ROYAL PALM BEACH ELEMENTARY
 
ROYAL PALM BEACH ELEMENTARY
11911 OKEECHOBEE BLVD
ROYAL PALM BEACH, 33411
FISH Drill Down
 Campus Info.
 Buildings:3 Rooms:235
 Portables:4
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
408598 03/27/2018 461682 00 0000 M Make necessary repairs to fire sprinkler system
402275 03/27/2018 447939 1 186B M Repair exhaust fan in bathroom
313050 03/27/2018 253601 P 0000 C Modify roof drainage from portables. Rain water leader drops water at bottom of exterior wall of portable and is going under units and undermining sidewalks
280327 03/27/2018 182957 2 0000 N/A No violations observed
234639 03/27/2018 91969 P 9669 N/A No violations observed
234636 03/27/2018 91963 P 9670 N/A No violations observed
234637 03/27/2018 91965 P 9671 N/A No violations observed
234638 03/27/2018 91967 P 9672 N/A No violations observed
408632 02/27/2018 461757 1 001 M Determine cause of water damaged ceiling tiles at 1-192A and replace tiles
408721 02/27/2018 461947 1 128 M Determine cause of water damaged ceiling tiles and replace tiles
408725 02/27/2018 461955 1 137 M Determine cause of water damaged ceiling tiles and replace tiles
408734 02/27/2018 461976 1 142 M Repair auto closer on door
408733 02/27/2018 461974 1 143B M Repair exhaust fan at stove
408728 02/27/2018 461961 1 148 M Adjust exterior door to latch properly
408653 02/27/2018 461805 1 150E M Repair door to close properly
408663 02/27/2018 461823 1 151C M Repair damaged wall at top of ramp at stage
408730 02/27/2018 461965 1 158 M Determine cause of water damaged ceiling tiles and replace tiles
408630 02/27/2018 461752 1 192 M Repair air conditioning system to ensure it operates as designed
408724 02/27/2018 461953 1 222 M Determine cause of water damaged ceiling tiles and replace tiles
408722 02/27/2018 461949 1 291 M Repair leaking air conditioning system to ensure it operates as designed
408726 02/27/2018 461957 2 101 M Clean plants and trees growing in gutters and downspouts
408684 02/27/2018 461868 P 9669 M Determine cause of water damaged ceiling tiles and replace tiles, replace missing tiles
408718 02/27/2018 461941 P 9669 M Secure loose data outlet on north wall
408719 02/27/2018 461943 P 9669 M Repair bathroom door to close properly
408681 02/27/2018 461863 P 9671 M Repair emergency lighting
408682 02/27/2018 461865 P 9671 M Determine cause of water damaged ceiling tiles and replace tiles
408720 02/27/2018 461945 1 126 O Prohibit use of black multi outlet extension cord at projector or replace with minimum 15A single outlet extension cord
408723 02/27/2018 461951 1 225 O Prohibit plugging surge protector into yellow extension cord, plug surge protector directly into permanent electrical outlet
408735 02/27/2018 461979 1 138A MS Provide type K fire extinguisher, remove expired ABC fire extinguisher
408731 02/27/2018 461968 1 139B MS Provide type K fire extinguisher, remove expired ABC fire extinguisher
408732 02/27/2018 461971 1 143B MS Provide type K fire extinguisher, remove expired ABC fire extinguisher
408667 02/27/2018 461833 1 153C MS Repair thumb latch to unlock properly
408727 02/27/2018 461959 1 158B MS Recharge fire extinguisher
408665 02/27/2018 461827 1 186B MS Repair thumb latch to unlock properly
408629 02/27/2018 461748 1 191 MS Provide current inspection tag for fire extinguisher
408677 02/27/2018 461852 1 197 MS Replace missing fire extinguisher
408672 02/27/2018 461840 1 9599 MS Repair gate between P-1 and 1-149 to open properly. Adjust gate at exterior wall of 1-132 to close and latch properly
408737 02/27/2018 461985 1 0000 OS Relocate flags hanging in corridors to hang parallel to wall surface. Flags may hang no more than 2 inches from wall surface to maintain clear view of exits
408729 02/27/2018 461963 1 149B OS Prohibit storage in kiln room
402279 02/27/2018 447947 1 198 OS Remove storage from electrical room
408673 02/27/2018 461846 1 199 OS Remove storage from generator room
408644 09/20/2017 461781 1 147 O Note: 2 light green leather sofas have NFPA 701 tags though tags are loose and may fall off. Left note for teacher to keep copies of tags
402258 09/19/2017 447901 1 131 M Make necessary repairs to fire sprinkler system as indicated on inspection report. Red and yellow tags
402370 09/19/2017 448141 1 191 M Repair covers of electrical panels 1LE section 2,1LC section 1 and 1LC section 2 to latch
402401 09/19/2017 448211 1 192 M Repair cover of electrical panel 1MD to latch
402367 09/19/2017 448135 1 196 M Replace missing screws for cover of electrical panel 1DB
402433 09/19/2017 448280 1 209 M Repair light fixture
402425 05/08/2017 448261 1 202A M Repair leaking toilet supply line
402371 04/28/2017 448143 1 152K M Repair door to open and close properly. Door hits frame
402436 04/28/2017 448286 1 205A M Repair exhaust fan in bathroom
402435 04/28/2017 448284 1 209A M Repair exhaust fan in bathroom
402378 04/28/2017 448158 1 001 MS Adjust fire doors in corridor at 1-192 to latch properly
402417 03/31/2017 448243 00 0000 M Clean out all gutters, downspouts and roof drains on campus
402409 03/31/2017 448231 1 005 M Adjust corridor door to exterior to latch properly
402368 03/31/2017 448137 1 107 M Repair light fixture
402267 03/31/2017 447921 1 114 M Secure handicapped sink to wall
402369 03/31/2017 448139 1 120A M Secure sink to wall
402268 03/31/2017 447923 1 123A M Repair leaking toilet supply line
402271 03/31/2017 447930 1 124 M Secure projection screen bracket to backer board
402269 03/31/2017 447925 1 127A M Repair exhaust fan in bathroom
402270 03/31/2017 447927 1 128A M Repair exhaust fan in bathroom
402379 03/31/2017 448162 1 136A M Repair exhaust fan in bathroom
402402 03/31/2017 448214 1 138B M Repair leaking toilet supply line
402404 03/31/2017 448218 1 140A M Repair leaking toilet supply line
402405 03/31/2017 448220 1 143B M Repair range exhaust fan. Not running
402276 03/31/2017 447941 1 150A M Caulk handicapped sink to wall
402372 03/31/2017 448145 1 151A M Repair or replace hanging exit sign at Stage ramp
402274 03/31/2017 447937 1 152 M Supply fan to Kitchen hood is not working. Repair or replace fan
402272 03/31/2017 447932 1 153B M Caulk open corner in bathroom
402273 03/31/2017 447934 1 153C M Caulk open corner in bathroom
402380 03/31/2017 448164 1 157 M Repair exhaust fan in bathroom
402399 03/31/2017 448207 1 170 M Provide current inspection tag for elevator
402281 03/31/2017 447952 1 199A M Replace missing strike plate on door frame
402428 03/31/2017 448267 1 203A M Repair leaking toilet supply line
402430 03/31/2017 448273 1 204A M Repair leaking toilet supply line
402423 03/31/2017 448258 1 205A M Repair leaking toilet supply line
402434 03/31/2017 448282 1 209 M Secure projection screen bracket to wall
402431 03/31/2017 448276 1 211B M Repair leaking toilet supply line
402437 03/31/2017 448288 1 212A M Anchor toilet to floor
402421 03/31/2017 448255 1 213B M Seal crack in bathroom floor
402411 03/31/2017 448235 1 214C M Repair leaking toilet supply line
402414 03/31/2017 448239 1 217 M Remove pencil sharpener without cover at door
402440 03/31/2017 448294 1 218B M Caulk sink to wall
402441 03/31/2017 448297 1 227 M Remove pencil sharpener with out cover at door
402283 03/31/2017 447956 2 0000 M Provide lock on gate of fencing around A-C equipment at building 2
402366 03/31/2017 448133 2 103 M Repair leaking toilet supply line
402259 03/31/2017 447903 P 9669 M Determine cause of water damaged ceiling tiles and replace tiles
402260 03/31/2017 447905 P 9669 M Secure threshold at bathroom door
402261 03/31/2017 447907 P 9670 M Repair emergency lighting at front door
402262 03/31/2017 447910 P 9670 M Secure projection screen backer board to wall
402263 03/31/2017 447913 P 9671 M Paint raw wood bathroom door
402264 03/31/2017 447915 P 9671 M Secure projection screen backer board to wall
402265 03/31/2017 447917 P 9672 M Replace crushed downspout
402266 03/31/2017 447919 P 9672 M Repair emergency lighting at front door
402257 03/31/2017 447899 00 0 O No access was available to 1-113 and 1-117. Please provide access to these rooms during the report review meeting
402373 03/31/2017 448148 1 150 O Provide safety cable for large light on north end of bar
402432 03/31/2017 448278 1 211B O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
402438 03/31/2017 448290 1 003 MS Adjust fire door at top of stairs to latch properly
402403 03/31/2017 448216 1 138B MS Repair thumb latch to enable door to be unlocked from outside of room
402377 03/31/2017 448156 1 150 MS Adjust Cafeteria door corridor to latch properly. 2nd door leaf from west
402277 03/31/2017 447943 1 151B MS Provide current inspection tag for fire extinguisher
402375 03/31/2017 448152 1 154 MS Adjust corridor door to latch properly
402376 03/31/2017 448154 1 156 MS Adjust corridor door to latch properly
402280 03/31/2017 447949 1 198 MS Remove storage from electrical room
402443 03/31/2017 448301 1 214 MS Adjust corridor door to latch properly
402412 03/31/2017 448237 1 217 MS Provide current inspection tag for fire extinguisher
402374 03/31/2017 448150 1 002 OS Prohibit hold open device on fire door from corridor to stair 1-003
402439 03/31/2017 448292 1 004 OS Remove and prohibit storing carts in 2nd floor corridor
402407 03/31/2017 448227 1 005 OS Prohibit hold open device on fire door in corridor at bottom of stairs
402406 03/31/2017 448223 1 135 OS Prohibit hold open device on door
402278 03/31/2017 447945 1 151A OS Remove and prohibit storage on Stage ramp
402282 03/31/2017 447954 1 187 OS Keep flammable cabinet closed and latched
402418 03/31/2017 448249 1 215 OS Prohibit hold open device on corridor door
402442 03/31/2017 448299 1 223 OS Prohibit hold open device on corridor door
386736 12/13/2016 414397 1 131 M Make necessary repairs to fire sprinkler system as indicated on inspection report (system has been red tagged)
386786 12/13/2016 414510 2 101 M Remove rust from steel roof structure on P.E. Pavillion
254969 12/13/2016 130971 1 0000 N/A No violations observed
386775 02/29/2016 414481 1 0000 M Repair emergency light in covered walkway on exterior wall of Building 1 between portables and staff dining room
386751 02/29/2016 414432 1 001 M Repair smoke doors in corridor adjacent to 1-008 to close properly
386738 02/29/2016 414401 1 133A M Anchor toilet to floor in staff restroom
386745 02/29/2016 414420 1 141A M Replace rusted escutcheon on fire sprinkler head and remove rust from ceiling hatch and re-paint
386730 02/29/2016 414385 1 146 M Replace ceiling tile back into metal ceiling grid at northeast corner of room
386752 02/29/2016 414437 1 149 M Repair damaged laminate hanging from bottom of door below sink
386760 02/29/2016 414450 1 151 M Repair loose handrail on the left side stage steps
386734 02/29/2016 414393 1 158 M Determine cause of water damaged ceiling tiles and replace tiles
386731 02/29/2016 414387 1 158E M Repair or replace rusted exterior exit door frame in CCTV studio
386739 02/29/2016 414406 1 192 M Repair leaky air conditioning system to ensure it operates as designed (standing water on floor from condensation leaks)
386740 02/29/2016 414408 1 192 M Replace missing cover on floor drain
386765 02/29/2016 414464 1 197 M Repair or replace rusted louvers in mechanical room doors
386764 02/29/2016 414462 1 198 M Repair emergency lighting
386797 02/29/2016 414534 1 206A M Secure loose toilet seat
386792 02/29/2016 414524 1 209 M Determine cause of water damaged ceiling tiles above sink on north wall and replace tiles
386790 02/29/2016 414522 1 213A M Secure loose toilet seat
386789 02/29/2016 414520 1 213B M Secure loose toilet seat
386778 02/29/2016 414492 2 0000 M Provide cover for exposed electrical outlet on exterior wall of P.E. Pavillion adjacent to drinking fountains
386783 02/29/2016 414502 2 101 M Repair rusted steel support columns on P.E. Pavillion (columns are showing rust where they attach to concrete floor)
386779 02/29/2016 414498 2 102 M Determine cause of water damaged ceiling tiles and replace tiles
386773 02/29/2016 414477 P 9670 M Repair emergency lighting at rear door
386770 02/29/2016 414474 P 9671 M Repair emergency lighting at rear door
386767 02/29/2016 414466 P 9672 M Determine cause of water damaged ceiling tiles and replace tiles
386769 02/29/2016 414471 P 9672 M Repair emergency lighting at rear door
386735 02/29/2016 414395 1 127 O Remove flammable curtains below counters
386742 02/29/2016 414414 1 134 O Remove and prohibit flammable curtains and window coverings
386744 02/29/2016 414418 1 136 O Remove and prohibit hanging paper and decorations from ceiling (paper tree hanging from ceiling in northwest corner of room)
386741 02/29/2016 414410 1 137 O Remove and prohibit flammable curtains and window coverings
386743 02/29/2016 414416 1 139 O Remove and prohibit hanging decorations from ceiling (plastic vines and stuffed animal)
386747 02/29/2016 414424 1 141 O Remove flammable curtains from below counters
386762 02/29/2016 414455 1 151B O Eliminate brown light duty multi utlet extension cord plugged into surge protector
386799 02/29/2016 414538 1 203 O Remove and prohibit paper covering window in door
386793 02/29/2016 414528 1 208 O Remove and prohibit hanging paper and decorations from ceiling
386726 02/29/2016 414376 1 220 O Remove and prohibit hanging flammable burlap decorations
386727 02/29/2016 414378 1 222 O Remove flammable fabric curtains below counters
386729 02/29/2016 414383 1 227 O Remove and prohibit combustible (residential) furniture (overstuffed chair)
386728 02/29/2016 414380 1 230 O Remove and prohibit flammable curtains and window coverings
386737 02/29/2016 414399 1 002 MS Recharge fire extinguisher in corridor adjacent to 1-130
386746 02/29/2016 414422 1 139B MS Recharge fire extinguisher
386748 02/29/2016 414426 1 143B MS Recharge fire extinguisher in kitchen
386732 02/29/2016 414389 1 158D MS Recharge fire extinguisher
386763 02/29/2016 414460 1 198 MS Recharge fire extinguisher
386757 02/29/2016 414443 1 0000 OS Prohibit storage of backpacks in second floor corridor to maintain clear aisle to exit
386749 02/29/2016 414428 1 004 OS Prohibit storage of backpacks in exit corridor to maintain clear aisle to exit
386733 02/29/2016 414391 1 158D OS Remove storage blocking clear access to fire extinguisher
374103 12/02/2015 387054 1 190 M Repair air conditioning unit on wall and ensure it operates as designed
280350 12/02/2015 183007 1 186 CS Modify gate in fence enclosure to allow egress at all times and remove padlock from gate
374117 04/02/2015 387084 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable. Old certificate in 1-199
374118 04/02/2015 387086 00 9599 M Make manhole cover level with adjacent concrete at exit gates behind P-4
361675 04/02/2015 360072 00 9599 M Repair water leak at OS&Y valves at SW corner of Bldg.1
374104 04/02/2015 387056 1 113 M Determine cause of water damaged ceiling tiles and replace tiles
374120 04/02/2015 387090 1 131 M Provide current inspection tag for fire sprinkler system
374110 04/02/2015 387068 1 152C M Secure loose escutcheon on fire sprinkler head
374115 04/02/2015 387079 1 153C M Repair unlock button on bathroom door to work properly
374105 04/02/2015 387058 1 181 M Replace heavily rusted hot water heater
374113 04/02/2015 387075 1 187 M Repair exhaust fan in flammable storage room
374116 04/02/2015 387082 1 139B O Remove plastic bag from stove burners to eliminate fire hazard
374112 04/02/2015 387073 1 158E O Prohibit piggy backed surge protectors in CCTV studio. Plug each surge protector directly into a permanent electrical outlet
374106 04/02/2015 387060 1 208 O Remove and prohibit attaching paper to window blinds
374108 04/02/2015 387064 1 208 O Remove and prohibit paper covering electrical outlets under center of writing board
374107 04/02/2015 387062 1 209 O Remove and prohibit attaching paper to window blinds
374119 04/02/2015 387088 1 008 MS Recharge fire extinguisher at west end of corridor adjacent to exit doors
374102 04/02/2015 387052 1 118A MS Provide current inspection tag for fire extinguisher
374109 04/02/2015 387066 1 152J MS Provide current inspection tag for fire extinguisher
374114 04/02/2015 387077 1 151C OS Remove storage at top of stage ramp adjacent to 1-194
374111 04/02/2015 387071 1 160 OS Remove and prohibit use of space heater
361661 01/06/2015 360044 1 203A M Repair unlock button on bathroom door to work properly
361676 04/08/2014 360074 00 9599 M Provide chain and padlock for fire department water main OS&Y valves located at at SW corner of Bldg. 1
361673 04/08/2014 360068 00 9599 M Repair panic hardware on gate adjacent to P-1 to open and close properly - hard to open
361665 04/08/2014 360052 1 125 M Adjust water flow for drinking spout
361662 04/08/2014 360046 1 132A M Repair unlock button on bathroom door to work properly
361660 04/08/2014 360042 1 201 M Secure loose cover plate for light switch
343971 04/08/2014 321299 2 0000 M Repair damaged downspouts at west side of P.E. pavilion (X4)
361667 04/08/2014 360056 2 101 M Remove vegetation growing from pavilion gutters
361668 04/08/2014 360058 2 102 M Determine cause of water damaged ceiling tiles and replace tiles
361669 04/08/2014 360060 2 102 M Repair deteriorated and water damaged finish on wall under AC unit
361672 04/08/2014 360066 P 9669 M Determine cause of water damaged ceiling tiles and replace tiles
361670 04/08/2014 360062 P 9671 M Repair emergency lighting above front door
361671 04/08/2014 360064 P 9671 M Repair broken vinyl base along wall adjacent to front door
361666 04/08/2014 360054 1 185 O Eliminate and prohibit use of spliced extension cord. Also plug microwave directly into wall outlet
361656 04/08/2014 360034 1 219 O Remove and prohibit paper on ceiling tiles
361657 04/08/2014 360036 1 229 O Prohibit plugging surge protector into surge protector at teacher desk - plug each surge protector directly into wall outlet
361663 04/08/2014 360048 1 154 MS Remove dog leg hold open device from corridor door
361664 04/08/2014 360050 1 148 OS Relocate music room risers to maintain 3 ft clear path to corridor doors
361674 04/08/2014 360070 1 151 OS Relocate storage on south side of stage to maintain clear path to exit ramp 1-151C
361659 04/08/2014 360040 1 208 OS Remove storage cart from bathroom
361658 04/08/2014 360038 1 218 OS Remove and prohibit use of toaster in classroom
313248 01/17/2014 254052 1 151 C Provide records that stage rigging has been inspected and conforms to required safety standards
343960 02/25/2013 321273 1 003 M Repair loose handrail at bottom landing of stairway
343957 02/25/2013 321267 1 117 M Determine cause of water damaged ceiling tiles and replace tiles
343958 02/25/2013 321269 1 170 M Provide current inspection tag for elevator
343970 02/25/2013 321295 1 199 M Repair emergency lighting
343959 02/25/2013 321271 1 0000 O Remove and prohibit flammable curtains and paper hanging from windows in classrooms
343966 02/25/2013 321287 1 149 MS Provide current inspection tag for fire extinguisher (tag has been torn off)
343968 02/25/2013 321293 P 9672 MS Recharge fire extinguisher
313253 02/25/2013 254062 1 199 CS Provide 90 minute fire rated door to 1-198
326909 11/15/2012 284375 1 131 M Replace missing fire sprinkler heads in spare heads box
313249 11/15/2012 254054 1 151 M Provide dated flame resistance label on stage curtain
313260 11/15/2012 254077 1 158E M Provide dated flame resistance label on CCTV curtain
280352 11/15/2012 183011 1 0000 C Provide suitable location for charging batteries
313259 11/15/2012 254075 1 101 FS Provide certification that fire alarm system has been tested and is fully operational. Strobe lights are not synchronized. Repair system so that strobes are synchronized
326890 03/08/2012 284336 00 0000 M Provide hurricane anchorage for plastic storage shed in fenced play area/courtyard south of portables
326913 03/08/2012 284383 1 140 M Repair or replace damaged toilet seat
326902 03/08/2012 284360 1 158G M Replace ceiling tile with hole in it
326903 03/08/2012 284362 1 160 M Pad and mark corners of shelf unit which are lower than 6'8"
326914 03/08/2012 284385 1 192 M Pad and mark corners of unit SF 1-1 which are lower than 6'8"
326895 03/08/2012 284346 1 196 M Repair door hardware, door is difficult to unlock
326900 03/08/2012 284356 1 197 M Repair AHU-7, water is leaking from unit
326893 03/08/2012 284342 1 199 M Provide certification that all student occupied spaces have emergency lights and all are operable, certificate is expired
326907 03/08/2012 284371 1 229B M Anchor toilet to floor
326894 03/08/2012 284344 2 103 M Adjust door closer to control speed of closing door
326896 03/08/2012 284348 P 9670 M Adjust door closer to control speed of closing door
326897 03/08/2012 284350 P 9671 M Adjust door closer to control speed of closing door
326898 03/08/2012 284352 P 9672 M Repair emergency lighting
326899 03/08/2012 284354 P 9672 M Secure cover for exhaust fan in bathroom
326911 03/08/2012 284379 1 127 O Provide minimum one foot blank wall space on lock side of door
326912 03/08/2012 284381 1 127 O Remove and prohibit air freshener
326905 03/08/2012 284366 1 219 O Remove and prohibit air freshener
326904 03/08/2012 284364 1 219A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
326901 03/08/2012 284358 1 158E C Provide records that CCTV rigging has been inspected and conforms to required safety standards
326892 03/08/2012 284340 1 008 MS Provide current inspection tag for fire extinguisher adjacent to 1-150 and west exterior doors
326910 03/08/2012 284377 1 131 MS Provide current inspection tag for fire sprinkler system
326891 03/08/2012 284338 1 191 MS Replace overcharged fire extinguisher
326908 03/08/2012 284373 1 218A OS Prohibit tables and chairs in vestibule to maintain clear aisle to exit
326906 03/08/2012 284368 1 221 OS Remove and prohibit use of candles
313256 10/05/2011 254069 00 0000 C Provide tactile warning at all curb cut ramps to south and east parking lots
313232 02/17/2011 254015 1 0000 M Repair light in exit sign in 2nd floor corridor adjacent to 1-223
313257 02/17/2011 254071 1 003 M Secure loose lower run inside handrail for stairs
313261 02/17/2011 254079 1 126 M Replace GFCI outlet
313254 02/17/2011 254064 1 152 M Secure loose protective cage around fire sprinkler head in walk-in freezer
313247 02/17/2011 254049 1 153 M Disable latch hold down device on door to exterior corridor
313240 02/17/2011 254035 1 157 M Repair door to open and close properly. Door rubs on frame
313235 02/17/2011 254025 1 193 M Provide missing KO seal in fire alarm junction box on east wall
313251 02/17/2011 254058 1 195 M Repair leaking air handler, AHU-6
313241 02/17/2011 254037 1 214B M Repair door to open and close properly
313237 02/17/2011 254029 1 217B M Repair thumb latch on bathroom door to enable door to be unlocked from outside of room
313239 02/17/2011 254033 1 221B M Replace missing screw in light switch plate
313255 02/17/2011 254066 1 229B M Grout open corners in bathroom
313258 02/17/2011 254073 1 290 M Seal east side of air handler to eliminate air leaks
313039 02/17/2011 253590 P 9669 M Repair emergency lighting
313243 02/17/2011 254041 1 0000 O Remove storage to provide minimum one foot blank wall space on lock side of door for all classrooms
313246 02/17/2011 254047 1 152 O Provide clear access to electrical panels
313244 02/17/2011 254043 1 185 O Eliminate extension cord or replace with minimum 15A cord
313245 02/17/2011 254045 1 185 O Prohibit plugging appliances into extension cord - plug directly into permanent electrical outlet
313242 02/17/2011 254039 1 201 O Provide primary and secondary evacuation routes on evacuation map
313238 02/17/2011 254031 1 217B O Keep shower drain filled with water. Once every 2 months pour a guart of water directly down the drain
313233 02/17/2011 254018 00 0000 C Provide fencing around fire main at west end of south parking lot
313069 02/17/2011 253659 1 0000 C Replace glazing in doors under covered walkway between building and portables with fire rated glazing
313252 02/17/2011 254060 1 002 MS Adjust fire door in corridor adjacent to 1-123 to latch properly
313236 02/17/2011 254027 1 210 MS Recharge fire extinguisher
313234 02/17/2011 254023 1 002 OS Remove rolled up carpet stored in corridor vestibule to west adjacent to stair 1-003
313250 02/17/2011 254056 1 151 OS Maintain clear aisle to both exits from stage
313041 02/17/2011 253598 P 9670 OS Maintain 3' wide aisle to exit
288327 09/24/2010 200070 00 0000 C Provide automatic fire sprinkler coverage for portables and covered walkway between portables and building
219084 09/24/2010 64946 1 290B C Make smoke stop barrier continuous from floor to roof deck
306990 04/09/2010 240136 1 113 M Determine cause of water damaged ceiling tiles and replace tiles
306991 04/09/2010 240138 1 117 M Determine cause of water damaged ceiling tiles and replace tiles
306995 04/09/2010 240146 1 131 M Determine cause of water damaged ceiling tiles and replace tiles
306996 04/09/2010 240148 1 131 M Repair leak in fire sprinkler piping above ceiling
307004 04/09/2010 240166 1 201 M Determine cause of water damaged ceiling tiles and replace tiles
307005 04/09/2010 240168 1 201 M Repair leaky sprinkler piping above ceiling
307006 04/09/2010 240170 1 202 M Secure pencil sharpener hanging from wall
288340 04/09/2010 200099 2 0000 M Clean, prime and paint steel columns for pavillion at floor level
288341 04/09/2010 200101 2 104 M Repair exhaust fan in bathroom
288336 04/09/2010 200090 P 9669 M Provide impervious wall finish for minimum six foot height in bathroom
307000 04/09/2010 240157 P 9669 M Repair emergency lighting at rear door
288337 04/09/2010 200093 P 9670 M Provide impervious wall finish for minimum six foot height in bathroom
288338 04/09/2010 200095 P 9671 M Provide impervious wall finish for minimum six foot height in bathroom
288339 04/09/2010 200097 P 9672 M Provide impervious wall finish for minimum six foot height in bathroom
306993 04/09/2010 240142 1 135 O Remove and prohibit combustible beanbag chairs
306994 04/09/2010 240144 1 137 O Remove and prohibit combustible beanbag chairs
307007 04/09/2010 240172 1 206 O Remove and prohibit flammable window coverings
307003 04/09/2010 240164 1 207 O Remove and prohibit flammable window coverings
307001 04/09/2010 240159 1 218 O Remove and prohibit flammable decorations hanging from ceiling and on windows
307002 04/09/2010 240162 1 219 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
306998 04/09/2010 240152 P 9672 O Maintain classroom in an orderly manner by removing excessive storage
306999 04/09/2010 240155 P 9672 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
306992 04/09/2010 240140 00 0000 C Provide exterior signage indicating property address
253795 04/09/2010 128435 00 0000 CS Immediately provide fire rated doors for dining room and staff dining as required by plans approved by Building Department or prohibit use of portables (rated doors in openings do not have stamp indicating tempered glass)
288328 04/09/2010 200074 1 117 CS Provide auto closer on corridor door
306997 04/09/2010 240150 1 152 CS Provide auto closers on fire doors held open by magnetic hold open devices on serving line doors and dishwashing room door
280369 01/11/2010 183046 1 002 C Provide automatic fire sprinkler coverage at exit at end of corridor
280368 01/11/2010 183044 1 004 C Provide automatic fire sprinkler coverage at exit at end of corridor
288330 03/30/2009 200078 1 0000 M Repair exit sign in corridor adjacent to 1-205 that is hanging by its wires
288333 03/30/2009 200084 1 002 M Provide directional arrows for exit sign in corridor adjacent to 1-126. (Directional arrows are knock-outs on face plate of sign)
288335 03/30/2009 200088 1 008 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to 1-151C
288331 03/30/2009 200080 1 136A M Repair thumb latch to enable door to be unlocked from outside of room
219301 03/30/2009 70652 1 158G M Relocate sprinkler head to be minimum 4 inches away from wall (requirement waived by Mark Lodge)
288325 03/30/2009 200066 1 193 M Remove sign indicating Fire Extinguisher Inside
288326 03/30/2009 200068 1 204 M Remove string attached to fire sprinkler head
280332 03/30/2009 182971 1 116 C Provide auto closer on corridor door
280529 03/30/2009 183397 1 230 C Provide emergency lighting in student occupied space
280530 03/30/2009 183399 1 231 C Provide emergency lighting in student occupied space
288324 03/30/2009 200064 1 154 MS Remove hold open device from corridor door
288332 03/30/2009 200082 1 210 MS Recharge fire extinguisher
288334 03/30/2009 200086 1 118A OS Provide clear access to fire extinguisher
288329 03/30/2009 200076 1 209 OS Prohibit running electrical cord across floor
280343 10/16/2008 182993 1 151 M Provide dated flame resistance label on side curtain panels on stage or remove panels
280355 10/16/2008 183017 1 199 M Provide certification that all student occupied spaces have emergency lights and all are operable
280331 10/16/2008 182967 P 9669 M Raise exterior electrical boxes so bottom of boxes are at least 8" above grade (not required per Terry Summerell)
280328 10/16/2008 182961 P 9670 M Raise exterior electrical boxes so bottom of boxes are at least 8" above grade (not required per Terry Summerell)
280329 10/16/2008 182963 P 9671 M Raise exterior electrical boxes so bottom of boxes are at least 8" above grade (not required per Terry Summerell)
280330 10/16/2008 182965 P 9672 M Raise exterior electrical boxes so bottom of boxes are at least 8" above grade (not required per Terry Summerell)
218908 10/16/2008 70644 P 9699 M Paint portable number on exterior walls to be visible to fire rescue
219390 10/16/2008 70627 P 9699 M Adjust south door to latch properly
280333 10/16/2008 182973 1 148 C Provide illuminated exit signs at both exit doors or reduce maximum occupancy from 50 to 49
219682 10/16/2008 64948 P 9699 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219391 10/16/2008 70600 P 9699 OS Relocate desk blocking clear access to south door
280386 10/16/2008 183082 1 101 FS Provide certification that fire alarm system has been tested and is fully operational - panel and record log dated 7/06
280363 04/25/2008 183034 1 001 M Replace cracked wire glass in fire door at bottom of center stair
280364 04/25/2008 183036 1 001 M Determine cause of water damaged ceiling tiles and replace tiles in corridor across from 1-192A
280367 04/25/2008 183042 1 142 M Repair water damaged wall finish
280341 04/25/2008 182989 1 150 M Provide signs at doors leading into corridor indicating "No Exit"
280349 04/25/2008 183005 1 150C M Replace missing escutcheon on fire sprinkler head
280354 04/25/2008 183015 1 152B M Seal gap between fire sprinkler escutcheon and ceiling
280372 04/25/2008 183053 1 170 M Provide current inspection tag for elevator - exp. date 8/1/07
252095 04/25/2008 124574 1 206 M Replace broken window glass
280373 04/25/2008 183056 1 290 M Repair leaking air handler unit
252061 04/25/2008 124499 P 0000 M Seal seams in flooring in all bathrooms in portables
280362 04/25/2008 183031 P 9669 M Adjust front door to latch properly
280385 04/25/2008 183080 1 136 O Remove and prohibit air freshener
280336 04/25/2008 182977 1 148 O Prohibit covering window in exterior door
280342 04/25/2008 182991 1 151 O Remove torn, flammable light blue curtains from back of stage
280339 04/25/2008 182985 1 156 O Remove and prohibit decorations hanging from fire sprinkler head
280338 04/25/2008 182983 1 158 O Remove and prohibit combustible (residential) chair and loveseat
280337 04/25/2008 182980 1 160 O Eliminate extension cord or replace with minimum 15A cord and prohibit 3 prong cord adaptor at microwave oven - plug microwave oven directly into electrical outlet
280379 04/25/2008 183068 1 205 O Eliminate extension cord or replace with minimum 15A cord
280381 04/25/2008 183071 1 205 O Remove and prohibit air freshener
280383 04/25/2008 183076 1 209 O Remove and prohibit scented oil
280371 04/25/2008 183050 1 224 O Prohibit plugging surge protector into extension cord
280377 04/25/2008 183063 1 230 O Post sign indicating evacuation routes
280376 04/25/2008 183061 1 231 O Post sign indicating evacuation routes
280361 04/25/2008 183029 P 9669 O Relocate bookcase and storage blocking clear access to electrical panel
280358 04/25/2008 183023 P 9671 O Remove and prohibit flammable curtains covering windows in doors
280356 04/25/2008 183019 P 9672 O Remove and prohibit flammable curtains covering windows in doors
280528 04/25/2008 183394 1 190 C Provide automatic fire sprinkler coverage for communications room - walls are not 2 hour fire rated
280384 04/25/2008 183078 1 138B MS Provide current inspection tag for fire extinguisher
280365 04/25/2008 183038 1 139B MS Provide current inspection tag for fire extinguisher
280366 04/25/2008 183040 1 143B MS Provide current inspection tag for fire extinguisher
280345 04/25/2008 182997 1 151B MS Adjust fire doors to close and latch properly
280340 04/25/2008 182987 1 154 MS Remove dog leg hold open device from corridor door
280353 04/25/2008 183013 1 187 MS Provide current inspection tag for fire extinguisher
280334 04/25/2008 182975 1 148 OS Relocate piano blocking clear path to exterior door
280344 04/25/2008 182995 1 151A OS Remove and prohibit trash can on ramp outside stage exit door
280346 04/25/2008 182999 1 151B OS Remove storage blocking clear access to operable leaf of double doors
280347 04/25/2008 183001 1 151B OS Prohibit keeping fixed leaf of double doors in open position
280348 04/25/2008 183003 1 151B OS Remove storage blocking clear access to fire extinguisher
280351 04/25/2008 183009 1 186 OS Prohibit charging batteries in room (per AP, batteries are charged outside)
280378 04/25/2008 183066 1 205 OS Prohibit wedging open corridor door
280382 04/25/2008 183073 1 209 OS Relocate desk blocking clear path to corridor door
280374 04/25/2008 183058 1 212 OS Relocate bookcase blocking clear path to corridor door
280370 04/25/2008 183048 1 224 OS Relocate storage and desk blocking clear access to corridor door
280360 04/25/2008 183027 P 9670 OS Remove storage blocking clear path to rear door
280359 04/25/2008 183025 P 9671 OS Relocate bookcase blocking clear path to rear door
280357 04/25/2008 183021 P 9672 OS Relocate backpack cubby, bookcase and ladder blocking clear path to rear door
253500 01/11/2007 127764 1 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
253524 01/11/2007 127814 1 0000 M Secure illuminated exit sign hanging from wire adjacent to 1-201
253779 01/11/2007 128403 1 136 M Adjust exterior door to latch properly
253516 01/11/2007 127798 1 138 M Adjust exterior door to latch properly
253504 01/11/2007 127772 1 138B M Repair exhaust fan in bathroom
253507 01/11/2007 127778 1 150A M Replace missing escutcheon on fire sprinkler head
253510 01/11/2007 127784 1 171 M Provide cover on exposed electrical junction box
252073 01/11/2007 124527 1 221 M Replace corroded fire sprinkler head
253749 01/11/2007 128330 P 9671 M Replace broken wire glass pane in door
253502 01/11/2007 127768 1 134 O Provide certification that blue carpet meets flame spread requirement or remove carpet
253754 01/11/2007 128341 1 151 O Remove and prohibit flammable paper and plastic sheets covering curtains
253517 01/11/2007 127800 1 151B O Reloacte storage to keep area within 18? of automatic fire sprinkler heads clear and unobstructed
253751 01/11/2007 128335 1 152F O Eliminate 13A extension cord for adding machine or replace with minimum 15A cord
253508 01/11/2007 127780 1 156 O Prohibit plugging microwave into an extension cord, plug microwave directly into wall outlet
253509 01/11/2007 127782 1 158 O Prohibit plugging surge protector into an extension cord, plug surge protector directly into wall outlet adjacent to 1-158D
253756 01/11/2007 128347 1 158 O Prohibit plugging one surge protector into another at (6) computer stations adjacent to entrance door
253511 01/11/2007 127786 1 182 O Prohibit plugging microwave into an extension cord, plug microwave directly into wall outlet
253522 01/11/2007 127810 1 202 O Remove and prohibit combustible beanbag chairs
253732 01/11/2007 128286 1 206 O Prohibit plugging microwave into extension cord, plug microwave directly into wall outlet
253735 01/11/2007 128300 P 9671 O Prohibit plugging microwave into extension cord, plug microwave directly into wall outlet
253739 01/11/2007 128311 P 9671 O Relocate TV blocking clear access to electrical panel
253742 01/11/2007 128315 P 9671 O Prohibit use of extension cord with multi-outlet end or replace with a surge protector under computer station
253514 01/11/2007 127793 P 9671 O Remove and prohibit use of toaster oven
253776 01/11/2007 128394 1 148 C Install maximum occupancy signage (50 occupants)
253778 01/11/2007 128399 1 001 MS Adjust smoke doors in corridor adjacent to 1-192A to latch properly
253501 01/11/2007 127766 1 118A MS Provide current inspection tag for fire extinguisher
253503 01/11/2007 127770 1 138A MS Provide current inspection tag for fire extinguisher
253505 01/11/2007 127774 1 139B MS Provide current inspection tag for fire extinguisher
253506 01/11/2007 127776 1 143B MS Provide current inspection tag for fire extinguisher
253512 01/11/2007 127789 1 186 MS Remove dog leg hold open device from fire door
253513 01/11/2007 127791 1 192A MS Provide current inspection tag for fire extinguisher
253755 01/11/2007 128345 1 151 OS Relocate table blocking clear access to stage ramp
253759 01/11/2007 128355 1 158 OS Relocate bookstand blocking view of fire extinguisher adjacent to exterior door
253518 01/11/2007 127802 1 186 OS Prohibit charging batteries for floor cleaning machines in room
253519 01/11/2007 127804 1 206 OS Prohibit use of wedge to hold fire door in open position
253521 01/11/2007 127808 1 222 OS Prohibit use of wedge to hold fire door in open position
253520 01/11/2007 127806 1 227 OS Prohibit use of wedge to hold fire door in open position
253523 01/11/2007 127812 1 229 OS Rearrange furniture to provide a minimum 3 ft clear aisle to corridor door
252054 08/31/2006 124490 1 152 M Repair freezer door to close properly
252027 05/02/2006 124426 1 005 M Adjust or replace smoke doors at bottom of stairway so that clearance between doors does not exceed 1/8 inch
252043 05/02/2006 124468 1 126A M Repair leaky stool in bathroom
252042 05/02/2006 124463 1 138 M Adjust exterior exit door to latch properly
252053 05/02/2006 124487 1 198 M Install cover on electric panel ILA Sect 2
252065 05/02/2006 124511 1 0000 O Remove and prohibit excessive flammable decorations on ceiling in second floor corridor
252048 05/02/2006 124472 1 127 O Remove and prohibit combustible residential foam couch
252038 05/02/2006 124454 1 138 O Remove and prohibit excessive flammable decorations on walls and ceilings
252019 05/02/2006 124415 1 139 O Remove and prohibit excessive flammable decorations on walls and ceiling
252036 05/02/2006 124449 1 140 O Remove and prohibit excessive flammable decorations on walls and ceiling
252016 05/02/2006 124405 1 141 O Remove and prohibit excessive flammable decorations on walls and ceiling
252018 05/02/2006 124411 1 143 O Remove and prohibit excessive flammable decorations on walls and ceiling
252023 05/02/2006 124421 1 145 O Remove and prohibit excessive flammable decorations on walls and ceiling
219052 05/02/2006 70633 1 158E O Prohibit running electrical cords across path to exterior door
252096 05/02/2006 124576 1 204 O Remove and prohibit excessive flammable wall decorations
252093 05/02/2006 124569 1 214 O Remove and prohibit excessive flammable wall decorations
252087 05/02/2006 124557 1 216 O Eliminate excessive storage in classroom
252090 05/02/2006 124564 1 216 O Eliminate multiple outlet extension cord powering tape recorder
252085 05/02/2006 124550 1 218 O Eliminate multiple outlet extension cord powering media cart in center of room
252066 05/02/2006 124513 1 219 O Eliminate three-way electrical adaptors (X2), one behind refrigerator and one by aquarium
218992 05/02/2006 70636 1 226 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
252051 05/02/2006 124483 1 001 MS Adjust smoke stop doors adjacent to 1-192A to latch properly
252008 05/02/2006 124392 1 101 MS Adjust smoke stop doors adjacent to 1-117 to latch properly
252010 05/02/2006 124396 1 139B MS Provide current inspection tag for fire extinguisher
252052 05/02/2006 124485 1 151B MS Provide current inspection tag for fire extinguisher
252063 05/02/2006 124507 1 195 MS Provide current inspection tag for fire extinguisher
252062 05/02/2006 124505 1 196 MS Provide current inspection tag for fire extinguisher
252094 05/02/2006 124572 1 210 MS Provide current inspection tag for fire extinguisher
252064 05/02/2006 124509 2 102 MS Provide current inspection tag for fire extinguisher
252081 05/02/2006 124542 1 0000 OS Prohibit hold open devices (wedges) on classroom corridor doors
252034 05/02/2006 124436 1 004 OS Remove desk in corridor @ 1-140 to maintain clear exit from room
252040 05/02/2006 124457 1 138A OS Eliminate storage on stove top
252013 05/02/2006 124402 1 139B OS Eliminate storage on stove top
252021 05/02/2006 124417 1 143B OS Eliminate storage on stove top
252076 05/02/2006 124532 1 229 OS Maintain clear aisle to corridor door
252057 05/02/2006 124493 P 9671 OS Maintain clear aisle to rear exit door
219299 03/15/2006 70592 1 107 M Determine cause of water damaged ceiling tiles and replace tiles
219373 03/15/2006 64964 1 170 M Provide certification that elevator has current inspection tag
218907 03/15/2006 70638 1 003 C Provide sign adjacent to 1-131 indicating "Fire Sprinkler Riser Inside"
219298 03/15/2006 70609 00 0000 CS Immediately provide fire rated construction and additional gates as required by plans approved by Building Department or prohibit use of portables
219333 03/15/2006 64982 00 0000 CS Provide spare fire sprinkler heads and a sprinkler head wrench adjacent to fire alarm panel @ front office
219215 10/25/2004 64938 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
218906 10/25/2004 70591 1 0000 M Replace missing ceiling tile in 2nd floor corridor adjacent to 1-229
218932 10/25/2004 70650 1 122 M Secure loose escutcheon on fire sprinkler head
218933 10/25/2004 70631 1 134A M Repair damaged button on outside of bathroom door lever to enable door to be unlocked from the outside
219388 10/25/2004 70635 1 150 M Repair out of order drinking fountain adjacent to gang bathrooms
219303 10/25/2004 64961 1 181 M Provide current inspection tag for hot water heater
218993 10/25/2004 64962 1 184 M Provide current inspection tag for hot water heater
219374 10/25/2004 70593 1 194 M Replace missing ceiling tile
219645 10/25/2004 70632 1 203A M Repair damaged button on outside of bathroom door lever to enable door to be unlocked from the outside
219024 10/25/2004 70651 1 211B M Replace missing escutcheon on fire sprinkler head
219025 10/25/2004 70594 1 220 M Replace missing ceiling tile
219302 10/25/2004 70645 P 9670 M Paint portable number on exterior walls to be visible to fire rescue
219389 10/25/2004 70628 P 9670 M Adjust south door to latch properly
219026 10/25/2004 70629 P 9671 M Adjust south door to latch properly
218960 10/25/2004 70603 P 9671 M Repair emergency lighting
218961 10/25/2004 70646 P 9671 M Paint portable number on exterior walls to be visible to fire rescue
218937 10/25/2004 70647 P 9672 M Paint portable number on exterior walls to be visible to fire rescue
219054 10/25/2004 70630 P 9672 M Adjust south door to latch properly
219641 10/25/2004 70604 1 104 O Prohibit plugging one surge protector into another
219642 10/25/2004 70648 1 113 O Relocate storage to keep area within 18? of automatic fire sprinkler heads clear and unobstructed
219216 10/25/2004 70623 1 124 O Remove and prohibit combustible beanbag chair
219022 10/25/2004 70624 1 127 O Remove and prohibit combustible beanbag chairs
219615 10/25/2004 70649 1 151B O Relocate storage to keep area within 18" of automatic fire sprinkler heads clear and unobstructed
219372 10/25/2004 70605 1 158 O Prohibit plugging one surge protector into another
219616 10/25/2004 70617 1 158E O Remove and prohibit display of flammable large cardboard/crape paper circle
218935 10/25/2004 70606 1 158E O Prohibit use of multiple outlets extension cord
219265 10/25/2004 70625 1 158F O Remove mirror or provide mirror made of tempered glass, safety glass, or stainless steel
219680 10/25/2004 70618 1 208 O Remove and prohibit display of flammable large lighthouse made of cardboard
219335 10/25/2004 70607 1 227 O Prohibit use of multi outlets adaptor for aquarium
219336 10/25/2004 70639 1 228 O Post sign indicating evacuation routes
219376 10/25/2004 70602 P 9671 O Relocate computer desk to provide clear access to electrical panel
219375 10/25/2004 70637 1 228 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
219337 10/25/2004 64949 P 9670 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219681 10/25/2004 70621 P 9671 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
218936 10/25/2004 70622 P 9672 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219679 10/25/2004 70613 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus
219614 10/25/2004 70595 1 0000 MS Adjust fire doors at top of stairwell adjacent to 1-290 to latch properly
219643 10/25/2004 70614 1 138B MS Relocate fire extinguisher from 1-140 to be inside kitchen area 1-138B
219644 10/25/2004 70615 1 139B MS Relocate fire extinguisher from 1-139 to be inside kitchen area 1-139B
219300 10/25/2004 70616 1 143B MS Relocate fire extinguisher from 1-145 to be inside kitchen area 1-143B
219377 10/25/2004 64963 1 152 MS Provide current inspection for fire suppression system
219371 10/25/2004 70626 1 0000 OS Prohibit use of wedge to hold fire doors open thru out building
219021 10/25/2004 70596 1 002 OS Remove table and chairs from corridor adjacent to 1-129
219171 10/25/2004 70597 1 003 OS Remove chairs and trash cans from stairwell
219172 10/25/2004 70598 1 136 OS Rearrange furniture to maintain a minimum 3 ft clear path to corridor door
218934 10/25/2004 64960 1 150F OS Prohibit recharging batteries in room
219023 10/25/2004 70612 1 151 OS Relocate storage to provide clear access to fire extinguisher on stage
218991 10/25/2004 70599 1 151C OS Remove storage along ramp to stage
219053 10/25/2004 70634 1 186 OS Prohibit recharging batteries for floor cleaning machines in room
219646 10/25/2004 70608 1 216 OS Prohibit electrical cord from running on floor across path to bathroom vestibule
218962 10/25/2004 64966 00 0000 CS Provide "Knox" padlock on gate to allow fire department access
219334 10/25/2004 70601 1 138 CS Rearrange furniture to maintain a minimum 3 ft clear path to corridor door