Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
406858 04/06/2018 457928 1 193 M Repair condensate leak from chilled water plumbing
406859 04/06/2018 457930 1 193 M Replace missing belt guard for EF1-4
406883 04/06/2018 457984 2 191 M Replace missing belt guard for SF2-2 and replace belt or repair motor. Very noisy
271705 04/06/2018 164457 1 0000 N/A No violations observed
406831 03/09/2018 457868 1 205C MS Repair thumb latch to enable door to be unlocked from outside of room
406832 03/09/2018 457870 1 205D MS Repair thumb latch to enable door to be unlocked from outside of room
406844 03/09/2018 457895 1 217C MS Repair thumb latch to enable door to be unlocked from outside of room
406870 01/24/2018 457954 00 0000 M Repair rusted gate on perimeter fencing south of Media center. Remove rust and fill perforations
406862 01/24/2018 457936 00 0000 M Repair rusted gate on perimeter fencing NW of 1-110. Frame for view panel badly rusted. Remove rust and fill holes
406864 01/24/2018 457939 1 0000 M Adjust chain link fence gate so it can close. Pre-K play area gate east of 1-119
406888 01/24/2018 457995 1 0000 M Secure loose ground wire to south exterior wall of building outside of 1-128
406865 01/24/2018 457941 1 002 M Replace missing escutcheon on fire sprinkler head at bottom of stairs
406834 01/24/2018 457874 1 105 M Repair leaking supply line for toilet
406871 01/24/2018 457957 1 120 M Secure loose backer board for projection screen to wall
406850 01/24/2018 457907 1 122 M Seal open corners in shower stall
406874 01/24/2018 457963 1 125 M Repair wall finish at drinking fountain
406873 01/24/2018 457961 1 125B M Repair leaking supply line for toilet
406852 01/24/2018 457911 1 128A M Seal open corners in shower stall
406872 01/24/2018 457959 1 131B M Repair leaking supply line for toilet
406855 01/24/2018 457921 1 133 M Eliminate ants
406836 01/24/2018 457879 1 134 M Eliminate termites
406837 01/24/2018 457881 1 134 M Repair broken window blinds
406835 01/24/2018 457877 1 135 M Eliminate ants and spiders
406854 01/24/2018 457919 1 191 M Replace missing screws for cover of electrical panel L1A
406856 01/24/2018 457924 1 192 M Condensate drain is stopped up and overflowing. Repair drain
406857 01/24/2018 457926 1 192 M Replace missing screws for cover of electrical panel AC1C
406866 01/24/2018 457944 1 195 M Replace missing screws for cover of electrical panel L1C
406884 01/24/2018 457986 1 203B M Repair or replace damaged dryer vent line
406833 01/24/2018 457872 1 205D M Caulk sink to wall
406830 01/24/2018 457866 1 210 M Electrical outlets in SW corner of room have no power. Repair circuit
406826 01/24/2018 457858 1 214B M Seal wall at bathroom sink to provide impervious finish
406887 01/24/2018 457992 1 217D M Repair lock, sticky latch
406827 01/24/2018 457860 1 292 M Replace missing screws for electrical panel H22
406828 01/24/2018 457862 1 292 M Breakers 2 and 31 on electrical panel L2A are tripped. Repair circuits
406845 01/24/2018 457897 1 293 M Secure or remove valve actuator resting on conduit and secure Greenfield conduit to junction box
406875 01/24/2018 457965 2 0000 M Adjust gate between chiller yard and 1-107 (Stage) to latch properly. Gate barely latches and can be pulled open
406841 01/24/2018 457889 2 101 M Eliminate spiders
406838 01/24/2018 457883 2 102B M Eliminate spiders
406839 01/24/2018 457885 2 102B M Repair exhaust fan at kiln
406840 01/24/2018 457887 2 102B M Replace fire sprinkler head in Kiln room with a higher temperature rated head
406843 01/24/2018 457893 2 103B M Determine cause of water damaged ceiling tiles and replace tiles
406842 01/24/2018 457891 2 105B M Replace damaged soap dispenser
406876 01/24/2018 457967 2 106B M Secure handicapped sink to wall
406877 01/24/2018 457969 2 106B M Repair leaking supply line for toilet
406879 01/24/2018 457975 2 109C M Repair emergency release hardware in cooler in Kitchen. Knob will not turn
406846 01/24/2018 457899 2 181 M Determine cause of water damaged ceiling tiles and replace tiles
406882 01/24/2018 457982 2 192 M Insulate hot water lines
406881 01/24/2018 457980 2 193 M Cover exposed wire nutted wires above entry
406880 01/24/2018 457978 2 194 M Overcrank warning light is lit on generator. Repair generator
406861 01/24/2018 457934 2 195 M Replace missing screws for covers of electrical panels ACB and DL1C
406825 01/24/2018 457856 00 0 O No access was available to 1-137. Please provide access to this room during the report review meeting
406847 01/24/2018 457901 1 121 O Remove and prohibit paper covering window in door. Acceptable for CODE situation only
406848 01/24/2018 457903 1 121 O Provide clear access to fire alarm pull station at rear door
406849 01/24/2018 457905 1 122 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
406853 01/24/2018 457914 1 126 O Remove and prohibit paper covering window in door. Acceptable for CODE situation only
406851 01/24/2018 457909 1 128A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
406868 01/24/2018 457948 1 136 O Keep area within 18 inches of fire sprinkler head clear and unobstructed
406829 01/24/2018 457864 1 212A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
406885 01/24/2018 457988 1 216B O Keep area within 18 inches of fire sprinkler head clear and unobstructed
406886 01/24/2018 457990 1 218 O Remove and prohibit paper covering window in door. Acceptable for CODE situation only
406867 01/24/2018 457946 1 195 MS Provide current inspection tag for fire extinguisher
406869 01/24/2018 457950 1 104 OS Remove and prohibit storing desk in corridor at 1-102
406878 01/24/2018 457971 2 107 OS Provide clear access to fire extinguisher on Stage
406824 08/21/2017 457854 00 0000 M Make necessary repairs to fire sprinkler system as indicated on inspection report. Red annual and yellow semi-annual and quarterly tags. Risers in rooms 1-194 and 2-191
392525 08/21/2017 426959 00 0000 M Make necessary repairs to fire sprinkler systems located in rooms 1-194 and 2-191 as indicated on annual inspection reports dated January 2016
406860 08/21/2017 457932 2 195 M Repair condensate leak from chilled water plumbing for AHU 2-3
271706 08/21/2017 164459 2 0000 N/A No violations observed
271574 08/21/2017 164152 3 0000 N/A No violations observed
392513 04/24/2017 426931 1 119B M Repair ventilation fan
392514 04/24/2017 426933 1 121A M Repair ventilation fan
392516 04/24/2017 426937 1 122 M Repair ventilation fan
392518 04/24/2017 426941 1 125A M Repair ventilation fan
392517 04/24/2017 426939 1 128A M Repair ventilation fan
392535 04/24/2017 426988 2 181C M Repair ventilation fan
392519 03/10/2017 426943 1 134 M Repair door to close properly, closes too fast
392512 03/10/2017 426929 1 170 M Provide current inspection tag for elevator
392529 03/10/2017 426976 1 192 M Repair clogged floor drain
392527 03/10/2017 426969 1 193 M Replace missing lock for electrical panel AC1B
392543 03/10/2017 427009 1 205C M Repair recessed thumb latch to enable door to be unlocked
392542 03/10/2017 427007 1 205D M Repair recessed thumb latch to enable door to be unlocked
392545 03/10/2017 427013 1 207 M Repair door to close properly, closes too fast
392546 03/10/2017 427015 1 211 M Repair door to close properly, closes too fast
392530 03/10/2017 426978 2 105B M Repair recessed thumb latch to enable door to be unlocked
392531 03/10/2017 426980 2 105C M Repair recessed thumb latch to enable door to be unlocked
392532 03/10/2017 426982 2 107A M Determine cause of water damaged ceiling tiles and replace tiles
392536 03/10/2017 426990 2 109C M Adjust door of walk in refrigerator to close properly
392537 03/10/2017 426992 2 109H M Replace missing escutcheon on fire sprinkler head
392526 03/10/2017 426963 2 192 M Complete repairs to hot water heater
392524 03/10/2017 426957 2 194 M Provide current certification that all student occupied spaces have emergency lights and all are operable, certificate dated August 2015
392523 03/10/2017 426955 2 195 M Repair door to latch properly
392521 03/10/2017 426947 2 195 M Repair leaking air conditioning system to ensure it operates as designed
392528 03/10/2017 426972 3 102 M Repair door to close and latch properly
392534 03/10/2017 426986 00 0000 O Properly secure belt cover for pump motor in chiller area
392511 03/10/2017 426927 1 117 O Remove and prohibit air freshener
392539 03/10/2017 427001 1 204 O Remove and prohibit air freshener
392541 03/10/2017 427005 1 204 O Remove and prohibit use of (flammable) colored plastic table coverings
392509 03/10/2017 426922 1 115 MS Provide current inspection tag for fire extinguisher
392510 03/10/2017 426924 1 118 MS Provide current inspection tag for fire extinguisher
392538 03/10/2017 426994 1 136 MS Provide current inspection tag for fire extinguisher
392544 03/10/2017 427011 1 291 MS Provide current inspection tag for fire extinguisher
392520 03/10/2017 426945 2 111 MS Provide current inspection tag for fire extinguisher
392515 03/10/2017 426935 1 122 OS Remove and prohibit excessive storage in bathroom to maintain clear aisle to exit
392522 03/10/2017 426952 2 110 OS Provide clear access to fire extinguisher
392533 03/10/2017 426984 2 9599 OS Prohibit storage on exterior stage ramp to maintain clear aisle to exit gate
381916 08/22/2016 404065 1 194 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report dated 1.5.15
381893 01/21/2016 404016 1 129C M Repair exhaust fan in bathroom
381891 01/21/2016 404012 1 132A M Repair water damaged wall finish behind toilet
381912 01/21/2016 404056 1 136 M Determine cause of water damaged ceiling tiles and replace tiles in back of storage room
381901 01/21/2016 404032 1 137A M Replace missing signage indicating room name and number with Braille characters
381913 01/21/2016 404058 1 182 M Adjust door to latch properly - custodial room is located inside media center
381877 01/21/2016 403980 1 203 M Repair light fixture adjacent to projector screen
381878 01/21/2016 403984 1 290 M Secure ceiling tile in place
381908 01/21/2016 404048 2 0000 M Adjust hardware on gate at bottom of exterior ramp behind stage to latch properly - gate is not secure
381904 01/21/2016 404038 2 107 M Adjust door closer to control speed of closing exterior door on stage
381898 01/21/2016 404026 2 109C M Provide protective cage around fire sprinkler head in cooler
381899 01/21/2016 404028 2 109D M Provide protective cage around fire sprinkler head in freezer
381900 01/21/2016 404030 2 109D M Replace missing escutcheon on fire sprinkler head in walk-in freezer
381911 01/21/2016 404054 2 190 M Replace broken ceiling tile - room is located inside kitchen
381902 01/21/2016 404034 2 191 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report dated 1.5.15
381903 01/21/2016 404036 2 191 M Repair door to open and close properly
381886 01/21/2016 404001 1 119A O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
381890 01/21/2016 404010 1 127 O Remove and prohibit paper on window blinds behind teacher desk
381892 01/21/2016 404014 1 132 O Prohibit plugging surge protector into surge protector at teacher desk - plug each surge protector directly into wall outlet
381884 01/21/2016 403997 1 215A O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
381881 01/21/2016 403991 1 216 O Prohibit plugging surge protector into surge protector at teacher desk - plug each surge protector directly into wall outlet
381882 01/21/2016 403993 1 218 O Prohibit plugging surge protector into surge protector at teacher desk - plug each surge protector directly into wall outlet
381883 01/21/2016 403995 1 219 O Prohibit plugging surge protector into surge protector at teacher desk - plug each surge protector directly into wall outlet
381914 01/21/2016 404060 2 104 O Keep communications cord inside cover strip track adjacent to exterior door and secure cover strip to flooring to eliminate trip hazard
381905 01/21/2016 404040 2 180 O Keep custodial room locked and latched to prevent student access
381906 01/21/2016 404043 2 181 O Keep custodial receiving room locked and latched to prevent student access
381888 01/21/2016 404005 1 125A MS Repair unlock hardware on bathroom door to work properly
381889 01/21/2016 404007 1 127B MS Repair unlock hardware on bathroom door to work properly
381896 01/21/2016 404022 1 137A MS Repair unlock hardware on bathroom door to work properly
381885 01/21/2016 403999 1 213B MS Repair unlock hardware on bathroom door to work properly
381897 01/21/2016 404024 2 101 MS Repair loose lock cylinder on exterior face of west exit door
381910 01/21/2016 404052 2 110 MS Repair or replace damaged flashing above door - flashing is bent and prohibiting door from latching properly
381907 01/21/2016 404046 2 192 MS Repair door lock to work properly - room was not accessible
381894 01/21/2016 404018 1 135 OS Relocate copy machine to provide clear access to fire extinguisher cabinet adjacent to circulation desk
381895 01/21/2016 404020 1 135A OS Prohibit storage of flammable acetone can adjacent to sink - relocate to flammable storage room 1-111
381887 01/21/2016 404003 1 191 OS Remove storage from electrical room
381879 01/21/2016 403987 1 214B OS Remove all stools from bathroom
381880 01/21/2016 403989 1 293 OS Remove storage from mechanical room
381915 01/21/2016 404062 2 104 OS Remove divider partition with extended legs located adjacent to exterior door which can cause trip hazard
381909 01/21/2016 404050 2 195 OS Remove storage from mechanical room
375461 04/16/2015 390006 1 001 M Replace missing escutcheon on fire sprinkler head at top landing of stairway
375457 04/16/2015 389998 1 135E M Determine cause of water damaged ceiling tiles at north windows and replace tiles
375456 04/16/2015 389996 1 190 M Determine cause of water damaged ceiling tiles and replace tiles
375462 04/16/2015 390008 1 192 M Repair leaking water valve on chilled water line on air handler to eliminate water leaking onto floor
375463 04/16/2015 390010 1 194 M Make necessary repairs to sprinkler system as indicated by red tag on sprinkler riser dated January, 2015
375458 04/16/2015 390000 1 206 M Determine cause of water damaged ceiling tiles next to storage room and replace tiles
375465 04/16/2015 390014 2 101 M Replace missing escutcheon on fire sprinkler head in music room
375466 04/16/2015 390016 2 102 M Secure hanging lens on light fixture
375467 04/16/2015 390018 2 107A M Determine cause of water damaged ceiling tiles and replace tiles
375469 04/16/2015 390022 2 181 M Determine cause of water damaged ceiling tiles and replace tiles
375470 04/16/2015 390024 2 181 M Anchor shelving to wall in custodial receiving
375464 04/16/2015 390012 2 191 M Make necessary repairs to sprinkler system as indicated by red tag on sprinkler riser, dated January 2015
375471 04/16/2015 390026 2 193 M Repair emergency lighting in electric room
375460 04/16/2015 390004 1 0000 O Remove and prohibit paper covering windows in doors (except during code red situations)
375459 04/16/2015 390002 1 0000 OS Prohibit hold open devices on fire doors (wedges holding classroom doors open during school hours)
375468 04/16/2015 390020 2 107 OS Relocate folding table blocking clear access to exit door at rear of stage
358318 02/11/2014 352813 1 002 M Secure loose handrail at bottom landing of stairs
358314 02/11/2014 352805 1 010 M Determine cause of water damaged ceiling tiles in corridor adjacent to 1-121 and replace tiles
358315 02/11/2014 352807 1 010 M Replace missing escutcheon on fire sprinkler head in corridor adjacent to 1-121
358316 02/11/2014 352809 1 011 M Repair drinking fountain in corridor
358312 02/11/2014 352799 1 114 M Determine cause of water damaged ceiling tiles and replace tiles
358313 02/11/2014 352802 1 121 M Determine cause of water damaged ceiling tiles and replace tiles
358228 02/11/2014 352612 1 121 M Repair deteriorated wall finish
358319 02/11/2014 352815 1 135 M Determine cause of water damaged ceiling tiles southeast corner of media center and replace tiles
358321 02/11/2014 352819 1 135A M Replace missing escutcheons on fire sprinkler heads (X2)
358320 02/11/2014 352817 1 182 M Place ceiling tiles back into metal ceiling grid
358327 02/11/2014 352831 1 205 M Secure drinking fountain to sink
358328 02/11/2014 352833 1 205 M Replace missing escutcheon on fire sprinkler head
358326 02/11/2014 352829 1 206 M Determine cause of water damaged ceiling tiles and replace tiles
358323 02/11/2014 352823 1 215 M Secure drinking fountain to sink
358324 02/11/2014 352825 1 292 M Repair inoperable air conditioner unit inside room (room temperature was very hot)
358330 02/11/2014 352838 2 102B M Repair ventilation fan in kiln room
358339 02/11/2014 352856 2 103 M Determine cause of water damaged ceiling tiles at west wall of cafeteria and replace tiles
358336 02/11/2014 352850 2 103B M Replace missing escutcheon on fire sprinkler head
358337 02/11/2014 352852 2 107 M Replace missing escutcheon on fire sprinkler head
358338 02/11/2014 352854 2 107 M Provide current date on flame resistance label on stage curtain (certification has no date)
358331 02/11/2014 352840 2 109A M Replace missing escutcheon on fire sprinkler head
358334 02/11/2014 352846 2 181 M Determine cause of water damaged ceiling tiles and replace tiles
358335 02/11/2014 352848 2 181A M Determine cause of water damaged ceiling tiles and replace tiles
358333 02/11/2014 352844 2 181B M Determine cause of water damaged ceiling tiles and replace tiles
358332 02/11/2014 352842 2 190 M Replace missing ceiling tiles
358317 02/11/2014 352811 1 130 O Remove and prohibit paper covering window in door
358329 02/11/2014 352835 1 205 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
358325 02/11/2014 352827 1 207 O Prohibit plugging surge protector into surge protector
358322 02/11/2014 352821 1 217A O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
326718 11/18/2013 283956 2 109 M Provide current state inspection tag for kitchen steamer
349036 04/08/2013 332137 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
349010 04/08/2013 332079 1 106A M Replace missing lever for emergency eye wash
349016 04/08/2013 332092 1 205D M Replace missing escutcheon on fire sprinkler head
349014 04/08/2013 332088 1 215 M Secure loose drinking spout
349026 04/08/2013 332112 2 102 M Adjust exterior door to latch properly
349027 04/08/2013 332114 2 102 M Provide tempered or safety glazing in display cabinet adjacent to kiln room or remove glass - teacher does not need the glass
349028 04/08/2013 332116 2 103 M Adjust SW doors to latch properly
349024 04/08/2013 332108 3 102 M Repair exhaust fan in bathroom
349025 04/08/2013 332110 3 103 M Repair exhaust fan in bathroom
349054 04/08/2013 332177 1 128 O Remove and prohibit excessive flammable paper decorations - limit wall covering to 50 percent of each wall area
349055 04/08/2013 332179 1 128 O Remove paper covering wall outlets and light switches to eliminate hazardous condition
349022 04/08/2013 332104 1 132 O Remove and prohibit paper covering window blinds
349023 04/08/2013 332106 1 135 O Remove and prohibit hanging paper from ceiling in media center
349019 04/08/2013 332098 1 203 O Remove clorox container adjacent to teacher desk to eliminate hazardous condition
349017 04/08/2013 332094 1 205 O Remove and prohibit hanging decorations from ceiling
349011 04/08/2013 332081 1 212 O Prohibit plugging surge protector into surge protector at teacher's desk - plug each surge protector directly into wall outlet
349012 04/08/2013 332083 1 212 O Remove and prohibit hanging decorations from ceiling
349029 04/08/2013 332118 2 104 O Secure electrical cord and cover strip to flooring to eliminate trip hazard
349037 04/08/2013 332139 2 180 O Remove tissue on door latch receiver which prohibit custodial room door from latching and to prohibit student access
349021 04/08/2013 332102 1 202 OS Prohibit use of door wedge as hold open device on corridor door
349018 04/08/2013 332096 1 203A OS Remove storage bin off bathroom floor
349013 04/08/2013 332086 1 212B OS Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
349015 04/08/2013 332090 1 215A OS Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
349020 04/08/2013 332100 1 216 OS Prohibit use of door wedge as hold open device on corridor door
349032 04/08/2013 332126 2 107 OS Relocate tables on stage to maintain 3 ft clear path to exit door to dining room
349031 04/08/2013 332123 2 107A OS Relocate shelf unit to provide clear access to fire extinguisher
349035 04/08/2013 332132 00 0000 CS Provide suitable area for charging floor cleaning machines - machines were charged in 2-181
326680 01/30/2013 283878 1 135C M Provide dated flame resistance label on CCTV Studio curtain
326716 01/30/2013 283952 2 107 M Provide dated flame resistance label on stage curtain - (Labeled IFR)
326695 12/15/2011 283908 00 0000 M Label fire department connections as to which building they serve (one is for Building 1 and the other is for Building 2, labels can be stenciled on with white paint)
326679 12/15/2011 283876 1 180 M Replace missing ceiling tiles
326713 12/15/2011 283946 1 195 M Provide correct mounting bracket for fire extinguisher (extinguisher is currently sitting on the floor)
326692 12/15/2011 283901 1 292 M Remove plastic bag covering heat detector on ceiling
326715 12/15/2011 283950 2 107 M Replace missing drywall around exterior exit door of stage
326714 12/15/2011 283948 2 107A M Replace missing ceiling tiles
326717 12/15/2011 283954 2 109 M Replace missing ceiling tile adjacent to kitchen exhaust hood
326719 12/15/2011 283958 2 182 M Determine cause of water damaged ceiling tiles and replace tiles
326721 12/15/2011 283962 2 194 M Repair emergency lighting in generator room
326711 12/15/2011 283942 1 137 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
326694 12/15/2011 283905 1 201A O Prohibit plugging microwave oven and refrigerator into surge protector - plug directly into permanent electrical outlet
326690 12/15/2011 283890 1 215 O Remove and prohibit flammable paper hanging on windows
326683 12/15/2011 283884 1 216 O Eliminate white multiple outlet extension cord powering glue gun
326682 12/15/2011 283882 1 217A O Prohibit plugging microwave oven and refrigerator into surge protector - plug directly into permanent electrical outlet
326681 12/15/2011 283880 1 218 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
326712 12/15/2011 283944 1 194 MS Provide current inspection tag for fire sprinkler system (Sytem inspection was marked quarterly with an inspection date 5-23-11)
326722 12/15/2011 283964 2 191 MS Provide current inspection tag for fire sprinkler system (Current tag is marked as quarterly inspection with inspected date of 5-23-11)
326693 12/15/2011 283903 1 291 OS Remove storage from mechanical room
326684 12/15/2011 283886 1 293 OS Remove storage from mechanical room
326720 12/15/2011 283960 2 181 OS Prohibit charging floor cleaning machine batteries in room
316294 10/05/2011 260641 1 292 M Repair air conditioning unit, room is very hot
316330 03/07/2011 260715 1 132 M Replace damaged fire sprinkler head, fusible link has drained all fluid, north/center location
316419 03/07/2011 260916 1 132A M Replace missing door stop
316305 03/07/2011 260665 1 135E M Determine cause of water damaged ceiling tiles and replace tiles
316298 03/07/2011 260651 1 195 M Mount fire extinguisher at maximum five feet above floor
316296 03/07/2011 260646 1 212 M Repair entry door hardware
316304 03/07/2011 260663 1 214B M Remove decorations from fire sprinkler head
316303 03/07/2011 260657 1 292 M Provide panel schedule for panel DL2B
316292 03/07/2011 260637 2 0000 M Re-install pressure guages located in the chiller yard, TRERICE guages
316340 03/07/2011 260739 2 101 M Determine cause of water damaged ceiling tiles and replace tiles, nw corner
316324 03/07/2011 260708 2 103 M Replace missing escutcheon on fire sprinkler head
316332 03/07/2011 260724 2 107A M Determine cause of water damaged ceiling tiles and replace tiles
316307 03/07/2011 260669 2 182 M Determine cause of water damaged ceiling tiles and replace tiles
316306 03/07/2011 260667 2 190 M Determine cause of water damaged ceiling tiles and replace tiles
316350 03/07/2011 260765 2 194 M Provide certification that all student occupied spaces have emergency lights and all are operable
316354 03/07/2011 260770 2 195 M Repair bottom latch of inactive leaf of exterior door
316300 03/07/2011 260654 1 123 O No access was available to this room. Please be prepared to access this room during the report review meeting.
316352 03/07/2011 260768 1 128 O Prohibit plugging extension cord into extension cord
316322 03/07/2011 260703 2 105 MS Provide current inspection tag for fire extinguisher
316338 03/07/2011 260734 2 109 MS Recharge fire extinguisher type K
316342 03/07/2011 260746 2 107A OS Provide clear access to fire extinguisher
316335 03/07/2011 260727 2 111 OS Provide clear access to fire extinguisher
316432 03/07/2011 260942 2 181 OS Prohibit charging floor machine batteries in room
304771 04/06/2010 235356 00 0000 M Paint building number on exterior walls of each building to be visible to fire rescue
290787 04/06/2010 205253 00 0000 M Lubricate all swivel connections to all Fire Department standpipes
304789 04/06/2010 235394 1 001 M Determine cause of water damaged ceiling tiles above middle landing of stairway and replace tiles
304784 04/06/2010 235384 1 115 M Determine cause of water damaged ceiling tiles and replace tiles
304774 04/06/2010 235364 1 134B M Replace missing escutcheon on fire sprinkler head
304762 04/06/2010 235337 1 135 M Determine cause of water damaged ceiling tiles and replace tiles
304793 04/06/2010 235404 1 202 M Determine cause of water damaged ceiling tiles and replace tiles
304791 04/06/2010 235399 1 203B M Repair door on storage closet to close properly (door drags on jamb)
304798 04/06/2010 235413 1 217A M Repair door to close properly (door drags on jamb)
304801 04/06/2010 235419 1 217A M Repair door to close properly (door drags on jamb)
304764 04/06/2010 235341 2 107 M Remove flammable canvas backdrop on wall behind stage curtains or apply flame retardent and verification that material passes flame spread ratings test
304763 04/06/2010 235339 2 190 M Replace missing escutcheon on fire sprinkler head
304766 04/06/2010 235346 3 0000 M Remove rust from metal roof beams on P.E. Pavilion and repaint beams
304779 04/06/2010 235373 1 118 O Remove storage on top rack of center storage rack to keep area within 18" of fire sprinkler head clear
304765 04/06/2010 235344 2 101 O Prohibit plugging surge protector into extension cord at teachers desk
304761 04/06/2010 235335 00 0000 C Provide exterior signage indicating property address
239784 04/06/2010 98960 1 001 C Adjust steps to make risers equal at intermediate landing to upper flight (steps were all measured and approval given by Victor Chodora to remove citation, 4-07-2010)
304785 04/06/2010 235388 1 171 MS Provide current inspection tag for fire extinguisher
304795 04/06/2010 235407 1 291 MS Provide current inspection tag for fire extinguisher
304776 04/06/2010 235369 1 190 OS Remove storage from telecommunications room
290788 04/16/2009 205255 00 0000 M Adjust door in perimeter fence at south side of campus to latch properly
290803 04/16/2009 205286 1 0000 M Unband palm trees adjacent to main entry
290798 04/16/2009 205275 1 004 M Repair damaged corner bead on corridor wall adjacent to 1-115
290792 04/16/2009 205263 1 021 M Repair hole in wall from door handle at north end of corridor. Install backing and door stop to prevent further damage
271568 04/16/2009 164139 1 022 M Replace missing escutcheon on fire sprinkler head in corridor adjacent to 1-213
290795 04/16/2009 205269 1 111 M Replace missing ceiling tiles
290799 04/16/2009 205278 1 128 M Determine cause of water damaged ceiling tiles and replace tiles
290800 04/16/2009 205280 1 190 M Determine cause of water damaged ceiling tiles and replace tiles
290797 04/16/2009 205273 1 212A M Secure sink to wall in bathroom
290802 04/16/2009 205284 1 216A M Repair thumb latch to enable door to be unlocked from outside of room
290794 04/16/2009 205267 2 106B M Replace missing toilet seat
290790 04/16/2009 205259 2 107A M Determine cause of water damaged ceiling tiles and replace tiles
290793 04/16/2009 205265 1 118 O Lower storage on top shelves to keep area within 18" of fire sprinkler head clear
290796 04/16/2009 205271 1 115 MS Provide current inspection tag for fire extinguisher
290791 04/16/2009 205261 1 217 OS Prohibit running electrical cord across floor
290801 04/16/2009 205282 2 180 OS Prohibit storage of gas powered equipment
271573 11/07/2008 164149 00 0000 M Repair or replace rusted door in perimeter fence at South campus
271567 11/07/2008 164137 1 022 M Replace missing escutcheon on fire sprinkler head in corridor adjacent to 1-217
271552 11/07/2008 164104 1 181 M Replace missing ceiling tiles
197661 11/07/2008 63544 1 193A M Replace missing signage indicating room number at appropriate height with raised and Braille characters
271551 11/07/2008 164102 1 205D M Secure sink to wall
271569 11/07/2008 164141 2 182 M Replace missing escutcheon on fire sprinkler head
271565 11/07/2008 164131 1 101 FS Repair punch list as indicated on fire alarm inspection report
290789 11/06/2008 205257 1 0000 C Provide suitable wiring for projectors to eliminate need for extension cords
271545 02/20/2008 164087 00 0000 M Repair sprinkler line leak and fill hole in ground in grassed area NW of Bldg. 3
271546 02/20/2008 164089 00 0000 M Install cap on fire department standpipe connection NE of Bldg. 2
271559 02/20/2008 164119 1 127B M Caulk sink to wall
271557 02/20/2008 164114 1 132A M Repair exhaust fan in bathroom
271558 02/20/2008 164116 1 132A M Repair thumb latch to enable door to be unlocked from outside
271560 02/20/2008 164121 1 133A M Caulk sink to wall
271556 02/20/2008 164112 1 134A M Repair exhaust fan in bathroom
239776 02/20/2008 98939 1 192 M Replace missing signage indicating room number at appropriate height with raised and Braille characters
239775 02/20/2008 98937 1 193 M Replace missing signage indicating room number at appropriate height with raised and Braille characters
271554 02/20/2008 164108 1 205C M Repair exhaust fan in bathroom
271555 02/20/2008 164110 1 205D M Repair exhaust fan in bathroom
271553 02/20/2008 164106 1 212C M Anchor shelving to wall
271561 02/20/2008 164123 2 103 M Replace ceiling tile at sprinkler escutcheon to eliminate gap between escutcheon and ceiling tile
271548 02/20/2008 164093 2 109G M Repiar thumb latch to enable door to be unlocked from outside of room
271562 02/20/2008 164125 2 181 M Determine cause of water damaged ceiling tiles and replace tiles and replace missing tiles
271563 02/20/2008 164127 2 181A M Determine cause of water damaged ceiling tiles and replace tiles
271564 02/20/2008 164129 2 181B M Determine cause of water damaged ceiling tiles and replace tiles
271566 02/20/2008 164134 2 192 M Install fire extinguisher sitting on floor at maximum of 5' above floor adjacent to door
271550 02/20/2008 164097 2 102A O Remove storage on top shelf to keep automatic fire sprinkler heads clear and unobstructed
271571 02/20/2008 164145 2 107A O Keep area within 18" of automatic fire sprinkler heads clear and unobstructed
271549 02/20/2008 164095 2 109 MS Provide current inspection tag for kitchen hood fire suppression system. Tag not punched
271547 02/20/2008 164091 1 115 OS Prohibit hold open devices on fire door
271572 02/20/2008 164147 2 107 OS Remove and prohibit storing chairs at exit
271570 02/20/2008 164143 2 110 OS Provide clear access to fire extinguisher
269646 09/12/2007 159771 1 011 M Replace missing escutcheon on fire sprinkler head adjacent to 1-135
269653 09/12/2007 159785 1 011 M Replace missing escutcheon on fire sprinkler head adjacent to 1-127
269655 09/12/2007 159789 1 128 M Replace missing escutcheons on fire sprinkler heads (X3)
269651 09/12/2007 159781 1 181 M Secure escutcheon on fire sprinkler head
269661 09/12/2007 159799 1 194 M Replace missing wrench in spare fire sprinkler head box
269637 09/12/2007 159753 2 109A M Replace missing escutcheon on fire sprinkler head
269669 09/12/2007 159819 1 214 C Provide additional power pole to eliminate plugging surge protectors together
269644 09/12/2007 159767 2 102 C Provide additional electrical outlet in NE corner of room (see teacher) to eliminate the need for extension cord and surge protector to power media cart
269663 05/03/2007 159804 1 002 M Secure handrail on lower run of stairs
269645 05/03/2007 159769 1 182 M Seal penetration in ceiling tiles. Ceiling tiles around chilled water return were cut too large leaving a penetration
269679 05/03/2007 159839 1 204 M Determine cause of water damaged ceiling tiles and replace tiles
269638 05/03/2007 159755 2 109 M Repair seal around freezer door, door does not shut correctly and ice forms around door and frame
269641 05/03/2007 159761 2 109 M Repair exterior door to close properly
269657 05/03/2007 159793 1 119 O Provide safety film for mirror, replace mirror with tempered glass, safety glass, or stainless steel mirror, or remove and prohibit mirror
269656 05/03/2007 159791 1 128 O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
269654 05/03/2007 159787 1 130 O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
269649 05/03/2007 159777 1 132 O Prohibit plugging surge protector into extension cord, plug each directly into a wall outlet
269648 05/03/2007 159775 1 132B O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
269650 05/03/2007 159779 1 133 O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
269682 05/03/2007 159842 1 202 O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
269683 05/03/2007 159846 1 203 O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
269678 05/03/2007 159835 1 205 O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
269676 05/03/2007 159832 1 207 O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
269674 05/03/2007 159828 1 207 O Prohibit orange 13A extension cord or replace with minimum 15A cord
269671 05/03/2007 159823 1 210 O Prohibit plugging surge protector into extension cord into extension cord, plug each directly into a wall outlet
269673 05/03/2007 159825 1 211 O Prohibit plugging surge protector into surge protector, plug surge protector directly into a wall outlet
269670 05/03/2007 159821 1 214 O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
269668 05/03/2007 159817 1 214 O Prohibit plugging surge protector into surge protector, plug each directly into a wall outlet
269667 05/03/2007 159815 1 215 O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
269665 05/03/2007 159809 1 216 O Prohibit multi outlet extension cord at media cart or replace with minimum 15A single outlet cord
269666 05/03/2007 159812 1 219 O Prohibit plugging surge protector into extension cord at media cart, plug surge protector directly into a wall outlet
269642 05/03/2007 159763 2 101 O Prohibit plugging surge protector into extension cord, plug surge protector directly into a wall outlet
269643 05/03/2007 159765 2 102 O Prohibit plugging surge protector into extension cord, plug surge protecor directly into a wall outlet
269647 05/03/2007 159773 1 011 C Provide engineers evaluation of cracked concrete around fire doors adjacent to 1-135 and repair according to engineer's recommendation
269684 05/03/2007 159849 1 193 MS Provide current inspection tag for fire extinguisher
269675 05/03/2007 159830 1 207 OS Prohibit running electrical cord under carpet
269639 05/03/2007 159757 2 181 OS Prohibit charging batteries in room
269640 05/03/2007 159759 2 181 OS Prohibit storage of flammable materials (baseboard stripper)
230053 02/08/2007 83016 1 170 M Provide current inspection tag for elevator (dated 2002)
239772 02/08/2007 98931 1 206A M Secure sink to wall
239474 02/08/2007 98372 1 293 M Secure loose outside air intake ductwork to wall
239788 02/08/2007 98968 2 103B M Replace missing escutcheon on fire sprinkler head
239787 02/08/2007 98966 2 180 M Replace missing escutcheon on fire sprinkler head
239478 02/08/2007 98382 2 191 M Provide a fire sprinkler head wrench in the spare fire sprinkler head box
239483 02/08/2007 98393 2 192 M Repair leaking hot water tank drain
197667 02/08/2007 63564 2 192 M Provide current state inspection tag for boiler
230072 02/08/2007 83057 1 122 C Provide signage indicating room name at appropriate height with raised and Braille characters
230025 02/08/2007 82954 1 129B C Relocate fire sprinkler head from above cabinets to provide proper coverage for room or remove cabinets
239477 02/08/2007 98379 1 194 MS Provide current inspection tag for fire sprinkler system. Old tag has date and signature whited out and signed over. Provide a new tag.
239476 02/08/2007 98377 2 191 MS Provide current inspection tag for fire sprinkler system. Old tag has date and signature whited out and signed over. Provide a new tag.
239766 09/28/2005 98923 1 127B M Secure sink to wall
239767 09/28/2005 98925 1 127B M Repair deteriorated wall finish at sink
239773 09/28/2005 98933 1 128B M Determine cause of water damaged ceiling tiles and replace tiles
239786 09/28/2005 98964 1 129B M Secure loose light switch. Replace missing screw in switch plate
239768 09/28/2005 98927 1 134A M Secure sink to wall
230027 09/28/2005 82958 1 135C M Adjust curtains in CCTV studio so top of curtains is a minimum 18" below the ceiling to allow fire sprinkler coverage behind curtain
239479 09/28/2005 98384 1 194 M Provide a fire sprinkler head wrench in the spare fire sprinkler head box
239785 09/28/2005 98962 1 194 M Secure loose 1" copper drain line that runs to floor drain
239779 09/28/2005 98945 1 194 M Label room ROOF ACCESS
239769 09/28/2005 98928 1 203A M Secure sink to wall
239770 09/28/2005 98929 1 205C M Secure sink to wall
239771 09/28/2005 98930 1 205D M Secure sink to wall
230100 09/28/2005 83116 1 205D M Repair lock to unlock properly from the outside
239482 09/28/2005 98391 1 206A M Repair lock to unlock properly from the outside
239781 09/28/2005 98951 1 207 M Repair GFCI outlet at sink
239783 09/28/2005 98958 1 210A M Anchor toilet to floor
239481 09/28/2005 98389 1 217C M Repair deteriorated wall finish at sink and caulk sink to wall
197666 09/28/2005 63552 1 217D M Repair lock to unlock properly from the outside
239778 09/28/2005 98943 1 280 M Label room ROOF ACCESS
239475 09/28/2005 98374 2 182 M Determine cause of water damaged ceiling tiles and replace tiles
239780 09/28/2005 98948 1 118 O Remove storage on top shelf to keep area within 18" of automatic fire sprinkler heads clear and unobstructed
239774 09/28/2005 98935 00 0000 MS Provide current inspection tags for all fire extinguishers on campus
230052 09/28/2005 83012 00 9599 MS Replace broken knox padlock on double gates adjacent to marquis (broken lock is in principal's secretary's office)
230037 09/28/2005 82979 2 109 MS Provide current inspection tag for fire (hood) suppression system
239777 09/28/2005 98941 1 101 FS Provide certification that fire alarm system has been tested and is fully operational. System has a current tag, the panel indicates normal but the annunciator map indicates system trouble
239480 09/28/2005 98387 1 135C FS Secure heat detector to ceiling
239782 09/28/2005 98955 1 180 FS Remove masking from heat detector
230019 04/22/2005 82941 00 0000 M Repair exhaust fans in bathrooms throughout campus
230015 04/22/2005 82933 00 9599 M Provide locks on gates of fence enclosures at fire department OS&Y valves
230018 04/22/2005 82939 1 001 M Determine cause of water damaged ceiling tiles and replace tiles at 2nd floor
230061 04/22/2005 83031 1 119 M Replace missing escutcheon on fire sprinkler head
230071 04/22/2005 83054 1 128B M Determine cause of water damaged ceiling tiles and replace tiles
230042 04/22/2005 82989 1 130 M Determine cause of water damaged ceiling tiles and replace tiles
230022 04/22/2005 82948 1 132A M Replace rusted escutcheon on fire sprinkler head
230028 04/22/2005 82960 1 135 M Replace missing escutcheon on fire sprinkler head outside 1-135C
230029 04/22/2005 82963 1 135F M Secure falling escutcheon on fire sprinkler head
230043 04/22/2005 82994 1 181 M Replace broken and missing ceiling tiles
230055 04/22/2005 83020 1 190 M Secure loose escutcheon on fire sprinkler head
230039 04/22/2005 82983 1 193 M Clean mold from walls in mechanical room
230044 04/22/2005 82996 1 193A M Replace missing ceiling tiles
230004 04/22/2005 82909 1 194 M Adjust door to latch properly
197663 04/22/2005 63546 1 195 M Eliminate ants
230090 04/22/2005 83095 1 202A M Relocate shelving to opposite wall to allow fire sprinkler head to provide full coverage
230083 04/22/2005 83081 1 202B M Secure loose escutcheon on handicapped grab bar
230084 04/22/2005 83083 1 202B M Modify lock to unlock properly from the outside
230109 04/22/2005 83133 1 206A M Repair lock to unlock properly from the outside
230085 04/22/2005 83085 1 212 M Replace missing escutcheons on fire sprinkler heads (x3)
230086 04/22/2005 83087 1 212 M Repair broken, hanging window blinds
230092 04/22/2005 83099 1 212B M Relocate shelves from under fire sprinkler head
230114 04/22/2005 83143 1 212C M Relocate shelving away from fire sprinkler head
230088 04/22/2005 83091 1 214 M Replace missing escutcheons on fire sprinkler heads (x2)
230107 04/22/2005 83130 1 215 M Replace missing escutcheons on fire sprinkler heads (x3)
230095 04/22/2005 83105 1 218B M Remove paint from fire sprinkler head
230096 04/22/2005 83107 1 219B M Relocate shelving away from fire sprinkler head
230082 04/22/2005 83079 1 219B M Secure loose escutcheon on fire sprinkler head
230010 04/22/2005 82920 1 281 M Replace missing ceiling tiles
230048 04/22/2005 83006 2 102B M Remove and prohibit hot plate
230049 04/22/2005 83009 2 102B M Secure loose escutcheon on fire sprinkler head
230017 04/22/2005 82937 2 106A M Replace missing escutcheon on fire sprinkler head
230058 04/22/2005 83026 2 107 M Repair water damaged wall finish adjacent to exterior door
230036 04/22/2005 82977 2 109 M Relocate metal shelf in alcove area outside 2-109G to opposite wall to allow full coverage for fire sprinkler head
230038 04/22/2005 82981 2 109 M Verify electrical reels above ceiling are UL rated and hardwired above ceiling
230002 04/22/2005 82904 2 109D M Lubricate emergency release knob in walk-in freezer to turn
230000 04/22/2005 82898 2 109D M Replace missing escutcheon on fire sprinkler head
230035 04/22/2005 82975 2 109E M Determine cause of water damaged ceiling tiles and replace tiles
230077 04/22/2005 83066 2 111 M Replace bulbs in explosion proof light fixtures
230078 04/22/2005 83069 2 111 M Relocate light switches for explosion proof light fixtures from 2-195 to 2-111 so switches are readily accessible
230056 04/22/2005 83022 2 181 M Determine cause of water damaged ceiling tiles and replace tiles
230074 04/22/2005 83061 2 194 M Repair emergency lighting
230076 04/22/2005 83063 2 194 M Provide current inspection on log for generator (indicate an inspection after the hurricanes)
230059 04/22/2005 83028 1 119A O Remove storage within 18" of fire sprinkler head
230065 04/22/2005 83042 1 120 O Remove and prohibit paper covering window in door
230062 04/22/2005 83036 1 121 O Remove and prohibit paper covering window in door
230064 04/22/2005 83039 1 121 O Remove and prohibit combustible (residential) sofa and chair
230020 04/22/2005 82944 1 127 O Replace bulbs in emergency light fixture
230069 04/22/2005 83050 1 128A O Remove decorations covering sign indicating room name and number
230024 04/22/2005 82952 1 129 O Provide verification that written permission from principal has been provided to keep rabbit in the classroom and that all required safety precautions are being followed and prohibit rabbit running loose in classroom at all times students are present
230023 04/22/2005 82950 1 129A O Maintain storage room in an orderly manner
230021 04/22/2005 82946 1 132B O Remove storage within 18" of fire sprinkler head
230093 04/22/2005 83101 1 203 O Remove and prohibit paper covering window in door
230094 04/22/2005 83103 1 203 O Prohibit plugging surge protector to extension cord
230116 04/22/2005 83146 1 206 O Prohibit plugging surge protector into extension cord
230091 04/22/2005 83097 1 214 O Replace bulbs in emergency light fixture
230087 04/22/2005 83089 1 214 O Prohibit plugging surge protector to surge protector
230099 04/22/2005 83112 1 215 O Prohibit plugging surge protector into extension cord
230089 04/22/2005 83093 1 215A O Remove storage within 18" of fire sprinkler head
230106 04/22/2005 83126 1 216 O Prohibit plugging surge protector into extension cord and prohibit use of 13A extension cord
230104 04/22/2005 83122 1 217 O Prohibit plugging surge protector into extension cord and prohibit use of 13A extension cord
230097 04/22/2005 83110 1 219 O Remove and prohibit combustible beanbag chairs
230034 04/22/2005 82973 2 101A O Maintain storage room in an orderly manner
230032 04/22/2005 82969 2 102 O Eliminate extension cord or replace with minimum 15A cord and prohibit use of cord with multi-outlet end
230047 04/22/2005 83003 2 102A O Maintain storage room in an orderly manner
230030 04/22/2005 82965 2 104 O Prohibit plugging surge protector to surge protector
230001 04/22/2005 82901 2 109D O Remove thermostat hanging on fire sprinkler head
230067 04/22/2005 83044 2 110 O Plug copy machine directly into electrical outlet (do not use extension cord)
230057 04/22/2005 83024 2 181 O Remove storage within 18" of fire sprinkler head
230073 04/22/2005 83059 2 181C O Remove excessive storage from top shelf
230007 04/22/2005 82912 3 102 O Keep bathroom clean and sanitary
230008 04/22/2005 82915 3 103 O Keep bathroom clean and sanitary
197660 04/22/2005 63543 1 193 C Provide signage indicating room number at appropriate height with raised and Braille characters (Never provided)
197662 04/22/2005 63545 1 194 C Provide signage indicating room number at appropriate height with raised and Braille characters
230033 04/22/2005 82971 2 101 C Provide sign indicating maximum occupancy adjacent to main entrance
230031 04/22/2005 82967 2 181 MS Immediately connect loose dryer vent
230054 04/22/2005 83018 1 118 OS Remove storage within 18" of fire sprinkler head
230026 04/22/2005 82956 1 134 OS Prohibit wedging open corridor door
230113 04/22/2005 83140 1 210 OS Prohibit blocking open corridor door
230111 04/22/2005 83137 1 211 OS Prohibit use of candles
230009 04/22/2005 82918 1 281 OS Prohibit recharging batteries in room
230046 04/22/2005 83000 2 102A OS Prohibit storage of flammable paint thinner and sealant
230079 04/22/2005 83073 2 110 OS Provide clear path from exterior door to gate for fence enclosure for electrical transformer
230080 04/22/2005 83075 2 110 OS Provide clear access to fire extinguisher
230081 04/22/2005 83077 2 110 OS Provide clear access to fire sprinkler test valve
230016 01/19/2005 82935 00 9599 M Label fire department standpipe connections and buildings served
197658 01/19/2005 63534 1 001 M Fasten all loose door seals on all exterior doors
197659 01/19/2005 63541 1 136 M Secure hanging wires from junction box in ceiling
230102 01/19/2005 83119 1 217C M Repair lock to unlock properly from the outside
197664 01/19/2005 63550 1 215A C Provide signage indicating room name and number at appropriate height with raised and Braille characters (Never provided)
197665 01/19/2005 63551 1 215B C Provide signage indicating room name and number at appropriate height with raised and Braille characters (Never provided)
197668 01/19/2005 63567 2 9599 C Provide protection for gas line outside and adjacent to 2-194
197657 01/19/2005 63533 00 0000 FS Provide certification that fire alarm system has been tested and is fully operational (Tag dated 01/03)