PALM BEACH GARDENS ELEMENTARY
 
PALM BEACH GARDENS ELEMENTARY
10060 RIVERSIDE DR
PALM BEACH GARDENS, 33410
FISH Drill Down
 Campus Info.
 Buildings:5 Rooms:267
 Portables:0
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
410901 10/04/2017 466653 00 9698 M Remove metal support pieces loosely wound around tree trunks on north side of driveway, north of chiller building
410876 10/04/2017 466603 2 013 M Determine cause of water damaged ceiling tiles adjacent to 2-294 and replace tiles
410892 10/04/2017 466636 2 109 M Determine cause of water damaged ceiling tiles and replace tiles
410893 10/04/2017 466638 2 113 M Repair door to close and latch properly
410898 10/04/2017 466649 2 122 M Determine cause of water damaged ceiling tiles and replace tiles
410848 10/04/2017 466545 2 211 M Determine cause of water damaged ceiling tiles and replace tiles
410877 10/04/2017 466605 2 215 M Determine cause of water damaged ceiling tiles and replace tiles
410850 10/04/2017 466547 2 293 M Remove mold from north wall
410879 10/04/2017 466608 5 190 M Remove trees and plants growing in chiller yard
410895 10/04/2017 466643 2 116 O Remove and prohibit anchor charts hanging from ceiling to maintain clear view of exit door
410897 10/04/2017 466647 2 118 O Prohibit covering electrical outlet, located below white board, with paper
410847 10/04/2017 466543 2 208 O Remove and prohibit air freshener
410880 10/04/2017 466610 3 101A O Prohibit use of black multi outlet extension cord at camera or replace with minimum 15A single outlet extension cord
410896 10/04/2017 466645 2 001 MS Recharge fire extinguisher in corridor adjacent to 2-117
410888 10/04/2017 466627 2 101 MS Remove pin style lock privacy lock to allow door to be unlocked without use of a special tool
410890 10/04/2017 466630 2 102 MS Remove pin style lock privacy lock to allow door to be unlocked without use of a special tool
410886 10/04/2017 466622 2 124 MS Remove pin style lock privacy lock to allow door to be unlocked without use of a special tool
410883 10/04/2017 466612 2 135 MS Remove pin style lock privacy lock to allow door to be unlocked without use of a special tool
410885 10/04/2017 466619 2 136 MS Remove pin style lock privacy lock to allow door to be unlocked without use of a special tool
410894 10/04/2017 466641 2 116 OS Relocate table at door to maintain clear aisle to exit
266370 10/04/2017 152639 1 0000 N/A No violations observed
266371 10/04/2017 152641 2 0000 N/A No violations observed
266372 10/04/2017 152643 3 0000 N/A No violations observed
302984 10/04/2017 231446 4 0000 N/A No violations observed
302986 10/04/2017 231451 5 0000 N/A No violations observed
404053 04/25/2017 451764 2 191 M Repair or replace surge suppressor for electrical panel 2LSH that is in fault
404054 04/25/2017 451766 5 190 M Remove rust from and refinish rusted motor stands in chiller yard
404061 04/11/2017 451781 00 0000 M Reinforcing steel is exposed on collar of catch basin SW of 2-120. Remove rust from steel and cover with grout or concrete patching product
404039 04/11/2017 451735 00 0000 M Repair un-even concrete in courtyard
404036 04/11/2017 451728 00 0000 M Clean out all downspouts, gutters and roof drains on campus
404055 04/11/2017 451768 1 191 M Replace missing screws for covers of electrical panels 1HA, 1LSH and 1LSL
404060 04/11/2017 451779 2 0000 M Seal open joint on exterior wall just east of north doors from corridor 2-006 at 4 feet above ground
404072 04/11/2017 451805 2 013 M Determine cause of water damaged ceiling tiles and replace tiles in 2nd floor corridor at 2-294
404044 04/11/2017 451746 2 112 M Secure faucet to sink
404048 04/11/2017 451754 2 115A M Grout where tile is missing next to sink
404033 04/11/2017 451721 2 192 M Replace missing screws for covers of electrical panels 2EQL and 2LA1
404034 04/11/2017 451724 2 192 M Provide correct bracket for fire extinguisher
404052 04/11/2017 451762 2 195 M Provide cover on exposed electrical junction box above AHU2-1 frequency drive
404071 04/11/2017 451803 2 213B M Seal open corner in bathroom
404070 04/11/2017 451801 2 219 M Remove pencil sharpener without cover at exit
404069 04/11/2017 451798 2 221 M Adjust air conditioning system. Teacher complains that it is too cold
404056 04/11/2017 451770 2 290 M Replace missing screws for cover of electrical panel 2MB2
404051 04/11/2017 451760 2 292 M Replace missing screws for covers of all electrical panels in room
404049 04/11/2017 451756 2 293 M Replace missing screws for cover of electrical panel 2MA2
404050 04/11/2017 451758 2 294 M Replace missing screws for covers of all electrical panels in room
404040 04/11/2017 451737 3 101F M Repair exhaust fan in bathroom
404041 04/11/2017 451739 3 101G M Repair exhaust fan in bathroom
404042 04/11/2017 451741 3 101H M Repair exhaust fan in bathroom
404043 04/11/2017 451743 3 101J M Repair exhaust fan in bathroom
404037 04/11/2017 451731 3 105A M Seal open corner in bathroom
404038 04/11/2017 451733 3 105B M Seal open corner in bathroom
404067 04/11/2017 451793 3 191 M Replace missing screws for cover of electrical panel 3DB
404062 04/11/2017 451783 3 198 M Replace missing screws for covers of electrical panels 3MA and 3HA
404059 04/11/2017 451777 5 193 M Replace missing screws for cover of electrical panel SH
404057 04/11/2017 451773 5 194 M Replace missing screws for covers of electrical panels EQMDP and EQL
404058 04/11/2017 451775 5 194 M Provide certification that all student occupied spaces have emergency lights and all are operable. Last certification 8-3-15
404045 04/11/2017 451748 2 116 O Remove and prohibit excessive flammable decorations on ceiling. Limit paper from ceiling to 12 sheets of standard sized paper (8.5 X 11). Prohibit attaching paper to blinds
404065 04/11/2017 451789 2 124 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
404046 04/11/2017 451750 2 132 O Remove and prohibit attaching paper to blinds. Acceptable on string lines next to walls or windows and attached to windows or walls
404035 04/11/2017 451726 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus
404064 04/11/2017 451787 2 0000 OS Remove and prohibit storage under all stairs in building 2
404063 04/11/2017 451785 2 001 OS Remove paper attached to wall above fire doors in corridor at 2-116 that prevents door from shutting completely
404066 04/11/2017 451791 2 131 OS Prohibit hold open device on corridor door
404047 04/11/2017 451752 2 132 OS Prohibit hold open device on corridor door
404068 04/11/2017 451796 2 224 OS Maintain clear aisle to exit. Relocate desks and chairs at exit
388923 01/19/2017 419108 00 0000 M Make necessary repairs to fire sprinkler systems in building 1, 2, and 3 as indicated on inspection report (systems are red tagged needing five year inspections)
361909 01/19/2017 360574 2 192 M Repair air conditioning unit above door in electrical room
388949 01/19/2017 419162 4 0000 M Eliminate bumps in hardcourt at P.E. Pavillion to prevent tripping hazard
388952 03/22/2016 419168 00 0000 M Remove dead palm tree located next to picnic table in courtyard between Building 2 and Building 3
388933 03/22/2016 419128 2 0000 M Repair sticky push bar on gate at kindergarten playground on south side of Building 2 (gate does not latch after pushing push bar because latch sticks in the open position)
388929 03/22/2016 419120 2 117A M Secure loose toilet seat
388926 03/22/2016 419114 2 124 M Secure loose toilet seat
388924 03/22/2016 419110 2 131 M Secure drinking fountain to sink
388934 03/22/2016 419130 2 136 M Secure loose toilet seat
388927 03/22/2016 419116 2 195 M Replace cover guard on motor and belt located on A/C duct
388915 03/22/2016 419091 2 206C M Secure loose toilet seat
388916 03/22/2016 419094 2 213B M Secure loose toilet seat in staff restroom
388919 03/22/2016 419100 2 218 M Secure loose toilet seat
388920 03/22/2016 419102 2 218 M Repair door on bathroom to close properly
388921 03/22/2016 419104 2 221A M Secure loose toilet seat
388947 03/22/2016 419158 3 0000 M Repair damaged chain link gate between Building 3 and Building 5 and provide chain and padlock so gate can be secured after school hours
388940 03/22/2016 419143 3 101C M Determine cause of water damaged ceiling tiles above electric panel ITV and replace tiles
388939 03/22/2016 419141 3 101F M Secure loose toilet seat
388942 03/22/2016 419147 3 102B M Secure loose toilet seat
388948 03/22/2016 419160 3 194 M Repair air conditioning unit DX3-2 above door to keep room cool
388950 03/22/2016 419164 4 0000 M Replace blue rubber handle on chain climber in Intermediate playground to prevent pinch injuries
388951 03/22/2016 419166 4 0000 M Adjust latch on gate of Intermediate playground so gate can latch properly
388946 03/22/2016 419156 5 190 M Remove vegetation growing in chiller yard
388944 03/22/2016 419151 5 193 M Repair air conditioning unit above door (room was very hot)
388945 03/22/2016 419153 5 193 M Repair emergency lighting
388936 03/22/2016 419135 2 107 O Remove and prohibit curtain covering window in door (window in doors should only be covered during code red situations)
388935 03/22/2016 419133 2 109 O Remove and prohibit attaching paper or decorations on window blinds
388930 03/22/2016 419122 2 115 O Remove and prohibit hanging plastic flags and decorations from ceiling
388941 03/22/2016 419145 3 101 O Remove and prohibit combustible beanbag chairs in Media Center
388938 03/22/2016 419139 1 122 MS Provide current inspection tag for fire extinguisher
388937 03/22/2016 419137 1 192 MS Provide current inspection tag for fire extinguisher
388931 03/22/2016 419124 2 001 MS Recharge fire extinguisher in first floor corridor across from 2
388932 03/22/2016 419126 2 001 MS Recharge fire extinguisher in first floor corridor adjacent to 2-114
388925 03/22/2016 419112 2 006 MS Recharge fire extinguisher in corridor adjacent to 2-125
388928 03/22/2016 419118 2 117 MS Recharge fire extinguisher
388917 03/22/2016 419096 2 281 MS Provide current inspection tag for fire extinguisher
388918 03/22/2016 419098 2 294 MS Provide current inspection tag for fire extinguisher
388943 03/22/2016 419149 3 180 MS Provide current inspection tag for fire extinguisher located next to washer and dryer
388922 03/22/2016 419106 2 013 OS Remove paper hanging from a string line blocking clear access to fire extinguisher in second floor corridor across from 2-225
374993 04/10/2015 388987 2 011 M Make necessary repairs to fire sprinkler system as indicated on inspection report 11.25.2014 - Riser had a red tag
374990 04/10/2015 388981 2 013 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to 2-194
374996 04/10/2015 388993 2 135 M Adjust bathroom door to latch properly
374992 04/10/2015 388985 3 103B M Replace missing unlock thumb latch on boys group bathroom door in dining room
374994 04/10/2015 388989 3 195 M Make necessary repairs to fire sprinkler system as indicated on inspection report 11.25.2014 - Riser had a red tag
375001 04/10/2015 389002 1 134 O Remove and prohibit hanging anchor charts from ceiling - You may hang up to (12) 8.5 by 11 inch size paper from ceiling
374988 04/10/2015 388977 2 111 O Remove and prohibit hanging anchor charts and running string line across ceiling - anchor charts can hang on string lines up to 2 inches away from walls
374995 04/10/2015 388991 2 112 O Remove and prohibit combustible residential armchair
374998 04/10/2015 388997 2 131 O Eliminate string line below 6 feet 8 inches
374999 04/10/2015 388999 2 131 O Remove and prohibit hanging fabric storage organizer from ceiling tile grid
374984 04/10/2015 388968 2 204 O Remove paper covering electrical outlets under center of writing board
374987 04/10/2015 388975 2 207 O Remove and prohibit hanging anchor charts and running string line across ceiling - anchor charts can hang on string lines up to 2 inches away from walls
374989 04/10/2015 388979 2 215 O Remove paper covering room name and number with raised and Braille characters
374985 04/10/2015 388970 2 222 O Remove and prohibit paper covering window in corridor door - paper can be relocated to outside face of corridor door
374986 04/10/2015 388973 2 222 O Remove and prohibit paper from projecting inside corridor door frame opening
374997 04/10/2015 388995 2 113A OS Remove large trash can used for storage in bathroom
374983 04/10/2015 388966 2 212A OS Remove storage from bathroom vestibule to maintain a minimum 3 ft clear path to both bathrooms
374981 04/10/2015 388962 2 212B OS Remove all storage from bathroom
374982 04/10/2015 388964 2 212C OS Remove storage from bathroom
374991 04/10/2015 388983 3 106A OS Relocate partition on stage south wall to provide clear access to fire extinguisher cabinet
324956 01/20/2015 280126 4 0000 M Repair surface of play courts. Covering bubbling up and loose in several spots. See coach
361961 01/20/2015 360681 4 101 M Repair rust, prime and paint base of steel columns at PE pavilion
361912 04/02/2014 360580 2 0000 M Close gap in chain link fencing adjacent to exterior wall of 2-114
361907 04/02/2014 360570 2 011 M Adjust exit doors at bottom of stairwell to latch properly
361915 04/02/2014 360587 2 108 M Repair auto closer on bathroom door
361901 04/02/2014 360558 2 111A M Close hatch on ceiling
361898 04/02/2014 360552 2 129 M Adjust water flow for drinking spout
361908 04/02/2014 360572 2 134 M Replace damaged surge protector with exposed wires under teacher desk
361910 04/02/2014 360576 2 135 M Repair door hardware to work properly - lock sticks
361904 04/02/2014 360564 3 101K M Determine cause of water damaged ceiling tiles and replace tiles
361957 04/02/2014 360661 4 0000 M Remove electrical outlet not in use on conduit within close proximity of SE corner of basketball court - outlet is not needed and conduit might be hazardous to students according to PE coach
361903 04/02/2014 360562 2 107 O Remove felt covering electrical outlet under writing board - under center of projector screen
361930 04/02/2014 360620 2 108 O Eliminate extension cord with multiple outlet end under teacher desk or replace with a surge protector
361940 04/02/2014 360639 2 109 O Eliminate brown extension cord with multiple outlet end under teacher desk or replace with a surge protector
361931 04/02/2014 360622 2 110 O Eliminate white extension cord with multiple outlet end for floor lamp adjacent to bathroom door or replace with a surge protector
361938 04/02/2014 360635 2 111 O Eliminate white extension cord with multiple outlet end under teacher desk or replace with a surge protector
361902 04/02/2014 360560 2 111 O Remove or relocate paper covering electrical outlet under writing board
361911 04/02/2014 360578 2 112 O Remove paper covering room name and number with Braille characters adjacent to corridor door
361934 04/02/2014 360628 2 112 O Eliminate extension cord with multiple outlet end under teacher desk or replace with a surge protector
361900 04/02/2014 360556 2 113 O Remove fabric covering electrical outlet under writing board
361936 04/02/2014 360631 2 118 O Eliminate white extension cord with multiple outlet end under teacher desk or replace with a surge protector
361897 04/02/2014 360550 2 123 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
361899 04/02/2014 360554 2 125 O Remove or relocate paper covering electrical outlet under writing board
361905 04/02/2014 360566 2 129 O Remove or relocate blue vinyl pockets sheet covering electrical outlet under writing board
361906 04/02/2014 360568 2 133 O Remove paper covering room name and number with Braille characters adjacent to corridor door
361929 04/02/2014 360617 2 201 O Eliminate white extension cord with multiple outlet end under teacher desk or replace with a surge protector
361928 04/02/2014 360615 2 203 O Eliminate white extension cord with multiple outlet end plugged into a surge protector under teacher desk or replace with a surge protector and plug directly into wall outlet
361894 04/02/2014 360544 2 208 O Remove or relocate paper covering electrical outlet under writing board
361913 04/02/2014 360582 2 209 O Remove paper covering room name and number with Braille characters adjacent to corridor door
361916 04/02/2014 360589 2 211 O Remove and prohibit large flammable vinyl tent from classroom
361922 04/02/2014 360601 2 212 O Eliminate brown extension cord with multiple outlet under computer stations in back of classroom or replace with a surge protector
361895 04/02/2014 360546 2 212 O Remove or relocate paper covering electrical outlet under writing board
361921 04/02/2014 360599 2 223 O Eliminate string line running across room with large charts
361919 04/02/2014 360595 2 224 O Eliminate string line running across room with large charts
361923 04/02/2014 360603 2 224 O Eliminate white extension cord with multiple outlet end under teacher desk or replace with a surge protector
361914 04/02/2014 360584 2 224 O Remove paper covering room name and number with Braille characters adjacent to corridor door
361927 04/02/2014 360613 2 225 O Eliminate white extension cord with multiple outlet end under teacher desk or replace with a surge protector
361920 04/02/2014 360597 2 226 O Eliminate string line running across room with large charts
361924 04/02/2014 360605 2 226 O Eliminate brown extension cord with multiple outlet end under teacher desk or replace with a surge protector
361925 04/02/2014 360607 2 226 O Eliminate white extension cord with multiple outlet end for glue gun adjacent to sink or replace with a surge protector
361926 04/02/2014 360609 2 227 O Eliminate white extension cord with multiple outlet end under teacher desk or replace with a surge protector
361942 04/02/2014 360645 3 101 O Eliminate orange extension cord with multiple outlet end under circulation desk or replace with a surge protector
361947 04/02/2014 360651 3 101 O Prohibit plugging surge protector into extension cord at computer stations in back of media center. Replace with another surge - long enough cord to reach wall outlet. Also secure or tape cords to floor to eliminate trip hazard
361891 04/02/2014 360538 3 180 O Prohibit running electrical cord through door between custodial receiving and adjacent bathroom
361892 04/02/2014 360540 3 180 O Keep door to custodial receiving locked and latched to prohibit student access
361893 04/02/2014 360542 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus
361896 04/02/2014 360548 2 110A OS Remove and prohibit use of toaster oven
361918 04/02/2014 360593 2 212A OS Remove storage from bathroom vestibule to maintain 3 ft clear path to both bathrooms
361917 04/02/2014 360591 2 217A OS Remove storage from bathroom vestibule to maintain 3 ft clear path to both bathrooms
348926 01/21/2014 331899 2 120 M Remove plants growing from under rain gutters on art room patio
324975 01/21/2014 280165 3 103 MS Replace painted fire sprinkler head in SE corner of room
348929 04/03/2013 331905 2 0000 M Provide cover on exposed electrical junction box on outside wall above entrance door of 2-194
348928 04/03/2013 331903 2 010 M Provide cover on exposed electrical junction box above exit doors at bottom stairway landing
348932 04/03/2013 331912 2 012 M Repair smoke stop doors in second floor corridor adjacent to 2-212 to close properly, doors close against each other
348933 04/03/2013 331914 2 013 M Determine cause of water damaged ceiling tiles in second floor corridor adjacent to 2-294 and replace tiles
348924 04/03/2013 331895 2 192 M Secure hanging cover on DX unit above door
348925 04/03/2013 331897 2 195 M Repair leaky water valve on air handler unit, water standing on floor
348930 04/03/2013 331907 2 280 M Close ceiling hatch in jantorial closet
348920 04/03/2013 331885 3 101A M Provide current date of flame resistance application on CCTV studio curtain, no date of treatment is listed on certificate
348921 04/03/2013 331888 3 106L M Repair emergency release knob to operate properly inside walk-in freezer in kitchen
348922 04/03/2013 331891 4 0000 M Repair drinking fountains at P.E. Pavillion
348934 04/03/2013 331917 5 194 M Repair emergency lighting in generator room
348923 04/03/2013 331893 2 0000 O Remove and prohibit flammable curtains and window coverings and flammable paper hanging from ceilings in the following rooms, 129, 127, 126, 226, 227
322467 04/03/2013 274046 3 005 C Provide automatic fire sprinkler coverage for all designated areas, no coverage in entry corridor to Media Center
348931 04/03/2013 331910 00 0000 CS Provide suitable area for charging floor machine and golf cart batteries
348927 04/03/2013 331901 2 120B CS Provide fire extinguisher outside of kiln room door
348919 04/03/2013 331883 1 101 FS Provide certification that fire alarm system has been tested and is fully operational, last inspected 1-17- 2012
324971 01/28/2013 280157 00 0000 MS Provide current inspection tags for all fire sprinkler systems. Current tags are dated 4/2011 for quarterly inspection and expired
324977 01/28/2013 280169 3 106 MS Provide current inspection tag for kitchen hood fire suppression system
324970 11/11/2011 280154 00 0000 M Provide current inspection log for all hot water heaters 40 gallon or higher capacity
324961 11/11/2011 280136 00 0000 M Remove straps and stakes from Holley trees south of bus loop adjacent to fence
324946 11/11/2011 280104 00 0000 M Remove 3/4" grey PVC pipe sticking out of ground and old tree stakes adjacent to fence, west of play court
324955 11/11/2011 280124 1 180 M Repair door to open and close properly
324959 11/11/2011 280132 2 011 M Replace missing escutcheon on fire sprinkler head at top of stairs
324960 11/11/2011 280134 2 013 M Determine cause of water damaged ceiling tiles and replace tiles in 2nd floor corridor adjacent to stair 2-011
324973 11/11/2011 280161 2 106B M Install fire extinguisher sitting on counter top at maximum five feet above floor
324964 11/11/2011 280142 2 192 M Secure loose ground at right end of ground bar
324957 11/11/2011 280128 2 205 M Secure loose pencil sharpener
324947 11/11/2011 280106 2 223 M Replace GFCI outlet left of sink that won't reset
324958 11/11/2011 280130 2 227C M Secure loose light switch
324976 11/11/2011 280167 2 290 M Repair leaking air handler
324966 11/11/2011 280146 3 103C M Secure loose dead bolt lock on door
324969 11/11/2011 280152 3 191 M Repair circuit 14 in panel 3LB. Breaker tripped
324948 11/11/2011 280109 5 193 M Secure loose ground for transformer 5T
324950 11/11/2011 280114 5 194 M Replace GFCI outlet on wall under battery charger that won't reset
324968 11/11/2011 280150 1 190 O Keep floor drain filled with water. Room smells of sewer gas
324965 11/11/2011 280144 2 109 O Remove and prohibit plug in air freshener
324963 11/11/2011 280140 2 120C O Prohibit plugging refrigerator into surge protector then into extension cord - plug directly into permanent electrical outlet
324952 11/11/2011 280118 2 220 O Post sign indicating evacuation routes
324967 11/11/2011 280148 3 192 O Keep floor drain filled with water. Room smells of sewer gas
324962 11/11/2011 280138 2 009 MS Adjust fire door at top of stairs to latch properly
324972 11/11/2011 280159 2 171 MS Provide current inspection tag for fire extinguisher
324953 11/11/2011 280120 5 191 MS Provide current inspection tag for fire extinguisher
324974 11/11/2011 280163 2 005 OS Remove and prohibit large recycle bins in corridor
324954 11/11/2011 280122 2 009 OS Prohibit hold open device on fire door at top of stairs
324951 11/11/2011 280116 2 201 OS Prohibit hold open device on corrridor door
324949 11/11/2011 280112 2 280 OS Prohibit charging batteries in room
322460 09/09/2011 274032 3 105 M Replace broken window glass, adjacent to 3-004
322518 09/09/2011 274156 2 010 MS Replace painted fire sprinkler head, 2nd floor stairwell
322520 05/04/2011 274160 1 101 M Re-install directional arrow in exit sign at entry door
322517 05/04/2011 274154 2 0000 M Provide cover on exposed electrical junction box above exterior door at 2-194
322464 05/04/2011 274040 2 005 M Replace missing escutcheon on exterior fire sprinkler head at entrance to 2-005, corridor adjacent to 2-120
322516 05/04/2011 274152 2 011 M Provide cover on exposed electrical junction box behind exit sign at exterior exit door
322472 05/04/2011 274058 2 104 M Determine cause of water damaged ceiling tiles and replace tiles
322515 05/04/2011 274150 2 108A M Repair bathroom door to close properly
322465 05/04/2011 274042 2 128 M Replace missing escutcheon on fire sprinkler head
322466 05/04/2011 274044 3 103 M Remove protective cap from fire sprinkler head, adjacent to 3-005
322462 05/04/2011 274036 3 103A M Provide cover on exposed electrical junction box
322469 05/04/2011 274050 5 194 M Repair emergency lighting
322461 05/04/2011 274034 3 104 O Eliminate 13A extension cords or replace with minimum 15A cord
322459 05/04/2011 274029 3 180 O Prohibit plugging refrigerator into surge protector - plug directly into permanent electrical outlet
322471 05/04/2011 274056 1 119 MS Seal penetration in ceiling around pipes to prevent spread of fire or smoke
322463 05/04/2011 274038 1 193 MS Seal all openings in ceiling to prevent spread of fire or smoke
322470 05/04/2011 274053 2 012 MS Adjust fire doors in corridor adjacent to 2-211 to latch properly
322513 05/04/2011 274146 2 190 MS Seal penetration in ceilings to prevent spread of fire or smoke
322514 05/04/2011 274148 2 295 MS Seal penetration in ceilings to prevent spread of fire or smoke
322519 05/04/2011 274158 3 102C MS Provide current inspection tag for fire extinguisher
322468 05/04/2011 274048 5 192 MS Provide current inspection tag for fire extinguisher
302878 02/01/2011 231221 00 0000 M Provide chain and lock on valve handles of fire main at north west campus
302955 02/01/2011 231386 2 294 M Provide correct fire sprinkler head in room. Overhead head has been installed in west wall
302982 02/01/2011 231433 4 101 M Modify or improve drainage on covered play area to eliminate standing water. Saw cut grooves at north side to facilitate drainage. See Coach
302877 03/24/2010 231219 00 0000 M Remove braces and banding from all trees
302873 03/24/2010 231209 00 0000 M Label fire department connections and the buildings they serve
302876 03/24/2010 231216 1 119 M Replace missing ceiling tiles
302875 03/24/2010 231214 1 121 M Replace missing ceiling tiles
302929 03/24/2010 231332 2 001 M Adjust corridor door to exterior adjacent to 2-120 to latch properly
302943 03/24/2010 231362 2 001 M Adjust or replace smoke doors so that head, jamb, and seal clearance do not exceed 1/8 inch. Doors in corridor adjacent to 2-116
302928 03/24/2010 231327 2 010 M Secure loose outside handrail for upper run of stairs
302935 03/24/2010 231345 2 011 M Provide box containing spare fire sprinkler heads and head wrench at sprinkler riser in stair vestibule. There are 2 boxes in room 3-195
302936 03/24/2010 231347 2 013 M Fill and refinish crack in corridor wall adjacent to stair 2-011
302944 03/24/2010 231364 2 013 M Adjust or replace smoke doors so that head, jamb, and seal clearance do not exceed 1/8 inch. Doors in corridor aedjacent to 2-212
302945 03/24/2010 231366 2 113A M Repair leaking flush valve on toilet
302946 03/24/2010 231368 2 113A M Eliminate water hammer when toilet is flushed. Repair or provide hammer arrester
302937 03/24/2010 231349 2 114 M Replace missing ceiling tiles
302947 03/24/2010 231370 2 116A M Eliminate water hammer when toilet is flushed. Repair or provide hammer arrester
302938 03/24/2010 231351 2 120B M Replace missing escutcheon on fire sprinkler head
302940 03/24/2010 231355 2 137 M Adjust door to latch properly
302941 03/24/2010 231358 2 193 M Replace missing ceiling tiles
302949 03/24/2010 231374 2 202C M Replace missing light switch plate
302950 03/24/2010 231376 2 218 M Caulk opening between wall and ceiling
302959 03/24/2010 231396 2 280 M Anchor shelving to wall
302962 03/24/2010 231401 2 293 M Provide cover on exposed fire alarm junction box at ceiling
302965 03/24/2010 231407 3 102B M Secure loose handicapped grabrail in bathroom
302970 03/24/2010 231413 3 103B M Seal opening around escutcheon under sink or provide larger escutcheon to cover opening
302966 03/24/2010 231409 3 106D M Secure loose escutcheon on fire sprinkler head
302967 03/24/2010 231411 3 194 M Repair exterior door latch so door can be opened
302874 03/24/2010 231212 1 122 O Lower storage on outside shelves to keep area within 18" of fire sprinkler head clear
302925 03/24/2010 231321 1 181 O Store old light tubes in box
302939 03/24/2010 231353 2 124 O Keep shower drain filled with water. Pour a quart of water down the drain every 2 months
302942 03/24/2010 231360 2 126 O Prohibit plugging surge protector into surge protector
302926 03/24/2010 231324 2 180 O Store old light tubes in box
302964 03/24/2010 231405 3 180 O Lower storage on shelving to keep area within 18" of fire sprinkler heads clear
302976 03/24/2010 231428 4 105 O Provide clear access to electrical panel
302948 03/24/2010 231372 2 191 MS Fire caulk opening around 1.5 inch electric conduit where it penetrates ceiling to prevent spread of fire or smoke
302957 03/24/2010 231390 2 192 MS Seal penetration in enclosure wall between horizontal steel beam and top of drywall to prevent spread of fire or smoke
302951 03/24/2010 231378 2 281 MS Provide current inspection tag for fire extinguisher
302932 03/24/2010 231336 2 001 OS Remove trash cans stored in exit corridor adjacent to 2-120
302960 03/24/2010 231398 2 280 OS Prohibit charging batteries in room
302954 03/24/2010 231384 2 281 OS Prohibit charging batteries in room
302963 03/24/2010 231403 3 104 OS Maintain clear aisle to both stage exits
302973 03/24/2010 231420 3 104A OS Provide clear access to fire extinguisher
261260 11/03/2009 143513 1 0000 N/A No violations observed
243144 06/30/2008 105842 1 102 M Provide current inspection tag for kitchen steamer
243150 06/30/2008 105856 00 0000 C Provide auto closers on doors of metal PE storage building
196580 06/30/2008 4423 00 0000 C Provide signage indicating room names and numbers at appropriate height with raised and Braille characters throughout campus
196581 06/30/2008 4457 00 9500 C Provide covered walkway to portables
196582 06/30/2008 4424 1 101A C Provide handicapped accessibility to stage (cafeteria)
196583 06/30/2008 4426 1 102 C Install emergency gas shut off for all appliances and connect to hood extinguishing system to allow shut down upon activation of the fire suppression system (kitchen, cafeteria)
243115 06/30/2008 105785 10 107 C Provide emergency lighting in corridor
196590 06/30/2008 4429 2 101 C Provide fire rated door for boiler room @ door to corridor (mechanical room)
243090 06/30/2008 105728 5 106 C Provide emergency lighting in corridor
243089 06/30/2008 105726 7 107 C Provide emergency lighting in corridor
196591 06/30/2008 35554 2 101 OS Remove storage from boiler room
196585 06/30/2008 4348 10 107 CS Make corridor fire rated including doors, frames, openings, hardware, etc. (covered walk)
196592 06/30/2008 4346 5 106 CS Make corridor fire rated including doors, frames, openings, hardware, etc. (covered walk)
196593 06/30/2008 4347 7 107 CS Make corridor fire rated including doors, frames, openings, hardware, etc. (covered walkway)
261270 06/30/2008 143523 11 0000 N/A No violations observed
261271 06/30/2008 143524 12 0000 N/A No violations observed
261272 06/30/2008 143525 13 0000 N/A No violations observed
261273 06/30/2008 143526 14 0000 N/A No violations observed
261262 06/30/2008 143515 3 0000 N/A No violations observed
261263 06/30/2008 143516 4 0000 N/A No violations observed
267531 06/30/2008 155108 6 0000 N/A No violations observed
267533 06/30/2008 155116 8 0000 N/A No violations observed
261268 06/30/2008 143521 9 0000 N/A No violations observed
261275 06/30/2008 143528 P 3681 N/A No violations observed
261276 06/30/2008 143529 P 3754 N/A No violations observed
266360 06/30/2008 152615 P 3995 N/A No violations observed
266334 04/19/2007 152561 00 0000 M Repair uneven sidewalk to West parking lot adjacent to gate with panic bar
266336 04/19/2007 152565 1 101 M Repair emergency lighting adjacent to West exit
266337 04/19/2007 152567 1 101 M Provide correct bracket for fire extinguisher adjacent to West exit
266341 04/19/2007 152575 1 101B M Install fire extinguisher sitting on floor at maximum five feet above floor adjacent to exit
266343 04/19/2007 152579 1 102D M Anchor toilet to floor
266342 04/19/2007 152577 1 106 M Repair emergency lighting
266339 04/19/2007 152571 10 104 M Anchor handicapped toilet and 2 urinals to floor
266340 04/19/2007 152573 11 103 M Repair emergency lighting
266358 04/19/2007 152611 13 104 M Repair emergency lighting adjacent to 13-121
266368 04/19/2007 152633 13 113 M Repair exhaust fan in Dark Room
266369 04/19/2007 152636 13 121 M Repair emergency lighting
266357 04/19/2007 152609 14 119C M Anchor shelving to wall
266363 04/19/2007 152622 3 102A M Anchor toilet to floor
266364 04/19/2007 152625 4 104A M Anchor toilet to floor
266367 04/19/2007 152631 5 101A M Determine cause of water damaged ceiling tiles and replace tiles
266366 04/19/2007 152629 9 104 M Anchor center toilet to floor
266345 04/19/2007 152583 00 0 O No access was available to 6-105, 7-106, 7-108, 11-104, 11-104A and 11-104B. Please be prepared to access these rooms during the report review meeting.
266344 04/19/2007 152581 10 101 O Eliminate extension cord for refrigerator. Plug refrigerator directly into outlet
266361 04/19/2007 152617 P 3754 O Provide clear access to electrical panel
230174 04/19/2007 83271 14 119 C Provide suitable wiring for keyboard lab
266335 04/19/2007 152563 12 102 MS Provide current inspection tag for 2 fire extinguishers
266365 04/19/2007 152627 13 122 MS Provide current inspection tag for fire extinguisher
266338 04/19/2007 152569 1 101C OS Maintain clear aisle to exit
266359 04/19/2007 152613 P 3681 OS Maintain clear aisle to stair door
266362 04/19/2007 152619 P 3754 OS Maintain clear aisle to stair door
261274 12/22/2006 143527 15 0000 N/A No violations observed
243148 12/21/2006 105851 1 101 M Replace missing cover on thermostat
243127 12/21/2006 105811 13 112 M Determine cause of water damaged ceiling tiles and replace tiles at exterior door
243146 12/21/2006 105847 5 103A M Determine cause of water damaged ceiling tiles and replace tiles
243173 12/21/2006 105903 7 101 M Replace missing cover on thermostat
243175 12/21/2006 105907 8 104 M Replace missing cover on thermostat
230173 12/21/2006 83269 14 119 O Eliminate multiple extension cords for keyboards
243065 12/21/2006 105675 11 106 OS Keep corridor door for mechanical room closed
243134 12/21/2006 105822 1 102B FS Provide heat detector in small storage room across from dryer
243141 12/21/2006 105838 11 108A FS Provide heat detector in storage room
261269 12/21/2006 143522 10 0000 N/A No violations observed
261261 12/21/2006 143514 2 0000 N/A No violations observed
261264 12/21/2006 143517 5 0000 N/A No violations observed
261265 12/21/2006 143518 6 0000 N/A No violations observed
261266 12/21/2006 143519 7 0000 N/A No violations observed
261267 12/21/2006 143520 8 0000 N/A No violations observed
261277 12/21/2006 143530 P 3995 N/A No violations observed
243147 03/20/2006 105849 1 101 M Repair emergency lighting
243131 03/20/2006 105818 1 102 M Repair emergency lighting
243113 03/20/2006 105780 10 105 M Repair auto closer on door
243066 03/20/2006 105677 11 101 M Repair emergency lighting
243140 03/20/2006 105836 13 104 M Repair emergency lighting adjacent to 13-121
243130 03/20/2006 105816 13 107 M Repair emergency lighting
243129 03/20/2006 105813 13 109 M Repair emergency lighting
243137 03/20/2006 105830 13 113 M Determine cause of water damaged ceiling tiles and replace tiles
243139 03/20/2006 105834 13 121 M Repair emergency lighting
243092 03/20/2006 105732 13 122A M Repair emergency lighting
243064 03/20/2006 105673 14 116 M Repair emergency lighting
243159 03/20/2006 105874 3 101 M Replace cracked glass in corridor door
243145 03/20/2006 105845 5 103 M Replace missing cover on thermostat
243087 03/20/2006 105722 6 102 M Provide cover on exposed electrical junction box adjacent to speaker
243101 03/20/2006 105753 P 3681 M Determine cause of water damaged ceiling tiles and replace tiles
243103 03/20/2006 105757 P 3681 M Repair emergency lighting
243093 03/20/2006 105734 P 3754 M Repair or replace deteriorated wood siding
243096 03/20/2006 105741 P 3754 M Determine cause of water damaged ceiling tiles and replace tiles
243097 03/20/2006 105743 P 3995 M Adjust ramp door to latch properly
243098 03/20/2006 105746 P 3995 M Repair emergency lighting
243099 03/20/2006 105748 P 3995 M Determine cause of water damaged ceiling tiles and replace tiles
243107 03/20/2006 105765 1 104 O No access was available to this room. Please be prepared to access this room during the report review meeting.
243069 03/20/2006 105683 11 104 O No access was available to this room. Please be prepared to access this room during the report review meeting.
243151 03/20/2006 105858 14 111 O Eliminate extension cord or replace with minimum 15A cord
243108 03/20/2006 105767 2 104 O No access was available to the walk-in cooler outside 2-104. Please be prepared to access this room during the report review meeting.
243157 03/20/2006 105870 3 101 O Eliminate extension cord or replace with minimum 15A cord
243158 03/20/2006 105872 3 101 O Prohibit plugging surge protector into extension cord
243161 03/20/2006 105877 3 104 O Prohibit plugging surge protector into extension cord
243156 03/20/2006 105867 4 103 O Prohibit plugging extension cord into surge protector
243154 03/20/2006 105863 4 103 O Eliminate extension cord or replace with minimum 15A cord
243071 03/20/2006 105687 5 102 O Remove and prohibit air freshener
243072 03/20/2006 105689 5 103 O Post sign indicating evacuation routes
243163 03/20/2006 105883 6 101 O Post sign indicating evacuation routes
243070 03/20/2006 105685 6 103 O Post sign indicating evacuation routes
243067 03/20/2006 105679 6 105 O Replace bulbs in light fixture
243171 03/20/2006 105899 7 101 O Eliminate extension cord or replace with minimum 15A cord
243172 03/20/2006 105901 7 101 O Post sign indicating evacuation routes
243105 03/20/2006 105761 7 102 O Post sign indicating evacuation routes
243167 03/20/2006 105891 7 103 O Post sign indicating evacuation routes
243149 03/20/2006 105853 7 106 O No access was available to this room. Please be prepared to access this room during the report review meeting.
243088 03/20/2006 105724 7 108 O No access was available to this room. Please be prepared to access this room during the report review meeting.
243179 03/20/2006 105917 8 102 O Post sign indicating evacuation routes
243176 03/20/2006 105910 8 103 O Post sign indicating evacuation routes
243125 03/20/2006 105806 9 101 O Prohibit plugging surge protector to surge protector
243121 03/20/2006 105797 9 103 O Post sign indicating evacuation routes
243094 03/20/2006 105738 P 3754 O Relocate microwave oven and storage blocking clear access to electrical panel
243100 03/20/2006 105751 P 3995 O Remove and prohibit halogen lamp
243110 03/20/2006 105774 14 119A F Secure heat detector hanging by wires
243118 03/20/2006 105792 10 103 MS Remove dog leg hold open device from corridor door
243091 03/20/2006 105730 13 122 MS Provide current inspection tag for fire extinguisher (dated 12/03)
243112 03/20/2006 105778 14 121A MS Provide current inspection tag for fire extinguisher (dated 12/02)
243073 03/20/2006 105691 2 102 MS Provide current inspection tag for fire extinguisher (dated 12/03)
243122 03/20/2006 105799 9 102 MS Remove dog leg hold open device from corridor door
243142 03/20/2006 105840 1 101A OS Relocate TV cart blocking bottom of stage steps
243074 03/20/2006 105694 1 105 OS Prohibit storage of gas powered pressure cleaner
243116 03/20/2006 105787 10 101 OS Relocate teacher's desk and storage blocking clear access to emergency escape window
243117 03/20/2006 105790 10 102 OS Relocate desks and table blocking clear access to emergency escape window
243114 03/20/2006 105782 10 105 OS Prohibit storage of flammable dust mop solution and WD40
243126 03/20/2006 105808 13 112 OS Relocate TV cart blocking clear path to exterior door
243138 03/20/2006 105832 13 119 OS Keep laminating machine turned off when not in use and room is not supervised
243135 03/20/2006 105826 13 125 OS Remove and prohibit running electrical cord under door
243063 03/20/2006 105671 14 115 OS Prohibit wedging open fire door
243111 03/20/2006 105776 14 120 OS Remove storage blocking clear path to exterior door adjacent to 14-120A
243153 03/20/2006 105860 4 101 OS Keep backpacks off floor in front of exterior door to provide clear path to exterior door
243155 03/20/2006 105865 4 103 OS Remove storage blocking clear access to exterior door
243162 03/20/2006 105880 4 104 OS Keep door to bathroom vestibule closed to prevent blocking exterior door
243164 03/20/2006 105885 5 101 OS Prohibit wedging open corridor door
243165 03/20/2006 105887 5 101 OS Remove and prohibit candles
243166 03/20/2006 105889 5 101 OS Remove bundle of hay from classroom
243136 03/20/2006 105828 5 103 OS Arrange desks to provide minimum 3' wide clear aisle to corridor door
234539 03/20/2006 91860 5 103 OS Relocate desk blocking clear access to emergency escape window
243068 03/20/2006 105681 5 103 OS Prohibit wedging open corridor door
243169 03/20/2006 105893 7 102 OS Relocate backpacks blocking clear access to emergency escape window
243104 03/20/2006 105759 7 104 OS Relocate bookcase blocking clear access to emergency escape window
243177 03/20/2006 105912 8 102 OS Relocate TV cart and storage blocking clear path to corridor door
243178 03/20/2006 105914 8 102 OS Relocate display board blocking clear access to emergency escape window
243174 03/20/2006 105905 8 104 OS Relocate desk blocking clear access to emergency escape window
243124 03/20/2006 105802 9 101 OS Relocate desk blocking clear access to emergency escape window
243120 03/20/2006 105794 9 103 OS Relocate teacher's desk and student desk blocking clear access to emergency escape window
243102 03/20/2006 105755 P 3681 OS Remove storage blocking clear path to stair door
196597 02/28/2006 4461 P 3681 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
196595 02/28/2006 35547 P 3754 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
196596 02/28/2006 4460 P 3995 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
196584 11/16/2005 4465 1 102 M Adjust nozzle for kitchen hood fire suppression system so that deep fryer is protected and paint lines on floor to indicate proper location of cooking equipment
234540 11/16/2005 91862 5 103 O Maintain classroom in an orderly manner
196594 11/16/2005 4459 P 248 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
230170 11/16/2005 83263 1 102 MS Provide current inspection tag for fire suppression system (dated 7/03)
230168 11/16/2005 83259 5 102 OS Keep area clear at emergency escape window
234538 11/16/2005 91858 5 103 OS Prohibit storage of flammable rubber cement
230175 11/16/2005 83273 12 101B FS Provide or verify heat detector in Mechanical closet in after-care office
243844 11/16/2005 107158 12 0000 N/A No violations observed
230171 12/22/2004 83265 1 101 M Determine cause of water damaged ceiling tiles and replace tiles
230166 12/22/2004 83255 1 101 M Repair emergency lighting above southwest door
230165 12/22/2004 83253 12 103B M Repair emergency lighting
230177 12/22/2004 83277 14 108 M Repair emergency lighting
230409 12/22/2004 83712 14 119 M Change number on occupancy sign to indicate a maximum of 49
230167 12/22/2004 83257 3 101 M Repair emergency lighting
230164 12/22/2004 83251 8 104 M Repair emergency lighting
196598 12/22/2004 35555 P 3681 M Repair or replace deteriorated wood siding adjacent to stair door
230176 12/22/2004 83275 14 101 O Keep lightning detector turned on and monitored at all times campus is occupied
230179 12/22/2004 83281 14 102 O Eliminate multiple electrical outlet adaptor (splitter)
230169 12/22/2004 83261 3 102 O Eliminate extension cord or replace with minimum 15A cord
196586 12/22/2004 35535 11 101 C Provide emergency lighting
196587 12/22/2004 35543 12 101 C Replace CO2 fire extinguisher with ABC fire extinguisher
196588 12/22/2004 4349 12 102 C Replace CO2 fire extinguisher with ABC fire extinguisher
196589 12/22/2004 4350 14 119 C Provide sign indicating maximum occupancy adjacent to main entrance (occupancy must be less than 50) (14-122, music lab)
230178 12/22/2004 83279 14 113 MS Provide current inspection tag for fire extinguisher (dated 12/03)
230172 12/22/2004 83267 12 103B FS Provide certification that fire alarm system has been tested and is fully operational (dated 8/03)