Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
419566 04/04/2018 485202 00 0000 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report dated 3-3-17
419569 04/04/2018 485209 1 0000 M Determine cause of water damaged ceiling tiles in first floor corridor adjacent to 1-190 and replace tiles
419567 04/04/2018 485205 1 101 M Make repairs to fire alarm system (Fire Alarm Panel was indicating trouble in the Kitchen Ansul System at time of inspection)
419572 04/04/2018 485217 1 123 M Determine cause of water damaged ceiling tile at entrance door and replace tiles
419574 04/04/2018 485221 1 124 M Repair deteriorated wall finish around door frame at exterior exit door
419573 04/04/2018 485219 1 125 M Determine cause of water damaged ceiling tiles and replace tiles
419575 04/04/2018 485223 1 128 M Secure loose faucet to sink
419579 04/04/2018 485231 1 139 M Secure loose faucet to sink
419578 04/04/2018 485229 1 140 M Determine cause of water damaged ceiling tiles next to projector screen and replace tiles
419568 04/04/2018 485207 1 147 M Determine cause of water damaged ceiling tiles at southeast corner of room and replace tiles
419592 04/04/2018 485258 1 148B M Determine cause of water damaged ceiling tiles and replace tiles
419600 04/04/2018 485276 1 150 M Determine cause of water damaged ceiling tiles in cafeteria above doorway into 1-186 and at east wall and replace tiles
419598 04/04/2018 485272 1 150 M Secure loose handrail at bottom of stage ramp on right side of stage
419599 04/04/2018 485274 1 150C M Replace missing escutcheon on fire sprinkler head in entrance to boy's restroom
419601 04/04/2018 485278 1 151 M Provide kitchen hood cleaning (date indicated for last hood cleaning was 01-10-17)
419594 04/04/2018 485262 1 153A M Provide current flame resistance certification for stage curtain (old date 4-6-2012 is expired)
419597 04/04/2018 485269 1 158 M Repair loose vinyl base along wall at southwest exit doors in media center
419596 04/04/2018 485267 1 158C M Provide current dated flame resistance certificate for CCTV curtain (old date is 6-30-11)
419602 04/04/2018 485280 1 198 M Provide current emergency lighting and generator certification (date on current certification is 5-27-16)
419590 04/04/2018 485254 1 205 M Secure loose faucet to sink
419586 04/04/2018 485246 1 212 M Replace missing activation button on drinking fountain
419587 04/04/2018 485248 1 212 M Determine cause of water damaged ceiling tiles next to windows and replace tiles
419584 04/04/2018 485242 1 215B M Repair out of service toilet
419583 04/04/2018 485240 1 217A M Re-caulk around sink in bathroom to provide impervious wall finish
419577 04/04/2018 485227 2 103 M Secure loose faucet to sink in boy's restroom
419608 04/04/2018 485296 3 0000 M Repair emergency lighting on exterior wall at entrance door to 3-104
419607 04/04/2018 485294 3 101A M Repair emergency lighting on wall next to bathroom
419605 04/04/2018 485290 4 101A M Repair emergency lighting on wall next to bathroom
419606 04/04/2018 485292 4 190 M Repair emergency lighting in mechanical room
419603 04/04/2018 485283 5 0000 M Secure drinking fountains (X2) to sinks at rear of building, one adjacent to 5-103 and another adjacent to 5-102
419604 04/04/2018 485285 5 101B M Repair leaky flush valve on toilet
419570 04/04/2018 485211 1 119 O Keep area within 18 inches of fire sprinkler head clear and unobstructed on top of storage rack
419593 04/04/2018 485260 1 148 O Eliminate white, light duty, multi-outlet extension cord at computer table
419588 04/04/2018 485250 1 210 O Remove and prohibit hanging decorations from ceiling
419589 04/04/2018 485252 1 210 O Relocate table next to door blocking clear space for exiting through doorway
419581 04/04/2018 485235 1 219 O Remove and prohibit air freshener
419580 04/04/2018 485233 1 224 O Eliminate white, light duty, multi-outlet extension cord (use surge protector instead)
419576 04/04/2018 485225 2 0000 C Repair rusted column on PE pavilion (column is rusted through next to concrete floor)
419582 04/04/2018 485237 1 0000 MS Adjust smoke door in second floor corridor adjacent to 1-217 to close properly
419591 04/04/2018 485256 1 004 MS Repair loose handle on smoke doors at bottom landing of stairway
419571 04/04/2018 485213 1 192 OS Remove storage from mechanical room
419595 04/04/2018 485265 1 195 OS Remove storage from electrical room
419585 04/04/2018 485244 1 290 OS Remove storage (boxes, rug) from mechanical room
262828 04/04/2018 145246 1 0000 N/A No violations observed
262829 04/04/2018 145247 2 0000 N/A No violations observed
296494 04/04/2018 217399 3 0000 N/A No violations observed
296495 04/04/2018 217401 4 0000 N/A No violations observed
296496 04/04/2018 217403 5 0000 N/A No violations observed
403365 01/18/2018 450278 00 0000 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report dated 2.11.16
403366 01/30/2017 450280 00 9599 M Label two fire department connections as to which buildings they serve - east of Bldgs. 3 and 4
403367 01/30/2017 450282 00 9599 M Label fire department connections as to which building it serves - west of Bldg. 5
403364 01/30/2017 450276 00 9599 M Replace broken padlock and keep OS&Y water main at bus loop chained and locked
403331 01/30/2017 450208 1 0000 M Determine cause of water damaged ceiling tiles and replace tiles at corridor doors adjacent to 1-105
403353 01/30/2017 450253 1 006 M Adjust exterior doors to latch properly at bottom of stairwell
403357 01/30/2017 450261 1 125 M Secure loose faucet to sink
403355 01/30/2017 450257 1 126 M Secure loose vinyl base along wall adjacent to exterior door
403361 01/30/2017 450270 1 143A M Patch hole in wall behind bathroom door and replace missing door stop
403349 01/30/2017 450245 1 206B M Patch hole in ceiling adjacent to sprinkler head
403348 01/30/2017 450243 1 206C M Patch hole in wall behind bathroom door and replace missing door stop
403351 01/30/2017 450249 2 103 M Repair exhaust fan in bathroom
403352 01/30/2017 450251 2 104 M Repair exhaust fan in bathroom
403330 01/30/2017 450205 1 101 O Provide a currently dated flame resistance certificate for curtains in front office - NA curtains removed
403333 01/30/2017 450212 1 119 O Relocate 2 boxes to keep area within 18 inches of fire sprinkler head clear and unobstructed
403356 01/30/2017 450259 1 127 O Remove and prohibit paper on window blinds
403362 01/30/2017 450272 1 143 O Remove and prohibit excessive flammable vinyl decorations at SE corner
403363 01/30/2017 450274 1 145 O Prohibit plugging surge protector into surge protector for radios - plug each surge protector directly into wall outlet
403343 01/30/2017 450233 1 148 O Remove and prohibit paper on window blinds
403344 01/30/2017 450235 1 149 O Eliminate white extension cord with multiple outlet end for speaker adjacent to 1-149A or replace with a surge protector
403341 01/30/2017 450229 1 205 O Remove and prohibit paper on window blinds
403342 01/30/2017 450231 1 207 O Remove and prohibit paper on window blinds
403350 01/30/2017 450247 1 207 O Remove and prohibit excessive flammable black vinyl sheathing on 2 bulletin boards in classroom
403346 01/30/2017 450239 1 208 O Remove and prohibit paper on window blinds
403347 01/30/2017 450241 1 208 O Remove paper covering electrical outlets under writing board
403340 01/30/2017 450227 1 219 O Remove and prohibit paper on window blinds
403334 01/30/2017 450214 1 220 O Post sign indicating primary and secondary evacuation routes in contrasting colors on evacuation map - contact FMC for assistance is needed
403336 01/30/2017 450219 1 222 O Remove and prohibit paper on window blinds
403339 01/30/2017 450225 1 223 O Remove and prohibit paper on window blinds
403337 01/30/2017 450221 1 224 O Remove and prohibit paper on window blinds
403338 01/30/2017 450223 1 224 O Remove and prohibit fabric covering window in corridor door
403335 01/30/2017 450216 1 227 O Post sign indicating primary and secondary evacuation routes in contrasting colors on evacuation map - contact FMC for assistance is needed
403345 01/30/2017 450237 1 0000 MS Provide current inspection tag for fire extinguisher in corridor adjacent to 1-212
403360 01/30/2017 450267 1 127A MS Repair unlock button on bathroom door to work properly
403359 01/30/2017 450265 1 139A MS Repair unlock button on bathroom door to work properly
403332 01/30/2017 450210 1 190 MS Provide current inspection tag for fire extinguisher
403354 01/30/2017 450255 1 122 OS Relocate easel to maintain 3 ft clear path to exterior door
403358 01/30/2017 450263 1 125 OS Remove and prohibit use of toaster oven
388376 01/11/2017 417934 00 0000 M Make repairs as noted on fire sprinkler inspection report dated February 2015. 1-182, and buildings 3 and 4. Provide current annual inspection tag for building 5
388384 01/11/2017 417950 2 0000 C Repair holes and damaged, rusty areas of pavilion
388389 03/28/2016 417960 00 8087 M Re-attach grounding wire to pole for covered walk at student drop of area
388388 03/28/2016 417958 1 101A M Adjust door closer on exterior door to control speed of closing door
388381 03/28/2016 417944 1 121A M Secure loose light switch cover plate
388382 03/28/2016 417946 1 124 M Repair deteriorated wall finish at exterior door
388383 03/28/2016 417948 1 128 M Repair deteriorated wall finish at exterior door
388366 03/28/2016 417913 1 150 M Repair damaged wall finish and secure loose base on wall at south exterior doors
388367 03/28/2016 417915 1 151H M Replace missing floor tile at threshold
388368 03/28/2016 417918 1 171 M Replace missing ceiling tiles
388380 03/28/2016 417942 1 180 M Replace broken bracket for fire extinguisher
388362 03/28/2016 417905 1 186 M Repair deteriorated wall finish and secure loose base on wall at exterior door, replace missing base on wall adjacent to table
388369 03/28/2016 417920 1 191 M Replace missing screws in electrical panel 1LE Sec 2
388361 03/28/2016 417903 1 199 M Adjust door closer to control speed of closing door
388375 03/28/2016 417932 1 9599 M Replace missing cover for cleanout in grass adjacent to sidewalk north of 1-145 and 1-144
388385 03/28/2016 417952 2 102 M Determine cause of water damaged ceiling tiles and replace tiles
388387 03/28/2016 417956 5 180 M Adjust door to latch properly
388377 03/28/2016 417936 1 0000 O Prohibit attaching papers directly to window blinds in the following rooms 1-126, 1-127, 1-128, 1-131, 1-139, 1-140, 1-142,
388379 03/28/2016 417940 1 135 O Remove excessive flammable (cloud paper) wall covering, limit coverage area to 50 percent of each wall in a building with fire sprinklers
388378 03/28/2016 417938 1 136 O Prohibit white 13A extension cord at air hockey table or replace with minimum 15A single outlet extension cord (March 2016 per school staff and zone team the table was manufactured with the white cord as part of the installation and has met UL standards)
388360 03/28/2016 417901 1 148 O Prohibit white 13A extension cord at window or replace with minimum 15A single outlet extension cord
388359 03/28/2016 417899 1 149 O Prohibit white 13A extension cord at electronic drums or replace with minimum 15A single outlet extension cord
388371 03/28/2016 417924 1 205 O Prohibit white 13A extension cord adjacent to microwave or replace with minimum 15A single outlet extension cord
388372 03/28/2016 417926 1 208 O Relocate string line to hang no more than 2 inches from wall surface
388365 03/28/2016 417911 1 158 MS Recharge fire extinguisher at exterior door
388363 03/28/2016 417907 1 186 MS Adjust exterior door to close and latch properly
388374 03/28/2016 417930 1 290 MS Recharge fire extinguisher
388386 03/28/2016 417954 4 101 MS Adjust door to 4-101A to close and latch properly
388358 03/28/2016 417897 1 149 OS Maintain clear aisle to exits
388370 03/28/2016 417922 1 211 OS Maintain clear aisle to exit
388373 03/28/2016 417928 1 212 OS Maintain clear aisle to exit
371558 03/30/2015 381542 00 0000 M Provide chain and lock on fence gate to chiller compound
371561 03/30/2015 381548 00 0000 M Remove poison ivy from cabbage palm at south campus at perimeter fence
371580 03/30/2015 381587 00 0000 M Provide caps for holes in play courts for volley ball posts
371565 03/30/2015 381556 1 0000 M Secure latch post for gate in fencing west of 1-128
371566 03/30/2015 381558 1 0000 M Replace missing escutcheon on fire sprinkler head in corridor adjacent to 1-193
371557 03/30/2015 381540 1 0000 M Secure loose down rod at bottom of door in corridor adjacent to 1-146
371555 03/30/2015 381535 1 0000 M Repair door in corridor adjacent to 1-137 to open and close properly. Door drags on floor
371542 03/30/2015 381507 1 101 M Secure 2 loose escutcheons on fire sprinkler head
371544 03/30/2015 381511 1 118 M Replace missing handicapped grabrail
371577 03/30/2015 381581 1 124 M Secure faucet to sink
371574 03/30/2015 381575 1 141 M Secure faucet to sink
371575 03/30/2015 381577 1 141A M Repair exhaust fan in bathroom
371573 03/30/2015 381573 1 142 M Secure faucet to sink
371547 03/30/2015 381518 1 144A M Repair leaking sink drain line
371548 03/30/2015 381520 1 144A M Provide larger clean out cover behind toilet to cover opening
371562 03/30/2015 381550 1 150 M Determine cause of water damaged ceiling tiles and replace tiles at SE corner of room at entry doors
371578 03/30/2015 381583 1 150E M Repair leaking handicapped toilet supply line
371579 03/30/2015 381585 1 150E M Secure loose handicapped grabrail
371551 03/30/2015 381526 1 151 M Clean Kitchen hood and provide tag indicating date cleaned. Tag indicates last cleaning 3-18-13
371571 03/30/2015 381568 1 158 M Adjust south door to exterior to latch properly
371549 03/30/2015 381522 1 185 M Repair or replace leaking water heater
371568 03/30/2015 381562 1 186 M Repair damaged wall at floor sink. Provide tile, stainless steel, aluminum or plastic backsplash to prevent further damage
371569 03/30/2015 381564 1 186 M Provide clean-out cover on wall at floor sink
371570 03/30/2015 381566 1 198 M Indicator lights for surge protector on panel 1LSMDP are not illuminated. Repair or replace surge protector
371588 03/30/2015 381605 1 201A M Secure faucet to sink in bathroom
371589 03/30/2015 381607 1 204 M Secure faucet to sink
371590 03/30/2015 381609 1 208 M Secure faucet to sink
371587 03/30/2015 381603 1 215A M Secure faucet to sink in bathroom
371560 03/30/2015 381546 1 220 M Secure faucet to sink
371550 03/30/2015 381524 1 222 M Secure faucet to sink
371586 03/30/2015 381601 1 224 M Secure faucet to sink
371585 03/30/2015 381599 1 224A M Repair leaking toilet supply line
371576 03/30/2015 381579 2 101 M Connect downspouts to storm sewer on south side of covered play area
371583 03/30/2015 381593 3 0000 M Replace pressure gauge on fire sprinkler riser. Needle frozen and face plate bent
371582 03/30/2015 381591 3 104 M Repair emergency lighting at rear of room
371581 03/30/2015 381589 3 104A M Determine cause of water damaged ceiling tiles and replace tiles
371539 03/30/2015 381501 4 0000 M Provide chain and lock on gate of fencing around fire main backflows at building 4
371537 03/30/2015 381497 4 101 M Repair emergency lighting
371540 03/30/2015 381503 4 101C M Repair damaged flush valve on toilet
371541 03/30/2015 381505 5 0000 M Provide current quarterly inspection tag for fire sprinkler system
371534 03/30/2015 381490 00 0 O No access was available to 1-105. Please provide access to this room during the report review meeting
371536 03/30/2015 381495 00 0000 O Provide name of Lead Crowd Manager who successfully completed the Crowd Management course as indicated in Bulletin # P-14808
371559 03/30/2015 381544 00 0000 O Prohibit parking on grass area at NW campus at custodial receiving
371584 03/30/2015 381596 1 0000 O Keep all shower drains filled with water. Every 2 months pour 1 quart of water down drains
371591 03/30/2015 381611 1 219 O Remove and prohibit plastic sheet covering on counter top
371538 03/30/2015 381499 1 227 O Provide secondary evacuation route on evacuation map
371554 03/30/2015 381533 1 0000 MS Adjust fire door in corridor adjacent to 1-136 to latch properly
371545 03/30/2015 381514 1 133A MS Repair thumb latch to enable door to be unlocked from outside of room
371546 03/30/2015 381516 1 144A MS Repair thumb latch to enable door to be unlocked from outside of room
371543 03/30/2015 381509 1 182 MS Provide current inspection tag for fire extinguisher
371552 03/30/2015 381528 1 203C MS Repair thumb latch to enable door to be unlocked from outside of room
371553 03/30/2015 381530 1 210B MS Repair thumb latch to enable door to be unlocked from outside of room
371563 03/30/2015 381552 1 153A OS Remove or relocate tables stored on Stage to maintain clear aisle to Stage exits
371567 03/30/2015 381560 1 186 OS Remove chain and padlock from gate of fenced enclosure in custodial receiving. Provide latch that can be opened from inside of enclosure
371564 12/12/2014 381554 1 192 M Repair or replace rusted and leaking fire sprinkler plumbing at east side of room adjacent to doors. Look for rust stain on floor
371572 12/12/2014 381570 1 196 M Repair or replace rusted and leaking fire sprinkler plumbing at elbow at NE corner of room. Look for rust marks on chilled water line insulation
371556 12/12/2014 381537 1 199A M Repair rusted and leaking fire sprinkler plumbing at SW of room at reducer. Look for rust marks on chilled water line insulation
358004 03/24/2014 352130 1 0000 M Repair crack in roof membrane above 1-101. Can be seen from looking out window of 1-211
357942 03/24/2014 352001 1 0000 M Provide chain and lock on gate of fencing around backflows outside of 1-193
357943 03/24/2014 352003 1 0000 M Provide lock on gate of fencing around electrical equipment outside of 1-158
357923 03/24/2014 351960 1 0000 M Adjust doors in corridor adjacent to 1-112 and 1-105 to latch properly
357924 03/24/2014 351962 1 0000 M Replace missing lower cover plate for panic hardware on doors in corridor adjacent to 1-117
357934 03/24/2014 351984 1 0000 M Fill gap between sidewalk and Kindergarten playground topping at west side of play area
357938 03/24/2014 351992 1 003 M Replace missing lower cover plate for panic hardware on fire door between stairs and corridor
357941 03/24/2014 351999 1 004 M Replace missing lower cover plate for panic hardware on fire doors at bottom of stairs
357880 03/24/2014 351870 1 118 M Secure loose handicaped grabrail
357920 03/24/2014 351954 1 122 M Replace GFI outlet that will not reset
357921 03/24/2014 351956 1 122A M Seal open corners in bathroom
357885 03/24/2014 351882 1 127A M Adjust door to 1-127 to latch properly
357918 03/24/2014 351950 1 128A M Repair exhaust fan in bathroom
357910 03/24/2014 351932 1 135 M Sign room 6 max or change swing of door to swing in direction of egress
357903 03/24/2014 351916 1 136 M Remove pencil sharpener without cover adjacent to door
357917 03/24/2014 351948 1 137A M Repair exhaust fan in bathroom
357912 03/24/2014 351937 1 139 M Secure loose push button to drinking fountain
357911 03/24/2014 351934 1 139A M Secure loose faucet
357926 03/24/2014 351966 1 140 M Secure loose faucet
357927 03/24/2014 351968 1 140A M Replace broken toilet seat
357913 03/24/2014 351939 1 141 M Replace GFCI outlet that will not trip
357914 03/24/2014 351941 1 141 M Exterminate ants in classroom
357902 03/24/2014 351914 1 144A M Repair exhaust fan in bathroom
357899 03/24/2014 351908 1 150C M Anchor and caulk toilet to wall
357886 03/24/2014 351884 1 150E M Repair leaking supply lines for 1st and handicapped toilets
357888 03/24/2014 351888 1 151 M Provide protective cage around fire sprinkler head in walk-in cooler
357889 03/24/2014 351890 1 151 M Provide protective cage around fire sprinkler head in walk-in freezer
357890 03/24/2014 351892 1 151 M Immediately repair broken emergency release hardware in walk-in cooler. Knob will not turn
357891 03/24/2014 351894 1 151 M Provide current inspection tag for kitchen hood fire suppression system. Tag is there, however, no date is punched on the tag
357887 03/24/2014 351886 1 151A M Repair leak on pulper in dish wash room
357900 03/24/2014 351910 1 151J M Replace GFCI outlet that will not trip
357898 03/24/2014 351906 1 153B M Replace missing escutcheon on fire sprinkler head
357896 03/24/2014 351902 1 155 M Replace missing escutcheon on fire sprinkler head. I left escutcheon on sink faucet
357904 03/24/2014 351918 1 171 M Repair rusted ceiling grid and check above ceiling for possible fire sprinkler leak. Sprinkler escutcheon is also rusted
357895 03/24/2014 351900 1 184 M Repair leaking union on water heater
357908 03/24/2014 351926 1 192 M Anchor air handler 2 at 4 corners
357909 03/24/2014 351928 1 192 M Close and lock EMS box adjacent to air handler 1
357905 03/24/2014 351920 1 192A M Wire security cabinet correctly. Do not place wire between door frame and box. Cut hole in box and provide cord restraint and or bushing
357919 03/24/2014 351952 1 193 M Close and lock EMS box
357931 03/24/2014 351977 1 195 M Secure cover for panel 1LB
357936 03/24/2014 351988 1 196 M Close and lock EMS cabinet
357937 03/24/2014 351990 1 196 M Anchor air handler 5 at 4 corners
357906 03/24/2014 351922 1 197 M Repair leaking plumbing for water heaters at 2 inch union and coupling
357935 03/24/2014 351986 1 198 M Repair coolant leak at top radiator hose on generator
357986 03/24/2014 352091 1 201B M Repair leaking toilet supply line
357991 03/24/2014 352101 1 203 M Remove pencil sharpener without cover adjacent to door
357988 03/24/2014 352095 1 203B M Repair exhaust fan in bathroom
357989 03/24/2014 352097 1 203C M Repair exhaust fan in bathroom
357990 03/24/2014 352099 1 203C M Secure push button to faucet
357993 03/24/2014 352106 1 204A M Secure sink to wall
357994 03/24/2014 352108 1 204B M Repair leaking toilet supply line
357995 03/24/2014 352110 1 206B M Secure sink to wall
357996 03/24/2014 352112 1 207C M Secure sink to wall
358003 03/24/2014 352127 1 209 M Secure loose faucet
357975 03/24/2014 352068 1 211A M Secure loose faucet
357976 03/24/2014 352070 1 213A M Repair exhaust fan in bathroom
357997 03/24/2014 352114 1 218A M Secure sink to wall
357979 03/24/2014 352076 1 219A M Repair leaking toilet supply line
357983 03/24/2014 352084 1 220 M Remove pencil sharpener without cover
357981 03/24/2014 352080 1 220A M Caulk sink to wall
357984 03/24/2014 352086 1 222 M Exterminate ants in classroom
357982 03/24/2014 352082 1 222A M Caulk sink to wall
357980 03/24/2014 352078 1 222A M Repair leaking toilet supply line
357969 03/24/2014 352057 1 225 M Secure loose push button to drinking fountain
357971 03/24/2014 352059 1 225 M Remove old pencil sharpener base adjacent to door
357998 03/24/2014 352116 1 226A M Secure sink to wall
357977 03/24/2014 352072 1 290 M Anchor air handler at 4 corners
357978 03/24/2014 352074 1 290 M Close and lock EMS cabinet
357973 03/24/2014 352064 1 291 M Secure air handler at 4 corners
357974 03/24/2014 352066 1 291 M Close and lock EMS cabinet
357892 03/24/2014 351896 2 104 M Adjust duration of flush for toilet. Too long
357953 03/24/2014 352024 3 101B M Repair leaking toilet supply line
357951 03/24/2014 352019 3 101C M Repair leaking toilet supply line
357950 03/24/2014 352017 3 104A M Determine cause of water damaged ceiling tiles and replace tiles
357952 03/24/2014 352021 3 104B M Repair leaking toilet supply line
357948 03/24/2014 352013 3 190 M Repair emergency lighting
357949 03/24/2014 352015 3 190 M Close and lock all open cabinets
357946 03/24/2014 352009 4 0000 M Provide lock on gate of fencing around fire sprinkler riser
357960 03/24/2014 352037 4 101 M Repair drinking fountain. No water
357958 03/24/2014 352032 4 101C M Repair door to open and close properly. Door hits frame
357962 03/24/2014 352042 4 104 M Repair emergency lighting at rear of room
357955 03/24/2014 352028 4 190 M Close and lock all open cabinets
357947 03/24/2014 352011 5 0000 M Provide lock on gate of fencing around fire sprinkler riser
357968 03/24/2014 352052 5 101 M Determine cause of water damaged ceiling tiles and replace tiles and replace missing tiles
357945 03/24/2014 352007 5 101B M Repair leaking toilet supply line
357944 03/24/2014 352005 5 180 M Replace missing ceiling tiles
357964 03/24/2014 352045 5 190 M Close and lock video cabinet
357965 03/24/2014 352049 5 190 M Repair emergency lighting
357922 03/24/2014 351958 00 0000 O Prohibit parking on grass area north of 1-145 and 1-144
357916 03/24/2014 351946 1 126B O Remove and prohibit storage on cook top
357930 03/24/2014 351974 1 150 O Inswinging doors into cafeteria have been marked as exits. Doors must swing in the direction of egress travel. The inswinging doors cannot be used as exits. The northern doors are the appropriate doors for exiting the cafeteria. Remove the exit signs from the inswinging doors or get a permit from the Building Department to change the door swing
357939 03/24/2014 351995 1 199 O Store loose old light tubes in more appropriate location in a box. Store in custodial closet or custodial receiving
357987 03/24/2014 352093 1 202 O Provide primary and secondary evacuation routes on evacuation map
357992 03/24/2014 352103 1 204 O Eliminate multiple outlet non 15 amp extension cord to fish tank. Replace with surge suppressor
358002 03/24/2014 352125 1 210 O Post sign indicating evacuation routes
357972 03/24/2014 352062 1 226 O Remove and prohibit hanging paper from ceiling. Attach to walls. A maximum of 12 8 and one half inch by 11 inch sheets of paper can be hung from the ceiling
357928 03/24/2014 351970 1 0000 MS Adjust fire door at bottom of stair 1-006 to latch properly
357929 03/24/2014 351972 1 0000 MS Adjust fire doors in corridor adjacent to 1-147 and 1-192 to latch properly
357882 03/24/2014 351875 1 125A MS Repair thumb latch to enable door to be unlocked from outside of bathroom
357883 03/24/2014 351877 1 133A MS Repair thumb latch to enable door to be unlocked from outside of bathroom
357884 03/24/2014 351880 1 139A MS Repair thumb latch to enable door to be unlocked from outside of bathroom
357901 03/24/2014 351912 1 143A MS Provide thumb latch to enable door to be unlocked. Replace lock, thumb latch missing
357881 03/24/2014 351873 1 180 MS Provide current inspection tag for fire extinguisher
357925 03/24/2014 351964 1 182 MS Provide current inspection tag for fire extinguisher
357932 03/24/2014 351979 1 195 MS Remove storage from electrical room
357999 03/24/2014 352118 1 206C MS Repair thumb latch to enable door to be unlocked from outside of room
358000 03/24/2014 352120 1 210B MS Repair thumb latch to enable door to be unlocked from outside of room
358001 03/24/2014 352122 1 217A MS Repair thumb latch to enable door to be unlocked from outside of room
357985 03/24/2014 352088 1 225A MS Repair thumb latch to enable door to be unlocked from outside of room
357915 03/24/2014 351943 1 130 OS Prohibit storage of gas powered equipment
357897 03/24/2014 351904 1 153A OS Maintain clear aisle to ramp exit
357933 03/24/2014 351982 1 158C OS Remove couch and chair at exit to maintain clear aisle to exit
357907 03/24/2014 351924 1 192 OS Remove storage from mechanical room
357940 03/24/2014 351997 1 198 OS Remove storage from generator room
347054 11/15/2013 327880 1 151 M Provide current state inspection tag for kitchen steamer (boiler)
347061 04/04/2013 327896 00 0000 M Provide boxes with wrench and spare fire sprinkler heads for Pre-K building
347056 04/04/2013 327886 00 0000 M Repair all exit gates with panic hardware at Pre-K area to operate properly
347038 04/04/2013 327847 1 0000 M Repair north exterior corridor doors between 1-150 and 1-148 to close and latch properly
347020 04/04/2013 327809 1 0000 M Replace missing latch plate on south gate in kindergarten play area
347013 04/04/2013 327794 1 008 M Adjust smoke doors at 1-217 to close and latch properly
347077 04/04/2013 327932 1 102 M Repair and secure loose emergency eye wash
347024 04/04/2013 327818 1 122 M Adjust exterior door to close and latch properly
347022 04/04/2013 327813 1 122A M Replace missing signage indicating room name and number, mount at appropriate height with raised and Braille characters
347019 04/04/2013 327807 1 131A M Mount fire extinguisher at maximum five feet above floor
347063 04/04/2013 327900 1 139A M Repair exhaust fan in bathroom
347068 04/04/2013 327910 1 142A M Repair exhaust fan in bathroom
347064 04/04/2013 327902 1 143 M Adjust door closer to control speed of closing door
347065 04/04/2013 327904 1 143A M Repair thumb latch on door to operate properly
347047 04/04/2013 327865 1 150 M Repair hole in west wall under south window
347045 04/04/2013 327861 1 150C M Replace missing base on wall in vestibule
347049 04/04/2013 327870 1 151 M Adjust door closer on exterior door to control speed of closing door
347050 04/04/2013 327872 1 151 M Adjust door of walk-in refrigerator to close properly
347051 04/04/2013 327874 1 151 M Repair emergency release hardware for walk-in refrigerator to operate easily
347052 04/04/2013 327876 1 151G M Shorten length of dryer hose to eliminate lint build up
347053 04/04/2013 327878 1 152 M Adjust door closer on exterior door to control speed of closing door
347043 04/04/2013 327857 1 156 M Replace missing soap dispenser
328534 04/04/2013 287893 1 158C M Provide dated flame resistance label on curtain in CCTV studio
347037 04/04/2013 327845 1 186 M Repair hole in west wall
347035 04/04/2013 327841 1 186 M Adjust door closer on exterior door to control speed of closing door
347027 04/04/2013 327822 1 192 M Pad and mark corners of duct at rear of room which are lower than 6 feet 8 inches
347032 04/04/2013 327834 1 198 M Provide certification that all student occupied spaces have emergency lights and all are operable, certificate is expired
347033 04/04/2013 327837 1 199 M Adjust door closer on exterior door to control speed of closing door
347034 04/04/2013 327839 1 199A M Adjust door closer on exterior door to control speed of closing door
347014 04/04/2013 327797 1 216 M Repair deteriorated wall finish at window
347015 04/04/2013 327799 1 216 M Replace missing base on wall at window
347055 04/04/2013 327883 2 0000 M Repair and repaint rusty areas of columns for covered play area at building 2
347059 04/04/2013 327892 3 101 M Repair emergency lighting
347060 04/04/2013 327894 3 101 M Adjust door closer to control speed of closing door
347057 04/04/2013 327888 5 101 M Adjust door closers on east and west doors to control speed of closing doors
347058 04/04/2013 327890 5 104 M Repair emergency lighting
347062 04/04/2013 327898 1 135 O Prohibit grey multi outlet extension cord or replace with minimum 15A single outlet cord
347069 04/04/2013 327912 1 142 O Relocate anchor charts to hang no more than 2 inches from wall, prohibit hanging charts from ceiling in center of classroom
347067 04/04/2013 327908 1 144 O Provide minimum one foot blank wall space on lock side of door
347066 04/04/2013 327906 1 145 O Prohibit white 13A extension cord or replace with minimum 15A single outlet cord
347042 04/04/2013 327855 1 158C O Prohibit plugging surge protector into extension cord
347048 04/04/2013 327868 1 186 O Prohibit using hold open device on door, keep door locked when students are occupying cafeteria
347036 04/04/2013 327843 1 186 O Prohibit use of espresso maker with modified power cord
347029 04/04/2013 327827 1 192A O No access was available to this room. Please provide access to this room during the report review meeting
347017 04/04/2013 327803 1 201 O Provide minimum one foot blank wall space on lock side of door
347016 04/04/2013 327801 1 210 O Post sign indicating primary and secondary evacuation routes
347076 04/04/2013 327930 1 191 C Verify that electrical room has 2 hour rated walls or provide automatic fire sprinkler coverage
347044 04/04/2013 327859 1 184 MS Provide current inspection tag for fire extinguisher
328518 04/04/2013 287860 3 0000 MS Provide current annual inspection tag for fire sprinkler system
328519 04/04/2013 287862 4 0000 MS Provide current annual inspection tag for fire sprinkler system
328520 04/04/2013 287864 5 0000 MS Provide current annual inspection tag for fire sprinkler system
347018 04/04/2013 327805 1 004 OS Prohibit hold open devices on fire doors at first floor corridor door
347039 04/04/2013 327849 1 158B OS Remove and prohibit use of space heater
347040 04/04/2013 327851 1 158C OS Maintain clear aisle to exterior door
347046 04/04/2013 327863 1 185 OS Prohibit using hold open device (wedge) at top of door which damages door and frame. Wedge at bottom of door between door and floor may be used temporarily
328527 04/04/2013 287878 00 0000 CS Provide suitable area for storage and recharging floor cleaning machines and golf carts
328530 12/17/2012 287884 1 151 M Adjust emergency release hardware in freezer or cooler to turn easily
328533 12/17/2012 287890 1 153A M Provide dated flame resistance label on all stage curtain
328544 12/17/2012 287914 1 203C M Repair unlock button on bathroom door to work properly
323396 12/17/2012 276061 1 158C C Provide records that CCTV Studio rigging has been inspected and conforms to required safety standards
328551 12/17/2012 287929 1 282 MS Provide current inspection tag for fire sprinkler system - tagged quarterly (4/28/2011)
328524 12/17/2012 287872 00 0000 FS Provide certification that fire alarm system has been tested and is fully operational. Provide report for review - report was not available for site
328528 02/10/2012 287880 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
328522 02/10/2012 287868 00 9599 M Adjust latch hardware of gate to latch properly between Bldg. 4 and basketball court
328536 02/10/2012 287897 1 0000 M Repair fire extinguisher cabinet in corridor adjacent to 1-159 to open easily
328539 02/10/2012 287904 1 003 M Secure loose graspable handrail for stairs at 2nd floor landing
328541 02/10/2012 287908 1 004 M Secure loose graspable handrail for stairs at top of intermediate landing
328540 02/10/2012 287906 1 006 M Secure loose graspable handrail for stairs at intermediate landing
328545 02/10/2012 287916 1 124A M Repair unlock button on bathroom door to work properly
328546 02/10/2012 287918 1 125A M Repair unlock button on bathroom door to work properly
328537 02/10/2012 287900 1 149 M Replace missing escutcheon on fire sprinkler head adjacent to 1-149B
328535 02/10/2012 287895 1 185 M Provide correct wall bracket for fire extinguisher and mount at maximum five feet above floor
328523 02/10/2012 287870 1 191 M Repair air conditioner unit to work properly above door
328543 02/10/2012 287912 1 201B M Repair unlock button on bathroom door to work properly
328547 02/10/2012 287921 1 205 M Repair door to open and close properly - door rubs on frame
328548 02/10/2012 287923 1 220 M Repair door to open/close properly
328542 02/10/2012 287910 1 225 M Repair door hardware - latch hardware sticks
328517 02/10/2012 287858 5 104 M Replace missing ceiling tiles
328882 02/10/2012 288638 1 101 O Provide certification that curtains are flameproof and passed the test standards of NFPA-701 or remove curtains
328532 02/10/2012 287888 1 150B O Remove paper covering room name and number for storage room adjacent to stage
328538 02/10/2012 287902 1 171 O Remove excessive lint on exhaust fan grille in elevator machine room
328549 02/10/2012 287925 1 211 O Eliminate white extension cord with multiple outlet end under computer stations adjacent to windows or replace with a surge protector
328525 02/10/2012 287874 1 180 MS Provide current inspection tag for fire extinguisher
328550 02/10/2012 287927 1 182 MS Provide current inspection tag for fire sprinkler system - tagged quarterly (4/28/2011)
328552 02/10/2012 287931 1 003 OS Prohibit use of wedge as hold open device on fire door at bottom of stairwell adjacent to 1-143
328531 02/10/2012 287886 1 150 OS Prohibit use of wedge as hold open device on fire doors to dining room
328529 02/10/2012 287882 1 151F OS Relocate storage to keep area within 18" of fire sprinkler head clear and unobstructed
328526 02/10/2012 287876 1 186 OS Prohibit charging batteries in room
328521 02/10/2012 287866 4 101A OS Relocate bookstand to provide clear access to fire extinguisher cabinet
188972 11/14/2011 30764 1 153A M Provide dated flame resistance label on light blue stage curtain
323390 04/27/2011 276049 1 005 M Determine cause of water damaged ceiling tiles in corridor adjacent to 1-006 stairway, and replace tiles
323391 04/27/2011 276051 1 005 M Repair smoke doors in corridor adjacent to 1-006 stairway to close properly
323417 04/27/2011 276105 1 008 M Repair smoke doors in second floor corridor adjacent to 1-217 to close properly
323388 04/27/2011 276045 1 102 M Determine cause of water damaged ceiling tiles and replace tiles
323407 04/27/2011 276085 1 131 M Replace missing escutcheon on fire sprinkler head
323394 04/27/2011 276056 1 151 M Adjust walk-in freezer and walk-in cooler doors to close and seal properly
323392 04/27/2011 276053 1 198 M Provide certification (emergency lighting report) that all student occupied spaces have emergency lights and all are operable
323405 04/27/2011 276081 3 0000 M Repair emergency light on exterior wall at entrance to 3-104
323403 04/27/2011 276077 5 104 M Determine cause of water damaged ceiling tiles and replace tiles
323389 04/27/2011 276047 1 104 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
323409 04/27/2011 276089 1 124 O Prohibit plugging microwave oven and refrigerator into surge protector - plug directly into permanent electrical outlet
323410 04/27/2011 276093 1 136 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
323413 04/27/2011 276098 1 227 O Remove and prohibit flammable decorations hanging from ceiling
323387 04/27/2011 276043 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus (last inspection date was January 2010)
323401 04/27/2011 276069 1 157 OS Prohibit storage of flammable sterno heat cans (store cans in flammable storage room or flammable storage cabinet)
295801 02/24/2011 215913 1 151 M Provide current inspection tag for kitchen steamer
299197 02/12/2010 223305 00 0000 M Paint building numbers on exterior walls to be visible to fire rescue personnel
282258 02/12/2010 187015 00 9599 M Secure loose post for gate in chain link fencing adjacent to 1-193 (see PE teacher)
299220 02/12/2010 223350 1 150 M Adjust SW double exit doors to open easily - hard to open
299187 02/12/2010 223284 1 170 M Provide current inspection tag for elevator
281925 02/12/2010 186303 1 185 M Replace missing grille for exhaust fan in custodial closet
299214 02/12/2010 223339 1 191 M Provide cover on exposed electrical junction box above door
299213 02/12/2010 223337 1 119 O Relocate storage to keep area within 18" of fire sprinkler head clear and unobstructed
299189 02/12/2010 223288 1 158B O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
299199 02/12/2010 223309 1 207 O Eliminate white 13A extension cord with multiple outlet end under teacher's desk or replace with minimum 15A cord single outlet end
299206 02/12/2010 223323 3 101 O Remove and prohibit combustible beanbag chairs(X2)
299205 02/12/2010 223321 3 104 O Remove and prohibit combustible beanbag chairs(X2)
299203 02/12/2010 223317 4 101 O Remove and prohibit combustible beanbag chairs (X2)
299204 02/12/2010 223319 4 104 O Remove and prohibit combustible beanbag chairs(X2)
299208 02/12/2010 223327 5 101 O Remove and prohibit combustible beanbag chairs(X2)
299207 02/12/2010 223325 5 104 O Remove and prohibit combustible beanbag chair
295794 02/12/2010 215898 00 0000 C Provide exterior signage indicating property address
299198 02/12/2010 223307 1 004 MS Adjust fire doors at top of stairwell to latch properly
299185 02/12/2010 223280 1 104A MS Provide current inspection tag for fire extinguisher
299186 02/12/2010 223282 1 119 MS Provide current inspection tag for fire extinguisher
299209 02/12/2010 223329 1 138 MS Adjust corridor door to latch properly
299210 02/12/2010 223331 1 140 MS Adjust corridor door to latch properly
299193 02/12/2010 223297 1 141 MS Adjust corridor door to latch properly - door rubs on frame
299211 02/12/2010 223333 1 142 MS Adjust corridor door to latch properly
299212 02/12/2010 223335 1 148A MS Replace missing fire extinguisher in kiln room
299188 02/12/2010 223286 1 150 MS Provide current inspection tag for fire extinguisher adjacent to 1-150A
299192 02/12/2010 223295 1 156 MS Adjust corridor door to latch properly - door rubs on frame
299215 02/12/2010 223341 1 190 MS Seal gap around conduit in wall adjacent to AC unit above door
299191 02/12/2010 223292 1 195 MS Remove maintenance storage from electrical room
299195 02/12/2010 223301 3 0000 MS Provide current inspection tag for fire sprinkler system
299194 02/12/2010 223299 4 0000 MS Provide current inspection tag for fire sprinkler system
299196 02/12/2010 223303 5 0000 MS Provide current inspection tag for fire sprinkler system
299218 02/12/2010 223346 1 153C OS Remove storage box at bottom of stage ramp
299216 02/12/2010 223343 1 154 OS Prohibit running communications cord across floor in front of door to dining room
299190 02/12/2010 223290 1 155 OS Remove and prohibit use of toaster in classroom
299200 02/12/2010 223311 1 213 OS Remove and prohibit use of toaster oven
299201 02/12/2010 223313 1 222 OS Remove and prohibit use of toaster oven
299202 02/12/2010 223315 1 222 OS Prohibit running electrical cord on floor across path to bathroom
295807 09/03/2009 215925 00 0000 M Label all fire department connections as to which buildings they supply
295802 09/03/2009 215915 1 151 M Loosen emergency release door knobs inside walk-in cooler and freezer to operate properly (both knobs were tightened so tight they were inoperable)
295808 09/03/2009 215927 1 211 O Remove and prohibit combustible residential couch furniture
282262 09/03/2009 187023 1 190 C Provide adequate ventilation for telecommunications room - room is very hot
282261 09/03/2009 187021 1 190 MS Prohibit wedging fire door in open position - blower fan is used to adjust room temperature
295809 04/21/2009 215929 1 006 M Replace missing escutcheon on fire sprinkler head
295799 04/21/2009 215909 1 158 M Repair exterior doors in southwest corner to close properly
232605 04/21/2009 88058 1 191 M Repair air conditioner to work properly, electrical room is too hot
295810 04/21/2009 215931 1 219A M Repair sink faucet in bathroom (faucet will not shut off)
281918 04/21/2009 186284 2 0000 M Repair damaged and leaking gutter at pavilion - see PE teacher
295803 04/21/2009 215917 3 190 M Repair door to open properly (door is wedged in jamb)
295804 04/21/2009 215919 4 190 M Repair door to open properly (door is wedged in jamb)
295805 04/21/2009 215921 5 190 M Repair door to open properly (door is wedged in jamb)
295797 04/21/2009 215905 1 149 O Eliminate 13 amp extension cord powering electronic piano or replace with minimum 15A cord
295795 04/21/2009 215901 1 003 MS Adjust fire doors at bottom of stairway to close properly and remain in the closed position (doors are wedged and held open by door stops attached to floor)
295796 04/21/2009 215903 1 003 MS Adjust exteior doors in stairway landing to close and latch properly
295811 04/21/2009 215933 1 220 MS Adjust corridor fire door to close properly
295806 04/21/2009 215923 5 190 MS Provide current inspection tag for fire extinguisher
295800 04/21/2009 215911 1 153A OS Prohibit wedges on double doors at back of stage
295798 04/21/2009 215907 1 197 OS Remove storage from mechanical room
281896 01/26/2009 186243 1 130 M Replace missing escutcheon on fire sprinkler head
282259 01/26/2009 187017 00 0000 C Provide suitable area for storage and recharging golf carts and floor cleaning machines
188967 01/26/2009 30827 1 003 C Adjust steps to make risers equal (Cor per Brad, approved by Bldg. Dept. 7/16/08))
188968 01/26/2009 30809 1 004 C Adjust steps to make risers equal (Cor per Brad, approved by Bldg. Dept. 7/16/08))
281893 04/23/2008 186237 1 128A M Repair damaged button on outside of bathroom door lever to enable door to be unlocked from the outside
281926 04/23/2008 186305 1 151 M Adjust two burner cook top to be under hood fire suppression nozzle
282260 04/23/2008 187019 1 190 M Replace missing ceiling tiles
281892 04/23/2008 186233 1 203C M Repair damaged button on outside of bathroom door lever to enable door to be unlocked from the outside
281890 04/23/2008 186223 1 206B M Repair damaged button on outside of bathroom door lever to enable door to be unlocked from the outside
281900 04/23/2008 186251 1 124 O Provide certification that carpet meets flame spread requirement or remove carpet
281924 04/23/2008 186300 1 151E O Eliminate multiple outlet adaptor or replace with a surge protector
281922 04/23/2008 186296 1 158B O Prohibit plugging microwave and toaster oven into surge protector - plug appliances directly into permanent electrical outlet
270148 04/23/2008 160905 1 222 O Provide certification of flame spread rating of carpeting or remove and prohibit carpeting
281904 04/23/2008 186259 1 147 MS Relocate fire extinguisher to be adjacent to exit door
281906 04/23/2008 186264 1 153B MS Relocate fire extinguisher to be adjacent to exit door
281913 04/23/2008 186273 1 004 OS Prohibit use of wedge to hold fire door in open position at bottom of stairs
281885 04/23/2008 186219 1 205 OS Remove and prohibit use of toaster oven
270126 01/25/2008 160862 1 129 M Determine cause of rusted fire sprinkler head and replace fire sprinkler head
270079 01/25/2008 160763 1 152 M Determine cause of leaking fire sprinkler head and repair leak
270080 01/25/2008 160765 1 153A M Replace missing escutcheon on fire sprinkler head
270153 01/25/2008 160921 1 211 M Determine cause of rusted fire sprinkler head and replace rusted fire sprinkler head
270150 01/25/2008 160915 1 221A M Replace missing escutcheon on fire sprinkler head
241992 01/25/2008 103493 1 227 M Replace missing escutcheon on fire sprinkler head
188962 04/30/2007 30873 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
270083 04/30/2007 160771 00 0000 M Repair west gate in play area adjacent to 1-193 to open properly
270077 04/30/2007 160759 1 0000 M Exterminate ants in office area (see office staff for exact locations)
188966 04/30/2007 30890 1 0000 M Adjust or replace fire doors through out facility so that clearance under bottom of doors does not exceed 1/2 inch
270136 04/30/2007 160877 1 006 M Repair exterior doors to open properly
270090 04/30/2007 160785 1 148 M Repair exterior door. Water leaks in the classroom when it rains (see teacher for details)
270081 04/30/2007 160767 1 158G M Replace missing sign at appropriate height with raised and Braille characters for room adjacent to south exterior doors of Media Center
270091 04/30/2007 160787 1 192A M Determine cause of leaking fire sprinkler pipe and repair leak
270152 04/30/2007 160919 1 211 M Anchor wood shelving to wall
270151 04/30/2007 160917 1 217B M Anchor shelving to wall
270128 04/30/2007 160866 1 127 O Remove and prohibit excessive flammable wall coverings and furniture
270096 04/30/2007 160799 1 137 O Remove and prohibit air freshener
270088 04/30/2007 160781 1 148 O Remove and prohibit air fresheners
270089 04/30/2007 160783 1 148 O Eliminate ant infestation at exterior door
270086 04/30/2007 160777 1 157 O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
270087 04/30/2007 160779 1 157 O Remove and prohibit paper decorations on ceiling
270085 04/30/2007 160775 1 159 O Remove and prohibit air freshener
270154 04/30/2007 160923 1 202 O Prohibit brown 13A extension cord or replace with minimum 15A cord
270142 04/30/2007 160892 1 216 O Prohibit use of white 13A extension cords (x2) or replace with minimum 15A cords
270092 04/30/2007 160789 1 134 MS Provide current inspection tag for fire extinguisher
270095 04/30/2007 160797 1 145 MS Provide current inspection tag for fire extinguisher
270094 04/30/2007 160795 1 0000 OS Remove and prohibit storage in corridor adjacent to 1-144
270156 04/30/2007 160927 1 104 OS Provide clear access to fire alarm breaker panel
270129 04/30/2007 160868 1 123 OS Keep area clear to exit door
270127 04/30/2007 160864 1 127 OS Keep area clear to exit door
270125 04/30/2007 160860 1 131 OS Keep area clear to exit door
270093 04/30/2007 160793 1 134 OS Prohibit running electrical cord for pencil sharpener into cabinet
270082 04/30/2007 160769 1 193 OS Remove storage from mechanical room
270138 04/30/2007 160887 1 216 OS Remove and prohibit use of toaster oven
270149 04/30/2007 160913 1 221 OS Remove and prohibit candles
270078 04/30/2007 160761 1 101A FS Provide log book with appropriate paperwork for fire alarm panel
270157 02/20/2007 160929 1 102 M Determine cause of water damaged ceiling tiles and replace tiles
232647 02/20/2007 88138 1 151 M Provide current inspection tag for kitchen steamer
188978 02/20/2007 30746 1 190 M Complete installation of ceiling grid and tiles or relocate sprinkler heads and heat detector to underside of roof deck
270155 02/20/2007 160925 1 210 O Remove and prohibit air freshener
242943 02/20/2007 105417 1 158C C Provide illuminated exit sign @ exterior door
241857 02/20/2007 103244 1 126B MS Provide current inspection tag for fire extinguisher in kitchen storage, Dated 02/2004
241937 02/20/2007 103377 1 151 MS Provide current inspection for fire hood suppression system, Dated 1/2005
241936 02/20/2007 103375 1 193 OS Prohibit recharging batteries for golf cart in room
241782 07/01/2006 103113 1 0000 CS Eliminate dead end corridor adjacent to 1-201 - second floor (approx. 20 feet)(Length verified by Brad Vermeulen)
241934 04/04/2006 103371 00 0000 M Verify that drinking fountains are working properly throughout campus (fountains were covered with black garbage bags)
241930 04/04/2006 103363 00 9699 M Fill hole in ground @ antenna near playground
188964 04/04/2006 30836 1 0000 M Adjust or replace smoke doors so that head, jamb, and seal clearance do not exceed 1/8 inch
242020 04/04/2006 103538 1 003 M Secure loose handrail @ north end stairwell
242017 04/04/2006 103532 1 004 M Secure loose handrail at stairwell adjacent to 1-280
242018 04/04/2006 103534 1 005 M Secure loose handrail @ stairwell adjacent to corridor 1-005 (bolt missing)
241760 04/04/2006 103083 1 112 M Determine cause of water damaged ceiling tiles and replace tiles
241761 04/04/2006 103084 1 116 M Determine cause of water damaged ceiling tiles and replace tiles
241762 04/04/2006 103085 1 121 M Determine cause of water damaged ceiling tiles @ door and replace tiles
241773 04/04/2006 103100 1 122 M Install door sweep on exterior door to eliminate gap at bottom of door
241892 04/04/2006 103286 1 122 M Replaced damaged weather-stripping on exterior door
241763 04/04/2006 103086 1 125 M Determine cause of water damaged ceiling tiles and replace tiles
241764 04/04/2006 103087 1 127 M Determine cause of water damaged ceiling tiles and replace tiles
242059 04/04/2006 103625 1 127 M Determine cause of peeling paint and repair
241928 04/04/2006 103359 1 149 M Secure loose weather-stripping on exterior door
242061 04/04/2006 103627 1 150 M Determine cause of deteriorated wall finish in dining room @ door and repair
241939 04/04/2006 103382 1 150C M Verify toilet in handicapped stall is working properly (water pressure low)
241967 04/04/2006 103450 1 150E M Repair water to run for sink and verify that toilets are working properly (water pressure low) in girl's restroom
242052 04/04/2006 103608 1 151 M Re-install metal plate threshold for cooler door (threshold is located on floor near cooler)
242053 04/04/2006 103613 1 151J M Repair exhaust fan in bathroom
242054 04/04/2006 103615 1 151K M Repair exhaust fan in bathroom
242056 04/04/2006 103618 1 152B M Repair exhaust fan in staff bathroom
241885 04/04/2006 103276 1 153A M Secure loose base adjacent to stage
241834 04/04/2006 103201 1 180 M Mount fire extinguisher at maximum five feet above floor (fire extinguisher located on floor)
232661 04/04/2006 88170 1 185 M Replace missing exhaust fan and grille in custodial room
241791 04/04/2006 103123 1 198 M Repair emergency lighting in generator room
242058 04/04/2006 103623 1 201B M Repair exhaust fan in boy's bathroom
241766 04/04/2006 103089 1 202 M Determine cause of water damaged ceiling tiles and replace tiles
241767 04/04/2006 103090 1 203 M Determine cause of water damaged ceiling tiles and replace tiles
188981 04/04/2006 30728 1 204 M Replace missing label on fire rated door
241772 04/04/2006 103097 1 205 M Repair or replace damaged vertical blinds
241976 04/04/2006 103464 1 205 M Provide sign indicating "Emergency Access" on exterior wall @ Emergency Access Window
241977 04/04/2006 103465 1 206 M Provide sign indicating "Emergency Access" on exterior wall @ Emergency Access Window
241768 04/04/2006 103091 1 207 M Determine cause of water damaged ceiling tiles and replace tiles
241769 04/04/2006 103092 1 219 M Determine cause of water damaged ceiling tiles and replace tiles
241933 04/04/2006 103369 1 219 M Remove water from lens for light fixture in ceiling near window
241968 04/04/2006 103451 1 219A M Secure sink to wall
241978 04/04/2006 103466 1 221 M Provide sign indicating "Emergency Access" on exterior wall @ Emergency Access Window
241770 04/04/2006 103093 1 221 M Determine cause of water damaged ceiling tiles and replace tiles
241969 04/04/2006 103452 1 221A M Secure sink to wall
241979 04/04/2006 103467 1 222 M Provide clear access to Emergency Access Window
241970 04/04/2006 103453 1 222A M Secure sink to wall
241980 04/04/2006 103468 1 223 M Provide sign indicating "Emergency Access" on exterior wall @ Emergency Access Window
241971 04/04/2006 103454 1 223A M Secure sink to wall
241804 04/04/2006 103138 1 281 M Replace missing vent cover in custodial room adjacent to elevator
241759 04/04/2006 103081 00 0000 O No access was available to 1-194 (Telecommunication Room). Please be prepared to access this room during the report review meeting.
241994 04/04/2006 103496 1 119 O Remove storage blocking fire sprinkler head
242935 04/04/2006 105398 1 119 O Relocate storage to keep area within 18" of automatic fire sprinkler heads clear and unobstructed
241792 04/04/2006 103125 1 122 O Eliminate pencil sharpener cord running through storage cabinet
241972 04/04/2006 103456 1 140 O Post sign indicating evacuation routes
241974 04/04/2006 103458 1 141 O Post sign indicating evacuation routes
242939 04/04/2006 105409 1 147 O Eliminate extension cords
241797 04/04/2006 103130 1 154 O Prohibit communication cable from running across floor to prevent tripping hazard
241886 04/04/2006 103278 1 155 O Provide certification of flame spread rating of carpeting or remove
241975 04/04/2006 103461 1 157 O Post sign indicating evacuation routes
241931 04/04/2006 103365 1 158C O Secure electric cord strip cover to floor
241887 04/04/2006 103279 1 201 O Provide certification of flame spread rating of rugs or remove
241990 04/04/2006 103487 1 201 O Prohibit decoration within 18" of automatic fire sprinkler head
241888 04/04/2006 103280 1 204 O Provide certification of flame spread rating of rugs or remove
241798 04/04/2006 103131 1 204 O Prohibit use of surge protector to power micro-wave
241932 04/04/2006 103367 1 204 O Prohibit electric fire place in classroom (not plugged in)
241799 04/04/2006 103132 1 206 O Prohibit use of surge protector to power micro-wave and refrigerator
241889 04/04/2006 103281 1 208 O Remove and prohibit combustible beanbag chair
241890 04/04/2006 103282 1 210 O Remove and prohibit combustible beanbag chair
241881 04/04/2006 103270 1 225 O Prohibit plug-in air freshener
241771 04/04/2006 103095 2 102 O Remove and prohibit paper covering window in door @ PE Equipment/Office room
241983 04/04/2006 103473 00 9699 C Modify or improve site drainage @ exterior doors between rooms 122 thru 130 and rooms 134 thru 144 (standing water and algae growing)
241776 04/04/2006 103107 1 0000 MS Adjust south corridor doors to latch properly adjacent to room 1-133 and stair 1-004
241777 04/04/2006 103108 1 0000 MS Adjust fire doors to latch properly between rooms 1-134 and 1-135
242932 04/04/2006 105395 1 0000 MS Adjust door to room 1-150E to latch properly
241856 04/04/2006 103243 1 119 MS Provide current inspection tag for fire extinguisher, Dated 02/2004
242937 04/04/2006 105405 1 131A MS Provide current inspection tag for Type "K" fire extinguisher, Dated 2004
241858 04/04/2006 103245 1 145 MS Provide current inspection tag for extinguisher in custodial office, Dated 02/2004
241778 04/04/2006 103109 1 151 MS Adjust exterior door to latch properly adjacent to 1-150
241781 04/04/2006 103112 1 151 MS Repair magnetic release hold open device for fire door between kitchen and serving area
188971 04/04/2006 30879 1 151B MS Provide current inspection tag for fire extinguisher (tag not punched)
241779 04/04/2006 103110 1 153B MS Adjust door to latch properly
243537 04/04/2006 106523 1 182 MS Provide current inspection tag for fire extinguisher, Dated 02/2004
243541 04/04/2006 106532 1 185 MS Provide current inspection tag for fire extinguisher, Dated 02/2004
188976 04/04/2006 30880 1 187 MS Provide fire rated sealant between interior and roof deck to prevent spread of fire or smoke
188979 04/04/2006 30882 1 192 MS Provide fire rated sealant between enclosure walls and roof deck to prevent spread of fire or smoke
242047 04/04/2006 103599 1 192 MS Remove stored ceiling tiles from mechanical room
242944 04/04/2006 105421 1 225 MS Repair door to latch properly
241780 04/04/2006 103111 1 227 MS Adjust fire door to latch properly
188982 04/04/2006 30884 1 291 MS Provide fire rated sealant between enclosure walls and roof deck to prevent spread of fire or smoke
241855 04/04/2006 103242 2 102 MS Provide current inspection tag for fire extinguisher, Dated 02/2004
241891 04/04/2006 103284 1 003 OS Prohibit wedging open fire doors @ bottom of stairwell door
241854 04/04/2006 103241 1 101 OS Remove boxes blocking fire extinguisher (front office)
241783 04/04/2006 103114 1 115 OS Remove storage blocking corridor door
243560 04/04/2006 106580 1 122 OS Keep area clear at emergency escape window
242936 04/04/2006 105402 1 122 OS Remove material blocking exterior door
241864 04/04/2006 103253 1 123 OS Prohibit plug-in air freshener
241784 04/04/2006 103115 1 127 OS Relocate or remove desk blocking corridor door
241868 04/04/2006 103257 1 131A OS Remove storage from stove
241785 04/04/2006 103116 1 147 OS Relocate or remove file cabinet blocking door
241786 04/04/2006 103117 1 151F OS Remove play pool blocking access to mechanical room 1-198
241871 04/04/2006 103260 1 151F OS Prohibit storage of flammable gloss protective enamel
241787 04/04/2006 103118 1 152 OS Arrange tables and chairs to provide a clear path to the exterior door
241788 04/04/2006 103119 1 153A OS Remove stage platform/riser blocking stage exit
241872 04/04/2006 103261 1 153B OS Prohibit storage of flammable spray paint (stage storage)
242941 04/04/2006 105413 1 153B OS Remove storage blocking exit door
241873 04/04/2006 103262 1 158F OS Prohibit storage of flammable spray in staff restroom
241874 04/04/2006 103263 1 158G OS Prohibit storage of flammable dust mop cleaner and WD40
241875 04/04/2006 103264 1 181 OS Prohibit storage of flammable Dust Mop Treatment and Disinfectant
241876 04/04/2006 103265 1 182 OS Prohibit storage of flammable WD40 and Dust Mop Treatment Cleaner
241877 04/04/2006 103266 1 186A OS Prohibit storage of gas powered blower
241878 04/04/2006 103267 1 186B OS Prohibit storage of flammable Dust Mop Treatment, WD40 and chewing gum remover
242049 04/04/2006 103603 1 199 OS Remove dairy crates from mechanical room
241879 04/04/2006 103268 1 204 OS Prohibit use of electrical hot plate on counter in classroom
241789 04/04/2006 103120 1 206 OS Remove microwave and file cabinet blocking emergency access window
241790 04/04/2006 103121 1 221 OS Remove material blocking emergency access window
241883 04/04/2006 103272 1 282 OS Prohibit storage of flammable Dust Mop Cleaner
241862 04/04/2006 103251 2 102 OS Prohibit storage of flammable field marker paint in PE Equipment/Office room
241938 04/04/2006 103379 00 0000 CS Provide Knox locks on bus loop and administration gates to allow fire department access
188961 02/17/2005 30845 00 0000 M Provide certification that elevator has current inspection tag
232645 02/17/2005 88134 1 101A M Adjust exterior double doors to latch properly
232606 02/17/2005 88062 1 151 M Repair emergency release hardware in freezer to turn easily
188975 02/17/2005 30755 1 158 M Adjust exterior door to latch properly
188980 02/17/2005 30737 1 197 M Provide current inspection tag for boilers
232632 02/17/2005 88107 1 281 M Secure loose grille on exhaust fan in custodial room
232642 02/17/2005 88128 2 101 M Secure loose gutter and downspout at south side of pavilion
232643 02/17/2005 88130 2 8088 M Secure loose screen at top of downspout at west wall of PE Bldg.
232648 02/17/2005 88140 1 119 O Relocate boxes to keep area within 18" of automatic fire sprinkler heads clear and unobstructed
232639 02/17/2005 88121 1 136 O Remove and prohibit combustible beanbag chair
232623 02/17/2005 88085 1 145 O Prohibit use of multi outlet adaptor adjacent to sink
233389 02/17/2005 89586 1 145 O Prohibit use of surge protector to power refrigerator. Plug appliances directly into wall outlet
232627 02/17/2005 88092 1 145 O Eliminate extension cord for alarm clock or replace with minimum 15A cord
232608 02/17/2005 88064 1 151 O Remove boxes blocking access to emergency release hardware in freezer
232624 02/17/2005 88089 1 186 O Prohibit use of surge protector to power microwave and toaster. Plug appliances directly into wall outlet
232640 02/17/2005 88124 1 203 O Remove and prohibit combustible residential rocker chair
232641 02/17/2005 88126 1 209 O Remove and prohibit combustible beanbag chairs
188965 02/17/2005 30872 1 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for bathroom adjacent to 1-104
188969 02/17/2005 30870 1 149 C Fill in maximum occupancy adjacent to main entrance
188970 02/17/2005 30871 1 150 C Fill in maximum occupancy adjacent to main entrance
188973 02/17/2005 30863 1 158 C Provide signage indicating room name and number at appropriate height with raised and Braille characters for storage room adjacent to exterior doors
188974 02/17/2005 62355 1 158 C Fill in maximum occupancy adjacent to main entrance
188963 02/17/2005 30877 1 0000 MS Repair smoke doors in corridor adjacent to 1-192A to close easily, door leaf rubs on edge protector
232609 02/17/2005 88068 1 0000 MS Adjust smoke doors in corridor adjacent to 1-135 to latch properly
232610 02/17/2005 88069 1 006 MS Adjust fire doors at bottom of stairwell to latch properly
232617 02/17/2005 88078 1 104A MS Provide current inspection tag for fire extinguisher
232618 02/17/2005 88079 1 127A MS Provide current inspection tag for fire extinguisher
232619 02/17/2005 88080 1 131A MS Provide current inspection tag for fire extinguisher
232611 02/17/2005 88070 1 133 MS Adjust fire door to latch properly
232620 02/17/2005 88081 1 181 MS Provide current inspection tag for fire extinguisher
232621 02/17/2005 88082 1 184 MS Provide current inspection tag for fire extinguisher
188977 02/17/2005 30881 1 190 MS Adjust fire door to latch properly
232612 02/17/2005 88071 1 210 MS Adjust fire door to latch properly
232613 02/17/2005 88072 1 225 MS Adjust fire door to latch properly
232644 02/17/2005 88132 1 003 OS Prohibit use of wedge to hold fire doors at bottom of stairs in open position
232635 02/17/2005 88110 1 126B OS Remove excessive storage in kitchen and provide clear access to fire extinguisher in kitchen
232636 02/17/2005 88115 1 127A OS Relocate boxes to provide clear access to fire extinguisher
232637 02/17/2005 88119 1 186 OS Relocate box blocking clear access to fire extinguisher
232646 02/17/2005 88136 1 186 OS Prohibit recharging batteries for floor cleaning machines in room