VERDE ELEMENTARY
 
VERDE ELEMENTARY
6590 VERDE TRAIL
BOCA RATON, 33433
FISH Drill Down
 Campus Info.
 Buildings:18 Rooms:320
 Portables:16
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
391665 03/05/2018 425010 00 0000 M Clean and repair damaged rain gutters -downspouts throughout campus
411778 03/05/2018 468521 10 001 M Repair exterior exit door to close properly
411779 03/05/2018 468523 10 002 M Repair exterior exit door to close properly
411780 03/05/2018 468525 10 004 M Repair entrance door to close properly
411776 03/05/2018 468517 11 003 M Determine cause of water damaged ceiling tiles and replace tiles
411730 03/05/2018 468421 12 003 M Repair exterior exit door to close properly
411729 03/05/2018 468419 12 005 M Determine cause of water damaged ceiling tiles and replace tiles
411717 03/05/2018 468395 2 0000 M Secure loose electrical outlet box at door of exterior refrigerator unit
411714 03/05/2018 468389 2 001 M Determine cause of water damaged ceiling tiles and replace tiles
411715 03/05/2018 468391 2 004 M Determine cause of water damaged ceiling tiles and replace tiles
411718 03/05/2018 468397 2 010 M Replace burned out bulbs in light fixtures inside flammable storage room
405198 03/05/2018 454221 3 0000 M Trim over grown tree branches at Bldg. 3 between art classroom and group bathrooms
411724 03/05/2018 468409 3 007 M Repair emergency lighting in girls restroom
411722 03/05/2018 468405 3 008 M Repair water leaking from air handler AHU-2 (standing water on floor)
411726 03/05/2018 468413 4 010 M Determine cause of water damaged ceiling tiles and replace tiles
411783 03/05/2018 468532 5 002 M Repair entrance door to close properly
411782 03/05/2018 468530 5 005 M Replace missing ceiling tiles
411790 03/05/2018 468546 6 004 M Repair entrance door to close properly
411791 03/05/2018 468548 6 004 M Repair exterior exit door to close properly
411793 03/05/2018 468552 7 006 M Replace missing light fixture lens
411786 03/05/2018 468538 8 003 M Determine cause of water damaged ceiling tiles and replace tiles
411774 03/05/2018 468513 9 0000 M Secure downspout at south side of Building 9 (downspout lying on the ground)
411775 03/05/2018 468515 9 008 M Repair or replace rusty door on mechanical room
411748 03/05/2018 468460 P 289 M Determine cause of water damaged ceiling tiles and replace tiles
411749 03/05/2018 468462 P 289 M Repair stair door to close properly
411764 03/05/2018 468493 P 31 M Determine cause of water damaged ceiling tiles and replace tiles
411765 03/05/2018 468495 P 31 M Repair unstable flooring (weak spongy flooring throughout portable)
411766 03/05/2018 468497 P 31 M Repair emergency lighting
411767 03/05/2018 468499 P 31 M Repair stair door to close properly
411768 03/05/2018 468501 P 339 M Remove vegetation growing through ramp railing
411758 03/05/2018 468481 P 3543 M Repair emergency lighting on ceiling
411759 03/05/2018 468483 P 3543 M Repair stair door to close and latch properly
411733 03/05/2018 468429 P 6146 M Repair caulk joints on exterior wall of portable
411734 03/05/2018 468431 P 6146 M Secure loose drinking fountain to sink
411736 03/05/2018 468435 P 6149 M Repair emergency lighting at both front and rear doors
411737 03/05/2018 468437 P 6399 M Remove and prohibit use of plug in deodorizer
411738 03/05/2018 468439 P 6399 M Determine cause of water damaged ceiling tiles adjacent to Bard unit and replace tiles
411739 03/05/2018 468441 P 6399 M Repair emergency lighting at rear door
411740 03/05/2018 468444 P 6400 M Determine cause of water damaged ceiling tiles and replace tiles
411741 03/05/2018 468446 P 6400 M Repair caulk joint in exterior wall adjacent to front door
411773 03/05/2018 468511 P 6478 M Repair emergency lighting at rear door
411772 03/05/2018 468509 P 6479 M Repair emergency lighting at front door
411771 03/05/2018 468507 P 6480 M Repair emergency lighting at rear door
411769 03/05/2018 468503 P 6481 M Repair ventilation fan in bathroom
411770 03/05/2018 468505 P 6481 M Repair emergency lighting at rear door
411763 03/05/2018 468491 P 9617 M Repair rear door to close properly
411760 03/05/2018 468485 P 9618 M Determine cause of water damaged ceiling tiles in middle of portable and at rear door and replace tiles
411761 03/05/2018 468487 P 9618 M Repair emergency lighting at rear door
411754 03/05/2018 468473 P 9620 M Repair emergency lighting at rear door
411751 03/05/2018 468467 P 9621 M Determine cause of water damaged ceiling tiles and replace tiles
411752 03/05/2018 468469 P 9621 M Repair emergency lighting at rear door
411750 03/05/2018 468465 P 9622 M Repair emergency lighting at both front and rear doors
411746 03/05/2018 468456 P 9936 M Determine cause of water damaged ceiling tiles adjacent to Bard unit band replace tiles
411747 03/05/2018 468458 P 9936 M Repair front entrance door to close properly (door slams shut with too much force)
411744 03/05/2018 468452 P 9937 M Repair emergency lighting at front door
411745 03/05/2018 468454 P 9937 M Determine cause of water damaged ceiling tiles and replace tiles
411742 03/05/2018 468448 P 9938 M Repair emergency lighting at rear door
411743 03/05/2018 468450 P 9938 M Determine cause of water damaged ceiling tiles and replace tiles
411713 03/05/2018 468386 1 009 O Remove and prohibit flammable curtains or spray with a flame retardant
411731 03/05/2018 468423 12 004 O Prohibit orange electrical cord powering refrigerator from running over doorway
411784 03/05/2018 468534 5 004 O Prohibit electrical cord from running through doorway
411735 03/05/2018 468433 P 6148 O Remove and prohibit flammable fabric tent hanging from ceiling
411762 03/05/2018 468489 P 9618 O Remove and prohibit paper covering window in door except during code red situations
411756 03/05/2018 468477 P 9619 O Remove and prohibit paper covering window in door except during code red situations
411757 03/05/2018 468479 P 9619 O Relocate panel blocking clear access to electrical panel
411755 03/05/2018 468475 P 9620 O Relocate cabinet to provide clear access to electrical panel
360105 03/05/2018 356706 00 0000 C Modify or improve storm drainage to prevent rain from running across sidewalks in interior courtyard between buildings 1, 2, 3 and 4
411727 03/05/2018 468415 1 023 MS Provide current inspection tag for fire extinguisher in mechanical room
411716 03/05/2018 468393 2 006 MS Recharge fire extinguisher in kitchen
411719 03/05/2018 468399 2 010 MS Provide current inspection tag for fire extinguisher
411721 03/05/2018 468403 2 020 MS Provide current inspection tag for fire extinguisher in generator room
411789 03/05/2018 468544 6 009 MS Recharge fire extinguisher in corridor
411711 03/05/2018 468382 1 018 OS Remove and prohibit use of space heater
411712 03/05/2018 468384 1 022C OS Remove and prohibit use of space heater (X2)
411728 03/05/2018 468417 1 023 OS Remove storage from mechanical room
411781 03/05/2018 468527 10 005 OS Remove storage from electrical room
411777 03/05/2018 468519 11 005 OS Remove storage from electrical room
411720 03/05/2018 468401 2 016 OS Remove storage from mechanical room
411723 03/05/2018 468407 3 004 OS Remove articles to provide clear access to fire extinguisher located next to 3-004A
411725 03/05/2018 468411 4 012 OS Remove storage from mechanical room
411787 03/05/2018 468540 5 008 OS Remove storage from mechanical room
411788 03/05/2018 468542 6 008 OS Remove storage from mechanical room
411792 03/05/2018 468550 7 008 OS Remove storage from mechanical room
411785 03/05/2018 468536 8 008 OS Remove storage from mechanical room
411753 03/05/2018 468471 P 9620 OS Remove paper covering fire extinguisher so extinguisher is visible inside room
260816 03/05/2018 143011 1 0000 N/A No violations observed
260825 03/05/2018 143020 10 0000 N/A No violations observed
260826 03/05/2018 143021 11 0000 N/A No violations observed
260827 03/05/2018 143022 12 0000 N/A No violations observed
411732 03/05/2018 468426 16 0000 N/A No violations observed
260817 03/05/2018 143012 2 0000 N/A No violations observed
260818 03/05/2018 143013 3 0000 N/A No violations observed
260819 03/05/2018 143014 4 0000 N/A No violations observed
260820 03/05/2018 143015 5 0000 N/A No violations observed
260821 03/05/2018 143016 6 0000 N/A No violations observed
260822 03/05/2018 143017 7 0000 N/A No violations observed
260823 03/05/2018 143018 8 0000 N/A No violations observed
260824 03/05/2018 143019 9 0000 N/A No violations observed
260842 03/05/2018 143037 P 289 N/A No violations observed
260843 03/05/2018 143038 P 31 N/A No violations observed
260845 03/05/2018 143040 P 339 N/A No violations observed
260844 03/05/2018 143039 P 3543 N/A No violations observed
260838 03/05/2018 143033 P 6146 N/A No violations observed
260839 03/05/2018 143034 P 6147 N/A No violations observed
260840 03/05/2018 143035 P 6148 N/A No violations observed
260841 03/05/2018 143036 P 6149 N/A No violations observed
286063 03/05/2018 195275 P 6399 N/A No violations observed
286064 03/05/2018 195277 P 6400 N/A No violations observed
359968 03/05/2018 356394 P 6478 N/A No violations observed
359967 03/05/2018 356392 P 6479 N/A No violations observed
359966 03/05/2018 356390 P 6480 N/A No violations observed
359965 03/05/2018 356388 P 6481 N/A No violations observed
260832 03/05/2018 143027 P 9617 N/A No violations observed
260833 03/05/2018 143028 P 9618 N/A No violations observed
260834 03/05/2018 143029 P 9619 N/A No violations observed
260835 03/05/2018 143030 P 9620 N/A No violations observed
260836 03/05/2018 143031 P 9621 N/A No violations observed
265298 03/05/2018 150280 P 9622 N/A No violations observed
335583 03/05/2018 303123 P 9936 N/A No violations observed
335584 03/05/2018 303124 P 9937 N/A No violations observed
359964 03/05/2018 356385 P 9938 N/A No violations observed
405197 04/10/2017 454219 00 9599 M Repair uneven and damaged concrete walkway between west side of pavilion and covered walkway at south side of campus
405163 04/10/2017 454144 10 011 M Repair or replace mechanical room rusted door
405184 04/10/2017 454193 12 001A M Repair exhaust fan in bathroom
405166 04/10/2017 454156 2 005 M Repair light in exit sign above kitchen back door
405170 04/10/2017 454164 4 006 M Determine cause of water damaged ceiling tiles and replace tiles
405173 04/10/2017 454170 6 003 M Secure faucet to sink
405172 04/10/2017 454168 6 005 M Repair light in exit sign above corridor exterior doors
405152 04/10/2017 454124 P 289 M Repair emergency lighting
405155 04/10/2017 454131 P 289 M Repair or replace deteriorated wood siding
405180 04/10/2017 454185 P 31 M Provide adequate support under ramp posts to prevent bounciness along ramp
405181 04/10/2017 454187 P 31 M Repair faucet to shut properly - faucet drips
405189 04/10/2017 454203 P 6147 M Repair emergency lighting above front door
405191 04/10/2017 454207 P 6400 M Seal gap between sink and wall in bathroom
405177 04/10/2017 454179 P 6481 M Repair emergency lighting above front door
405139 04/10/2017 454094 P 9618 M Secure exhaust fan grille to ceiling in bathroom
405140 04/10/2017 454100 P 9619 M Secure exhaust fan grille to ceiling in bathroom
405145 04/10/2017 454108 P 9620 M Repair emergency lighting above front door
405196 04/10/2017 454217 P 9936 M Repair broken vinyl base along wall adjacent to back door
405128 04/10/2017 454074 00 0000 O Remove and prohibit paper covering window in classroom doors through out facility with the exception of code RED duration
405157 04/10/2017 454134 P 289 O Remove glass mirror from bathroom or provide mirror made of tempered glass, safety glass, or stainless steel
405182 04/10/2017 454189 P 31 O Prohibit plugging surge protector into surge protector under computer stations adjacent to bathroom
405183 04/10/2017 454191 P 31 O Eliminate white extension cord with multiple outlet end for pencil sharpener or replace with a surge protector
405186 04/10/2017 454197 P 6148 O Remove and prohibit excessive flammable red vinyl sheathing on front door
405187 04/10/2017 454199 P 6148 O Remove paper covering electrical panel
405188 04/10/2017 454201 P 6148 O Remove and prohibit excessive flammable netting hanging from ceiling adjacent to AC unit
405176 04/10/2017 454177 P 6479 O Remove and prohibit flammable curtains on window
405146 04/10/2017 454111 P 9620 O Remove and prohibit flammable curtains on window
405147 04/10/2017 454113 P 9620 O Remove paper covering electrical panel
405150 04/10/2017 454119 P 9621 O Remove paper covering electrical panel
405195 04/10/2017 454215 P 9936 O Eliminate white extension cord with multiple outlet end adjacent to teacher desk or replace with a surge protector
405193 04/10/2017 454211 P 9937 O Relocate bookcase to provide clear access to electrical panel
405194 04/10/2017 454213 P 9937 O Remove and prohibit combustible red residential chair
405168 04/10/2017 454160 2 020 MS Provide current inspection tag for fire extinguisher in generator room
405207 04/10/2017 454243 5 001 MS Adjust corridor door to latch properly
405175 04/10/2017 454174 6 001 MS Secure loose hardware on corridor door
405192 04/10/2017 454209 P 6400 MS Repair bathroom door hardware to work properly - lock sticks
405178 04/10/2017 454181 P 6480 MS Secure loose hardware on bathroom door and replace missing unlock hardware on door
405132 04/10/2017 454078 1 012 OS Remove computer equipment of floor to maintain safe egress to east exit
405136 04/10/2017 454089 1 012 OS Remove anchor charts off exterior door to make door easily visible
405127 04/10/2017 454072 1 016 OS Remove and prohibit use of space heater at front desk
405129 04/10/2017 454076 1 022C OS Remove and prohibit use of space heater
405165 04/10/2017 454153 10 001 OS Relocate anchor chart stand to maintain clear path to exterior door
405185 04/10/2017 454195 12 007 OS Remove storage from mechanical room
405167 04/10/2017 454158 2 016 OS Remove storage from mechanical room adjacent to kitchen back door
405169 04/10/2017 454162 4 008 OS Relocate green board to keep area clear at emergency escape window
405174 04/10/2017 454172 6 002 OS Relocate floor fan to maintain clear path to exterior door
405171 04/10/2017 454166 7 002 OS Relocate anchor chart stand to maintain clear path to exterior door
405179 04/10/2017 454183 P 339 OS Relocate large cardboard box to maintain clear path to stair door
405190 04/10/2017 454205 P 6147 OS Relocate table to maintain 3 ft clear path to back exit door
405143 04/10/2017 454102 P 9619 OS Rearrange furniture to maintain 3 ft clear path to back exit door
391735 01/24/2017 425158 2 018 M Repair leaking chiller at P-1 (blue) to ensure it operates as designed
335548 01/24/2017 303049 P 289 M Replace missing hurricane anchor for blocks adjacent to ramp and on west side of portable
391738 04/25/2016 425164 1 017 M Remove one latch from emergency escape window
391705 04/25/2016 425096 10 001 M Adjust door closer on exterior door to control speed of closing door
391707 04/25/2016 425100 10 004 M Repair exterior door to close and latch properly
391697 04/25/2016 425080 11 009 M Repair or replace damaged door
391693 04/25/2016 425071 11 010 M Repair damaged, cracked ceiling and damaged wall at base
391679 04/25/2016 425040 12 005 M Repair (west) main entrance door to close and latch properly
391728 04/25/2016 425143 2 001 M Determine cause of water damaged ceiling tiles and replace tiles
391729 04/25/2016 425145 2 004 M Determine cause of water damaged ceiling tiles and replace tiles, replace missing tiles
391736 04/25/2016 425160 2 005 M Repair door of walk in refrigerator to close properly (located outside)
391737 04/25/2016 425162 2 005 M Provide cover on exposed electrical junction box located above sinks
391732 04/25/2016 425152 2 102 M Determine cause of water damaged ceiling tiles and replace tiles
391698 04/25/2016 425082 3 001 M Determine cause of water damaged ceiling tiles and replace tiles, replace missing tiles
391699 04/25/2016 425084 3 001A M Provide cover on exposed electrical junction box on wall
391700 04/25/2016 425086 3 001B M Determine cause of water damaged ceiling tiles and replace tiles
391703 04/25/2016 425092 3 004 M Determine cause of water damaged ceiling tiles and replace tiles
391702 04/25/2016 425090 3 004C M Replace missing ceiling tiles
391723 04/25/2016 425133 4 001 M Determine cause of water damaged ceiling tiles and replace tiles
391726 04/25/2016 425139 4 013 M Determine cause of water damaged ceiling tiles and replace tiles
391722 04/25/2016 425131 5 001 M Secure loose base on wall adjacent to storage area
391721 04/25/2016 425129 5 004 M Repair corridor door to close and latch properly
391717 04/25/2016 425121 6 002 M Adjust door closer to control speed of closing door
391704 04/25/2016 425094 9 001 M Repair exterior door to close and latch properly
391680 04/25/2016 425042 P 289 M Repair broken emergency lighting
391711 04/25/2016 425109 P 31 M Determine cause of water damaged ceiling tiles and replace tiles
335538 04/25/2016 303026 P 3543 M Replace missing hurricane anchors at mate line for portable
391720 04/25/2016 425127 P 6478 M Determine cause of water damaged ceiling tiles and replace tiles
391690 04/25/2016 425062 P 9617 M Repair emergency lighting (x2)
391687 04/25/2016 425056 P 9618 M Repair emergency lighting at west door
391688 04/25/2016 425058 P 9618 M Determine cause of water damaged ceiling tiles and replace tiles
391685 04/25/2016 425052 P 9619 M Repair emergency lighting (x2)
391683 04/25/2016 425048 P 9620 M Determine cause of water damaged ceiling tiles and replace tiles
391681 04/25/2016 425044 P 9621 M Repair emergency lighting (x2)
391676 04/25/2016 425034 P 9936 M Repair emergency lighting at north door
391677 04/25/2016 425036 P 9936 M Secure loose base adjacent to door on south wall
391673 04/25/2016 425028 P 9937 M Repair south door to close properly
391674 04/25/2016 425030 P 9937 M Determine cause of water damaged ceiling tiles and replace tiles at south wall
391671 04/25/2016 425024 P 9938 M Repair emergency lighting (x2)
391672 04/25/2016 425026 P 9938 M Determine cause of water damaged ceiling tiles and replace tiles
391706 04/25/2016 425098 10 001 O Prohibit use of surge protector with damaged cord, located adjacent to computer
391694 04/25/2016 425073 11 002 O Relocate string line to hang no more than 2 inches from wall surface
391692 04/25/2016 425069 11 010 O Replace bulbs in light fixture
391730 04/25/2016 425147 2 004 O Prohibit use of grey multi outlet extension cord (at refrigerator)
391731 04/25/2016 425150 2 004 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
391733 04/25/2016 425154 2 015 O Prohibit plugging refrigerator into surge protector, plug directly into permanent electrical outlet
391725 04/25/2016 425137 4 002 O Prohibit plugging surge protector into orange multi outlet extension cord adjacent to computer. Prohibit use of multi outlet extension cord. Plug surge protector directly into permanent electrical outlet
391727 04/25/2016 425141 4 013 O Prohibit attaching light to ceiling grid
391712 04/25/2016 425111 P 31 O Prohibit attaching papers to window blinds
391713 04/25/2016 425113 P 339 O Prohibit running data and electrical cords over ramp door
391714 04/25/2016 425115 P 339 O Prohibit plugging surge protector into yellow extension cord adjacent to computers
391667 04/25/2016 425014 P 6148 O Remove and prohibit flammable tent hanging from ceiling
391668 04/25/2016 425017 P 6149 O Remove and prohibit excessive flammable decorations on walls and excessive storage in room. Limit coverage area to 20 percent of each wall in a room without fire sprinklers
391670 04/25/2016 425022 P 6399 O Remove and prohibit anchor charts hanging from ceiling
391719 04/25/2016 425125 P 6478 O Remove and prohibit air freshener
391689 04/25/2016 425060 P 9617 O Remove and prohibit anchor charts and posters hanging from ceiling
391684 04/25/2016 425050 P 9620 O Relocate string line to hang no more than 2 inches from wall surface
391675 04/25/2016 425032 P 9936 O Prohibit hanging string line across the room, relocate string ling to hang no more than 2 inches from wall surface
391678 04/25/2016 425038 P 9936 O Remove and prohibit air freshener (plug in style)
391701 04/25/2016 425088 3 004 MS Provide current inspection tag for fire extinguisher
391716 04/25/2016 425119 6 009 MS Recharge fire extinguisher
391695 04/25/2016 425076 00 0000 OS Remove chains and padlocks from gates
391696 04/25/2016 425078 11 003 OS Maintain clear aisle to exterior exit
391691 04/25/2016 425064 11 011 OS Remove storage from mechanical room
391666 04/25/2016 425012 12 007 OS Remove storage from mechanical room
391734 04/25/2016 425156 2 016 OS Remove storage from mechanical room
391724 04/25/2016 425135 4 008 OS Relocate computer to keep area clear at emergency escape window
391715 04/25/2016 425117 6 008 OS Remove storage from mechanical room
391710 04/25/2016 425107 7 004 OS Maintain clear aisle to exterior exit
391709 04/25/2016 425105 7 008 OS Remove storage from mechanical room
391708 04/25/2016 425103 8 008 OS Remove storage from mechanical room
391686 04/25/2016 425054 P 3543 OS Maintain clear aisle to stair exit
391669 04/25/2016 425019 P 6149 OS Provide clear access to fire extinguisher
391718 04/25/2016 425123 P 6480 OS Provide clear access to fire extinguisher
366815 02/05/2016 371236 2 0000 M Repair valve handle at can wash. See custodian
360037 02/05/2016 356545 P 31 M Replace deteriorated wood siding
360041 02/05/2016 356556 P 339 M Replace deteriorated wood siding
366859 02/05/2016 371323 P 3543 M Exterminate termites and repair damage
359984 02/05/2016 356432 P 6399 M Replace cover for cleanout and storm drain grate behind unit
360119 05/04/2015 356736 1 022B M Repair exhaust fan in bathroom
359989 05/04/2015 356443 10 006B M Repair exhaust fan in bathroom
360101 05/04/2015 356698 10 010 M Replace rusted leaking water heater
366814 05/04/2015 371234 2 007 M Repair exhaust fan in bathroom
335502 05/04/2015 302944 4 005C M Repair exhaust fan in bathroom
366852 05/04/2015 371310 P 31 M Repair exhaust fan in bathroom
343051 05/04/2015 319326 4 013 O Treat green curtain with flame retardant spray and provide manufacturers certification of treatment or remove and prohibit curtain
366912 03/30/2015 371439 P 9936 M Adjust rear door to latch properly
359980 03/30/2015 356423 00 0 O No access was available to the restrooms in the building at the old Park. Please provide access to these rooms during the report review meeting
360043 03/30/2015 356560 00 0000 O Prohibit parking on grass area at west end of campus
366808 03/30/2015 371222 00 0000 OS Prohibit hold open devices on classroom doors. Classroom doors should remain closed when school is in session
360108 03/30/2015 356713 00 0000 OS Prohibit storage of gasoline and gas powered equipment in metal storage building next to building 2
366470 03/30/2015 370480 11 012 OS Remove and prohibit chairs, desks and tables in corridor to maintain clear aisle to exit
335523 03/30/2015 302992 12 007 OS Remove storage from mechanical room
366817 03/30/2015 371240 2 016 OS Remove storage from mechanical room
366822 03/30/2015 371251 5 008 OS Remove storage from mechanical room
366827 03/30/2015 371259 5 009 OS Remove and prohibit chairs, desks and tables in corridor to maintain clear aisle to exit
366969 03/30/2015 371570 6 009 OS Remove and prohibit chairs, desks and tables in corridor to maintain clear aisle to exit
366950 03/30/2015 371522 7 008 OS Remove storage from mechanical room
366839 03/30/2015 371285 7 009 OS Remove and prohibit chairs, desks and tables in corridor to maintain clear aisle to exit
366848 03/30/2015 371303 8 008 OS Remove storage from mechanical room
366840 03/30/2015 371287 8 009 OS Remove and prohibit chairs, desks and tables in corridor to maintain clear aisle to exit
366821 03/17/2015 371245 2 0000 M Replace missing anchor on cooling tower
335516 03/17/2015 302975 P 6146 M Remove excess vinyl floor tile glue from floor
366894 03/17/2015 371402 P 9617 M Replace missing flooring in bathroom
360065 03/17/2015 356613 P 9620 M Refinish bathroom floor
366931 03/13/2015 371475 1 006B M Repair exhaust fan in bathroom
366467 03/13/2015 370474 1 008 M Flapper valve in toilet not sealing. Toilet runs on. Replace flapper valve
366465 03/13/2015 370470 1 016 M Provide certification that fire alarm system has been tested and is fully operational. New system tagged 7-2013
366466 03/13/2015 370472 1 022C M Repair door to open and close properly. Door hits frame
366792 03/13/2015 371187 10 001 M Adjust door to exterior to latch properly
366797 03/13/2015 371197 10 003 M Repair leaking supply line to drinking fountain
366807 03/13/2015 371215 10 003 M Adjust door to exterior to latch properly
366791 03/13/2015 371184 10 004 M Adjust door to exterior to latch properly
366930 03/13/2015 371473 10 011 M Insulate chilled water lines
366836 03/13/2015 371279 11 002 M Adjust drinking fountain. Arc too low
366837 03/13/2015 371281 11 003 M Adjust drinking fountain. Arc too low
366809 03/13/2015 371224 12 003 M Caulk loose window in door to 12-002
359996 03/13/2015 356458 12 007 M Place exposed wires in conduit or junction box
366816 03/13/2015 371238 2 0000 M Paint warning stripe along loading dock behind Kitchen
366927 03/13/2015 371466 2 001 M Determine cause of water damaged ceiling tiles and replace tiles at east side of room
366921 03/13/2015 371458 2 004 M Adjust door to kitchen to latch properly. Sticky latch
366959 03/13/2015 371541 2 011 M Secure loose ground lug to water pipe. Wrong room number
366812 03/13/2015 371229 2 012 M Determine cause of water damaged ceiling tiles and replace tiles
366818 03/13/2015 371242 2 016 M Provide cover on exposed electrical junction box on supply side of air handler
366926 03/13/2015 371464 2 018 M Secure loose door knob
366963 03/13/2015 371552 3 001B M Determine cause of water damaged ceiling tiles and replace tiles
343043 03/13/2015 319308 3 008 M Repair door to latch properly
366961 03/13/2015 371545 3 008A M Repair cover of panel C to latch
366957 03/13/2015 371536 4 004 M Determine cause of water damaged ceiling tiles and replace tiles
366933 03/13/2015 371479 4 008 M Determine cause of water damaged ceiling tiles and replace tiles
366964 03/13/2015 371555 5 003 M Remove damaged pencil sharpener adjacent to bathroom
366824 03/13/2015 371253 5 008 M Breaker 9 on panel 1-E tripped. Repair circuit
335490 03/13/2015 302920 5 008 M Provide cover on exposed electrical gutter
366949 03/13/2015 371519 5 009 M Repair door hardware. Panic bar will not retract latch
366966 03/13/2015 371560 6 004A M Secure loose handicapped grabrail
360104 03/13/2015 356704 7 0000 M Remove rubber tree growing in fascia outside of 7-002
366834 03/13/2015 371275 7 002 M Repair drinking fountain. Arc too high
360004 03/13/2015 356475 7 002C M Replace missing ceramic base tile along wall
335534 03/13/2015 303015 7 002C M Repair crack in wall and refinish wall
360028 03/13/2015 356525 7 004C M Paint refinished bathroom wall
366838 03/13/2015 371283 7 004C M Repair damaged wall at base
366953 03/13/2015 371524 7 008 M Breaker 23 on panel 3E is tripped. Repair circuit
366844 03/13/2015 371295 8 001 M Adjust drinking fountain. Arc too high
366845 03/13/2015 371297 8 002A M Repair damaged wall at base
335535 03/13/2015 303018 8 003A M Refinish wall in bathroom
366847 03/13/2015 371299 8 004 M Secure loose base along wall adjacent to exterior door
335536 03/13/2015 303020 8 004A M Refinish wall in bathroom
366841 03/13/2015 371289 9 001 M Secure loose spout on drinking fountain
343142 03/13/2015 319523 9 001 M Adjust door closer on exterior door to control speed of closing door
360026 03/13/2015 356521 9 001A M Secure loose handicapped grabrail
366842 03/13/2015 371291 9 002 M Adjust door closer on door to corridor to control speed of closing
366929 03/13/2015 371470 9 004A M Finish unfinished wall in bathroom to provide impervious wall finish
360044 03/13/2015 356562 9 005 M Secure hanging heat detector
366468 03/13/2015 370476 P 0000 M Replace lock on gate of fencing around electrical equipment adjacent to P-8A
366965 03/13/2015 371558 P 0000 M Provide lock on gate of fencing around electrical equipment adjacent to P-10-1
366851 03/13/2015 371308 P 31 M Determine cause of water damaged ceiling tiles and replace tiles in classroom and bathroom
366885 03/13/2015 371383 P 31 M Clean out gutters and downspout
366886 03/13/2015 371385 P 339 M Clean out gutters and downspouts
366855 03/13/2015 371318 P 339 M Determine cause of water damaged ceiling tiles and replace tiles
366862 03/13/2015 371332 P 6146 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
366863 03/13/2015 371336 P 6146 M Secure loose faucet to sink
366865 03/13/2015 371340 P 6147 M Secure sink to wall in bathroom and make repair impervious
366866 03/13/2015 371342 P 6148 M Repair emergency lighting X 2
366867 03/13/2015 371344 P 6149 M Exterior 12 inch by 12 inch junction box is partially buried. Remove dirt from beneath box so that it does not contact ground
366868 03/13/2015 371346 P 6149 M Adjust rear door to latch properly
366871 03/13/2015 371353 P 6149 M Patch and refinish bathroom wall adjacent to toilet paper dispenser. Make repair impervious
366874 03/13/2015 371358 P 6400 M Repair electrical panel to latch
366878 03/13/2015 371362 P 6400 M Secure faucet to sink
366881 03/13/2015 371372 P 6400 M Adjust door to bathroom to latch properly. Door hits frame
359983 03/13/2015 356429 P 6400 M Reconnect downspout to storm drainage system
366884 03/13/2015 371380 P 6478 M Determine cause of water damaged hard ceiling in bathroom adjacent to exhaust fan and repair leak and ceiling
360086 03/13/2015 356660 P 6479 M Repair emergency lighting at rear
366891 03/13/2015 371394 P 6480 M Repair ceiling grid. Loose piece
366892 03/13/2015 371398 P 6480 M Secure sink to wall in bathroom. Make repair impervious
366893 03/13/2015 371400 P 9617 M Determine cause of water damaged ceiling tiles and replace tiles
366895 03/13/2015 371404 P 9617 M Make repair to wall at bathroom sink impervious
366897 03/13/2015 371406 P 9618 M Repair rear door to open and close properly
366899 03/13/2015 371411 P 9618 M Repair emergency lighting at rear door
366901 03/13/2015 371415 P 9618 M Determine cause of water damaged ceiling tiles and replace tiles
366905 03/13/2015 371423 p 9619 M Repair emergency lighting at front door
366907 03/13/2015 371429 P 9620 M Seal bathroom wall at sink to provide impervious wall finish
366911 03/13/2015 371437 P 9622 M Determine cause of water damaged ceiling tiles and replace tiles
366913 03/13/2015 371441 P 9937 M Repair rear door to open and close properly
366914 03/13/2015 371443 P 9937 M Determine cause of water damaged ceiling tiles and replace tiles
366915 03/13/2015 371445 P 9937 M Repair emergency lighting at front door
366916 03/13/2015 371447 P 9937 M Replace missing storm drain grate behind unit
366917 03/13/2015 371449 P 9938 M Replace missing storm drain grate behind unit
366918 03/13/2015 371451 P 9938 M Adjust rear door to latch properly
366919 03/13/2015 371453 P 9938 M Determine cause of water damaged ceiling tiles and replace tiles
366920 03/13/2015 371455 P 9938 M Replace missing base along wall in bathroom
366932 03/13/2015 371477 00 0000 O Provide clear access to electrical panel in closet behind bathroom building in old park
366910 03/13/2015 371435 P 9621 O Provide clear access to electrical panel
247868 03/13/2015 115519 00 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters. (Now on ADA report)
366804 03/13/2015 371213 10 003 MS Provide current inspection tag for fire extinguisher
366796 03/13/2015 371195 10 003 MS Adjust corridor door to latch properly
366790 03/13/2015 371181 10 004 MS Adjust corridor door to latch properly
366829 03/13/2015 371265 11 004 MS Adjust corridor door to latch properly
366835 03/13/2015 371277 11 012 MS Recharge fire extinguisher
366928 03/13/2015 371468 9 004 MS Adjust corridor door to latch properly
360109 03/13/2015 356715 00 0000 OS Prohibit storage of gasoline and gas powered equipment in metal storage building north of building 2. Waived by Tom Hogarth. Separate enclosed storage building
366469 03/13/2015 370478 10 012 OS Remove and prohibit chairs, desks and tables in corridor to maintain clear aisle to exit
366830 03/13/2015 371267 12 003 OS Maintain clear aisle to rear exit
366962 03/13/2015 371549 3 008A OS Remove storage from mechanical room
366955 03/13/2015 371532 5 002 OS Relocate desk to maintain clear aisle to rear exit
366833 03/13/2015 371273 6 008 OS Remove storage from mechanical room
366843 03/13/2015 371293 9 009 OS Remove and prohibit chairs, desks and tables in corridor to maintain clear aisle to exit
366864 03/13/2015 371338 P 6147 OS Maintain clear 3 foot clear aisle to rear exit
366908 03/13/2015 371432 P 9621 OS Maintain clear aisle to rear exit
335494 03/13/2015 302926 00 0000 CS Provide an appropriate storage area for gasoline and gas powered equipment
359972 03/13/2015 356405 10 012 CS Change swing of classroom door at 10-002 (6C) to swing into classroom to eliminate dead end corridor
359973 03/13/2015 356407 11 012 CS Change swing of classroom door at 11-002 (7C) to swing into classroom to eliminate dead end corridor
359974 03/13/2015 356409 5 009 CS Change swing of classroom door at 5-002 (1C) to swing into classroom to eliminate dead end corridor
359976 03/13/2015 356413 7 009 CS Change swing of classroom door at 7-002 (3C) to swing into classroom to eliminate dead end corridor
359977 03/13/2015 356415 8 009 CS Change swing of classroom door at 8-002 (4C) to swing into classroom to eliminate dead end corridor
359978 03/13/2015 356417 9 009 CS Change swing of classroom door at 9-002 (5C) to swing into classroom to eliminate dead end corridor
359998 09/10/2014 356463 00 0000 M Clean out all gutters and downspouts on campus. 3 foot trees growing in some gutters
359992 09/10/2014 356450 12 003A M Refinish bathroom walls. Peeling paint and unfinished plaster
366832 09/10/2014 371269 3 004A M Repair exhaust fan for kiln. Do not use kiln until exhaust fan is repaired. Cord cap removed, kiln cannot be used
359999 09/10/2014 356465 5 008 M Close and lock open fire alarm cabinet
335646 09/10/2014 303254 7 003 M Adjust corridor door to latch properly
335647 09/10/2014 303258 8 002 M Adjust corridor door to latch properly
360070 09/10/2014 356624 P 0000 M Fill undermined sidewalk adjacent to P-9D. Modify storm drainage to prevent further damage
360036 09/10/2014 356542 P 289 M Seal seam in bathroom floor
360039 09/10/2014 356551 P 339 M Repair guardrail along ramp. Large gap between ramp landing guardrail and side of unit. Fill gap to prohibit passage 4 inch sphere
360046 09/10/2014 356567 P 3543 M Replace deteriorated wood siding
360057 09/10/2014 356596 P 9617 M Fill undermined rear landing and improve storm drainage from unit to prevent further erosion
360062 09/10/2014 356606 P 9617 M Replace crushed downspout
360063 09/10/2014 356608 P 9619 M Fill undermined rear landing and improve storm drainage from unit to prevent further erosion
360060 09/10/2014 356602 P 9619 M Patch or refinish bathroom floor. Pieces of epoxy floor coating are missing
360098 09/10/2014 356685 P 9936 M Refinish bathroom floor. Old finish coming up and missing pieces
360100 09/10/2014 356691 P 9936 M Replace grate for storm drain behind unit
360048 09/10/2014 356571 P 3543 O Provide clear access to electrical panel
343098 09/10/2014 319429 P 3543 O Prohibit plugging surge protector into surge protector
360110 09/10/2014 356717 4 001 C Install maximum occupancy signage. Contact Building Department for maximum occupancy number
360090 09/10/2014 356669 P 9938 C Provide impervious floor surface in bathroom. Vinyl floor tile not impervious
360107 04/03/2014 356710 00 0000 M Repair leaking irrigation line next to sidewalk south of 1-012
360045 04/03/2014 356564 00 0000 M Replace broken cover for box in playfield north of building 11
360032 04/03/2014 356534 00 0000 M Adjust new gate with panic hardware to west parking lot to latch properly
359981 04/03/2014 356425 00 0000 M Repair drinking fountain at bathroom building in old Park. Runs continually
335428 04/03/2014 302782 00 0000 M Remove rust, prime and paint columns at pavilion in old park at west end of campus. One column is rusted through. Contact Building Department for necessary repairs
335434 04/03/2014 302799 1 003 M Provide cover on old clock box
360121 04/03/2014 356740 1 012A M Secure loose door knob
360120 04/03/2014 356738 1 012B M Determine cause of water damaged ceiling tiles and replace tiles adjacent to heat detector
360118 04/03/2014 356734 1 022A M Replace missing strike plate on door frame
359985 04/03/2014 356434 1 023 M Close and lock open TV cabinet
359987 04/03/2014 356438 10 001 M Repair dripping faucet
359988 04/03/2014 356441 10 002 M Secure loose faucet to sink
359986 04/03/2014 356436 10 011 M Close 2 open junction boxes
360102 04/03/2014 356700 11 0000 M Replace crushed downspout adjacent to 11-011
335607 04/03/2014 303174 11 006B M Repair exhaust fan in bathroom
360103 04/03/2014 356702 11 009 M Caulk urinals to wall
343103 04/03/2014 319440 11 009 M Replace missing floor tile
360106 04/03/2014 356708 12 0000 M Replace missing cover plate for panic bar on gate east of building 12
359991 04/03/2014 356448 12 002A M Secure loose handicapped grabrail
359995 04/03/2014 356456 12 007 M Close and secure card access cabinet
335524 04/03/2014 302995 12 007 M Provide schedules for panels H-H and H
360111 04/03/2014 356719 2 003 M Replace missing ceiling tiles
359993 04/03/2014 356452 2 005 M 3 compartment sink in Kitchen has drain leak, repair leak.
359994 04/03/2014 356454 2 005 M Replace missing faucet handle for 3 compartment sink in Kitchen
360122 04/03/2014 356742 2 015A M Determine cause of water damaged ceiling tiles and replace tiles
360125 04/03/2014 356748 2 016 M Close and lock fire alarm box
360124 04/03/2014 356746 2 016A M Insulate hot water lines
360123 04/03/2014 356744 2 018 M Repair panel H1 to latch
360117 04/03/2014 356732 2 018 M Repipe drain for expansion tank. Pipe rusted through
360114 04/03/2014 356726 2 019 M Label all circuits on electrical panel EMI
360112 04/03/2014 356722 2 020 M Provide bracket and hang fire extinguisher at maximum five feet above floor adjacent to exit
360126 04/03/2014 356750 3 001B M Determine cause of water damaged ceiling tiles and replace tiles
360129 04/03/2014 356757 3 004D M Determine cause of water damaged ceiling tiles and replace tiles and replace missing tiles
360127 04/03/2014 356752 3 007 M Repair emergency lighting
360128 04/03/2014 356754 3 007 M Anchor toilet 2 to floor
359997 04/03/2014 356461 3 008 M Panel C breaker 14 tripped. Repair circuit
343050 04/03/2014 319324 4 013 M Determine cause of water damaged ceiling tiles and replace tiles
360013 04/03/2014 356494 5 001 M Repair delaminating door
360014 04/03/2014 356496 5 002 M Repair delaminating door
360006 04/03/2014 356480 5 002C M Secure loose handicapped grabrail
360008 04/03/2014 356484 5 002C M Toilet runs continually, repair
360015 04/03/2014 356498 5 006 M Repair delaminating door
360016 04/03/2014 356500 6 001 M Repair delaminating door
360011 04/03/2014 356490 6 001A M Secure loose handicapped grabrail
360001 04/03/2014 356469 6 003 M Secure loose faucet to sink
360009 04/03/2014 356486 6 008 M Breakers 20 and 22 tripped on electric panel. Repair circuits
360010 04/03/2014 356488 6 008 M Label all circuits on electrical panel. Schedule indicates circuits 20 and 22 are spares and the breakers are tripped
343060 04/03/2014 319345 6 009 M Secure loose base on wall adjacent to drinking fountain
360003 04/03/2014 356473 7 002 M Replace GFCI outlet that will not trip
360012 04/03/2014 356492 7 004C M Secure loose handicapped grabrail
360017 04/03/2014 356502 8 001 M Repair delaminating door
360024 04/03/2014 356517 8 003A M Secure loose handicapped grabrail
360031 04/03/2014 356531 8 006 M Provide cover on old clock box
360025 04/03/2014 356519 9 001 M Adjust door to exterior to latch properly
360027 04/03/2014 356523 9 002A M Secure loose handicapped grabrail
360018 04/03/2014 356504 9 003 M Repair delaminating door
360033 04/03/2014 356536 9 004 M Provide cover on old clock box
360034 04/03/2014 356538 P 0000 M Secure storm drain grates and frames to pipe at portables. Many grates and frames are displaced leaving large holes in the ground
359982 04/03/2014 356427 P 0000 M Provide chain and lock on gate of fencing around electrical equipment adjacent to P-9936 (P-9-I)
335661 04/03/2014 303282 P 0000 M Exterior junction boxes for P-9-A, B, C and D are partially buried. Remove dirt from around boxes so that boxes do not contact ground
360038 04/03/2014 356548 P 31 M Repair exhaust fan in bathroom
360042 04/03/2014 356558 P 339 M Repair emergency lighting
360049 04/03/2014 356573 P 6146 M Secure faucet to sink
360050 04/03/2014 356576 P 6147 M Replace missing storm drain grate behind unit
343115 04/03/2014 319467 P 6148 M Replace missing sign indicating epoxy wall finish in bathroom
360054 04/03/2014 356588 P 6400 M Repair electrical panel to latch
360088 04/03/2014 356665 P 6478 M Replace ceiling tiles with holes in them
360089 04/03/2014 356667 P 6478 M Repair toilet that runs continually
360085 04/03/2014 356658 P 6479 M Replace ceiling tiles with holes in them
360082 04/03/2014 356651 P 6480 M Replace ceiling tiles with holes in them
360073 04/03/2014 356631 P 6481 M Replace ceiling tiles with holes in them
360055 04/03/2014 356590 P 9617 M Determine cause of water damaged ceiling tiles and replace tiles
360056 04/03/2014 356592 P 9617 M Caulk bathroom sink to wall
360058 04/03/2014 356598 P 9618 M Adjust rear door to latch properly
360061 04/03/2014 356604 P 9619 M Caulk sink to bathroom wall
360066 04/03/2014 356615 P 9620 M Secure sink to wall in bathroom
360067 04/03/2014 356617 P 9621 M Adjust front door to latch properly, sticky latch
360097 04/03/2014 356683 P 9936 M Secure sink to wall in bathroom
360099 04/03/2014 356688 P 9936 M Adjust rear door to latch properly
360093 04/03/2014 356675 P 9937 M Determine cause of water damaged ceiling tiles and replace tiles
360094 04/03/2014 356677 P 9937 M Adjust rear door to latch properly
360091 04/03/2014 356671 P 9938 M Caulk sink to wall in bathroom
343105 04/03/2014 319444 11 002 O Prohibit white multi outlet extension cord or replace with minimum 15A single outlet cord
343038 04/03/2014 319297 2 015 O Prohibit plugging microwave into extension cord and surge protector - plug directly into permanent electrical outlet
360005 04/03/2014 356478 5 001 O Prohibit plugging surge protector into extension cord into surge protector
343052 04/03/2014 319328 5 002 O Prohibit plugging surge protector into orange extension cord
343054 04/03/2014 319332 5 003 O Prohibit plugging surge protector into wall mounted surge protector adjacent to pencil sharpener
343056 04/03/2014 319336 5 004 O Prohibit plugging surge protector into black multi outlet extension cord
335489 04/03/2014 302917 6 002 O Prohibit plugging surge protector into extension cord
360019 04/03/2014 356506 7 001 O Prohibit plugging surge protector into surge protector
360030 04/03/2014 356529 8 001 O Prohibit plugging surge protector into extension cord
343070 04/03/2014 319369 P 31 O Prohibit plugging surge protector into surge protector
343071 04/03/2014 319371 P 31 O Prohibit plugging surge protector into black extension cord adjacent to teachers desk
360040 04/03/2014 356553 P 339 O Prohibit plugging surge protector into extension cord
343095 04/03/2014 319422 P 3543 O Relocate string line to hang no more than 2 inches from wall
343097 04/03/2014 319427 P 3543 O Remove excessive flammable wall decorations, solid paper on walls (including plastic straw), limit coverage to 20 percent of each wall
335515 04/03/2014 302973 P 6146 O Prohibit plugging surge protector into extension cord
343117 04/03/2014 319471 P 6148 O Prohibit running electrical cord across floor
360051 04/03/2014 356580 P 6149 O Remove and prohibit excessive flammable decorations. Maximum of 20 percent of wall area can be covered with flammable decorations
360053 04/03/2014 356585 P 6400 O Eliminate multiple outlet adapter, use surge suppressor
343125 04/03/2014 319489 P 6400 O Prohibit running electrical cord across floor and under rug
360059 04/03/2014 356600 P 9618 O Provide clear access to electrical panel
343093 04/03/2014 319416 P 9619 O Prohibit plugging surge protector into black multi outlet extension cord, plug into permanent electrical outlet. Prohibit multi outlet extension cord
343094 04/03/2014 319419 P 9619 O Prohibit running electrical cord across floor
343091 04/03/2014 319412 P 9620 O Prohibit plugging surge protectors into multi outlet extension cords, plug surge protectors directly into permanent electrical outlets. Prohibit multi outlet extension cords
343092 04/03/2014 319414 P 9620 O Prohibit running electrical cord(s) across floor
315411 04/03/2014 258736 P 9620 O Eliminate extension 13A cord or replace with minimum 15A cord
360035 04/03/2014 356540 P 289 C Attach ground wire to 10 inch by 10 inch exterior junction box
360047 04/03/2014 356569 P 3543 C Attach ground wire to 10 inch by 10 inch exterior junction box
360077 04/03/2014 356641 P 6478 C Provide impervious epoxy wall finish in bathroom or if epoxy painted provide sign indicating so
360076 04/03/2014 356639 P 6479 C Provide impervious epoxy wall finish in bathroom or if epoxy painted provide sign indicating so
360075 04/03/2014 356637 P 6480 C Provide impervious epoxy wall finish in bathroom or if epoxy painted provide sign indicating so
360072 04/03/2014 356629 P 6481 C Provide impervious epoxy wall finish in bathroom or if epoxy painted provide sign indicating so
360080 04/03/2014 356647 P 9936 C Provide impervious epoxy wall finish in bathroom or if epoxy painted provide sign indicating so
360079 04/03/2014 356645 P 9937 C Provide impervious epoxy wall finish in bathroom or if epoxy painted provide sign indicating so
360078 04/03/2014 356643 P 9938 C Provide impervious epoxy wall finish in bathroom or if epoxy painted provide sign indicating so
360116 04/03/2014 356730 2 019 MS Remove storage from electrical room
343047 04/03/2014 319317 3 005A MS Provide current inspection tag for fire extinguisher. Dated 2007
360002 04/03/2014 356471 6 009 MS Recharge fire extinguisher
360021 04/03/2014 356510 7 002 MS Recharge fire extinguisher
360087 04/03/2014 356663 P 6478 MS Provide current inspection tag for fire extinguisher
360084 04/03/2014 356656 P 6479 MS Provide current inspection tag for fire extinguisher
360081 04/03/2014 356649 P 6480 MS Provide current inspection tag for fire extinguisher
360071 04/03/2014 356627 P 6481 MS Provide current inspection tag for fire extinguisher
360068 04/03/2014 356619 P 9622 MS Recharge fire extinguisher
343144 04/03/2014 319527 10 001 OS Maintain clear aisle to (exterior) exit
343104 04/03/2014 319442 11 001 OS Prohibit running electrical cords under carpet in front of door and projector screen
359990 04/03/2014 356446 11 003 OS Maintain 3 foot clear aisle to rear exit
335617 04/03/2014 303194 11 012 OS Remove and prohibit chairs and desks in corridor
343132 04/03/2014 319503 12 001 OS Prohibit running electrical cord under carpet
343134 04/03/2014 319507 12 002 OS Prohibit running electrical cord in front of door
343135 04/03/2014 319509 12 003 OS Prohibit running electrical cords across floor
360115 04/03/2014 356728 2 019 OS Remove storage from electrical room
335486 04/03/2014 302910 5 009 OS Remove and prohibit chairs and desks in corridor
360000 04/03/2014 356467 6 002 OS Maintain 3 foot clear aisle to rear exit
335488 04/03/2014 302914 6 009 OS Remove and prohibit chairs and desks in corridor
360020 04/03/2014 356508 7 001 OS Maintain 3 foot clear aisle to rear exit
360022 04/03/2014 356512 7 002 OS Maintain 3 foot clear aisle to rear exit
360023 04/03/2014 356514 7 003 OS Maintain 3 foot clear aisle to rear exit
335520 04/03/2014 302983 7 009 OS Remove and prohibit desks and chairs in corridor
360029 04/03/2014 356527 8 008 OS Remove storage from mechanical room
335521 04/03/2014 302986 8 009 OS Remove and prohibit chairs and desks in corridor
343141 04/03/2014 319521 9 001 OS Prohibit running electrical cords across floor
315404 04/03/2014 258721 P 6146 OS Relocate cabinet blocking rear exit
343112 04/03/2014 319460 P 6147 OS Maintain clear aisle to (rear)) exit
343116 04/03/2014 319469 P 6148 OS Maintain clear aisle to (rear) exit
360083 04/03/2014 356654 P 6480 OS Maintain 3 foot clear aisle to rear exit
335528 04/03/2014 303003 P 9618 OS Prohibit running electrical cord under rug
343100 04/03/2014 319433 P 9618 OS Maintain clear aisle to (rear) exit
360064 04/03/2014 356611 P 9620 OS Maintain 3 foot clear aisle to rear exit
343088 04/03/2014 319406 P 9621 OS Relocate or turn file cabinet at rear door to maintain clear aisle to exit
360069 04/03/2014 356622 P 9622 OS Maintain 3 foot clear aisle to rear exit
360095 04/03/2014 356679 P 9936 OS Provide clear access to fire extinguisher
360096 04/03/2014 356681 P 9936 OS Maintain 3 foot clear aisle to rear exit
360092 04/03/2014 356673 P 9938 OS Maintain 3 foot clear aisle to rear exit
360113 04/03/2014 356724 2 019 CS Provide auto closer on 90 minute fire door
359975 04/03/2014 356411 6 009 CS Change swing of classroom door at 6-002 (2C) to swing into classroom to eliminate dead end corridor
343145 12/11/2013 319529 10 002 M Repair corridor door to close and latch properly
335636 12/11/2013 303234 11 0000 M Replace missing shingles on SE side of roof
335609 12/11/2013 303177 11 006 M Provide cover on old clock box
335460 12/11/2013 302855 4 003 M Provide cover on old clock box
335624 12/11/2013 303209 9 003 M Replace GFCI outlet that will not trip
343109 12/11/2013 319452 P 6146 M Adjust door closer on entrance door to control speed of closing door
343110 12/11/2013 319455 P 6146 M Replace damaged flooring adjacent to teachers desk and at mate line
335602 12/11/2013 303163 11 002 O Remove and prohibit hanging paper on string line. String line is acceptable against wall
343106 12/11/2013 319446 11 002 O Prohibit plugging surge protector into orange extension cord
343107 12/11/2013 319448 11 002 O Remove and prohibit flammable (green) plastic table skirt
343108 12/11/2013 319450 11 004 O Prohibit plugging surge protector into surge protector
335606 12/11/2013 303172 11 005 O Prohibit storage in electrical room to maintain clear access to electrical panels
343140 12/11/2013 319519 12 004 O Prohibit plugging refrigerator into orange extension cord - plug directly into permanent electrical outlet
343057 12/11/2013 319338 5 004 O Prohibit running electrical cords across floor
343055 12/11/2013 319334 5 004 O Prohibit covering electrical outlet (at bulletin board) with yellow paper
343062 12/11/2013 319349 6 003 O Prohibit running electrical cords across floor
335455 12/11/2013 302843 6 004 O Prohibit plugging surge protector into surge protector
343075 12/11/2013 319379 7 002 O Prohibit running electrical cords across floor
343078 12/11/2013 319386 7 004 O Prohibit running electrical cord across floor
343081 12/11/2013 319392 8 002 O Prohibit running electrical cords across floor
343082 12/11/2013 319394 8 003 O Prohibit multi outlet electrical adaptor
343083 12/11/2013 319396 8 004 O Prohibit running electrical cords across floor
343072 12/11/2013 319373 P 31 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet. Microwave oven gone
343073 12/11/2013 319375 P 31 O Remove and prohibit flammable (orange) plastic table coverings
343068 12/11/2013 319365 P 339 O Prohibit plugging surge protector into surge protector at computers
343069 12/11/2013 319367 P 339 O Remove and prohibit flammable plastic curtains and table coverings
343066 12/11/2013 319361 P 339 O Remove excessive flammable wall covering / solid paper on walls, limit coverage to maximum 20 percent of each wall
343111 12/11/2013 319458 P 6147 O Prohibit brown 13A extension cord at lamp or replace with minimum 15A cord
343101 12/11/2013 319435 P 9617 O Prohibit running electrical cord(s) across floor
343099 12/11/2013 319431 P 9618 O Prohibit plugging surge protector into orange extension cord
335552 12/11/2013 303058 P 9619 O Prohibit plugging surge protector into surge protector
335577 12/11/2013 303104 P 0000 C Modify or improve site drainage for portables P-9A through P-9I. Adjacent parking lot is higher than finish floor elevation and portables flood when it rains. Connect roof drains to storm drainage system. Currently roof drains dump water at bottom of portable wall
343133 12/11/2013 319505 12 002 OS Prohibit running electrical cord through ceiling tile
343048 12/11/2013 319320 4 012 OS Remove storage from mechanical room
343096 12/11/2013 319424 P 3543 OS Relocate furniture to maintain clear aisle to (stair) exit
343152 12/11/2013 319545 P 3543 OS Prohibit storage (potted plants) on ramp and stair landings to maintain clear aisle to exits
343113 12/11/2013 319462 P 6147 OS Prohibit hanging curtain over(entrance) door
200497 12/11/2013 25391 10 012 CS Change swing of classroom door at 10-002 (6C) to swing into classroom to eliminate dead end corridor
200502 12/11/2013 25392 11 012 CS Change swing of classroom door at 11-002 (7C) to swing into classroom to eliminate dead end corridor
200522 12/11/2013 25386 5 009 CS Change swing of classroom door at 5-002 (1C) to swing into classroom to eliminate dead end corridor
200525 12/11/2013 25387 6 009 CS Change swing of classroom door at 6-002 (2C) to swing into classroom to eliminate dead end corridor
200528 12/11/2013 25388 7 009 CS Change swing of classroom door at 7-002 (3C) to swing into classroom to eliminate dead end corridor
200532 12/11/2013 25389 8 009 CS Change swing of classroom door at 8-002 (4C) to swing into classroom to eliminate dead end corridor
200535 12/11/2013 25390 9 009 CS Change swing of classroom door at 9-002 (5C) to swing into classroom to eliminate dead end corridor
343151 12/11/2013 319542 1 016 FS Make repairs to fire alarm as noted on inspection report
343148 03/18/2013 319535 00 0000 M Replace rusty braces for pipe under cooling tower
343149 03/18/2013 319537 00 0000 M Install cap on fire department standpipe connection NW of cooling tower
343087 03/18/2013 319404 00 0000 M Repair sharp, damaged edge of column for covered walk adjacent to ramp of P-1
343150 03/18/2013 319540 1 009 M Relocate fire extinguisher from closet to classroom and mount fire extinguisher in classroom at maximum five feet above floor
335611 03/18/2013 303182 10 003 M Adjust corridor doors to latch properly
335614 03/18/2013 303189 10 004 M Adjust exterior and corridor doors to latch properly
343147 03/18/2013 319533 10 006B M Anchor toilet to floor
343143 03/18/2013 319525 10 011 M Repair door to open properly
343102 03/18/2013 319437 11 011 M Repair door to lock
343137 03/18/2013 319513 12 003 M Repair door to close and latch properly
343139 03/18/2013 319517 12 003A M Repair deteriorated wall finish
343037 03/18/2013 319295 2 001 M Determine cause of water damaged ceiling tiles and replace tiles @ east exterior doors
343041 03/18/2013 319304 2 005 M Repair / replace damaged electrical cord on ice machine
343042 03/18/2013 319306 2 008 M Repair / replace bracket for fan (staff has fan temporarily secured with string)
335479 03/18/2013 302894 2 008 M Rain water comes through exhaust vent for dishwashing machine. Repair roof leaks
343039 03/18/2013 319299 2 016 M Fill void in electrical panel D (right side)
343044 03/18/2013 319310 3 001 M Repair light in exit sign adjacent to emergency exit door
343053 03/18/2013 319330 5 002 M Repair exterior door to close properly
343058 03/18/2013 319341 5 006B M Repair non working toilet
343059 03/18/2013 319343 5 008 M Repair door hardware to lock properly
343063 03/18/2013 319351 6 009 M Determine cause of water damaged ceiling tiles and replace tiles
343079 03/18/2013 319388 8 001 M Adjust corridor door closer to control speed of closing door
335550 03/18/2013 303053 P 289 M Seal seam in bathroom flooring
343120 03/18/2013 319479 P 6149 M Adjust door closer on rear door to control speed of closing door
343121 03/18/2013 319481 P 6399 M Adjust door closer on entrance door to control speed of closing door
343122 03/18/2013 319483 P 6399 M Repair emergency lighting at entrance door
343124 03/18/2013 319487 P 6399 M Replace missing sign indicating epoxy wall finish in bathroom
343126 03/18/2013 319491 P 6400 M Repair emergency lighting at rear door
343084 03/18/2013 319398 P 9622 M Repair emergency lighting at entrance door
343085 03/18/2013 319400 P 9622 M Repair damaged electrical outlet on north exterior wall
343131 03/18/2013 319501 P 9936 M Replace missing sign indicating impervious wall finish in bathroom
343129 03/18/2013 319497 P 9937 M Replace missing sign indicating impervious wall finish in bathroom
343128 03/18/2013 319495 P 9938 M Replace missing sign indicating impervious wall finish in bathroom
343146 03/18/2013 319531 10 003 O Prohibit plugging microwave and refrigerator into multi outlet extension cord - plug directly into permanent electrical outlet
343138 03/18/2013 319515 12 003A O Remove and prohibit air freshener
343040 03/18/2013 319302 2 004 O Prohibit plugging refrigerator into grey multi outlet power strip - plug directly into permanent electrical outlet. Prohibit use of multi outlet power strip
343049 03/18/2013 319322 4 008 O Prohibit plugging surge protector into surge protector at computers
343061 03/18/2013 319347 6 003 O Prohibit multi outlet extension cord or replace with minimum 15A single outlet cord
343076 03/18/2013 319381 7 004 O Prohibit plugging surge protector into surge protector
343080 03/18/2013 319390 8 001 O Prohibit plugging surge protector into surge protector
343086 03/18/2013 319402 P 289 O Prohibit running electrical cord under carpet
343119 03/18/2013 319477 P 6149 O Prohibit white 13A extension cord at pencil sharpener or replace with minimum 15A single outlet cord
343089 03/18/2013 319408 P 9621 O Prohibit running electrical cord(s) across floor
343045 03/18/2013 319313 3 006 C Provide emergency lighting (built into ceiling light fixture)
343046 03/18/2013 319315 3 007 C Provide emergency lighting (built into ceiling light fixture)
343064 03/18/2013 319357 P 31 C Provide bottom rail on ramp landing guardrail at 2 inches above floor
343074 03/18/2013 319377 P 31 C Provide bottom rail on stair landing guardrail at 2 inches above floor
343065 03/18/2013 319359 P 339 C Provide bottom rail on stair landing guardrail at 2 inches above floor
343067 03/18/2013 319363 P 339 C Provide bottom rail on ramp landing guardrail at 2 inches above floor
335587 03/18/2013 303132 P 9938 C Provide impervious floor surface in bathroom. Vinyl floor tile is not considered impervious
343123 03/18/2013 319485 P 6399 MS Recharge fire extinguisher
343130 03/18/2013 319499 P 9936 MS Recharge fire extinguisher
343136 03/18/2013 319511 12 003 OS Maintain clear aisle to (exterior) exit
343077 03/18/2013 319384 7 004 OS Remove and prohibit use of space heater
343114 03/18/2013 319465 P 6148 OS Prohibit running electrical cord under carpet
343118 03/18/2013 319474 P 6149 OS Remove and prohibit excessive flammable wall coverings (including bathroom)
343127 03/18/2013 319493 P 9938 OS Maintain clear aisle to (rear) exit
335513 10/30/2012 302969 00 0000 M Trim under growth and remove old dead vegetation from old park at west side of campus
335612 10/30/2012 303185 10 004 M Secure loose faucet to sink
335613 10/30/2012 303187 10 004 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to corridor door
335510 10/30/2012 302963 2 0000 M Replace missing anchor for cooling tower
335474 10/30/2012 302884 3 0000 M Repair drinking fountain that will not drain on exterior wall adjacent to 3-007 and 3-008
335476 10/30/2012 302888 5 002C M Repair toilet that runs continually. Raise float on chain. Float is submerged and raises flapper and flapper does not seal
335453 10/30/2012 302838 5 004 M Secure loose faucet to sink
335443 10/30/2012 302819 6 002A M Repair deteriorated wall finish
335484 10/30/2012 302906 6 006B M Repair toilet that runs continually
335514 10/30/2012 302971 P 0000 M Repair wooden box over lift station adjacent to P-4
335545 10/30/2012 303042 P 289 M Provide landing at bottom of stairs
335542 10/30/2012 303036 P 31 M Provide landing at bottom of stairs
335543 10/30/2012 303038 P 339 M Provide landing at bottom of stairs
335544 10/30/2012 303040 P 3543 M Provide landing at bottom of stairs
335580 10/30/2012 303115 P 6147 M Secure sink to wall in bathroom
335527 10/30/2012 303001 P 9617 M Seal seam in bathroom flooring
335553 10/30/2012 303060 P 9619 M Seal seam in bathroom flooring
335559 10/30/2012 303073 P 9620 M Seal seam in bathroom flooring
335561 10/30/2012 303076 P 9621 M Seal seam in bathroom flooring
335565 10/30/2012 303082 P 9622 M Seal seam in bathroom flooring
335591 10/30/2012 303138 P 9936 M Seal seam in bathroom flooring
335547 10/30/2012 303046 7 003 O Remove and prohibit hanging paper from ceiling
335441 10/30/2012 302814 2 016 OS Remove storage from mechanical room
335620 10/30/2012 303200 9 009 OS Remove and prohibit desks and chairs in corridor
335556 10/30/2012 303067 P 9620 OS Maintain 3 foot clear aisle to rear exit
335567 10/30/2012 303090 P 9622 OS Maintain 3 foot clear aisle to rear exit
200484 04/26/2012 57216 00 9699 C Provide or designate and mark drive surface to allow fire department vehicle access to portable classrooms
335640 04/12/2012 303237 00 0000 M Domestic water back flow preventer has water continually running from differential pressure dump. Repair
335432 04/12/2012 302795 1 002B M Repair exhaust fan in bathroom
335436 04/12/2012 302802 1 005 M Replace GFCI outlet that will not trip
335437 04/12/2012 302806 1 023 M Determine cause of water damaged hard ceiling and repair ceiling
335610 04/12/2012 303180 10 001 M Repair damaged drinking fountain outside of rear door
335628 04/12/2012 303217 10 008 M Secure loose toilet seat
335629 04/12/2012 303220 10 008 M Anchor handicapped toilet to floor
335634 04/12/2012 303229 10 009 M Repair leaking flush valve for handicapped toilet
335626 04/12/2012 303213 10 012 M Secure loose faucet to center sink
335605 04/12/2012 303168 11 002 M Remove piece of cardboard at clerestory window
335616 04/12/2012 303191 11 008 M Pad and mark edges of unistrut used as framing member for bathroom partition which are lower than 6'8", or raise unistrut to 6 foot 8 inches
335650 04/12/2012 303264 12 001 M Adjust door to exterior to latch properly
335652 04/12/2012 303266 12 002 M Repair drinking fountain, low flow
335653 04/12/2012 303270 12 002 M Repair leaking faucet on sink
335656 04/12/2012 303276 12 002A M Secure loose handicapped grabrail
335657 04/12/2012 303279 12 003 M Repair drinking fountain, low flow
335522 04/12/2012 302990 12 007 M Repair door lock. Will not lock
335525 04/12/2012 302997 12 007 M Repair circuit 22 on panel H. Breaker tripped
335511 04/12/2012 302965 2 002 M Secure loose handrail/guardrail along ramp
335503 04/12/2012 302946 2 005 M Repair leaking faucet on 3 compartment sink
335509 04/12/2012 302960 2 012 M Secure grinder to counter top
335508 04/12/2012 302958 2 015A M Determine cause of water damaged ceiling tiles and replace tiles
335440 04/12/2012 302811 2 018 M Repair backflow device for make up water for chilled water system. Differential pressure dump is constantly running
335595 04/12/2012 303149 3 004A M Replace GFCI outlet adjacent to sink that will not trip
335594 04/12/2012 303144 3 008A M Repair circuit 14 on panel C. Breaker tripped
335501 04/12/2012 302941 4 010 M Determine cause of water damaged ceiling tiles and replace tiles
335478 04/12/2012 302892 4 012 M Adjust door to latch properly. Hinge backer plate is bent
335500 04/12/2012 302937 4 013 M Remove curtain from room or provide evidence of flame proofing
335473 04/12/2012 302882 5 001A M Secure loose handicapped grabrail
335475 04/12/2012 302886 5 002C M Secure loose handicapped grabrail
335457 04/12/2012 302848 5 003 M Adjust corridor door to latch properly
335458 04/12/2012 302850 5 004 M Adjust corridor door to latch properly
335452 04/12/2012 302836 6 001 M Adjust corridor door to latch properly
335495 04/12/2012 302930 6 001A M Secure loose handicapped grabrail
335442 04/12/2012 302816 6 002A M Repair toilet that continually runs
335497 04/12/2012 302933 6 004A M Secure loose handicapped grabrail
335546 04/12/2012 303044 7 003 M Determine cause of water damaged ceiling tiles and replace tiles and replace missing tiles
335644 04/12/2012 303247 7 008 M Repair circuit 23 on panel 3-E. GFI breaker will not reset
335649 04/12/2012 303261 8 002 M Repair delaminating corridor door
335537 04/12/2012 303023 8 004A M Repair toilet that runs continually
335532 04/12/2012 303011 8 006 M Determine cause of water damaged ceiling tiles and replace tiles and replace missing tiles
335619 04/12/2012 303198 9 0000 M Secure loose lens on exterior light fixture adjacent to entry
335621 04/12/2012 303202 9 001 M Adjust door to exterior to latch properly
335622 04/12/2012 303204 9 002 M Adjust corridor door to latch properly
335623 04/12/2012 303206 9 002 M Secure loose faucet on sink
335618 04/12/2012 303196 9 008 M Provide cover on exposed electrical junction box adjacent to air handler disconnect
335666 04/12/2012 303290 P 0000 M Repair and seal open expansion joints on exterior of P-9A through P-9I
335549 04/12/2012 303051 P 289 M Adjust ramp door to latch properly
335539 04/12/2012 303028 P 3543 M Repair emergency lighting
335540 04/12/2012 303030 P 3543 M Secure loose formica in bathroom
335519 04/12/2012 302981 P 6399 M Repair emergency lighting adjacent to rear door
335529 04/12/2012 303005 P 9618 M Seal seam in bathroom flooring
335530 04/12/2012 303007 P 9618 M Water running out of AC unit not coming out condensate drain. Repair AC unit
335555 04/12/2012 303064 P 9619 M Adjust rear door to latch properly
335558 04/12/2012 303069 P 9620 M Repair damaged wall at sink. Make repair impervious
335562 04/12/2012 303079 P 9621 M Repair drinking fountain at exterior wall. Low flow
335566 04/12/2012 303087 P 9622 M Refinish exterior wall where finish came off
335598 04/12/2012 303154 11 001 O Prohibit plugging extension cord into extension cord
335526 04/12/2012 302999 12 007 O Install fire extinguisher on bracket and make it accessible
308307 04/12/2012 243013 P 339 O Prohibit plugging surge protector into extension cord
335554 04/12/2012 303062 P 9619 O Remove 1/2 inch grey PVC in ground adjacent to entry
315413 04/12/2012 258741 P 9621 O Eliminate 13A extension cord or replace with minimum 15A cord
315415 04/12/2012 258745 P 9622 O Prohibit plugging extension cord into surge protector
335454 04/12/2012 302840 10 012 C Provide illuminated exit sign above 10-002 (6C)classroom door
335456 04/12/2012 302845 11 012 C Provide illuminated exit sign above classroom 11-002 (7C) door
335430 04/12/2012 302792 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus
335655 04/12/2012 303273 12 002 OS Prohibit running electrical cord into ceiling
335507 04/12/2012 302952 2 015 OS Prohibit blocking open door to cafeteria with a wedge on the hinge side of the door. This will damage the door, hinges and door frame. Temporarily block the door open with a wedge between the bottom of the door and the floor
335477 04/12/2012 302890 4 012 OS Remove storage from mechanical room
335533 04/12/2012 303013 7 001 OS Maintain 3 foot clear aisle to rear exit
335541 04/12/2012 303032 P 3543 OS Maintain 3 foot clear aisle to rear exit
335517 04/12/2012 302977 P 6148 OS Maintain 3 foot clear aisle to rear exit
335518 04/12/2012 302979 P 6148 OS Prohibit running electrical cord under rug
335667 04/12/2012 303302 P 6399 OS Prohibit running electrical cord under rug
335668 04/12/2012 303304 P 6399 OS Maintain 3 foot clear aisle to rear exit
335531 04/12/2012 303009 P 9618 OS Maintain 3 foot clear aisle to rear exit
335551 04/12/2012 303055 P 9619 OS Prohibit running electrical cord across floor causing a tripping hazard
315400 02/17/2012 258712 6 009 M Determine cause of water damaged ceiling tiles and replace tiles
308327 02/17/2012 243055 11 001 O Prohibit plugging extension cord into surge protector
247882 02/17/2012 115547 9 009 C Provide illuminated exit sign above 9-002 (5C) classroom door
260828 02/17/2012 143023 14 0000 N/A No violations observed
315156 02/22/2011 258192 1 006 M Replace missing threshold
315387 02/22/2011 258684 1 009 M Determine cause of water damaged ceiling tiles and replace tiles
315157 02/22/2011 258194 1 009A M Determine cause of water damaged ceiling tiles and replace tiles
315149 02/22/2011 258177 1 012A M Determine cause of water damaged ceiling tiles and replace tiles
315151 02/22/2011 258182 1 012A M Replace missing door stop
315152 02/22/2011 258184 1 012A M Determine cause of water damaged ceiling tiles and replace tiles
315148 02/22/2011 258174 1 012C M Determine cause of water damaged ceiling tiles and replace tiles
315140 02/22/2011 258156 1 015 M Repair interior door to close properly
315142 02/22/2011 258160 1 015A M Anchor toilet to floor
315143 02/22/2011 258163 1 021 M Determine cause of water damaged ceiling tiles and replace tiles
315146 02/22/2011 258171 1 220 M Repair exterior corridor door to close properly
315396 02/22/2011 258702 10 002 M Repair exterior door to close properly
315395 02/22/2011 258700 10 004 M Determine cause of water damaged ceiling tiles and replace tiles
315397 02/22/2011 258704 11 012 M Determine cause of water damaged ceiling tiles and replace tiles
315392 02/22/2011 258694 3 006 M Anchor toilet to floor
315389 02/22/2011 258688 4 003 M Provide cover on exposed electrical junction box (missing clock)
315390 02/22/2011 258690 4 010 M Determine cause of water damaged ceiling tiles and replace tiles
315388 02/22/2011 258686 4 013 M Determine cause of water damaged ceiling tiles and replace tiles
315393 02/22/2011 258696 5 009 M Determine cause of water damaged ceiling tiles and replace tiles
315399 02/22/2011 258710 6 004 M Repair lock on exterior door
315401 02/22/2011 258714 7 002C M Repair broken tile base along wall in bathroom
315398 02/22/2011 258706 8 004A M Repair damaged wall finish and base tile
315402 02/22/2011 258717 P 339 M Repair damaged rain gutter/downspout
315403 02/22/2011 258719 P 6146 M Repair rear door to close properly
315405 02/22/2011 258723 P 6148 M Repair rear door to close properly
315406 02/22/2011 258725 P 6399 M Repair rear door to close properly
315407 02/22/2011 258727 P 6399 M Determine cause of water damaged ceiling tiles and replace tiles
315408 02/22/2011 258729 P 6400 M Repair rear door to close properly
315409 02/22/2011 258731 P 9618 M Repair emergency lighting at front door
315410 02/22/2011 258733 P 9620 M Repair emergency lighting X2
315412 02/22/2011 258738 P 9621 M Repair emergency lighting at front door
315414 02/22/2011 258743 P 9622 M Repair emergency lighting at rear door
315154 02/22/2011 258187 1 004 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
315155 02/22/2011 258190 1 004 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet and remove 13A extension cord
308279 02/22/2011 242954 1 004 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
315145 02/22/2011 258168 1 021 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
315394 02/22/2011 258698 5 004 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
315386 02/22/2011 258682 1 009B MS Provide current inspection tag for fire extinguisher
315391 02/22/2011 258692 3 005A MS Provide current inspection tag for fire extinguisher
308297 02/22/2011 242988 6 001 OS Prohibit electrical cord from running across floor at entrance door
308285 09/30/2010 242965 2 012 M Determine cause of water damaged ceiling tiles and replace tiles
308338 09/30/2010 243076 P 289 M Adjust steps to make risers equal
200547 09/30/2010 25510 P 3543 M Adjust steps to make risers equal
308295 09/30/2010 242986 5 006 O Prohibit plugging microwave oven and coffee maker into surge protector - plug directly into permanent electrical outlet
308298 09/30/2010 242993 6 001 O Eliminate 13 amp at extension cord at sink or replace with minimum 15A cord
308300 09/30/2010 242997 6 001 O Prohibit plugging surge protector into extension cord
308305 09/30/2010 243007 6 002 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
308282 09/30/2010 242959 P 6147 O Relocate bookcase ro provide clear access to electrical panel
308329 09/30/2010 243057 P 0000 C Provide impervious wall finish for minimum six foot height in all portable bathrooms
308286 09/30/2010 242967 2 012 MS Provide current inspection tag for fire extinguisher
308281 09/30/2010 242956 1 023 OS Remove storage from mechanical room
308325 09/30/2010 243050 10 110 OS Remove storage (tables) from mechanical room
308287 09/30/2010 242969 2 016 OS Remove storage from mechanical room
308290 09/30/2010 242975 4 012 OS Remove storage from mechanical room
247881 04/26/2010 115545 5 009 M Relocate illuminated exit sign at center of hallway to be above 5-002 (1C) classroom door
308319 04/26/2010 243037 8 008 M Replace damaged fire extinguisher bracket to allow extinguisher to hang on wall
247878 04/26/2010 115539 8 009 M Relocate illuminated exit sign at center of hallway to be above 8-002 (4C) classroom door
308324 04/26/2010 243047 9 003 M Repair corridor door to close properly
308336 04/26/2010 243072 P 289 M Repair emergency lighting
308309 04/26/2010 243018 P 31 M Repair emergency lighting
308331 04/26/2010 243061 P 9619 M Repair emergency lighting at rear door
308333 04/26/2010 243065 P 9620 M Repair both front and rear entrance doors to close properly
308334 04/26/2010 243069 P 9621 M Repair emergency lighting
308288 04/26/2010 242971 2 018 O Replace burned out bulbs in light fixture
308289 04/26/2010 242973 2 019 O Replace burned out bulbs in light fixtures
308291 04/26/2010 242978 4 012 O Replace burned out bulbs in light fixtures
308301 04/26/2010 243000 6 001 O Eliminate 13 amp extension cord powering recorder
308308 04/26/2010 243016 P 31 O Prohibit plugging microwave oven and coffee maker into surge protector - plug directly into permanent electrical outlet
200488 04/26/2010 25442 1 012 C Make exterior walkway level with interior floor (computer lab)
308306 04/26/2010 243010 6 008 MS Provide current inspection tag for fire extinguisher
308284 04/26/2010 242962 P 6146 OS Maintain clear aisle to rear exit door (minimum 3' clearance)
276302 01/27/2010 174360 11 011 M Replace missing latch hardware for fixed door leaf in mechanical room
276297 01/30/2009 174349 1 020 M Provide additional outlets to eliminate use of excessive extension cords
200492 01/30/2009 57233 1 8088 M Provide correct building numbers on site map of fire annunciator panel
276260 01/30/2009 174265 10 011 M Adjust door to latch properly
286046 01/30/2009 195236 12 005 M Determine cause of water damaged ceiling tiles and replace tiles
286051 01/30/2009 195248 2 001 M Secure loose handrail on stage ramp
286050 01/30/2009 195246 2 005 M Perform kitchen hood cleaning and provide current tag stating date it was cleaned
276293 01/30/2009 174340 4 008 M Replace missing sign indicating "emergency escape window"
247874 01/30/2009 115531 7 008 M Replace broken latch hardware for fixed leaf for door in mechanical room
286053 01/30/2009 195252 P 289 M Determine cause of water damaged ceiling tiles and replace tiles
286054 01/30/2009 195254 P 289 M Repair stair door to close properly
286055 01/30/2009 195256 P 3543 M Determine cause of water damaged ceiling tiles and replace tiles
276311 01/30/2009 174381 P 3543 M Adjust stair door to latch properly
286061 01/30/2009 195270 P 6146 M Repair rear door to close properly
286060 01/30/2009 195267 P 9622 M Repair emergency lighting @ rear door
286058 01/30/2009 195261 P 9619 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
286059 01/30/2009 195265 P 9620 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
286066 01/30/2009 195280 00 0000 C Provide exterior signage indicating property address
200495 01/30/2009 25450 10 009 C Provide partitions between urinals (6-bathroom)
200500 01/30/2009 25452 11 009 C Provide partitions between urinals (7-bathroom)
286049 01/30/2009 195242 2 006 F Provide heat detector in room with clothes dryer
286048 01/30/2009 195240 2 007 MS Provide current inspection tag for fire extinguisher
200478 01/30/2009 25383 00 0000 CS Provide Knox box to allow fire department access
286047 01/30/2009 195238 12 002 CS Provide fire extinguisher in classroom (sign outside states "Fire Extinguisher Inside")
286045 01/30/2009 195234 1 014 FS Provide certification that fire alarm system has been tested and that all items noted to be deficient on report dated 09-16-08 have been corrected. Send copy of repair report to Boca Raton Fire Rescue.
276298 09/18/2008 174351 2 017 M Replace burned out bulbs in flammable storage room
265118 09/18/2008 149887 5 008 M Repair door hardware - lock sticks
286056 09/18/2008 195259 P 0000 M Raise exterior electrical boxes so bottom of boxes is at least 8 inches above grade (Not applicable per Tom Hogarth, 01/09)
276310 09/18/2008 174379 P 289 M Secure loose stair bottom
286062 09/18/2008 195273 P 6149 M Repair rear door to close properly
200476 09/18/2008 25441 00 0000 C Provide verification that foundation system is adequate for metal storage building adjacent to Bldg. 2
247836 03/10/2008 115454 12 002 M Repair light in exit signs
276299 03/10/2008 174353 2 018 M Replace missing latch hardware for fixed door leaf in mechanical room
265119 03/10/2008 149889 3 007 M Modify thumblatch so it cannot be locked from inside bathroom
276308 03/10/2008 174373 7 003 M Remove downspout on grass outside classroom exterior door
247834 03/10/2008 115450 P 339 M Adjust steps to make risers equal
276295 03/10/2008 174345 1 020 O Prohibit plugging surge protector into surge protector
276296 03/10/2008 174347 1 020 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
276262 03/10/2008 174269 11 004 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
276276 03/10/2008 174291 5 001 O Eliminate (6) plug electrical outlet adaptor adjacent to closet or replace with a surge protector
276305 03/10/2008 174369 5 002 O Secure cover strip for electrical cords to flooring - to eliminate slipping
276271 03/10/2008 174285 6 004 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
276265 03/10/2008 174277 7 001 O Prohibit plugging surge protector into surge protector behind teacher's desk
276306 03/10/2008 174371 7 003 O Secure cover strip for electrical cords to flooring - to eliminate slipping
276268 03/10/2008 174280 7 004 O Remove and prohibit combustible residential arm chair
276309 03/10/2008 174377 P 289 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
276312 03/10/2008 174383 P 3543 O Provide clear access to electrical panel
276304 03/10/2008 174362 P 6149 O Remove storage/ plastic bags behind cabinets adjacent to window and under computer stations to reduce excessive storage / fuel load
276314 03/10/2008 174387 P 9617 O Remove and prohibit use of flammable table cloths and vinyl sheet around teacher's desk
276316 03/10/2008 174391 P 9619 O Relocate storage cabinet to provide clear access to electrical panel
265095 03/10/2008 149841 3 005A MS Provide current inspection tag for fire extinguisher
276256 03/10/2008 174257 1 023 OS Remove storage from mechanical room
276261 03/10/2008 174267 11 004 OS Relocate table and chairs to maintain a minimum 3 ft clear aisle to exterior door
276277 03/10/2008 174302 12 001 OS Remove and prohibit use of toaster oven
276278 03/10/2008 174304 12 004 OS Remove and prohibit use of hot plate
276257 03/10/2008 174259 2 016 OS Remove storage from mechanical room
265093 03/10/2008 149837 2 018 OS Remove storage from mechanical room
276258 03/10/2008 174261 2 019 OS Remove storage from electrical room
276294 03/10/2008 174343 3 004 OS Relocate cart to keep area clear at emergency escape window
276264 03/10/2008 174273 8 006 OS Remove and prohibit use of toaster
276263 03/10/2008 174271 9 003 OS Relocate table and chairs to maintain clear aisle to exterior door
276313 03/10/2008 174385 P 9618 OS Rearrange furniture to maintain clear path to back door
276319 03/10/2008 174398 P 9621 OS Rearrange furniture to maintain clear path to back door
276321 03/10/2008 174400 P 9621 OS Prohibit running electrical cord across path to back door
276259 03/10/2008 174263 2 013 FS Secure hanging heat detector in dry storage room
200537 03/05/2008 25455 P 289 M Modify existing foundations and anchorage to comply with engineering requirements
200554 03/05/2008 25472 P 339 M Modify existing foundations and anchorage to comply with engineering requirements
265101 11/09/2007 149853 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
247860 11/09/2007 115503 10 001 M Repair light in exit signs
247861 11/09/2007 115505 10 002 M Repair light in exit signs
247862 11/09/2007 115507 10 003 M Repair light in exit signs
265106 11/09/2007 149863 11 001 M Repair light in exit signs
265107 11/09/2007 149865 11 002 M Repair light in exit signs
247859 11/09/2007 115501 11 004 M Repair light in exit signs
247880 11/09/2007 115543 6 009 M Relocate illuminated exit sign at center of hallway to be above 6-002 (2C) classroom door
247879 11/09/2007 115541 7 009 M Relocate illuminated exit sign at center of hallway to be above 7-002 (3C) classroom door
265108 11/09/2007 149867 8 001 M Secure loose faucet to sink
200541 11/09/2007 25509 P 289 M Adjust steps to make risers equal
265299 11/09/2007 150282 P 9620 M Repair door hardware - Lock sticks on front door
200479 11/09/2007 25454 00 9500 C Provide covered walkway to portables
247870 11/09/2007 115523 3 005A C Make exterior walkway level with interior floor
200542 11/09/2007 25456 P 289 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
200539 11/09/2007 25459 P 289 C Provide balusters on stair landing guardrail at six inches apart
200540 11/09/2007 25460 P 289 C Provide guardrails at stair landing at a minimum 42 inches high
247842 11/09/2007 115467 P 3543 C Provide non-slip surface for ramp
247877 12/01/2006 115537 00 9599 M Secure loose chain link fencing to top rail and plumb bent post in play area behind Bldg. 12
247851 12/01/2006 115485 11 001 M Replace missing light fixture outside exterior door
247855 12/01/2006 115493 11 011 M Repair or replace rusted door
200503 12/01/2006 25506 12 002 M Repair or replace bubbled vinyl flooring adjacent to 12-003
264875 12/01/2006 149350 12 005 M Repair light in exit sign
200509 12/01/2006 25446 3 001 M Fill in maximum occupancy sign to indicate actual allowable occupancy (max. occupancy = 49)
247867 12/01/2006 115517 3 008A M Adjust door to latch properly
200513 12/01/2006 25448 4 001 M Fill in maximum occupancy sign to indicate actual allowable occupancy (max. occupancy = 49)
247826 12/01/2006 115434 6 003A M Repair exhaust fan in bathroom
265102 12/01/2006 149855 6 004A M Repair exhaust fan in bathroom
247827 12/01/2006 115436 6 009 M Determine cause of water damaged ceiling tiles and replace tiles
247872 12/01/2006 115527 8 005 M Replace broken cover plate for light switch
247850 12/01/2006 115483 9 002A M Repair exhaust fan in bathroom
265110 12/01/2006 149871 9 003 M Replace broken cover for exposed electrical outlet adjacent to TV cart
247845 12/01/2006 115473 9 004A M Repair exhaust fan in bathroom
247833 12/01/2006 115448 P 339 M Repair exhaust fan in bathroom
247843 12/01/2006 115469 P 3543 M Repair emergency lighting adjacent to ramp door
200546 12/01/2006 25511 P 3543 M Adjust concrete landing at bottom of steps so width of landing is same as width of stair treads
264886 12/01/2006 149372 P 6147 M Rotate drinking spout to eliminate spraying on floor
247865 12/01/2006 115513 1 015 O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet (clinic)
264883 12/01/2006 149366 1 020 O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
265105 12/01/2006 149861 10 001 O Remove and prohibit combustible beanbag chairs (x2)
247876 12/01/2006 115535 5 001 O Eliminate 13A extension cord for projector or replace with minimum 15A cord
265115 12/01/2006 149881 6 001 O Remove mirror adjacent to corridor door or provide mirror made of tempered glass, safety glass, or stainless steel
247839 12/01/2006 115461 P 289 O Eliminate 13A extension cord or replace with minimum 15A cord
265113 12/01/2006 149877 P 339 O Provide certification that carpet meets flame spread requirement or remove carpet
265114 12/01/2006 149879 P 339 O Remove and prohibit combustible residential chair
264882 12/01/2006 149364 P 3543 O Prohibit plugging one surge protector into another under computer station, plug each surge protector directly into wall outlet
264887 12/01/2006 149374 P 6147 O Relocate metal cabinet to provide clear access to electrical panel
264885 12/01/2006 149370 P 6149 O Relocate metal cabinet to provide clear access to electrical panel
265300 12/01/2006 150284 P 9619 O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
247883 12/01/2006 115549 10 012 C Provide illuminated exit sign above 10-002 (6C) classroom door
247884 12/01/2006 115551 11 012 C Provide illuminated exit sign above 11-002 (7C) classroom door
200553 12/01/2006 25471 P 31 C Provide handrails on each side of stair
264880 12/01/2006 149360 1 023 MS Replace missing fire extinguisher
265099 12/01/2006 149849 11 002 MS Replace missing fire extinguisher
265103 12/01/2006 149857 11 011 MS Replace missing fire extinguisher in mechanical room
265100 12/01/2006 149851 2 004 MS Replace missing fire extinguisher
265090 12/01/2006 149831 2 012 MS Provide current inspection tag for fire extinguisher
265091 12/01/2006 149833 2 020 MS Provide current inspection tag for fire extinguisher
265116 12/01/2006 149883 6 007 MS Close hatch on ceiling
265096 12/01/2006 149843 7 008 MS Recharge fire extinguisher
265097 12/01/2006 149845 8 008 MS Recharge fire extinguisher
264881 12/01/2006 149362 P 3543 MS Recharge fire extinguisher
264884 12/01/2006 149368 P 6149 MS Recharge fire extinguisher
265297 12/01/2006 150278 P 9618 MS Recharge fire extinguisher
265301 12/01/2006 150286 00 0000 OS Prohibit storage of gas can in metal storage building adjacent to Bldg. 2
265303 12/01/2006 150290 00 0000 OS Prohibit storage of gas powered pressure cleaner in metal Bldg. behind P-8A
264879 12/01/2006 149358 1 023 OS Remove storage from mechanical room
265104 12/01/2006 149859 10 005 OS Remove storage from electrical room
265098 12/01/2006 149847 11 002 OS Remove and prohibit use of toaster oven
264877 12/01/2006 149354 12 003 OS Remove and prohibit use of toaster oven
264878 12/01/2006 149356 12 004 OS Remove and prohibit use of toaster oven
265092 12/01/2006 149835 2 016 OS Remove storage from mechanical room
265120 12/01/2006 149891 3 004 OS Relocate rolling cart blocking clear access to emergency escape window and blocking view of "Emergency Exit" sign at window
265094 12/01/2006 149839 4 012 OS Remove storage from mechanical room
247875 12/01/2006 115533 5 001 OS Relocate storage cart and desk to maintain clear path to exterior door
265117 12/01/2006 149885 6 009 OS Remove carts and chairs from hallway section in corridor
265111 12/01/2006 149873 7 001 OS Relocate table adjacent to corridor door to maintain clear aisle to exit
265112 12/01/2006 149875 7 009 OS Remove tables from hallway section in corridor
265109 12/01/2006 149869 9 003 OS Arrange desks to maintain a minimum 3 ft clear aisle to both doors
264876 12/01/2006 149352 P 6149 OS Remove and prohibit use of toaster oven
265296 12/01/2006 150276 P 9617 OS Remove and prohibit use of toaster oven
265302 12/01/2006 150288 00 0000 FS Complete installation of heat detector in metal Bldg. behind P-8A
247846 12/01/2006 115475 9 005 FS Secure heat detector to ceiling in custodial room
200548 04/25/2006 25463 P 31 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
200545 04/25/2006 25462 P 3543 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
247863 04/13/2006 115509 10 004 M Repair light in exit signs
247847 04/13/2006 115477 10 010 M Secure loose cover for exhaust fan in custodial room
247857 04/13/2006 115497 11 001 M Repair light in exit signs
247858 04/13/2006 115499 11 002 M Repair light in exit signs
247856 04/13/2006 115495 11 011 M Adjust door to latch properly
247864 04/13/2006 115511 2 017 M Replace burned bulbs in light fixtures (flammable storage room)
247869 04/13/2006 115521 3 0000 M Remove inappropriate occupancy sign from vestibule area between art and music rooms
247835 04/13/2006 115452 3 001 M Repair light in exit signs (music lab)
247852 04/13/2006 115487 P 9617 M Secure loose exhaust fan grille in bathroom
247831 04/13/2006 115444 1 012 O Prohibit plugging one surge protector into another at computer stations
247837 04/13/2006 115456 12 002 O Prohibit plugging one surge protector into another at computer stations
247832 04/13/2006 115446 P 31 O Prohibit plugging one surge protector into another under teacher's desk
247844 04/13/2006 115471 P 3543 O Prohibit plugging surge protector into an extension cord. Plug surge protector directly into wall outlet
247853 04/13/2006 115489 P 9617 O Prohibit plugging one surge protector into another at teacher's desk
247840 04/13/2006 115463 P 9622 O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
247830 04/13/2006 115442 1 009B MS Provide current inspection tag for fire extinguisher
247828 04/13/2006 115438 6 007 MS Close hatch on ceiling
247849 04/13/2006 115481 9 002 MS Recharge fire extinguisher
247848 04/13/2006 115479 10 005 OS Remove storage from electrical room
247866 04/13/2006 115515 12 004 OS Prohibit running electrical cord through door into vestibule area
247871 04/13/2006 115525 8 004 OS Arrange desks to maintain a minimum 3 ft clear aisle to exterior door
247841 04/13/2006 115465 P 9619 OS Arrange furniture to maintain a minimum 3 ft clear aisle to back door
234362 04/13/2006 91502 P 9622 OS Relocate storage away from exit door
247838 04/13/2006 115458 2 015 FS Provide heat detector in storage room
247873 04/13/2006 115529 8 005 FS Secure heat detector to ceiling
200477 01/19/2006 25412 00 0000 M Provide verification that all student occupied spaces have emergency lights and all are operable
200475 01/19/2006 25480 00 0000 M Provide hurricane anchors for storage container adjacent to Building 2
200514 01/19/2006 25385 4 001 C Provide illuminated exit sign at door into 4-010 or provide second exit door directly to the exterior (media center)
234352 01/19/2006 91486 10 0000 MS Provide current inspection tag for all fire extinguishers
234353 01/19/2006 91487 11 0000 MS Provide current inspection tag for all fire extinguishers
234354 01/19/2006 91488 12 0000 MS Provide current inspection tag for all fire extinguishers
234355 01/19/2006 91489 3 004 MS Provide current inspection tag for fire extinguisher
234356 01/19/2006 91490 3 004B MS Provide current inspection tag for fire extinguisher
234348 01/19/2006 91482 5 0000 MS Provide current inspection tag for all fire extinguishers
234349 01/19/2006 91483 6 0000 MS Provide current inspection tag for all fire extinguishers
200487 01/19/2006 57224 1 012 CS Provide sufficient wiring and electrical outlets to eliminate the need for multiple extension cords for electrical and electronic equipment
200505 01/19/2006 25393 12 003 CS Provide door to the exterior or provide rated corridor within building and secondary egress window (kindergarten)
200480 03/14/2005 25481 00 9599 M Grade soil area adjacent to P-4 where portable was
200481 03/14/2005 57214 00 9599 M Replace missing boards on top of lift station cover
200491 03/14/2005 57232 1 017 M Pad and mark corners of television shelf unit which are lower than 6?8?
200493 03/14/2005 57235 10 0000 M Repair lights in all exit signs
200498 03/14/2005 63213 11 001 M Repair roof leaks
200508 03/14/2005 57242 2 001 M Secure loose handrail along ramp
200512 03/14/2005 57247 3 8088 M Paint yellow warning strip on corners and edges of raised concrete slab under water fountain between bathrooms
200526 03/14/2005 25493 6 009 M Repair or replace bubbled vinyl flooring adjacent to 6-005 (corridor)
200529 03/14/2005 57269 8 0000 M Determine cause of water damaged ceiling tiles throughout Building 8 and replace tiles
200538 03/14/2005 57276 P 289 M Clean all air conditioning vents
234367 03/14/2005 91512 P 289 M Repair or replace badly deteriorated stairs
234368 03/14/2005 91514 P 289 M Repair ramp door to open and close properly
200559 03/14/2005 25514 P 339 M Adjust steps to make risers equal
200562 03/14/2005 25513 P 339 M Adjust stair landing to be level with interior floor
200555 03/14/2005 25515 P 339 M Repair or replace deteriorated wood siding
234360 03/14/2005 91498 P 9617 M Eliminate multiple extension cords
200486 03/14/2005 57225 1 012 O Eliminate multiple extension cords
200489 03/14/2005 57229 1 016 O Eliminate household extension cord or replace with minimum 15A and grounded cord to television
234358 03/14/2005 91493 3 005A O Prohibit student access in coach's office or arrange storage in an orderly manner and provide clear access to exit
200515 03/14/2005 63212 4 004 O Prohibit use of candles
200517 03/14/2005 57260 4 013 O Eliminate multiple extension cords
200536 03/14/2005 57275 P 289 O Eliminate multiple extension cords
200511 03/14/2005 25447 3 007 C Provide tempered glass, safety glass, or stainless steel for mirrors (bathroom)
200543 03/14/2005 57274 P 289 C Provide clear access to electrical panel
200549 03/14/2005 25470 P 31 C Provide balusters on stair landing guardrail at six inches apart
200550 03/14/2005 25467 P 31 C Provide balusters at six inches apart on ramp landing guardrail
200551 03/14/2005 25466 P 31 C Provide guardrails at ramp landing at a minimum 42 inches high
200552 03/14/2005 25464 P 31 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
200556 03/14/2005 25478 P 339 C Provide balusters on stair landing guardrail at six inches apart
200557 03/14/2005 25476 P 339 C Provide balusters at six inches apart on ramp landing guardrail
200558 03/14/2005 25475 P 339 C Provide guardrails at ramp landing at a minimum 42 inches high
200560 03/14/2005 25474 P 339 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
200561 03/14/2005 25479 P 339 C Provide handrails on each side of stair
234350 03/14/2005 91484 7 0000 MS Provide current inspection tag for all fire extinguishers
234351 03/14/2005 91485 9 0000 MS Provide current inspection tag for all fire extinguishers
200483 03/14/2005 57248 00 9699 OS Keep gate to lake property closed and locked at all times other than parent drop off or pickup
200510 03/14/2005 57246 3 005A OS Prohibit storage of flammable spray paints and lubricants (under sink)
200516 03/14/2005 57258 4 012 OS Remove storage from mechanical room
200518 03/14/2005 57261 4 013 OS Prohibit electrical extension cords from running through ceiling
234366 03/14/2005 91509 5 003 OS Maintain clear aisle to exit
234361 03/14/2005 91501 P 9618 OS Relocate storage away from exit door
200482 03/14/2005 57215 00 9698 CS Provide gate locks to allow fire department access
200519 03/14/2005 57259 4 013 CS Provide sufficient wiring and electrical outlets to eliminate the need for multiple extension cords for electrical and electronic equipment
200544 03/14/2005 25461 P 289 CS Provide proper grounding for portable unit (land on panel)
200474 03/14/2005 25394 00 0000 FS Provide heat detector in storage container adjacent to Building 2
200485 03/14/2005 57222 1 009A FS Provide heat detector in storage room
200490 03/14/2005 57230 1 016 FS Install smoke detector @ fire alarm panel
200494 03/14/2005 25405 10 006A FS Provide heat detector in storage closet in teachers' planning room (Building 6)
200496 03/14/2005 25406 10 011 FS Relocate heat detector to peak point of ceiling in mechanical room
200499 03/14/2005 25407 11 006A FS Provide heat detector in storage closet in teachers' planning room (Building 7)
200501 03/14/2005 25408 11 011 FS Relocate heat detector to peak point of ceiling in mechanical room
200504 03/14/2005 25409 12 002B FS Relocate heat detector to high point of ceiling (kindergarten, closet)
200506 03/14/2005 25410 12 007 FS Relocate heat detector to peak point of ceiling of mechanical room (K-Building)
200507 03/14/2005 25411 14 001 FS Provide heat detector in storage room (K-Storage Building)
200520 03/14/2005 25395 5 006A FS Provide heat detector in storage closet in teachers' planning room (Building 1)
200521 03/14/2005 25396 5 008 FS Relocate heat detector to peak point of ceiling in mechanical room (Building 1)
200523 03/14/2005 25397 6 006A FS Provide heat detector in storage closet in teachers' planning room (Building 2)
200524 03/14/2005 25398 6 008 FS Relocate heat detector to peak point of ceiling of mechanical room (Building 2)
200527 03/14/2005 25399 7 006A FS Provide heat detector in storage closet in teachers' planning room (Building 3)
200530 03/14/2005 25401 8 006A FS Provide heat detector in storage closet in teachers' planning room (Building 4)
200531 03/14/2005 25402 8 008 FS Relocate heat detector to peak point of ceiling in mechanical room (Building 4)
200533 03/14/2005 25403 9 006A FS Provide heat detector in storage closet in teachers' planning room (Building 5)
200534 03/14/2005 25404 9 008 FS Relocate heat detector to peak point of ceiling in mechanical room (Building 5)