent to 1-171
319316 03/10/2011 267215 1 007 F Replace missing magnet for hold open device on fire door
319287 03/10/2011 267156 1 139 OS Remove and prohibit use of toaster
319284 03/10/2011 267150 1 142 OS Maintain clear aisle to exterior exit
319281 03/10/2011 267143 1 193 OS Remove storage from mechanical room
319302 03/10/2011 267187 1 194 OS Remove storage from electrical room
319241 03/10/2011 267057 1 291 OS Remove storage from mechanical room
319260 03/10/2011 267097 P 9341 OS Maintain clear aisle to exit
319259 03/10/2011 267095 P 9409 OS Maintain clear aisle to exits
319257 03/10/2011 267091 P 9411 OS Maintain clear aisle to exit
309245 12/15/2010 245077 1 119 M Determine cause of water damaged ceiling tiles and replace tiles
309251 12/15/2010 245089 1 102A O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
309222 12/14/2010 245031 P 9133 M Determine cause of water damaged ceiling tiles and replace tiles
309223 12/14/2010 245033 P 9134 M Determine cause of water damaged ceiling tiles and replace tiles
309227 12/14/2010 245041 P 9342 M Repair router for computer, making loud humming noise
309231 12/14/2010 245049 P 9344 M Determine cause of water damaged ceiling tiles and replace tiles
309238 12/14/2010 245063 P 9479 M Repair rear door to open/close properly
309298 12/14/2010 245188 1 292 OS Remove storage from electrical room, printers and toner
271923 12/14/2010 164936 00 9699 CS Modify gate in fenced area adjacent to chillers to allow egress at all times by providing panic hardware on gate and remove padlock
265750 12/14/2010 151264 P 6132 N/A No violations observed
265751 12/14/2010 151266 P 6133 N/A No violations observed
265752 12/14/2010 151268 P 6134 N/A No violations observed
265753 12/14/2010 151270 P 6135 N/A No violations observed
265754 12/14/2010 151272 P 6136 N/A No violations observed
271846 12/14/2010 164767 P 6303 N/A No violations observed
271847 12/14/2010 164769 P 6304 N/A No violations observed
271850 12/14/2010 164774 P 6305 N/A No violations observed
271892 12/14/2010 164863 P 6306 N/A No violations observed
309270 04/30/2010 245129 00 0000 M Install cap on fire department connection, north of portable 1
309242 04/30/2010 245071 1 001 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to 1-180
309278 04/30/2010 245148 1 003 M Repair exterior door in corridor to open/close properly, door closest to stairwell
309279 04/30/2010 245150 1 003 M Repair corridor doors to open/close properly, both sets of doors to corridor 1-001
309253 04/30/2010 245094 1 007 M Repair damaged panic hardware and magnetic hold open device on corridor door to corridor 1-002
309288 04/30/2010 245168 1 009 M Replace missing ceiling tile adjacent to 1-130
309308 04/30/2010 245208 1 101S M Replace missing escutcheon on fire sprinkler head
309248 04/30/2010 245083 1 102 M Determine cause of water damaged ceiling tiles and replace tiles
309259 04/30/2010 245106 1 102 M Replace missing escutcheon on fire sprinkler head by NW door
309261 04/30/2010 245110 1 102 M Replace missing ceiling tile by door to 1-103
309254 04/30/2010 245096 1 104G M Determine cause of water damaged ceiling tiles and replace tiles
309275 04/30/2010 245142 1 109 M Replace missing escutcheon on fire sprinkler head
309272 04/30/2010 245133 1 111 M Determine cause of water damaged ceiling tiles and replace tiles
309273 04/30/2010 245138 1 111A M Determine cause of water damaged ceiling tiles and replace tiles
309274 04/30/2010 245140 1 111A M Anchor toilet to floor
309252 04/30/2010 245091 1 113 M Secure loose faucet
309246 04/30/2010 245079 1 118 M Replace missing escutcheon on fire sprinkler head
309247 04/30/2010 245081 1 118 M Determine cause of water damaged ceiling tiles and replace tiles
309281 04/30/2010 245154 1 120 M Determine cause of water damaged ceiling tiles and replace tiles
309280 04/30/2010 245152 1 120B M Repair plumbing leak, water on floor
309283 04/30/2010 245158 1 129 M Replace missing ceiling tiles
309287 04/30/2010 245166 1 130 M Determine cause of water damaged ceiling tiles and replace tiles
309286 04/30/2010 245164 1 130A M Determine cause of water damaged ceiling tiles and replace tiles
309284 04/30/2010 245160 1 131 M Determine cause of water damaged ceiling tiles and replace tiles
309289 04/30/2010 245170 1 137 M Replace missing escutcheon on fire sprinkler head
309290 04/30/2010 245172 1 137 M Adjust hanging ceiling tile
309243 04/30/2010 245073 1 181 M Determine cause of water damaged ceiling tiles and replace tiles
309282 04/30/2010 245156 1 183 M Repair door to latch properly
309285 04/30/2010 245162 1 184 M Determine cause of water damaged ceiling tiles and replace tiles
309258 04/30/2010 245104 1 185B M Determine cause of water damaged ceiling tiles and replace tiles
309257 04/30/2010 245102 1 196 M Provide latch for fire door
309256 04/30/2010 245100 1 197 M Repair emergency lighting
309276 04/30/2010 245144 1 199 M Provide cover on exposed electrical junction box above Fire Extinguisher
309277 04/30/2010 245146 1 199 M Repair door to latch properly
309303 04/30/2010 245198 1 201 M Determine cause of water damaged ceiling tiles and replace tiles
309304 04/30/2010 245200 1 204A M Determine cause of water damaged ceiling tiles and replace tiles
309293 04/30/2010 245178 1 210 M Determine cause of water damaged ceiling tiles and replace tiles
309301 04/30/2010 245194 1 213 M Replace missing escutcheon on fire sprinkler head
309302 04/30/2010 245196 1 213B M Replace missing escutcheon on fire sprinkler head
309296 04/30/2010 245184 1 224 M Determine cause of water damaged ceiling tiles and replace tiles
309292 04/30/2010 245176 1 225 M Determine cause of water damaged ceiling tiles and replace tiles
309307 04/30/2010 245206 1 280 M Replace missing ceiling tile
309306 04/30/2010 245204 1 290 M Mount fire extinguisher at maximum five feet above floor
309269 04/30/2010 245127 2 0000 M Repair drinking fountain adjacent to 2-102
309267 04/30/2010 245123 2 102 M Secure sink to wall
309268 04/30/2010 245125 2 104 M Repair flourescent light fixture
309220 04/30/2010 245027 P 6303 M Repair emergency lighting
309221 04/30/2010 245029 P 6303 M Secure loose faucet
309226 04/30/2010 245039 P 9341 M Secure base at front door
309228 04/30/2010 245043 P 9343 M Repair rear door to open/close properly
309230 04/30/2010 245047 P 9344 M Repair emergency lighting at rear door
309233 04/30/2010 245053 P 9345 M Repair emergency lighting at front door
309236 04/30/2010 245059 P 9411 M Repair emergency lighting (X2)
309237 04/30/2010 245061 P 9411 M Provide cover on exposed electrical junction box
309239 04/30/2010 245065 P 9481 M Repair emergency lighting
309240 04/30/2010 245067 P 9481 M Repair rear door to open/close properly, door seems to be hitting landing
309241 04/30/2010 245069 P 9481 M Secure sink to wall in bathroom
309266 04/30/2010 245120 1 126A O Prohibit plugging refrigerator & microwave into surge protector - plug directly into permanent electrical outlet
309305 04/30/2010 245202 1 204B O Keep area within 18" of fire sprinkler head clear, remove top shelf
309300 04/30/2010 245192 1 213 O Prohibit plugging surge protector into extension cord
309295 04/30/2010 245182 1 222 O Prohibit plugging surge protector into extension cord
309291 04/30/2010 245174 1 223 O Prohibit plugging extension cord into surge protector
285384 04/30/2010 193775 P 9411 O Remove and prohibit flammable fabric covering window behind teacher's desk
309271 04/30/2010 245131 1 101J MS Provide current inspection tag for fire extinguisher
309249 04/30/2010 245085 1 102 MS Provide current inspection tag for fire extinguisher
309250 04/30/2010 245087 1 102A MS Provide current inspection tag for fire extinguisher
309262 04/30/2010 245112 1 107 MS Provide current inspection tag for fire extinguisher
309264 04/30/2010 245116 1 107J MS Provide current inspection tag for fire extinguisher
309263 04/30/2010 245114 1 107K MS Provide current inspection tag for fire extinguisher
309265 04/30/2010 245118 1 126 MS Provide current inspection tag for fire extinguisher
309260 04/30/2010 245108 1 195 MS Provide current inspection tag for fire extinguisher
309255 04/30/2010 245098 1 197A MS Provide current inspection tag for fire extinguisher
309297 04/30/2010 245186 1 292 MS Provide current inspection tag for fire extinguisher
309225 04/30/2010 245037 P 9136 MS Mount fire extinguisher to wall adjacent to exit door
309235 04/30/2010 245057 P 9410 MS Provide current inspection tag for fire extinguisher
309244 04/30/2010 245075 1 181 OS Prohibit charging floor cleaner batteries in room
309299 04/30/2010 245190 1 291 OS Remove storage from electrical room
309229 04/30/2010 245045 P 9343 OS Maintain clear aisle to exit, remove desk at rear door
309232 04/30/2010 245051 P 9345 OS Maintain clear aisle to rear door
309234 04/30/2010 245055 P 9408 OS Maintain clear aisle to rear door
271839 04/30/2010 164748 P 9412 OS Relocate both white storage cabinets to maintain clear access to back door
285362 02/10/2010 193731 00 9599 M Install cap on fire department standpipe connection adjacent to P-423 (x2)
201417 02/10/2010 62463 1 0000 M Relocate all metal storage shelving in storage closets to opposite side of room away from fire sprinkler heads or remove top shelf (1-128A,1-134B)
285273 02/10/2010 193527 1 101A M Mount fire extinguisher at maximum five feet above floor
285374 02/10/2010 193756 1 207 M Replace missing escutcheon on fire sprinkler head
296511 02/10/2010 217442 1 290 M Repair inoperable air conditioning DX unit (per Frank Debogorski's e-mail dated 2/3/09)
251764 02/10/2010 123875 1 290 M Improve ventilation in electric room. Room very hot
285984 02/10/2010 195107 P 0000 M Provide impervious wall finish for minimum six foot height in all portable bathrooms
285364 02/10/2010 193735 P 9344 M Repair emergency lighting above entry door
285360 02/10/2010 193724 1 118 O Eliminate (6) plug outlet adaptor adjacent to corridor door
285379 02/10/2010 193766 1 222 O Eliminate multiple outlet adaptor on back wall adjacent to bookshelf
285376 02/10/2010 193760 2 104 O Prohibit plugging surge protector into extension cord under computer stations
285365 02/10/2010 193737 P 9479 O Eliminate extension cord with a multiple outlet end or replace with a surge protector at NW corner
285370 02/10/2010 193748 P 9481 O Prohibit plugging extension cord into surge protector adjacent to teacher's desk
285275 02/10/2010 193531 1 102 MS Adjust fire doors adjacent to 1-180 to latch properly
285369 02/10/2010 193745 P 9135 OS Relocate storage bins to maintain a minimum 3 ft clear path to back door
285371 02/10/2010 193750 P 9481 OS Relocate storage cabinet to maintain clear path to back door
271816 01/29/2009 164703 1 115 M Replace missing door for toilet stall (x2)
285381 01/29/2009 193770 1 117 M Install maximum occupancy signage of 72 occupants
285268 01/29/2009 193517 1 139 M Replace missing ceiling tiles
285386 01/29/2009 193781 1 180 M Provide rigid conduit for electrical wires out of junction box above exhaust fan
285267 01/29/2009 193515 1 181 M Replace missing ceiling tiles
285269 01/29/2009 193519 1 185 M Replace missing ceiling tiles
285982 01/29/2009 195099 P 0000 M Raise exterior electrical boxes so bottom of boxes is at least 8 inches above grade for all portables (not required per Terry Summerell)
251823 01/29/2009 124000 P 9133 M Seal seam in vinyl flooring in bathroom
285368 01/29/2009 193743 P 9135 M Adjust back door to latch properly
285366 01/29/2009 193739 P 9136 M Replace missing ceiling tiles
251855 01/29/2009 124065 P 9136 M Seal seam in vinyl flooring in bathroom
251853 01/29/2009 124062 P 9341 M Seal seam in vinyl flooring in bathroom
251860 01/29/2009 124076 P 9342 M Seal seam in vinyl flooring in bathroom
251861 01/29/2009 124078 P 9343 M Seal seam in vinyl flooring in bathroom
251862 01/29/2009 124080 P 9408 M Seal seam in vinyl flooring in bathroom
251867 01/29/2009 124090 P 9412 M Seal seam in vinyl flooring in bathroom
285274 01/29/2009 193529 1 101J O Prohibit plugging toaster oven into extension cord - plug directly into permanent electrical outlet
285277 01/29/2009 193535 1 106D O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
285264 01/29/2009 193509 1 120 O Remove and prohibit combustible beanbag chair
285378 01/29/2009 193764 1 205 O Remove and prohibit combustible residential couch which has a tear
271878 01/29/2009 164833 1 208 O Prohibit plugging extension cord into surge protector under teacher's desk
285372 01/29/2009 193752 1 212 O Remove and prohibit combustible residential couch
285373 01/29/2009 193754 1 212 O Remove and prohibit glass top residential table
285265 01/29/2009 193511 P 6132 O Remove and prohibit combustible beanbag chairs (x2)
285266 01/29/2009 193513 P 9412 O Relocate bookshelf to provide clear access to electrical panel
285272 01/29/2009 193525 1 103A MS Provide current inspection tag for fire extinguisher
285271 01/29/2009 193523 1 104G MS Provide current inspection tag for fire extinguisher
285276 01/29/2009 193533 1 106D MS Replace missing fire extinguisher
285259 01/29/2009 193499 1 107E MS Provide current inspection tag for fire extinguisher
285262 01/29/2009 193505 1 132 MS Provide current inspection tag for fire extinguisher
285261 01/29/2009 193503 1 136 MS Provide current inspection tag for fire extinguisher
285260 01/29/2009 193501 1 140 MS Provide current inspection tag for fire extinguisher
285270 01/29/2009 193521 1 195 MS Provide current inspection tag for fire extinguisher
285258 01/29/2009 193497 1 292 MS Provide current inspection tag for fire extinguisher
285263 01/29/2009 193507 P 6133 MS Provide current inspection tag for fire extinguisher
285377 01/29/2009 193762 1 133 OS Rearrange furniture to maintain a minimum 3 ft clear path throughout classroom
285375 01/29/2009 193758 1 227 OS Remove and prohibit use of toaster oven
271870 01/29/2009 164816 P 9134 OS Relocate storage blocking clear access to back door
285367 01/29/2009 193741 P 9136 OS Relocate bookshelf to maintain a minimum 3 ft clear aisle to back door
285363 01/29/2009 193733 P 9343 OS Remove storage to maintain clear path to back door
271872 01/29/2009 164820 P 9345 OS Relocate storage blocking clear access to back door
285382 01/29/2009 193772 P 9411 FS Secure hanging heat detector
265717 09/03/2008 151191 P 9135 M Modify downspout to prevent rain water from undermining sidewalk and fill undermined sidewalk
265719 09/03/2008 151197 P 9341 M Replace broken vinyl floor tile at mate line
265724 09/03/2008 151211 P 9344 M Seal open seam in bathroom flooring
265730 09/03/2008 151222 P 9345 M Seal open seam in bathroom flooring
251863 09/03/2008 124082 P 9409 M Seal open seam in vinyl flooring in bathroom
265736 09/03/2008 151236 P 9410 M Seal open seam in bathroom flooring
251869 09/03/2008 124094 P 9413 M Seal open seam in vinyl flooring in bathroom
251871 09/03/2008 124098 P 9479 M Seal open seam in vinyl flooring in bathroom
251873 09/03/2008 124102 P 9480 M Seal open seam in vinyl flooring in bathroom
251879 09/03/2008 124115 P 9481 M Seal open seam in vinyl flooring in bathroom
271881 09/03/2008 164839 1 202 O Remove and prohibit use of electrical skillet in classroom - located above wall cabinet above sink
271873 09/03/2008 164823 1 210 O Provide certification that carpet meets flame spread requirement or remove carpet
271890 09/03/2008 164857 P 9411 O Relocate book stand to provide clear access to electrical panel
271760 01/22/2008 164588 1 103 M Replace missing escutcheon on fire sprinkler head (x4)
271759 01/22/2008 164586 1 104 M Replace missing escutcheon on fire sprinkler head adjacent to hand washing sink
271786 01/22/2008 164644 1 105 M Replace safety pin on fire extinguisher
271812 01/22/2008 164697 1 106D M Secure loose bracket for fire extinguisher
271877 01/22/2008 164831 1 107 M Replace missing escutcheon on fire sprinkler head (x3)
271864 01/22/2008 164803 1 107E M Mount fire extinguisher at maximum five feet above floor
271866 01/22/2008 164808 1 107G M Provide safety cables for spot lights in studio
271865 01/22/2008 164805 1 126 M Determine cause of water damaged ceiling tiles and replace tiles
271789 01/22/2008 164649 1 185 M Determine cause of water damaged ceiling tiles and replace tiles
271863 01/22/2008 164801 1 190 M Mount fire extinguisher at maximum five feet above floor
271790 01/22/2008 164653 1 195 M Replace missing ceiling tiles
271788 01/22/2008 164647 1 197A M Mount fire extinguisher at maximum five feet above floor
271874 01/22/2008 164825 1 210C M Replace missing escutcheon on fire sprinkler head
271875 01/22/2008 164827 1 216B M Replace missing escutcheon on fire sprinkler head
271853 01/22/2008 164780 P 6132 M Mount fire extinguisher at maximum five feet above floor
271855 01/22/2008 164784 P 6136 M Adjust water flow to drinking fountain
271868 01/22/2008 164812 P 9133 M Repair back door to close properly
271869 01/22/2008 164814 P 9134 M Provide cover for exposed electrical outlet under AC unit
265720 01/22/2008 151199 P 9342 M Secure sink to wall in bathroom
265727 01/22/2008 151215 P 9344 M Seal damaged wall at sink to make wall impervious
265732 01/22/2008 151226 P 9345 M Secure sink to wall in bathroom
265735 01/22/2008 151233 P 9409 M Replace broken vinyl floor tile at mate line
265738 01/22/2008 151238 P 9410 M Seal damaged wall at sink to make wall impervious
271860 01/22/2008 164795 1 101T O Eliminate (6) plug outlet adaptor at electrical outlet
271867 01/22/2008 164810 1 107A O Prohibit plugging microwave into extension cord. Plug microwave directly into wall outlet
271819 01/22/2008 164713 1 110 O Remove and prohibit combustible beanbag chairs (x3)
271818 01/22/2008 164710 1 110B O Relocate storage to keep area within 18" of automatic fire sprinkler heads clear and unobstructed
271859 01/22/2008 164793 1 117 O Prohibit piggy backed surge protectors under keyboard instruments. Plug each surge protector directly into wall outlet - Request additional outlets from M&PO if needed
271820 01/22/2008 164716 1 118 O Remove and prohibit combustible beanbag chairs
271824 01/22/2008 164719 1 118 O Prohibit use of white extension cord with multi-outlet end adjacent to teacher's desk
271861 01/22/2008 164797 1 123 O Eliminate multiple outlet adaptor at electrical outlet
271879 01/22/2008 164835 1 204 O Prohibit plugging extension cord into surge protector
271880 01/22/2008 164837 1 206A O Prohibit plugging microwave into extension cord. Plug microwave directly into wall outlet
271882 01/22/2008 164841 1 213 O Remove and prohibit paper covering windows
271883 01/22/2008 164843 1 213A O Remove and prohibit use of toaster oven in classroom or closet
271862 01/22/2008 164799 1 216 O Eliminate multiple outlet adaptor at electrical outlet
271876 01/22/2008 164829 1 223B O Remove and prohibit combustible beanbag chairs (x3)
271826 01/22/2008 164727 2 104 O Prohibit use of extension cord with multi-outlet end at TV cart
271854 01/22/2008 164782 P 6132 O Relocate bookcase to provide clear access to electrical panel
271885 01/22/2008 164847 P 9341 O Remove and prohibit combustible beanbag chair
271889 01/22/2008 164855 P 9343 O Relocate book stand to provide clear access to electrical panel
271841 01/22/2008 164756 P 9413 O Prohibit use of white extension cord with multi-outlet end
271844 01/22/2008 164760 P 9413 O Remove and prohibit flammable curtains covering window in door
271852 01/22/2008 164778 P 9479 O Prohibit plugging microwave into an extension cord, plug microwave directly into wall outlet
271833 01/22/2008 164737 P 9479 O Prohibit use of yellow extension cord with multi-outlet end behind microwave
271845 01/22/2008 164765 P 9480 O Remove and prohibit flammable curtains on window adjacent to back door
266292 01/22/2008 152468 P 9481 O Provide clear access to electrical panel
271791 01/22/2008 164655 1 106B MS Recharge fire extinguisher
271829 01/22/2008 164730 1 0000 OS Prohibit storage of TV carts in 2nd floor corridors
265634 01/22/2008 151016 1 117 OS Maintain clear aisle to east exit door
265664 01/22/2008 151079 1 216 OS Prohibit running electrical cord across floor
271884 01/22/2008 164845 1 224 OS Prohibit running electrical cord under carpet
271858 01/22/2008 164788 P 6134 OS Relocate table to maintain clear aisle to back door
271851 01/22/2008 164776 P 6306 OS Relocate desks and chairs to maintain clear aisle to both doors
271886 01/22/2008 164849 P 9341 OS Replace chairs blocking clear access to back door
271887 01/22/2008 164851 P 9342 OS Relocate table to maintain a minimum 3 ft clear aisle to back door
271888 01/22/2008 164853 P 9343 OS Relocate storage cabinet to maintain a clear aisle to back door
271871 01/22/2008 164818 P 9344 OS Relocate storage blocking clear access to back door
265626 09/18/2007 151000 1 101S M Repair or replace rippled carpeting. Tripping hazard
251760 09/18/2007 123867 1 104 M Provide current inspection tag for Kitchen steamer
265632 09/18/2007 151012 1 184 M Replace missing ceiling tiles
265653 09/18/2007 151057 P 6136 M Secure sink to wall
265722 09/18/2007 151204 P 9342 M Make exterior walkway level with interior floor
201427 09/18/2007 9827 1 126B C Provide additional air flow to keep temperature lower in room when kiln is in use
251791 09/18/2007 123944 1 181 OS Prohibit charging batteries in room
251836 09/18/2007 124026 1 107G CS Provide suitable wiring for lighting on light bar. Lights should be plugged into the bus bar on the ceiling and not run off of extension cords
265640 04/11/2007 151028 1 002 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to 1-191
265629 04/11/2007 151006 1 009 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to stairs 1-010
265622 04/11/2007 150992 1 102 M Repair hole in wall adjacent to 1-106A
265624 04/11/2007 150996 1 104G M Replace missing escutcheon on fire sprinkler head
265639 04/11/2007 151026 1 106 M Secure loose base along wall, adjacent to 1-117
201423 04/11/2007 62477 1 108A M Adjust level of sprinkler head to a minimum of 1" below ceiling
265630 04/11/2007 151008 1 110 M Replace missing escutcheon on fire sprinkler head
265635 04/11/2007 151018 1 114A M Determine cause of water damaged ceiling tiles and replace tiles
230502 04/11/2007 83897 1 132 M Modify exhaust fan for stove to vent directly to the exterior rather than into room
230497 04/11/2007 83885 1 136 M Modify exhaust fan for stove to vent directly to the exterior rather than into room
230495 04/11/2007 83881 1 140 M Modify exhaust fan for stove to vent directly to the exterior rather than into room
251831 04/11/2007 124020 1 182 M Replace missing escutcheon on fire sprinkler head
265636 04/11/2007 151020 1 185 M Install fire extinguisher sitting on floor at maximum five feet above floor adjacent ot door
265637 04/11/2007 151022 1 185 M Replace missing ceiling tiles
251832 04/11/2007 124021 1 195 M Replace missing escutcheon on fire sprinkler head
265627 04/11/2007 151002 1 199A M Repair door latch to enable door to be opened
265660 04/11/2007 151071 1 210 M Replace missing escutcheons on 2 fire sprinkler heads
265659 04/11/2007 151069 1 211A M Replace missing escutcheon on fire sprinkler head
265663 04/11/2007 151077 1 211A M Determine cause of water damaged ceiling tiles and replace tiles
265658 04/11/2007 151067 1 212B M Replace missing escutcheon on fire sprinkler head
265656 04/11/2007 151063 1 214 M Determine cause of water damaged ceiling tiles and replace tiles
265657 04/11/2007 151065 1 214 M Replace missing escutcheon on fire sprinkler head
266288 04/11/2007 152458 1 216 M Replace missing escutcheon on fire sprinkler head
265662 04/11/2007 151075 1 223A M Secure sink to wall
265654 04/11/2007 151059 1 227A M Secure loose escutcheon on fire sprinkler head
265655 04/11/2007 151061 1 281 M Replace damaged threshold
265641 04/11/2007 151032 1 293 M Improve ventilation in room. Room very hot
265661 04/11/2007 151073 2 190 M Remove sign indicating "Fire Extinguisher Inside"
265642 04/11/2007 151034 P 6132 M Secure sink to wall in bathroom
265643 04/11/2007 151036 P 6132 M Paint building number on exterior wall to be visible to fire rescue personnel
265644 04/11/2007 151038 P 6133 M Secure sink to wall
265645 04/11/2007 151040 P 6133 M Paint building number on exterior wall to be visible to fire rescue personnel
265646 04/11/2007 151042 P 6133 M Adjust rear door to latch properly
265647 04/11/2007 151044 P 6134 M Paint building number on exterior wall to be visible to fire rescue personnel
265648 04/11/2007 151046 P 6134 M Repair deteriorated wall finish adjacent to sink in bathroom
265649 04/11/2007 151049 P 6135 M Paint building number on exterior wall to be visible to fire rescue personnel
265650 04/11/2007 151051 P 6135 M Repair deteriorated wall finish adjacent to sink in bathroom
265651 04/11/2007 151053 P 6136 M Paint building number on exterior wall to be visible to fire rescue personnel
265652 04/11/2007 151055 P 6136 M Install fire extinguisher sitting on floor at maximum five feet above floor adjacent to door
265718 04/11/2007 151195 P 9136 M Repair emergency lighting
265723 04/11/2007 151208 P 9342 M Replace missing threshold for bathroom door
265734 04/11/2007 151230 P 9408 M Replace missing threshold for bathroom door
265740 04/11/2007 151241 P 9413 M Seal damaged wall at sink to make wall impervious
265743 04/11/2007 151249 P 9479 M Seal cove base to wall in bathroom to make wall impervious
265747 04/11/2007 151257 P 9481 M Seal damaged wall at sink to make wall impervious
265713 04/11/2007 151186 P 9133 O Provide clear access to electrical panel
265714 04/11/2007 151188 P 9135 O Provide clear access to electrical panel
266290 04/11/2007 152464 P 9409 O Provide clear access to electrical panel
265741 04/11/2007 151245 P 9479 O Eliminate extension cord or replace with minimum 15A cord
266291 04/11/2007 152466 P 9480 O Provide clear access to electrical panel
201414 04/11/2007 9795 00 0000 MS Provide current inspection tag for fire sprinkler system (last inspection 1/20/02)
265638 04/11/2007 151024 1 002 MS Adjust fire door in corridor adjacent to 1-171 to latch properly
265628 04/11/2007 151004 1 009 MS Adjust fire door in corridor adjacent to stair 1-010 to latch properly
265625 04/11/2007 150998 1 103A MS Provide current inspection tag for fire extinguisher
266287 04/11/2007 152455 1 104 MS Provide current inspection for Kitchen hood fire suppression system
265631 04/11/2007 151010 1 195 MS Provide current inspection tag for fire extinguisher
251840 04/11/2007 124034 1 183 OS Prohibit charging batteries in room
251769 04/11/2007 123887 1 208 OS Remove toaster oven from room
266289 04/11/2007 152461 1 215 OS Remove and prohibit use of toaster oven
265746 04/11/2007 151255 P 6132 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station
265745 04/11/2007 151253 P 9480 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station
265633 04/11/2007 151014 1 102A FS Provide Fire Alarm log book at Fire Alarm panel
265728 04/11/2007 151219 P 9345 FS Secure heat detector to ceiling
251882 12/15/2006 124121 00 0000 M Rotate fire department connection adjacent to P-21 180 degrees
230556 12/15/2006 84010 00 0000 M Turn F.D. standpipe connection 180 degrees at rear of P-413, it now faces towards portable and is not accessible
201415 12/15/2006 9794 00 0000 M Provide verification that all student occupied spaces have emergency lights and all are operable
251771 12/15/2006 123891 1 103A M Replace missing escutcheon on fire sprinkler head
230540 12/15/2006 83975 1 104E M Repair leak causing ice to form at ceiling inside freezer
201424 12/15/2006 62478 1 108B M Adjust level of sprinkler head to a minimum of 1" below ceiling
251799 12/15/2006 123960 1 226B M Repair exhaust fan in bathroom
251876 12/15/2006 124109 P 9480 M Secure sink to wall
265623 12/15/2006 150994 00 0000 MS Immediately install chain and padlock on Fire Main adjacent to bike enclosure at West parking lot. Fire Main has no tamper switches on it.
251761 12/15/2006 123869 1 104 MS Provide current inspection tag for Kitchen hood fire suppression system
230490 12/15/2006 83871 1 193A OS Remove storage from communications room
251884 12/15/2006 124127 1 205 OS Remove toaster oven from room
230565 12/15/2006 84030 P 9133 OS Maintain clear aisle to exit
201419 02/24/2006 9820 1 007 M Replace glazing in smoke doors in corridor with fire rated glazing
251830 02/24/2006 124019 1 010 M Replace missing escutcheon on fire sprinkler head
251777 02/24/2006 123905 1 104C M Anchor toilet to floor
251770 02/24/2006 123889 1 106B M Secure loose fire extinguisher bracket
251762 02/24/2006 123871 1 108B M Secure loose handicapped grabrail
251763 02/24/2006 123873 1 113 M Secure loose handicapped grabrail
251775 02/24/2006 123902 1 114A M Secure sink to wall
251772 02/24/2006 123896 1 116B M Anchor toilet to floor
251798 02/24/2006 123956 1 120 M Adjust door to latch properly. Door drags on top of frame.
251787 02/24/2006 123933 1 120B M Repair exhaust fan in bathroom
251796 02/24/2006 123952 1 128B M Replace missing screw for light switch plate
251790 02/24/2006 123939 1 130A M Repair thumb latch to enable door to be unlocked from outside
251794 02/24/2006 123950 1 134 M Replace missing ceiling tiles
251806 02/24/2006 123977 1 134A M Secure sink to wall
251807 02/24/2006 123978 1 139B M Secure sink to wall
251800 02/24/2006 123963 1 185 M Determine cause of water damaged ceiling tiles and replace tiles
232913 02/24/2006 88609 1 194 M Repair ventilation fan - room too hot
251839 02/24/2006 124032 1 197 M Remove 2 inch rigid conduit in bar joist that is duct taped to bar joist brace
230530 02/24/2006 83955 1 198 M Provide current inspection tag for hot water heater
251808 02/24/2006 123979 1 203B M Secure sink to wall
251766 02/24/2006 123880 1 209A M Repair exhaust fan in bathroom
251767 02/24/2006 123882 1 209B M Repair exhaust fan in bathroom
251768 02/24/2006 123884 1 213B M Repair exhaust fan in bathroom
251833 02/24/2006 124022 1 214B M Replace missing escutcheon on fire sprinkler head
251786 02/24/2006 123931 1 220A M Repair exhaust fan in bathroom
251793 02/24/2006 123946 1 221B M Secure loose handicapped grabrail
251809 02/24/2006 123980 1 224A M Secure sink to wall
251834 02/24/2006 124023 1 225 M Replace missing escutcheon on fire sprinkler head
251765 02/24/2006 123878 1 292 M Repair door lock to enable door to be locked
230566 02/24/2006 84032 1 293 M Install missing grill on air conditioning duct
251810 02/24/2006 123981 P 9133 M Secure sink to wall
251803 02/24/2006 123970 P 9133 M Adjust South door to latch properly
251826 02/24/2006 124007 P 9134 M Adjust South door to latch properly
251883 02/24/2006 124124 P 9135 M Adjust rear door to latch properly
251852 02/24/2006 124060 P 9136 M Repair emergency lighting
251819 02/24/2006 123990 P 9341 M Secure sink to wall
251817 02/24/2006 123988 P 9342 M Secure sink to wall
251816 02/24/2006 123987 P 9343 M Secure sink to wall
251881 02/24/2006 124119 P 9345 M Provide cover on exposed electrical junction box at exterior
251814 02/24/2006 123985 P 9408 M Secure sink to wall
251812 02/24/2006 123983 P 9409 M Secure sink to wall
251864 02/24/2006 124084 P 9410 M Adjust door to latch properly. Door drags on frame
251866 02/24/2006 124088 P 9411 M Repair damaged flooring
251811 02/24/2006 123982 P 9411 M Secure sink to wall
251868 02/24/2006 124092 P 9412 M Replace damaged light switch in bathroom
251818 02/24/2006 123989 P 9413 M Secure sink to wall
251874 02/24/2006 124104 P 9480 M Modify downspout for gutter to prevent drainage from undermining entry slab and backfill undermined entry slab
251872 02/24/2006 124100 P 9480 M Adjust rear door to latch properly
251875 02/24/2006 124106 P 9481 M Modify downspout for gutters to prevent drainage from undermining entry slab and backfill undermined entry slab
251877 02/24/2006 124111 P 9481 M Secure sink to wall
251878 02/24/2006 124113 P 9481 M Adjust rear door to latch properly
201420 02/24/2006 62476 1 012 C Adjust level of sprinkler head to a minimum of 1" below ceiling (adjacent to 1-290)
230538 02/24/2006 83971 1 113 C Provide emergency lighting
251774 02/24/2006 123899 00 0000 MS Provide current inspection tags for all fire extinguishers on campus
251838 02/24/2006 124030 1 007 MS Adjust fire door in corridor adjacent to corridor 1-002 to latch properly
251784 02/24/2006 123926 1 009 MS Adjust fire door in corridor at stair adjacent to 1-142 to latch properly
201421 02/24/2006 9799 1 104 MS Provide current inspection for fire suppression system (08/03)
230533 02/24/2006 83961 1 185 MS Provide current inspection tag for fire sprinkler system
251837 02/24/2006 124028 1 117 OS Maintain clear aisle to North exit
251825 02/24/2006 124004 P 9134 OS Maintain clear aisle to south exit
251858 02/24/2006 124070 P 9341 OS Maintain clear aisle to rear exit
251859 02/24/2006 124074 p 9342 OS Maintain clear aisle to rear exit
251865 02/24/2006 124086 P 9410 OS Maintain clear aisle to rear exit
230549 02/24/2006 83996 P 9410 OS Maintain clear aisle to exit
251870 02/24/2006 124096 P 9479 OS Maintain clear aisle to rear exit
230506 01/21/2005 83905 1 0000 M Adjust east corridor exit door to close properly @ 1-126
230528 01/21/2005 83951 1 002 M Determine cause of water damaged ceiling tiles in corridor and replace tiles
230479 01/21/2005 83843 1 008 M Determine cause of water damaged ceiling tiles in hallway and replace tiles
230568 01/21/2005 84036 1 013 M Determine cause of water damaged ceiling tiles in second floor corridor adjacent to 1-202 and replace tiles
230475 01/21/2005 83833 1 101C M Replace missing escutcheon on fire sprinkler head
230476 01/21/2005 83836 1 101C M Determine cause of water damaged ceiling tiles and replace tiles
230474 01/21/2005 83831 1 101K M Determine cause of water damaged ceiling tiles and replace tiles
230542 01/21/2005 83979 1 104A M Determine cause of water damaged ceiling tiles and replace tiles
230543 01/21/2005 83981 1 104A M Replace plastic dryer vent with metal dryer vent pipe
230544 01/21/2005 83983 1 104G M Determine cause of water damaged ceiling tiles and replace tiles
230541 01/21/2005 83977 1 104G M Mount fire extinguisher at maximum five feet above floor
230539 01/21/2005 83973 1 105A M Repair hole in wall caused by door knob
230477 01/21/2005 83838 1 107 M Provide sign indicating Fire Extinguisher location on west wall
230482 01/21/2005 83849 1 107F M Determine cause of water damaged ceiling tiles and replace tiles
230483 01/21/2005 83852 1 107F M Secure light fixture hanging from ceiling
230481 01/21/2005 83847 1 107H M Determine cause of water damaged ceiling tiles and replace tiles
230529 01/21/2005 83953 1 109B M Anchor shelving to wall
230525 01/21/2005 83944 1 110 M Pad and mark corners of TV shelf which is lower than 6'8"
230526 01/21/2005 83947 1 111 M Pad and mark corners of TV shelf which is lower than 6'8"
230527 01/21/2005 83949 1 111 M Determine cause of water damaged ceiling tiles and replace tiles
230524 01/21/2005 83942 1 112 M Pad and mark corners of TV shelf which is lower than 6'8"
230523 01/21/2005 83941 1 114 M Pad and mark corners of TV shelf which is lower than 6'8"
230521 01/21/2005 83937 1 116 M Pad and mark corners of TV shelf which is lower than 6'8"
230536 01/21/2005 83967 1 117A M Replace missing escutcheon on fire sprinkler head
230520 01/21/2005 83934 1 118 M Pad and mark corners of TV shelf which is lower than 6'8"
230488 01/21/2005 83867 1 119 M Repair or replace flourescent light fixtures (x5)
201425 01/21/2005 62455 1 120 M Pad and mark corners of Television shelf which are lower than 6?8?
230510 01/21/2005 83914 1 122 M Pad and mark corners of TV shelf which are lower than 6'8"
230509 01/21/2005 83909 1 126 M Pad and mark corners of TV shelf which are lower than 6'8"
230504 01/21/2005 83901 1 132 M Pad and mark corners of TV shelf, which are lower than 6'8"
230500 01/21/2005 83893 1 134 M Determine cause of water damaged ceiling tiles and replace tiles
230499 01/21/2005 83890 1 136 M Determine cause of water damaged ceiling tiles by window and replace tiles
201428 01/21/2005 62458 1 136 M Pad and mark corners of unit which are lower than 6?8?
230492 01/21/2005 83875 1 140 M Determine cause of water damaged ceiling tiles and replace tiles
230491 01/21/2005 83873 1 142 M Determine cause of water damaged ceiling tiles and replace tiles
230505 01/21/2005 83903 1 184 M Determine cause of water damaged ceiling tiles and replace tiles
230534 01/21/2005 83963 1 185 M Replace plastic dryer vent pipe with metal vent pipe
230531 01/21/2005 83957 1 185 M Determine cause of water damaged ceiling tiles and replace tiles
230532 01/21/2005 83959 1 185B M Determine cause of water damaged ceiling tiles and replace tiles
230567 01/21/2005 84034 1 208 M Pad and mark corners of TV shelf which is lower than 6'8"
201436 01/21/2005 9831 1 293 M Repair ventilation fan - room too hot
230564 01/21/2005 84028 P 9134 M Repair door to latch properly
230561 01/21/2005 84022 P 9135 M Repair emergency lighting
230562 01/21/2005 84024 P 9135 M Repair rear door to latch properly
230554 01/21/2005 84006 P 9136 M Repair stair door to latch properly
230555 01/21/2005 84008 P 9136 M Install base along wall in portable
230547 01/21/2005 83989 P 9411 M Repair emergency lighting
230551 01/21/2005 84000 P 9479 M Determine cause of water damaged ceiling tiles and replace tiles
230553 01/21/2005 84004 P 9480 M Determine cause of water damaged ceiling tiles and replace tiles
201422 01/21/2005 62464 1 106D O Keep area within 18? of automatic fire sprinkler heads clear and unobstructed
230513 01/21/2005 83919 1 120A O Eliminate extension cord powering refrigerator
230569 01/21/2005 84038 1 205 O Keep area within 18" of automatic fire sprinkler heads clear and unobstructed
230552 01/21/2005 84002 P 9479 O Provide clear access to electrical panel
201416 01/21/2005 9817 00 0000 C Provide door closers on all exterior mechanical room doors
201418 01/21/2005 9820 1 007 C Replace glazing in smoke doors in corridor with fire rated glazing
230560 01/21/2005 84019 P 9133 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
230559 01/21/2005 84017 P 9134 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
230558 01/21/2005 84015 P 9135 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
230557 01/21/2005 84013 P 9136 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
201437 01/21/2005 62436 P 9341 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
201438 01/21/2005 62459 P 9342 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
201439 01/21/2005 62468 P 9343 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
201440 01/21/2005 65055 P 9408 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
201443 01/21/2005 65058 P 9409 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
201442 01/21/2005 65057 P 9410 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
201441 01/21/2005 65056 P 9411 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
201445 01/21/2005 65060 P 9412 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
201444 01/21/2005 65059 P 9413 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
201446 01/21/2005 65061 P 9479 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
201448 01/21/2005 65063 P 9480 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
201447 01/21/2005 65062 P 9481 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
230484 01/21/2005 83854 1 0000 MS Label all fire rated doors, frames, and hardware in corridors, stairwells, etc.
230518 01/21/2005 83930 1 002 MS Repair smoke doors @ room 1-118 to close properly
201431 01/21/2005 62433 1 196 MS Seal penetration in fire wall
230480 01/21/2005 83845 1 008 OS Remove tables in hallway to maintain clear aisle to exit
230478 01/21/2005 83840 1 107M OS Prohibit use of candles
230487 01/21/2005 83863 1 119 OS Relocate shelves blocking door between 1-119 and 1-107
230503 01/21/2005 83899 1 132 OS Maintain clear aisle to rear exit
230501 01/21/2005 83895 1 134 OS Maintain clear aisle to rear exit
230496 01/21/2005 83883 1 138 OS Maintain clear aisle to exit
230493 01/21/2005 83877 1 140 OS Maintain clear aisle to rear exit
230494 01/21/2005 83879 1 140 OS Prohibit storage on stove top surface
230485 01/21/2005 83856 1 181 OS Prohibit recharging batteries in janitor's closet
230572 01/21/2005 84044 1 185 OS Prohibit storage of gas powered leaf blower
230545 01/21/2005 83985 2 103 OS Prohibit storage of flammable paint
230563 01/21/2005 84026 P 9134 OS Maintain clear aisle to exit
230546 01/21/2005 83987 P 9343 OS Maintain clear aisle to rear exit
230548 01/21/2005 83994 P 9411 OS Maintain clear aisle to rear exit
230550 01/21/2005 83998 P 9412 OS Maintain clear aisle to exit
201412 01/21/2005 9793 00 0000 FS Provide certification that fire alarm system has been tested and is fully operational