ROOSEVELT ELEMENTARY
 
ROOSEVELT ELEMENTARY
1220 15TH ST
WEST PALM BEACH, 33401
FISH Drill Down
 Campus Info.
 Buildings:6 Rooms:263
 Portables:0
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
410161 03/01/2018 465036 2 0000 M Repair exhaust fan in all individual bathroom - 1st floor
385436 03/01/2018 411647 4 112E M Provide protective cage around fire sprinkler head
410165 03/01/2018 465044 1 125 O Eliminate extension cord with multiple outlet end adjacent to microwave or replace with a surge protector
410159 03/01/2018 465034 2 112 O Prohibit plugging surge protector into surge protector under computer stations. Plug each surge protector directly into wall outlet
410196 03/01/2018 465108 3 002 O Remove and prohibit excessive flammable blue and red vinyl sheathing on bulletin boards in corridor between 3-113 and 3-115
410142 03/01/2018 464998 3 107 O Replace flickering light bulbs in girls bathroom or have maintenance repair light fixture
410090 03/01/2018 464891 4 112 O Adjust two burners cook top to be under hood fire suppression nozzle in kitchen
262830 03/01/2018 145248 1 0000 N/A No violations observed
262833 03/01/2018 145251 4 0000 N/A No violations observed
262834 03/01/2018 145252 5 0000 N/A No violations observed
262835 03/01/2018 145253 6 0000 N/A No violations observed
385422 01/30/2018 411618 00 0000 M Re-insulate chilled water pump at south end of chiller compound at building 3
410089 01/30/2018 464889 00 9599 M Keep gate in chain link fence around drainage/retention area locked to prohibit student access at bus loop
410163 01/30/2018 465042 1 112 M Determine cause of water damaged ceiling tiles and replace tiles
410149 01/30/2018 465012 2 192 M Fill undermined dirt under and around stoop at north side of Bldg.
410147 01/30/2018 465002 3 001 M Repair missing vinyl base along wall in west corridor adjacent to 3-108
410138 01/30/2018 464990 3 103B M Repair exhaust fan in bathroom
410085 01/30/2018 464881 3 113A M Repair exhaust fan in bathroom
410126 01/30/2018 464965 4 0000 M Repair damaged concrete finish at top of exterior ramp behind stage
410093 01/30/2018 464897 4 110 M Repair damaged corner edge protector at wall adjacent to 4-103
410091 01/30/2018 464893 4 110 M Repair fire extinguisher cabinet door to open and close properly - adjacent to NW exit doors
399384 01/30/2018 441730 4 119 M Repair deteriorated wall finish around doors
410154 01/30/2018 465024 5 103 M Adjust water flow for drinking spout
410155 01/30/2018 465026 5 111 M Adjust water flow for drinking spout
410087 01/30/2018 464885 6 102 M Repair exhaust fan in bathroom
410088 01/30/2018 464887 6 104 M Determine cause of water damaged ceiling tiles and replace tiles
410184 01/30/2018 465082 1 126 O Remove and prohibit excessive flammable blue vinyl sheathing on corridor door
410201 01/30/2018 465115 2 101 O Remove glass top in front of circulation desk. Glass is not marked tempered. You can ask Rickie Mann to install an approved safety film on both sides or remove glass top from media center
410152 01/30/2018 465016 2 101 O Prohibit plugging surge protector into surge protector under computer stations. Plug each surge protector directly into wall outlet
410192 01/30/2018 465102 2 103 O Remove and prohibit excessive flammable red and blue vinyl sheathing on tables
410190 01/30/2018 465096 2 110 O Remove and prohibit excessive flammable black vinyl sheathing on tables
410191 01/30/2018 465100 2 111 O Remove and prohibit excessive flammable pink vinyl sheathing on corridor door
410158 01/30/2018 465029 2 120 O Remove and prohibit paper on window blinds behind teacher desk
410186 01/30/2018 465088 2 203 O Remove and prohibit excessive flammable yellow, white and green vinyl sheathing on tables and on corridor door
410162 01/30/2018 465039 2 207 O Prohibit plugging surge protector into surge protector under computer stations positioned back to back. Plug each surge protector directly into wall outlet
410188 01/30/2018 465092 2 212 O Remove and prohibit excessive flammable white and yellow vinyl sheathing at teacher desk and adjacent to corridor door
410168 01/30/2018 465053 2 215 O Remove and prohibit paper covering window in corridor door
410194 01/30/2018 465105 3 113 O Remove and prohibit excessive flammable blue and red vinyl sheathing on tables
410124 01/30/2018 464959 3 117 O Replace missing burners or unplug cooking range from electrical outlet to eliminate hazardous condition
410131 01/30/2018 464970 4 0000 O Pressure clean exterior ramp behind stage to eliminate slipping caused by mold
410136 01/30/2018 464980 00 0000 MS Replace padlock with broken key on gate to chiller compound east of Bldg. 3
410166 01/30/2018 465047 00 0000 MS Provide current inspection tag for all fire extinguishers throughout campus. Tag date Sept. 2016
410167 01/30/2018 465049 2 208 MS Adjust corridor door to latch properly - door rubs on frame
410118 01/30/2018 464951 3 112 MS Adjust corridor door to latch properly - door rubs on frame
410086 01/30/2018 464883 3 115 MS Adjust corridor door to latch properly - door rubs on frame
410092 01/30/2018 464895 4 180 MS Secure loose door lever on custodial room door in dining room 4-110
410117 01/30/2018 464948 3 002 OS Remove desk and chairs at north end of corridor adjacent to 3-102
410119 01/30/2018 464954 3 112 OS Relocate file cabinet to maintain 3 ft clear path to exterior door
410181 10/05/2017 465080 00 0000 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report dated 1.26.2017
410173 10/05/2017 465060 00 9599 M Replace damaged concrete wheel stop in parking lot facing front office
399394 10/05/2017 441750 2 0000 M Repair damaged bottom of exterior wall finish at northeast corner of Building 2 below security camera
399397 10/05/2017 441756 2 007 M Repair door to second floor restroom vesrtibule to close properly
399409 10/05/2017 441780 2 120A M Repair ventilation fan in restroom. NA - whole floor was cited
399411 10/05/2017 441784 2 121A M Repair ventilation fan in restroom. NA - whole floor was cited
410139 10/05/2017 464994 3 103 M Adjust exterior door to latch properly
410140 10/05/2017 464996 3 180 M Repair exhaust fan in custodial room
385245 10/05/2017 411239 00 0000 C Post sign indicating primary and secondary evacuation routes in contrasting colors for buildings 2 and 5
350886 10/05/2017 336091 00 0000 C Modify or improve drainage from play courts to eliminate standing water on courts
262831 10/05/2017 145249 2 0000 N/A No violations observed
262832 10/05/2017 145250 3 0000 N/A No violations observed
385421 03/15/2017 411616 00 0000 M Remove trees from north end of chiller compound at building 3
399393 03/15/2017 441748 00 0000 M Secure covers on all in-ground electrical boxes at northeast corner of Building 3
399386 03/15/2017 441734 00 0000 M Provide chain and padlock on gate at retention pond south of Building 4
399374 03/15/2017 441710 1 125 M Replace missing escutcheon on fire sprinkler head
399376 03/15/2017 441714 1 192 M Make necessary repairs to fire sprinkler system as indicated on inspection report
399419 03/15/2017 441800 2 101 M Repair rusted steel side window framing at floor level next to west exit doors
399420 03/15/2017 441802 2 101 M Replace missing vinyl base at corner wall next to 2-102
399417 03/15/2017 441796 2 110 M Place ceiling tile back into metal ceiling grid
399416 03/15/2017 441794 2 113 M Secure hanging light fixture lens
399414 03/15/2017 441790 2 114 M Replace missing push button on drinking fountain on sink
399413 03/15/2017 441788 2 116 M Replace broken ceiling tile around sprinkler head above storage cabinet
399410 03/15/2017 441782 2 118A M Secure loose lens on light fixture
399415 03/15/2017 441792 2 193 M Place exposed electrical wiring coming out of conduit next to ceiling into junction box
399400 03/15/2017 441762 2 212 M Replace missing ceiling tile next to bathroom wall
399408 03/15/2017 441778 2 216 M Determine cause of water damaged ceiling tiles at southeast corner of room and replace tiles
399430 03/15/2017 441822 3 101 M Determine cause of water damaged ceiling tiles and replace tiles
399429 03/15/2017 441820 3 103 M Determine cause of water damaged ceiling tiles and replace tiles
399407 03/15/2017 441776 3 109 M Repair emergency lighting
399405 03/15/2017 441772 3 110 M Verify mirror is safety glass or cover with protective film
399406 03/15/2017 441774 3 111 M Repair emergency lighting
399404 03/15/2017 441770 3 112 M Verify mirror is safety glass or cover mirror with protective film
399403 03/15/2017 441768 3 115A M Repair ventilation fan in restroom
399402 03/15/2017 441766 3 117 M Repair damaged ceiling above window
399392 03/15/2017 441746 3 191 M Repair emergency lighting inside electric room
399401 03/15/2017 441764 3 192 M Replace missing ceiling tiles
399390 03/15/2017 441742 4 0000 M Repair damaged concrete landing on exterior ramp behind stage exit
399379 03/15/2017 441720 4 104 M Determine cause of water damaged ceiling tiles at southwest corner of room and replace tiles
399380 03/15/2017 441722 4 105 M Secure loose handrail on stairs in front of stage
399378 03/15/2017 441718 4 105 M Secure loose handrail at stage ramp
399382 03/15/2017 441726 4 112A M Secure loose ceiling hatch cover
399381 03/15/2017 441724 4 113 M Replace ceiling tiles that have holes in them
399383 03/15/2017 441728 4 119 M Repair or replace rusted door
399385 03/15/2017 441732 4 183 M Place ceiling tiles back into metal ceiling grid
399388 03/15/2017 441738 4 194 M Repair emergency lighting in electric room
399387 03/15/2017 441736 4 195 M Repair emergency lighting in generator room
399423 03/15/2017 441808 5 109 M Determine cause of water damaged ceiling tiles around fire sprinkler head and replace tiles
399425 03/15/2017 441812 5 118 M Determine cause of water damaged ceiling tiles and replace tiles
399426 03/15/2017 441814 5 118 M Replace burned electrical outlet on east wall below window
399427 03/15/2017 441816 5 118 M Spray and Eliminate nesting wasps in outside art patio
399389 03/15/2017 441740 6 101 M Repair drinking fountain at P.E. Paviliion
399375 03/15/2017 441712 1 125 O Eliminate multi outlet extension cord
399418 03/15/2017 441798 2 101 O Relocate wooden rack covering fire alarm pull station at exit door
399422 03/15/2017 441806 2 103A O Remove and prohibit hanging paper and decorations from ceiling located inside CCTV control room
399412 03/15/2017 441786 2 119 O Remove and prohibit hanging paper and decorations from ceiling
399398 03/15/2017 441758 2 210 O Remove and prohibit hanging paper and decorations from ceiling
399424 03/15/2017 441810 5 117C O Remove and prohibit storage blocking access to fire sprinkler riser
350885 03/15/2017 336089 00 0000 C Modify or improve drainage from covered walkway to prevent storm water from draining across sidewalk between buildings 1 and 2 (NA per Patrick Joyce. All drains are pointed away from sidewalk and there are no stains to cause slippery surface)
399377 03/15/2017 441716 1 192 MS Provide current inspection tag for fire extinguisher
399396 03/15/2017 441754 2 190 MS Provide current inspection tag for fire extinguisher
399395 03/15/2017 441752 2 192 MS Provide current inspection tag for fire extinguisher
399391 03/15/2017 441744 3 191 MS Provide current inspection tag for fire extinguisher
399421 03/15/2017 441804 2 101 OS Remove and prohibit candles located on table next to door into 2-102
399399 03/15/2017 441760 2 209 OS Remove storage to maintain clear 3' aisle to exit door
385239 11/15/2016 411225 1 192 M Make necessary repairs to fire sprinkler system as indicated on inspection report
385423 11/15/2016 411620 3 106 M Repair emergency lighting
385232 11/15/2016 411210 5 106 M Repair exhaust fan in bathroom
385220 03/22/2016 411184 00 0000 M Provide chain and lock on gate of fencing around fire main back flows at SW campus
385221 03/22/2016 411186 00 0000 M Paint building numbers on exterior walls of all buildings to be visible to fire rescue
385235 03/22/2016 411216 1 103 M Determine cause of water damaged ceiling tiles and replace tiles
385237 03/22/2016 411220 1 108 M Repair exhaust fan in bathroom
385238 03/22/2016 411222 1 123 M Determine cause of water damaged ceiling tiles and replace tiles
332060 03/22/2016 295477 2 0000 M Label fire department connection for building 2
385229 03/22/2016 411204 2 001 M Adjust door to exterior to latch properly
385241 03/22/2016 411229 2 004 M Adjust corridor door to stair 2-005 to latch properly
385228 03/22/2016 411202 2 101 M Adjust west door to exterior to latch properly
385222 03/22/2016 411188 2 108A M Repair exhaust fan in bathroom
385223 03/22/2016 411190 2 108B M Repair exhaust fan in bathroom
385226 03/22/2016 411196 2 111A M Repair exhaust fan in bathroom
385224 03/22/2016 411192 2 119A M Secure sink to wall
385225 03/22/2016 411194 2 119A M Repair exhaust fan in bathroom
385458 03/22/2016 411697 2 182 M Finish raw wood door
385240 03/22/2016 411227 2 191 M Replace screws for covers of electrical panels
385452 03/22/2016 411685 2 197 M Replace missing screws for covers of electrical panels
385456 03/22/2016 411693 2 209A M Secure sink to wall
385419 03/22/2016 411612 3 0000 M Provide covers for open boxes in ground NW of 3-191. Perhaps use aluminum diamond plate
385420 03/22/2016 411614 3 102 M Adjust door to exterior to latch properly
385448 03/22/2016 411675 3 103 M Repair emergency lighting or remove it. 3 emergency fixtures in room
385444 03/22/2016 411667 3 104 M Anchor shelving to wall
385445 03/22/2016 411669 3 104 M Repair emergency lighting
385443 03/22/2016 411665 3 111 M Replace missing window blinds
385425 03/22/2016 411625 3 111 M Oil hinges of door to exterior. Teacher complained of squeaky hinge
385426 03/22/2016 411627 3 111A M Provide escutcheon on wall for toilet supply line
385450 03/22/2016 411680 3 113A M Secure loose ceramic base tile and grout tile
385424 03/22/2016 411622 3 114 M Repair emergency lighting
385427 03/22/2016 411629 3 114A M Refinish unfinished wall in bathroom to provide impervious wall finish
385428 03/22/2016 411631 3 192 M Replace missing ceiling tiles
385418 03/22/2016 411610 3 193 M Adjust door to exterior to latch properly
385234 03/22/2016 411214 4 105 M Adjust Stage door to exterior to latch properly
385440 03/22/2016 411657 4 108 M Secure handicapped sink to wall
385244 03/22/2016 411236 4 110 M Adjust NW doors to exterior to latch properly
385439 03/22/2016 411655 4 112B M Replace missing escutcheon on fire sprinkler head
385435 03/22/2016 411645 4 112D M Provide protective cage around fire sprinkler head
385437 03/22/2016 411651 4 112D M Adjust door to walk-in freezer in Kitchen to latch properly
385438 03/22/2016 411653 4 112E M Adjust door to walk-in cooler in Kitchen to latch properly
385441 03/22/2016 411659 4 119 M Fire sprinkler plumbing is rusting at 90 and rusty drip marks on floor. Repair
385442 03/22/2016 411661 4 119 M Provide sign, not just calculation sheet, indicating how many machines can be charged in room
385432 03/22/2016 411639 4 194 M Replace missing screws for covers of panels 4L and 4D
385431 03/22/2016 411637 4 196 M Repair leaking union on north unit
385227 03/22/2016 411200 5 104A M Anchor toilet to floor
385231 03/22/2016 411208 5 111A M Secure loose faucet
385230 03/22/2016 411206 5 114A M Anchor toilet to floor
385233 03/22/2016 411212 5 192 M Provide missing screws for cover of panel 5HLS
385433 03/22/2016 411641 6 102 M Repair exhaust fan in bathroom
385434 03/22/2016 411643 6 102 M Anchor toilet to floor
385455 03/22/2016 411691 00 0000 O Someone is blocking open doors with a block or stick between the hinges and door frame. This will damage the hinges, door and frame. Temporarily block open door with a wedge between the floor and the bottom of the door
385243 03/22/2016 411234 2 122 O Remove and prohibit paper covering window in door. Acceptable for emergency Code situation only
385457 03/22/2016 411695 2 211 O Remove and prohibit attaching paper to blinds. Paper can be attached to wall or on string lines close to wall or in front of windows
385447 03/22/2016 411673 3 103 O Remove and prohibit paper covering window in door. Acceptable for Emergency Code situations only
385446 03/22/2016 411671 3 191 O Anchor Blonder Tongue amp to wall. Currently jammed into open cabinet
385429 03/22/2016 411633 4 121 O Replace bulbs in light fixtures
385430 03/22/2016 411635 4 184 O Maintain clear access to emergency eye wash - shower
385236 03/22/2016 411218 1 190 MS Provide current inspection tag for fire extinguisher and recharge extinguisher
385451 03/22/2016 411682 2 008 MS Adjust fire door in 2nd floor corridor at stair 2-001 to latch properly
385453 03/22/2016 411687 2 197 MS Provide current inspection tag for fire extinguisher
385454 03/22/2016 411689 2 210 MS Adjust corridor door to latch properly
385242 03/22/2016 411231 2 103 OS Maintain clear aisle to exit to exterior. Book cart/rack at door
385449 03/22/2016 411678 3 190 OS Remove old light tubes stored in mechanical room
350881 11/19/2015 336080 00 0000 M Provide fencing around fire main backflows at SW campus adjacent to perimeter fence
350839 11/19/2015 335995 2 115A M Repair exhaust fan in bathroom
357096 11/19/2015 350158 2 191 M Label walls as 2 hour fire and smoke barrier
350843 11/19/2015 336003 00 0000 O Indicate primary and secondary evacuation routes on all evacuation maps in classrooms
350887 11/19/2015 336093 4 0000 C Modify or improve drainage to prevent storm water from running across sidewalk adjacent to 4-113
350890 03/09/2015 336099 00 0000 M Repair or replace damaged door on east wall of chiller compound
372523 03/09/2015 383647 1 0000 M Determine cause of water damaged ceiling tiles and replace tiles in corridor at 1-102 and 1-105
372563 03/09/2015 383728 1 101 M Make repairs as noted on fire alarm report
372524 03/09/2015 383649 2 103A M Properly contain wires protruding out of ceiling grid
372534 03/09/2015 383669 2 207 M Adjust door closer to control speed of closing door
372549 03/09/2015 383699 3 004 M Repair emergency lighting adjacent to 3-117
372539 03/09/2015 383679 3 103 M Repair emergency lighting
372536 03/09/2015 383673 3 103C M Determine cause of water damaged ceiling tiles and replace tiles at west wall
372540 03/09/2015 383681 3 104 M Repair exterior door to open and close properly
372541 03/09/2015 383683 3 111 M Repair exterior door to close and latch properly
372544 03/09/2015 383689 3 113A M Anchor toilet to floor
372546 03/09/2015 383693 3 114 M Adjust door closer on exterior door to control speed of closing door
372547 03/09/2015 383695 3 114 M Repair deteriorated wall finish at exterior door
372551 03/09/2015 383703 4 102 M Repair hole in east wall finish
372553 03/09/2015 383707 4 110 M Replace missing base on wall at serving line doors
372552 03/09/2015 383705 4 9599 M Repair broken concrete at seam adjacent to 4-110 SE exterior door
372560 03/09/2015 383722 5 103B M Adjust door closer to control speed of closing door
372558 03/09/2015 383718 5 108 M Secure loose escutcheon on fire sprinkler head
372556 03/09/2015 383714 5 113 M Adjust door closer to control speed of closing door
372561 03/09/2015 383724 5 190 M Repair or replace rusty areas of duct at AHU 5-2, adjacent to RF 5-2
372550 03/09/2015 383701 6 102 M Anchor toilet to floor
372538 03/09/2015 383677 Chillers 0000 M Replace missing cover and insulation for chilled water line at pump 1. Secure protective grates on chillers
372562 03/09/2015 383726 1 115 O Remove and prohibit air freshener
372527 03/09/2015 383655 2 102 O Prohibit brown 13A extension cord on shelf above microwave or replace with 15A single outlet extension cord
372526 03/09/2015 383653 2 103 O Remove and prohibit use of flammable (red) plastic sheets on tables
372528 03/09/2015 383657 2 109 O Remove and prohibit air freshener
372529 03/09/2015 383659 2 116 O Provide clear floor space on the lock side of door
372530 03/09/2015 383661 2 118 O Provide clear floor space on the lock side of door
372531 03/09/2015 383663 2 120 O Provide clear floor space on the lock side of door
372535 03/09/2015 383671 2 207 O Prohibit plugging surge protector into surge protector
372533 03/09/2015 383667 2 210 O Provide clear floor space on the lock side of door
372532 03/09/2015 383665 2 215 O Remove and prohibit air freshener
372542 03/09/2015 383685 3 113 O Provide clear floor space on the lock side of door
372543 03/09/2015 383687 3 113 O Remove and prohibit excessive paper hanging on walls, maximum coverage is 20 percent of each wall in a building without fire sprinklers
357117 03/09/2015 350200 3 113 O Relocate cabinet to allow clear view of 3-113A sign
372557 03/09/2015 383716 5 113 O Remove and prohibit hanging anchor charts hanging from ceiling
372555 03/09/2015 383712 5 114 O Remove and prohibit flammable (green) plastic sheets hanging on shelves at sink area
350848 03/09/2015 336013 2 191 MS Seal penetration in enclosure ceiling where refrigerant lines go through to prevent spread of fire or smoke
372537 03/09/2015 383675 3 190 MS Recharge fire extinguisher
372554 03/09/2015 383710 4 112 MS Provide current inspection tag for type K fire extinguisher adjacent to 4-112E
372559 03/09/2015 383720 5 192 MS Provide current inspection tag for fire extinguisher
372525 03/09/2015 383651 2 103 OS Maintain clear aisle to exit
372545 03/09/2015 383691 3 113 OS Maintain clear aisle to exit
372548 03/09/2015 383697 3 115 OS Maintain clear aisle to exit
350835 11/22/2014 335987 2 108A M Repair exhaust fan in bathroom
350836 11/22/2014 335989 2 108B M Repair exhaust fan in bathroom
350838 11/22/2014 335993 2 112A M Repair exhaust fan in bathroom
350831 11/22/2014 335979 2 114A M Repair exhaust fan in bathroom
350833 11/22/2014 335983 2 118A M Repair exhaust fan in bathroom
350840 11/22/2014 335997 2 119A M Repair exhaust fan in bathroom
350834 11/22/2014 335985 2 120A M Repair exhaust fan in bathroom
350832 11/22/2014 335981 2 121A M Repair exhaust fan in bathroom
350888 11/22/2014 336095 3 0000 M Remove tree growing on covered walkway adjacent to 3-118
350928 11/22/2014 336180 3 0000 M Seal cracks in south exterior wall
357120 11/22/2014 350208 3 115 M Repair emergency lighting
350892 11/22/2014 336103 3 111 OS Maintain clear aisle to rear exit
356988 03/14/2014 349916 00 0000 M Repair damaged chain link fencing at bike rack
357123 03/14/2014 350214 00 0000 M Repair surface areas of play court which are damaged and cracked
357097 03/14/2014 350160 00 0000 M Provide 3210 padlocks for 2 PIV at parking area NW of main office
357110 03/14/2014 350186 00 0000 M Provide 3210 padlock for PIV south of 4-110
350830 03/14/2014 335977 00 0000 M Eliminate red ants in play fields, see Coach if necessary
357131 03/14/2014 350231 1 0000 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to 1-190
357130 03/14/2014 350229 1 114 M Adjust door closer on exterior door to control speed of closing door
357094 03/14/2014 350150 2 002 M Repair damaged wall and replace missing base on wall at entrance to media center
357089 03/14/2014 350140 2 004 M Repair hole in wall adjacent to 2-122
350868 03/14/2014 336054 2 103 M Adjust door to exterior to latch properly
357095 03/14/2014 350152 2 107 M Repair door to close and latch
357088 03/14/2014 350138 2 182 M Repair door to close and latch properly
357092 03/14/2014 350146 2 194 M Secure loose base on wall
357078 03/14/2014 350117 2 206A M Replace broken toilet seat
357085 03/14/2014 350131 2 211 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to window in corner of room
357086 03/14/2014 350134 2 213 M Secure cover on light fixture adjacent to cabinets
357087 03/14/2014 350136 2 216 M Secure cover on light fixture adjacent to 2-012
357121 03/14/2014 350210 3 002 M Refinish peeling paint on walls at 3-117
357113 03/14/2014 350192 3 002 M Repair emergency lighting adjacent to 3-108
357112 03/14/2014 350190 3 103 M Determine cause of water damaged ceiling tiles and replace tiles
357111 03/14/2014 350188 3 103A M Repair loose base on north wall
350921 03/14/2014 336166 3 103C M Determine cause of water damaged ceiling tiles and replace tiles
350909 03/14/2014 336142 3 106 M Repair emergency lighting
357114 03/14/2014 350194 3 110 M Repair emergency lighting (x2)
357115 03/14/2014 350196 3 111 M Repair emergency lighting
350858 03/14/2014 336034 3 112A M Patch hole in wall
357118 03/14/2014 350202 3 113 M Repair emergency lighting
350852 03/14/2014 336022 3 115 M Repair emergency lighting
357122 03/14/2014 350212 3 117 M Repair door to close and latch properly
357102 03/14/2014 350170 4 104 M Repair, secure damaged trim piece on door
357101 03/14/2014 350168 4 106 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to window
357104 03/14/2014 350174 4 110 M Repair damaged concrete patch at SE exterior door adjacent to 4-192
357099 03/14/2014 350164 4 110 M Adjust door closer on NW door to control speed of closing door
357100 03/14/2014 350166 4 110 M Adjust door closers on North exterior doors ( 2 sets) to control speed of closing doors
357106 03/14/2014 350178 4 112 M Replace damaged floor tile at 4-120
357105 03/14/2014 350176 4 112A M Repair damaged wall at light switch
350903 03/14/2014 336127 4 112E M Replace missing escutcheon on fire sprinkler head
357103 03/14/2014 350172 4 180 M Repair hole in wall
357107 03/14/2014 350180 4 184 M Repair deteriorated wall finish at eye wash drain
357108 03/14/2014 350182 4 184 M Provide adequate drainage for eye wash
357109 03/14/2014 350184 4 184 M Replace missing base on wall
357127 03/14/2014 350223 5 102 M Adjust door closer to control speed of closing door
357129 03/14/2014 350227 5 190 M Replace missing cover on unit RF-5-1
357098 03/14/2014 350162 2 101 O Prohibit plugging surge protector into surge protector at computers
357093 03/14/2014 350148 2 112 O Provide clear floor space on the lock side of door
357090 03/14/2014 350142 2 118 O Provide clear floor space on the lock side of door
357091 03/14/2014 350144 2 121 O Prohibit use of flammable plastic table skirts
356990 03/14/2014 349920 2 205 O Remove and prohibit paper covering window in door
356989 03/14/2014 349918 2 206 O Remove and prohibit paper covering window in door
356991 03/14/2014 349922 2 207 O Prohibit plugging surge protector into surge protector
350849 03/14/2014 336015 2 208 O Remove and prohibit hanging paper on blinds
357079 03/14/2014 350119 2 210 O Prohibit hanging papers on window blinds
357083 03/14/2014 350127 2 211 O Provide clear floor space on the lock side of door
357084 03/14/2014 350129 2 211 O Remove and prohibit use of damaged beanbag chair
357082 03/14/2014 350125 2 214 O Prohibit hanging papers on window blinds
357081 03/14/2014 350123 2 216A O Remove and prohibit air freshener
357116 03/14/2014 350198 3 111 O Prohibit white 13A extension cord at projector or replace with minimum 15A cord
350860 03/14/2014 336038 3 112 O Relocate string lines to hang no more than 2 inches from wall
357119 03/14/2014 350206 3 113 O Relocate string line to hang no more than 2 inches from wall
350914 03/14/2014 336152 3 113 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
357128 03/14/2014 350225 5 101 O Prohibit plugging orange extension cord into surge protector
357126 03/14/2014 350221 5 108 O Remove and prohibit use of (flammable) red plastic table covering
357125 03/14/2014 350219 5 111 O Remove and prohibit paper covering window in door
357124 03/14/2014 350217 5 117 O Replace missing sign indicating primary and secondary evacuation routes
350844 03/14/2014 336005 2 193 MS Label walls as 2 hour fire and smoke barrier
332047 03/14/2014 295450 2 196 MS Provide current inspection tags for fire sprinkler systems (current tags marked quarterly with inspected date of 5-23-11)
357080 03/14/2014 350121 2 196 MS Recharge fire extinguisher
350862 03/14/2014 336042 2 197 MS Label walls as 2 hour fire and smoke barrier
357132 03/14/2014 350233 1 0000 OS Re-word sign on exterior exit door adjacent to 1-123 to read Emergency Exit Only
350916 03/14/2014 336156 3 113 OS Maintain clear aisle to rear exit
350855 10/23/2013 336028 00 0000 M Provide lock on gate of fencing around transformer enclosure west of building 6. Chain is there on fence
350931 10/23/2013 336186 2 213A M Repair toilet to flush
350912 10/23/2013 336148 3 109 M Repair emergency lighting
350859 10/23/2013 336036 3 112 M Repair emergency lighting
350917 10/23/2013 336158 3 113A M Repair exhaust fan in bathroom
350894 10/23/2013 336107 3 114 M Repair emergency lighting x 2
350872 10/23/2013 336062 4 107A M Secure loose handicapped grabrail
332064 10/23/2013 295485 4 112 M Provide current state inspection tag for kitchen steamer (NA, changed to boiler less system per email from Stacey Marshall 8/2013)
299146 10/23/2013 223197 4 112D M Repair walk in freezer door to close properly
350919 10/23/2013 336162 2 114 O Remove and prohibit hanging paper on blinds
350845 10/23/2013 336007 2 121 O Remove and prohibit hanging paper on blinds
350908 10/23/2013 336140 3 110 O Remove and prohibit hanging plastic sheets from ceiling
350913 10/23/2013 336150 3 113 O Remove and prohibit excessive flammable decorations. Maximum of 20 percent of total wall can be covered with paper. Remove and prohibit hanging string lines from ceiling
270172 10/23/2013 160966 2 194 C Provide additional fire sprinkler head to provide coverage on both sides of communication equipment
350930 10/23/2013 336184 2 005 MS Adjust fire door at top of stairs to latch properly
350901 10/23/2013 336122 4 116 MS Replace painted fire sprinkler head
350871 10/23/2013 336060 4 191 MS Label walls as 2 hour fire and smoke barrier
350925 10/23/2013 336174 3 104A OS Prohibit storage of gas powered equipment
350891 10/23/2013 336101 3 112 OS Maintain clear aisle to rear exit
350854 10/23/2013 336026 4 119 OS Prohibit storage of gas powered equipment
350898 10/23/2013 336115 4 194 OS Remove old light tubes stored in electrical room
350926 05/16/2013 336176 00 0000 M Secure loose inside handrail along ramp in interior courtyard and secure loose toe kick
270159 05/16/2013 160938 00 9599 M Secure chain link fence between 4-110 and 4-193 to bottom wire and regrade fill along area at bottom to prevent access to campus
350883 05/16/2013 336085 1 0000 M Repair hole in wall at floor level in interior corridor adjacent to 1-102 and 1-103
350867 05/16/2013 336052 1 113 M Determine cause of water damaged ceiling tiles and replace tiles
350884 05/16/2013 336087 2 004 M Replace missing escutcheon on fire sprinkler head in corridor adjacent to stair 2-001
350869 05/16/2013 336056 2 105 M Secure 2 loose grounds and 1 loose lug to ground bar
350837 05/16/2013 335991 2 106 M Repair exhaust fan in bathroom
350920 05/16/2013 336164 2 114 M Determine cause of water damaged ceiling tiles and replace tiles
350933 05/16/2013 336190 2 182 M Secure loose GFCI outlet
350863 05/16/2013 336044 2 196 M Repair leaking air handler
350857 05/16/2013 336032 2 201 M Repair leaking toilet supply line
350861 05/16/2013 336040 2 208A M Secure sink to wall
350856 05/16/2013 336030 2 213A M Repair leaking toilet supply line
350907 05/16/2013 336136 3 0000 M Repair emergency lighting in corridor adjacent to 3-112
350895 05/16/2013 336109 3 0000 M Close large gap under chain link fencing at kindergarten play ground at south end
350889 05/16/2013 336097 3 0000 M Replace cover for data box in grassed area adjacent to sidewalk outside of 3-103
350922 05/16/2013 336168 3 102 M Adjust rear door to latch properly
350923 05/16/2013 336170 3 103 M Adjust rear door to latch properly
350924 05/16/2013 336172 3 103 M Repair emergency eye wash - shower, low flow
350851 05/16/2013 336019 3 107 M Repair leaking toilet supply line
350911 05/16/2013 336146 3 109 M Repair power pole that is coming apart
350910 05/16/2013 336144 3 109A M Anchor toilet to floor
350853 05/16/2013 336024 3 111 M Eliminate insect infestation
350915 05/16/2013 336154 3 113 M Repair emergency lighting
350927 05/16/2013 336178 3 192 M Determine cause of water damaged ceiling tiles and replace tiles and replace missing tiles
350873 05/16/2013 336064 4 107A M Seal crack in corner of wall behind toilet
350874 05/16/2013 336066 4 107A M Make light switch plate flush to wall. Sharp corner is sticking out
350902 05/16/2013 336124 4 112B M Replace missing escutcheon on fire sprinkler head
350897 05/16/2013 336113 4 194 M Secure loose right lower ground to ground bar
350906 05/16/2013 336134 4 195 M Provide cord restraints on cords going into 2 transfer switches
350870 05/16/2013 336058 5 103A M Anchor toilet to floor
350880 05/16/2013 336078 5 105 M Exterminate ants in classroom
350878 05/16/2013 336074 5 107 M Anchor toilet to floor
350877 05/16/2013 336072 5 110A M Secure sink to wall
350876 05/16/2013 336070 5 113 M Repair or replace drinking fountain. Push button is loose and comes off. Also adjust flow, too low
350875 05/16/2013 336068 5 118 M Determine cause of water damaged ceiling tiles and replace tiles
350879 05/16/2013 336076 5 180 M Patch and refinish damaged wall
350829 05/16/2013 335972 00 0 O No access was available to 4-122. Please provide access to this room during the report review meeting
350865 05/16/2013 336048 1 108 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
350866 05/16/2013 336050 1 110B O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
350896 05/16/2013 336111 2 101 O Prohibit plugging surge protector into extension cord adjacent to 2-180
350841 05/16/2013 335999 2 113 O Remove and prohibit paper covering window in door
350918 05/16/2013 336160 2 116 O Remove and prohibit hanging paper on blinds
350846 05/16/2013 336009 2 118 O Remove and prohibit hanging paper on blinds
350842 05/16/2013 336001 2 119 O Remove and prohibit paper covering window in door
350847 05/16/2013 336011 2 120 O Remove and prohibit hanging paper on blinds
350850 05/16/2013 336017 2 214 O Remove and prohibit paper covering window in door
350893 05/16/2013 336105 3 109 O Remove and prohibit paper covering window in door
350929 05/16/2013 336182 3 116A O Keep all fixture drains filled with water. Every 2 months pour 1 quart of water down all drains. Room used for storage
350900 05/16/2013 336119 4 115 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
350905 05/16/2013 336132 4 182 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
350904 05/16/2013 336130 4 184 O Maintain clear access to emergency eye wash - shower
350899 05/16/2013 336117 5 117 O Post sign indicating evacuation routes
350932 05/16/2013 336188 2 217 OS Prohibit hold open devices on corridor door
332063 03/01/2013 295482 4 112E M Repair walk-in cooler door to close and seal properly
332057 03/01/2013 295470 4 196 M Repair or replace leaking water heater
332065 03/01/2013 295487 4 112 MS Provide current inspection tag for kitchen hood fire suppression system (tag on suppression sytem is labeled October 2010)
332038 04/09/2012 295423 2 0000 M Check ventilation fans inside classroom bathrooms for proper operation (fans did not come on when switches were turned on)
332040 04/09/2012 295432 2 114 M Determine cause of water damaged ceiling tiles and replace tiles
332052 04/09/2012 295460 3 001 M Repair hole in wall in corridor adjacent to west exit doors
332054 04/09/2012 295464 3 002 M Repair emergency lighting in corridor adjacent to 3-112
332056 04/09/2012 295468 3 002 M Repair emergency lighting in corridor adjacent to south exit
332053 04/09/2012 295462 3 103C M Determine cause of water damaged ceiling tiles and replace tiles
332050 04/09/2012 295456 3 191 M Provide cover on exposed electrical junction box on south wall
332051 04/09/2012 295458 3 191 M Repair emergency lighting
332067 04/09/2012 295491 4 104 M Determine cause of water damaged ceiling tiles and replace tiles
332066 04/09/2012 295489 4 105 M Repair loose handrail along stage ramp
312489 04/09/2012 252416 4 105 M Provide dated flame resistance label on stage curtain (current label 6-16-04)
332058 04/09/2012 295472 4 195 M Provide certification that all student occupied spaces have emergency lights and all are operable
332046 04/09/2012 295443 2 001 O Remove or relocate door mat on outside of stairway exit doors to allow door to close properly (door gets caught on mat and will not close)
299163 04/09/2012 223233 2 101 O Prohibit plugging surge protector into surge protector @ computers
332041 04/09/2012 295434 2 114 O Remove and prohibit paper covering window in door
312421 04/09/2012 252275 2 115 O Remove and prohibit plastic (purple) curtains
312422 04/09/2012 252277 2 117 O Remove and prohibit plastic (black) curtains
332042 04/09/2012 295436 2 118 O Remove and prohibit paper covering window in door
332049 04/09/2012 295454 2 212 O Remove and prohibit paper covering window in door
332055 04/09/2012 295466 3 114 O Prohibit plugging surge protector into surge protector
332068 04/09/2012 295493 5 101 O Prohibit plugging surge protector into extension cord
332039 04/09/2012 295430 2 193 MS Recharge fire extinguisher
332061 04/09/2012 295480 4 191 MS Recharge fire extinguisher
332059 04/09/2012 295474 4 194 MS Recharge fire extinguisher
332043 04/09/2012 295438 2 0000 OS Prohibit hold open devices (wedges) on classroom corridor doors (doors were held open by wedges during time when class is being held)
332048 04/09/2012 295452 2 196 OS Remove storage from mechanical room (flammable cardboard boxes)
312429 02/23/2011 252293 00 0000 M Lubricate all fire department connections on campus (four locations) per M. Jackson, WPBFR
312407 02/23/2011 252239 00 0000 M Secure loose bottom rail on exterior stage guardrail
312426 02/23/2011 252285 1 117 M Determine cause of water damaged ceiling tiles and replace tiles
312442 02/23/2011 252318 2 180 M Anchor shelving to wall
312436 02/23/2011 252307 2 190 M Repair leaking air handler in mechanical room
312437 02/23/2011 252309 2 192 M Replace missing wrench from fire sprinkler spare heads box
312439 02/23/2011 252313 2 192 M Repair seal on bottom of door, rain water leaks into room
312447 02/23/2011 252329 3 002 M Repair emergency lighting in corridor
312477 02/23/2011 252391 3 103 M Repair emergency lighting
312466 02/23/2011 252370 3 106 M Repair emergency lighting
312467 02/23/2011 252373 3 109 M Repair emergency lighting
312464 02/23/2011 252365 3 110 M Repair emergency lighting
312462 02/23/2011 252362 3 111 M Repair emergency lighting
312460 02/23/2011 252355 3 113 M Repair emergency lighting
312451 02/23/2011 252337 3 114 M Repair emergency lighting
312450 02/23/2011 252334 3 115 M Repair emergency lighting
312487 02/23/2011 252412 4 118 M Determine cause of water damaged ceiling tiles and replace tiles
312478 02/23/2011 252395 4 121 M Replace missing lock on flammable storage cabinet(cabinet was removed)
312479 02/23/2011 252397 4 184 M Determine cause of water damaged ceiling tiles and replace tiles
312481 02/23/2011 252399 4 194 M Repair exterior door to close properly
312400 02/23/2011 252224 5 104B M Anchor shelving to wall
312403 02/23/2011 252231 5 117C M Replace missing fire sprinkler heads in spare heads box
312402 02/23/2011 252229 5 192 M Fill void in electrical panel 5L
312484 02/23/2011 252406 6 102 M Anchor toilet to floor
312483 02/23/2011 252403 6 104 M Replace missing ceiling tiles
312446 02/23/2011 252327 2 105 O No access was available to this room. Please be prepared to access this room during the report review meeting
312412 02/23/2011 252249 2 116 O Remove and prohibit plastic (dinosaur) sheet covering table adjacent to bathroom
312423 02/23/2011 252279 2 117 O Remove and prohibit air freshener
312424 02/23/2011 252281 2 121 O Provide minimum one foot blank wall space on lock side of door
312425 02/23/2011 252283 2 121 O Remove and prohibit plastic sheet covering table adjacent to bathroom
312409 02/23/2011 252243 2 204 O Remove and prohibit plastic sheets covering display boards
312410 02/23/2011 252245 2 206 O Remove and prohibit air freshener
299179 02/23/2011 223266 2 207 O Prohibit plugging surge protector into surge protector
312472 02/23/2011 252376 3 104 O Provide minimum one foot blank wall space on lock side of doors
312452 02/23/2011 252339 3 112 O Provide minimum one foot blank wall space on lock side of door
312461 02/23/2011 252360 3 113 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
312458 02/23/2011 252349 3 113 O Remove screw protruding from side of cabinet adjacent to corridor door
312491 02/23/2011 252421 4 105 O Prohibit wrapping extension cords around stage curtain scaffolding
312494 02/23/2011 252427 4 105 O Provide certification that stage lighting powered by extension cords is approved then provide safety cables for lights
312445 02/23/2011 252325 4 122 O No access was available to this room. Please be prepared to access this room during the report review meeting
312405 02/23/2011 252235 5 117C O Remove and prohibit flammable plastic sheets/table coverings
312406 02/23/2011 252237 5 118B O Prohibit storage on kiln
312488 02/23/2011 252414 4 105 C Provide records that stage rigging has been inspected and conforms to required safety standards
312443 02/23/2011 252321 1 192 MS Provide current inspection tag for fire sprinkler system
312413 02/23/2011 252251 2 004 MS Recharge fire extinguisher in corridor adjacent to 2-002 (elevator) corridor
312438 02/23/2011 252311 2 192 MS Provide current inspection tag for fire sprinkler system
312408 02/23/2011 252241 2 196 MS Provide current inspection tag for fire sprinkler system
312486 02/23/2011 252410 4 112 MS Provide current inspection tag for kitchen hood fire suppression system
312485 02/23/2011 252408 4 190 MS Provide current inspection tag for fire sprinkler system
312404 02/23/2011 252233 5 117C MS Provide current inspection tag for fire sprinkler system
312401 02/23/2011 252226 5 192 MS Provide current inspection tag for fire extinguisher
312411 02/23/2011 252247 2 0000 OS Prohibit hold open devices on fire doors (classroom doors)on 1st and 2nd floor
312440 02/23/2011 252315 2 102 OS Remove and prohibit candles
312475 02/23/2011 252386 3 104 OS Prohibit cord in front of exit door (exterior) to maintain clear aisle to exit
312453 02/23/2011 252341 3 112 OS Maintain clear aisle to exit doors
312454 02/23/2011 252343 3 112 OS Remove and prohibit candles
312448 02/23/2011 252332 3 115 OS Maintain clear aisle to (exterior) exit
312490 02/23/2011 252418 4 104 OS Remove and prohibit candles
312399 02/23/2011 252221 1 101 FS Make repairs as noted on fire alarm report
299145 09/14/2010 223195 4 112E M Repair walk in refrigerator door to close properly
296127 09/14/2010 216600 P 0000 C Provide covered walkway to portables
299143 09/14/2010 223190 3 118 OS Prohibit charging batteries in room
262837 09/14/2010 145255 P 9348 N/A No violations observed
262836 09/14/2010 145254 P 9349 N/A No violations observed
299151 02/19/2010 223207 00 0000 M Lubricate all fire department connections on campus (four locations)
299133 02/19/2010 223165 1 0000 M Fill gap around fire alarm pull station adjacent to SW exterior door and 1-117
299093 02/19/2010 223079 1 117 M Determine cause of water damaged ceiling tiles and replace tiles
299155 02/19/2010 223216 2 0000 M Repair exhaust fans in classroom bathrooms
299177 02/19/2010 223262 2 008 M Replace missing escutcheon on fire sprinkler head in corridor adjacent to 2-209
299172 02/19/2010 223252 2 010 M Repair door to restroom vestibule to open/close properly
299162 02/19/2010 223231 2 109 M Replace ceiling tile with hole in it
299161 02/19/2010 223229 2 112 M Replace ceiling tile with hole in it
299160 02/19/2010 223226 2 115 M Replace ceiling tile with hole in it
299158 02/19/2010 223222 2 119 M Replace ceiling tile with hole in it
299156 02/19/2010 223218 2 122 M Replace ceiling tile with hole in it
299169 02/19/2010 223246 2 203 M Replace ceiling tile with hole in it
299170 02/19/2010 223248 2 204 M Replace ceiling tile with hole in it
299168 02/19/2010 223244 2 204 M Replace missing escutcheon on fire sprinkler head
299171 02/19/2010 223250 2 206 M Replace ceiling tile with hole in it
299176 02/19/2010 223260 2 211 M Replace ceiling tile with hole in it
299174 02/19/2010 223256 2 214 M Provide cover for exposed electrical outlet adjacent to teacher's desk
299175 02/19/2010 223258 2 215 M Replace ceiling tile with hole in it
299106 02/19/2010 223107 3 002 M Repair emergency lighting in corridor adjacent to 3-110
299096 02/19/2010 223085 3 103B M Repair exhaust fan in bathroom
299097 02/19/2010 223087 3 106A M Replace cracked/broken ceiling tile
299134 02/19/2010 223167 3 107 M Seal gap around light fixture in restroom
299105 02/19/2010 223105 3 110 M Repair door to open/close properly
299109 02/19/2010 223113 3 111 M Repair emergency lighting
299140 02/19/2010 223182 3 112 M Repair emergency lighting
299139 02/19/2010 223180 3 113 M Anchor wooden shelving (ABCD letters on side)to wall, see teacher for location
299136 02/19/2010 223172 3 113 M Repair emergency lighting
299142 02/19/2010 223186 3 114 M Repair emergency lighting
299144 02/19/2010 223192 3 192 M Replace missing ceiling tiles
299147 02/19/2010 223199 4 102 M Repair light fixture, lights do not work
299183 02/19/2010 223275 5 103A M Repair exhaust fan in bathroom
299182 02/19/2010 223273 5 113A M Repair exhaust fan in bathroom
299180 02/19/2010 223269 5 118 M Secure escutcheon on fire sprinkler head
299153 02/19/2010 223211 P 9348 M Determine cause of water damaged ceiling tiles and replace tiles
299154 02/19/2010 223213 P 9349 M Repair emergency lighting
299091 02/19/2010 223074 1 107 O Relocate storage to keep area within 18" of fire sprinkler heads clear
299164 02/19/2010 223235 2 101 O Prohibit black multi outlet extension cord (@computers near clock) or replace with minimum 15A cord. Prohibit plugging surge protector into extension cord
299166 02/19/2010 223239 2 102 O Prohibit brown 13A extension cord or replace with minimum 15A cord
299167 02/19/2010 223241 2 102 O Remove and prohibit air freshener
299141 02/19/2010 223184 3 112 O Prohibit brown 13A extension cord or replace with minimum 15A cord
299184 02/19/2010 223277 5 104 O Remove and prohibit combustible beanbag chairs
270176 02/19/2010 160974 3 0000 C Modify gate at south end of 3-002 to allow egress at all times and remove chain and padlock
270186 02/19/2010 160994 4 121 C Relocate light switch for flammable storage room out of fenced enclosure for kitchen refrigeration units
299165 02/19/2010 223237 2 192 MS Provide current inspection tag for fire sprinkler system
278176 02/19/2010 178347 2 195 MS Seal penetration around conduit in floor
299178 02/19/2010 223264 2 196 MS Provide current inspection tag for fire sprinkler system
299152 02/19/2010 223209 4 190 MS Provide current inspection tag for fire sprinkler system
299150 02/19/2010 223205 4 194 MS Seal penetration around conduit on east wall to prevent the spread of fire or smoke
299159 02/19/2010 223224 2 116 OS Remove and prohibit candles
299157 02/19/2010 223220 2 118 OS Remove and prohibit use of space heater
299173 02/19/2010 223254 2 212 OS Maintain clear aisle to exit
299107 02/19/2010 223109 3 111 OS Prohibit hold open devices on fire door
299135 02/19/2010 223170 3 111 OS Maintain clear aisle to exit doors
299137 02/19/2010 223176 3 111A OS Prohibit storage in restroom to maintain clear aisle to exit
299138 02/19/2010 223178 3 113 OS Prohibit storage in restroom to maintain clear aisle to exit
299108 02/19/2010 223111 3 113 OS Prohibit hold open devices on fire door
299094 02/19/2010 223081 3 191 OS Remove storage from electrical room
299148 02/19/2010 223201 4 102 OS Prohibit charging batteries in room
299149 02/19/2010 223203 4 110 OS Relocate plant to provide clear access to fire extinguisher adjacent to 4-102
299181 02/19/2010 223271 5 118 OS Provide clear access to fire extinguisher adjacent to kiln room
296112 09/01/2009 216569 2 107 M Repair deteriorated wall finish on east wall
296123 09/01/2009 216591 2 109 M Repair peeling paint finish on wall at teachers desk
278115 09/01/2009 178227 4 112D M Replace damaged seal on bottom of freezer door, water from cleaning the floors gets in the freezer
278126 04/22/2009 178245 00 0000 M FDC's throughout campus need to be greased. They do not swivel as designed to and will prevent proper use by fire department, per M. Jackson, WPBFR
270237 04/22/2009 161100 00 9599 M Keep gates to retention pond adjacent to bus loop locked
296113 04/22/2009 216571 2 004 M Replace battery in lighted exit sign in lobby @ elevator
270168 04/22/2009 160957 2 101 M Replace missing signage for courtyard doors indicating room name and number at appropriate height with raised and Braille characters
296114 04/22/2009 216573 2 170 M Provide current inspection tag for elevator (Tag expired August, 08)
296115 04/22/2009 216575 2 171 M Provide cover on exposed electrical junction box
296125 04/22/2009 216595 2 196 M Replace missing spare sprinkler heads box with one containing extra fire sprinkler heads and wrench
296128 04/22/2009 216602 3 117 M Repair emergency lighting
296117 04/22/2009 216579 4 104 M Determine cause of water damaged ceiling tiles and replace tiles
296121 04/22/2009 216587 5 109 M Determine cause of water damaged ceiling tiles and replace tiles
296119 04/22/2009 216583 P 9349 O Provide clear access to electrical panel
296110 04/22/2009 216565 00 0000 C Provide exterior signage indicating property address
296111 04/22/2009 216567 00 0000 MS Provide current inspection tags for fire extinguishers throughout campus
296126 04/22/2009 216598 2 207 MS Repair door hardware to allow door to latch properly
296116 04/22/2009 216577 1 192 OS Remove storage from mechanical room
296124 04/22/2009 216593 2 194 OS Remove storage from telecommuncations room
296120 04/22/2009 216585 4 190 OS Remove storage from mechanical room
296118 04/22/2009 216581 4 194 OS Remove storage from electrical room
296122 04/22/2009 216589 5 192 OS Remove storage from electrical room
278143 01/28/2009 178284 2 111A M Replace painted fire sprinkler head
278148 01/28/2009 178287 2 113A M Verify damaged fire sprinkler head. If head is dusty it can be cleaned or if damage is paint then head needs to be replaced
270169 01/28/2009 160960 2 116A M Adjust fire sprinkler head to project a minimum 1" below escutcheon
278214 01/28/2009 178431 2 213A M Replace painted fire sprinkler head
278213 01/28/2009 178429 2 215A M Replace painted fire sprinkler head
278285 01/28/2009 178585 1 101 FS Provide current inspection tag for fire alarm panel
270161 03/26/2008 160943 00 9599 M Repair or replace inoperable padlock on PIV south of Building 4
270166 03/26/2008 160953 2 001 M Replace sign at top of stair indicating Exit with raised and braille characters
278278 03/26/2008 178569 2 001 M Replace missing signage at courtyard door indicating room name and number at appropriate height with raised and Braille characters
278279 03/26/2008 178573 2 005 M Replace missing signage at courtyard door indicating room name and number at appropriate height with raised and Braille characters
270167 03/26/2008 160955 2 005 M Replace sign at top of stair indicating Exit with sign with raised and Braille characters
278132 03/26/2008 178264 2 107 M Repair door to close properly
278273 03/26/2008 178559 3 0000 M Repair emergency lighting at west corridor adjacent to 3-108
278221 03/26/2008 178446 3 109 M Repair emergency lighting
278220 03/26/2008 178444 3 110 M Repair emergency lighting
278215 03/26/2008 178434 3 112 M Repair emergency lighting
278218 03/26/2008 178440 3 113 M Provide electrical outlet in ceiling adjacent to projector to eliminate need for extension cord in ceiling
278212 03/26/2008 178427 3 114 M Repair emergency lighting
278210 03/26/2008 178423 3 115 M Position ceiling tiles into place
278211 03/26/2008 178425 3 116 M Repair emergency lighting
278186 03/26/2008 178371 3 192 M Position ceiling tiles into place
278184 03/26/2008 178367 4 106 M Determine cause of water damaged ceiling tiles and replace tiles
278185 03/26/2008 178369 4 110 M Repair fire extinguisher cabinet to open, adjacent to NW cafeteria doors across from 4-106
278116 03/26/2008 178229 4 110 M Replace missing magnetic release hold open device for fire door at serving line
278122 03/26/2008 178242 4 184 M Determine cause of water damaged ceiling tiles and replace tiles
278178 03/26/2008 178355 5 109 M Mount fire extinguisher at maximum five feet above floor
278182 03/26/2008 178363 P 9349 M Repair emergency lighting
278183 03/26/2008 178365 P 9349 M Adjust door closer to control speed of closing door (east door)
278280 03/26/2008 178575 1 116 O Prohibit multi outlet electrical adaptor
278131 03/26/2008 178254 2 101 O Prohibit plugging surge protector into black multi outlet extension cord @ computers. Plug surge protector directly into permanent outlet, use minimum 15A single outlet extension cord for other applications
278149 03/26/2008 178298 2 115 O Remove and prohibit air freshener
278216 03/26/2008 178436 3 112 O Prohibit brown 13A extension cord or replace with minimum 15A cord
278217 03/26/2008 178438 3 113 O Prohibit plugging orange extension cord into surge protector, plug each directly into permanent outlet. Prohibit running orange extension cord into ceiling
278173 03/26/2008 178342 5 104B O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
278180 03/26/2008 178359 5 114 O Mount sign indicating evacuation routes
270224 03/26/2008 161073 2 191 MS Remove paper from heat detector, leftover from painting
278276 03/26/2008 178566 3 190 MS Repair door lock to open properly
278119 03/26/2008 178237 4 112 MS Provide current inspection tag for type "K" fire extinguisher
278135 03/26/2008 178267 2 103 OS Remove and prohibit use of George Foreman Grill
270223 03/26/2008 161071 2 190 OS Remove storage from mechanical room
278219 03/26/2008 178442 3 111 OS Relocate flag to provide clear view of fire alarm strobe/horn
278209 03/26/2008 178421 3 115 OS Maintain clear aisle to exterior exit door
270240 03/26/2008 161106 3 118 OS Prohibit storage of flammable materials (paint)
270195 03/26/2008 161013 4 102 OS Prohibit charging batteries in room
270201 03/26/2008 161026 4 119 OS Prohibit storage of flammable materials (paint)
270244 03/26/2008 161114 5 192 OS Prohibit charging batteries in room
278181 03/26/2008 178361 5 118 CS Provide fire extinguisher for kiln room
270225 11/27/2007 161075 00 0000 M Secure bottom rail to handrails at outside stage
270209 11/27/2007 161043 P 9349 OS Keep areas to exit doors clear
270193 05/14/2007 161009 1 0000 CS Provide keys for knox box contact Mike Wennergren,WPB Fire Rescue @ 561-807-4756 to install keys in box (May 14th, 2007, Odell French, Roosevelt ES confirmed that WBP installed Keys in Knox Box)
270245 05/03/2007 161116 00 8087 M Remove exit signs (X2 store bought) leftover from construction directing traffic into courtyard instead of out double doors to parking lot
270158 05/03/2007 160935 00 9599 M Lower lid of water valve box outside 3-190 to be level with sidewalk
270160 05/03/2007 160940 00 9599 M Provide padlock on gate of fence enclosure for FPL transformer behind 4-193
270162 05/03/2007 160945 1 110 M Secure loose emergency eye wash
270246 05/03/2007 161118 1 112 M Determine cause of water damaged ceiling tiles and replace tiles
270163 05/03/2007 160947 1 119 M Verify electrical strip adjacent to sink is on GFCI circuit and label strip or provide GFCI circuit
270211 05/03/2007 161047 2 105 M Secure loose ceiling tile
270213 05/03/2007 161051 2 112 M Determine cause of water damaged ceiling tiles and replace tiles
270177 05/03/2007 160976 3 0000 M Repair damaged finish on columns at north entrance
270228 05/03/2007 161082 3 103 M Remove expired fire extinguisher
270178 05/03/2007 160978 3 109 M Repair emergency lighting
270179 05/03/2007 160980 3 110 M Repair emergency lighting
270218 05/03/2007 161061 3 110A M Replace missing sign indicating room name and number at appropriate height with raised and Braille characters. Sign located in room 2-120 stuck to counter top adjacent to sink
270180 05/03/2007 160982 3 111 M Repair emergency lighting
270181 05/03/2007 160984 3 112 M Repair emergency lighting
270182 05/03/2007 160986 3 112 M Remove out of date fire extinguisher adjacent to sink
270234 05/03/2007 161094 3 112 M Trim palm frond located outside of 3-112, palm frond hangs in front of exterior door
270183 05/03/2007 160988 3 116 M Repair emergency lighting
270184 05/03/2007 160990 3 192 M Replace missing ceiling tiles
270185 05/03/2007 160992 4 0000 M Provide padlock for gate for fence enclosure for refrigeration units behind kitchen
270196 05/03/2007 161015 4 110 M Repair deteriorated wall finish adjacent to serving line entrance and 4-122
270197 05/03/2007 161017 4 112B M Connect exhaust vent for dryer
270238 05/03/2007 161102 4 184 M Repair inoperable dryer
270239 05/03/2007 161104 4 184 M Repair smashed exterior dryer vent cover located on east wall outside 4-184
270202 05/03/2007 161028 4 195 M Provide (log book)certification that emergency generator is operable
270242 05/03/2007 161110 5 0000 M Adjust escutcheon on fire sprinkler head in corridor adjacent to 5-112
270190 05/03/2007 161002 5 118B M Provide or verify exhaust fan in kiln room works, timer in room does not activate a fan
270191 05/03/2007 161005 P 9349 M Fill pipe trench at fence enclosure east of P-25
270192 05/03/2007 161007 P 9349 M Repair gate in fence enclosure southeast of P-25, gate will not close preventing padlock from locking properly
270212 05/03/2007 161049 2 101 O Prohibit black multi outlet extension cord @ computers. Replace with surge protector plugged directly into a wall outlet
270214 05/03/2007 161053 2 116 O Prohibit white 13A extension cord or replace with minimum 15A cord
270215 05/03/2007 161055 2 116 O Remove and prohibit air freshener
270216 05/03/2007 161057 2 118 O Remove and prohibit combustible beanbag chairs (X2)
270219 05/03/2007 161063 2 122 O Prohibit brown 13A extension cord or replace with minimum 15A cord
270222 05/03/2007 161069 2 207 O Prohibit plugging surge protector into surge protector, plug each directly into a wall outlet
270221 05/03/2007 161067 2 212 O Remove and prohibit air freshener
270220 05/03/2007 161065 2 213A O Remove and prohibit air freshener
270227 05/03/2007 161080 3 0000 O Post signs indicating primary and secondary evacuation routes
270231 05/03/2007 161088 3 110 O Prohibit plugging microwave into surge protector, plug microwave directly into a wall outlet
270232 05/03/2007 161090 3 113 O Prohibit black multi outlet extension cord or replace with minimum 15A single outlet cord
270194 05/03/2007 161011 4 104 O Maintain storage room in an orderly manner ( to allow access to room, door would not fully open due to contents)
270198 05/03/2007 161019 4 184 O Prohibit storage of golf cart
270241 05/03/2007 161108 5 117 O Prohibit plugging surge protector into surge protector, plug each directly into a wall outlet
270203 05/03/2007 161030 P 9348 O Remove and prohibit air fresheners
270206 05/03/2007 161037 P 9348 O Remove and prohibit paper covering windows in doors
270207 05/03/2007 161039 P 9348 O Prohibit 13A extension cord or replace with minumum 15A cord
270208 05/03/2007 161041 P 9349 O Repair emergency lighting
270165 05/03/2007 160951 2 0000 C Indicate secondary means of exiting from each classroom on evacuation signs
270188 05/03/2007 160998 5 0000 C Indicate secondary means of exiting for each classroom on evacuation signs
270170 05/03/2007 160962 2 171 F Secure heat detector which is hanging by its wires
270164 05/03/2007 160949 1 192 MS Provide current inspection tag for fire sprinkler riser
270171 05/03/2007 160964 2 192 MS Provide current inspection tag for fire sprinkler riser
270173 05/03/2007 160968 2 196 MS Provide current inspection tag for fire sprinkler riser
270187 05/03/2007 160996 4 190 MS Provide current inspection tag for fire sprinkler riser
270189 05/03/2007 161000 5 117C MS Provide current inspection tag for fire sprinkler riser
270217 05/03/2007 161059 2 120 OS Remove and prohibit candle
270229 05/03/2007 161084 3 103 OS Keep area clear to exterior exit door
270233 05/03/2007 161092 3 112 OS Keep area clear to exterior exit door
270236 05/03/2007 161098 3 114 OS Keep area clear to exterior exit door
270235 05/03/2007 161096 3 116 OS Keep area clear to exterior exit door
270230 05/03/2007 161086 3 190 OS Remove storage from mechanical room
270200 05/03/2007 161023 4 112 OS Provide clear access to Ansul pull station (for kitchen suppresion system)
270199 05/03/2007 161021 4 184 OS Prohibit charging batteries in room
270243 05/03/2007 161112 5 192 OS Remove storage from electrical room
270204 05/03/2007 161032 P 9348 OS Remove and prohibit candles
270205 05/03/2007 161034 P 9348 OS Keep areas to exit doors clear
270226 02/21/2007 161077 2 004 M Repair damaged concrete walk in front of doors to 2-005
270210 02/21/2007 161045 2 104 M Replace missing escutcheon on fire sprinkler head
270174 02/21/2007 160970 2 202 M Secure loose escutcheon on fire sprinkler head
219500 11/28/2005 71096 1 101 M Determine cause of water damaged ceiling tiles and replace tiles
219532 11/28/2005 63170 P 16 M Replace missing hurricane tie-downs for portable
219283 11/28/2005 71156 P 16 M Adjust steps to make risers equal
219916 11/28/2005 71161 P 16 M Repair or replace deteriorated wood siding and fascia beam
219625 11/28/2005 71150 P 16 M Repair roof leaks and replace damaged ceiling tiles
219561 11/28/2005 71144 P 3652 M Provide shims under ramp supports to eliminate vibration along ramp
219443 11/28/2005 63168 P 3652 M Replace missing hurricane tie-downs for portable
219154 11/28/2005 63162 P 3653 M Replace missing hurricane tie-downs for portable
219661 11/28/2005 63176 P 3668 M Replace missing hurricane tie-downs for portable
219228 11/28/2005 63161 P 3759 M Adjust ramp landing to be level with interior floor
219444 11/28/2005 71159 P 3759 M Repair or replace deteriorated wood siding
219626 11/28/2005 71160 P 73 M Repair or replace deteriorated wood siding
219950 11/28/2005 71140 P 753 M Repair damaged downspout adjacent to ramp
219442 11/28/2005 71162 P 753 M Repair or replace deteriorated wood siding on west side of unit
219600 11/28/2005 63174 P 80 M Replace missing hurricane tie-downs for portable
219599 11/28/2005 71106 12 106 O Prohibit plugging one surge protector into another adjacent to computer station AC0870
219915 11/28/2005 6564 00 9500 C Provide covered walkway to portables
219251 11/28/2005 71110 00 9599 C Provide fencing around lift station adjacent to P-18
219533 11/28/2005 63902 P 126 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219282 11/28/2005 71128 P 16 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219285 11/28/2005 71127 P 3652 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219537 11/28/2005 71124 P 3653 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219627 11/28/2005 71131 P 3668 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219662 11/28/2005 71123 P 3759 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219663 11/28/2005 71154 P 3759 C Provide balusters along stair handrails at six inches apart
219917 11/28/2005 71129 P 4064 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219193 11/28/2005 71126 P 4083 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219535 11/28/2005 71125 P 73 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219469 11/28/2005 71132 P 753 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219224 11/28/2005 71130 P 80 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219562 11/28/2005 71133 P 9344 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219313 11/28/2005 71134 P 9345 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219886 11/28/2005 71135 P 9346 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219445 11/28/2005 71136 P 9347 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219473 11/28/2005 71137 P 9348 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219629 11/28/2005 71138 P 9349 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219314 11/28/2005 71139 P 9350 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219222 11/28/2005 6433 1 190 FS Relocate heat detector to ceiling
219225 11/28/2005 71141 P 80 FS Provide heat detector in storage room
234492 11/18/2005 91749 10 101 M Provide certification that wood frame construction for time out room meets required flame spread rating (E-6)
219635 11/18/2004 6634 00 9599 M Repair broken sidewalk on north side of campus, north of Buildings 1, 2, and 3
219220 11/18/2004 71111 00 9599 M Repair damaged cover for lift station adjacent to P-14
219317 11/18/2004 6635 00 9599 M Repair broken sidewalk transition between Buildings 10 and 11
219598 11/18/2004 71097 1 105 M Determine cause of water damaged ceiling tiles and replace tiles
219221 11/18/2004 71098 1 106 M Determine cause of water damaged ceiling tiles and replace tiles
219153 11/18/2004 71099 1 108 M Determine cause of water damaged ceiling tiles and replace tiles
219189 11/18/2004 71100 1 109 M Determine cause of water damaged ceiling tiles and replace tiles
219190 11/18/2004 71158 12 001 M Patch hole in wall adjacent to 12-104
219531 11/18/2004 71101 12 108 M Determine cause of water damaged ceiling tiles and replace tiles
219197 11/18/2004 6649 5 101A M Determine cause of water damaged ceiling tiles and replace tiles (B-4, storage)
219156 11/18/2004 6651 6 101A M Provide dated flame resistance label on black stage curtains at back of stage or remove
219287 11/18/2004 6652 6 101A M Determine cause of water damaged ceiling tiles and replace tiles
219157 11/18/2004 6655 6 102 M Repair air conditioning unit to eliminate water dripping in kitchen (see kitchen manager for exact location)
219351 11/18/2004 6654 6 102 M Verify activation of hood fire suppression system will initiate school fire alarm
219604 11/18/2004 63148 6 111 M Lubricate emergency release hardware in freezer
219542 11/18/2004 6658 9 101A M Determine cause of water damaged ceiling tiles and replace tiles (E-4, storage)
219534 11/18/2004 71152 P 126 M Repair roof leaks and replace damaged ceiling tiles
219191 11/18/2004 71155 P 126 M Secure loose metal siding at NW corner of unit
219321 11/18/2004 6671 P 1418 M Adjust steps to make risers equal
219203 11/18/2004 6675 P 1439 M Secure and protect insulation on portable unit
219198 11/18/2004 63171 P 16 M Determine cause of water damaged ceiling tiles and replace tiles
219544 11/18/2004 63196 P 1859 M Repair damaged ceiling at match line
219576 11/18/2004 6679 P 298 M Adjust steps to make risers equal
218924 11/18/2004 63190 P 298 M Repair or replace deteriorated wood siding
219226 11/18/2004 71149 P 3652 M Repair roof leaks and replace damaged ceiling tiles
219471 11/18/2004 71104 P 3652 M Repair emergency lighting
219346 11/18/2004 63163 P 3653 M Repair damaged flooring
219379 11/18/2004 63164 P 3653 M Repair or replace deteriorated wood siding
219227 11/18/2004 71146 P 3653 M Repair roof leaks and replace damaged ceiling tiles
219628 11/18/2004 71145 P 3759 M Repair roof leaks and replace damaged ceiling tiles
219289 11/18/2004 6681 P 390 M Adjust steps to make risers equal
219290 11/18/2004 63186 P 390 M Replace missing hurricane anchor for portable
218923 11/18/2004 63187 P 390 M Repair exhaust fan in bathroom
219507 11/18/2004 6682 P 390 M Adjust stair landing to be level with interior floor
218922 11/18/2004 6696 P 4056 M Adjust steps to make risers equal
219162 11/18/2004 63184 P 4056 M Repair inoperable air conditioner (Work order # 585331)
219472 11/18/2004 71105 P 4064 M Repair emergency lighting
219630 11/18/2004 63172 P 4064 M Determine cause of water damaged ceiling tiles and replace tiles
219565 11/18/2004 63173 P 4064 M Repair damaged flooring
219953 11/18/2004 71148 P 4083 M Repair roof leaks and replace damaged ceiling tiles
219353 11/18/2004 63166 P 4083 M Determine cause of water damaged ceiling tiles and replace tiles
219323 11/18/2004 6686 P 4101 M Adjust steps to make risers equal
219324 11/18/2004 6677 P 43 M Replace missing graspable handrails on each side of ramp at between 34-38 inches high
219506 11/18/2004 6621 P 4509 M Remove mold on ramp and landing and repaint with non-slip surface
219508 11/18/2004 63192 P 4518 M Repair damaged flooring
219204 11/18/2004 6689 P 4518 M Adjust steps to make risers equal
219675 11/18/2004 63191 P 4518 M Determine cause of water damaged ceiling tiles and replace tiles
219638 11/18/2004 63180 P 655 M Pad and mark corners of unit which are lower than 6?8?
219257 11/18/2004 63179 P 655 M Determine cause of water damaged ceiling tiles and replace tiles
219320 11/18/2004 63181 P 655 M Repair flickering light in bathroom
219536 11/18/2004 71157 P 73 M Repair bent support under stair landing
219284 11/18/2004 71147 P 73 M Repair roof leaks and replace damaged ceiling tiles
219560 11/18/2004 63178 P 753 M Provide labeling for all circuits in electrical panel
219885 11/18/2004 71151 P 80 M Repair roof leaks and replace damaged ceiling tiles
219192 11/18/2004 71142 P 80 M Provide cover on exposed exterior electrical junction box
219563 11/18/2004 71143 P 9344 M Provide sealant to close gap between base of toilet and flooring
219530 11/18/2004 71107 12 103 O Eliminate extension cord adjacent to north wall or replace with minimum 15A cord
219230 11/18/2004 71109 P 4064 O Relocate book cart blocking access to fire alarm pull station adjacent to stair door
219538 11/18/2004 71108 P 9347 O Prohibit use of extension cord to extension cord to power appliances
219474 11/18/2004 6498 00 9599 C Provide paved walkway/parking area for SE side of campus; prohibit parking on grass and adjacent to buildings
219253 11/18/2004 6500 00 9599 C Improve site drainage to eliminate standing water on walkway at Building 3 after rain
218890 11/18/2004 6499 00 9599 C Improve site drainage to eliminate standing water on walkway at Building 2 after rain
219665 11/18/2004 6631 00 9599 C Turn barbs down on all fencing
219631 11/18/2004 6497 00 9599 C Provide covered walkway from building to bus loop at north side of campus
219503 11/18/2004 6559 10 103 C Provide exhaust fan in bathroom
219475 11/18/2004 6561 10 105 C Provide partitions between urinals
219286 11/18/2004 6560 10 105 C Provide exhaust fan in bathroom
219502 11/18/2004 6547 4 105 C Provide partitions between urinals
219602 11/18/2004 6549 6 101 C Provide tempered glazing, safety glass, or safety plastic in windows within 48 inches of doors
219632 11/18/2004 6550 6 101A C Provide handicapped accessibility to stage
219566 11/18/2004 6551 6 102 C Replace glazing in door between dining and serving area with tempered glass, safety glass, or safety plastic
219567 11/18/2004 6552 6 105 C Provide fire rated door which swings into the boiler room
219347 11/18/2004 6484 8 102 C Provide certification that wood paneling meets required flame spread rating or remove paneling
218893 11/18/2004 6580 P 1418 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
218894 11/18/2004 6583 P 1418 C Provide graspable handrails on each side of ramp at between 34-38 inches high
219605 11/18/2004 6582 P 1418 C Provide bottom rail on stair landing guardrail at two inches above floor
219673 11/18/2004 6581 P 1418 C Modify ramp to be minimum 44 inches wide
219571 11/18/2004 6587 P 1439 C Provide bottom rail on stair landing guardrail at two inches above floor
219236 11/18/2004 6588 P 1439 C Provide graspable handrails on each side of ramp at between 34-38 inches high
219355 11/18/2004 6589 P 1439 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
219381 11/18/2004 6584 P 1439 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219504 11/18/2004 6585 P 1439 C Provide bottom rail on ramp landing guardrail at two inches above floor
219505 11/18/2004 6586 P 1439 C Modify ramp to be minimum 44 inches wide
219201 11/18/2004 6619 P 1859 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219255 11/18/2004 6608 P 298 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219256 11/18/2004 6609 P 298 C Provide graspable handrails on each side of ramp at between 34-38? high
219607 11/18/2004 6607 P 298 C Provide handrails along north stair at 34-38? high with continuous graspable surface
219608 11/18/2004 6614 P 390 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
219637 11/18/2004 6612 P 390 C Provide balusters on stair landing guardrail at six inches apart
219573 11/18/2004 6615 P 390 C Provide ramp for portable
219237 11/18/2004 6616 P 390 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219202 11/18/2004 6611 P 390 C Provide bottom rail on stair landing guardrail at two inches above floor
218896 11/18/2004 6613 P 390 C Provide handrails on each side of stair
219477 11/18/2004 6610 P 390 C Provide guardrails at stair landing at a minimum 42 inches high
218895 11/18/2004 6627 P 4056 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219478 11/18/2004 6618 P 4101 C Provide handrails on each side of stair
219356 11/18/2004 6617 P 4101 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219354 11/18/2004 6578 P 4155 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219574 11/18/2004 6623 P 4163 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219636 11/18/2004 6605 P 43 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
219606 11/18/2004 6603 P 43 C Provide guardrails at stair landing at a minimum 42 inches high
219674 11/18/2004 6606 P 43 C Provide ramp for portable
219382 11/18/2004 6602 P 43 C Provide balusters on stair landing guardrail at six inches apart
219318 11/18/2004 6604 P 43 C Provide handrails on each side of stair
219543 11/18/2004 6600 P 43 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
218897 11/18/2004 6591 P 43 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219319 11/18/2004 6620 P 4509 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219575 11/18/2004 6622 P 4518 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219572 11/18/2004 63157 P 6010 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219570 11/18/2004 6575 P 655 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
219158 11/18/2004 6573 P 655 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219159 11/18/2004 6574 P 655 C Provide handrails on each side of stair
219160 11/18/2004 6576 P 655 C Provide ramp for portable
219161 11/18/2004 6577 P 655 C Provide tempered glass, safety glass, or stainless steel for mirrors
218892 11/18/2004 6566 P 868 C Provide balusters at six inches apart on ramp landing guardrail
219199 11/18/2004 6565 P 868 C Provide guardrails at ramp landing at a minimum 42 inches high
219200 11/18/2004 6567 P 868 C Provide bottom rail on ramp landing guardrail at two inches above floor
219235 11/18/2004 6569 P 868 C Provide graspable handrails on each side of ramp at between 34-38 inches high
219288 11/18/2004 6571 P 868 C Provide tempered glazing, safety glass, or safety plastic in windows within 48 inches of doors
219380 11/18/2004 6572 P 868 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
219671 11/18/2004 6568 P 868 C Provide handrails on each side of stair
219672 11/18/2004 6570 P 868 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
219348 11/18/2004 6463 8 101 F Provide fire alarm strobe light
219232 11/18/2004 6628 8 101 F Lower fire alarm pull station to be maximum 4' 6" above floor
219468 11/18/2004 71112 1 103 MS Provide current inspection tag for fire extinguisher
219603 11/18/2004 66653 6 102 MS Verify that electricity and gas to appliances shuts off upon activation of hood suppression system
219352 11/18/2004 63151 8 104 MS Provide current inspection tag for fire extinguisher (dated 12/03)
219223 11/18/2004 71114 P 16 MS Provide current inspection tag for fire extinguisher
219951 11/18/2004 71113 P 3653 MS Provide current inspection tag for fire extinguisher
219952 11/18/2004 71115 P 3668 MS Provide current inspection tag for fire extinguisher
219322 11/18/2004 63185 P 4056 MS Provide fire extinguisher with minimum 4A capacity in portable
219229 11/18/2004 71122 P 4064 MS Provide 2A fire extinguisher with minimum 4A capacity in portable
219470 11/18/2004 71116 P 753 MS Provide current inspection tag for fire extinguisher
219564 11/18/2004 71117 P 9345 MS Provide current inspection tag for fire extinguisher
219918 11/18/2004 71118 P 9346 MS Provide current inspection tag for fire extinguisher
219194 11/18/2004 71119 P 9347 MS Provide current inspection tag for fire extinguisher
219664 11/18/2004 71120 P 9349 MS Provide current inspection tag for fire extinguisher
219501 11/18/2004 71121 P 9350 MS Provide current inspection tag for fire extinguisher
219914 11/18/2004 71102 12 105 OS Relocate table to provide a clear path to exterior door
219884 11/18/2004 71103 12 107 OS Relocate table to provide a clear path to exterior door
219670 11/18/2004 6492 7 103 OS Prohibit storage of gas powered pressure cleaner
219252 11/18/2004 6430 00 9599 CS Modify gate in fenced area around kitchen freezer to allow egress at all times and remove chain and padlock
219316 11/18/2004 6471 10 101 FS Provide heat detector in time out room used for storage (E-6)
219669 11/18/2004 6472 10 101A FS Provide heat detector in storage room (E-6, storage)
219541 11/18/2004 6473 10 102A FS Provide heat detector in storage room (E-5 storage)
219233 11/18/2004 6474 10 102A FS Provide heat detector in concealed attic space (E-5, storage)
218891 11/18/2004 6476 11 101A FS Provide heat detector in concealed attic space (E-7, storage)
219350 11/18/2004 6475 11 101A FS Provide heat detector in storage room (E-7, storage)
219539 11/18/2004 6477 12 103C FS Provide heat detector in storage room
219155 11/18/2004 6478 12 190 FS Relocate heat detector to underside of roof deck
219568 11/18/2004 6455 4 101 FS Provide heat detector in storage room
219231 11/18/2004 6456 5 101A FS Provide heat detector in storage room (B-4, storage)
219633 11/18/2004 6458 5 102A FS Provide heat detector in concealed attic space (B-3, storage)
219666 11/18/2004 6457 5 102A FS Provide heat detector in storage room (B-3, storage)
219569 11/18/2004 6459 6 104 FS Provide heat detector in locker and cleaning supplies storage areas (X2)
219315 11/18/2004 6460 7 101A FS Provide heat detector in storage room (D-2, storage)
219195 11/18/2004 6461 7 102A FS Provide heat detector in storage room (D-1, storage)
219667 11/18/2004 6462 7 102A FS Provide heat detector in concealed attic space (D-1, storage)
219349 11/18/2004 6464 8 104 FS Provide heat detector in storage room
219196 11/18/2004 6465 9 101A FS Provide heat detector in storage room (E-4, storage)
219540 11/18/2004 6466 9 102A FS Provide heat detector in storage room (E-3, storage)
219476 11/18/2004 6467 9 102A FS Provide heat detector in concealed attic space (E-3, storage)
219668 11/18/2004 6469 9 104A FS Provide heat detector in storage room (E-1, storage)
219634 11/18/2004 6470 9 104A FS Provide heat detector in concealed attic space (E-1, storage)
219234 03/28/2004 6485 00 8087 C Provide certification that wood adequate illumination for all exterior corridors for evening