Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
392461 01/31/2018 426817 1 0000 M Repair exhaust fan in second floor bathrooms:1-201B, 1-201C, 1-202A, 1-203A, 1-204B, 1-205B, 1-206A, 1-207B, 1-208B, 1-209A and 1-216A
406889 01/31/2018 457998 1 0000 M Repair exhaust fans in first floor bathrooms in rooms 1-129A, 1-134A, 1-136A, 1-137A, 1-139A, 1-141A, 1-147H, 1-147K
406890 01/31/2018 458000 1 0000 M Repair exhaust fans in second floor bathrooms 1-215A, 1-217A, 1-217B, 1-221A, 1-221B
406923 01/31/2018 458067 1 008 M Adjust smoke doors at bottom of stairs to close properly (doors hit each other when closing)
406902 01/31/2018 458026 1 121 M Secure loose toilet seat
406911 01/31/2018 458045 1 127A M Secure loose toilet seat
406924 01/31/2018 458072 1 132B M Provide dated flame resistance certification for CCTV studio curtains
406915 01/31/2018 458053 1 138 M Adjust water flow on drinking fountain (very small amount of water comes out of spout)
406918 01/31/2018 458057 1 138 M Determine cause of water damaged ceiling tiles above teacher's desk and replace tiles
406920 01/31/2018 458063 1 140 M Determine cause of water damaged ceiling tiles in front of white board and replace tiles
406925 01/31/2018 458074 1 147H M Secure loose toilet seat
406904 01/31/2018 458030 1 150 M Determine cause of water damaged ceiling tiles and replace tiles
406905 01/31/2018 458032 1 151 M Determine cause of water damaged ceiling tiles and replace tiles
406903 01/31/2018 458028 1 152 M Determine cause of water damaged ceiling tiles and replace tiles
406909 01/31/2018 458042 1 192 M Repair water leaking from air conditioning unit AHU4 to ensure it operates as designed (water is standing on the floor from leak
406927 01/31/2018 458078 1 199 M Provide cover on exposed electrical junction box above electric panel 1HA
406928 01/31/2018 458080 1 199 M Repair emergency lighting
406931 01/31/2018 458088 1 199 M Secure bare electrical wiring hanging below A/C unit at ceiling
406929 01/31/2018 458082 1 199A M Repair emergency lighting in generator room
406926 01/31/2018 458076 1 199C M Make necessary repairs to fire sprinkler system as indicated on inspection report (System was red tagged during annual inspection April 2017)
406907 01/31/2018 458034 1 199F M Repair water leaking from air conditioning unit AHU17-1 to ensure it operates as designed (water is standing on floor)
406908 01/31/2018 458039 1 199F M Repair emergency lighting
406940 01/31/2018 458106 1 205 M Determine cause of water damaged ceiling tiles at windows and replace tiles
406941 01/31/2018 458108 1 206 M Repair drinking fountain to shut off properly (water does not shut off when activation knob is released)
406939 01/31/2018 458104 1 215 M Secure loose activation knob on drinking fountain
406938 01/31/2018 458102 1 215A M Secure and caulk sink to wall to provide impervious wall
406936 01/31/2018 458098 1 217 M Repair broken window blinds
406934 01/31/2018 458094 1 218 M Secure loose activation knob on drinking fountain
406933 01/31/2018 458092 1 221 M Repair loose activation knob drinking fountain
406945 01/31/2018 458116 2 001 M Repair emergency lighting in corridor at ramp
406949 01/31/2018 458124 2 001 M Repair emergency lighting in corridor adjacent to 2-181 janitor's closet
406944 01/31/2018 458114 2 104 M Repair emergency lighting
406947 01/31/2018 458120 2 105 M Repair emergency lighting at entrance door
406948 01/31/2018 458122 2 109 M Repair emergency lighting at entrance door
406946 01/31/2018 458118 2 191 M Repair emergency lighting in electric room
406942 01/31/2018 458110 3 101 M Determine cause of water damaged ceiling tiles and replace tiles
406943 01/31/2018 458112 P 6081 M Provide non-slip impervious floor surface in bathroom (seam in flooring runs under stool)
406900 01/31/2018 458022 1 105 O Keep area within 18 inches of fire sprinkler head clear and unobstructed on top shelf of storage rack
406932 01/31/2018 458090 1 222 O Prohibit plugging extension cord into surge protector under desk
373201 01/31/2018 385098 00 0000 C Sloped ground at east property line is eroding onto the basketball courts. Stabilize the bank to eliminate erosion and clean sand off of basketball courts
406930 01/31/2018 458085 1 199B MS Check on possible natural gas leak in boiler room to eliminate hazardous condition (strong natural gas odor was present during inspection of room, maintenance was notified)
406937 01/31/2018 458100 1 215 MS Provide current inspection tag for fire extinguisher
406935 01/31/2018 458096 1 217 MS Provide current inspection tag for fire extinguisher
406901 01/31/2018 458024 1 190 OS Remove storage from electrical room
256416 01/31/2018 134056 1 0000 N/A No violations observed
256417 01/31/2018 134058 2 0000 N/A No violations observed
256418 01/31/2018 134060 3 0000 N/A No violations observed
256415 01/31/2018 134054 P 6081 N/A No violations observed
256414 01/31/2018 134052 P 6083 N/A No violations observed
256413 01/31/2018 134050 P 6084 N/A No violations observed
271116 01/31/2018 163156 P 6233 N/A No violations observed
392465 08/22/2017 426826 1 192A M Repair air conditioning system above door to ensure it operates as designed
392458 11/17/2016 426810 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable - Old certificate in 1-199A
392459 11/17/2016 426813 00 9599 M Repair or replace bent sign for handicapped parking spot at kitchen parking area
392460 11/17/2016 426815 1 0000 M Repair exhaust fan in first floor bathrooms:1-120, 1-121, 1-122 and 1-123
392439 11/17/2016 426770 1 0000 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report dated 3.16.16 - riser located in 1-199C
392466 11/17/2016 426828 1 192 M Pad and mark corners of air handler duct which are lower than 6 feet 8 inches above path to back of mechanical room
392457 11/17/2016 426808 1 199 M Repair air conditioning system to ensure it operates as designed - main electrical room is very hot
392450 11/17/2016 426793 1 199E M Repair emergency lighting
392440 11/17/2016 426772 1 204 M Repair operating button on drinking spout to work properly
392467 11/17/2016 426831 1 280 M Repair ventilation fan in custodial room
392446 11/17/2016 426785 2 102 M Remove hedges outside emergency escape window
392447 11/17/2016 426787 2 104 M Remove hedges outside emergency escape window
392448 11/17/2016 426789 2 108 M Remove hedges outside emergency escape window
392449 11/17/2016 426791 2 110 M Remove hedges outside emergency escape window
392453 11/17/2016 426800 P 6083 M Adjust back exterior door to latch properly
392442 11/17/2016 426776 1 205 O Remove and prohibit excessive flammable black vinyl sheathing covering board adjacent to computer stations, adjacent to writing board, in corridor adjacent to door and on corridor door
392469 11/17/2016 426835 1 219 O Prohibit running electrical and communications cords across floor adjacent to teacher desk to eliminate trip hazard. You may rearrange furniture and equipment to block the path where cords are located
392454 11/17/2016 426802 P 6083 O Remove and prohibit use of glass mirror in classroom - currently mounted on bathroom door
392456 11/17/2016 426806 1 0000 MS Repair door lock hardware to work properly at chiller compound - lock sticks
392462 11/17/2016 426820 1 138 MS Provide current inspection tag for fire extinguisher
392455 11/17/2016 426804 1 146B MS Secure loose lock cylinder to door
392451 11/17/2016 426795 1 199E MS Provide current inspection tag for fire extinguisher - Dated Dec. 2014
392452 11/17/2016 426797 1 199F MS Provide current inspection tag for fire extinguisher - Dated Dec. 2014
392441 11/17/2016 426774 1 210 MS Secure loose lever on corridor door
392443 11/17/2016 426778 1 215 MS Provide current inspection tag for fire extinguisher - Dated Oct. 2013
392444 11/17/2016 426780 1 217 MS Provide current inspection tag for fire extinguisher - Dated Oct. 2013
392445 11/17/2016 426783 2 001 MS Recharge fire extinguisher in corridor adjacent to 2-190
392464 11/17/2016 426824 1 136 OS Relocate storage unit behind bathroom door - currently prohibiting door from opening 90 degrees
392463 11/17/2016 426822 1 139A OS Remove large cardboard box from bathroom
392468 11/17/2016 426833 1 218 OS Relocate black storage cabinets adjacent to corridor door - cabinets projects into clear width of corridor door
378411 02/18/2016 396485 1 116 M Determine cause of water damaged ceiling tiles and replace tiles
378337 02/18/2016 396334 1 138A M Replace missing escutcheon on fire sprinkler head
378393 02/18/2016 396450 1 146C M Repair hole in wall behind door in accessible stall
378394 02/18/2016 396452 1 146C M Provide door stop in accessible stall
378408 02/18/2016 396479 1 170 M Provide current inspection tag for elevator
378382 02/18/2016 396425 1 196 M Mount fire extinguisher at maximum five feet above floor
378384 02/18/2016 396431 1 199 M Repair air conditioning system to ensure that it operates as designed
378386 02/18/2016 396435 1 199 M Repair door to 1-199A close and latch properly
378392 02/18/2016 396448 1 199E M Repair door to close properly
378390 02/18/2016 396443 1 199F M Repair emergency lighting
378391 02/18/2016 396445 1 199F M Repair door to close and latch properly
378407 02/18/2016 396477 1 221B M Anchor toilet to floor
378409 02/18/2016 396481 1 290 M Refinish and repair rusty areas of ducts
378389 02/18/2016 396440 1 9599 M Remove tree growing at AC units adjacent to 1-199B
378400 02/18/2016 396463 2 001 M Repair rusty, deteriorated base wall finish at decorative glass block walls at east and west side of 2-001 corridor
378401 02/18/2016 396465 2 102 M Repair emergency lighting
378404 02/18/2016 396471 2 109 M Repair broken base along wall at exterior wall, repair damaged wall at exterior door
378402 02/18/2016 396467 2 110 M Adjust door closer to control speed of closing door
373251 02/18/2016 385209 3 104 M Covered play area structure is rusting. Some framing members have penetrations. Clean, repair and refinish
373063 02/18/2016 384806 P 6081 M Seal seam in bathroom flooring
378399 02/18/2016 396461 P 6083 M Repair emergency lighting at entrance door
378396 02/18/2016 396456 P 6233 M Secure hanging heat detector
378398 02/18/2016 396458 P 6233 M Repair emergency lighting at east door
378410 02/18/2016 396483 1 105 O Relocate storage to keep area within 18 inches of fire sprinkler head clear and unobstructed
378406 02/18/2016 396475 1 132G O Post sign indicating primary and secondary evacuation routes in contrasting colors
378338 02/18/2016 396336 1 138 O Prohibit green multi outlet extension cord at decorative tree or replace with minimum 15A single outlet extension cord
378412 02/18/2016 396488 1 198 O Clean sand piles on floor. If ants have returned generate work order for additional extermination
378405 02/18/2016 396473 2 109 O Remove and prohibit air freshener, plug in style
378339 02/18/2016 396338 1 009 MS Adjust smoke doors in first floor corridor adjacent to 1-008 stairs to close properly
378395 02/18/2016 396454 1 152 MS Provide current inspection tag for fire extinguisher
378383 02/18/2016 396429 1 199D MS Provide current inspection tag for fire extinguisher
378403 02/18/2016 396469 2 110 OS Prohibit hanging paper in front of emergency escape window
373250 09/01/2015 385206 00 0000 M Play court topping is coming up in several areas. Fill and seal these areas.
373193 09/01/2015 385082 1 198 M Eliminate ants in room
373061 04/17/2015 384802 1 147 M Modify Kitchen hood fire suppression system control box per inspection report. Repaired
373059 03/23/2015 384797 00 0000 M Repair leaking packing on domestic water backflows at south end of east property line
373200 03/23/2015 385096 00 0000 M Remove trees growing in chiller compound
373258 03/23/2015 385226 1 0000 M Seal open vertical joint on exterior wall at inside corner outside of 1-138 at north end of corridor 1-009
373194 03/23/2015 385084 1 146D M Secure sink to wall
373257 03/23/2015 385224 1 146F M Adjust stage door to exterior to latch properly
373262 03/23/2015 385234 1 147 M Clean Kitchen hood and leave tag indicating date cleaned. Last cleaning 9-25-13
373264 03/23/2015 385238 1 186 M Adjust flow of emergency eye wash.
373260 03/23/2015 385230 1 199A M Provide certification that all student occupied spaces have emergency lights and all are operable. Last certification 7-9-13
373191 03/23/2015 385078 1 199C M Secure flow switch box to 1st floor fire sprinkler riser
373192 03/23/2015 385080 1 199C M Provide current quarterly inspection tag for fire sprinkler system
373184 03/23/2015 385062 1 201A M Seal wall at sink to provide impervious wall finish
373197 03/23/2015 385090 1 203A M Caulk sink to wall
373198 03/23/2015 385092 1 203B M Anchor 1st shelf at entry to wall
373196 03/23/2015 385088 1 205 M Repair or replace drinking fountain that runs continually
373195 03/23/2015 385086 1 209A M Caulk sink to wall
373188 03/23/2015 385070 2 102B M Repair leaking toilet supply line
373186 03/23/2015 385066 2 107 M Repair emergency lighting
373185 03/23/2015 385064 2 108 M Determine cause of water damaged ceiling tiles and replace tiles at exterior wall
373265 03/23/2015 385240 2 110 M Repair emergency lighting
373249 03/23/2015 385203 3 0000 M Eliminate insect infestation in building 3. Ants and spiders
373253 03/23/2015 385215 3 102 M Repair leaking supply line for toilet
373254 03/23/2015 385217 3 102 M Adjust toilet flush length. Too long
373255 03/23/2015 385219 3 103 M Repair exhaust fan in bathroom
373252 03/23/2015 385211 3 104 M Repair drinking fountain that will not shut off
373202 03/23/2015 385100 P 0000 M Provide lock on gate of fencing around electrical equipment north of P-3 and P-1
373065 03/23/2015 384810 P 6083 M Repair emergency lighting at rear of unit
373066 03/23/2015 384812 P 6084 M Repair emergency lighting at front of unit
373067 03/23/2015 384814 P 6084 M Caulk sink to wall
373068 03/23/2015 384816 P 6233 M Repair emergency lighting at front of unit
373069 03/23/2015 384818 P 6233 M Secure hanging heat detector
373060 03/23/2015 384800 00 0000 O Provide name of Lead Crowd Manager who successfully completed the Crowd Management course as indicated in Bulletin # P-14808
373189 03/23/2015 385072 00 0000 O Remove and prohibit attaching paper to blinds. Paper is acceptable on the window or on a string line in front of the windows. Rooms 1-128, 1-139, 1-205, 1-207, 1-208, 1-209, 1-215, 1-216, 2-107 and 2-108
373064 03/23/2015 384808 P 6081 O Provide clear access to electrical panel
373247 03/23/2015 385197 00 0000 C Eliminate standing water on play courts. Mold on surface
373248 03/23/2015 385200 00 0000 C Eliminate standing water on covered play area
373199 03/23/2015 385094 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus
373256 03/23/2015 385222 1 008 MS Adjust fire door in corridor at 1-142 to latch properly
373266 03/23/2015 385242 1 008 MS Adjust fire door at top of stairs next to 1-280 to latch properly
373259 03/23/2015 385228 1 011 MS Adjust fire door at west end of corridor to latch properly
373263 03/23/2015 385236 1 186 MS Remove chain and padlock from gate to caged area in custodial receiving. Provide lock with thumb latch inside so you cannot be locked in caged area
373261 03/23/2015 385232 1 199A MS Prohibit hold open device on fire door to 1-199
373190 03/23/2015 385076 1 199D OS Provide clear access to fire extinguisher
373187 03/23/2015 385068 2 106 OS Prohibit hold open device on corridor door
352869 03/12/2014 340832 1 199F M Provide cover on open Neptronic box on air handler
352914 03/12/2014 340927 1 205 M Secure push button to top of drinking fountain
352906 03/12/2014 340911 00 0000 C Stabilize bank and fill eroded area east of the NE playground
352883 03/06/2014 340862 00 0000 M Remove dirt and sod to provide channel to catch basin to drain north parking lot at SW corner of parking lot
352888 03/06/2014 340873 1 0000 M Remove rebar pins holding concrete border in place for planting beds east of 1-151
352892 03/06/2014 340883 1 0000 M Replace cover for open box in grassed area north of 1-199B
352913 03/06/2014 340925 1 005 M Secure loose down rod to door at bottom of stairs
352879 03/06/2014 340852 1 102 M Adjust water flow for emergency eye wash - shower. Low flow
352880 03/06/2014 340854 1 102 M Repair inoperable intercom
352881 03/06/2014 340857 1 102 M Repair broken window blinds
352878 03/06/2014 340850 1 118 M Adjust door to latch properly
352886 03/06/2014 340869 1 121 M Secure loose seat on 1st toilet
352884 03/06/2014 340865 1 127A M Replace missing escutcheon on fire sprinkler head
352875 03/06/2014 340844 1 128 M Replace missing escutcheon on fire sprinkler head
352910 03/06/2014 340919 1 129 M Replace GFCI outlet that will not trip
352874 03/06/2014 340842 1 132A M Repair light fixtures
352885 03/06/2014 340867 1 139 M Replace left GFCI outlet that will not trip
352860 03/06/2014 340814 1 140 M Secure loose bracket for fire extinguisher and rehang extinguisher that is in room 1-138A
352864 03/06/2014 340822 1 146A M Caulk 2 toilets to wall
352865 03/06/2014 340824 1 146C M Caulk toilet to wall
352866 03/06/2014 340826 1 146C M Secure loose tile to wall behind handicapped toilet
352867 03/06/2014 340828 1 146C M Provide escutcheon for trap primer line at wall
352876 03/06/2014 340846 1 146F M Replace missing end cap on stage ramp handrail
352862 03/06/2014 340818 1 147 M Adjust kitchen hood fire suppression system nozzle to properly cover range or relocate range to be directly beneath suppression head
352861 03/06/2014 340816 1 147F M Replace missing escutcheon on fire sprinkler head
352919 03/06/2014 340939 1 170 M Provide current inspection tag for elevator
352870 03/06/2014 340834 1 192 M Anchor 4 corners of air handler
352895 03/06/2014 340889 1 192 M AHU 2 and AHU 4 have condensate leaking onto the air handlers and rusting them. Insulate chilled water lines to eliminate condensate dripping onto air handlers
352909 03/06/2014 340917 1 195 M Anchor 4 corners of air handler
352871 03/06/2014 340836 1 197 M Anchor 4 corners of air handler
352893 03/06/2014 340885 1 199 M Close open EMS box
352894 03/06/2014 340887 1 199 M Provide a latch for panel 1DA
352872 03/06/2014 340838 1 199C M Anchor 4 corners of air handler
352889 03/06/2014 340875 1 199E M Repair emergency lighting
352917 03/06/2014 340934 1 201 M Repair exhaust fan in bathroom
352916 03/06/2014 340931 1 201A M Caulk sink to wall
352915 03/06/2014 340929 1 203A M Caulk sink to wall
352922 03/06/2014 340945 1 216B M Caulk sink to wall
352920 03/06/2014 340941 1 217B M Caulk sink to wall
352926 03/06/2014 340953 1 218B M Secure loose door handle
352923 03/06/2014 340947 1 219A M Caulk sink to wall
352921 03/06/2014 340943 1 221B M Caulk sink to wall
352918 03/06/2014 340936 1 290 M Anchor air handler at 4 corners
352924 03/06/2014 340949 1 291 M Replace belt guard on outside air unit
352925 03/06/2014 340951 1 291 M Anchor air handler at 4 corners
352904 03/06/2014 340907 2 101 M Repair emergency lighting
352903 03/06/2014 340905 2 102B M Provide finish for new door
352902 03/06/2014 340903 2 105 M Repair emergency lighting
352898 03/06/2014 340895 2 107B M Repair leaking toilet supply line
352897 03/06/2014 340893 2 108 M Repair or replace leaking faucet
352896 03/06/2014 340891 2 108A M Caulk sink to wall
352900 03/06/2014 340899 2 190 M Anchor 4 corners of air handler
352901 03/06/2014 340901 2 190 M Repair emergency lighting
352899 03/06/2014 340897 2 191 M Repair emergency lighting
352877 03/06/2014 340848 3 101 M Repair air conditioning, not working since beginning of year
352907 03/06/2014 340913 3 101 M Repair exhaust fan in bathroom
352908 03/06/2014 340915 3 102 M Repair exhaust fan in bathroom
352868 03/06/2014 340830 P 0000 M Provide new locks on gates of fencing around electrical enclosure and lift station enclosure north of portables
352853 03/06/2014 340797 P 6081 M Exterior junction boxes are in contact with ground. Remove dirt from beneath boxes so that they are not in contact with ground
352854 03/06/2014 340799 P 6081 M Secure loose sink to wall in bathroom
352855 03/06/2014 340802 P 6083 M Exterior 12 inch by 12 inch junction box is in contact with ground. Remove dirt from beneath box so that it is not in contact with ground
352856 03/06/2014 340804 P 6084 M Exterior 12 inch by 12 inch junction box is in contact with ground. Remove dirt from beneath box so that it is not in contact with ground
352857 03/06/2014 340806 P 6084 M Caulk bathroom sink to wall
352858 03/06/2014 340808 P 6233 M Exterior junction boxes are in contact with ground. Remove dirt from beneath boxes so that they are not in contact with ground
352859 03/06/2014 340810 P 6233 M Determine cause of water damaged ceiling tiles and replace tiles at mate line
352911 03/06/2014 340921 1 132G O Post sign indicating evacuation routes
352905 03/06/2014 340909 1 193 O Prohibit running electrical cord through door opening
352882 03/06/2014 340859 1 003 C Provide illuminated exit sign on east side of smoke stop doors in corridor adjacent to 1-191. Center sign over door leaf
352912 03/06/2014 340923 1 005 MS Adjust fire door at bottom of stairs to latch properly
352863 03/06/2014 340820 1 146L MS Provide current inspection tag for fire extinguisher or remove unnecessary extinguisher
352887 03/06/2014 340871 1 151B OS Prohibit storage of flammable aerosol cans. Store in flammable storage cabinet
352873 03/06/2014 340840 1 199D OS Provide clear access to fire extinguisher and fire blanket
352890 03/06/2014 340877 1 199E CS Provide automatic fire sprinkler coverage for room. Plan does not indicate 2 hour walls. No sprinkler head in room
338487 09/12/2013 309534 1 199B M Complete repairs to hot water heater
338484 12/11/2012 309528 00 0000 M Provide current inspection logs for hot water heaters in the following rooms 1-184, 1-185, 2-181, 2-180
338501 12/11/2012 309564 1 013 M Adjust door closers on north exterior corridor doors to control speed of closing doors
338500 12/11/2012 309562 1 136 M Replace missing escutcheon on fire sprinkler head
338488 12/11/2012 309536 1 147 M Repair Blodgett oven (facing walk in cooler) which is not keeping temperature, per staff
338503 12/11/2012 309568 1 150 M Replace missing escutcheon on fire sprinkler head adjacent to cabinets
338504 12/11/2012 309570 1 171 M Provide current inspection tag for elevator
338485 12/11/2012 309530 1 186 M Adjust flow of emergency eye wash
338493 12/11/2012 309548 1 195 M Repair hole around water pipe in east wall
338511 12/11/2012 309585 1 205 M Repair drinking fountain, water wont turn off after use
338513 12/11/2012 309592 1 206A M Make repairs to bathroom, staff posted out of order sign on bathroom door
338514 12/11/2012 309594 1 206A M Secure sink to wall
338509 12/11/2012 309581 1 215A M Anchor toilet to floor
338495 12/11/2012 309552 2 001 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to 2-109
338498 12/11/2012 309558 2 104 M Repair emergency lighting
338494 12/11/2012 309550 2 105 M Repair rear door to close and latch properly
338497 12/11/2012 309556 2 108 M Determine cause of water damaged ceiling tiles and replace tiles in corner of room
338496 12/11/2012 309554 2 110 M Adjust door closer on corridor door to control speed of closing door
338491 12/11/2012 309544 P 6081 M Adjust door closer on entrance door to control speed of closing door
338489 12/11/2012 309539 P 6233 M Adjust door closers on front and rear doors to control speed of closing doors
338482 12/11/2012 309524 1 142 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
338483 12/11/2012 309526 1 142 O Remove and prohibit paper covering window in door
338481 12/11/2012 309522 1 144 O Prohibit white multi outlet electrical adaptor, prohibit plugging microwave and refrigerator into electrical adaptor, plug microwave and refrigerator directly into permanent electrical outlet
338508 12/11/2012 309579 1 215 O Prohibit white 13A multi outlet extension cord at teachers desk or replace with minimum 15A single outlet cord
338506 12/11/2012 309575 1 217 O Remove and prohibit paper covering window in door
338505 12/11/2012 309573 1 221 O Remove and prohibit paper covering window in door
338492 12/11/2012 309546 P 6081 O Provide clear access to electrical panel, blue vinyl sheet with pockets blocking electrical panel
338490 12/11/2012 309541 P 6233 O Remove and prohibit paper covering windows in doors
338580 12/11/2012 309748 1 132J C Provide signage indicating room name and number at appropriate height with raised and Braille characters for "new" office between 1-132G and 1-132E
338517 12/11/2012 309601 1 0000 MS Provide current annual inspection tags for fire sprinkler system
338499 12/11/2012 309560 1 007 MS Adjust smoke doors (2 sets) adjacent to 1-142 and 1-143 to close and latch properly
338512 12/11/2012 309588 1 008 MS Adjust fire doors at second floor landing to close and latch properly
338515 12/11/2012 309596 1 013 MS Adjust fire doors at second floor landing to close and latch properly
338502 12/11/2012 309566 1 152 MS Provide current inspection tag for fire extinguisher
338486 12/11/2012 309532 1 199C MS Provide current inspection tag for fire sprinkler system. Provide quarterly and annual inspection tags
338507 12/11/2012 309577 1 215 MS Recharge fire extinguisher
338516 12/11/2012 309598 1 105 OS Keep area within 18 inches of fire sprinkler head clear and unobstructed
338510 12/11/2012 309583 1 203 OS Maintain clear aisle to exit
312107 09/10/2012 251562 1 132B M Provide dated flame resistance label on blue curtain (Date on curtain: more than 5 yrs)
312106 09/10/2012 251560 1 146F M Provide dated flame resistance label on all stage curtains (Date on curtains: more than 5 yrs)
312108 09/10/2012 251564 1 132B C Provide records that stage rigging has been inspected and conforms to required safety standards
327642 01/30/2012 285982 2 0000 M Provide sod to stabilize area adjacent to 2-101 exterior door and east gate in fenced playground. Sweep excessive sand to eliminate slip hazard
327619 01/19/2012 285935 1 127A M Secure sink to wall
327621 01/19/2012 285939 1 136A M Secure sink to wall
327620 01/19/2012 285937 1 141A M Secure sink to wall
327626 01/19/2012 285949 1 146A M Secure sink to wall in girls bathroom
327585 01/19/2012 285866 1 151 M Determine cause of water damaged ceiling tiles and replace tiles
327590 01/19/2012 285872 1 186 M Adjust water flow for emergency eye wash
327600 01/19/2012 285895 1 210 M Secure ceiling tile in place adjacent to corridor door
327591 01/19/2012 285878 1 216A M Replace missing escutcheon on fire sprinkler head
327613 01/19/2012 285924 2 108 M Repair emergency lighting
327618 01/19/2012 285932 P 6233 M Secure sink to wall
327598 01/19/2012 285890 1 208 O Replace missing evacuation map
271159 01/19/2012 163242 00 0000 C Provide suitable area for recharging floor cleaning machines
327583 01/19/2012 285859 1 146L MS Provide current inspection tag for fire extinguisher
327623 01/19/2012 285942 1 185 MS Adjust door to latch properly
327584 01/19/2012 285862 1 199C MS Provide current inspection tag for fire sprinkler system - tagged quarterly 5/23/11
327593 01/19/2012 285880 1 215 MS Provide current inspection tag for fire extinguisher
327594 01/19/2012 285883 1 217 MS Provide current inspection tag for fire extinguisher
327587 01/19/2012 285869 1 186 OS Prohibit charging batteries for floor cleaning machines in room
311649 10/28/2011 250544 1 221 M Replace missing panels for vertical blinds - see teacher
311604 10/28/2011 250453 2 001 M Repair emergency lighting in corridor adjacent to 2-104
311600 10/28/2011 250445 P 6083 M Adjust back door to latch properly
311599 10/28/2011 250442 P 6084 M Adjust back door to latch properly
311611 10/28/2011 250469 1 007 MS Adjust fire doors in corridor adjacent to 1-140 to latch properly
311632 11/17/2010 250506 00 0000 M Re-paint all building numbers on exterior wall to be visible to fire rescue - current numbers are approx. 4 inches high. Numbers need to be 6 to 12 inch high & one inch wide stroke
311635 11/17/2010 250514 00 0000 M Re-number property address on marquee - Current numbers are approx. 4 inches high. Numbers need to be 6 to 12 inch high & one inch side stroke
311652 11/17/2010 250552 00 9599 M Secure loose top of chain link fencing at east side of playground adjacent to 2-101
311653 11/17/2010 250554 00 9599 M Provide padlock and keep gate to chain link fenced enclosure around retention area at NW corner of Bldg. 2 locked to prohibit unauthorized access
311709 11/17/2010 250673 00 9599 M Repair bent and loose stop sign at west end of parking lot adjacent to Bldg. 2 (X2)
311716 11/17/2010 250690 00 9599 M Secure loose bottom of chain link fencing at SW corner of playground adjacent to 2-109
311614 11/17/2010 250475 1 107 M Chain helium cylinder to wall
311616 11/17/2010 250480 1 130 M Adjust door to latch properly
311615 11/17/2010 250477 1 132F M Determine cause of water damaged ceiling tiles and replace tiles
311607 11/17/2010 250459 1 147 M Adjust two burners cook top to be under hood fire suppression nozzle
311608 11/17/2010 250462 1 147C M Lubricate emergency disconnect knob in cooler to turn easily
311627 11/17/2010 250502 1 151 M Relocate wall bracket for fire extinguisher adjacent to corridor door to be on opposite side adjacent to paper towel dispenser
311610 11/17/2010 250466 1 186B M Secure exhaust fan cover to ceiling
311637 11/17/2010 250521 1 199 M Provide cover on exposed electrical junction box above exterior door
311628 11/17/2010 250504 1 199F M Repair air handler to eliminate water leak
311651 11/17/2010 250550 1 203A M Repair or replace noisy exhaust fan in bathroom
311638 11/17/2010 250523 1 207 M Secure loose drinking spout
311641 11/17/2010 250529 1 218 M Secure loose faucet to sink
311639 11/17/2010 250526 1 221 M Secure loose faucet to sink
311650 11/17/2010 250547 1 221 M Lubricate hinges on door to bathroom vestibule to open and close easily
311606 11/17/2010 250457 2 109 M Repair emergency lighting
311602 11/17/2010 250449 3 101 M Replace missing screen for window
311603 11/17/2010 250451 3 101 M Repair light fixture to work proplrly - see PE teacher
311601 11/17/2010 250447 3 103 M Secure exhaust fan cover to ceiling
311612 11/17/2010 250471 1 134 O Remove and prohibit air freshener adjacent to teacher's desk
311613 11/17/2010 250473 1 134 O Maintain house keeping by removing boards which were covering wires behind teacher's printer station
311647 11/17/2010 250538 1 222 O Eliminate white extension cord with multiple outlet end - currently plugged into a surge protector under window
311636 11/17/2010 250519 1 199 MS Remove maintenance storage from electrical room
311710 11/17/2010 250676 1 134 OS Prohibit use of wedge to hold fire door in open position
311643 11/17/2010 250533 1 213 OS Prohibit use of chair to hold fire door in open position
311605 11/17/2010 250455 2 108 OS Remove all storage to keep area clear at emergency escape window
231360 11/17/2010 85692 00 0000 CS Provide fire rated construction as required by table 600 for enclosed courtyard between 1-146 and 1-152 (waived by architect AG)
304388 04/19/2010 234537 00 9599 M Remove tree stake (not in use) to prevent tripping hazard, adjacent to bicycle parking area and exterior stairs west of building 1
300613 04/19/2010 226318 00 9699 M Make manhole cover level with turf adjacent to play area/covered PE area
304213 04/19/2010 234120 1 004 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to 1-005
304385 04/19/2010 234531 1 009 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to cafeteria doors and 1-146
304386 04/19/2010 234533 1 102 M Secure loose escutcheons on fire sprinkler heads
304387 04/19/2010 234535 1 102A M Secure loose escutcheon on fire sprinkler head
304212 04/19/2010 234118 1 120 M Replace missing escutcheon on fire sprinkler head
304373 04/19/2010 234507 1 132B M Fill hole in ground and remove post sticking out of ground adjacent to exterior door of 1-132B
304356 04/19/2010 234471 1 146 M Replace missing escutcheons on fire sprinkler heads
304353 04/19/2010 234464 1 147 M Repair leaking fixture for hood cleaning command center, located in wall cabinet across from dish room (Gaylord Ventillation Control Cabinet)
304352 04/19/2010 234454 1 147A M Repair exhaust fan/hood at dishwashing area, staff reports that fan does not work properly
304359 04/19/2010 234477 1 152 M Determine cause of water damaged ceiling tiles and replace tiles
304360 04/19/2010 234479 1 152 M Replace missing escutcheon on fire sprinkler head, secure loose escutcheon on fire sprinkler head
304361 04/19/2010 234482 1 152 M Remove orange safety clip from fire sprinkler head
304300 04/19/2010 234322 1 186 M Repair hole in wall below white board
304290 04/19/2010 234294 1 198 M Adjust fire sprinkler head so deflector projects a minimum 1" below escutcheon
304355 04/19/2010 234468 1 199 M Verify proper function of emergency light, could not reach test button
304354 04/19/2010 234466 1 199A M Verify proper function of emergency light, could not reach test button
304382 04/19/2010 234525 1 202A M Replace missing escutcheon on fire sprinkler head
304383 04/19/2010 234527 1 204B M Replace missing escutcheon on fire sprinkler head
304379 04/19/2010 234519 1 217 M Determine cause of water damaged ceiling tiles and replace tiles
304376 04/19/2010 234513 1 218 M Replace damaged (rusty) fire sprinkler head
304368 04/19/2010 234497 2 108 M Repair emergency lighting
304370 04/19/2010 234501 2 109 M Repair corridor door to close properly
304367 04/19/2010 234494 3 102 M Secure loose exhaust fan cover in ceiling
290414 04/19/2010 204459 3 104 M Remove rust and repaint rusted areas under P.E. Pavilion roof
304365 04/19/2010 234490 P 6233 M Determine cause of water damaged ceiling tiles and replace tiles
304215 04/19/2010 234124 1 132H O Prohibit plugging surge protector into (orange) extension cord in office located between 1-132G and 1-132E
304286 04/19/2010 234286 1 142 O Remove and prohibit air freshener
304287 04/19/2010 234288 1 142 O Prohibit white 13A extension cord or replace with minimum 15A single outlet cord
304288 04/19/2010 234290 1 142 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
304289 04/19/2010 234292 1 145A O No access was available to this room. Please be prepared to access this room during the report review meeting
304357 04/19/2010 234473 1 150 O Prohibit plugging surge protector into multi outlet extension cord, plug into permenent electrical outlet, prohibit multi outlet extension cord
304358 04/19/2010 234475 1 150 O Prohibit running cords across floor to prevent tripping hazard
304363 04/19/2010 234486 1 151C O Prohibit brown 13A extension cord or replace with minimum 15A cord
304384 04/19/2010 234529 1 206 O Prohibit white 13A extension cord or replace with minimum 15A cord
304372 04/19/2010 234505 2 9699 O Clean mold and moss from kindergarten play area mat to prevent slipping hazard
231337 04/19/2010 85644 1 013 C Provide intermediate handrail for stairs greater than 88" wide (stairs are 92"+) (4/16/10 Waived by Victor Chodora, stairs measured 88")
304216 04/19/2010 234127 1 132H C Provide signage indicating room name and number (for new office) at appropriate height with raised and Braille characters
290954 04/19/2010 205599 P 0000 C Provide impervious wall finish for minimum six foot height in bathrooms
304375 04/19/2010 234511 P 6083 C Provide non-slip impervious floor surface in bathroom
304374 04/19/2010 234509 P 6084 C Provide non-slip impervious floor surface in bathroom
304285 04/19/2010 234283 1 007 MS Adjust fire door adjacent to 1-143 to close and latch properly
304291 04/19/2010 234296 1 146L MS Provide current inspection tag for fire extinguisher
304362 04/19/2010 234484 1 152 MS Provide current inspection tag for fire extinguisher
304292 04/19/2010 234298 1 186 MS Provide current inspection tag for fire extinguisher
304380 04/19/2010 234521 1 215 MS Provide current inspection tag for fire extinguisher
304378 04/19/2010 234517 1 217 MS Provide current inspection tag for fire extinguisher
304381 04/19/2010 234523 1 290 MS Provide current inspection tag for fire extinguisher
304214 04/19/2010 234122 1 128 OS Prohibit flammable (green) plastic table cloth
304364 04/19/2010 234488 1 151A OS Prohibit storage on kiln
304377 04/19/2010 234515 1 218 OS Remove and prohibit candles
304371 04/19/2010 234503 2 110 OS Prohibit hold open devices on fire door
304369 04/19/2010 234499 2 110 OS Remove and prohibit paper hanging in front of emergency window
304366 04/19/2010 234492 P 6081 OS Maintain clear aisle to exit doors
304351 04/19/2010 234451 1 186 CS Provide adequate egress from cage area to allow safe evacuation
231354 04/19/2010 85680 1 199E CS Eliminate transfer grill between electrical room and kiln room (1-151A) to provide/maintain fire separation between electrical room and kiln room and provide adequate return air for electrical room
290421 11/17/2009 204472 1 171 M Provide current inspection tag for elevator
290423 11/17/2009 204476 P 6083 M Repair rear door to close properly (drags on threshold)
290412 11/17/2009 204455 00 0000 C Provide exterior signage indicating property address
271147 11/17/2009 163219 2 106 OS Prohibit use of wedge to hold fire door in open position
290420 03/24/2009 204470 1 003 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to stairway 1-013
239022 03/24/2009 97594 1 120 M Replace missing escutcheon on fire sprinkler head
290433 03/24/2009 204495 1 132 M Replace missing escutcheon on fire sprinkler head
290411 03/24/2009 204453 1 147 M Provide current inspection tag for kitchen steamer
290419 03/24/2009 204468 1 151 M Determine cause of water damaged ceiling tiles and replace tiles
290417 03/24/2009 204464 1 152 M Replace missing ceiling tiles
290429 03/24/2009 204487 1 205 M Replace missing escutcheon on fire sprinkler head
290427 03/24/2009 204483 1 210 M Determine cause of water damaged ceiling tiles and replace tiles
290428 03/24/2009 204485 1 210 M Repair deteriorated wall finish where projector screen was hanging, and attach screen to wall
290432 03/24/2009 204493 1 217 M Determine cause of water damaged ceiling tiles and replace tiles
290413 03/24/2009 204457 3 103 M Repair door on boys bathroom to close properly (drags on threshold)
290422 03/24/2009 204474 P 6233 M Determine cause of water damaged ceiling tiles and replace tiles
290425 03/24/2009 204479 P 6083 O Remove paper covering electric panel
290430 03/24/2009 204489 1 215 MS Provide current inspection tag for fire extinguisher
290431 03/24/2009 204491 1 217 MS Provide current inspection tag for fire extinguisher
290418 03/24/2009 204466 1 151C OS Prohibit running fan cord under door
290426 03/24/2009 204481 1 199C OS Remove storage from mechanical room
290415 11/13/2008 204461 P 0000 M Raise exterior electrical boxes so bottom of boxes is at least 8 inches above grade (not required per Terry Summerell)
271156 11/13/2008 163237 1 136 O Provide certification that American-Indian style carpet meets flame spread requirement or remove carpet
271154 11/13/2008 163233 1 139 O Provide certification that tan carpet meets flame spread requirement or remove carpet
271153 11/13/2008 163231 2 110 O Provide certification that green carpet adjacent to corridor door meets flame spread requirement or remove carpet
271142 01/17/2008 163209 1 004 M Replace cracked (wire ) glass in fire door in corridor facing 1-129
271139 01/17/2008 163202 1 004 M Secure loose escutcheon on fire sprinkler head in corridor adjacent to 1-192
271143 01/17/2008 163211 1 005 M Replace cracked (wire ) glass in fire door at top of stairwell
271119 01/17/2008 163162 1 123 M Replace missing escutcheon on fire sprinkler head
271120 01/17/2008 163164 1 129 M Replace missing escutcheon on fire sprinkler head
271141 01/17/2008 163206 1 129A M Replace missing ceramic base tile along wall under sink
271133 01/17/2008 163190 1 141A M Secure loose ceiling tiles in bathroom
239039 01/17/2008 97620 1 147D M Repair walk in freezer door to close and seal
271134 01/17/2008 163192 1 151 M Mount fire extinguisher at maximum five feet above floor
231296 01/17/2008 85556 1 171 M Provide certification that elevator has current inspection
271129 01/17/2008 163182 1 184 M Replace missing ceiling tile
271121 01/17/2008 163166 1 186B M Replace missing escutcheon on fire sprinkler head
271157 01/17/2008 163239 1 199A M Remove vine growing through ventilation window in generator room
271137 01/17/2008 163198 1 199B M Mount fire extinguisher at maximum five feet above floor
271125 01/17/2008 163174 1 199E M Repair auto closer on door
271126 01/17/2008 163176 1 199E M Repair emergency lighting
271127 01/17/2008 163178 1 199F M Repair emergency lighting
271128 01/17/2008 163180 1 199F M Repair door to open and close properly
271152 01/17/2008 163229 1 201 M Replace missing escutcheon on fire sprinkler head in bathroom
271131 01/17/2008 163186 1 203A M Replace broken lens on light fixture
271150 01/17/2008 163225 1 281 M Adjust door to latch properly
271146 01/17/2008 163217 2 001 M Repair emergency lighting in corridor adjacent to 2-190
271144 01/17/2008 163213 2 102 M Repair emergency lighting
271148 01/17/2008 163221 2 105 M Repair exterior door to open and close properly
271145 01/17/2008 163215 2 190 M Repair emergency lighting
271161 01/17/2008 163250 3 104 M Replace missing spout on drinking fountain (x2)
256412 01/17/2008 134048 3 104 M Replace damaged metal roof
271155 01/17/2008 163235 1 134 O Provide certification that tan carpet meets flame spread requirement or remove carpet
231294 01/17/2008 85552 00 8088 C Provide shield across 2 outside air vents on exterior wall of Building 1 @ 1-141 and 1-139 to prevent rain water from blowing into building
271151 01/17/2008 163227 1 008 MS Adjust fire door at top of stairwell to latch properly
271130 01/17/2008 163184 1 008 MS Adjust fire doors in corridor to latch properly adjacent to 1-142
271117 01/17/2008 163158 1 146L MS Provide current inspection tag for fire extinguisher
271122 01/17/2008 163168 1 152 MS Provide current inspection tag for fire extinguisher
271135 01/17/2008 163194 1 152 MS Relocate fire extinguisher to be adjacent to door
271118 01/17/2008 163160 1 194 MS Provide current inspection tag for fire extinguisher
271124 01/17/2008 163172 1 215 MS Provide current inspection tag for fire extinguisher
271123 01/17/2008 163170 1 217 MS Provide current inspection tag for fire extinguisher
271138 01/17/2008 163200 1 010 OS Remove all storage along stage ramp
271140 01/17/2008 163204 1 135 OS Relocate storage blocking clear access to east exit door
271132 01/17/2008 163188 1 217 OS Remove metal storage cabinet from entrance hallway
271149 01/17/2008 163223 1 218 OS Relocate chair and storage cart to maintain clear aisle to corridor door
256419 09/05/2007 134062 1 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
231328 09/05/2007 85624 1 003 M Adjust or replace smoke doors so that head and jamb clearance do not exceed 1/8 inch
231349 09/05/2007 85668 1 147 M Provide current inspection tag for kitchen steamer
239024 09/05/2007 97596 1 202A M Replace missing escutcheon on fire sprinkler head
231322 09/05/2007 85612 1 0000 C Adjust or replace fire doors throughout building so that clearance under doors does not exceed 1/2 inch
231325 09/05/2007 85616 1 0000 C Replace missing labels for fire rated door and remove paint from painted over labels on frames in building
271136 09/05/2007 163196 P 6083 MS Adjust concrete landing so that back door opens and closes freely - currently door does not open
231340 10/05/2006 85651 1 121 M Adjust level of fire sprinkler head to extend a minimum of 1" below escutcheon
256424 10/05/2006 134075 1 121 M Replace missing escutcheon on fire sprinkler head
256421 10/05/2006 134067 1 147C M Repair walk in cooler door to close and seal
256422 10/05/2006 134070 1 147D M Repair emergency release inside freezer to turn easily
231350 10/05/2006 85670 1 147D M Repair emergency release inside freezer to turn easily
256404 10/05/2006 134028 1 193 M Seal crack in masonry wall at corner
256410 10/05/2006 134044 1 194 M Mount fire extinguisher at maximum five feet above floor
256402 10/05/2006 134024 2 103 M Repair emergency lighting
256408 10/05/2006 134038 2 106 M Provide padlock for roof hatch to prohibit unauthorized access
256405 10/05/2006 134030 2 107 M Adjust exterior door to latch properly
256398 10/05/2006 134016 1 105 O Relocate storage to keep area within 18" of automatic fire sprinkler heads clear and unobstructed
256403 10/05/2006 134026 1 129 O Remove and prohibit paper covering window in door
256425 10/05/2006 134077 1 138 O Eliminate 13A extension cord adjacent to sink or replace with minimum 15A cord
256428 10/05/2006 134083 1 144 O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
256427 10/05/2006 134081 1 146E O Prohibit plugging surge protector into an extension cord, plug surge protector directly into wall outlet and prohibit use of 13A extension cord
256429 10/05/2006 134085 1 204 O Remove and prohibit combustible beanbag chair
256409 10/05/2006 134040 2 110A O Prohibit plugging microwave into an extension cord, plug microwave directly into wall outlet
239042 10/05/2006 97626 1 003 MS Adjust fire door in corridor at 1-192A to latch properly
256423 10/05/2006 134073 1 008 MS Adjust fire doors in corridor to latch properly
256399 10/05/2006 134018 1 146L MS Provide current inspection tag for fire extinguisher
256400 10/05/2006 134020 1 194 MS Provide current inspection tag for fire extinguisher
256420 10/05/2006 134064 1 199C MS Provide current inspection tag for fire sprinkler system
256430 10/05/2006 134087 1 215 MS Provide current inspection tag for fire extinguisher
256431 10/05/2006 134089 1 217 MS Provide current inspection tag for fire extinguisher
256401 10/05/2006 134022 2 106 MS Provide current inspection tag for fire extinguisher
256426 10/05/2006 134079 1 010 OS Relocate storage carts at top of stage ramp to maintain clear ramp
256407 10/05/2006 134034 2 106 OS Prohibit use of wedge to hold fire door in open position
256406 10/05/2006 134032 2 107 OS Relocate table blocking clear access to exterior door
256411 10/05/2006 134046 3 101 OS Relocate refrigerator to provide clear access to fire extinguisher
239025 09/22/2005 97598 00 9698 M Dig trench from standing water at SW corner of north parking lot to catch basin to eliminate standing water
231330 09/22/2005 85628 1 005 M Provide missing fire door hardware at bottom of doors
231332 09/22/2005 85632 1 005 M Replace broken window glass in fire door
231334 09/22/2005 85636 1 007 M Provide missing fire door hardware at bottom of doors
231335 09/22/2005 85639 1 008 M Provide missing fire door hardware at bottom of doors
239023 09/22/2005 97595 1 134 M Replace missing escutcheon on fire sprinkler head
239031 09/22/2005 97609 1 136A M Secure sink to wall
239030 09/22/2005 97607 1 137A M Secure sink to wall
239029 09/22/2005 97605 1 146C M Secure sink to wall in handicapped stall
239044 09/22/2005 97630 1 182 M Anchor shelving to wall
239026 09/22/2005 97600 1 192A M Repair unit DX3 or adjust thermostat. Unit was not on and room was very warm
239051 09/22/2005 97643 1 201 M Repair exhaust fan in bathroom
239052 09/22/2005 97644 1 201A M Repair exhaust fan in bathroom
239050 09/22/2005 97641 1 201A M Replace handicapped grabrail which has come off wall. Grabrail is on the floor by the sink
239053 09/22/2005 97645 1 201B M Repair exhaust fan in bathroom
239054 09/22/2005 97646 1 201C M Repair exhaust fan in bathroom
231357 09/22/2005 85686 1 210 M Replace cracked wire glazing in fire door
239027 09/22/2005 97602 1 216A M Secure sink to wall
239047 09/22/2005 97635 1 216A M Secure loose door lever
239049 09/22/2005 97639 1 290 M Remove sign indicating "Fire Extinguisher Inside"
239073 09/22/2005 97669 2 001 M Adjust exterior door at 2-191 to latch properly
239074 09/22/2005 97671 2 001 M Verify emergency light in corridor at 2-108 is working
239048 09/22/2005 97637 2 106 M Remove sign indicating "Fire Extinguisher Inside"
239045 09/22/2005 97631 2 180 M Anchor shelving to wall
239028 09/22/2005 97604 3 102 M Secure sink to wall
231293 09/22/2005 85550 00 9599 C Adjust steps on sidewalk, NW of Building 1 to make risers equal
231347 09/22/2005 85662 1 141 C Adjust level of fire sprinkler head to extend a minimum of 1" below escutcheon (adjacent to sink area)
239071 09/22/2005 97665 1 282 C Mark door of room ROOF ACCESS
239046 09/22/2005 97633 2 001 C Provide an emergency light at the east end of the corridor
231358 09/22/2005 85688 2 001 C Provide non-slip impervious floor surface under drinking fountain (x2)
239040 09/22/2005 97622 1 007 MS Adjust fire door in corridor at 1-141 to latch properly
239041 09/22/2005 97624 1 147 MS Provide current inspection tag for type K fire extinguisher on hood. No date punched
239017 09/22/2005 97589 1 195 MS Provide current inspection tag for fire extinguisher
239018 09/22/2005 97590 1 197 MS Provide current inspection tag for fire extinguisher
239019 09/22/2005 97591 1 199E MS Provide current inspection tag for fire extinguisher
239020 09/22/2005 97592 1 199F MS Provide current inspection tag for fire extinguisher
239021 09/22/2005 97593 2 191 MS Provide current inspection tag for fire extinguisher
239043 09/22/2005 97628 1 150 OS Remove storage at south exit to maintain clear aisle to exit
239070 09/22/2005 97663 1 280 OS Prohibit recharging batteries in room
239072 09/22/2005 97667 2 001 OS Remove table in exit corridor at 2-190
239032 09/22/2005 97611 1 105 CS Provide automatic fire sprinkler coverage for room.
239033 09/22/2005 97613 1 101 FS Provide certification that fire alarm system has been tested and is fully operational. Panel indicates GROUND FAULT
231326 02/07/2005 85622 1 0000 M Paint building number on exterior wall to be visible to fire rescue personnel
231295 02/07/2005 85554 1 0000 M Replace missing roof tiles @ west end of Building 1
231291 02/07/2005 85546 1 004 M Remove sign indicating "Fire Alarm Inside" at north exterior door from corridor
231339 02/07/2005 85646 1 117 M Replace missing cover for in-the-wall condensate over-flow
231344 02/07/2005 85659 1 132C M Anchor shelving to wall
231318 02/07/2005 85605 1 132F M Adjust door to 1-132 to latch properly
231272 02/07/2005 85526 1 137A M Secure sink to wall
231273 02/07/2005 85527 1 139A M Secure sink to wall
231274 02/07/2005 85528 1 141A M Secure sink to wall
231275 02/07/2005 85529 1 146A M Secure sink to wall
231348 02/07/2005 85666 1 146C M Secure sinks to wall
231287 02/07/2005 85541 1 152 M Repair leaking sprinkler line and replace wet stained ceiling tiles
231288 02/07/2005 85542 1 152A M Repair leaking sprinkler line and replace wet stained ceiling tiles
231353 02/07/2005 85676 1 197 M Remove sign indicating "Fire Extinguisher Inside" - mechanical room
231283 02/07/2005 85537 1 199A M Remove sign indicating "Fire Extinguisher Inside"
231276 02/07/2005 85530 1 199B M Repair leaking mixing valve
231284 02/07/2005 85538 1 199C M Remove sign indicating "Fire Extinguisher Inside"
231285 02/07/2005 85539 1 199D M Remove sign indicating "Fire Extinguisher Inside"
231336 02/07/2005 85641 1 199E M Repair emergency lighting
231355 02/07/2005 85682 1 199F M Repair emergency lighting
231277 02/07/2005 85531 1 201 M Secure sink to wall
231278 02/07/2005 85532 1 201A M Secure sink to wall
231356 02/07/2005 85684 1 202A M Replace missing escutcheon on fire sprinkler head
231279 02/07/2005 85533 1 203A M Secure sink to wall
231280 02/07/2005 85534 1 205A M Secure sink to wall
231281 02/07/2005 85535 1 206A M Secure sink to wall
231298 02/07/2005 85561 1 209 M Determine cause of water damaged ceiling tiles and replace tiles
231282 02/07/2005 85536 1 215A M Secure sink to wall
231289 02/07/2005 85543 1 216A M Replace missing escutcheon on fire sprinkler head
231290 02/07/2005 85544 1 217A M Repair leaking sprinkler line and replace wet stained ceiling tiles
231299 02/07/2005 85563 2 001 M Determine cause of water damaged ceiling tiles in corridor at 2-106 and replace tiles
231308 02/07/2005 85585 2 001 M Repair emergency lighting in corridor at 2-190
231310 02/07/2005 85589 2 107 M Repair emergency lighting
231311 02/07/2005 85591 2 180 M Repair ventilation fan in janitor's closet
231315 02/07/2005 85600 2 181 M Anchor shelving to wall
231286 02/07/2005 85540 2 191 M Remove sign indicating "Fire Extinguisher Inside"
231292 02/07/2005 85548 1 104 O Keep area within 18" of automatic fire sprinkler heads clear and unobstructed
231343 02/07/2005 85655 1 132 C Install maximum occupancy signage
231351 02/07/2005 85672 1 150 C Install maximum occupancy signage in music room
231352 02/07/2005 85674 1 151A C Provide ventilation to the exterior for kiln room
231317 02/07/2005 85602 2 106 C Provide tempered or safety glass in fire extinguisher cabinet or remove glazing
231359 02/07/2005 85690 3 0000 C Paint building number on exterior wall to be visible to fire rescue personnel
231300 02/07/2005 85566 1 003 MS Adjust fire door in corridor at intersection with corridor 1-012 to latch properly
231269 02/07/2005 85523 1 004 MS Provide current inspection tag for fire extinguisher in corridor at 1-129
231301 02/07/2005 85568 1 008 MS Adjust fire door at top of stairs at 1-280 to latch properly
231314 02/07/2005 85598 1 014 MS Recharge fire extinguisher in second floor corridor at 1-218
231306 02/07/2005 85579 1 199D MS Chain cylinder to wall
231270 02/07/2005 85524 1 215 MS Provide current inspection tag for fire extinguisher
231271 02/07/2005 85525 1 217 MS Provide current inspection tag for fire extinguisher
231313 02/07/2005 85596 1 101 OS Provide clear access to fire alarm pull station
231319 02/07/2005 85607 1 186 OS Prohibit recharging batteries in room
231320 02/07/2005 85609 1 282 OS Prohibit recharging batteries in room
231312 02/07/2005 85594 1 101 FS Provide certification that fire alarm system has been tested and is fully operational