Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
407561 01/30/2018 459460 00 0000 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report 10-27-16 - risers 1-292 and 3-191
407358 01/30/2018 459010 1 0000 M Determine cause of water damaged ceiling tiles and replace tiles in the following rooms of Building #1 (115, 123, 124, 136, 138, 150, 150F, 159D, 163, 170A, 181, 186, 188, 192, 198)
362263 01/30/2018 361323 1 0000 M Repair leaking rain gutters and downspouts on building 1. Clean out all gutters and downspouts
407449 01/30/2018 459213 1 100D M Replace missing ceiling tiles in corridor
407352 01/30/2018 458999 1 100F M Determine cause of water damaged ceiling tiles in corridor adjacent to south exit doors and replace tiles
407351 01/30/2018 458997 1 100G M Determine cause of water damaged ceiling tiles in corridor adjacent to 1-143 and replace tiles
407353 01/30/2018 459001 1 100J M Determine cause of water damaged ceiling tiles in corridor adjacent to 1-197 and replace tiles
407447 01/30/2018 459209 1 100L M Determine cause of water leaking above ceiling in corridor and repair leak (water is currently dripping into large garbage can)
407448 01/30/2018 459211 1 100L M Determine cause of water damaged ceiling tiles in corridor adjacent to courtyard and replace tiles
407419 01/30/2018 459147 1 120 M Repair broken window blinds
407423 01/30/2018 459155 1 146 M Determine cause of water damaged ceiling tiles and replace tiles
407424 01/30/2018 459157 1 146 M Replace missing vinyl base at entrance door
407429 01/30/2018 459168 1 147 M Provide correct signage indicating room name and number to say 1-147 as per FISH map (current sign says 1-150C)
407430 01/30/2018 459170 1 147A M Secure hanging lens on light fixture in restroom
392928 01/30/2018 427848 1 150A M Replace broken base tile along wall adjacent to south exit door in serving area
407435 01/30/2018 459182 1 150B M Replace impervious ceiling tile with hole in it on north side of kitchen hood
407436 01/30/2018 459184 1 150B M Replace one missing moisture proof ceiling tile above steamer on south side of kitchen hood
407432 01/30/2018 459174 1 155 M Determine cause of water dripping from ceiling and repair leak inside dry storage room of kitchen (water is caught with a garbage can to prevent further damage to stock)
407434 01/30/2018 459180 1 155A M Secure hanging lens on light fixture
407433 01/30/2018 459178 1 155B M Secure hanging lens on light fixture
407426 01/30/2018 459161 1 157 M Provide current emergency lighting and generator certification so that all student occupied spaces have emergency lights and all are operable ((current certification is dated 6-16-16)
407437 01/30/2018 459188 1 161 M Repair out of order toilet
407438 01/30/2018 459190 1 161A M Repair bathroom door to close properly
407442 01/30/2018 459199 1 173 M Repair loose veneer on bathroom door
407443 01/30/2018 459201 1 179 M Repair light fixture
407444 01/30/2018 459203 1 180 M Replace ceiling tile that has a hole in it adjacent to east wall
407446 01/30/2018 459207 1 185 M Provide correct signage indicating room name and number to read 1-185 as per FISH map (current sign says 1-195
407451 01/30/2018 459217 1 188 M Repair leaks around top of window
407445 01/30/2018 459205 1 195 M Repair leaky air handler unit to prevent standing water on floor
407354 01/30/2018 459003 1 203 M Determine cause of water damaged ceiling tiles and replace tiles
407356 01/30/2018 459007 1 205 M Determine cause of water damaged ceiling tiles and replace tiles
407450 01/30/2018 459215 1 206 M Provide current dated flame resistance certification on CCTV studio curtains
407439 01/30/2018 459192 1 290 M Secure loose fire extinguisher bracket, (fire extinguisher sitting on floor because bracket will not hold the weight)
407440 01/30/2018 459194 1 290 M Repair water leak on AHU5, water standing on floor from leak
407460 01/30/2018 459235 3 104A M Repair ventilation fan in staff restroom
407461 01/30/2018 459237 3 104B M Repair ventilation fan in staff restroom
407360 01/30/2018 459018 3 105 M Determine cause of water damaged ceiling tiles and replace tiles
407361 01/30/2018 459020 3 107 M Determine cause of water damaged ceiling tiles and replace tiles
407362 01/30/2018 459022 3 108 M Determine cause of water damaged ceiling tiles and replace tiles
407363 01/30/2018 459024 3 110 M Determine cause of water damaged ceiling tiles and replace tiles
407462 01/30/2018 459239 3 111 M Repair broken window blinds
407453 01/30/2018 459221 3 113 M Repair damaged wall around door
407459 01/30/2018 459233 3 170 M Provide current inspection tag for elevator
407458 01/30/2018 459231 3 171 M Provide covers on exposed electrical junction boxes in elevator equipment room
407457 01/30/2018 459229 3 190 M Repair door to close properly (door rubs on jamb and does not close by itself)
407455 01/30/2018 459225 3 191 M Repair leaky water valve on chilled water supply line
407465 01/30/2018 459245 3 201C M Repair out of order toilet
407466 01/30/2018 459247 3 202A M Repair ventilation fan in restroom
407463 01/30/2018 459241 3 210 M Repair damaged corner at wall next to entrance door
392949 01/30/2018 427893 3 280 M Repair ventilation fan in custodial room
407464 01/30/2018 459243 3 291 M Repair air conditioning unit above door, room is very warm
407420 01/30/2018 459149 1 125 O Remove and prohibit paper covering window in door except during code red
407422 01/30/2018 459153 1 139 O Replace burned out bulbs in light fixture
407431 01/30/2018 459172 1 155 O Keep area within 18 inches of fire sprinkler head clear and unobstructed
392908 01/30/2018 427808 1 0000 C Post sign indicating primary and secondary evacuation routes in contrasting colors through out Bldg. 1 - Evacuation maps are hand marked and 50 percent of the maps are missing secondary routes
407421 01/30/2018 459151 1 100E MS Recharge fire extinguisher in corridor adjacent to 1-131
407428 01/30/2018 459166 1 147 MS Recharge fire extinguisher in flammable storage room
407456 01/30/2018 459227 3 190 MS Provide current inspection tag for fire extinguisher
407454 01/30/2018 459223 3 192 MS Provide current inspection tag for fire extinguisher (current tag is from 2014)
407425 01/30/2018 459159 1 148 OS Remove storage from mechanical room
407427 01/30/2018 459164 1 156 OS Remove storage from hot water heater room
407441 01/30/2018 459196 1 162 OS Prohibit hold open device(wooden floor wedge) on entrance door while students are attending class
407452 01/30/2018 459219 3 113 OS Prohibit storage of gasoline can in storage room, store in flammable storage room
254993 01/30/2018 131028 1 0000 N/A No violations observed
254994 01/30/2018 131030 2 0000 N/A No violations observed
254995 01/30/2018 131032 3 0000 N/A No violations observed
392892 08/28/2017 427775 00 0000 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report 10.20.15 - risers: 1-292 and 3-191
392920 11/28/2016 427832 1 100L M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to 1-195
392922 11/28/2016 427836 1 100M M Repair light in exit sign above school east entrance door
392946 11/28/2016 427887 1 118 M Mount signage indicating room name and number at appropriate height with raised and Braille characters at maximum 5 ft to center of sign
392947 11/28/2016 427889 1 119 M Mount signage indicating room name and number at appropriate height with raised and Braille characters at maximum 5 ft to center of sign
392937 11/28/2016 427866 1 123 M Determine cause of water damaged ceiling tiles and replace tiles
392939 11/28/2016 427870 1 135 M Provide current inspection log for hot water heater
392944 11/28/2016 427883 1 143 M Secure loose faucet to sink
392943 11/28/2016 427881 1 148 M Repair air handler to eliminate water leak
392927 11/28/2016 427846 1 150A M Replace broken vinyl floor tiles at south exit door in serving area
392924 11/28/2016 427840 1 150H M Replace broken ceiling tiles
392933 11/28/2016 427858 1 161 M Adjust girls bathroom door to latch properly in covered play area behind stage
392914 11/28/2016 427820 1 166 M Replace missing laminate wood back splash at sink counter
392916 11/28/2016 427824 1 170 M Determine cause of water damaged ceiling tiles and replace tiles
392918 11/28/2016 427828 1 170C M Replace heavily rusted hot water heat
392913 11/28/2016 427818 1 172 M Replace missing laminate wood back splash at sink counter
392907 11/28/2016 427806 1 185 M Replace missing vinyl floor tiles under sink
392930 11/28/2016 427852 1 198 M Determine cause of water damaged ceiling tiles and replace tiles
392936 11/28/2016 427864 1 207 M Determine cause of water damaged ceiling tiles and replace tiles
392942 11/28/2016 427879 1 290 M Repair air handler to eliminate water leak
392919 11/28/2016 427830 1 291 M Replace missing ceiling tiles
392950 11/28/2016 427895 3 0000 M Replace missing insulated cover for exposed electrical outlet on east exterior wall
392951 11/28/2016 427897 3 001 M Adjust east exit doors to latch properly at end of corridor adjacent to stairwell 3-005
392899 11/28/2016 427790 3 101 M Determine cause of water damaged ceiling tiles and replace tiles
392898 11/28/2016 427788 3 103 M Determine cause of water damaged ceiling tiles and replace tiles
392897 11/28/2016 427786 3 105 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to windows
392896 11/28/2016 427783 3 107 M Determine cause of water damaged ceiling tiles and replace tiles
392894 11/28/2016 427779 3 110 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to windows
392895 11/28/2016 427781 3 111 M Determine cause of water damaged ceiling tiles and replace tiles
392948 11/28/2016 427891 3 170 M Provide current inspection tag for elevator
392906 11/28/2016 427804 3 201B M Secure loose light fixture to ceiling
392905 11/28/2016 427802 3 205A M Patch hole in wall behind bathroom door 3-205B and replace missing door stop
392902 11/28/2016 427796 3 206 M Repair damaged drawer at teacher desk
392945 11/28/2016 427885 1 131 O Remove glass mirror behind sink or provide mirror made of tempered glass, safety glass, or stainless steel
392940 11/28/2016 427875 1 136 O Remove and prohibit flammable vinyl large tent in speech class
392929 11/28/2016 427850 1 147 O Relocate storage to maintain clear access to emergency eye wash - shower in custodial receiving
392952 11/28/2016 427899 1 150B O Adjust two burners cook top to be under hood fire suppression nozzle in kitchen
392953 11/28/2016 427901 1 150B O Secure wobbly two burners cook top in kitchen
392915 11/28/2016 427822 1 166 O Prohibit plugging surge protector into extension cord under computer stations - plug surge protector directly into wall outlet
392917 11/28/2016 427826 1 170 O Replace burned out light bulbs in light fixtures
392912 11/28/2016 427816 1 174 O Eliminate white extension cord with multiple outlet end under computer stations or replace with a surge protector
392921 11/28/2016 427834 1 179 O Remove and prohibit excessive flammable vinyl blue sheathing on table adjacent to door leading to bathroom vestibule
392911 11/28/2016 427814 1 183 O Eliminate white extension cord with multiple outlet end adjacent to teacher desk or replace with a surge protector
392910 11/28/2016 427812 1 189 O Prohibit plugging surge protector into extension cord behind computer stations - plug surge protector directly into wall outlet
392935 11/28/2016 427862 1 206 O Secure electrical cord cover strips to flooring in CCTV studio to eliminate slip hazard
392938 11/28/2016 427868 2 101 O Replace burned out light bulbs in storage room or ask maintenance for assistance if needed
392893 11/28/2016 427777 3 102 O Remove paper covering signage indicating room name and number with raised and Braille characters. You may place paper above or below designated sign
392900 11/28/2016 427792 3 107 O Remove and prohibit paper on window blinds
392901 11/28/2016 427794 3 107 O Remove and prohibit excessive flammable blue vinyl sheathing on desk adjacent to corridor door
392904 11/28/2016 427800 3 205 O Remove paper covering designated evacuation map adjacent to corridor door
392903 11/28/2016 427798 3 209 O Remove paper covering designated evacuation map adjacent to corridor door
392941 11/28/2016 427877 1 146 MS Adjust corridor door to latch properly
392926 11/28/2016 427844 1 150F MS Remove hold open device from east fire door to stage ramp
392932 11/28/2016 427856 1 157 MS Remove maintenance cardboard boxes from main electrical room
392934 11/28/2016 427860 1 158 MS Provide current inspection tag for fire extinguisher - Dated Oct. 2014
392931 11/28/2016 427854 1 160 MS Provide fire extinguisher adjacent to kiln room
392909 11/28/2016 427810 1 187 MS Adjust corridor door to latch properly
392923 11/28/2016 427838 1 199 MS Provide current inspection tag for fire extinguisher - Dated April 2015
392925 11/28/2016 427842 1 150F OS Relocate TV on stage to provide clear access to fire extinguisher cabinet
378711 08/26/2016 397141 1 292 M Provide current, correct inspection tag for fire sprinkler system and make any necessary repairs if indicated on report
378722 02/16/2016 397163 1 101 M Trouble indicated on fire alarm panel
378721 02/16/2016 397161 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
378710 02/16/2016 397139 1 123 M Determine cause of water damaged ceiling tiles and replace tiles
378712 02/16/2016 397144 1 124 M Adjust door to latch properly
378709 02/16/2016 397137 1 124A M Secure cover on light fixture
378708 02/16/2016 397135 1 131 M Determine cause of water damaged ceiling tiles and replace tiles
378706 02/16/2016 397131 1 133 M Repair broken fire alarm strobe - horn
378705 02/16/2016 397129 1 138 M Repair light in exit sign at corridor door
378701 02/16/2016 397121 1 140 M Repair light in exit sign
378695 02/16/2016 397107 1 147 M Turn on water for emergency eye wash
378698 02/16/2016 397115 1 149 M Determine cause of water damaged ceiling and make necessary repairs
378699 02/16/2016 397117 1 149 M Adjust door to latch properly
378688 02/16/2016 397093 1 150 M Determine cause of water damaged ceiling tiles and replace tiles
378686 02/16/2016 397089 1 150 M Repair corridor doors at 1-100 ramp to open properly
378692 02/16/2016 397101 1 150B M Replace broken bracket for fire extinguisher adjacent to 1-152
378685 02/16/2016 397087 1 150F M Determine cause of water damaged ceiling tiles and replace tiles
378687 02/16/2016 397091 1 150H M Determine cause of water damaged ceiling tiles and replace tiles
378690 02/16/2016 397097 1 150L M Secure loose escutcheon on fire sprinkler head
378697 02/16/2016 397113 1 152A M Adjust door to latch properly
378696 02/16/2016 397109 1 157 M Provide current certification that all student occupied spaces have emergency lights and all are operable
378680 02/16/2016 397077 1 158 M Pad and mark corners of VCR unit which are lower than 6 feet 8 inches
378674 02/16/2016 397064 1 161 M Repair light in exit sign
378677 02/16/2016 397070 1 165 M Repair light in exit sign
378676 02/16/2016 397068 1 166A M Repair back check device on bathroom door
378675 02/16/2016 397066 1 168 M Repair light in exit sign
378671 02/16/2016 397058 1 171 M Determine cause of water damaged ceiling tiles and replace tiles
378672 02/16/2016 397060 1 172 M Repair light in exit sign
378669 02/16/2016 397054 1 186 M Determine cause of water damaged ceiling tiles and replace tiles
378714 02/16/2016 397148 1 187 M Adjust door closer to control speed of closing door
378713 02/16/2016 397146 1 189B M Replace missing escutcheon on fire sprinkler head in vestibule at 1-189A
374908 02/16/2016 388805 1 195 M Repair leaking air handler
378681 02/16/2016 397079 1 199 M Repair leaking air handler
378715 02/16/2016 397149 1 203 M Adjust door closer on corridor door to control speed of closing door
378716 02/16/2016 397151 1 203 M Repair light in exit sign
378718 02/16/2016 397155 1 205 M Repair light in exit sign
378717 02/16/2016 397153 1 206 M Repair light in exit sign
378684 02/16/2016 397085 1 290 M Repair leaking air handlers, replace missing covers for Neptronic units on AHU 5
378480 02/16/2016 396637 3 101 M Determine cause of water damaged ceiling tiles and replace tiles
378482 02/16/2016 396641 3 105 M Adjust door closer to control speed of closing door
378481 02/16/2016 396639 3 108 M Determine cause of water damaged ceiling tiles and replace tiles
378483 02/16/2016 396643 3 111 M Determine cause of water damaged ceiling tiles and replace tiles
378478 02/16/2016 396633 3 170 M Provide current inspection tag for elevator
378668 02/16/2016 397052 3 191 M Repair leaking chilled water return
378666 02/16/2016 397047 3 201C M Replace missing door stop
378663 02/16/2016 397040 3 205B M Replace missing escutcheon on fire sprinkler head
378664 02/16/2016 397042 3 208 M Repair electrical outlet adjacent to sink, breaker trips when microwave is used
378703 02/16/2016 397125 1 140 O Prohibit use of multi outlet electrical adaptor at computer adjacent to window
378704 02/16/2016 397127 1 141 O Relocate string line to hang no more than 2 inches from wall surface
378673 02/16/2016 397062 1 169 O Remove and prohibit air freshener sticks
326213 02/16/2016 282861 1 291A C Provide automatic fire sprinkler coverage for room. Plan does not indicate 2 hour walls
378678 02/16/2016 397072 1 100J MS Recharge fire extinguisher adjacent to 1-160
378720 02/16/2016 397159 1 113 MS Provide current inspection tag for fire extinguisher
378700 02/16/2016 397119 1 143A MS Repair door lock, handle is missing unlock tab
378691 02/16/2016 397099 1 150B MS Recharge fire extinguisher
378693 02/16/2016 397103 1 150E MS Adjust freezer door to close and latch properly
378689 02/16/2016 397095 1 150J MS Repair door lock to properly function, key spins in lock cylinder but doesn't catch
378694 02/16/2016 397105 1 155 MS Provide current inspection tag for fire extinguisher
378682 02/16/2016 397081 1 199 MS Recharge fire extinguisher
378719 02/16/2016 397157 1 206 MS Provide current inspection tag for fire extinguisher
378683 02/16/2016 397083 1 290 MS Provide current inspection tag for fire extinguisher
378679 02/16/2016 397074 1 8087 MS Repair south gate door hardware in P.E. area adjacent to 1-158 to allow proper egress
378479 02/16/2016 396635 3 102 MS Recharge fire extinguisher
378667 02/16/2016 397050 3 201C MS Repair thumb latch to enable door to be unlocked
378665 02/16/2016 397044 3 204C MS Repair door lock to properly function
378484 02/16/2016 396645 3 208B MS Repair door lock on bathroom door
378702 02/16/2016 397123 1 140 OS Maintain clear aisle to exterior exit
362296 09/03/2015 361398 1 290 M Replace missing covers and repair damper motors on AHU-5
374967 09/03/2015 388931 3 201B M Repair exhaust fan in bathroom
362301 05/13/2015 361408 1 148 M Replace cover for damper motor on AHU-1
362264 05/13/2015 361325 1 194 M Replace missing covers for damper motors on AHU-12
362375 05/13/2015 361581 1 291 M Cover open damper motors on air handler
374902 05/13/2015 388792 1 292 M Provide current quarterly inspection tag for fire sprinkler system
362373 05/13/2015 361577 1 293 M Cover open damper motors on AHU-9
374951 05/13/2015 388897 3 104B M Repair exhaust fan in bathroom
374911 05/13/2015 388811 3 191 M Provide current quarterly inspection tag for fire sprinkler system
374964 05/13/2015 388925 3 205B M Replace missing escutcheon on fire sprinkler head
362348 04/10/2015 361524 00 0000 M Unband Sabal palm trees at building 3
362282 04/10/2015 361367 1 0000 M Center exit signs over correct door leaves in corridor adjacent to 1-150J
362271 04/10/2015 361340 1 0000 M Repair lights in 2 exit signs in interior courtyard
374917 04/10/2015 388823 1 0000 M Adjust door from interior courtyard adjacent to 1-195 to latch properly
374933 04/10/2015 388860 1 0000 M Repair broken edge of sidewalk outside of 1-164
362281 04/10/2015 361365 1 100C M Center exit signs over correct door leaves in corridor adjacent to 1-117
362284 04/10/2015 361371 1 100F M Center exit signs over correct door leaves in corridor adjacent to 1-182
374921 04/10/2015 388833 1 100F M Repair light in exit sign in corridor at 1-162
374922 04/10/2015 388835 1 100F M Repair light in exit sign in corridor at 1-168
374891 04/10/2015 388767 1 100F M Center exit sign over correct door leaf in corridor adjacent to 1-180
362283 04/10/2015 361369 1 100M M Center exit signs over correct door leaves in corridor adjacent to 1-187
374896 04/10/2015 388778 1 101 M Repair light in exit sign
374887 04/10/2015 388758 1 115 M Repair light in exit sign
374948 04/10/2015 388891 1 119 M Cover opening in sink
374947 04/10/2015 388889 1 123 M Replace missing ceiling tiles
374890 04/10/2015 388764 1 131 M Determine cause of water damaged ceiling tiles and replace tiles
374913 04/10/2015 388817 1 134 M Adjust rear door to latch properly
374930 04/10/2015 388852 1 138 M Repair light in exit sign
374928 04/10/2015 388849 1 138A M Repair leaking toilet supply line
374932 04/10/2015 388856 1 139 M Secure loose power pole
374927 04/10/2015 388847 1 141 M Repair damaged light fixture. See teacher
374889 04/10/2015 388762 1 142 M Repair lights in 3 exit signs.
374915 04/10/2015 388821 1 145 M Repair toilet partition. Top rail missing screws
374938 04/10/2015 388870 1 146 M Determine cause of water damaged ceiling tiles and replace tiles
362299 04/10/2015 361404 1 146 M Determine cause of water damaged ceiling tiles and replace tiles
374939 04/10/2015 388872 1 147 M Repair door to corridor to open and close properly. Rubs on frame
374900 04/10/2015 388787 1 147 M Repair emergency eye wash, low flow
362294 04/10/2015 361394 1 150G M Secure hanging light fixture
374892 04/10/2015 388770 1 153 M Repair or replace dryer vent hose that has come apart
374888 04/10/2015 388760 1 156 M Re-insulate hot water lines
374926 04/10/2015 388839 1 157 M Label all circuits on electrical panel AC-1
374940 04/10/2015 388874 1 158A M Repair leaking toilet supply line
374934 04/10/2015 388862 1 159A M Repair leaking toilet supply line
374935 04/10/2015 388864 1 159A M Replace missing escutcheon on fire sprinkler head
374898 04/10/2015 388782 1 161 M Repair door to open and close properly. Rubs on frame
374943 04/10/2015 388880 1 168A M Repair leaking flush valve for toilet
374897 04/10/2015 388780 1 172 M Replace sink backsplash
374945 04/10/2015 388885 1 172 M Determine cause of water damaged and moldy ceiling tiles and replace tiles
374961 04/10/2015 388919 1 174 M Repair light in exit sign
374949 04/10/2015 388893 1 176A M Repair exhaust fan in bathroom
374958 04/10/2015 388913 1 177B M Repair exhaust fan in bathroom
374959 04/10/2015 388915 1 177C M Repair exhaust fan in bathroom
374957 04/10/2015 388911 1 179 M Determine cause of water damaged ceiling tiles and replace tiles
374907 04/10/2015 388803 1 182 M Adjust door to exterior to latch properly
374956 04/10/2015 388909 1 183 M Determine cause of water damaged ceiling tiles and replace tiles
374920 04/10/2015 388831 1 185 M Determine cause of water damaged ceiling tiles and replace tiles
374941 04/10/2015 388876 1 188 M Repair exhaust fan in bathroom
374919 04/10/2015 388829 1 200 M Determine cause of water damaged ceiling tiles and replace tiles at north end of room
374901 04/10/2015 388790 1 291 M Repair leaking air handler 8
374903 04/10/2015 388794 3 101 M Repair leaking drinking fountain and adjust flow
374953 04/10/2015 388902 3 103A M Replace broken toilet seat
374954 04/10/2015 388904 3 107A M Caulk sink to wall
374955 04/10/2015 388907 3 110 M Adjust flow of drinking fountain
374905 04/10/2015 388799 3 110 M Determine cause of water damaged ceiling tiles and replace tiles
374904 04/10/2015 388796 3 111 M Determine cause of water damaged ceiling tiles and replace tiles
374906 04/10/2015 388801 3 112 M Determine cause of water damaged ceiling tiles and replace tiles
374952 04/10/2015 388900 3 180 M Secure loose door handle
374910 04/10/2015 388809 3 191 M Provide all types of fire sprinkler heads in spare heads box. Box has only upright heads. Provide some pendant heads
374912 04/10/2015 388814 3 191 M Provide lower latch for inactive leaf of door. Door is bending
374968 04/10/2015 388933 3 203 M Secure loose push button to drinking fountain
374965 04/10/2015 388927 3 204B M Repair leaking toilet supply line
374966 04/10/2015 388929 3 204C M Repair leaking toilet supply line
374963 04/10/2015 388923 3 208B M Adjust door to latch properly. Sticky latch
374885 04/10/2015 388751 00 0 O No access was available to 1-112, 1-113, 1-149 and 1-150G. Please provide access to these rooms during the report review meeting
374894 04/10/2015 388773 1 136A O Prohibit running electrical cord through door opening
374899 04/10/2015 388785 1 147 O Maintain clear access to emergency eye wash - shower
374937 04/10/2015 388866 1 159C O Keep all fixture drains filled with water. Every 2 months pour water down all drains. Room used for storage
374944 04/10/2015 388882 1 170 O Post sign indicating evacuation routes
374946 04/10/2015 388887 1 171 O Remove and prohibit hanging paper on blinds. Acceptable on wall, windows or on string line close to wall or windows
374960 04/10/2015 388917 1 178 O Post sign indicating evacuation routes
374962 04/10/2015 388921 3 007 MS Adjust fire door in corridor adjacent to 3-209 to latch properly.
374909 04/10/2015 388807 3 191 MS Remove 55 gallon drum stored in mechanical room
374950 04/10/2015 388895 3 113 OS Prohibit storage of gas powered pressure cleaner
374886 01/21/2015 388756 1 150B C Adjust fire suppression nozzles that cover tilting skillet in Kitchen per Hood inspection report
362270 01/15/2015 361338 00 0000 M Remove dirt and grass from drainage flume at north end of west parking lot. Adjacent to fire main backflows
362308 01/15/2015 361423 1 0000 M Repair leaking differential pressure dump on 3 quarter inch backflow device in chiller compound
362306 01/15/2015 361418 1 0000 M Paint rusted gas line in chiller compound
374942 01/15/2015 388878 1 160 M Repair exhaust fan in bathroom. Wrong room number
362279 01/15/2015 361361 1 292 M Provide lock on gate of fencing around backflows at west campus outside of 1-292
362215 01/15/2015 361223 3 111A M Repair leaking toilet supply line
362343 01/15/2015 361513 3 192 M Repair or replace surge suppressor for panel LSH. Surge in fault
362261 01/15/2015 361319 1 150B C Adjust kitchen hood fire suppression heads to cover tilting skillet
362285 04/16/2014 361374 00 0000 M Eliminate ants in play fields. See coach.
362280 04/16/2014 361363 1 0000 M Repair or replace damaged irrigation head in interior courtyard outside of 1-291A
362307 04/16/2014 361420 1 0000 M Repair noisey chilled water pump in chiller compound
362309 04/16/2014 361425 1 0000 M Repair leaking over pressure relief valve in chiller compound
362363 04/16/2014 361556 1 100M M Determine cause of water damaged ceiling tiles in corridor at main entry and replace tiles
362364 04/16/2014 361558 1 102 M Determine cause of water damaged ceiling tiles and replace tiles
362366 04/16/2014 361562 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
362368 04/16/2014 361566 1 113 M Determine cause of water damaged ceiling tiles and replace tiles
362266 04/16/2014 361329 1 124 M Replace missing escutcheon on fire sprinkler head. Escutcheon is on top of refrigerator
362303 04/16/2014 361412 1 134 M Adjust door to exterior to latch properly
362268 04/16/2014 361333 1 138A M Repair leaking toilet supply line
362211 04/16/2014 361214 1 139 M Determine cause of water damaged ceiling tiles and replace tiles
362223 04/16/2014 361240 1 140 M Replace GFCI outlet that will not trip
362224 04/16/2014 361242 1 141 M Repair dripping faucet on bathroom sink
362212 04/16/2014 361216 1 142A M Repair leaking toilet supply line
362213 04/16/2014 361218 1 142A M Caulk sink to bathroom wall
362304 04/16/2014 361414 1 144 M Repair leaking supply line for handicapped toilet
362305 04/16/2014 361416 1 144 M Caulk urinal to wall
362300 04/16/2014 361406 1 148 M Close and lock 2 EMS cabinets
362277 04/16/2014 361356 1 150 M Adjust SW door to exterior to latch properly
362278 04/16/2014 361359 1 150 M Repair or replace damaged SW door to exterior
362218 04/16/2014 361229 1 150 M Determine cause of water damaged ceiling tiles and replace tiles
362220 04/16/2014 361234 1 150B M Provide protective cages around fire sprinkler heads in walk-in cooler and freezer
362276 04/16/2014 361354 1 150B M Secure loose GFCI outlet on west wall in Kitchen
362262 04/16/2014 361321 1 150F M Secure loose handrail for stairs from stage to cafeteria
362297 04/16/2014 361400 1 150L M Repair leaking supply line for 1st toilet
362298 04/16/2014 361402 1 150L M Repair leaking flush valve on handicapped toilet
343233 04/16/2014 319714 1 152A M Repair or replace rusty, damaged door
362260 04/16/2014 361317 1 156 M Repair leaking elbow on water heater
362286 04/16/2014 361376 1 158 M Determine cause of water damaged ceiling tiles and replace tiles
362310 04/16/2014 361427 1 159A M Repair leaking toilet supply line
362219 04/16/2014 361231 1 159D M Determine cause of water damaged ceiling tiles and replace tiles
362289 04/16/2014 361383 1 163 M Determine cause of water damaged ceiling tiles and replace tiles
362287 04/16/2014 361378 1 164A M Replace GFCI outlet that will not reset
362288 04/16/2014 361380 1 164A M Repair leaking toilet supply line
362290 04/16/2014 361386 1 171A M Anchor toilet to floor
362379 04/16/2014 361589 1 181A M Repair leaking toilet supply line
362367 04/16/2014 361564 1 185 M Determine cause of water damaged ceiling tiles and replace tiles
362365 04/16/2014 361560 1 186 M Determine cause of water damaged ceiling tiles and replace tiles
362371 04/16/2014 361573 1 192A M Repair leaking toilet supply line
362377 04/16/2014 361585 1 195 M Repair leaking air handler AHU-10
362378 04/16/2014 361587 1 195 M Close and lock EMS cabinet
362265 04/16/2014 361327 1 196 M Determine cause of water damaged ceiling tiles and replace tiles
362349 04/16/2014 361526 1 200 M Secure loose power pole in Media Center
362369 04/16/2014 361568 1 205 M Determine cause of water damaged ceiling tiles and replace tiles
362381 04/16/2014 361593 1 206 M Determine cause of water damaged ceiling tiles and replace tiles
362382 04/16/2014 361595 1 206 M Repair light in exit sign
362376 04/16/2014 361583 1 291 M Close and lock EMS cabinet
362216 04/16/2014 361225 1 291A M Provide spacers to cover openings in panel LPP3B
362217 04/16/2014 361227 1 291A M Determine cause of water damaged ceiling tiles and replace tiles
362372 04/16/2014 361575 1 293 M Install hanging Neptronic motor to air handler
362374 04/16/2014 361579 1 293 M Close and lock EMS cabinet
362312 04/16/2014 361432 3 0000 M Provide lock on gate of fencing around AC equipment outside of 3-113
362346 04/16/2014 361520 3 0000 M Provide lock on gate of fencing around electrical equipment at building 3
362347 04/16/2014 361522 3 0000 M Provide cover on open boxes in ground at electrical enclosure at building 3
362342 04/16/2014 361511 3 0000 M Provide chain and lock on valve handles of fire main backflows north of building 3
362318 04/16/2014 361444 3 101A M Caulk sink to wall
362315 04/16/2014 361438 3 103A M Cauklk sink to wall
362350 04/16/2014 361528 3 104A M Repair leaking toilet supply line
362311 04/16/2014 361430 3 105A M Adjust toilet, runs too long
362316 04/16/2014 361440 3 106A M Caulk sink to wall
362221 04/16/2014 361236 3 107A M Replace damaged paper towel dispenser in bathroom
362317 04/16/2014 361442 3 108A M Caulk sink to wall
362222 04/16/2014 361238 3 110A M Replace damaged paper towel dispenser in bathroom
362313 04/16/2014 361434 3 111A M Caulk sink to wall
362314 04/16/2014 361436 3 112A M Caulk sink to wall
362214 04/16/2014 361221 3 112A M Repair leaking toilet supply line
362273 04/16/2014 361344 3 113 M Repair damaged wall at door
362274 04/16/2014 361346 3 170 M Close open Simplex cabinets
362344 04/16/2014 361515 3 191 M Close and lock EMS cabinet
343249 04/16/2014 319747 3 191 M Replace missing fire sprinkler heads in spare heads box. Only 1 type of head in box
362393 04/16/2014 361621 3 201B M Caulk sink to wall in bathroom
362400 04/16/2014 361636 3 201B M Repair leaking toilet supply line
362392 04/16/2014 361619 3 201C M Caulk sink to wall in bathroom
362399 04/16/2014 361634 3 201C M Repair leaking toilet supply line
362394 04/16/2014 361624 3 202A M Caulk sink and toilet to wall in bathroom
362387 04/16/2014 361606 3 203C M Caulk sink to wall in bathroom
362390 04/16/2014 361612 3 204B M Caulk sink to wall in bathroom
362391 04/16/2014 361615 3 204C M Caulk sink to wall in bathroom
362388 04/16/2014 361609 3 205B M Caulk sink to wall in bathroom
362397 04/16/2014 361630 3 208B M Repair leaking toilet supply line
362385 04/16/2014 361602 3 208C M Caulk sink to wall in bathroom
362386 04/16/2014 361604 3 209A M Caulk sink to wall in bathroom
362398 04/16/2014 361632 3 209A M Repair leaking toilet supply line
362401 04/16/2014 361638 3 292 M Close and lock 6 open cabinets
362210 04/16/2014 361212 00 0 O No access was available to 1-111 and 1-149. Please provide access to these rooms during the report review meeting
362267 04/16/2014 361331 1 129 O Remove and prohibit hanging paper on string lines from ceiling. String lines are acceptable against the wall
362302 04/16/2014 361410 1 131A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
362292 04/16/2014 361390 1 150F O Provide clear access to electrical panel
362272 04/16/2014 361342 1 185 O Prohibit running electrical cord across floor causing a tripping hazard
362383 04/16/2014 361597 1 185A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
362370 04/16/2014 361571 1 193 O Remove and prohibit storage on water heater
362380 04/16/2014 361591 1 206 MS Adjust door to corridor to latch properly
362396 04/16/2014 361627 3 007 MS Adjust fire door at top of stair 3-005 to latch properly
362269 04/16/2014 361336 1 104 OS Prohibit hold open device on fire door
362293 04/16/2014 361392 1 150F OS Provide clear access to fire extinguisher on stage
362291 04/16/2014 361388 1 150F OS Remove and prohibit storage on stage ramp to maintain clear aisle to exit
362295 04/16/2014 361396 1 150G OS Provide clear access to fire extinguisher
362345 04/16/2014 361517 3 191 OS Remove 55 gallon drum from mechanical room
343219 01/16/2014 319684 1 292 M Replace missing fire sprinkler heads and wrench in spare heads box
343250 01/16/2014 319749 3 105A M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
362384 01/16/2014 361600 1 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters. Individual bathrooms in building 1 classrooms are not numbered. NA, cited on ADA compliance report
326047 03/05/2013 282496 00 0000 M Adjust fence gate to latch properly. Gate adjacent to 1-185
343214 03/05/2013 319674 1 0000 M Pad and mark corners of VCR units which are lower than 6 feet 8 inches. 1-191, 1-192, 1-190, 1-189, 1-118, 1-125, 1-133, 1-132, 1-134, 1-138, 1-140, 1-142, 1-141, 1-143, 1-146, 1-163, 1-167, 1-171, 1-176, 1-175, 1-184, 1-185, 1-208
343253 03/05/2013 319755 1 100A M Repair light in exit sign
343245 03/05/2013 319738 1 100L M Repair light in exit sign adjacent to 1-196
343254 03/05/2013 319757 1 102 M Determine cause of water damaged ceiling tiles and replace tiles
343211 03/05/2013 319668 1 115 M Determine cause of water damaged ceiling tiles and replace tiles
343222 03/05/2013 319690 1 140 M Repair light in exit signs (x2)
343223 03/05/2013 319692 1 142 M Repair light in exit sign
343226 03/05/2013 319698 1 143 M Repair light in exit sign
343224 03/05/2013 319694 1 145 M Repair damaged laminate on counter top
343225 03/05/2013 319696 1 145 M Replace missing soap dispenser
343227 03/05/2013 319700 1 146 M Determine cause of water damaged ceiling tiles and replace tiles
343252 03/05/2013 319753 1 147 M Keep water to emergency eye wash/shower turned on
343231 03/05/2013 319709 1 150 M Pad and mark corners of VCR units (x2) adjacent to stage which are lower than 6 feet 8 inches
343236 03/05/2013 319720 1 150B M Provide additional outlet adjacent to 1-150D (walk in cooler) to allow reach in freezer to be plugged in properly (NA, relocated freezer)
326239 03/05/2013 282920 1 150F M Determine cause of water damaged ceiling tiles and replace tiles on stage
343229 03/05/2013 319704 1 150L M Fill hole in ceiling around fire sprinkler head
343237 03/05/2013 319722 1 163 M Determine cause of water damaged ceiling tiles and replace tiles
343241 03/05/2013 319730 1 176 M Repair light in exit sign
343244 03/05/2013 319736 1 179 M Determine cause of water damaged ceiling tiles and replace tiles
343217 03/05/2013 319680 1 190 M Replace missing escutcheon on fire sprinkler head adjacent to 1-190A
343213 03/05/2013 319672 1 191A M Repair non working sink in bathroom (no water)
343232 03/05/2013 319711 1 203 M Repair light in exit sign
343248 03/05/2013 319745 1 205 M Determine cause of water damaged ceiling tiles and replace tiles
343212 03/05/2013 319670 1 291A M Repair door to unlock, no access to room
343218 03/05/2013 319682 1 293 M Repair door to close and latch properly
343235 03/05/2013 319718 1 9599 M Remove nails protruding from fence adjacent to 1-149
343251 03/05/2013 319751 3 108 M Determine cause of water damaged ceiling tiles and replace tiles
343220 03/05/2013 319686 1 136B O Prohibit plugging refrigerator and microwave into black multi outlet extension cord, plug directly into permanent electrical outlets. Prohibit multi outlet extension cord
343221 03/05/2013 319688 1 139 O Post sign indicating primary and secondary evacuation routes
343228 03/05/2013 319702 1 146 O Prohibit running electrical cord under carpet
343238 03/05/2013 319724 1 166 O Prohibit plugging surge protector into white extension cord under teachers desk, plug surge protector directly into permanent electrical outlet
343239 03/05/2013 319726 1 172 O Prohibit green multi outlet extension cord or replace with minimum 15A single outlet cord
343240 03/05/2013 319728 1 174 O Prohibit plugging surge protector into white multi outlet extension cord at document camera, plug surge protector directly into permanenet electrical outlet
343242 03/05/2013 319732 1 178 O Prohibit plugging surge protector into orange extension cord at projector, plug surge protector directly into permanent electrical outlet
343243 03/05/2013 319734 1 179 O Prohibit running black multi outlet extension cord under carpet, prohibit black multi outlet extension cord or replace with minimum 15A single outlet cord
343246 03/05/2013 319741 1 185 O Post sign indicating primary and secondary evacuation routes
343215 03/05/2013 319676 1 190 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
343216 03/05/2013 319678 1 190 O Prohibit running electrical cord under carpet
343230 03/05/2013 319707 1 100 C Provide non-slip surface for stage ramp
343234 03/05/2013 319716 1 157 OS Remove storage from electrical room
326254 11/01/2012 282949 1 142A M Repair exhaust fan in bathroom
282170 11/01/2012 186826 1 150F M Provide dated flame resistance label on stage curtain. Left curtain is labeled as inherently flame resistant and the right curtain is labeled as flame resistant by immersion
326260 11/01/2012 282965 1 156 M Provide current state inspection tag for hot water storage tank in excess of 120 gallons
326259 11/01/2012 282963 1 157 M Adjust door to latch properly
326221 11/01/2012 282878 1 165 M Remove pencil sharpener with no cover adjacent to sink
326276 11/01/2012 283001 1 178 M Replace GFCI outlet that won't trip
326274 11/01/2012 282997 1 181A M Repair exhaust fan in bathroom
326275 11/01/2012 282999 1 181C M Repair exhaust fan in bathroom
326034 11/01/2012 282470 1 186 M Determine cause of water damaged ceiling tiles and replace tiles
326256 03/14/2012 282954 00 0000 M Replace missing cap on gas diaphragm on north exterior wall of chiller compound
326257 03/14/2012 282957 00 0000 M Provide cover on exposed electrical junction box in chiller compound adjacent to lawn sprinkler time clock
326262 03/14/2012 282971 00 0000 M Repair chain link fence top rail that has come apart at bus loop adjacent to basketball courts
326263 03/14/2012 282973 00 0000 M Provide a barrier between the basketball courts and the catch basin adjacent to the courts. Large drop off to adjacent catch basin
326264 03/14/2012 282975 00 0000 M Secure loose chain link fencing fabric at NE corner of north parking lot
326245 03/14/2012 282930 00 0000 M Fill holes in ground of play fields, see Coach
326248 03/14/2012 282935 00 0000 M Recaulk open expansion joints on exterior walls and around windows
326250 03/14/2012 282941 00 0000 M Repair or replace rusted rain gutters and downspouts and seal openings in gutters and downspouts
326052 03/14/2012 282506 00 0000 M Clean debris and trash out of gutters at entry to school
326282 03/14/2012 283013 00 0000 M Provide lock on gate of fence around drainage/retention pond
308773 03/14/2012 244038 1 0000 M Remove peeling paint from ceiling in outside stage adjacent to 1-158 and repaint ceiling
326051 03/14/2012 282504 1 100D M Determine cause of water damaged ceiling tiles at west end of corridor and replace tiles
326214 03/14/2012 282863 1 100L M Determine cause of water damaged ceiling tiles in corridor adjacent to 1-195 and replace tiles
326057 03/14/2012 282517 1 108 M Repair faucet to shut off
326078 03/14/2012 282575 1 111 M Determine cause of water damaged ceiling tiles and replace tiles
326044 03/14/2012 282490 1 119 M Replace GFCI outlet at sink that won't trip
326043 03/14/2012 282488 1 119A M Secure loose escutcheon on fire sprinkler head
326045 03/14/2012 282492 1 120 M Pad and mark corners of DVD player which are lower than 6'8"
326036 03/14/2012 282474 1 123 M Determine cause of water damaged ceiling tiles and replace tiles
326048 03/14/2012 282498 1 124 M Repair light fixtures. Won't turn on
326029 03/14/2012 282456 1 124 M Replace GFCI outlet at sink that won't trip
326030 03/14/2012 282458 1 128 M Replace GFCI outlet at sink that won't trip
326031 03/14/2012 282460 1 131 M Replace GFCI outlet at sink that won't trip
326246 03/14/2012 282933 1 135 M Provide current inspection log for hot water heater
326252 03/14/2012 282947 1 138 M Repair leaking toilet supply line
326255 03/14/2012 282952 1 145 M Repair exhaust fan in bathroom
326232 03/14/2012 282902 1 146 M Determine cause of water damaged ceiling tiles adjacent to door to cafeteria and replace tiles
326229 03/14/2012 282896 1 147A M Repair leaking toilet supply line
326230 03/14/2012 282898 1 148 M Provide cover on exposed Fire Alarm junction box on south wall
326231 03/14/2012 282900 1 148 M Repair leaking air handler AHU 2
322842 03/14/2012 274867 1 149 M Re-key lock on flammable storage room to be on "A" key
326238 03/14/2012 282917 1 150 M Determine cause of water damaged ceiling tiles in cafeteria adjacent to stage and replace tiles
326235 03/14/2012 282911 1 150B M Secure loose GFCI outlet on wall at prep table in kitchen
326234 03/14/2012 282908 1 150C M Repair drain leak on 3 compartment sink
326261 03/14/2012 282969 1 156 M Condensate water from water heater runs on floor, plumb to drain
326258 03/14/2012 282960 1 157 M Provide correct bracket for fire extinguisher
326217 03/14/2012 282870 1 158A M Repair leaking toilet supply line
326219 03/14/2012 282874 1 161 M Replace cover for cleanout
326218 03/14/2012 282872 1 161A M Repair leaking toilet supply line
326223 03/14/2012 282882 1 171A M Repair exhaust fan in bathroom
326224 03/14/2012 282884 1 171C M Repair exhaust fan in bathroom
326227 03/14/2012 282891 1 172 M Replace GFCI outlet that won't trip
326226 03/14/2012 282889 1 174 M Replace GFCI outlet that won't trip
326225 03/14/2012 282887 1 174A M Repair exhaust fan in bathroom
326273 03/14/2012 282995 1 176A M Repair exhaust fan in bathroom
326271 03/14/2012 282991 1 177B M Repair exhaust fan in bathroom
326272 03/14/2012 282993 1 177C M Repair exhaust fan in bathroom
326277 03/14/2012 283003 1 179 M Replace GFCI outlet that won't trip
326278 03/14/2012 283005 1 179 M Determine cause of water damaged ceiling tiles and replace tiles
326215 03/14/2012 282865 1 183 M Replace GFCI outlet adcacent to sink that will not trip
326216 03/14/2012 282867 1 183 M Replace missing escutcheon on fire sprinkler head
326035 03/14/2012 282472 1 188 M Determine cause of water damaged ceiling tiles and replace tiles
326041 03/14/2012 282484 1 191A M Repair door to open and close properly
326042 03/14/2012 282486 1 192 M Remove pencil sharpener with no cover on it adjacent to sink
326204 03/14/2012 282843 1 195 M Provide cover on exposed 6" X 6" Fire Alarm junction box on east wall
326203 03/14/2012 282841 1 195A M Cover opening in panel LPP2B
326205 03/14/2012 282845 1 196 M Provide cover on exposed electrical junction box on north wall
326242 03/14/2012 282922 1 199 M Provide covers on exposed Neptronic A/C control boxes
326053 03/14/2012 282508 1 207 M Provide current inspection log for hot water heater. Badly rusted at bottom
326202 03/14/2012 282838 1 291A M Cover opening in panel LPP3B
326055 03/14/2012 282512 1 292 M Replace 2 broken valve handles on fire sprinkler risers
326049 03/14/2012 282500 2 101 M Repair ventilation fan, won't run
326050 03/14/2012 282502 2 101 M Adjust door to latch properly
326281 03/14/2012 283007 3 0000 M Install lock on post indicator valve (PIV) at building 3
326267 03/14/2012 282981 3 103A M Repair leaking toilet supply line
326269 03/14/2012 282985 3 105A M Secure sink to wall
326265 03/14/2012 282977 3 107 M Install knee guard for sink that is sitting on floor
326287 03/14/2012 283022 3 108 M Replace GFCI outlet that won't trip
326268 03/14/2012 282983 3 110A M Repair leaking toilet supply line
326285 03/14/2012 283019 3 180 M Repair door to open and close properly
326266 03/14/2012 282979 3 193 M Secure loose grounds to ground bar
326291 03/14/2012 283032 3 204C M Replace missing escutcheon on fire sprinkler head. Room signed 3-204B
326290 03/14/2012 283030 3 280 M Anchor shelving to wall
326027 03/14/2012 282452 00 0 O No access was available to 1-114 and 1-185. Please provide access to these rooms during the report review meeting.
326046 03/14/2012 282494 00 0000 O Indicate primary and secondary routes in contrasting colors on evacuation maps
326228 03/14/2012 282894 1 147 O Maintain clear access to emergency eye wash/shower
326039 03/14/2012 282480 1 190 O Eliminate string lines below 6'8"
326040 03/14/2012 282482 1 193 O Remove and prohibit storage on water heater
326033 03/14/2012 282467 1 194 O Prohibit storing used light tubes in mechanical room. Store in box in appropriate location such as custodial receiving or custodial closet
326206 03/14/2012 282847 1 196 O Replace tubes in light fixture
326233 03/14/2012 282905 1 290 O Do not store used light tubes in mechanical room. Store used light tubes in box in appropriate area such as custodial receiving, custodial closet or flammable storage room
326032 03/14/2012 282464 1 291 O Prohibit storing old light tubes in mechanical room. Store in box in appropriate location. Custodial receiving or custodial closet
326270 03/14/2012 282989 3 107 O Eliminate multi-outlet extension cord or replace with minimum 15A cord
290732 03/14/2012 205133 00 0000 C Provide suitable area for storage and recharging of golfcart and floor cleaning machines
199897 03/14/2012 24374 1 0000 C Provide bottom rail and balusters on stair landing guardrail at exterior stage
326222 03/14/2012 282880 1 171 MS Adjust corridor door to latch properly
326292 03/14/2012 283035 1 187 MS Adjust corridor door to latch properly
326038 03/14/2012 282478 1 206 MS Adjust door to corridor to latch properly
326054 03/14/2012 282510 1 207 MS Adjust door to latch properly
326056 03/14/2012 282514 1 292 MS Provide current inspection tag for fire sprinkler system
326283 03/14/2012 283015 3 191 MS Provide current inspection tag for fire sprinkler system
326028 03/14/2012 282454 00 0000 OS Custodians are blocking open doors by inserting a block of wood between the door frame and door on the hinge side. This damages the door, hinges and frame. Block open the door with a wedge between the door and floor
326058 03/14/2012 282520 1 104 OS Prohibit hold open device on fire door. Door labeled 1-1/2 hour fire door
326220 03/14/2012 282876 1 160C OS Keep area within 18" of fire sprinkler head clear and unobstructed
322847 04/26/2011 274879 00 0000 M Install caps on fire department standpipe connections on the west side of Building 1
322837 04/26/2011 274857 1 0000 M Secure loose spout on drinking fountain at covered play area adjacent to outdoor stage
322843 04/26/2011 274869 1 139 M Determine cause of water damaged ceiling tiles and replace tiles
322844 04/26/2011 274871 1 139 M Repair hanging cabinet doors on cabinets adjacent to windows
322846 04/26/2011 274877 1 139 M Repair opening in wall around light switch
322838 04/26/2011 274859 1 146 M Determine cause of water damaged ceiling tiles and replace tiles
322839 04/26/2011 274861 1 147 M Connect dryer duct to back of clothes dryer
322841 04/26/2011 274865 1 149 M Replace burned out explosion proof bulbs in light fixture of flammable storage room
322836 04/26/2011 274855 1 160C M Determine cause of water damaged ceiling tiles and replace tiles
322835 04/26/2011 274853 1 163 M Determine cause of water damaged ceiling tiles and replace tiles
322834 04/26/2011 274850 1 165 M Repair light in exit sign above entrance door
322833 04/26/2011 274848 1 168 M Repair light in exit sign above entrance door
322831 04/26/2011 274844 1 183 M Replace damaged ceiling tile with hole adjacent to front door
322830 04/26/2011 274842 1 184 M Repair exterior exit door to close and latch properly
322849 04/26/2011 274883 1 192 M Determine cause of water damaged ceiling tiles and replace tiles
322777 04/26/2011 274725 1 203 M Determine cause of water damaged ceiling tiles and replace tiles
322776 04/26/2011 274723 1 205 M Determine cause of water damaged ceiling tiles and replace tiles
322832 04/26/2011 274846 1 291 M Remove storage of used flouescent bulbs from mechanical room
322749 04/26/2011 274661 00 0000 C Provide exterior signage indicating property address
322750 04/26/2011 274665 1 113 MS Provide current inspection tag for fire extinguisher
322840 04/26/2011 274863 1 156 MS Provide current inspection tag for fire extinguisher
322829 04/26/2011 274840 1 194 MS Provide current inspection tag for fire extinguisher
322848 04/26/2011 274881 1 294 MS Provide current inspection tag for fire extinguisher
282172 02/14/2011 186830 1 150F M Repair damaged smoke hatch release
308793 02/14/2011 244079 3 292 M Repair leak in chilled water line at the back of air handler unit (water dripping onto floor)
199902 02/14/2011 63691 1 0000 C Provide auto closers on all doors to corridor
199899 02/14/2011 24226 1 0000 CS Provide automatic fire sprinkler coverage for covered play pavilion at exterior stage (no longer required as per Mark Lodge 2-14-11)
308753 04/15/2010 243998 1 100C M Determine cause of water damaged ceiling tiles in corridor adjacent to 1-191 and replace tiles
308751 04/15/2010 243994 1 116 M Determine cause of water damaged ceiling tiles and replace tiles
282110 04/15/2010 186695 1 116 M Seal gap between fire sprinkler escutcheon and ceiling tile
308752 04/15/2010 243996 1 117 M Determine cause of water damaged ceiling tiles and replace tiles
308758 04/15/2010 244008 1 124 M Replace missing ceiling tiles
308759 04/15/2010 244010 1 124 M Replace missing escutcheon on fire sprinkler head
308781 04/15/2010 244054 1 125 M Determine cause of water damaged ceiling tiles and replace tiles
308760 04/15/2010 244012 1 134 M Replace missing signage indicating room name and number
308762 04/15/2010 244016 1 147 M Replace missing signage indicating room name and number on outside wall
298577 04/15/2010 221902 1 150 M Replace number on maximum occupancy sign to indicate maximum occupancy = 463 (per Angel Goitia, 6/10/09)
308771 04/15/2010 244034 1 150F M Determine cause of water damaged ceiling tiles and replace tiles
282171 04/15/2010 186828 1 150F M Repair or remove damaged stage curtain
308768 04/15/2010 244028 1 153 M Repair kinked dryer vent to work properly
308769 04/15/2010 244030 1 153 M Replace missing signage indicating room name and number
308764 04/15/2010 244020 1 156 M Replace missing signage indicating room name and number
308765 04/15/2010 244022 1 157 M Replace missing signage indicating room name and number
308774 04/15/2010 244040 1 160C M Determine cause of water damaged ceiling tiles and replace tiles
308775 04/15/2010 244042 1 170 M Replace missing ceiling tiles
308776 04/15/2010 244044 1 170C M Repair door to close properly
308789 04/15/2010 244071 1 185 M Determine cause of water damaged ceiling tiles and replace tiles
308754 04/15/2010 244000 1 192 M Determine cause of water damaged ceiling tiles and replace tiles
308777 04/15/2010 244046 1 196 M Replace damaged ceiling tiles
308772 04/15/2010 244036 1 198 M Determine cause of water damaged ceiling tiles and replace tiles
298576 04/15/2010 221900 1 200 M Replace number on maximum occupancy sign to indicate maximum occupancy = 174 (per Angel Goitia, 6/10/09)
308786 04/15/2010 244064 1 203 M Determine cause of water damaged ceiling tiles and replace tiles
308782 04/15/2010 244056 1 204A M Replace missing signage indicating room name and number
308784 04/15/2010 244060 1 206 M Determine cause of water damaged ceiling tiles and replace tiles
308787 04/15/2010 244067 1 207 M Determine cause of water damaged ceiling tiles and replace tiles
308788 04/15/2010 244069 1 207 M Repair door to close properly (door rubs on jamb)
308779 04/15/2010 244050 1 291A M Replace missing signage indicating room name and number
308792 04/15/2010 244077 3 005 M Repair deteriorated wall finish at bottom of stair landing next to exteior exit door
308790 04/15/2010 244073 3 107 M Determine cause of water damaged ceiling tiles and replace tiles
308794 04/15/2010 244081 3 201B M Replace missing escutcheon on fire sprinkler head
308757 04/15/2010 244006 1 124B O Replace burned out bulbs in light fixture
308766 04/15/2010 244024 1 155 O Keep area within 18" of fire sprinkler head clear
308778 04/15/2010 244048 1 195 O Replace burned out bulbs in light fixture
308770 04/15/2010 244032 1 290 O Replace burned out bulbs in light fixture
308749 04/15/2010 243990 00 0000 C Provide exterior signage indicating property address
204002 04/15/2010 78765 1 123 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
252298 04/15/2010 125020 1 124B C Provide signage indicating room name and number at appropriate height with raised and Braille characters
290752 04/15/2010 205172 1 146 C Provide illuminated exit sign above door to dining room - M O = 74
253875 04/15/2010 128612 1 149 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
203990 04/15/2010 78741 1 150 C Provide illuminated exit sign @ northwest corridor doors
204004 04/15/2010 78767 1 150C C Provide signage indicating room name and number at appropriate height with raised and Braille characters
204011 04/15/2010 78774 1 292 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
204013 04/15/2010 78776 2 101 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
255130 04/15/2010 131289 3 005 C Adjust steps to make risers equal (upper run of stairs) (the dimensions were re-measured and approved as accetable by Victor Chodora, 4-23-10)
255113 04/15/2010 131255 3 104A C Provide signage indicating room name and number at appropriate height with raised and Braille characters
255114 04/15/2010 131257 3 104B C Provide signage indicating room name and number at appropriate height with raised and Braille characters
255123 04/15/2010 131275 3 170 C Provide signage indicating room name and number at appropriate height with raised and Braille characters (elevator)
308750 04/15/2010 243992 1 113 MS Provide current inspection tag for fire extinguisher
308763 04/15/2010 244018 1 149 MS Provide current inspection tag for fire extinguisher
199909 04/15/2010 24428 1 150B MS Verify that electricity and gas to appliances shuts off upon activation of hood suppression system
308767 04/15/2010 244026 1 155 MS Provide current inspection tag for fire extinguisher
308785 04/15/2010 244062 1 205 MS Provide current inspection tag for fire extinguisher
308783 04/15/2010 244058 1 206 MS Provide current inspection tag for fire extinguisher
308780 04/15/2010 244052 1 291A MS Provide current inspection tag for fire extinguisher
308755 04/15/2010 244002 1 294 MS Provide current inspection tag for fire extinguisher
308791 04/15/2010 244075 3 193 MS Seal penetration around conduit in ceiling to prevent spread of fire or smoke
308761 04/15/2010 244014 1 148 OS Remove storage from mechanical room
282169 02/01/2010 186824 1 150G M Relocate light fixtures that interfere with coverage of fire sprinkler heads (location is o.k. according to County Fire Inspector Chris Finkley)
282157 02/01/2010 186797 1 150K M Provide room number on sign indicating room name
282097 02/01/2010 186669 1 101 MS Replace missing fire extinguisher adjacent to corridor door (not needed according to County Fire Inspector Chris Finkley, another fire extinguisher is located within 75 feet)
290758 03/20/2009 205187 00 0000 M Repair or replace rusted window and door frames in interior courtyard
255133 03/20/2009 131297 1 0000 M Repair or replace leaking gutter at school entrance -east side
282159 03/20/2009 186804 1 0000 M Repair lights in all exit signs in interior courtyard
282106 03/20/2009 186687 1 100B M Repair light in exit sign outside 1-106
282109 03/20/2009 186693 1 116 M Determine cause of water damaged ceiling tiles and replace tiles
290721 03/20/2009 205111 1 117 M Determine cause of water damaged ceiling tiles and replace tiles
290723 03/20/2009 205115 1 120 M Replace missing escutcheon on fire sprinkler head
290722 03/20/2009 205113 1 123 M Determine cause of water damaged ceiling tiles and replace tiles
282112 03/20/2009 186699 1 124B M Replace bulbs in light fixture
282131 03/20/2009 186744 1 144 M Provide number on sign indicating room name
282132 03/20/2009 186747 1 145 M Provide number on sign indicating room name
290743 03/20/2009 205155 1 150K M Replace missing escutcheon on fire sprinkler head
290756 03/20/2009 205181 1 157 M Repair door lever on inside face of door to turn easily
290741 03/20/2009 205151 1 158 M Replace missing escutcheon on fire sprinkler head
290724 03/20/2009 205117 1 173 M Replace missing escutcheon on fire sprinkler head
282192 03/20/2009 186871 1 174A M Seal gap between fire sprinkler escutcheon and ceiling
290748 03/20/2009 205166 1 196 M Replace missing signage indicating room name and number
282224 03/20/2009 186938 1 203 M Repair light in exit sign
290749 03/20/2009 205169 1 204 M Secure ceiling tiles in place
282215 03/20/2009 186920 1 205 M Repair light in exit sign
282223 03/20/2009 186936 1 206 M Repair light in exit sign
282111 03/20/2009 186697 1 292 M Replace bulbs in light fixture
282146 03/20/2009 186778 3 0000 M Label fire department connections north of Bldg. 3
290727 03/20/2009 205123 3 190 M Replace missing signage indicating room name and number
290726 03/20/2009 205121 3 193 M Determine cause of water damaged ceiling tiles and replace tiles
255116 03/20/2009 131261 3 201B M Replace missing escutcheon on fire sprinkler head
290728 03/20/2009 205125 3 202A M Replace missing signage indicating room name and number
290725 03/20/2009 205119 3 204B M Replace missing escutcheon on fire sprinkler head
290737 03/20/2009 205143 3 204C M Replace missing cap on sink faucet
290735 03/20/2009 205139 3 207 M Adjust door closer to control speed of closing door
290746 03/20/2009 205161 1 136A O Relocate storage bins to keep area within 18" of fire sprinkler head clear
290745 03/20/2009 205159 1 147 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
290739 03/20/2009 205147 1 152 O Replace burned bulbs in light fixture
290740 03/20/2009 205149 1 158 O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
290747 03/20/2009 205164 1 169A O Maintain storage room in an orderly manner
290738 03/20/2009 205145 1 187 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
290757 03/20/2009 205185 1 189 O Prohibit piggy backed surge protectors and extension cords under teacher's desk - plug each surge protector directly into wall outlet and eliminate use of extension cord with multiple outlet end
290729 03/20/2009 205127 3 110 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
282197 03/20/2009 186881 3 201 O Replace bulbs in light fixture
290744 03/20/2009 205157 1 147 MS Provide current inspection tag for fire extinguisher (X2)
290742 03/20/2009 205153 1 160D MS Close hatch on ceiling
290733 03/20/2009 205135 3 103 MS Adjust fire door to latch properly
290730 03/20/2009 205129 3 192 MS Provide current inspection tag for fire extinguisher
290731 03/20/2009 205131 3 191 OS Remove and prohibit golfcart storage in mechanical room
290734 03/20/2009 205137 3 205 OS Prohibit use of wedge to hold fire door in open position
290736 03/20/2009 205141 3 292 OS Remove custodial storage from mechanical room
282161 11/18/2008 186808 1 0000 M Repair damaged rain gutter in interior courtyard
282116 11/18/2008 186707 1 124 M Replace missing escutcheons on two fire sprinkler heads near exterior door
253890 11/18/2008 128635 1 146 M Install maximum occupancy signage inside music room with appropriate occupancy number( current signage is outside door indicating occupancy of 1.297 - actual max. occ. = 74)
282151 11/18/2008 186787 1 150L M Seal gap between fire sprinkler escutcheon and ceiling
282167 11/18/2008 186820 1 156 M Replace missing escutcheon on fire sprinkler head
204007 11/18/2008 78770 1 158 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
253922 11/18/2008 128711 1 160D M Replace corroded fire sprinkler head and escutcheon
204008 11/18/2008 78771 1 161 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
282206 11/18/2008 186902 1 184 M Adjust exterior door to latch properly
255121 11/18/2008 131271 3 106A M Replace missing escutcheon on fire sprinkler head
282177 11/18/2008 186840 3 201C M Replace missing escutcheon on fire sprinkler head
282175 11/18/2008 186836 1 159C O Replace bulbs in light fixture
282100 11/18/2008 186675 1 100A FS Make repairs to fire alarm system as indicated on inspection report dated 11/28/2007
282118 04/16/2008 186711 1 100D M Replace missing escutcheon on fire sprinkler head outside 1-121
282164 04/16/2008 186814 1 100L M Replace missing escutcheon on fire sprinkler head outside 1-180
282216 04/16/2008 186922 1 100M M Replace missing escutcheon on fire sprinkler head outside 1-185
282098 04/16/2008 186671 1 101 M Provide appropriate support bracket for defibrillator (hung from fire extinguisher bracket)
282099 04/16/2008 186673 1 102 M Determine cause of water damaged ceiling tiles and replace tiles
282115 04/16/2008 186705 1 123 M Determine cause of water damaged ceiling tiles and replace tiles
282113 04/16/2008 186701 1 124B M Replace missing ceiling tiles
282128 04/16/2008 186738 1 126B M Repair inoperable lock on bathroom door
282129 04/16/2008 186741 1 144 M Replace missing escutcheon on fire sprinkler head
282102 04/16/2008 186679 1 146 M Determine cause of water damaged ceiling tiles and replace tiles
282144 04/16/2008 186774 1 150 M Determine cause of water damaged ceiling tiles and replace tiles
282173 04/16/2008 186832 1 150F M Determine cause of water damaged ceiling tiles and replace tiles at smoke hatch
282154 04/16/2008 186790 1 150L M Provide room number on sign indicating room name
253880 04/16/2008 128621 1 152A M Replace missing escutcheon on fire sprinkler head
204005 04/16/2008 78768 1 152A M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
204006 04/16/2008 78769 1 156 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
253879 04/16/2008 128619 1 156 M Replace rusted fire sprinkler head
204009 04/16/2008 78772 1 161A M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
282191 04/16/2008 186869 1 167 M Determine cause of water damaged ceiling tiles and replace damaged and missing tiles
282184 04/16/2008 186855 1 178 M Determine cause of water damaged ceiling tiles and replace tiles
282204 04/16/2008 186898 1 184 M Replace missing ceiling tiles
282222 04/16/2008 186934 1 188 M Determine cause of water damaged ceiling tiles and replace tiles
282179 04/16/2008 186844 1 191 M Replace missing signage indicating room name and number
282149 04/16/2008 186784 1 195 M Repair leaking a/c unit
282207 04/16/2008 186904 1 205 M Determine cause of water damaged ceiling tiles and replace tiles
282214 04/16/2008 186918 1 291A M Replace out of place ceiling tile
282212 04/16/2008 186914 1 294 M Replace missing escutcheon on fire sprinkler head
282196 04/16/2008 186879 3 007 M Repair hole in wall at top of steps
282180 04/16/2008 186847 3 193 M Determine cause of water damaged ceiling tiles and replace damaged and missing tiles
282200 04/16/2008 186888 3 210 M Repair leaking drinking spigot at sink
282201 04/16/2008 186890 3 210 M Replace missing escutcheon on fire sprinkler head
282160 04/16/2008 186806 1 0000 O Clean algae from sidewalk in interior courtyard
282117 04/16/2008 186709 1 104 O Eliminate extension cord or replace with minimum 15A cord
282105 04/16/2008 186685 1 105 O Remove and prohibit air freshener
282107 04/16/2008 186689 1 107 O Remove and prohibit air freshener spray
282108 04/16/2008 186691 1 108 O Remove and prohibit air freshener spray
282103 04/16/2008 186681 1 110 O No access was available to this room. Please be prepared to access this room during the report review meeting.
282104 04/16/2008 186683 1 113 O No access was available to this room. Please be prepared to access this room during the report review meeting.
282143 04/16/2008 186772 1 127 O Replace bulbs in emergency lights
282142 04/16/2008 186769 1 139 O Replace bulbs in emergency lights
282141 04/16/2008 186750 1 141 O Replace bulbs in emergency lights
282101 04/16/2008 186677 1 147 O No access was available to this room. Please be prepared to access this room during the report review meeting.
282166 04/16/2008 186818 1 149 O No access was available to this room. Please be prepared to access this room during the report review meeting.
282163 04/16/2008 186812 1 155A O Remove and prohibit air freshener spray
282185 04/16/2008 186857 1 166 O Eliminate extension cord or replace with minimum 15A cord
282187 04/16/2008 186861 1 167 O Replace bulbs in emergency lights
282188 04/16/2008 186863 1 168 O Replace bulbs in emergency lights
282189 04/16/2008 186865 1 173 O Replace bulbs in emergency lights
282174 04/16/2008 186834 1 174 O Highlight evacuation route map to show evacuation from correct classroom
282181 04/16/2008 186849 1 178 O Eliminate extension cord or replace with minimum 15A cord
282182 04/16/2008 186851 1 178 O Prohibit plugging surge protector into extension cord
282183 04/16/2008 186853 1 178 O Prohibit taping electrical cords to floor
282202 04/16/2008 186893 1 183 O Replace bulbs in emergency lights
282217 04/16/2008 186924 1 185 O Eliminate extension cord or replace with minimum 15A cord
282218 04/16/2008 186926 1 185 O Prohibit plugging surge protector into extension cord
282209 04/16/2008 186908 1 189 O Replace bulbs in emergency lights
282210 04/16/2008 186910 1 200 O Remove and prohibit nets hanging from ceiling with lights suspended from ceiling
282226 04/16/2008 186942 1 203 O Eliminate extension cord at computer or replace with minimum 15A cord
282221 04/16/2008 186932 1 207 O Remove and prohibit air freshener at a/c vent
282194 04/16/2008 186875 3 105 O Eliminate extension cord or replace with minimum 15A cord
282114 04/16/2008 186703 1 122 C Provide emergency lighting in student space or prohibit use as student space
282162 04/16/2008 186810 1 150B MS Provide current inspection for kitchen hood fire suppression system (dated 7/07)
282168 04/16/2008 186822 1 150G MS Provide current inspection tag for fire extinguisher
282225 04/16/2008 186940 1 203 MS Provide current inspection tag for fire extinguisher and remove unused fire extinguisher
282213 04/16/2008 186916 1 294 MS Provide current inspection tag for fire extinguisher
282148 04/16/2008 186781 1 134 OS Remove storage blocking clear path to exterior door
282176 04/16/2008 186838 1 150F OS Remove tables from stage ramp
282186 04/16/2008 186859 1 166 OS Prohibit running extension cord under rug
282190 04/16/2008 186867 1 169 OS Remove desks from exit corridor
282178 04/16/2008 186842 1 175 OS Remove and prohibit use of hot plate
282203 04/16/2008 186896 1 183 OS Remove storage blocking clear path to exterior door
282205 04/16/2008 186900 1 184 OS Relocate file cabinet blocking clear path to exterior door
282219 04/16/2008 186928 1 185 OS Remove storage blocking clear path to corridor door
282208 04/16/2008 186906 1 189 OS Relocate desk blocking clear path to corridor door
282211 04/16/2008 186912 1 192 OS Relocate table blocking clear path to corridor door
282220 04/16/2008 186930 1 194 OS Remove storage from mechanical room
282195 04/16/2008 186877 3 105 OS Prohibit running extension cord under rug
282193 04/16/2008 186873 3 112 OS Relocate table blocking clear path to corridor door
282198 04/16/2008 186883 3 201 OS Relocate chairs blocking clear path to corridor door
282199 04/16/2008 186885 3 203 OS Relocate chairs blocking clear path to corridor door
199898 01/23/2008 63680 00 0000 C Center exit sign over correct door leaf for all smoke stop doors in corridors
199915 01/23/2008 24338 1 170 C Provide emergency lighting in room (no emergency light shown on design plans)
255131 01/23/2008 131292 3 291 C Provide engineer's evaluation of cracked concrete ceiling and masonry wall and repair according to engineer's recommendation
204000 09/08/2006 78761 00 9599 M Maintain lawn sprinkler system to prevent dry areas of lawn
203994 09/08/2006 78749 1 0000 M Repair rusted downspout on both sides of main entrance (north side of building)
253907 09/08/2006 128680 1 0000 M Repair electrical outlet at exterior stage ( see PE teacher Mr. Peccio)
252281 09/08/2006 124980 1 100J M Replace missing escutcheon on fire sprinkler head in corridor between courtyard and 1-150J
204015 09/08/2006 78780 1 100K M Lower sprinkler head in corridor @ 1-184 so head projects minimum 1" below ceiling
253857 09/08/2006 128570 1 122 M Replace missing ceiling tiles
253858 09/08/2006 128572 1 122 M Provide cover on exposed electrical junction box above light switch
253856 09/08/2006 128568 1 124B M Replace missing ceiling tiles
253892 09/08/2006 128648 1 150C M Replace missing escutcheon on fire sprinkler head
204017 09/08/2006 78784 1 150F M Provide dated flame resistance label on stage curtain
253905 09/08/2006 128676 1 150G M Repair light fixture hanging from wires
253901 09/08/2006 128665 1 152 M Remove metal shelf under fire sprinkler head
252295 09/08/2006 125014 1 153 M Replace missing escutcheon on fire sprinkler head
199913 09/08/2006 63710 1 158 M Replace sprinkler head with paint on it
253909 09/08/2006 128684 1 160C M Determine cause of water damaged ceiling tiles and replace tiles
253904 09/08/2006 128674 1 161 M Replace missing escutcheon on fire sprinkler head
252267 09/08/2006 124950 1 166A M Replace missing escutcheon on fire sprinkler head
253917 09/08/2006 128701 1 168A M Replace missing escutcheon on fire sprinkler head
253924 09/08/2006 128715 1 180 M Replace missing escutcheon on fire sprinkler head
253927 09/08/2006 128721 1 184 M Repair door lever to open easily
253920 09/08/2006 128707 1 189 M Replace missing escutcheon on fire sprinkler head in bathroom vestibule between 1-189 & 1-190
253919 09/08/2006 128705 1 194 M Repair light fixture in mechanical room
255128 09/08/2006 131285 3 0000 M Adjust water flow for all classroom drinking fountains in Bldg. 3
255117 09/08/2006 131263 3 101A M Secure loose escutcheon on fire sprinkler head
255124 09/08/2006 131277 3 102 M Determine cause of water damaged ceiling tiles and replace tiles
255119 09/08/2006 131267 3 103 M Repair door to open and close properly - door rubs on frame
255122 09/08/2006 131273 3 103A M Replace missing escutcheon on fire sprinkler head
255127 09/08/2006 131283 3 112A M Secure light fixture in place
255118 09/08/2006 131265 3 180 M Adjust door to latch properly
255120 09/08/2006 131269 3 190 M Replace missing escutcheon on fire sprinkler head
255115 09/08/2006 131259 3 290 M Determine cause of water damaged ceiling tiles and replace tiles
199931 09/08/2006 24458 P 3667 M Adjust steps to make risers equal
199928 09/08/2006 63709 P 3743 M Adjust ramp boards to be even
252296 09/08/2006 125016 P 3743 M Repair emergency lighting
199926 09/08/2006 24449 P 608 M Adjust steps to make risers equal
203987 09/08/2006 78734 P 776 M Repair emergency lighting
199922 09/08/2006 24446 P 777 M Adjust steps to make risers equal
253859 09/08/2006 128574 1 127 O Remove and prohibit combustible bean bag chair
253861 09/08/2006 128578 1 132 O Remove and prohibit flammable decorations around door
253873 09/08/2006 128604 1 134 O Remove and prohibit combustible residential children furniture
253868 09/08/2006 128587 1 139 O Prohibit plugging one surge protector into another under computer stations at NE corner
253871 09/08/2006 128601 1 140 O Remove and prohibit use of toaster
253881 09/08/2006 128624 1 147 O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
204023 09/08/2006 78796 1 149 O Maintain storage room in an orderly manner
253902 09/08/2006 128670 1 151 O Eliminate 13A extension cord or replace with minimum 15A cord
253923 09/08/2006 128713 1 169 O Highlight evacuation routes on evacuation map
253926 09/08/2006 128719 1 173 O Remove and prohibit combustible beanbag chair - shape of whale
253925 09/08/2006 128717 1 180 O Replace burned out bulbs in light fixtures
253918 09/08/2006 128703 1 185 O Remove and prohibit use of toaster
253921 09/08/2006 128709 1 188 O Eliminate multiple outlet adaptor adjacent to microwave
253855 09/08/2006 128565 1 192A O Replace flickering light bulb
252189 09/08/2006 124784 1 203 O Eliminate multiple outlet extension cord powering VCR
252185 09/08/2006 124776 1 206 O Eliminate yellow 13 amp extension cord lying on floor
255126 09/08/2006 131281 3 110 O Remove and prohibit combustible beanbag chairs
199907 09/08/2006 24377 1 146 C Provide sign indicating maximum occupancy adjacent to main entrance
252182 09/08/2006 124771 1 206 C Provide auto closer on corridor door
199919 09/08/2006 24379 P 776 C Provide ramp for portable
253870 09/08/2006 128596 1 139 MS Replace ABC fire extinguisher with a CO2 fire extinguisher
255132 09/08/2006 131295 3 006 MS Align magnetic release hardware on fire doors and walls at elevator vestibule - 2nd floor
255125 09/08/2006 131279 3 113 MS Provide current inspection tag for fire extinguisher
253848 09/08/2006 128550 1 115 OS Remove tables and chairs from exit hallway adjacent to 1-116
253884 09/08/2006 128633 1 147 OS Prohibit use of wedge to hold fire door in open position
253883 09/08/2006 128630 1 148 OS Remove storage from mechanical room
253897 09/08/2006 128654 1 150 OS Relocate bench booth blocking access to fire extinguisher cabinet at NW corner
253903 09/08/2006 128672 1 150 OS Relocate tables blocking clear access to fire alarm pull station adjacent to SE corner
252285 09/08/2006 124990 1 150F OS Remove and prohibit storage along stage ramp, north side of stage
253878 09/08/2006 128617 1 156 OS Remove storage from boiler room
253906 09/08/2006 128678 1 158 OS Prohibit running extension cord under door
253853 09/08/2006 128558 1 293 OS Remove table and chairs from mechanical room
255129 09/08/2006 131287 3 208 OS Prohibit use of wedge to hold fire door in open position
199929 09/08/2006 63682 P 3743 OS Keep door unlocked when facility is occupied to allow access to fire alarm pull station
255112 09/08/2006 131253 00 0000 FS Repair fire alarm system - alarm panel indicates trouble
254984 09/08/2006 131007 0 0 N/A Note: Portables are not in use. They are scheduled for demolition
254985 09/08/2006 131010 P 3667 N/A No violations observed
254986 09/08/2006 131012 P 3743 N/A No violations observed
254987 09/08/2006 131014 P 608 N/A No violations observed
254988 09/08/2006 131016 P 776 N/A No violations observed
254990 09/08/2006 131020 P 777 N/A No violations observed
199903 05/10/2006 65467 00 9599 M Repair broken sidewalk @ east end of north parking lot
252210 05/10/2006 124831 1 100D M Replace missing escutcheon on fire sprinkler head in corridor adjacent to 1-293
252224 05/10/2006 124857 1 100E M Replace missing escutcheon on fire sprinkler head in corridor adjacent to 1-141
252247 05/10/2006 124903 1 100E M Replace damaged ceiling tile in corridor adjacent to 1-127
252177 05/10/2006 124762 1 101 M Replace missing escutcheon on fire sprinkler head above receptionist desk
252179 05/10/2006 124768 1 116 M Determine cause of water damaged ceiling tiles and replace tiles
252211 05/10/2006 124833 1 123 M Determine cause of water damaged ceiling tiles and replace tiles
252212 05/10/2006 124835 1 124 M Replace missing ceiling tiles
252215 05/10/2006 124840 1 128 M Eliminate ant infestation at exterior exit door
252238 05/10/2006 124888 1 136B M Determine cause of water damaged ceiling tiles and replace tiles in closet
252222 05/10/2006 124852 1 140 M Repair light in exit sign
252227 05/10/2006 124868 1 142 M Repair light in exit sign
252229 05/10/2006 124871 1 143 M Replace missing signage indicating room name and number
252231 05/10/2006 124874 1 143 M Determine cause of water damaged ceiling tiles and replace tiles by window
252232 05/10/2006 124879 1 143 M Repair light in exit sign
252292 05/10/2006 125006 1 146 M Replace missing escutcheon on fire sprinkler head
252289 05/10/2006 124999 1 147 M Replace missing escutcheons on fire sprinkler heads (x3) in custodial receiving room
252287 05/10/2006 124997 1 150 M Repair exterior exit door at southeast corner of cafeteria to latch properly
252275 05/10/2006 124969 1 150F M Repair exit door to outside stage to close properly
252286 05/10/2006 124994 1 150G M Close ceiling hatch
203993 05/10/2006 78747 1 157 M Provide certification that emergency generator is operable
252272 05/10/2006 124964 1 160 M Replace missing escutcheon on fire sprinkler head
252269 05/10/2006 124953 1 165 M Determine cause of water damaged ceiling tiles and replace tiles
252270 05/10/2006 124957 1 165 M Repair light in exit sign
252265 05/10/2006 124947 1 168 M Replace missing escutcheon on fire sprinkler head
252256 05/10/2006 124927 1 179 M Determine cause of water damaged ceiling tiles and replace tiles
252191 05/10/2006 124793 1 182 M Replace missing escutcheon on fire sprinkler head
252194 05/10/2006 124795 1 183 M Replace missing ceiling tiles by windows
252197 05/10/2006 124803 1 185 M Determine cause of water damaged ceiling tiles and replace tiles
252199 05/10/2006 124807 1 186 M Determine cause of water damaged ceiling tiles and replace tiles
252203 05/10/2006 124815 1 191 M Repair or replace damaged cabinet door by windows
252206 05/10/2006 124823 1 192 M Determine cause of water damaged ceiling tiles and replace tiles
252190 05/10/2006 124789 1 207 M Replace missing escutcheon on fire sprinkler head
252297 05/10/2006 125018 P 777 M Replace broken window glass by ramp
252239 05/10/2006 124894 1 129 O Remove and prohibit combustible beanbag chairs
252242 05/10/2006 124898 1 129 O Remove and prohibit Christmas tree lights
252217 05/10/2006 124844 1 131 O Eliminate multiple outlet extension cord at rear door
252271 05/10/2006 124959 1 163 O Eliminate 13 amp extension cord by computers
252264 05/10/2006 124944 1 168 O Post sign indicating evacuation routes
252262 05/10/2006 124940 1 171 O Post sign indicating evacuation routes
252261 05/10/2006 124936 1 173 O Post sign indicating evacuation routes
252258 05/10/2006 124930 1 175 O Eliminate 3-way outlet adaptor by microwave
252278 05/10/2006 124974 1 0000 MS Provide current inspection tag for fire extinguisher in exterior courtyard adjacent to 1-163
252234 05/10/2006 124882 1 139 MS Provide current inspection tag for fire extinguisher
252294 05/10/2006 125011 1 150B MS Provide current inspection tag for kitchen hood fire suppression system (tag indicates inspection date 07-05)
252201 05/10/2006 124811 1 187 MS Provide current inspection tag for fire extinguisher
252251 05/10/2006 124916 1 195A MS Provide current inspection tag for fire extinguisher
252249 05/10/2006 124913 1 291A MS Provide current inspection tag for fire extinguisher
252208 05/10/2006 124826 1 294 MS Provide current inspection tag for fire extinguisher
252219 05/10/2006 124847 1 131 OS Maintain clear aisle to both exit doors
204022 05/10/2006 78794 1 148 OS Remove storage from mechanical room
252205 05/10/2006 124819 1 192 OS Maintain clear aisle to corridor door
252436 04/17/2006 125323 P 3677 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
252437 04/17/2006 125325 P 3743 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
199924 04/17/2006 29659 P 608 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
252438 04/17/2006 125327 P 776 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
252439 04/17/2006 125329 P 777 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
199900 03/16/2006 24343 00 0000 M Provide verification that all student occupied spaces have emergency lights and all are operable
203978 03/16/2006 78720 1 150 M Determine cause of water damaged ceiling tiles and replace tiles
203995 03/16/2006 78751 1 150E M Repair auto closer on freezer door
203992 03/16/2006 78745 P 3743 M Repair damaged flooring
203986 03/16/2006 78732 1 150F O Provide clear access to electrical panel
204003 03/16/2006 78766 1 149 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
199914 03/16/2006 24378 1 160D C Redirect kiln vent to exhaust to the exterior rather than to the covered pavilion
204010 03/16/2006 78773 1 196 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
199916 03/16/2006 24340 1 200 C Provide panic hardware on corridor door adjacent to 1-101 (occupancy is greater than 100)
204012 03/16/2006 78775 1 294B C Provide signage indicating room name and number at appropriate height with raised and Braille characters
204021 03/16/2006 78792 1 157 OS Remove storage from generator room
199901 03/16/2006 63701 00 0000 CS Provide "Knox" padlock on gate to allow fire department access
203972 12/17/2004 78714 1 100K M Determine cause of water damaged ceiling tiles and replace tiles
203973 12/17/2004 78715 1 114 M Determine cause of water damaged ceiling tiles and replace tiles
203974 12/17/2004 78716 1 120 M Determine cause of water damaged ceiling tiles and replace tiles
199905 12/17/2004 24423 1 135 M Provide current inspection log for hot water heater
203975 12/17/2004 78717 1 136 M Determine cause of water damaged ceiling tiles and replace tiles
203998 12/17/2004 78757 1 136 M Provide cover on exposed electrical junction box @ clock
203976 12/17/2004 78718 1 146 M Determine cause of water damaged ceiling tiles and replace tiles
203977 12/17/2004 78719 1 146A M Determine cause of water damaged ceiling tiles and replace tiles
199910 12/17/2004 24427 1 150B M Replace missing cover for thermostat outside 1-155
199912 12/17/2004 24431 1 150F M Determine cause of water damaged ceiling tiles and replace tiles
204018 12/17/2004 78786 1 150F M Provide warning strip along edge of stage
203997 12/17/2004 78755 1 156 M Provide current inspection tag for boiler
203979 12/17/2004 78721 1 158 M Determine cause of water damaged ceiling tiles and replace tiles
204016 12/17/2004 78782 1 200 M Replace missing escutcheon on fire sprinkler head @ south wall, above pull station
203980 12/17/2004 78722 1 205 M Determine cause of water damaged ceiling tiles and replace tiles
199917 12/17/2004 24444 1 207 M Provide current inspection log for hot water heater
203981 12/17/2004 78723 P 776 M Determine cause of water damaged ceiling tiles and replace tiles
204019 12/17/2004 78788 P 776 M Repair or replace deteriorated handrail/guardrail for stairs
203982 12/17/2004 78724 P 777 M Determine cause of water damaged ceiling tiles and replace tiles
203996 12/17/2004 78753 1 0000 O Remove rusted and broken waste container inside courtyard
204014 12/17/2004 78778 1 152 O Remove top storage shelf to keep area within 18" of automatic fire sprinkler heads clear and unobstructed
203988 12/17/2004 78736 1 201 O Eliminate multiple extension cords
203999 12/17/2004 78759 1 291A O Replace burned out light bulb or have maintenance repair light fixture
199906 12/17/2004 24337 1 136 C Provide or verify emergency lighting in room
199930 12/17/2004 29663 P 3667 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
199927 12/17/2004 63684 P 3743 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
199918 12/17/2004 29658 P 776 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
199920 12/17/2004 29659 P 777 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
203991 12/17/2004 78743 1 0000 MS Provide current inspection tags for all fire extinguishers throughout campus (last inspection date 11/03)
204020 12/17/2004 78790 1 121 OS Remove desk and files from communications room and prohibit use as an office
203984 12/17/2004 78728 1 150 OS Relocate table booth @ northwest corridor exit door to maintain clear aisle to exit
203989 12/17/2004 78738 1 206 OS Prohibit electrical cord from running through wall from 206A
203985 12/17/2004 78730 P 3667 OS Maintain clear aisle to exit
199908 06/30/2004 24424 1 146 M Repair or replace rippled carpeting
199911 06/30/2004 63671 1 150E M Repair noisy fan in walk-in freezer
199896 06/30/2004 24375 00 0000 C Provide sign indicating maximum occupancy adjacent to main entrance at covered PE area
199904 06/30/2004 63676 1 105 C Complete wiring to printer
199925 06/30/2004 24393 P 608 C Provide guardrails at stair landing at a minimum 42 inches high
199921 06/30/2004 63708 P 777 C Provide bottom rail on ramp landing guardrail at two inches above floor