ADULT EDUCATION CENTER
 
ADULT EDUCATION CENTER
2161 N MILITARY TRAIL
WEST PALM BEACH, 33409
FISH Drill Down
 Campus Info.
 Buildings:10 Rooms:113
 Portables:9
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
373033 04/11/2018 384742 00 0000 M Repair or replace badly rusted doors on metal storage building
419075 04/11/2018 484140 1 0000 M Repair emergency lighting in interior corridor at 1-119 and 1-115
419082 04/11/2018 484154 1 110 M Repair emergency lighting
419083 04/11/2018 484157 1 111 M Repair emergency lighting
419039 04/11/2018 484064 1 111 M Label all circuits on electrical panel. No panel in room
419041 04/11/2018 484068 1 111 M Repair emergency lighting
419084 04/11/2018 484159 1 113C M Secure loose door handle to door
419043 04/11/2018 484073 1 114 M Repair emergency lighting
419086 04/11/2018 484163 1 120 M Repair emergency lighting
419089 04/11/2018 484169 2 101 M Repair emergency lighting
419090 04/11/2018 484171 3 101 M Repair emergency lighting
419091 04/11/2018 484173 3 102 M Repair emergency lighting
305822 04/11/2018 237640 4 102 M Repair sidewalk at entry. Slope on repair is too great. See Building Department for correct repair. On ADA report per Patrick Joyce
419038 04/11/2018 484062 5 0000 M Trim trees off of north side of roof
419065 04/11/2018 484119 5 101 M Repair emergency lighting
419068 04/11/2018 484125 5 102 M Repair emergency lighting
419093 04/11/2018 484177 5 106 M Replace missing fuse in fuse box
419067 04/11/2018 484123 6 102 M Repair emergency lighting
419064 04/11/2018 484117 6 102 M Repair Bard air conditioning system. Not working
419035 04/11/2018 484056 6 102 M Repair emergency lighting
419066 04/11/2018 484121 7 0000 M Secure loose handrail - guardrail for stairs outside of 7-102
419070 04/11/2018 484129 7 101 M Repair emergency lighting
419069 04/11/2018 484127 7 102 M Repair emergency lighting
419072 04/11/2018 484133 8 101 M Repair emergency lighting
419071 04/11/2018 484131 8 102 M Repair emergency lighting
419032 04/11/2018 484050 8 103 M Secure faucet to sink
419033 04/11/2018 484052 8 103 M Repair leaking flush valves on both toilets
419092 04/11/2018 484175 8 105 M Replace missing fuse in fuse box
419034 04/11/2018 484054 P 1346 M Repair emergency lighting
419047 04/11/2018 484082 P 2113 M Straighten support leg for stairs
419045 04/11/2018 484077 P 2113 M Repair emergency lighting
419046 04/11/2018 484079 P 3770 M Repair damaged soffit at stairs
419048 04/11/2018 484084 P 3771 M Repair emergency lighting X 2
419049 04/11/2018 484086 P 3775 M Repair emergency lighting
419051 04/11/2018 484088 P 3775 M Repair rear door to open and close properly. Drags on landing
373040 04/11/2018 384757 P 3775 M Repair or replace deteriorated wood siding
419054 04/11/2018 484095 P 717 M Repair or replace deteriorated wood siding
384157 04/11/2018 408938 P 755 M Repair or replace deteriorated wood siding and seal joints at old repairs
419030 04/11/2018 484046 00 0 O No access was available to the metal storage building at the portables. Please provide access to this building during the report review meeting
419087 04/11/2018 484165 1 104 O Provide clear access to electrical panel
419040 04/11/2018 484066 1 111 O Provide clear access to electrical panel. No panel in room
419031 04/11/2018 484048 1 112 C Post sign indicating primary and secondary evacuation routes in contrasting colors
419073 04/11/2018 484136 00 0000 MS Provide current inspection tag for fire extinguisher in metal storage building west of building 8
419042 04/11/2018 484070 1 111 MS Remove slide bolt from inside of door
419044 04/11/2018 484075 1 115 MS Provide current inspection tag for fire extinguisher
419052 04/11/2018 484092 P 6128 OS Maintain 3 foot clear aisle to rear exit
257016 04/11/2018 135279 3 0000 N/A No violations observed
257017 04/11/2018 135281 4 0000 N/A No violations observed
257019 04/11/2018 135285 6 0000 N/A No violations observed
257020 04/11/2018 135287 7 0000 N/A No violations observed
257021 04/11/2018 135289 8 0000 N/A No violations observed
257008 04/11/2018 135268 P 1346 N/A No violations observed
257006 04/11/2018 135266 P 2113 N/A No violations observed
257007 04/11/2018 135267 P 3770 N/A No violations observed
257009 04/11/2018 135269 P 3771 N/A No violations observed
257010 04/11/2018 135270 P 3775 N/A No violations observed
292187 04/11/2018 208237 P 6128 N/A No violations observed
270791 04/11/2018 162404 P 755 N/A No violations observed
419036 01/11/2018 484058 00 0000 M Repair all emergency lights on exterior walls or remove them
403979 01/11/2018 451606 00 0000 M Repair or replace deteriorated, rotting wood on covered walks throughout campus
419074 01/11/2018 484138 1 101 M Determine cause of water damaged ceiling tiles and replace tiles
345447 01/11/2018 324438 1 102 M Remove raised concrete base where serving area was removed to eliminte tripping hazard. Room used for Custodial storage. Storage is kept on top of raised concrete to eliminate tripping hazard
419088 01/11/2018 484167 2 101 M Determine cause of water damaged ceiling tiles and replace tiles
419037 01/11/2018 484060 5 101A M Label all circuits on electrical panel
419094 01/11/2018 484179 5 106 M Repair leaking toilet supply line
419056 01/11/2018 484099 P 717 M Determine cause of water damaged ceiling tiles and replace tiles
345450 01/11/2018 324442 00 9599 C Modify or improve site drainage at entrance gate to eliminate standing water - see Mr. Williams (custodian)
257014 01/11/2018 135275 1 0000 N/A No violations observed
257015 01/11/2018 135277 2 0000 N/A No violations observed
270786 01/11/2018 162384 5 0000 N/A No violations observed
257012 01/11/2018 135272 P 1361 N/A No violations observed
257011 01/11/2018 135271 P 717 N/A No violations observed
403976 04/19/2017 451597 1 101 M Remove grounding plug from outlet adjacent to west stage stairs
403978 04/19/2017 451601 1 108 M Replace missing screws in electrical panel
403975 04/19/2017 451595 1 109 M Repair emergency lighting
403413 04/19/2017 450384 1 111 M Repair emergency lighting
403977 04/19/2017 451599 1 8087 M Replace missing level support piece under stair landing adjacent to 1-002
403972 04/19/2017 451589 4 102 M Repair broken emergency lighting
403412 04/19/2017 450382 5 103 M Repair emergency lighting
403974 04/19/2017 451593 7 101 M Repair emergency lighting
403973 04/19/2017 451591 8 105 M Remove nails protruding from door frame
403395 04/19/2017 450343 P 1346 M Replace broken electrical outlet covers
403396 04/19/2017 450345 P 1346 M Repair emergency lighting
403398 04/19/2017 450350 P 1361 M Provide bottom rail on stair landing guardrail at 2 inches above floor
403399 04/19/2017 450352 P 2113 M Repair stair door to close properly, too fast
403397 04/19/2017 450348 P 2113 M Provide bottom rail on ramp and stair landing guardrails at 2 inches above floor
403394 04/19/2017 450341 P 3770 M Repair emergency lighting (x2)
403402 04/19/2017 450359 P 3775 M Adjust stair landing to be level with interior portable floor to allow proper function of door
403403 04/19/2017 450361 P 3775 M Repair emergency lighting
403404 04/19/2017 450363 P 6128 M Repair emergency lighting at south door
403405 04/19/2017 450365 P 6128 M Provide bottom rail on ramp landing guardrail at 2 inches above floor
403400 04/19/2017 450354 P 717 M Provide bottom rail on stair and ramp landing guardrails at 2 inches above floor
403401 04/19/2017 450357 P 717 M Determine cause of water damaged ceiling tiles and replace tiles
403616 04/19/2017 450825 1 111 O Prohibit white 13A extension cord adjacent to router or replace with minimum 15A single outlet extension cord
403410 04/19/2017 450376 6 101 O Prohibit plugging surge protector into surge protector, adjacent to teachers desk
403411 04/19/2017 450380 6 101 O Prohibit use of white 13A extension cord adjacent to teachers desk or replace with minimum 15A single outlet extension cord
403406 04/19/2017 450367 6 102 O Remove and prohibit air freshener (pop up style)
403407 04/19/2017 450370 6 102 O Prohibit use of multi outlet extension cords (green and white) in classroom and storage closet or replace with minimum 15A single outlet cords
403408 04/19/2017 450372 6 102A O Prohibit running electrical cords under door into 6-102
403746 04/19/2017 451110 1 115 OS Keep area clear at emergency escape window
403409 04/19/2017 450374 6 102 OS Remove and prohibit use of toaster oven
384142 01/11/2017 408902 5 0000 M Remove vegetation growing from covered walkway soffit adjacent to 5-102
384159 01/11/2017 408942 P 1346 M Remove vegetation growing between ramp and portable exterior
384154 01/11/2017 408932 P 717 M Remove vegetation growing between ramp and portable exterior
384126 01/22/2016 408869 00 9599 M Secure loose bottom or ramp at west end of Bldg. 1 and adjacent to Bldg. 7
384129 01/22/2016 408875 1 0000 M Repair emergency lighting in corridor adjacent to 1-112
384148 01/22/2016 408917 1 0000 M Remove vegetation growing adjacent to exterior stair handrail outside north corridor exit doors adjacent to 1-108
384149 01/22/2016 408920 1 101 M Repair emergency lighting on south wall
384150 01/22/2016 408923 1 101 M Secure loose electrical outlet box to wall adjacent to drinking fountains
384151 01/22/2016 408926 1 106 M Secure loose screen to vent above door in old boiler room
373000 01/22/2016 384670 1 112 M Determine cause of water damaged ceiling tiles and replace tiles
384128 01/22/2016 408873 1 117 M Repair emergency lighting
384127 01/22/2016 408871 1 120 M Repair door to open and close properly - door rubs on frame
384130 01/22/2016 408877 2 0000 M Secure loose guardrail facing 2-101
384136 01/22/2016 408891 2 102 M Replace deteriorated wood panel around AC unit
384140 01/22/2016 408898 3 103 M Repair emergency lighting
384137 01/22/2016 408893 3 104 M Patch hole in ceiling
384138 01/22/2016 408895 3 106 M Patch hole in ceiling
384135 01/22/2016 408888 5 102 M Replace deteriorated wood panel around AC unit
384143 01/22/2016 408905 7 0000 M Secure loose guardrail adjacent to 7-102
384144 01/22/2016 408908 7 103 M Repair light switch to work properly. Light fixture does not stay on
384132 01/22/2016 408881 8 101 M Replace deteriorated wood panel around AC unit
384134 01/22/2016 408885 8 102 M Replace deteriorated wood panel around AC unit
384146 01/22/2016 408913 8 102 M Repair emergency lighting
384145 01/22/2016 408911 8 104 M Repair door to open and close properly - door rubs on frame
384158 01/22/2016 408940 P 1346 M Repair or replace deteriorated wood siding
384160 01/22/2016 408944 P 1361 M Remove vegetation growing between ramp and portable exterior
384162 01/22/2016 408948 P 1361 M Repair damaged flooring and rotted subflooring adjacent to stair and ramp doors
384163 01/22/2016 408950 P 1361 M Secure communications junction box to wall adjacent to teacher desk
384155 01/22/2016 408934 P 2113 M Secure hanging heat detector
384192 01/22/2016 409010 P 3775 M Provide adequate support under ramp posts to eliminate bounciness along ramp
384161 01/22/2016 408946 P 3775 M Remove vegetation growing between ramp and portable exterior
384153 01/22/2016 408930 P 6128 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to AC unit
384191 01/22/2016 409008 P 717 M Provide adequate support under ramp posts to eliminate bounciness along ramp
384156 01/22/2016 408936 P 755 M Repair emergency lighting
384152 01/22/2016 408928 1 101A O Provide cover strip for electrical cord running across floor for projector at platform and secure cover strip to flooring to eliminate trip hazard
384147 01/22/2016 408915 1 113C MS Replace missing door lever on bathroom door
372996 03/30/2015 384656 1 0000 M Secure loose handrail on Northeast exterior stairway on Building 1
373006 03/30/2015 384683 1 0000 M Repair emergency lighting in exterior walkway between Building 1 and 5 adjacent to 1-115
373043 03/30/2015 384760 1 101 M Repair or replace damaged wood doors on cafeteria
372997 03/30/2015 384665 1 111 M Determine cause of water damaged ceiling tiles and replace tiles
373001 03/30/2015 384674 1 114 M Repair emergency lighting
372998 03/30/2015 384667 1 119 M Repair emergency lighting
373008 03/30/2015 384688 3 0000 M Repair emergency lighting in exterior walkway adjacent to 3-106
373009 03/30/2015 384692 3 104 M Repair damaged plastic laminate on bathroom stall door
373011 03/30/2015 384695 4 102 M Repair door to close properly
373014 03/30/2015 384698 5 0000 M Repair emergency lighting in exterior walkway adjacent to 5-107
373018 03/30/2015 384710 5 101 M Repair or replace damaged entrance door (door has a hole at the inside bottom of door)
373023 03/30/2015 384721 6 101 M Repair or replace damaged entrance door
373026 03/30/2015 384726 6 101 M Repair emergency lighting
373027 03/30/2015 384730 7 0000 M Repair emergency lighting in walkway adjacent to 7-103
373028 03/30/2015 384733 8 104 M Repair or replace damaged door on men's bathroom
270788 03/30/2015 162392 P 1346 M Modify existing foundations and anchorage to comply with engineering requirements
373032 03/30/2015 384739 P 3770 M Repair stair door to close properly
373039 03/30/2015 384753 P 3775 M Repair ramp door to close properly
373030 03/30/2015 384735 P 6128 M Determine cause of water damaged ceiling tiles and replace tiles
373037 03/30/2015 384746 P 717 M Replace broken vinyl floor tiles at ramp door
373004 03/30/2015 384678 1 115 O Prohibit plugging surge protector into surge protector at teachers desk
359394 12/10/2014 355162 1 102 M Patch hole in ceiling where kitchen hood was removed
359398 12/10/2014 355171 5 108 M Patch hole in ceiling adjacent to heat detector
270783 07/15/2014 162374 1 0000 CS Make corridor fire rated (citation removed under new evaluation system and Tom Hogarth wants this facility to be classified as a business occupancy.)
270784 06/26/2014 162376 1 0000 C Adjust steps to make risers equal for exterior stairs north of 1-108 (citation waived by T. Hogarth, 6-26-14)
270782 06/26/2014 162372 1 0000 C Adjust steps to make risers equal at both east entry stairs (citation waived as per T. Hogarth, 6-26-14)
359382 03/11/2014 355141 1 0000 M Secure loose handrails on North exterior stairs on east side of Building 1
359383 03/11/2014 355143 1 111 M Replace missing heat detector above fire alarm panel (base for heat detector is there, but the detector is missing)
359384 03/11/2014 355145 1 111 M Determine cause of water damaged ceiling tiles and replace tiles
359385 03/11/2014 355147 1 112 M Repair emergency lighting above entrance door
359387 03/11/2014 355149 1 112 M Determine cause of water damaged ceiling tiles and replace tiles
359389 03/11/2014 355154 1 118 M Determine cause of water damaged ceiling tiles and replace tiles
359395 03/11/2014 355166 4 101 M Repair emergency lighting
359399 03/11/2014 355175 8 0000 M Secure loose handrail on exterior stairs west side of Building 8
359413 03/11/2014 355200 P 3770 M Repair emergency lighting at stair door
359410 03/11/2014 355196 P 3771 M Repair emergency lighting at stair door
359403 03/11/2014 355181 P 717 M Repair emergency lighting
359407 03/11/2014 355186 P 755 M Repair ramp door to close properly
359408 03/11/2014 355192 P 755 M Determine cause of water damaged ceiling tiles and replace tiles
359417 03/11/2014 355205 1 109 O Eliminate and prohibit use of white, multiple outlet extension cord under desk next to windows
359401 03/11/2014 355177 00 0000 MS Provide current inspection tag for fire extinguisher inside metal flammable storage building west side of Building 8
359390 03/11/2014 355156 1 119 MS Provide current inspection tag for fire extinguisher
359396 03/11/2014 355169 4 102 MS Recharge fire extinguisher
306207 12/09/2013 238464 8 106 M Eliminate termites and repair termite damage
306179 12/09/2013 238403 P 3770 M Clean out rain gutters and replace missing downspout
345446 12/09/2013 324436 P 717 M Replace termite damaged exterior window sill along ramp
345444 02/26/2013 324432 00 0000 M Replace missing lens on light fixture in metal storage Bldg. adjacent to P-602
345299 02/26/2013 324120 1 003 M Repair emergency lighting in corridor adjacent to 1-109
345301 02/26/2013 324124 1 109 M Repair emergency lighting adjacent to principal's office
345303 02/26/2013 324128 1 113 M Repair emergency lighting
345298 02/26/2013 324118 1 117 M Repair emergency lighting
345302 02/26/2013 324126 1 118 M Repair emergency lighting
345300 02/26/2013 324122 1 120 M Repair emergency lighting
345306 02/26/2013 324134 3 103 M Repair emergency lighting
345307 02/26/2013 324136 3 104 M Repair or replace damaged emergency lighting
345445 02/26/2013 324434 5 104 M Make necessary repairs to soft spots in subflooring - replace cracked and missing tiles
345296 02/26/2013 324114 5 105 M Repair emergency lighting in police office
345448 02/26/2013 324440 6 0000 M Seal wide gap to eliminate trip hazard in concrete sidewalk between classrooms 6-101 & 5-101
345314 02/26/2013 324150 7 101 M Repair emergency lighting
345315 02/26/2013 324152 8 102 M Repair emergency lighting
345316 02/26/2013 324154 8 104 M Repair emergency lighting
345318 02/26/2013 324158 P 1346 M Remove vegetation growing between ramp and portable
345309 02/26/2013 324140 P 3770 M Replace missing ceiling tile above electrical panel
345311 02/26/2013 324144 P 755 M Determine cause of water damaged ceiling tiles and replace tiles above writing board and adjacent to closet door
345313 02/26/2013 324148 1 111A O Eliminate extension cord with multiple outlet end or replace with a surge protector
345305 02/26/2013 324132 2 101 O Prohibit plugging surge protector into surge protector under computer stations adjacent to door - plug each surge protector directly into wall outlet
345308 02/26/2013 324138 4 102 O Prohibit plugging surge protector into surge protector under computer stations adjacent to door - plug each surge protector directly into wall outlet
345319 02/26/2013 324160 P 1346 O Relocate storage to provide clear access to electrical panel
345310 02/26/2013 324142 P 6128 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
305820 02/26/2013 237633 1 101 C Make exterior walkway level with interior floor. (2 exits to exterior - at east and SW exits) (NA - on ADA report)
305821 02/26/2013 237635 1 108 C Make exterior walkway level with interior floor. (Exit to exterior) (NA - on ADA report)
270793 02/26/2013 162411 3 103 C Make exterior walkway level with interior floor (NA - on ADA report)
270794 02/26/2013 162413 3 104 C Make exterior walkway level with interior floor (NA - on ADA report)
270787 02/26/2013 162386 6 101 C Make exterior walkway level with interior floor (NA - on ADA report)
270796 02/26/2013 162417 7 101 C Make exterior walkway level with interior floor (NA - on ADA report)
270798 02/26/2013 162421 8 103 C Make exterior walkway level with interior floor (NA - on ADA report)
270799 02/26/2013 162423 8 104 C Make exterior walkway level with interior floor (NA - on ADA report)
345297 02/26/2013 324116 1 0000 MS Remove hold open device from corridor doors: 1-109(x2), 1-119, 1-118, 1-112, 1-114 & 1-115
345295 02/26/2013 324112 1 101 OS Relocate table to maintain 3 ft clear aisle to east exit door
345304 02/26/2013 324130 1 114 OS Relocate computer station to provide clear access to fire extinguisher
345317 02/26/2013 324156 5 102 OS Relocate file cabinet to maintain 3 ft clear aisle to exit door
345294 02/26/2013 324110 1 119 CS Provide auto closer on corridor door
345312 02/26/2013 324146 1 122 CS Provide auto closer on corridor door
305827 11/28/2012 237651 00 0000 M Modify or improve site drainage to eliminate standing water at south end of parking lot
336215 11/28/2012 304493 00 0000 M Fill holes in ground and undermined area of concrete sidewalk between 4-105 and 6-101
306069 11/28/2012 238174 P 755 M Modify or improve drainage at portable to eliminate standing water at stairs
336230 11/28/2012 304525 00 0000 C Turn barbs down on fencing around tank adjacent to 1-121
306078 11/28/2012 238191 1 101 C Provide guardrail at minimum of 42 inches all around stage used as a classroom or do not use stage as classroom
270792 11/28/2012 162408 3 102 C Make exterior walkway level with interior floor
270797 11/28/2012 162419 8 101 C Make exterior walkway level with interior floor
336251 04/24/2012 304569 00 0000 M Repair/remove rust on tank in courtyard adjacent to 1-121 (Previously tank was used for water storage, no longer in use, surrounding gate will be kept locked, tank poses no threat)
336224 04/24/2012 304511 1 002 M Repair emergency lighting in covered walk across from 5-105
336238 04/24/2012 304541 1 101 M Repair emergency lighting
336233 04/24/2012 304531 1 102 M Replace type K fire extinguisher with ABC fire extinguisher, adjacent to 1-104. Kitchen not is use
336234 04/24/2012 304533 1 102 M Repair emergency lighting adjacent to 1-104
336231 04/24/2012 304527 1 103 M Repair broken emergency lighting
336232 04/24/2012 304529 1 106 M Provide cover on exposed electrical junction box behind hot water heaters
336226 04/24/2012 304516 1 110 M Repair emergency lighting
336225 04/24/2012 304514 1 115 M Repair emergency lighting
336228 04/24/2012 304521 1 121 M Repair broken emergency lighting
336199 04/24/2012 304459 2 101 M Repair emergency lighting
336200 04/24/2012 304461 2 101 M Seal open area on wall at clock
336204 04/24/2012 304470 3 001 M Repair uneven concrete walk adjacent to 3-103
336201 04/24/2012 304463 3 101 M Repair emergency lighting
336202 04/24/2012 304465 3 102 M Repair emergency lighting
336203 04/24/2012 304468 3 103 M Replace missing base tiles along wall
336206 04/24/2012 304475 3 105 M Fill void in electrical panel
336239 04/24/2012 304543 3 106 M Provide cover for openings in wall and ceiling
336205 04/24/2012 304472 4 001 M Repair uneven concrete walk adjacent to 4-101
336207 04/24/2012 304477 4 001 M Repair emergency lighting adjacent to 4-101
336214 04/24/2012 304491 4 104 M Repair light fixture, lights do not turn on
336213 04/24/2012 304489 4 105 M Repair light fixture, lights do not turn on
336220 04/24/2012 304503 5 001 M Repair emergency lighting adjacent to 5-108
336221 04/24/2012 304505 5 001 M Remove plants/trees growing from covered walk adjacent to 5-102
336223 04/24/2012 304509 5 104 M Replace broken floor tile
336222 04/24/2012 304507 5 107 M Provide cover for exposed electrical outlet at A/C outlet
336218 04/24/2012 304499 6 001 M Repair loose handrail on stairs west of 6-102
336219 04/24/2012 304501 6 002 M Repair emergency lighting
336217 04/24/2012 304497 6 102A M Fill void in electrical panel
336235 04/24/2012 304535 8 001 M Repair emergency lighting in corridor adjacent to 8-105
336236 04/24/2012 304537 8 101 M Repair emergency lighting
336247 04/24/2012 304560 P 1346 M Clean gutters on portable
336248 04/24/2012 304562 P 1361 M Repair emergency lighting
336249 04/24/2012 304564 P 1361 M Provide adequate support under ramp posts to prevent bounciness along ramp
336250 04/24/2012 304566 P 2113 M Repair emergency lighting
336210 04/24/2012 304483 P 3770 M Repair ramp door to close and latch properly
336211 04/24/2012 304485 P 3770 M Determine cause of water damaged ceiling tiles and replace tiles
336240 04/24/2012 304545 P 3771 M Determine cause of water damaged ceiling tiles and replace tiles
336241 04/24/2012 304547 P 3771 M Repair emergency lighting
336242 04/24/2012 304549 P 3771 M Provide adequate support under ramp posts to prevent bounciness along ramp
336216 04/24/2012 304495 P 6128 M Determine cause of water damaged ceiling tiles and replace tiles
336243 04/24/2012 304551 P 755 M Secure loose handrail at middle landing on ramp
336244 04/24/2012 304553 P 755 M Determine cause of water damaged ceiling tiles and replace tiles
336245 04/24/2012 304556 P 755 M Remove nail protruding from threshold at ramp door to allow door to open properly,
336246 04/24/2012 304558 P 755 M Repair stair door to close and latch properly
336227 04/24/2012 304518 1 110 O Prohibit plugging surge protector into orange extension cord at desk adjacent to window
336208 04/24/2012 304479 4 101 O Prohibit plugging surge protector into surge protector adjacent to teachers desk
336237 04/24/2012 304539 00 0000 MS Provide current inspection tag for fire extinguisher in shed west of building 8
336198 04/24/2012 304457 1 004 OS Prohibit sign on exterior doors adjacent to 1-113 reading No Exit, sign may read Emergency Exit Only
336229 04/24/2012 304523 1 121 OS Prohibit storage of lighter fluid
336209 04/24/2012 304481 4 102 OS Relocate desk to maintain clear aisle to exit
336212 04/24/2012 304487 P 3770 FS Secure hanging heat detector
321309 03/05/2012 271528 P 1346 M Repair hole in floor adjacent to stair door
306140 03/05/2012 238316 P 2113 M Provide weatherstriping or raise threshold to seal opening at bottom of ramp door
270779 03/05/2012 162366 00 9500 C Provide covered walkway to portables
270790 07/20/2011 162396 P 1361 M Modify existing foundations and anchorage to comply with engineering requirements
270800 07/20/2011 162425 P 2113 M Modify existing foundations and anchorage to comply with engineering requirements
270801 07/20/2011 162427 P 3770 M Modify existing foundations and anchorage to comply with engineering requirements
270805 07/20/2011 162436 P 3771 M Modify existing foundations and anchorage to comply with engineering requirements
270802 07/20/2011 162429 P 3775 M Modify existing foundations and anchorage to comply with engineering requirements
270804 07/20/2011 162433 P 717 M Modify existing foundations and anchorage to comply with engineering requirements
243920 07/20/2011 107332 P 755 M Modify existing foundations and anchorage to comply with engineering requirements
321318 04/18/2011 271547 1 106 M Secure exposed wires on hot water heater (no longer in use, gas line disconnected)
321319 04/18/2011 271549 1 106 M Strong gas smell present, verify that hot water heater is in proper working order (no longer in use, gas line disconnected)
321095 04/18/2011 271066 1 110 M Repair emergency lighting
321101 04/18/2011 271079 1 117 M Repair emergency lighting
321092 04/18/2011 271056 1 119 M Repair/secure ADA handle on door, handle is loose making door difficult to open
321316 04/18/2011 271543 2 101 M Repair emergency lighting
321300 04/18/2011 271508 5 101 M Repair emergency lighting
321288 04/18/2011 271458 5 8087 M Repair emergency lighting in exterior corridor adjacent to 5-107
321302 04/18/2011 271512 6 8087 M Repair emergency lighting in exterior corridor adjacent to 6-103
321083 04/18/2011 271041 7 102 M Repair emergency lighting
321077 04/18/2011 271023 8 103 M Secure plumbing access panel on wall behind toilet
321081 04/18/2011 271037 8 103 M Repair emergency lighting
321080 04/18/2011 271028 8 8087 M Repair emergency lighting in exterior corridor adjacent to 8-105
306154 04/18/2011 238327 P 2113 M Repair damaged east interior wall adjacent to windows
321312 04/18/2011 271534 P 3770 M Repair emergency lighting
321304 04/18/2011 271515 P 3775 M Repair emergency lighting
321310 04/18/2011 271530 P 755 M Repair emergency lighting
321097 04/18/2011 271071 1 0000 O Post signs indicating primary and secondary evacuation routes for student occupied areas
321320 04/18/2011 271551 1 104 O No access was available to this room. Please be prepared to access this room during the report review meeting
321086 04/18/2011 271045 1 108 O Prohibit plugging grey extension cord into surge protector @ reception/main desk. 15A single outlet extension cord may be plugged directly into permanent electrical outlet
321087 04/18/2011 271048 1 108 O Prohibit plugging surge protector into grey extension cord, adjacent to American Flag
321074 04/18/2011 271018 1 109B O Prohibit plugging surge protector into surge protector (wall mounted square surge protector)
321094 04/18/2011 271062 1 111 O Prohibit plugging microwave into surge protector, plug directly into permanent electrical outlet, adjacent to 1-111A
321100 04/18/2011 271076 1 122 O No access was available to this room. Please be prepared to access these rooms during the report review meeting
321315 04/18/2011 271541 4 102 O Prohibit white 13A extension cord or replace with minimum 15A cord
321299 04/18/2011 271506 5 104 O Prohibit white 13A extension cord or replace with minimum 15A cord
321103 04/18/2011 271082 5 104 O Prohibit plugging surge protector into extension cord
321301 04/18/2011 271510 6 101 O Prohibit plugging surge protector into surge protector
321082 04/18/2011 271039 8 101 O Prohibit white 13A extension cord or replace with minimum 15A cord
321313 04/18/2011 271536 P 3770 O Prohibit plugging surge protector into orange extension cord
271639 04/18/2011 164314 00 9698 C Provide crosswalks from student / visitor parking area to sidewalks
321321 04/18/2011 271553 1 111 F Provide current inspection report for Fire Alarm
321072 04/18/2011 271014 1 109 MS Provide current inspection tag for fire extinguisher
321096 04/18/2011 271069 8 102 MS Provide current inspection tag for fire extinguisher
321311 04/18/2011 271532 P 0000 MS Provide current inspection tags for fire extinguishers in portables
321317 04/18/2011 271545 1 103 OS Remove and prohibit use of space heater
321073 04/18/2011 271016 1 109 OS Prohibit running electrical cords under carpet
321098 04/18/2011 271073 1 112 OS Prohibit running electrical cord under carpet
321314 04/18/2011 271539 4 102 OS Maintain clear aisle to exit
305801 01/14/2011 237591 3 103 M Anchor toilets to floor
306197 01/14/2011 238448 P 717 M Replace rotted east exterior siding
306070 01/14/2011 238176 P 755 M Seal seam in vinyl flooring
270795 01/14/2011 162415 4 102 C Make exterior walkway level with interior floor
257013 01/14/2011 135273 P 471 N/A No violations observed
305825 03/23/2010 237647 00 0000 M Repair uneven sidewalk on covered walkway between Bldgs. 3 & 4
305826 03/23/2010 237649 00 0000 M Repair uneven sidewalk on covered walkway between Bldgs. 4 & 5
305817 03/23/2010 237627 1 0000 M Repair drinking fountain in interior corridor adjacent to 1-113A to work
305804 03/23/2010 237598 1 0000 M Secure loose handrail for stairs adjacent to 1-121
305812 03/23/2010 237615 1 0000 M Repair emergency lighting in exterior corridor adjacent to 1-115
306109 03/23/2010 238260 1 0000 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to 1-109
306123 03/23/2010 238263 1 0000 M Repair inoperable low drinking fountain in interior corridor adjacent to 1-120
306073 03/23/2010 238183 1 110 M Repair emergency lighting
306072 03/23/2010 238181 1 111 M Repair emergency lighting
305813 03/23/2010 237617 3 0000 M Repair emergency lighting in exterior corridor adjacent to 3-101
305799 03/23/2010 237586 3 103 M Repair hole in ceiling
305828 03/23/2010 237653 4 0000 M Repair emergency lighting in exterior walkway adjacent to 4-101
306071 03/23/2010 238179 4 102 M Repair emergency lighting
306074 03/23/2010 238185 5 102 M Repair emergency lighting
306068 03/23/2010 238172 5 103 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to windows
305818 03/23/2010 237629 5 103 M Eliminate bees. See teacher
292184 03/23/2010 208233 6 0000 M Repair emergency lighting in covered walkway adjacent to 6-103
306079 03/23/2010 238196 8 0000 M Repair emergency lighting in exterior corridor adjacent to 8-106
306128 03/23/2010 238296 P 1361 M Adjust rear door to latch properly
306132 03/23/2010 238307 P 1361 M Make bottom of ramp level with sidewalk
306135 03/23/2010 238311 P 2113 M Make bottom of ramp level with sidewalk
306187 03/23/2010 238427 P 3775 M Repair emergency lighting
306195 03/23/2010 238445 P 6128 M Remove flammable wall covering
306200 03/23/2010 238454 P 755 M Determine cause of water damaged ceiling tiles and replace tiles
305806 03/23/2010 237601 00 0 O No access was available to 1-122, 2-103 and 3-106. Please be prepared to access these rooms during the report review meeting.
306075 03/23/2010 238187 1 111 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
305815 03/23/2010 237621 2 101 O Prohibit plugging surge protector into extension cord
305819 03/23/2010 237631 5 104 O Prohibit plugging microwave and refrigerator into extension cord - plug directly into permanent electrical outlet
306184 03/23/2010 238416 P 3770 C Provide bottom rail on ramp and stair landing guardrail at two inches above floor
306201 03/23/2010 238456 00 0000 MS Provide current inspection tag for fire extinguisher in metal shed west of building 8
306076 03/23/2010 238189 1 101 OS Maintain clear aisle to NE exit
305811 03/23/2010 237611 1 114 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station
305814 03/23/2010 237619 4 101 OS Keep door unlocked when facility is occupied to access fire extinguisher
305824 03/23/2010 237645 4 102 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station and fire extinguisher
305816 03/23/2010 237624 7 102 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station
306190 03/23/2010 238431 P 3775 OS Provide clear access to fire extinguisher
306193 03/23/2010 238437 P 6128 OS Maintain clear aisle to rear exit
306198 03/23/2010 238451 P 717 OS Maintain clear aisle to rear exit
305823 03/23/2010 237642 1 114 CS Provide auto closer on corridor door
306185 03/23/2010 238424 P 3770 FS Secure hanging heat detector
270785 12/15/2009 162378 2 101 C Make exterior walkway level with interior floor
292174 04/06/2009 208210 1 109 M Repair emergency lighting
292175 04/06/2009 208212 1 110 M Repair emergency lighting
292177 04/06/2009 208216 1 117 M Replace missing wall tile above urinal in mens bathroom
292181 04/06/2009 208225 4 0000 M Repair emergency lighting in covered walkway adjacent to 4-101
292183 04/06/2009 208231 5 107 M Provide cover on exposed electrical junction box in ceiling
292178 04/06/2009 208218 7 0000 M Repair emergency lighting in covered walkway adjacent to 7-103
292180 04/06/2009 208222 P 3775 M Repair stair door to close properly
292179 04/06/2009 208220 P 755 M Adjust stair door to latch properly
292182 04/06/2009 208227 2 102 O Prohibit plugging surge protector into surge protector @ teachers desk
270777 04/06/2009 162362 00 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
270780 04/06/2009 162368 00 9599 C Turn barbs down on all fencing
292185 04/06/2009 208235 1 121 MS Provide current inspection tag for fire extinguisher
292176 04/06/2009 208214 1 108A FS Provide heat detector in room used for storage
284066 12/10/2008 190906 1 101A C Provide handicapped accessibility to stage
270789 12/10/2008 162394 P 1346 C Modify or replace stair with stair minimum 44" wide
270781 02/15/2008 162370 00 9598 C Provide adequate handicapped parking on west side of cafeteria; existing three spaces do not meet code requirements
270778 01/28/2008 162364 00 0000 M Provide non-slip surface for wood ramp between Buildings 1&7
271647 01/28/2008 164330 00 0000 M Repair doors to metal storage building adjacent to P-602 to open and close properly
271645 01/28/2008 164326 1 0000 M Repair emergency lighting in interior corridor adjacent to 1-115 (106)
271640 01/28/2008 164316 8 104 M Repair emergency lighting in men's bathroom
271649 01/28/2008 164334 1 109 O Prohibit piggy backing surge protectors and extension cords under desks in front office
271644 01/28/2008 164324 1 111A O Eliminate brown extension cord or replace with minimum 15A cord
271646 01/28/2008 164328 5 104 O Eliminate (6) plug outlet adaptor adjacent to teacher's desk or replace with a surge protector
271648 01/28/2008 164332 1 109 C Provide outlets adjacent to desks in front office to eliminate use of excessive extension cords
271641 01/28/2008 164318 1 101 OS Remove partition blocking access to north exit door adjacent to stage
271642 01/28/2008 164320 2 101A FS Secure hanging heat detector
271643 01/28/2008 164322 P 3770 FS Secure hanging heat detector
270803 09/17/2007 162431 P 471 M Modify existing foundations and anchorage to comply with engineering requirements
256984 02/20/2007 135219 1 0000 M Secure loose handrail for stairs adjacent to 1-109
187685 02/20/2007 8187 1 002 M Replace missing center handrail for steps (adjacent to 5-105)
256988 02/20/2007 135227 1 109 M Repair emergency lighting
256985 02/20/2007 135221 1 112 M Repair emergency escape window to stay open
242807 02/20/2007 105131 1 112 M Determine cause of water damaged ceiling tiles and replace tiles
256990 02/20/2007 135231 1 118 M Reinstall emergency escape sign for escape window. Sign came off of wall and is on top of shelf adjacent to emergency escape window
256989 02/20/2007 135229 1 120 M Repair door to open and close properly
256987 02/20/2007 135225 1 121 M Repair emergency lighting
256991 02/20/2007 135233 5 101 M Determine cause of water damaged ceiling tiles and replace tiles
242854 02/20/2007 105229 5 101 M Replace missing ceiling tiles
242843 02/20/2007 105206 5 102 M Replace missing ceiling tiles
256995 02/20/2007 135241 5 102 M Eliminate 2 wasp nests in west windows
256998 02/20/2007 135247 6 101A M Secure loose ceiling tiles in closet
256992 02/20/2007 135235 P 1346 M Determine cause of water damaged ceiling tiles and replace tiles
257002 02/20/2007 135257 P 717 M Determine cause of water damaged ceiling tiles and replace tiles
256982 02/20/2007 135215 00 0 O No access was available to 1-111B, 2-101A, 2-103, 3-106, 4-104, P-3775 (P-607)and metal storage building adjacent to portables. Please be prepared to access these rooms during the report review meeting.
257000 02/20/2007 135253 P 3770 O Clean leaves and mold off of stairs
256983 02/20/2007 135217 1 109A C Provide additional electric outlets to eliminate need for extension cords
257001 02/20/2007 135255 P 3775 C Complete roof installation
256994 02/20/2007 135239 5 107 MS Provide current inspection tag for fire extinguisher
256999 02/20/2007 135251 7 101 MS Replace missing fire extinguisher
256997 02/20/2007 135245 P 471 MS Provide current inspection tag for fire extinguisher
256996 02/20/2007 135243 4 105 FS Secure heat detector to ceiling
242836 03/23/2006 105184 00 0000 M Repair damaged chain link fencing on east side of Building 2, at exterior stairway adjacent to 2-101
242839 03/23/2006 105196 00 0000 M Repair broken sidewalk caused by uprooted tree, east side of Building 2
242841 03/23/2006 105201 00 0000 M Repair uneven sidewalk between Building 3 & 4
187681 03/23/2006 30866 00 9599 M Repair uneven sidewalk in courtyard adjacent to 1-121 and adjacent to old fuel tanks
242815 03/23/2006 105141 1 0000 M Repair exterior corridor door @ steps adjacent to 1-108 to close and latch properly
242819 03/23/2006 105152 1 0000 M Repair exterior corridor door at south side of 1-108 to close and latch properly
242830 03/23/2006 105180 2 101 M Replace missing ceiling tiles
242858 03/23/2006 105235 8 0000 M Repair emergency lighting in covered walkway adjacent to 8-104
242873 03/23/2006 105263 8 0000 M Repair emergency lighting in covered walkway adjacent to 8-106
242869 03/23/2006 105256 8 105 M Fill voids in electric panel (three blank fuse holes)
242891 03/23/2006 105309 P 1361 M Replace hurricane damaged steel siding on south side of portable
242892 03/23/2006 105311 P 2113 M Repair emergency lighting
242893 03/23/2006 105313 P 2113 M Adjust steps to make risers equal
242894 03/23/2006 105315 P 2113 M Provide cover on bare electrical wiring hanging out of metal siding on the north side of portable
242880 03/23/2006 105282 P 3770 M Replace missing ceiling tiles
242896 03/23/2006 105319 P 3775 M Replace missing ceiling tiles
242895 03/23/2006 105317 P 717 M Determine cause of water damaged ceiling tiles and replace tiles
242888 03/23/2006 105298 P 755 M Repair damaged rain gutter on south side of portable (ramp side)
242889 03/23/2006 105305 P 755 M Secure bottom of stairway to concrete walk
233395 03/23/2006 89599 1 108A O Eliminate surge protector powering coffee pot
242806 03/23/2006 105129 1 110 O Eliminate multiple 13 amp extension cords and three way adaptor plugged into outlet
242890 03/23/2006 105307 P 1346 O Provide clear access to electrical panel
242809 03/23/2006 105135 00 0000 MS Provide current inspection tag for fire extinguishers throughout entire campus, last inspection 04-2004.
242810 03/23/2006 105137 1 119 OS Provide clear access to fire extinguisher
233412 11/14/2005 89634 00 9599 M Repair hurricane damaged chain link fencing north of parking lot
233402 11/14/2005 89613 00 9599 M Repair broken sidewalk between Buildings 6 and 8
242808 11/14/2005 105133 1 0000 M Secure loose handrails on exterior stair adjacent to 1-113
233397 11/14/2005 89603 1 105 M Replace plastic dryer vent with metal vent pipe
233393 11/14/2005 89595 1 117 M Replace missing wall tiles @ end urinal in boy's bathroom
242851 11/14/2005 105223 5 108 M Patch hole on ceiling in janitors closet
187704 11/14/2005 8166 P 471 C Modify ramp to be minimum 44 inches wide
187718 11/14/2005 8179 P 717 C Modify ramp to be minimum 44 inches wide
242829 11/14/2005 105165 1 102 FS Provide heat detector in room used for storage (old kitchen now used as a storage room)
187679 02/22/2005 30859 00 9599 M Remove pile of metal ramp parts from parking lot
233396 02/22/2005 89601 1 0000 M Repair emergency light outside south entrance of room 1-101
233394 02/22/2005 89597 1 102 M Repair emergency lighting
187686 02/22/2005 30854 1 106 M Provide current inspection log for boilers (latest date: Aug. 2002)
233420 02/22/2005 89652 1 112 M Repair or replace old stained, worn and rippled carpeting
187689 02/22/2005 30869 1 118 M Repair emergency escape window to stay open
233421 02/22/2005 89654 1 119 M Repair or replace old stained, worn and rippled carpeting
233398 02/22/2005 89605 1 121 M Repair emergency lighting
187692 02/22/2005 30837 2 101 M Repair emergency lighting
233399 02/22/2005 89607 5 103 M Repair emergency lighting
233401 02/22/2005 89611 6 101 M Repair emergency lighting
187700 02/22/2005 30829 7 102 M Secure loose ceiling tiles and loose crown molding above chalk writing board
233403 02/22/2005 89615 8 0000 M Repair emergency lighting in corridor @ room 8-106
233404 02/22/2005 89618 8 0000 M Repair emergency light in corridor @ room 8-105
233406 02/22/2005 89622 P 1346 M Repair ramp door to latch properly
233407 02/22/2005 89624 P 1361 M Repair emergency lighting
187713 02/22/2005 30857 P 1361 M Provide sign indicating ?Fire Alarm Pull Station Inside?
233408 02/22/2005 89626 P 2113 M Secure loose metal siding @ ramp door
233405 02/22/2005 89620 P 3770 M Repair stair door to close properly
233409 02/22/2005 89628 P 3775 M Determine cause of water damaged ceiling tiles and replace tiles
233410 02/22/2005 89630 P 3775 M Repair damaged floor tile
233411 02/22/2005 89632 P 3775 M Repair emergency lighting
187717 02/22/2005 29546 P 3775 M Adjust steps to make risers equal
187705 02/22/2005 30856 P 471 M Remove interior partition wall in Career Center portable (prohibited by code)
187707 02/22/2005 30828 P 471 M Determine cause of water damaged ceiling tiles and replace tiles
187720 02/22/2005 63114 P 717 M Extend graspable handrail to bottom of ramp
187721 02/22/2005 30858 P 717 M Provide sign indicating "Fire Alarm Pull Station Inside"
233390 02/22/2005 89589 1 103 O Eliminate extension cord powering microwave oven
233391 02/22/2005 89591 1 113B O Eliminate surge protector powering microwave and refrigerator
187687 02/22/2005 8148 1 106 C Provide fire rated door for boiler room
187691 02/22/2005 8152 2 101 C Replace threshold with one at maximum 1/2 inch high
187715 02/22/2005 30851 P 2113 C Provide handicapped accessible hardware on ramp door
233422 02/22/2005 89656 P 471 C Provide graspable handrails on each side of ramp at between 34-38" high
233392 02/22/2005 89593 1 105 OS Provide clear access to fire extinguisher
187677 02/22/2005 30855 00 0000 CS Provide lock box and knox locks to allow fire department access
187676 02/22/2005 30846 00 0000 FS Modify zones map on east exterior wall to correspond with active zones on fire alarm panel inside room 1-111