TIMBER TRACE ELEMENTARY
 
TIMBER TRACE ELEMENTARY
5200 117TH CT. N.
PALM BEACH GARDENS, 33418
FISH Drill Down
 Campus Info.
 Buildings:11 Rooms:248
 Portables:25
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
409185 02/19/2018 462954 3 304 O Remove and prohibit hanging paper and decorations from ceiling
409184 02/19/2018 462952 3 305 O Remove and prohibit hanging paper and decorations (pom-poms) from ceiling
409183 02/19/2018 462950 3 306 O Remove and prohibit hanging paper and decorations from ceiling
409192 02/19/2018 462969 3 307 O Remove and prohibit hanging paper and decorations from ceiling
409191 02/19/2018 462967 3 308 O Remove and prohibit hanging paper and decorations from ceiling
409190 02/19/2018 462965 3 309 O Remove and prohibit hanging paper and decorations (pom-poms) from ceiling
409189 02/19/2018 462959 3 310 O Remove and prohibit flammable curtains covering shelves, or treat fabric with a flame retardant
409197 02/19/2018 462979 4 401 O Remove and prohibit flammable curtains above cabinets or treat fabric with a flame retardant
409198 02/19/2018 462982 5 506 O Remove and prohibit hanging paper and decorations from ceiling
409207 02/19/2018 462999 5 516 OS Remove storage from electrical room
409276 02/19/2018 463145 7 190 OS Remove storage from mechanical room
409209 02/15/2018 463001 00 0000 M Determine cause of hole in ground inside fence enclosure behind Portable 16 and fill hole (possible rodent shelter)
409205 02/15/2018 462995 00 0000 M Repair gate on chain link fence enclosure on electric transformer south of Building 7 to close and replace padlock
409200 02/15/2018 462984 00 0000 M Trim tree branches overhanging roof of Building 5 in courtyard
409172 02/15/2018 462928 1 116 M Anchor loose communications junction box to wall behind photocopy machine
409173 02/15/2018 462930 1 118 M Re-connect dryer duct to clothes dryer vent pipe
409178 02/15/2018 462940 2 203A M Secure loose toilet seat
409180 02/15/2018 462944 2 205 M Provide a mounting bracket and mount fire extinguisher at maximum five feet above floor
409204 02/15/2018 462993 5 119 M Repair exterior exit door to close properly
409203 02/15/2018 462990 5 501B M Replace missing vent cover in ceiling
409206 02/15/2018 462997 5 517 M Determine cause of water damaged ceiling tiles and replace tiles
409272 02/15/2018 463138 8 819 M Replace missing ceiling tiles
409279 02/15/2018 463152 9 0000 M Remove vegetation growing from gutter on west side of Building 9
409277 02/15/2018 463147 9 904 M Repair emergency lighting in generator room
409278 02/15/2018 463149 9 904 M Provide current emergency generator and lighting certificate that all student occupied spaces have emergency lights and all are operable
409232 02/15/2018 463051 P 0000 M Replace missing caulking in covered walkway column next to P-29
409221 02/15/2018 463027 P 9553 M Repair emergency lighting at rear door
409217 02/15/2018 463021 P 9554 M Repair emergency lighting at both front and rear doors
409216 02/15/2018 463019 P 9555 M Determine cause of water damaged ceiling tiles at rear door and replace tiles
409214 02/15/2018 463015 P 9556 M Repair emergency lighting at both front and rear doors
409215 02/15/2018 463017 P 9556 M Repair rear door to close properly
409251 02/15/2018 463096 P 9713 M Repair emergency lighting at front door
409249 02/15/2018 463087 P 9714 M Repair emergency lighting at front and rear doors
409244 02/15/2018 463077 P 9715 M Repair emergency lighting at rear door
409235 02/15/2018 463060 P 9717 M Repair emergency lighting at both front and rear doors
409239 02/15/2018 463063 P 9717 M Secure sink to wall in bathroom and re-caulk to provide impervious wall
409234 02/15/2018 463056 P 9718 M Repair emergency lighting at rear door
409227 02/15/2018 463043 P 9719 M Repair emergency lighting at front door
409229 02/15/2018 463045 P 9719 M Replace ceiling tiles back into ceiling grid
409254 02/15/2018 463100 P 9720 M Eliminate nesting ants or insects at rear window
409255 02/15/2018 463104 P 9720 M Repair emergency lighting at rear door
409257 02/15/2018 463107 P 9721 M Repair emergency lighting at both front and rear doors
409259 02/15/2018 463110 P 9722 M Repair emergency lighting at both front and rear door
409260 02/15/2018 463113 P 9724 M Repair emergency lighting at rear door
409263 02/15/2018 463116 P 9724 M Repair loose vinyl base outside bathroom wall
409264 02/15/2018 463121 P 9725 M Repair emergency lighting at rear door
409265 02/15/2018 463123 P 9726 M Repair emergency lighting at both front and rear doors
409266 02/15/2018 463125 P 9727 M Repair front door to close properly
409267 02/15/2018 463128 P 9727 M Repair emergency lighting at rear door
409223 02/15/2018 463034 P 9749 M Repair emergency lighting at rear door
409224 02/15/2018 463037 P 9750 M Repair emergency lighting at rear door
409225 02/15/2018 463039 P 9751 M Repair emergency lighting at rear door
409226 02/15/2018 463041 P 9752 M Repair emergency lighting at rear door
409174 02/15/2018 462932 1 118B O Eliminate white, multi plug extension cord located inside custodial office
409175 02/15/2018 462934 2 201 O Remove and prohibit hanging paper and decorations from ceiling
409176 02/15/2018 462936 2 202 O Remove and prohibit hanging paper and decorations from ceiling
409177 02/15/2018 462938 2 203 O Remove and prohibit hanging paper and decorations from ceiling
409179 02/15/2018 462942 2 203 O Remove and prohibit flammable curtains on cabinets, or treat with a flame retardant
409182 02/15/2018 462948 2 204 O Remove and prohibit hanging paper and decorations from ceiling
409186 02/15/2018 462956 3 303 O Remove and prohibit flammable curtains covering front of tables next to windows
409195 02/15/2018 462972 4 401 O Eliminate brown, light duty, multi plug extension cord behind teacher's desk
409274 02/15/2018 463141 7 704 O Prohibit use of multi-outlet extension cord, use surge protector instead
409271 02/15/2018 463132 8 809 O Clean area behind washer and dryer to prevent fire hazard
409218 02/15/2018 463025 P 9553 O Remove storage to provide clear access to electrical panel
409181 02/15/2018 462946 2 205 OS Remove storage from electrical room
263458 02/15/2018 146437 1 0000 N/A No violations observed
263459 02/15/2018 146438 2 0000 N/A No violations observed
263460 02/15/2018 146439 3 0000 N/A No violations observed
263461 02/15/2018 146440 4 0000 N/A No violations observed
263462 02/15/2018 146441 5 0000 N/A No violations observed
263463 02/15/2018 146442 6 0000 N/A No violations observed
263464 02/15/2018 146443 7 0000 N/A No violations observed
263465 02/15/2018 146444 8 0000 N/A No violations observed
263466 02/15/2018 146445 9 0000 N/A No violations observed
279508 02/15/2018 181198 P 9552 N/A No violations observed
263489 02/15/2018 146468 P 9553 N/A No violations observed
263488 02/15/2018 146467 P 9554 N/A No violations observed
263491 02/15/2018 146470 P 9555 N/A No violations observed
263490 02/15/2018 146469 P 9556 N/A No violations observed
268964 02/15/2018 158241 P 9712 N/A No violations observed
263469 02/15/2018 146448 P 9713 N/A No violations observed
263470 02/15/2018 146449 P 9714 N/A No violations observed
263471 02/15/2018 146450 P 9715 N/A No violations observed
263472 02/15/2018 146451 P 9716 N/A No violations observed
263473 02/15/2018 146452 P 9717 N/A No violations observed
263474 02/15/2018 146453 P 9718 N/A No violations observed
263475 02/15/2018 146454 P 9719 N/A No violations observed
263476 02/15/2018 146455 P 9720 N/A No violations observed
263477 02/15/2018 146456 P 9721 N/A No violations observed
263478 02/15/2018 146457 P 9722 N/A No violations observed
263479 02/15/2018 146458 P 9723 N/A No violations observed
263480 02/15/2018 146459 P 9724 N/A No violations observed
263481 02/15/2018 146460 P 9725 N/A No violations observed
263482 02/15/2018 146461 P 9726 N/A No violations observed
263483 02/15/2018 146462 P 9727 N/A No violations observed
263484 02/15/2018 146463 P 9749 N/A No violations observed
263486 02/15/2018 146465 P 9750 N/A No violations observed
263485 02/15/2018 146464 P 9751 N/A No violations observed
279544 02/15/2018 181270 P 9752 N/A No violations observed
409275 09/27/2017 463143 7 703 M Repair or replace non-working kiln
373748 09/27/2017 386289 P 0000 C Storm drainage from portables collects between portables and sidewalks. Storm water ends up draining under portables. Modify drainage to get storm water away from portables
395093 01/26/2017 432497 00 9599 M Repair or replace rusted frame for exit gate between Bldgs. 3 and 4
395094 01/26/2017 432502 00 9599 M Repair auto closer on exit gate between Bldgs. 3 and 4
395096 01/26/2017 432507 1 104 M Make necessary repairs to fire alarm system as indicated on report dated 11.24.15
395083 01/26/2017 432478 1 120 M Repair rusted hot water tank
395074 01/26/2017 432458 2 201A M Secure exhaust fan grille to ceiling in bathroom
395099 01/26/2017 432514 5 512 M Repair plumbing line to faucet - no water access
395076 01/26/2017 432463 7 703 M Repair exhaust fan at kiln
321621 01/26/2017 272198 8 813 M Change swing of north exit door to music room to swing in direction of egress - exiting through a closet is not an approved egress
360207 01/26/2017 356928 9 903 M Repair or replace rusted door
395118 01/26/2017 432553 P 9555 M Repair emergency lighting above front door
395122 01/26/2017 432562 P 9712 M Repair emergency lighting above front door
395123 01/26/2017 432564 P 9715 M Repair emergency lighting above front door
395106 01/26/2017 432528 P 9717 M Adjust front door to latch properly
395108 01/26/2017 432532 P 9720 M Repair emergency lighting above front door
395126 01/26/2017 432571 P 9723 M Re-anchor storage cabinet to wall facing the toilet to maintain clear access to graspable handrail
395124 01/26/2017 432566 P 9724 M Repair emergency lighting above front door
395125 01/26/2017 432568 P 9727 M Repair emergency lighting above front door
395119 01/26/2017 432555 P 9749 M Repair emergency lighting above front door
395120 01/26/2017 432557 P 9751 M Repair emergency lighting above front door
395116 01/26/2017 432548 P 9751 M Repair uneven concrete walkway outside back door
395117 01/26/2017 432550 P 9752 M Repair uneven concrete walkway outside back door
395121 01/26/2017 432559 P 9752 M Repair emergency lighting above front door
395065 01/26/2017 432439 3 302 O Remove and prohibit excessive flammable vinyl sheathing at teacher desk
395066 01/26/2017 432441 3 305 O Remove and prohibit paper on window blinds
395056 01/26/2017 432421 3 311 O Remove and prohibit paper on window blinds
395088 01/26/2017 432486 3 311 O Remove paper covering emergency escape window sign
395091 01/26/2017 432491 3 311 O Prohibit plugging surge protector into surge protector at computer stations - plug each surge protector directly into wall outlet
395061 01/26/2017 432430 3 312 O Remove and prohibit paper covering window in door
395055 01/26/2017 432417 4 401 O Remove and prohibit paper on window blinds
395100 01/26/2017 432516 5 117 O Remove and prohibit paper on window blinds
395095 01/26/2017 432504 5 502 O Remove and prohibit paper on window blinds
395098 01/26/2017 432511 5 511 O Remove and prohibit paper on window blinds
395115 01/26/2017 432546 P 9553 O Remove and prohibit excessive flammable vinyl sheathing on bulletin board adjacent to teacher desk and adjacent to bathroom (X2)
395102 01/26/2017 432520 P 9713 O Remove and prohibit paper covering window in door
395103 01/26/2017 432522 P 9714 O Remove and prohibit paper on window blinds
395104 01/26/2017 432524 P 9714 O Remove and prohibit combustible curtains on window
395105 01/26/2017 432526 P 9716 O Eliminate string lines running across room
395107 01/26/2017 432530 P 9717 O Remove paper covering electrical outlet under writing board
395109 01/26/2017 432534 P 9720 O Remove and prohibit excessive flammable vinyl sheathing at teacher desk, under writing board and on cabinet adjacent to back door
395111 01/26/2017 432538 P 9725 O Remove red paper covering electrical outlet adjacent to back door
395112 01/26/2017 432540 P 9725 O Relocate shelf unit to provide clear access to electrical panel
395113 01/26/2017 432542 P 9752 O Remove and prohibit paper on window blinds
395080 01/26/2017 432474 8 810 MS Provide current inspection tag for fire extinguisher in staff dining room
395077 01/26/2017 432465 9 903 MS Repair door lock hardware to work properly - hard to open
395097 01/26/2017 432509 5 110A OS Remove storage unit from bathroom
395064 01/26/2017 432437 6 604 OS Remove and prohibit use of hot plate - adjacent to mircrowave
395079 01/26/2017 432470 7 705 OS Remove storage from mechanical room - also labeled 7-190
395101 01/26/2017 432518 P 9712 OS Remove and prohibit use of toaster oven
395110 01/26/2017 432536 P 9724 OS Remove storage from bathroom
395114 01/26/2017 432544 P 9752 OS Relocate bench outside back door to maintain safe egress
381499 09/22/2016 403166 1 120 M Provide current state inspection tag for hot water heater - NA verified by Mark
381508 02/24/2016 403185 00 0000 M Remove tree growing in fence enclosure south of 5-119
381536 02/24/2016 403244 1 104 M Repair deficiencies as noted on fire alarm report
381535 02/24/2016 403242 1 106 M Repair door to latch properly
381486 02/24/2016 403137 3 0000 M Clean rain gutters and downspouts
381488 02/24/2016 403142 3 311 M Repair emergency escape window to open properly
381485 02/24/2016 403135 3 313 M Replace missing screws in electrical panel HD, HD1, LD1, LD
381487 02/24/2016 403139 3 8087 M Repair auto closer on exterior gate adjacent to 3-306
381502 02/24/2016 403172 4 402 M Repair emergency escape window to open properly
381501 02/24/2016 403170 5 501 M Provide cover on exposed electrical junction box in cabinet below emergency window
381503 02/24/2016 403174 5 506 M Repair emergency escape window to open properly
381513 02/24/2016 403195 5 510A M Secure loose grabrail in bathroom
381511 02/24/2016 403191 5 513 M Repair deteriorated wall finish
381512 02/24/2016 403193 5 513 M Adjust door closer to control speed of closing door
381510 02/24/2016 403189 5 516 M Replace missing screws in electrical panel HC
381509 02/24/2016 403187 5 517 M Adjust door closer to control speed of closing door
381494 02/24/2016 403155 6 608 M Replace missing base on north wall under clock
381505 02/24/2016 403179 6 614 M Determine cause of water damaged ceiling tiles and replace tiles
381492 02/24/2016 403151 6 8087 M Remove tree growing from exterior column adjacent to 6-607
381500 02/24/2016 403168 7 190 M Disable thumb latch for deadbolt
381533 02/24/2016 403237 8 806 M Adjust door closer to control speed of closing door
381506 02/24/2016 403181 8 814 M Replace missing ceiling tiles
381507 02/24/2016 403183 8 814 M Repair light fixture
381482 02/24/2016 403129 8 815 M Replace missing screws in electrical panel LA1
381483 02/24/2016 403131 8 815 M Mount fire extinguisher at maximum five feet above floor
381532 02/24/2016 403235 P 0000 M Replace missing in ground drain covers adjacent to P-21, P-22, P-23, P-26
381517 02/24/2016 403203 P 8087 M Fill gaps in concrete walk at P-13, P-15 and P-3, P-5 north
381531 02/24/2016 403233 P 9552 M Repair emergency lighting (x2)
381529 02/24/2016 403229 P 9553 M Determine cause of water damaged ceiling tiles and replace tiles
381515 02/24/2016 403199 P 9715 M Repair south door to latch properly
381518 02/24/2016 403205 P 9716 M Repair south door to latch properly
381525 02/24/2016 403220 P 9719 M Replace missing sign or stencil indicating impervious wall finish in bathroom
360364 02/24/2016 357261 P 9722 M Repair exhaust fan in bathroom
381519 02/24/2016 403207 P 9723 M Repair north door to latch properly
381520 02/24/2016 403209 P 9723 M Repair emergency lighting at north door
381521 02/24/2016 403211 P 9724 M Repair exhaust fan in bathroom
381524 02/24/2016 403217 P 9726 M Adjust door closer on south door to control speed of closing door
381526 02/24/2016 403223 P 9727 M Replace missing sign or stencil indicating impervious wall finish in bathroom
373780 02/24/2016 386357 P 9750 M Repair exhaust fan in bathroom
381489 02/24/2016 403144 2 203 O Remove and prohibit net and lights hanging from ceiling
381490 02/24/2016 403147 3 305 O Remove and prohibit decorative paper spheres hanging from ceiling. Adjust papers identifying centers to be above 6 feet 8 inches
381491 02/24/2016 403149 3 305 O Remove and prohibit large paper tree and reading hut
381495 02/24/2016 403157 6 605 O Remove and prohibit air freshener
381493 02/24/2016 403153 6 609 O Remove and prohibit air freshener
381504 02/24/2016 403177 6 613 O Remove and prohibit curtains hanging from ceiling
381530 02/24/2016 403231 P 9552 O Remove and prohibit flammable green curtains over windows and doors
381528 02/24/2016 403227 P 9556 O Remove and prohibit anchor charts hanging from ceiling in center of room. Anchor charts may hang no more than 2 inches from wall surface or on a string line no more than 2 inches from wall surface
381514 02/24/2016 403197 P 9714 O Remove and prohibit flammable window coverings
381522 02/24/2016 403213 P 9717 O Remove and prohibit anchor charts hanging from ceiling in center of room. Anchor charts may hang no more than 2 inches from wall surface or on a string line no more than 2 inches from wall surface
381523 02/24/2016 403215 P 9725 O Remove and prohibit air freshener
381498 02/24/2016 403163 1 120 MS Provide current inspection tag for fire extinguisher
381534 02/24/2016 403239 8 802 MS Recharge fire extinguisher adjacent to 8-807
381484 02/24/2016 403133 3 308 OS Keep area clear at emergency escape window
381496 02/24/2016 403159 6 605 OS Remove and prohibit use of candles
381497 02/24/2016 403161 6 627 OS Remove and prohibit use of candles
381516 02/24/2016 403201 P 9714 OS Remove and prohibit use of candle
373642 10/08/2015 386061 2 201A M Repair exhaust fan in bathroom
373800 10/08/2015 386401 3 303 M Secure drinking fountain to sink
360407 10/08/2015 357354 3 303A M Repair exhaust fan in bathroom
360404 10/08/2015 357347 3 304A M Repair exhaust fan in bathroom
360412 10/08/2015 357364 3 309A M Repair exhaust fan in bathroom
373643 10/08/2015 386063 3 310A M Repair exhaust fan in bathroom
373805 10/08/2015 386411 5 190 M Replace belt guard for outside air intake motor
373797 10/08/2015 386395 8 811B M Repair exhaust fan in bathroom
360231 10/08/2015 356981 P 0000 M Lift station behind P-7 is covered with dirt. Tank top should be above 100 year flood level. Remove dirt from on top of tank and verify correct elevation of tank
373660 10/08/2015 386104 P 9715 M Fill hole in ground at sidewalk outside of rear door
373749 04/30/2015 386291 P 0000 M Landings at portables have been undermined by storm drainage. Fill all undermined landings
373771 04/30/2015 386337 P 9724 M Repair exhaust fan in bathroom
373636 04/15/2015 386047 8 802 M Make repairs to Kitchen hood fire suppression system per inspection report. Manifold not correct. No deficiencies per 4-7-15 report
360216 04/15/2015 356948 P 9553 M Replace missing storm drain grate
373787 04/06/2015 386372 00 0000 M Provide lock for gate on south perimeter fence at west end of fence
373639 04/06/2015 386053 1 105 M Determine cause of water damaged ceiling tiles and replace tiles
373638 04/06/2015 386051 1 108A M Repair leaking flush valve for toilet
373791 04/06/2015 386382 1 117 M Secure loose laminate and loose door hold open on door to 1-118
373788 04/06/2015 386375 1 118 M Adjust door to corridor to latch properly
373647 04/06/2015 386074 1 120 M Anchor loose door threshold
360230 04/06/2015 356979 1 120 M Insulate hot water lines
373794 04/06/2015 386389 1 122 M Clock motor for canopy lights time clock is not working. Replace clock motor. Time clock disconnected, on EMS
373798 04/06/2015 386397 2 203A M Secure loose handicapped grabrail
373799 04/06/2015 386399 2 206 M Repair or replace emergency lighting relay. Emergency lights always on
373803 04/06/2015 386407 3 308 M Secure drinking fountain to sink
373648 04/06/2015 386077 3 309 M Repair broken window blinds
373637 04/06/2015 386049 5 504A M Repair leaking flush valve for toilet
373804 04/06/2015 386409 5 508 M Repair or replace broken latch on emergency escape window
373645 04/06/2015 386070 6 609 M Replace broken plastic cover on exposed electrical junction box on panel to left of door
373789 04/06/2015 386377 8 114 M Repair auto closer on south door to corridor
373646 04/06/2015 386072 8 802 M Clean Kitchen hood and provide tag indicating date cleaned. Last cleaning 6-17-2013
373796 04/06/2015 386393 8 811A M Repair exhaust fan in bathroom
360393 04/06/2015 357322 8 814A M Provide cover for thermostat
360208 04/06/2015 356931 9 903 M Label all circuits on electrical panel XL
373792 04/06/2015 386385 9 904 M Repair oil leak on generator
373782 04/06/2015 386361 P 0000 M Provide lock on gate of fencing around lift station behind P-29
373649 04/06/2015 386080 P 9552 M Repair emergency lighting at front door
373650 04/06/2015 386082 P 9552 M Replace missing grate for storm drain at rear of unit
373651 04/06/2015 386084 P 9553 M Make wall at bathroom sink impervious
373652 04/06/2015 386086 P 9554 M Make wall at bathroom sink impervious
373653 04/06/2015 386088 P 9555 M Make wall at bathroom sink impervious
373654 04/06/2015 386091 P 9712 M Adjust rear door to latch properly
373655 04/06/2015 386093 P 9712 M Unclog toilet
373656 04/06/2015 386096 P 9712 M Make wall at sink impervious
373657 04/06/2015 386098 P 9714 M Secure sink to wall in bathroom
373751 04/06/2015 386295 P 9717 M Replace leaking flapper valve for toilet
373752 04/06/2015 386297 P 9719 M Replace fill valve for toilet that does not shut off
373753 04/06/2015 386300 P 9720 M Make bathroom wall at sink impervious
373755 04/06/2015 386302 P 9722 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
373756 04/06/2015 386305 P 9722 M Repair exhaust fan in bathroom. Duplicate
373772 04/06/2015 386339 P 9724 M Make wall at bathroom sink impervious
373773 04/06/2015 386341 P 9725 M Make wall at bathroom sink impervious
373774 04/06/2015 386344 P 9725 M Adjust rear door to latch properly
373776 04/06/2015 386348 P 9727 M Rear storm pipe is filled with dirt and grate is missing. Flush dirt from pipe and install grate on drain
373778 04/06/2015 386353 P 9749 M Make wall at bathroom sink impervious
373781 04/06/2015 386359 P 9750 M Secure sink to wall in bathroom
373783 04/06/2015 386364 P 9751 M Replace missing epoxy floor finish in bathroom behind toilet
373784 04/06/2015 386366 P 9751 M Make wall at bathroom sink impervious
373785 04/06/2015 386368 P 9752 M Adjust rear door to latch properly
373786 04/06/2015 386370 P 9752 M Connect downspout to elbow
373635 04/06/2015 386045 00 0 O No access was available to 1-121, 8-814C, 8-814D, 8-823 and 9-901 Please provide access to these rooms during the report review meeting
373801 04/06/2015 386403 00 0000 O Remove and prohibit attaching paper to blinds. Paper is acceptable on windows or on string lines in front of windows. Rooms 3-301, 3-309, 3-311, 3-312, 4-401, 5-501, 5-502, 5-517, P-19 and P-27
373802 04/06/2015 386405 3 311 O Remove and prohibit hanging string line from ceiling. String lines are acceptable against wall or in in front of windows close to wall
373640 04/06/2015 386056 8 815 O Prohibit charging batteries in room
360215 04/06/2015 356946 P 9553 O Provide clear access to electrical panel
373659 04/06/2015 386102 P 9714 O Remove and prohibit hanging string lines from ceiling. String lines are acceptable against the wall or in front of windows close to the wall
373662 04/06/2015 386109 P 9715 O Remove and prohibit hanging string lines from ceiling. String lines are acceptable against the wall of in front of windows close to wall
373750 04/06/2015 386293 P 9716 O Remove and prohibit hanging string lines from ceiling. String lines are acceptable against wall or in front of windows close to wall
373768 04/06/2015 386311 P 9724 O Remove and prohibit excessive flammable decorations hanging from ceiling. Limit to 12 standard sheets of paper
373770 04/06/2015 386335 P 9724 O Remove and prohibit plug in air freshener
373779 04/06/2015 386355 P 9750 O Remove and prohibit excessive flammable decorations hung from ceiling. 12 standard sheets of paper is the limit to hang from the ceiling
373641 04/06/2015 386058 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus
373790 04/06/2015 386380 8 114 MS Repair auto closer on south door to stage
373644 04/06/2015 386067 5 516 OS Remove storage from electrical room
373795 04/06/2015 386391 7 706 OS Remove storage from mechanical room
373793 04/06/2015 386387 9 904 OS Prohibit storage of gasoline or gas powered equipment. Store in flammable storage room
373775 04/06/2015 386346 P 9725 OS Maintain 3 foot clear aisle to rear exit
373777 04/06/2015 386351 P 9749 OS Provide clear access to fire extinguisher
360403 12/15/2014 357345 2 204A M Repair exhaust fan in bathroom
360220 12/15/2014 356957 3 307 M Repair emergency escape window to open properly. Hard to open
360226 12/15/2014 356969 5 501 M Repair emergency escape window to open properly. Hard to open
360395 12/15/2014 357326 8 820A M Replace missing ceramic wall tile around both urinals
360261 12/15/2014 357044 P 9719 M Replace missing ceramic tile on floor sink in Janitors closet. Tile covers wood sink bowl
290558 12/15/2014 204764 00 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for all buildings. On ADA compliance report
320777 08/20/2014 270387 8 802 M Provide current inspection tag for kitchen steamer
360209 04/11/2014 356933 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable. Last certification in room 9-903 dated 2/10/11
360211 04/11/2014 356937 00 0000 M Provide weather-proof covers for outlets and light switch on NW column of covered play area
360206 04/11/2014 356926 1 112 M Secure sink to wall
360205 04/11/2014 356924 1 114 M Adjust door to latch properly
360400 04/11/2014 357338 2 190 M Close and lock open cabinet
360399 04/11/2014 357336 2 201A M Secure loose handicapped grabrail
360406 04/11/2014 357350 2 207 M Replace GFCI outlet that will not trip
360408 04/11/2014 357356 3 303A M Secure loose toilet seat
360225 04/11/2014 356967 3 312 M Repair emergency escape window to open properly. Hard to open
360418 04/11/2014 357372 5 0000 M Secure gate latch post to building at SE corner of 5-509
360415 04/11/2014 357370 5 504B M Repair leaking flush valve for urinal
360222 04/11/2014 356961 5 507A M Secure loose toilet seat
360414 04/11/2014 357368 5 508 M Replace GFCI outlet that will not trip
360419 04/11/2014 357377 5 510A M Caulk urinal to wall
360223 04/11/2014 356963 5 516 M Close and lock open cabinets
360385 04/11/2014 357306 6 614 M Secure data box to wall
360218 04/11/2014 356953 6 617 M Exterminate ants in classroom
360398 04/11/2014 357333 7 702 M Determine cause of water damaged ceiling tiles and replace tiles
360219 04/11/2014 356955 8 802 M Repair deficient items listed on kitchen hood fire suppression system inspection report
360394 04/11/2014 357324 8 814A M Repair hole in wall above door
360391 04/11/2014 357318 8 814A M Close and lock Won Door cabinet.
360392 04/11/2014 357320 8 814A M Replace missing cover for Audio cabinet
360387 04/11/2014 357309 8 815 M Close and lock 2 fire alarm boxes
360389 04/11/2014 357314 8 819 M Adjust door to latch properly
360396 04/11/2014 357329 8 820A M Repair leaking flush valve for 2nd urinal
360397 04/11/2014 357331 8 822A M Repair leaking flush valve for toilets 2 and handicapped toilet
360210 04/11/2014 356935 9 903 M Close and lock fire alarm cabinet
360227 04/11/2014 356971 P 0000 M Provide chain and lock on gate of fencing around lift station and lock lid of tank adjacent to P-29
360382 04/11/2014 357298 P 0000 M Attach all green plastic storm drain grates to drain pipe. Many grates displaced leaving large hole in ground. Black drain pipe exposed to sun is falling apart and getting damaged by lawn mowing equipment. Repair storm drainage system for all portables and clean out storm drainage pipes. Bury exposed black pipe and get water away from units. Currently storm water goes under units
360213 04/11/2014 356942 P 9552 M Caulk sink to bathroom wall
360214 04/11/2014 356944 P 9552 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360217 04/11/2014 356950 P 9553 M Junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360228 04/11/2014 356974 P 9554 M Caulk sink to wall in bathroom
360229 04/11/2014 356977 P 9554 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360232 04/11/2014 356983 P 9555 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360233 04/11/2014 356985 P 9555 M Determine cause of water damaged ceiling tiles and replace tiles at rear door
360234 04/11/2014 356987 P 9556 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360235 04/11/2014 356989 P 9713 M Caulk sink to wall in bathroom
360238 04/11/2014 356998 P 9713 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360239 04/11/2014 357000 P 9713 M Remove unattached concrete piece at rear landing
360241 04/11/2014 357004 P 9714 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360242 04/11/2014 357006 P 9714 M Remove unattached concrete at rear landing
360243 04/11/2014 357008 P 9714 M Adjust front door to latch properly
360245 04/11/2014 357012 P 9715 M Exterior junction boxes are partialy buried. Remove dirt from beneath boxes so that they do not contact ground
360246 04/11/2014 357014 P 9715 M Remove unattached concrete at rear landing
360247 04/11/2014 357016 P 9716 M Caulk sink to wall in bathroom
360248 04/11/2014 357018 P 9716 M Replace missing storm drain grate
360249 04/11/2014 357020 P 9716 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360250 04/11/2014 357022 P 9716 M Remove unattached concrete at rear landing
360251 04/11/2014 357024 P 9717 M Caulk sink to wall in bathroom
360253 04/11/2014 357028 P 9717 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360254 04/11/2014 357030 P 9717 M Remove unattached concrete at rear landing
360255 04/11/2014 357033 P 9718 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360256 04/11/2014 357035 P 9719 M Caulk sink to wall in bathroom
360258 04/11/2014 357039 P 9719 M Repair electrical panel door to latch
360259 04/11/2014 357041 P 9719 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360260 04/11/2014 357041 P 9719 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360361 04/11/2014 357255 P 9720 M Caulk sink to bathroom wall
360362 04/11/2014 357257 P 9720 M Exterior junction boxes are in contact with ground. Remove dirt from beneath boxes so that they do not contact ground
360363 04/11/2014 357259 P 9721 M Exterior 12 inch by 12 inch junction box is partially buried. Remove dirt from under box so that it does not contact ground
360365 04/11/2014 357263 P 9722 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so that they do not contact ground
360366 04/11/2014 357265 P 9722 M Adjust rear door to latch properly
360367 04/11/2014 357268 P 9723 M Replace broken toilet seat
360368 04/11/2014 357270 P 9724 M 12 inch by 12 inch junction box is partially buried. Remove dirt from beneath box so that it does not contact ground
360369 04/11/2014 357272 P 9724 M Adjust rear door to latch properly
360370 04/11/2014 357274 P 9724 M Replace cracked toilet seat
360371 04/11/2014 357276 P 9724 M Reattach grate to drain pipe
360372 04/11/2014 357278 P 9725 M Remove unattacheed concrete at rear landing
360373 04/11/2014 357280 P 9726 M Adjust rear door to latch properly
360374 04/11/2014 357282 P 9726 M Remove unattached concrete at rear landing
360375 04/11/2014 357284 P 9727 M Remove unattached concrete at rear landing
360376 04/11/2014 357286 P 9749 M Exterior junction boxes are in contact with ground. Remove dirt from beneath boxes so that they do not contact ground
360377 04/11/2014 357288 P 9750 M Exterior junction boxes are in contact with ground. Remove dirt from beneath boxes so that they do not contact ground
360378 04/11/2014 357290 P 9750 M Caulk sink to wall in bathroom
360379 04/11/2014 357292 P 9751 M Exterior junction boxes are in contact with ground. Remove dirt from beneath boxes so that they do not contact ground
360380 04/11/2014 357294 P 9751 M Patch or refinish bathroom floor. Missing pieces
360381 04/11/2014 357296 P 9752 M Reattach storm drain grate to pipe
360401 04/11/2014 357341 2 201 O Post sign indicating evacuation routes
360402 04/11/2014 357343 2 203 O Post sign indicating evacuation routes
360413 04/11/2014 357366 3 308 O Provide clear access to fire alarm pull station
360410 04/11/2014 357358 3 309 O Post sign indicating evacuation routes
360411 04/11/2014 357361 3 309 O Prohibit plugging surge protector into surge protector
360420 04/11/2014 357379 5 511 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
360224 04/11/2014 356965 5 517 O Post sign indicating evacuation routes
360236 04/11/2014 356993 P 9713 O Remove and prohibit hanging string lines with paper from ceiling. String lines are acceptable against wall
360237 04/11/2014 356996 P 9714 O Remove and prohibit hanging string lines with paper from ceiling. String lines are acceptable against wall
360244 04/11/2014 357010 P 9715 O Remove and prohibit hanging paper from ceiling. Attach hangings to wall. Maximum of 12 sheets of 8 and one half by 11 inch paper can be hung from ceiling
360221 04/11/2014 356959 4 402 MS Provide current inspection tag for fire extinguisher
360212 04/11/2014 356940 8 823 OS Provide clear access to fire extinguisher
360240 04/11/2014 357002 P 9714 OS Maintain 3 foot clear aisle to rear exit
360252 04/11/2014 357026 P 9717 OS Maintain 3 foot clear aisle to rear exit
360257 04/11/2014 357037 P 9719 OS Maintain 3 foot clear aisle to rear exit
340581 12/16/2013 314039 1 120 M Provide current state inspection tag for boiler. Burner 399,000 BTU and storage tank
340579 03/13/2013 314035 1 122 M Repair emergency lighting
340587 03/13/2013 314049 3 304 M Replace missing ceiling tiles
340591 03/13/2013 314058 3 312 M Repair emergency escape window to open properly
340589 03/13/2013 314054 3 313 M Repair door to close properly
340556 03/13/2013 313987 5 510B M Anchor toilet to floor
340594 03/13/2013 314064 6 608 M Repair emergency escape window to open properly
340558 03/13/2013 313989 7 701 M Adjust door closer on south door to control speed of closing door
340560 03/13/2013 313993 8 811A M Repair exhaust fan
340561 03/13/2013 313998 8 811A M Anchor toilet to floor
340563 03/13/2013 314001 8 811B M Repair exhaust fan
340583 03/13/2013 314041 8 821 M Replace missing soap dispenser
340539 03/13/2013 313950 P 0000 M Prohibit exterior junction boxes of P-5 through P-9 from coming into contact with dirt
340538 03/13/2013 313948 P 9552 M Repair emergency lighting at west door
340537 03/13/2013 313946 P 9553 M Repair emergency lighting at west door
340535 03/13/2013 313942 P 9554 M Repair emergency lighting at east door
340536 03/13/2013 313944 P 9554 M Repair door hardware on bathroom door
340534 03/13/2013 313940 P 9555 M Repair emergency lighting at west door
334760 03/13/2013 301324 P 9555 M Repair bathroom door hardware - lock sticks
340533 03/13/2013 313938 P 9556 M Repair emergency lighting at west door
340545 03/13/2013 313962 P 9714 M Secure bathroom sink to wall
340548 03/13/2013 313968 P 9717 M Secure bathroom sink to wall
340549 03/13/2013 313971 P 9717 M Replace missing floor tile at south door
340541 03/13/2013 313954 P 9718 M Provide cover on exposed exterior electrical junction box on south side of portable
340543 03/13/2013 313958 P 9720 M Repair emergency lighting at north door
340546 03/13/2013 313964 P 9722 M Repair exhaust fan in bathroom
340550 03/13/2013 313973 P 9725 M Repair emergency lighting at north door
340552 03/13/2013 313977 P 9727 M Repair emergency lighting at south door
340542 03/13/2013 313956 P 9750 M Repair emergency lighting at south door
340569 03/13/2013 314013 1 118B O Prohibit use of grey multi outlet power strip, use approved surge protector
340585 03/13/2013 314045 3 305 O Relocate string line to hang no more than 2 inches from wall
340592 03/13/2013 314061 5 508 O Remove and prohibit air freshener
340554 03/13/2013 313981 5 512 O Relocate string line to hang no more than 2 inches from wall
340553 03/13/2013 313979 5 514 O Relocate string line to hang no more than 2 inches from wall
340544 03/13/2013 313960 P 9714 O Relocate string line to hang no more than 2 inches from wall
340555 03/13/2013 313984 5 512 MS Recharge fire extinguisher
340568 03/13/2013 314009 9 901 MS Provide current inspection tag for fire extinguisher
340578 03/13/2013 314033 1 118 OS Prohibit storage of gasoline
340566 03/13/2013 314006 7 190 OS Remove storage from mechanical room
340551 03/13/2013 313975 P 9726 OS Maintain clear aisle to (north) exit
340540 03/13/2013 313952 P 9749 OS Maintain clear aisle to exit (rear) exit door
334764 10/03/2012 301332 00 9599 M Replace missing caulk between sidewalk sections between P-18 and P-19
334762 10/03/2012 301328 P 9749 M Repair missing window blinds
334720 10/03/2012 301243 8 802 MS Provide current inspection tag for kitchen hood fire suppression system
320792 04/09/2012 270417 1 120 M Provide current state inspection tag for boiler
334748 04/09/2012 301299 3 302A M Seal gap between toilet and floor
334740 04/09/2012 301284 3 305 M Prohibit plugging extension cord into surge protector adjacent to teacher desk - plug extension cord into a permanent outlet
334713 04/09/2012 301227 3 311 M Repair emergency escape window to open properly - hard to open
334743 04/09/2012 301289 3 317 M Replace missing auto closer on door
334734 04/09/2012 301270 5 120 M Replace missing floor tiles adjacent to exterior door
334736 04/09/2012 301276 5 515B M Close gaps around ceiling vent in closet
334723 04/09/2012 301246 6 608 M Replace broken latch hardware for emergency escape window - room labeled 609
320775 04/09/2012 270383 8 813 M Provide dated flame resistance label on stage curtains along back wall
334761 04/09/2012 301326 P 9555 M Repair emergency lighting above front door
334763 04/09/2012 301330 P 9749 M Repair damaged floor tile adjacent to back door
334739 04/09/2012 301282 3 305 O Prohibit plugging extension cord into surge protector adjacent to teacher desk - plug extension cord into a permanent outlet
334696 04/09/2012 301190 3 305 O Remove and prohibit hanging paper tree from ceiling and on wall
334699 04/09/2012 301195 3 305 O Eliminate white extension cord with multiple outlet end behind computer stations or replace with a surge protector
334693 04/09/2012 301184 3 308 O Remove and prohibit hanging paper below door frame
334706 04/09/2012 301209 3 308 O Prohibit plugging surge protector into surge protector at computer stations - plug each surge protector directly into permanent outlet
334703 04/09/2012 301203 3 310 O Prohibit plugging extension cord into surge protector - plug extension cord directly into wall outlet
334732 04/09/2012 301267 5 120 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
334689 04/09/2012 301178 5 501 O Remove and prohibit hanging paper from string line in front of emergency window
334683 04/09/2012 301165 8 816A O Remove glass mirror or provide mirror made of tempered glass, safety glass, or stainless steel
334685 04/09/2012 301169 8 816B O Remove glass mirror or provide mirror made of tempered glass, safety glass, or stainless steel
334752 04/09/2012 301305 P 9723 O Prohibit plugging surge protector into surge protector at teachers desk - plug each surge protector directly into wall outlet
334759 04/09/2012 301321 P 9726 O Remove and prohibit hanging paper from ceiling
320774 04/09/2012 270381 00 0000 C Provide suitable area for recharging batteries for floor cleaning mchines
334714 04/09/2012 301229 8 823 MS Provide current inspection tag for fire extinguisher
334716 04/09/2012 301234 1 122 OS Remove storage from electrical room
334745 04/09/2012 301294 3 306A OS Remove box from bathroom
334709 04/09/2012 301216 3 307A OS Remove storage bins form bathroom
334712 04/09/2012 301221 4 403 OS Remove table and storage from bathroom vestibule to maintain clear access to bathroom 4-403A
334726 04/09/2012 301253 6 608 OS Relocate copy machine to keep area clear at emergency escape window - room labeled 609
334731 04/09/2012 301261 6 609 OS Relocate table adjacent to teachers desk to keep area clear at emergency escape window - room labeled 610
334719 04/09/2012 301238 9 904 OS Remove storage blocking clear access to generator
334757 04/09/2012 301317 P 9714 OS Rearrange furniture to maintain 3 ft clear path to back door
334755 04/09/2012 301311 P 9726 OS Relocate desk to maintain clear aisle to back door
334687 04/09/2012 301174 8 816 CS Provide fire extinguisher
321135 02/21/2012 271152 1 0000 M Repair missing cover on panic hardware on exit door adjacent to 1-122
320780 02/21/2012 270393 8 812 M Repair lock on door to work properly - was not able to lock the door
290581 04/01/2011 204811 3 0000 M Replace missing cover on drinking fountain adjacent to 3-307
320772 03/31/2011 270377 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable (old certificate is in 9-103)
320773 03/31/2011 270379 00 9599 M Replace missing insulated cover for electrical GFCI outlet at pavilion
320779 03/31/2011 270391 00 9599 M Replace missing stop sign at east end of parking area
320794 03/31/2011 270421 00 9599 M Replace missing caps on fire department standpipe connection east of Bldg. 5
320829 03/31/2011 270505 00 9599 M Replace missing cover for storm drain line in landscape outside back door of P-10
321134 03/31/2011 271150 1 0000 M Repair or replace rusted door frame on exit door adjacent to 1-122
320786 03/31/2011 270405 1 108 M Repair sink in clinic to drain properly
320824 03/31/2011 270495 2 203 M Determine cause of water damaged ceiling tiles and replace tiles
320826 03/31/2011 270499 3 317 M Repair door lock to work properly - room was not accessible
320790 03/31/2011 270413 5 507 M Secure ceiling tile in place
321622 03/31/2011 272200 8 813 M Relocate illuminated exit sign above closet door(814) to be above north exit door to music room
321623 03/31/2011 272202 8 814A M Remove illuminated exit sign inside closet above door to music room 814
320838 03/31/2011 270523 P 9553 M Repair emergency lighting above front door
320845 03/31/2011 270538 P 9712 M Repair emergency lighting above back door
320841 03/31/2011 270529 P 9714 M Repair emergency lighting (X2)
320842 03/31/2011 270532 P 9715 M Repair emergency lighting (X2)
320844 03/31/2011 270536 P 9716 M Repair emergency lighting above front door
320830 03/31/2011 270507 P 9716 M Adjust back door to latch properly
320843 03/31/2011 270534 P 9717 M Repair emergency lighting (X2)
320847 03/31/2011 270542 P 9718 M Repair emergency lighting (X2)
320848 03/31/2011 270545 P 9719 M Repair emergency lighting (X2)
320849 03/31/2011 270547 P 9721 M Repair emergency lighting (X2)
320828 03/31/2011 270503 P 9721 M Repace broken foor tiles adjacent to back door
320854 03/31/2011 270557 P 9722 M Repair emergency lighting above front door
320850 03/31/2011 270549 P 9723 M Repair emergency lighting (X2)
320851 03/31/2011 270551 P 9724 M Repair emergency lighting (X2)
320853 03/31/2011 270555 P 9725 M Repair emergency lighting above front door
320852 03/31/2011 270553 P 9726 M Repair emergency lighting (X2)
320846 03/31/2011 270540 P 9727 M Repair emergency lighting
320839 03/31/2011 270525 P 9749 M Repair emergency lighting above front door
320840 03/31/2011 270527 P 9751 M Repair emergency lighting above front door
320787 03/31/2011 270407 1 107 O Eliminate (3) plug orange adaptor adjacent to desk or replace with a surge protector
320823 03/31/2011 270493 3 306 O Prohibit plugging surge protector into surge protector at teacher's desk - plug each surge protector directly into permanent electrical outlet
320797 03/31/2011 270427 3 309 O Prohibit plugging surge protector into surge protector adjacent to teacher's desk
320784 03/31/2011 270401 5 501 O Remove and prohibit paper and decorations hanging from ceiling
320783 03/31/2011 270399 5 506 O Remove and prohibit paper and decorations hanging from ceiling
320791 03/31/2011 270415 5 508 O Prohibit plugging surge protector into surge protector and into another surge under computer stations - plug each surge protector directly into wall outlet
320782 03/31/2011 270397 5 511 O Remove and prohibit paper and decorations hanging from ceiling
320785 03/31/2011 270403 5 517 O Remove and prohibit excessive flammable decorations
321620 03/31/2011 272195 7 701 O Provide certification that fabric and art work meet flame spread requirements or limit to 20 percent of each wall area
320781 03/31/2011 270395 8 812 O Remove cobwebs off heat detector on ceiling
320833 03/31/2011 270514 P 9712 O Remove and prohibit paper and decorations hanging from ceiling
320834 03/31/2011 270516 P 9713 O Remove and prohibit excessive flammable decorations
320836 03/31/2011 270519 P 9715 O Remove and prohibit paper and decorations hanging from ceiling
320837 03/31/2011 270521 P 9716 O Remove and prohibit paper and decorations hanging from ceiling
320831 03/31/2011 270509 P 9716 O Remove and prohibit flammable blue vinyl straw covering window
320827 03/31/2011 270501 P 9725 O Prohibit plugging surge protector into cart outlet - Plug surge protector directly into wall outlet
320776 03/31/2011 270385 8 813 C Provide records that stage rigging has been inspected and conforms to required safety standards
320793 03/31/2011 270419 1 120 MS Remove plastic drain pipes stored in boiler room
320825 03/31/2011 270497 2 206 MS Relocate type K fire extinguisher to other side of ABC fire extinguisher - Type K fire extinguisher is very close to stove top burners
320778 03/31/2011 270389 8 802 MS Provide current inspection tag for kitchen hood fire suppression system
320788 03/31/2011 270409 1 118 OS Prohibit charging batteries for floor cleaning machine in room
320798 03/31/2011 270429 3 301 OS Relocate storage to provide clear access to fire extinguisher cabinet
320799 03/31/2011 270431 3 301 OS Rearrange desks to maintain 3 ft clear path to exit door
320796 03/31/2011 270425 3 307 OS Relocate desk adjacent to exterior door to maintain clear path to exit door
320795 03/31/2011 270423 3 308 OS Remove storage bins from bathroom
321136 03/31/2011 271154 4 401 OS Keep area clear at emergency escape window - remove paper covering emergency escape window sign, remove paper on blinds at emergency window and remove storage in front of emergency window
320789 03/31/2011 270411 5 501A OS Remove storage bins from bathrooms
320771 03/31/2011 270375 5 520 OS Remove and prohibit use of toaster oven
320832 03/31/2011 270511 P 9714 OS Relocate table to maintain 3 ft clear aisle to back door
279472 01/19/2011 181122 00 0000 M Modify or improve site drainage at portables. Roofs are drained into area between sidewalks and runoff collects next to and underneath portables undermining sidewalks and flooding junction boxes on portables
290804 01/19/2011 205289 8 813 C Change swing of exit door on stage to swing in direction of egress
305634 04/20/2010 237245 1 105 M Determine cause of water damaged ceiling tiles and replace tiles
305633 04/20/2010 237243 1 108 M Secure junction box on south wall adjacent to entrance door
305590 04/20/2010 237157 1 112 M Repair leaking sink faucet, when water is on faucet leaks
305594 04/20/2010 237166 1 119 M Repair holes in walls
290570 04/20/2010 204789 1 119 M Repair door lock - lock sticks
305595 04/20/2010 237168 1 122 M Repair emergency lighting
305611 04/20/2010 237200 3 311 M Repair emergency escape window to open properly
305612 04/20/2010 237202 3 8087 M Repair auto closer on exterior gate adjacent to 3-306
305592 04/20/2010 237161 6 601 M Repair drinking fountain adjacent to 6-602, water does not turn on
305607 04/20/2010 237192 7 190 M Mount fire extinguisher at maximum five feet above floor
305599 04/20/2010 237176 8 801 M Repair drinking fountain adjacent to 8-801A
279488 04/20/2010 181156 8 802 M Repair pilot light on 2 burner range. Light continually goes out.
305598 04/20/2010 237174 8 809 M Replace damaged dryer vent hose
305600 04/20/2010 237178 8 813 M Provide dated flame resistance label on stage curtains
305632 04/20/2010 237241 8 814 M Repair wall behind door for 8-814A, door stop is pushed into wall
305631 04/20/2010 237240 8 821 M Repair deteriorated wall finish
305602 04/20/2010 237182 9 901 M Repair light fixture in flammable storage room, light does not turn on
305608 04/20/2010 237194 9 903 M Fill void in electrical panel LA4
305604 04/20/2010 237186 9 904 M Repair leaking fixture in generator room
305605 04/20/2010 237188 9 904 M Repair emergency lighting
305620 04/20/2010 237218 P 9717 M Anchor (tan) shelving to wall
305623 04/20/2010 237224 P 9752 M Determine cause of water damaged ceiling tiles and replace tiles
305593 04/20/2010 237164 1 118 O Prohibit plugging microwave into orange extension cord - plug directly into permanent electrical outlet
305613 04/20/2010 237204 3 303 O Prohibit plugging surge protector into surge protector under computers
305617 04/20/2010 237212 5 501 O Prohibit 13A extension cords( brown, white) adjacent to to computers and teacher's desk
305618 04/20/2010 237214 5 509 O Prohibit plugging orange extension cord into surge protector
305616 04/20/2010 237210 6 610 O Prohibit multi outlet electrical adaptor
305601 04/20/2010 237180 8 814A O Remove and prohibit flammable green plastic grass decorations
279484 04/20/2010 181148 9 904 O Remove storage from generator room
305625 04/20/2010 237228 P 9712 O Remove and prohibit air freshener (sticks in oil)
305622 04/20/2010 237222 P 9717 O Provide clear access to electrical panel
305628 04/20/2010 237234 P 9720 O Remove and prohibit combustible beanbag chairs
279471 04/20/2010 181120 00 0000 C Modify or provide site drainage to eliminate standing water in depression in ground north of P-17
234598 04/20/2010 22118 00 0000 C Provide suitable area for storage of golf carts and recharging golf cart batteries (N/A April 2010, school has one gas powered golf cart which is stored outside)
305615 04/20/2010 237208 2 206 MS Provide current inspection tag for fire extinguisher
305596 04/20/2010 237170 8 802 MS Provide current inspection tag for fire extinguisher adjacent to freezer and refrigerator
305609 04/20/2010 237196 8 823 MS Provide current inspection tag for fire extinguisher
305603 04/20/2010 237184 9 901 MS Replace missing fire extinguisher
290571 04/20/2010 204791 1 122 OS Remove storage from electrical room
305614 04/20/2010 237206 2 201 OS Remove and prohibit use of toaster
217613 04/20/2010 67879 2 207 OS Remove storage on stove burners to prevent fire
290563 04/20/2010 204774 5 516 OS Remove storage from electrical room
305606 04/20/2010 237190 7 190 OS Remove storage from mechanical room
305597 04/20/2010 237172 8 806A OS Prohibit storage of flammable materials (sterno)
305610 04/20/2010 237198 8 823 OS Provide clear access to fire extinguisher
305624 04/20/2010 237226 P 9712 OS Maintain clear aisle to exit doors, chairs and microwave blocking rear door
305626 04/20/2010 237230 P 9712 OS Remove and prohibit storage in bathroom
305621 04/20/2010 237220 P 9717 OS Maintain clear aisle to exit doors
305627 04/20/2010 237232 P 9720 OS Prohibit flammable plastic table cloth
305629 04/20/2010 237236 P 9723 OS Maintain clear aisle to exit doors
305619 04/20/2010 237216 P 9727 OS Remove and prohibit excessive storage
305591 04/20/2010 237159 1 101 FS Make repairs to fire alarm as noted on punch list and provide certification that fire alarm system has been tested and is fully operational
290815 04/20/2010 205312 P 9719 FS Provide heat detector in custodial room adjacent to P-25
290810 12/01/2009 205301 P 0000 M Provide impervious wall finish for minimum six foot height in all portable bathrooms
290572 04/08/2009 204793 1 120 M Provide current inspection tag for boiler
290569 04/08/2009 204787 2 190 M Repair door lock - lock sticks
279489 04/08/2009 181158 5 190 M Modify or repair DX units 5-1 and 5-2 so that air filter can be inserted in units
290575 04/08/2009 204798 6 604 M Chain helium cylinder to wall
290560 04/08/2009 204768 7 704 M Replace missing ceiling tiles
217714 04/08/2009 63526 8 802 M Provide current inspection tag for kitchen steamer
290808 04/08/2009 205297 P 0000 M Raise exterior electrical boxes so bottom of boxes is at least 8 inches above grade for all portables (not required per Terry Summerell)
290825 04/08/2009 205332 P 9715 M Adjust back door to latch properly
290817 04/08/2009 205317 P 9716 M Adjust back door to latch properly
290826 04/08/2009 205335 P 9722 M Adjust front door to latch properly
290806 04/08/2009 205295 2 202 O Prohibit plugging surge protector into surge protector under computer stations
290582 04/08/2009 204813 3 301 O Prohibit plugging surge protector into surge protector at teacher's desk
290583 04/08/2009 204815 3 302 O Prohibit plugging extension cord for printer into surge protector
290584 04/08/2009 204817 3 302 O Remove and prohibit paper on exterior side of classroom door
290568 04/08/2009 204785 3 304 O Remove and prohibit paper on light fixtures
290566 04/08/2009 204781 3 306 O Prohibit piggy backed surge protectors at teacher's desk - plug each surge protector directly into permanent electrical outlet
290585 04/08/2009 204819 3 310 O Reduce excessive storage around teacher's desk and adjacent to small refrigerator. Also keep electrical wall outlets exposed
290586 04/08/2009 204821 3 311 O Prohibit plugging surge protector into surge protector at computer stations
290587 04/08/2009 204823 3 311 O Eliminate extension cord with multiple outlet end adjacent to teacher's desk or replace with a surge protector
290588 04/08/2009 204825 3 311 O Reduce excessive storage adjacent to teacher's desk, across path to 3-302 and around small refrigerator. Also remove paper product to keep electrical wall outlet exposed adjacent to refrigerator
290576 04/08/2009 204800 5 501B O Remove and prohibit combustible residential foam chairs in closet
290564 04/08/2009 204776 5 503 O Prohibit plugging surge protector into surge protector at teacher's desk
290579 04/08/2009 204806 5 506 O Remove and prohibit excessive paper hanging from ceiling
290580 04/08/2009 204808 5 508 O Remove and prohibit excessive paper hanging from ceiling
290577 04/08/2009 204802 5 511 O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
290578 04/08/2009 204804 5 511 O Remove and prohibit excessive paper hanging from ceiling
290565 04/08/2009 204778 5 512 O Prohibit plugging surge protector into surge protector under computer stations
290561 04/08/2009 204770 6 603 O Prohibit plugging surge protector into surge protector for computer stations under windows and adjacent to writing board (X2)
290562 04/08/2009 204772 6 614 O Prohibit piggy backed surge protectors under windows - plug each surge protector directly into permanent electrical outlet
290812 04/08/2009 205305 P 9556 O Prohibit plugging surge protector into surge protector at projector cart
290833 04/08/2009 205349 P 9712 O Eliminate white extension cord with multiple outlet end under teacher's desk or replace with a surge protector
290835 04/08/2009 205353 P 9712 O Remove and prohibit net on ceiling and straw curtain above sink counter
290827 04/08/2009 205338 P 9721 O Prohibit plugging surge protector into extension cord under teacher's desk
290820 04/08/2009 205321 P 9723 O Remove and prohibit combustible beanbag chair
290821 04/08/2009 205326 P 9723 O Remove and prohibit excessive paper decorations on back door
290816 04/08/2009 205315 P 9726 O Prohibit plugging surge protector into surge protector under teacher's station
290805 04/08/2009 205293 2 206 MS Provide current inspection tag for fire extinguisher (x2)
291570 04/08/2009 206908 6 628 MS Provide current inspection tag for fire extinguisher
290574 04/08/2009 204796 1 118 OS Prohibit charging batteries for floor cleaning machines in room
290567 04/08/2009 204783 3 304 OS Remove and prohibit use of toaster oven
290834 04/08/2009 205351 P 9712 OS Remove excessive storage from bathroom
290829 04/08/2009 205340 P 9713 OS Rearrange furniture to maintain 3 ft clear aisle to back door
290823 04/08/2009 205329 P 9723 OS Relocate silk tree to provide clear access to fire alarm pull station
290831 04/08/2009 205345 P 9752 OS Rearrange desks to maintain 3 ft clear aisle to both exit doors
290559 04/08/2009 204766 8 806A FS Provide heat detector in custodial storage room
279509 11/19/2008 181200 P 9553 M Raise exterior junction boxes to be above grade, not sitting in dirt
279510 11/19/2008 181202 P 9554 M Raise exterior junction boxes to be above grade
279511 11/19/2008 181204 P 9555 M Raise exterior junction boxes to be above grade
279514 11/19/2008 181210 P 9556 M Raise exterior junction boxes to be above grade
279517 11/19/2008 181216 P 9712 M Raise exterior junction boxes to be above grade
279519 11/19/2008 181220 P 9713 M Raise exterior junction boxes to be above grade
279520 11/19/2008 181222 P 9714 M Raise exterior junction boxes to be above grade
279521 11/19/2008 181224 P 9715 M Raise exterior junction boxes to be above grade
279522 11/19/2008 181226 P 9716 M Raise exterior junction boxes to be above grade
279523 11/19/2008 181228 P 9717 M Raise exterior junction boxes to be above grade
279524 11/19/2008 181230 P 9718 M Raise exterior junction boxes to be above grade and replace damaged box
279525 11/19/2008 181232 P 9719 M Raise exterior junction boxes to be above grade
279529 11/19/2008 181240 P 9720 M Raise exterior junction boxes to be above grade
279530 11/19/2008 181242 P 9721 M Raise exterior junction boxes to be above grade
279532 11/19/2008 181246 P 9722 M Raise exterior junction boxes to be above grade
279533 11/19/2008 181248 P 9723 M Raise exterior junction boxes to be above grade
279534 11/19/2008 181250 P 9724 M Raise exterior junction boxes to be above grade
279535 11/19/2008 181252 P 9725 M Replace loose and missing coating on exterior wall
279537 11/19/2008 181256 P 9726 M Replace loose and missing coating on exterior wall
279539 11/19/2008 181260 P 9749 M Raise exterior junction boxes to be above grade
279541 11/19/2008 181264 P 9750 M Raise exterior junction boxes to be above grade
279543 11/19/2008 181268 P 9751 M Raise exterior junction boxes to be above grade
279531 04/18/2008 181244 00 0000 M Provide chain and lock for gate of fenced electrical enclosure adjacent to portables
279476 04/18/2008 181131 00 0000 M Replace missing cover for panic bars on doors to bus loop between Bldgs. 3 & 4
279498 04/18/2008 181178 1 119 M Fill hole in floor adjacent to access door from 1-118
279499 04/18/2008 181180 1 119 M Secure loose cover for SF 1-1
279496 04/18/2008 181174 1 119 M Provide cover on exposed electrical junction box adjacent to door to exterior
279505 04/18/2008 181192 2 202 M Exterminate ants in classroom
279494 04/18/2008 181170 3 306A M Secure loose door knob
279506 04/18/2008 181194 3 313 M Repair auto closer on door
279474 04/18/2008 181127 5 0000 M Repair inoperable air conditioner serving rooms 5-118, 5-119 and 5-120
279507 04/18/2008 181196 5 501B M Replace missing ceiling tiles
279495 04/18/2008 181172 5 502 M Repair emergency escape window to open properly
279477 04/18/2008 181133 5 506 M Replace missing ceiling tiles
279491 04/18/2008 181163 7 701 M Clean out clay traps under sinks. Provide access panel and unions on trap to facilitate removal
279487 04/18/2008 181154 8 809A M Secure sink to wall
279502 04/18/2008 181186 8 811A M Repair exhaust fan in bathroom
279503 04/18/2008 181188 8 811B M Repair exhaust fan in bathroom
279478 04/18/2008 181135 8 812 M Cover opening in exterior wall adjacent to door at hose outlet
279482 04/18/2008 181144 8 813 M Repair floor electrical outlets to eliminate need for extension cords
279500 04/18/2008 181182 8 816A M Repair exhaust fan in bathroom
279501 04/18/2008 181184 8 816B M Repair exhaust fan in bathroom
279492 04/18/2008 181165 8 818 M Repair deteriorated finish at SW corner of wall
279485 04/18/2008 181150 8 819 M Reset loose ceiling tiles
279483 04/18/2008 181146 8 821 M Repair deteriorated finish on north wall
279490 04/18/2008 181160 9 0000 M Caulk open expansion joint on north exterior wall
279493 04/18/2008 181167 9 902 M Provide cover on open electrical box on SW exterior wall
279528 04/18/2008 181238 P 9720 M Secure sink to wall in bathroom
279536 04/18/2008 181254 P 9725 M Secure sink to wall in bathroom
279538 04/18/2008 181258 P 9727 M Secure sink to wall in bathroom
279542 04/18/2008 181266 P 9751 M Replace broken toilet seat
279473 04/18/2008 181125 00 0 O No access was available to 8-801A. Please be prepared to access this room during the report review meeting.
279512 04/18/2008 181206 P 9555 O Remove and prohibit plug in air freshener
279513 04/18/2008 181208 P 9556 O Remove and prohibit plug in air freshener
279516 04/18/2008 181214 P 9712 O Eliminate extension cord or replace with minimum 15A cord
279497 04/18/2008 181176 1 119 MS Provide current inspection tag for fire extinguisher
279526 04/18/2008 181234 P 9719 MS Recharge fire extinguisher
279486 04/18/2008 181152 4 402 OS Keep area clear at emergency escape window
279479 04/18/2008 181137 6 608 OS Keep area clear at emergency escape window
279504 04/18/2008 181190 6 610 OS Provide clear access to fire alarm pull station
279481 04/18/2008 181142 8 813 OS Prohibit running electrical cord through door opening to 8-814A
279515 04/18/2008 181212 P 9712 OS Prohibit running electrical cord across floor creating a tripping hazard
279518 04/18/2008 181218 P 9712 OS Maintain clear aisle to rear exit
279540 04/18/2008 181262 P 9750 OS Prohibit running electrical cord across floor creating a tripping hazard
268841 04/18/2008 157979 5 190 CS Provide fire extinguisher in mechanical room
279480 04/18/2008 181139 6 616 FS Provide heat detector in normally unoccupied space
279475 04/18/2008 181129 7 190 FS Secure hanging heat detector
268965 12/18/2007 158243 P 9555 M Anchor toilet to floor
269828 12/18/2007 160178 4 402 O Eliminate multiple extension cords - multi outlet adaptors, 13A extension cords with multi oultlet end, surge into another, surge into extension cords, etc... for aquariums in science room
269821 12/18/2007 160162 4 402 C Provide additional outlets to eliminate use of excessive extension cords ( see teacher for exact locations)
268967 04/27/2007 158247 00 9599 M Provide cover on exposed electrical junction box where ceiling fan was at pavilion (x2)
248177 04/27/2007 116160 00 9599 M Install caps on fire department standpipe connection adjacent to P-17
268835 04/27/2007 157967 7 701 M Adjust exterior door to latch properly
268837 04/27/2007 157971 8 814 M Replace missing latch hardware on door to stage - adjacent to 8-814A
268832 04/27/2007 157961 8 816A M Repair exhaust fan in bathroom
268833 04/27/2007 157963 8 816B M Repair exhaust fan in bathroom
268968 04/27/2007 158250 P 9552 M Mount fire extinguisher at maximum five feet above floor and adjacent to door
269809 04/27/2007 160120 P 9716 M Adjust front door to latch properly
269803 04/27/2007 160108 P 9725 M Adjust door closer to control speed of closing door
269808 04/27/2007 160118 00 9599 O Prohibit parking on grass area adjacent to P-26
268826 04/27/2007 157949 1 113 O Eliminate power strip under desk or replace with a surge protector
268827 04/27/2007 157951 1 118 O Prohibit plugging refrigerator into an extension cord, plug appliances directly into wall outlet
268828 04/27/2007 157953 1 118A O Eliminate extension cord used to power coffee maker and radio or replace with a surge protector
269795 04/27/2007 160092 2 201 O Remove and prohibit paper covering windows
269796 04/27/2007 160094 2 201 O Eliminate multiple outlet electrical adaptor adjacent to back door
269818 04/27/2007 160156 3 302 O Remove excessive storage in classroom which causes excessive fuel load and keep area in an orderly manner
269819 04/27/2007 160158 3 304 O Eliminate use of extension cord with multiple outlet end at sink counter
269820 04/27/2007 160160 3 304 O Prohibit use of extension cord to power microwave, plug microwave directly into wall outlet
269799 04/27/2007 160100 3 304 O Eliminate multiple outlet electrical adaptor adjacent to communicating door
269826 04/27/2007 160173 3 304 O Provide certification that carpet meets flame spread requirement or remove carpet
269825 04/27/2007 160171 3 307 O Provide certification that carpet meets flame spread requirement or remove carpet
269817 04/27/2007 160154 3 311 O Remove excessive storage in classroom which causes excessive fuel load and keep area in an orderly manner
268843 04/27/2007 157983 4 401 O Prohibit plugging one surge protector into another at computer stations adjacent to teacher's desk, plug each surge protector directly into wall outlet
269829 04/27/2007 160180 4 402 O Eliminate extension cord with multiple outlet end or replace with a surge protector
268842 04/27/2007 157981 5 501 O Prohibit plugging one surge protector into another under computer stations, plug each surge protector directly into wall outlet
268845 04/27/2007 157987 5 502 O Eliminate multiple outlet adaptor behind fish tank adjacent to door
268847 04/27/2007 157991 5 506 O Remove and prohibit paper covering windows
268848 04/27/2007 157993 5 511 O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
268846 04/27/2007 157989 5 512 O Remove and prohibit paper covering windows
269806 04/27/2007 160114 6 603 O Remove display cabinet donated to school or provide safety protection on glazing in display cabinet
269830 04/27/2007 160182 6 604 O Remove excessive storage / decoration in back area which causes excessive fuel load and keep area in an orderly manner
269831 04/27/2007 160184 6 604A O Keep area in an orderly manner and maintain a clear path to toilet
269815 04/27/2007 160150 6 604A O Prohibit pluging refrigerator into extension cord - plug appliances directly into wall outlet
268969 04/27/2007 158252 P 9552 O Relocate storage cabinet to provide clear access to electrical panel
268966 04/27/2007 158245 P 9556 O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
269810 04/27/2007 160122 P 9716 O Eliminate power strip or replace with a surge protector
269827 04/27/2007 160175 P 9716 O Provide certification that carpet meets flame spread requirement or remove carpet
269824 04/27/2007 160169 P 9723 O Secure electrical cord cover strip to floor to eliminate tripping
269822 04/27/2007 160164 P 9723 O Remove and prohibit excessive paper covering
269823 04/27/2007 160166 P 9726 O Remove and prohibit excessive paper covering
269801 04/27/2007 160104 P 9727 O Remove paper covering electrical panel
268834 04/27/2007 157965 8 802 F Repair broken magnetic hold open device on south fire door between serving area and dining room
268830 04/27/2007 157957 1 122 MS Provide current inspection tag for fire extinguisher
269797 04/27/2007 160096 3 314 MS Close hatch on ceiling
269793 04/27/2007 160088 6 629 MS Provide current inspection tag for fire extinguisher
248173 04/27/2007 116152 8 802 MS Provide current inspection tag for hood fire suppression system
269804 04/27/2007 160110 1 118 OS Prohibit storage of gas powered pressure cleaner
268831 04/27/2007 157959 1 122 OS Remove storage from electrical room
268829 04/27/2007 157955 1 199 OS Remove table and lockers cabinet to maintain clear path to exit door - SW corner of Bldg. 1 adjacent to custodial receiving
269794 04/27/2007 160090 2 201 OS Remove and prohibit use of toaster oven
268844 04/27/2007 157985 4 401 OS Relocate storage to keep area clear at emergency escape window
268839 04/27/2007 157975 6 608 OS Relocate desks to keep area clear at emergency escape window
268840 04/27/2007 157977 6 609 OS Relocate storage to keep area clear at emergency escape window
268838 04/27/2007 157973 6 617 OS Relocate computer station to maintain 3ft clear aisle to exit door
269805 04/27/2007 160112 8 815 OS Prohibit storage of gas powered leaf blower
268836 04/27/2007 157969 9 903 OS Prohibit storage and charging golf cart batteries in room
269800 04/27/2007 160102 P 9722 OS Remove and prohibit use of toaster oven at sink counter
269807 04/27/2007 160116 P 9751 OS Relocate student's desk adjacent to teacher's desk to maintain a minimum 3 ft clear aisle to exit door
269816 04/27/2007 160152 6 604A FS Provide heat detector in bathroom used for storage
269802 04/27/2007 160106 P 9719 FS Provide heat detector in custodial room
248178 02/01/2007 116162 00 0000 M Repair exhaust fans in all individual bathrooms
217402 02/01/2007 67860 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
248130 02/01/2007 116072 1 120 M Provide current inspection tag for boiler
248172 02/01/2007 116150 8 806A M Repair exhaust fan in storage room
248106 02/01/2007 116023 2 206 MS Provide current inspection tag for fire extinguisher (x2)
248043 02/01/2007 115914 8 823 MS Provide current inspection tag for fire extinguisher
248044 02/01/2007 115917 9 904 MS Provide current inspection tag for fire extinguisher
217713 02/01/2007 67865 00 0000 FS Provide certification that fire alarm system has been tested and is fully functional - paper work was not avialable for review
248132 04/17/2006 116077 1 117 M Replace safety pin on fire extinguisher
217644 04/17/2006 63487 1 118 M Replace missing exhaust duct for dryer
248127 04/17/2006 116066 1 119 M Mount fire extinguisher at maximum five feet above floor
248122 04/17/2006 116054 3 311 M Replace broken latch on emergency escape window
248115 04/17/2006 116039 3 314 M Secure loose air conditioning grille to ceiling
248166 04/17/2006 116138 5 501 M Replace missing sign for emergency escape window
217769 04/17/2006 63532 5 501 M Repair emergency escape window to stay open
248165 04/17/2006 116136 5 517A M Patch damaged ceiling finish around exhaust fan
248167 04/17/2006 116140 9 901 M Replace burned out light bulbs in light fixtures (flammable storage room )
248047 04/17/2006 115925 P 9712 M Determine cause of water damaged ceiling tiles and replace tiles
248176 04/17/2006 116158 0 O No access was available to 1-122, 5-516, 6-629, 7-705 & 7-706. Please be prepared to access these rooms during the report review meeting.
248136 04/17/2006 116079 1 118A O Prohibit use of extension cord to power microwave, plug microwave directly into wall outlet (custodial office)
248125 04/17/2006 116059 2 201 O Eliminate multiple outlet adaptor behind computer station
248118 04/17/2006 116046 3 304 O Prohibit plugging 13A cord into surge protector, plug surge protector directly into wall outlet
248109 04/17/2006 116026 3 306 O Remove and prohibit use of toaster oven
248110 04/17/2006 116031 3 307 O Remove and prohibit use of toaster oven
248169 04/17/2006 116144 5 120 O Prohibit use of surge protectors to power microwave and toaster oven, plug appliances directly into wall outlet
248163 04/17/2006 116131 5 502 O Eliminate spliced orange extension cord under writing board or replace with minimum 15A cord
248164 04/17/2006 116134 5 502 O Prohibit plugging 13A cord into surge protector, plug surge protector directly into wall outlet
248170 04/17/2006 116146 6 617 O Prohibit use of extension cord with multi-outlet end adjacent to refrigerator
248171 04/17/2006 116148 6 617 O Prohibit plugging surge protector into 13A extension cord and into another surge protector, plug each surge protector directly into wall outlet
248050 04/17/2006 115927 P 9723 O Prohibit plugging 13A cord into surge protector, plug surge protector directly into wall outlet
248074 04/17/2006 115956 P 9726 O Eliminate 13A extension cord for coffee maker or replace with minimum 15A cord
248139 04/17/2006 116087 6 617 C Provide additional outlets to eliminate use of excessive extension cords (see principal)
248175 04/17/2006 116156 8 802 F Replace missing magnetic release hold open device on wall for north fire door between kitchen and dining room
248105 04/17/2006 116021 3 313 MS Replace missing fire extinguisher
248045 04/17/2006 115919 8 810 MS Recharge fire extinguisher
248174 04/17/2006 116154 8 816 MS Remove dog leg hold open device from fire door
248046 04/17/2006 115921 P 9751 MS Provide current inspection tag for fire extinguisher
248168 04/17/2006 116142 9 903 OS Remove storage from electrical room
248161 04/17/2006 116128 5 513 FS Complete installation of heat detector
217802 01/24/2006 67886 00 0000 M Repair roof leaks through out campus
217803 01/24/2006 67882 00 9599 M Trim or remove over grown vegetation within 3 feet of hydrant west of kitchen
234600 01/24/2006 22141 1 118 M Label fire rated door at corridor
234602 01/24/2006 22147 5 506 M Provide label for fire rated door
217770 01/24/2006 67847 5 515 M Replace damaged grille for air conditioning unit on exterior wall along covered walkway
217348 01/24/2006 67848 5 517 M Replace damaged grille for air conditioning unit on exterior wall along covered walkway
234614 01/24/2006 22149 6 624 M Label fire rated door (into corridor)
217349 01/24/2006 67885 8 801 M Repair or replace damaged cover on drinking fountain adjacent to south exit door
234604 01/24/2006 22153 8 802 M Label fire rated doors between kitchen and dining area
234605 01/24/2006 22162 8 814 M Label fire rated door (into corridor)
234599 01/24/2006 22119 00 0000 C Replace glazing in doors with tempered glass, safety glass, or safety plastic throughout campus or provide certification of safety glass
234603 01/24/2006 22128 7 701 C Replace glazing in display window with fire rated glazing or wired glass or provide auto closer on fire door for display cabinet to maintain fire rating along corridor
217647 01/24/2006 63521 8 814 C Provide panic hardware on exit door adjacent to stage or change maximum occupancy of room to be less than 100
234609 01/24/2006 22130 P 4512 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
234610 01/24/2006 22131 P 4597 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
234611 01/24/2006 22132 P 4600 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
234612 01/24/2006 22134 P 798 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
217464 01/24/2006 67891 P 9552 C Paint portable number on exterior walls to be visible to fire rescue personnel
217463 01/24/2006 67890 P 9553 C Paint portable number on exterior walls to be visible to fire rescue personnel
217579 01/24/2006 67889 P 9554 C Paint portable number on exterior walls to be visible to fire rescue personnel
217753 01/24/2006 67888 P 9555 C Paint portable number on exterior walls to be visible to fire rescue personnel
217809 01/24/2006 67887 P 9556 C Paint portable number on exterior walls to be visible to fire rescue personnel
217574 01/24/2006 67892 1 122 OS Remove storage from electrical room
234606 01/24/2006 22076 8 815 CS Provide fire rated door
234607 01/24/2006 22077 8 816 CS Provide fire rated door
234608 01/24/2006 22078 8 820 CS Provide fire rated door
234523 01/24/2006 91814 8 822 CS Provide fire rated door
234524 01/24/2006 91816 8 823 CS Provide fire rated door
217747 10/06/2004 63507 1 118 M Replace missing emergency eye wash
217645 10/06/2004 67881 1 122 M Provide cover on exposed electrical junction box
218088 10/06/2004 67849 3 310 M Determine cause of water damaged ceiling tiles and replace tiles
217404 10/06/2004 67901 3 311 M Repair damaged wall finish adjacent to fire extinguisher cabinet
217372 10/06/2004 67866 3 313 M Mount fire extinguisher at maximum five feet above floor
217614 10/06/2004 63527 5 199 M Replace missing panel on drinking fountain outside 5-501
234601 10/06/2004 22146 5 501A M Change sign for bathroom (which indicates 517A) with sign at bathroom in 5-517 (which indicates 501A)
217991 10/06/2004 67859 5 502 M Adjust door closer to control speed of closing door
217806 10/06/2004 67850 5 511 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to exterior door
218089 10/06/2004 67851 5 512 M Determine cause of water damaged ceiling tiles and replace tiles
217575 10/06/2004 67852 5 515 M Determine cause of water damaged ceiling tiles and replace tiles
217576 10/06/2004 67867 5 516 M Mount fire extinguisher at maximum five feet above floor
217646 10/06/2004 67864 8 802 M Repair light in exit sign at serving line area
217350 10/06/2004 67853 8 802 M Determine cause of water damaged ceiling tiles and replace tiles
218060 10/06/2004 63490 8 806 M Determine cause of water damaged ceiling tiles and replace tiles
217405 10/06/2004 67854 8 806A M Determine cause of water damaged ceiling tiles and replace tiles
218061 10/06/2004 67902 8 810A M Repair damaged wall finish
217807 10/06/2004 67883 8 814A M Post sign limiting occupancy to maximum 9 students
217715 10/06/2004 67855 P 4512 M Determine cause of water damaged ceiling tiles and replace tiles
217808 10/06/2004 67856 P 4597 M Determine cause of water damaged ceiling tiles and replace tiles
217751 10/06/2004 67884 P 4597 M Secure toilet to floor
217578 10/06/2004 67857 P 4600 M Determine cause of water damaged ceiling tiles and replace tiles
217351 10/06/2004 67858 P 798 M Determine cause of water damaged ceiling tiles and replace tiles
218092 10/06/2004 67900 P 798 M Repair exhaust fan in bathroom
234613 10/06/2004 22183 P 798 M Repair or replace deteriorated wood siding
217309 10/06/2004 63510 1 116 O Eliminate extension cord or replace with minimum 15A cord and prohibit plugging extension cord into surge protector
217989 10/06/2004 67861 2 201 O Prohibit plugging one surge protector into another (plug surge protector directly into a wall outlet)
217306 10/06/2004 67862 6 601 O Prohibit plugging one surge protector into another (plug surge protector directly into a wall outlet)
217748 10/06/2004 67863 6 604 O Prohibit use of multi outlet adapter for wall outlet adjacent to door
217755 10/06/2004 63513 7 704 O Eliminate extension cord or replace with minimum 15A cord
217374 10/06/2004 67880 8 814A O Limit room occupancy to 9 occupants
217810 10/06/2004 67876 P 9553 O Remove and prohibit combustible residential foam chairs
217686 10/06/2004 67875 P 9554 O Remove and prohibit combustible residential chair
234176 10/06/2004 91103 5 501A C Change sign for bathroom (which indicaes 517A) with sign at bathroom in 5-517 (which indicates 501A)
218093 10/06/2004 67874 P 9552 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
217754 10/06/2004 67873 P 9553 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
217494 10/06/2004 67872 P 9554 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
217462 10/06/2004 67871 P 9555 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
217772 10/06/2004 67870 P 9556 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
217580 10/06/2004 63491 5 199 MS Repair door at end of corridor between Bldgs. 5 & 6 to open properly
217992 10/06/2004 67877 6 624 MS Remove hold open device from fire door
217375 10/06/2004 67878 8 823 MS Remove hold open device from fire door
217612 10/06/2004 67868 1 118 OS Prohibit storage of gasoline and gas powered leaf blowers, relocate to flammable storage room 9-901
217403 10/06/2004 67869 1 119 OS Prohibit storage of gas powered pressure cleaner, relocate to flammable storage room 9-901
217804 10/06/2004 67897 1 119 OS Remove storage from mechanical room
217346 10/06/2004 67899 1 120 OS Remove storage from hot water heater room
217990 10/06/2004 67893 2 205 OS Remove storage from electrical room
217684 10/06/2004 67894 3 313 OS Remove storage from electrical room
218090 10/06/2004 67895 5 516 OS Remove storage from electrical room
217749 10/06/2004 67898 8 815 OS Remove storage from mechanical room
218091 10/06/2004 67896 9 903 OS Remove and prohibit storage of golf cart in switch gear room
234177 10/06/2004 91105 8 813 CS Provide exit from stage when curtain is closed -- remove lock from one door leading into music room
234615 10/06/2004 22075 8 813 CS Provide exit from stage when curtain is closed - remove lock from one door leading into music room