BEAR LAKES MIDDLE
 
BEAR LAKES MIDDLE
This site is a Hurricane Shelter
3505 SHENANDOAH BLVD
WEST PALM BEACH, 33409
FISH Drill Down
 Campus Info.
 Buildings:18 Rooms:387
 Portables:0
 Floor Plans
 Surveys
 Aerials
Workorders
Deficiency CSIR
    2018-2019     2017-2018     2016-2017     2015-2016     2014-2015     2013-2014
Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
412717 03/15/2018 470559 1 104A M Determine cause of water damaged ceiling tiles in principal's restroom cubicle and replace tiles
412719 03/15/2018 470565 1 120 M Anchor loose junction box to wall
412829 03/15/2018 470792 10 109 M Repair emergency lighting in mezzanine mechanical room above 10-106
412841 03/15/2018 470821 11 101 M Repair inoperable drinking fountain at front of stage
412845 03/15/2018 470830 11 101 M Determine cause of water damaged ceiling tiles at northeast exit doors of cafeteria and replace tiles
397227 03/15/2018 437075 11 101 M Repair rusted bottom frame of vision panel adjacent to south exterior doors (X2)
412837 03/15/2018 470813 11 107 M Secure hanging light fixture lens in faculty dining room
371420 03/15/2018 381242 11 108A M Repair exhaust fan in bathroom
371421 03/15/2018 381244 11 108B M Repair exhaust fan in bathroom
412839 03/15/2018 470817 11 109 M Repair or replace damaged door in serving line
412840 03/15/2018 470819 11 111 M Repair door in serving line to close properly
412838 03/15/2018 470815 11 112 M Replace missing floor tiles in kitchen
412836 03/15/2018 470811 11 116 M Secure hanging light fixture lens in custodial office
412834 03/15/2018 470802 11 122 M Repair water leak above ceiling (tile has been removed and water is dripping into plastic garbage can)
412832 03/15/2018 470798 12 102 M Replace rusted louvers in metal door
412765 03/15/2018 470659 13 190 M Repair emergency lighting
412801 03/15/2018 470731 14 190 M Repair emergency lighting
412802 03/15/2018 470733 14 190 M Repair leaks in chilled water piping
412785 03/15/2018 470698 15 190 M Repair door to close properly
412759 03/15/2018 470647 16 001 M Repair hole in wall caused by door handle at top landing of stairway
412739 03/15/2018 470603 16 001 M Replace missing face plate in lighted exit sign at exterior doors in bottom landing of stairway
412752 03/15/2018 470631 16 006 M Repair or replace damaged fire door and closer at top landing of stairway
412746 03/15/2018 470619 16 009 M Replace missing face plate on lighted exit sign
412747 03/15/2018 470621 16 009 M Determine cause of water damaged and missing ceiling tiles and replace tiles
412741 03/15/2018 470607 16 101 M Replace missing vinyl corner protector at doorway
412744 03/15/2018 470615 16 105 M Determine cause of water damaged ceiling tiles and replace tiles
412733 03/15/2018 470591 16 106 M Determine cause of water damaged ceiling tiles at windows and replace tiles
412731 03/15/2018 470589 16 108 M Determine cause of water damaged ceiling tiles at windows and replace tiles
412722 03/15/2018 470569 16 109 M Replace broken toilet seat in stall #1 of girl's restroom
412728 03/15/2018 470582 16 110 M Place ceiling tile back into metal ceiling grid
412729 03/15/2018 470584 16 110 M Determine cause of water damaged ceiling tiles adjacent to 16-110A and replace tiles
412730 03/15/2018 470586 16 110A M Secure loose toilet seat
412727 03/15/2018 470580 16 110B M Secure loose toilet seat
412726 03/15/2018 470578 16 114 M Repair broken window blinds
412724 03/15/2018 470574 16 115 M Determine cause of water damaged ceiling tiles and replace tiles
412725 03/15/2018 470576 16 116A M Replace missing toilet seat
412748 03/15/2018 470623 16 170 M Provide current inspection tag for elevator (expired 8-1-17)
412737 03/15/2018 470601 16 190 M Determine cause of water damaged ceiling tiles and replace tiles
412763 03/15/2018 470655 16 205 M Replace missing A/C grill in ceiling (grill is sitting on top of cabinet inside room)
412757 03/15/2018 470643 16 206 M Determine cause of water damaged ceiling tiles at windows and replace tiles
412755 03/15/2018 470639 16 210 M Repair light fixture
412749 03/15/2018 470625 16 213 M Secure clean out cover on wall in first stall in girl's restroom
412830 03/15/2018 470794 17 0000 M Replace missing cover on light switch on exterior wall next to door
412831 03/15/2018 470796 17 101 M Replace rusted louvers in metal door
412796 03/15/2018 470720 2 101 M Determine cause of water damaged ceiling tiles next to windows and replace tiles
412794 03/15/2018 470717 2 105 M Repair ventilation fans in exhaust hoods above two stoves on south wall
412793 03/15/2018 470715 2 109 M Replace missing base along wall
412789 03/15/2018 470706 2 112 M Determine cause of water damaged ceiling tiles in kitchen and replace tiles
412792 03/15/2018 470713 2 113 M Replace missing base along wall
412779 03/15/2018 470686 2 114 M Repair damaged laminate on table top
412780 03/15/2018 470688 2 116 M Provide handicapped accessible door hardware on entrance door
412784 03/15/2018 470696 2 117 M Replace damaged floor tile at south exit door
412815 03/15/2018 470763 3 112 M Repair or replace damaged metal strip on exterior exit door to prevent injury
412813 03/15/2018 470759 3 119 M Prohibit use of plug in room deodorizer
412811 03/15/2018 470755 4 102 M Repair or replace damaged door
412810 03/15/2018 470751 4 103 M Replace missing and water damaged ceiling tiles
412805 03/15/2018 470741 4 104 M Determine cause of water damaged ceiling tiles and replace tiles
412806 03/15/2018 470743 4 104 M Secure bent electrical utility column next to counters on west wall
412807 03/15/2018 470745 4 104 M Repair damaged vinyl flooring
412809 03/15/2018 470748 4 104 M Repair emergency exhaust fan
412804 03/15/2018 470739 4 105 M Determine cause of water damaged ceiling tiles and replace tiles
412799 03/15/2018 470726 5 111 M Replace ceiling tiles back into ceiling grid
412797 03/15/2018 470724 5 116 M Repair emergency lighting
397219 03/15/2018 437059 5 124 M Repair broken window blinds on large window
412778 03/15/2018 470684 6 101 M Provide handicapped accessible door hardware on corridor door
412777 03/15/2018 470682 6 110 M Determine cause of water damaged ceiling tiles in corridor adjacent to west exit doors and replace tiles
412772 03/15/2018 470673 7 101 M Repair south exterior exit door to close properly
412768 03/15/2018 470665 7 104 M Determine cause of water damaged ceiling tiles and replace tiles
412766 03/15/2018 470661 7 105A M Determine cause of water damaged ceiling tiles and replace tiles
412767 03/15/2018 470663 7 106 M Repair or replace damaged fire extinguisher cabinet in corridor outside 7-105
412769 03/15/2018 470667 7 107 M Determine cause of water damaged ceiling tiles and replace tiles
412770 03/15/2018 470669 7 108 M Determine cause of water damaged ceiling tiles and replace tiles
412771 03/15/2018 470671 7 110 M Replace ceiling tile with hole in it in corridor next to 7-109
412775 03/15/2018 470677 7 110 M Secure hanging lighted exit sign at east exit doors of corridor
412817 03/15/2018 470768 8 102 M Replace missing ceiling tiles
412816 03/15/2018 470765 8 117 M Repair leak in chilled water return piping to prevent standing water on floor (room has sign marked 8-115)
412818 03/15/2018 470770 9 102A M Replace missing ceiling tiles
412824 03/15/2018 470782 9 114 M Replace broken ceramic base tiles in shower room
412825 03/15/2018 470784 9 114 M Secure hanging light fixture in shower room
412823 03/15/2018 470780 9 114A M Replace missing ceiling and water damaged tiles in laundry room
412822 03/15/2018 470778 9 126 M Repair emergency lighting in mezzanine mechanical room
412842 03/15/2018 470824 11 102 O Prohibit plugging surge protector into surge protector next to drinking fountains
412843 03/15/2018 470826 11 102 O Prohibit electrical cord from running through door into 11-104
412736 03/15/2018 470599 16 104 O Replace burned out bulbs in light fixtures
412735 03/15/2018 470595 16 106 O Prohibit use of plug in room deodorizers
412745 03/15/2018 470617 16 107 O Remove and prohibit hanging curtains from ceiling
412760 03/15/2018 470649 16 201 O Remove and prohibit paper covering window in door
412762 03/15/2018 470653 16 203 O Remove and prohibit paper covering window in door
412781 03/15/2018 470690 2 116 O Remove and prohibit paper covering window in door
412782 03/15/2018 470692 2 117 O Remove and prohibit paper covering window in door
412814 03/15/2018 470761 3 114 O Remove and prohibit paper covering window in door
412812 03/15/2018 470757 3 119 O Remove and prohibit paper covering window in door
371526 03/15/2018 381472 00 0000 C Modify or improve storm drainage from covered walkway to prevent storm water from running across sidewalk between buildings 2 and 5
357799 03/15/2018 351685 00 0000 C Modify or improve storm drainage from covered walkway from building 16 to building 8 to prevent storm drainage from running across walkway
412743 03/15/2018 470613 16 103 C Replace missing sign indicating primary and secondary evacuation routes in contrasting colors
412761 03/15/2018 470651 16 201 C Post sign indicating primary and secondary evacuation routes in contrasting colors
412758 03/15/2018 470645 16 202 C Replace missing sign indicating primary and secondary evacuation routes in contrasting colors
412756 03/15/2018 470641 16 206 C Post sign indicating primary and secondary evacuation routes in contrasting colors
412754 03/15/2018 470637 16 210 C Post sign indicating primary and secondary evacuation routes in contrasting colors
412753 03/15/2018 470633 16 216 C Post sign indicating primary and secondary evacuation routes in contrasting colors
412750 03/15/2018 470627 16 217 C Post sign indicating correct primary and secondary evacuation routes in contrasting colors
412751 03/15/2018 470629 16 219 C Replace missing sign indicating primary and secondary evacuation routes in contrasting colors
412828 03/15/2018 470790 10 106 MS Provide current inspection tag for fire extinguisher
412826 03/15/2018 470786 10 108 MS Provide current inspection tag for fire extinguisher
412827 03/15/2018 470788 10 108B MS Provide current inspection tag for fire extinguisher
412844 03/15/2018 470828 11 105 MS Provide current inspection tag for fire extinguisher
412791 03/15/2018 470710 12 109A MS Remove and prohibit hold open device (handle on plunger placed between door and jamb)
412800 03/15/2018 470729 14 190 MS Provide current inspection tag for fire extinguisher
412723 03/15/2018 470572 16 109 MS Secure loose deadbolt lock on entrance door to girl's restroom
412720 03/15/2018 470567 16 180 MS Recharge fire extinguisher
412787 03/15/2018 470700 2 113A MS Remove and prohibit hold open device (plunger handle placed between door and jamb)
412783 03/15/2018 470694 2 117 MS Recharge fire extinguisher
412773 03/15/2018 470675 7 110 MS Recharge fire extinguisher in corridor adjacent to 7-101
412819 03/15/2018 470772 9 109 MS Provide current inspection tag for fire extinguisher
412820 03/15/2018 470774 9 121A MS Provide current inspection tag for fire extinguisher
412718 03/15/2018 470563 1 130 OS Remove storage from mechanical room
412835 03/15/2018 470805 11 122 OS Prohibit storage of gasoline cans and gas powered leaf blower and lawn tractor
412833 03/15/2018 470800 11 125 OS Prohibit storage of gasoline cans (store in flammable storage room
412764 03/15/2018 470657 13 190 OS Remove storage from mechanical room
412821 03/15/2018 470776 9 121A OS Remove storage from electrical room
255201 03/15/2018 131447 1 0000 N/A No violations observed
255211 03/15/2018 131468 10 0000 N/A No violations observed
255212 03/15/2018 131470 11 0000 N/A No violations observed
255213 03/15/2018 131472 12 0000 N/A No violations observed
321335 03/15/2018 271584 13 0000 N/A No violations observed
255215 03/15/2018 131476 14 0000 N/A No violations observed
255216 03/15/2018 131478 15 0000 N/A No violations observed
255217 03/15/2018 131480 16 0000 N/A No violations observed
297015 03/15/2018 218512 17 0000 N/A No violations observed
277601 03/15/2018 177130 18 0000 N/A No violations observed
255202 03/15/2018 131449 2 0000 N/A No violations observed
255203 03/15/2018 131451 3 0000 N/A No violations observed
255204 03/15/2018 131453 4 0000 N/A No violations observed
255205 03/15/2018 131455 5 0000 N/A No violations observed
255206 03/15/2018 131458 6 0000 N/A No violations observed
255208 03/15/2018 131462 7 0000 N/A No violations observed
255209 03/15/2018 131464 8 0000 N/A No violations observed
255210 03/15/2018 131466 9 0000 N/A No violations observed
397209 10/31/2017 437039 9 122 M Repair or replace damaged door to storage room
397617 10/31/2017 437917 16 001 MS Adjust fire door at bottom of stairwell to open and latch properly - bottom of door rubs on flooring
382917 02/10/2017 406241 00 0000 M Make repairs to uneven bricks in courtyard between Bldgs. 8 and 10 along Bldg. 11 to prevent tripping hazard
397198 02/10/2017 437016 1 101 M Repair problems with fire alarm system - Troubles indicated on panel
397228 02/10/2017 437077 11 0000 M Repair uneven sidewalk outside SE exit door of dining room 11-101
382908 02/10/2017 406222 11 112 M Stabilize 2 burner stove
397629 02/10/2017 437942 16 218 M Repair damaged flooring adjacent to writing board
397599 02/10/2017 437881 2 101 M Secure communications junction box to electrical pole in back of room
397215 02/10/2017 437051 2 103B M Repair door to open and close properly - door is painted shut in interior courtyard behind mechanical room
397601 02/10/2017 437885 2 105 M Repair damaged oven door or remove appliance if not in use
397606 02/10/2017 437895 2 112 M Repair painted exterior door to open and close properly - door did not open
397225 02/10/2017 437071 2 113 M Repair auto closer on door
397229 02/10/2017 437080 2 119A M Remove revolving door for dark room not in use
397607 02/10/2017 437897 4 105 M Repair painted exterior door to open and close properly - door did not open
397213 02/10/2017 437047 5 0000 M Repair uneven sidewalk adjacent to 5-107
397221 02/10/2017 437063 5 117 M Remove illuminated exit sign above small access door - not a designated exit
397214 02/10/2017 437049 5 119 M Repair mechanical room door to open and close properly - door is painted shut
397609 02/10/2017 437901 6 101 M Repair painted exterior door to open and close properly - door did not open
397624 02/10/2017 437931 6 102 M Patch hole in flooring and replace rotted baseboard adjacent to exterior door
397615 02/10/2017 437913 7 0000 M Replace missing lens on light fixture outside boys group bathroom
397610 02/10/2017 437903 7 101 M Repair painted fire door facing bathroom to open and close properly - door did not open
397613 02/10/2017 437909 7 104 M Secure loose window pane in exterior door
397614 02/10/2017 437911 7 107 M Repair corridor door to open and close properly - door rubs on frame
397608 02/10/2017 437899 7 113A M Repair painted boys group bathroom door to open and close properly - door did not open
397205 02/10/2017 437030 8 0000 M Repair uneven sidewalk at NW corner of building 8
397196 02/10/2017 437012 8 118A M Repair boys bathroom door to open and close properly
397208 02/10/2017 437037 9 102A M Determine cause of water damaged ceiling tiles and replace tiles
397207 02/10/2017 437034 9 112 M Fill in maximum occupancy sign to read 565
397619 02/10/2017 437921 00 0000 O Provide name of Lead Crowd Manager who successfully completed the Crowd Management course as indicated in Bulletin # P-14808
397201 02/10/2017 437022 1 114 O Eliminate white extension cord with multiple outlet end for lamp on back counter or replace with a surge protector
397202 02/10/2017 437024 1 123 O Secure electrical cord gray cover strip to flooring to eliminate slip hazard
397612 02/10/2017 437907 10 107 O Remove and prohibit combustible curtains and teepee from room
397628 02/10/2017 437940 16 0000 O Remove green paper covering designated sign indicating primary and secondary evacuation routes in 2nd floor classrooms: 16-210 and 16-217
397632 02/10/2017 437951 16 0000 O Remove green paper covering designated sign indicating primary and secondary evacuation routes in 1st floor classrooms: 16-103 and 16-117
397216 02/10/2017 437053 16 117 O Remove and prohibit paper covering window in corridor door
397631 02/10/2017 437946 16 207 O Prohibit (3) piggy backed surge protectors under computer stations - plug each surge protector directly into wall outlet
397630 02/10/2017 437944 16 217 O Remove and prohibit air freshener under writing board
397600 02/10/2017 437883 2 101 O Provide cover strip for electrical cords running across floor between desks and secure cover strip to flooring to eliminate trip hazard
397627 02/10/2017 437937 3 106 O Eliminate 13A brown extension cord with multiple outlet end plugged into a surge protector at desk adjacent to exterior door
397626 02/10/2017 437935 4 101 O Remove broken glass table top from closet space to eliminate hazard
397220 02/10/2017 437061 5 124 O Remove and prohibit combustible curtain on window
397204 02/10/2017 437028 8 101 O Provide cover strip for electrical cords running across floor at back desk and secure cover strip to flooring to eliminate trip hazard
397195 02/10/2017 437010 1 0000 MS Secure loose lock cylinder at school entrance gate at SW corner of Bldg. 1
397199 02/10/2017 437018 1 112 MS Provide current inspection tag for fire extinguisher
397200 02/10/2017 437020 1 126 MS Provide current inspection tag for fire extinguisher
397226 02/10/2017 437073 11 104 MS Provide current inspection tag for fire extinguisher in mechanical room
397611 02/10/2017 437905 11 126 MS Provide current inspection tag for fire extinguisher
397618 02/10/2017 437919 16 001 MS Adjust fire door at top of stairwell to open and latch properly - bottom of door rubs on flooring
397616 02/10/2017 437915 16 006 MS Adjust fire door at bottom of stairwell to open and latch properly - bottom of door rubs on flooring
397605 02/10/2017 437893 16 192 MS Provide current inspection tag for fire extinguisher
397602 02/10/2017 437887 2 108 MS Provide current inspection tag for fire extinguisher
397223 02/10/2017 437067 2 109 MS Provide current inspection tag for fire extinguisher
397224 02/10/2017 437069 2 113 MS Provide current inspection tag for fire extinguisher
397603 02/10/2017 437889 2 114 MS Provide current inspection tag for fire extinguisher
397604 02/10/2017 437891 2 116 MS Provide current inspection tag for fire extinguisher
397212 02/10/2017 437045 2 117 MS Provide current inspection tag for fire extinguisher
397211 02/10/2017 437043 2 120 MS Provide current inspection tag for fire extinguisher
397218 02/10/2017 437057 5 107 MS Provide current inspection tag for fire extinguisher
397621 02/10/2017 437925 6 104 MS Recharge fire extinguisher
397622 02/10/2017 437927 6 105 MS Replace missing fire extinguisher
397623 02/10/2017 437929 6 106 MS Replace missing fire extinguisher adjacent to 6-104
397206 02/10/2017 437032 9 112 MS Replace missing fire extinguisher at NE corner of gymnasium
397197 02/10/2017 437014 1 132 OS Relocate shelf unit to maintain clear access to girls bathroom in clinic
397217 02/10/2017 437055 16 114A OS Remove storage to maintain clear path to bathroom facilities
397620 02/10/2017 437923 16 291 OS Remove bulletin board from mechanical room to provide clear access to control panels and equipment
397222 02/10/2017 437065 2 109 OS Relocate refrigerator to provide clear access to fire extinguisher
397625 02/10/2017 437933 4 105 OS Relocate storage to maintain 3 ft clear path to exterior door
397203 02/10/2017 437026 8 102 OS Remove storage along path to back exit door to maintain safe egress
371461 10/26/2016 381333 00 0000 M Clean out all rain gutters and downspouts on campus. Trees and weeds are growing in gutters
371427 10/26/2016 381258 11 112 M Repair Kitchen hood exhaust fan. Kitchen manager has to use hand- auto switch on disconnect in room 11-119 to turn fan on
371357 10/26/2016 381107 11 112 M Repair inoperable Kitchen Hood wash down system
382905 10/26/2016 406214 11 112 M Refinish rusty exterior sides of Blodgett oven
382849 10/26/2016 406100 16 191 M Make necessary repairs as noted on Annual fire sprinkler inspection report
382850 10/26/2016 406102 9 123 M Provide current state inspection tag for boiler
382922 03/09/2016 406251 00 9699 M Remove tree growing in exterior electrical panel enclosure east of 5-115
382911 03/09/2016 406228 1 119 M Prohibit use of surge protector (at fan) with damaged cord
382925 03/09/2016 406257 1 8087 M Remove plants and trees growing from brick columns north of building 1 at aluminum covered walk
382888 03/09/2016 406178 10 108 M Replace missing cover for thermostat
382900 03/09/2016 406204 11 103C M Remove expired fire extinguisher
382914 03/09/2016 406234 11 104 M Repair deteriorated ceiling finish
382904 03/09/2016 406212 11 112 M Repair and recalibrate Blodgett Oven
382906 03/09/2016 406217 11 112 M Provide current panel schedule for electrical panels LKA and LK
382907 03/09/2016 406219 11 112 M Replace missing screws to secure loose cover on electrical panel HK
382913 03/09/2016 406232 11 120 M Repair broken emergency release hardware in cooler
382912 03/09/2016 406230 11 121 M Repair broken emergency release hardware in freezer
382898 03/09/2016 406200 11 122 M Determine cause of water damaged ceiling tiles and replace tiles
382897 03/09/2016 406198 12 103 M Replace missing screws in electrical panel H9
382879 03/09/2016 406160 14 190 M Repair leaking chilled water return for air conditioning system to ensure that entire system operates as designed
382824 03/09/2016 406046 16 007 M Secure hanging exit sign at 16-209
382822 03/09/2016 406042 16 007 M Replace missing escutcheons on fire sprinkler heads in corridor adjacent to 16-206 and 16-218
382813 03/09/2016 406023 16 009 M Repair 1st floor corridor door to close and latch properly
382816 03/09/2016 406030 16 106 M Adjust door closer to control speed of closing door
382814 03/09/2016 406025 16 107 M Replace ballast in light fixture
382805 03/09/2016 406007 16 171 M Close and secure cover for elevator control box
382828 03/09/2016 406055 16 215 M Provide door stop for accessible stall door
382806 03/09/2016 406009 16 292 M Adjust door closer to control speed of closing door
382807 03/09/2016 406011 16 292 M Replace missing screws in electrical panel M2A
382854 03/09/2016 406110 2 112 M Repair inoperable exhaust fan at stove
382834 03/09/2016 406067 2 116 M Remove or replace broken plastic window in fire extinguisher cabinet
382835 03/09/2016 406069 2 116 M Replace missing cover for black electrical adaptor box plugged into power pole adjacent to teachers desk
382833 03/09/2016 406065 2 117 M Repair courtyard door to close and latch properly
382871 03/09/2016 406144 3 102 M Repair corridor door to close and latch properly
382869 03/09/2016 406140 3 103 M Repair exterior door to close and latch properly
382870 03/09/2016 406142 3 103A M Replace missing ceiling tiles
382866 03/09/2016 406134 3 107 M Secure loose glass in frame of emergency egress window
382859 03/09/2016 406120 3 117 M Repair rotting wooden base on wall at exterior door
382856 03/09/2016 406114 3 119 M Replace broken data outlet box on east wall, replace broken junction box cover plate on east wall
382872 03/09/2016 406146 3 120 M Determine cause of water damaged ceiling tiles in corridor adjacent to 3-119 and replace tiles
382876 03/09/2016 406154 3 124 M Replace missing protective cover for electrical outlet
382883 03/09/2016 406168 3 125 M Replace missing screws in electrical panels H2B, H2A, H2, L2B
382903 03/09/2016 406210 3 8087 M Repair damaged floor tiles on exterior walk adjacent to 3-101
371454 03/09/2016 381316 4 104 M Repair inoperable emergency exhaust fan
382877 03/09/2016 406156 4 104A M Determine cause of water damaged ceiling tiles and replace tiles
382926 03/09/2016 406259 5 112 M Secure sink to wall
382921 03/09/2016 406249 5 117 M Replace missing thermostat cover
382918 03/09/2016 406243 5 119 M Repair door to close and latch properly
382923 03/09/2016 406253 5 8088 M Refinish rusty areas of exterior window and door frames on east exterior wall of 5-115
382836 03/09/2016 406071 6 101 M Replace missing cover for black electrical adaptor box plugged in adjacent to teachers desk
382837 03/09/2016 406073 6 101 M Replace ballasts in light fixture
382840 03/09/2016 406081 6 109 M Remove wasp nest at north exterior door
382841 03/09/2016 406084 7 110 M Repair hanging exit sign
371524 03/09/2016 381466 7 113A M Repair exhaust fan in bathroom
371525 03/09/2016 381468 7 114A M Repair exhaust fan in bathroom
382847 03/09/2016 406096 7 118 M Repair light fixture
382902 03/09/2016 406208 7 8087 M Repair damaged floor tiles on exterior walk adjacent to 7-101
382885 03/09/2016 406172 8 102 M Repair emergency lighting
357780 03/09/2016 351645 9 102A M Modify or improve drain for washing machine to prevent water on floor
382893 03/09/2016 406190 9 102B M Provide clear paint coat to seal new raw wooden door
382851 03/09/2016 406104 9 108 M Remove wasps nests on exterior walls of 9-107 and 9-108
382895 03/09/2016 406194 9 109 M Replace missing screws on electrical panels H7A, L7A, L7
382894 03/09/2016 406192 9 110 M Repair broken wall tiles at 9-106
382890 03/09/2016 406182 9 114 M Repair broken base wall tile at 9-117
382891 03/09/2016 406186 9 114 M Provide cover on exposed electrical junction box on wall adjacent to 9-116
382889 03/09/2016 406180 9 114A M Determine cause of water damaged ceiling tiles and replace tiles
382896 03/09/2016 406196 00 0000 O Prohibit parking on grass area west of building 9 and at track
357707 03/09/2016 351484 10 105 O Prohibit charging batteries in room
382887 03/09/2016 406176 10 108 O Remove and prohibit flammable curtains and window coverings
382901 03/09/2016 406206 11 107 O Prohibit plugging refrigerator into surge protector- plug directly into permanent electrical outlet
382804 03/09/2016 406004 16 0000 O Prohibit covering framed, approved evacuation maps with school designed evacuation maps, school designed maps may hang adjacent to framed maps
382817 03/09/2016 406032 16 103 O Remove and prohibit paper covering window in door
382818 03/09/2016 406034 16 103 O Remove and prohibit multi outlet electrical adaptor at microwave
382815 03/09/2016 406028 16 105 O Remove and prohibit flammable green curtains
382808 03/09/2016 406013 16 113 O Remove and prohibit air fresheners, one plugged in and one on top of cabinet
382811 03/09/2016 406019 16 114 O Remove and prohibit air freshener, plug in style
382812 03/09/2016 406021 16 114A O Remove and prohibit air freshener spray
382809 03/09/2016 406015 16 116 O Remove and prohibit paper covering window in door
382810 03/09/2016 406017 16 116 O Remove and prohibit air freshener, plug in style
382820 03/09/2016 406038 16 190 O Keep floor clean and sanitary
382825 03/09/2016 406049 16 207 O Remove and prohibit flammable curtains
382826 03/09/2016 406051 16 207 O Remove and prohibit air freshener, plug in style
382827 03/09/2016 406053 16 207 O Remove and prohibit anchor charts hanging from ceiling in the center of room. Anchor charts may hang from ceiling no more than 2 inches from wall surface
382829 03/09/2016 406057 16 219 O Remove and prohibit air fresheners, plug in style
382863 03/09/2016 406128 2 105 O Remove and prohibit use of flammable (blue) plastic table coverings
382853 03/09/2016 406108 2 109B O Remove and prohibit air freshener, plug in style
382852 03/09/2016 406106 2 109C O Remove and prohibit air freshener
382832 03/09/2016 406063 2 117 O Remove and prohibit paper covering window in door
382830 03/09/2016 406059 2 120 O Remove and prohibit paper covering window in door
382874 03/09/2016 406150 3 101 O Remove and prohibit air freshener
382873 03/09/2016 406148 3 102 O Provide sign indicating primary and secondary evacuation routes in contrasting colors
382868 03/09/2016 406138 3 106 O Remove and prohibit air freshener
371470 03/09/2016 381352 3 107 O Provide sign indicating primary and secondary evacuation routes in contrasting colors
382864 03/09/2016 406130 3 108 O Remove and prohibit use of flammable (blue) plastic table coverings
382862 03/09/2016 406126 3 112 O Prohibit plugging surge protector into extension cord
382861 03/09/2016 406124 3 113 O Provide sign indicating primary and secondary evacuation routes in contrasting colors
357755 03/09/2016 351589 3 117A O Remove trash behind dryer
382858 03/09/2016 406118 3 117C O Remove and prohibit air freshener
382855 03/09/2016 406112 3 119 O Remove and prohibit air fresheners, plug in style, one located at sink
382857 03/09/2016 406116 3 119A O Remove and prohibit air freshener
382884 03/09/2016 406170 3 127 O Replace bulbs in light fixture
382878 03/09/2016 406158 4 104 O Relocate storage to maintain clear access to emergency eye wash
382881 03/09/2016 406164 4 108 O Remove and prohibit anchor charts hanging over(exterior) door to maintain clear aisle to exit. Anchor charts may hang from ceiling no more than 2 inches from wall surface
382882 03/09/2016 406166 4 109 O Prohibit use of 2 grey multi outlet power strips at computers adjacent to windows, surge protectors are acceptable replacements
382924 03/09/2016 406255 5 114 O Remove and prohibit air freshener
382838 03/09/2016 406075 6 101 O Remove and prohibit paper covering window in corridor door
382846 03/09/2016 406094 7 102 O Remove and prohibit air freshener
382845 03/09/2016 406092 7 104 O Replace missing fire blanket
382843 03/09/2016 406088 7 105 O Remove and prohibit air freshener, plug in style
357822 03/09/2016 351737 7 116 O Replace bulbs in light fixture
382886 03/09/2016 406174 8 109C O Remove and prohibit air freshener
382909 03/09/2016 406224 8 114 O Prohibit running electrical cord under door
382910 03/09/2016 406226 8 114 O Prohibit charging batteries in room
382892 03/09/2016 406188 9 104 O Remove and prohibit air freshener
382919 03/09/2016 406245 1 112 MS Recharge fire extinguisher
382865 03/09/2016 406132 3 107 MS Move hurricane shutter to allow egress window to function properly
382920 03/09/2016 406247 5 117B MS Provide current inspection tag for fire extinguisher
382842 03/09/2016 406086 7 110 MS Replace missing fire extinguisher
382848 03/09/2016 406098 7 119A MS Provide current inspection tag for fire extinguisher
382916 03/09/2016 406239 1 132 OS Relocate cabinet at 1-132A to allow egress from 1-132A at all times
382915 03/09/2016 406236 11 104 OS Remove storage from mechanical room
382899 03/09/2016 406202 11 122 OS Prohibit storage of gas powered equipment
371424 03/09/2016 381251 11 125 OS Prohibit storage of gasoline and gas powered equipment
382823 03/09/2016 406044 16 205 OS Maintain clear aisle to exit
382831 03/09/2016 406061 2 120 OS Maintain clear aisle to courtyard exit door
382875 03/09/2016 406152 3 101 OS Remove and prohibit use of toaster oven
382867 03/09/2016 406136 3 106 OS Remove and prohibit use of candles
382860 03/09/2016 406122 3 117 OS Relocate table to maintain clear aisle to (exterior) exit
382880 03/09/2016 406162 4 107 OS Relocate computer table and desk at exterior door to maintain clear aisle to exit
382927 03/09/2016 406261 5 107 OS Remove and prohibit use of space heater
371520 03/09/2016 381457 5 108 OS Provide clear access to fire extinguisher
371521 03/09/2016 381459 5 108 OS Remove storage from mechanical room
382839 03/09/2016 406077 6 104 OS Maintain clear aisle to exterior exit
382821 03/09/2016 406040 6 202 OS Maintain clear aisle to exit
382844 03/09/2016 406090 7 105 OS Remove and prohibit anchor chart hanging over(exterior) door to maintain clear aisle to exit. Anchor chart may hang from ceiling no more than 2 inches from wall surface
357747 03/09/2016 351571 9 108 OS Remove storage from mechanical room
371425 10/26/2015 381253 11 109 M Repair light fixture in serving line
371356 10/26/2015 381105 11 112 M Repair leaking plumbing. Leak is from tee underneath 3 compartment sink behind Hobart control box
371351 10/26/2015 381092 11 112 M Modify kitchen hood fire suppression system. Heads and piping covering tilting skillet in Kitchen are incorrect per hood inspection report. Repair suppression system
371503 10/26/2015 381423 16 006 M Repair door at top of stairs to open and close properly. Extended hinge is bent
371439 10/26/2015 381286 2 121 M Remove rust from, replace stucco and refinish damaged eyebrows on walls of interior courtyard. Stucco stops and metal lathe are rusting
371468 10/26/2015 381347 4 105 O Keep area clear to emergency electrical disconnect to allow ready access
371499 10/26/2015 381414 8 109D O Close cover on fluorescent light fixture
347086 10/26/2015 327952 16 291 C Provide automatic fire sprinkler coverage for area under duct which is in excess of 4 feet wide (NA per M. Lodge May 2014)
357713 10/26/2015 351497 3 125 OS Remove storage from electrical room
371474 03/25/2015 381361 00 0000 M Lower or remove 2 inch PVC pipe sticking up 6 inches in grassed area south of chiller compound at building 12. If pipe is needed install concrete collar around pipe and cut pipe flush with collar
371434 03/25/2015 381276 00 0000 M Repair or remove damaged chain link fencing at east softball field
371435 03/25/2015 381278 00 0000 M Replace lock on gate of fencing around irrigation pump enclosure west of building 10
371437 03/25/2015 381282 00 0000 M Remove lift hooks from lids of acid tanks outside of science labs in buildings 4, 6 and 7
371432 03/25/2015 381271 1 127A M Secure loose handicapped grabrail
371431 03/25/2015 381269 1 131 M Secure loose handicapped grabrail
371492 03/25/2015 381400 10 101 M Repair power pole that is coming apart
371494 03/25/2015 381404 10 104 M Repair door to open and close properly
371422 03/25/2015 381246 10 108B M Remove 3 fittings in bottom of fire alarm cabinet and provide KO seals for openings
357789 03/25/2015 351664 10 108B M Land all wires in fire alarm terminal box. 8 exposed wires were observed. Make a better connection to the terminal bar for the 2 bottom left wires
371429 03/25/2015 381264 11 104A M Adjust condensate drain from air handler to drop water into floor drain not on floor
357706 03/25/2015 351481 11 108 M Adjust door to latch properly
357722 03/25/2015 351515 11 109 M Finish unpainted wood door
371430 03/25/2015 381267 11 109 M Repair hot table on serving line. Not working, no heat
357723 03/25/2015 351517 11 111 M Adjust door to latch properly
371352 03/25/2015 381094 11 112 M Clean Kitchen hood and provide tag indicating date of cleaning. Current tag dated 8-7-13
371478 03/25/2015 381368 11 112 M Label all circuits on electrical panel HK in Kitchen
371479 03/25/2015 381372 11 112 M Repair panel H1B in Kitchen to latch
371353 03/25/2015 381096 11 114A M Secure loose toilet seat
371354 03/25/2015 381098 11 114A M Anchor toilet to floor
371355 03/25/2015 381103 11 123 M Repair top refrigeration unit. Fan running very slowly and backwards
357717 03/25/2015 351505 11 124 M Replace missing insulation on hot water lines
371447 03/25/2015 381302 12 103 M Repair door to open and close properly
371448 03/25/2015 381304 12 103 M Provide cover on 12 inch by 12 inch electrical box on north wall
371532 03/25/2015 381484 14 190 M Remove exposed and rusting horizontal block reinforcement on east exterior wall and patch wall
371436 03/25/2015 381280 16 0000 M Floor of chiller compound at building 16 has a layer of mud and mold on it. Clean out holes at bottom of wall to provide better drainage and provide more holes at bottom of wall to better drain floor if needed. Clean out mud and mold
371475 03/25/2015 381364 16 001 M Paint unfinished wood door at bottom of stairs
371460 03/25/2015 381330 16 001 M Repair hole in wall at top of stairs from door handle. Provide door stop with backing to prevent further damage to wall
371483 03/25/2015 381381 16 001 M Cover and refinish wall at bottom of stairs where corner bead is exposed
371482 03/25/2015 381379 16 002 M Replace missing base along corridor wall at south entry to building
371476 03/25/2015 381366 16 006 M Paint unfinished wood door at bottom of stairs
371445 03/25/2015 381298 16 009 M Secure loose outside lower handrail for stairs
371504 03/25/2015 381425 16 009 M Determine cause of water damaged ceiling tiles at bottom of stairs and replace tiles
357766 03/25/2015 351613 16 109 M Repair damaged hard ceiling
371459 03/25/2015 381328 16 113 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to fire sprinkler head. Check for leaking fire sprinkler line
371458 03/25/2015 381326 16 171 M Close elevator pump box
371446 03/25/2015 381300 16 213 M Secure loose deadbolt lock to bathroom door. Missing screw
371449 03/25/2015 381306 16 215 M Replace missing escutcheon on fire sprinkler head
371450 03/25/2015 381308 18 101 M Provide cover on exposed electrical junction box on east exterior wall where light fixture was removed
371451 03/25/2015 381310 18 101 M Replace or patch over missing brick in south exterior wall
371508 03/25/2015 381433 2 0000 M Remove sign indicating secondary egress into 5-116 from exterior wall of 2-117
371438 03/25/2015 381284 2 101 M Eliminate termites in cabinets and repair termite damage
357729 03/25/2015 351530 2 109A M Replace broken and missing ceramic base tile along wall at entry
371527 03/25/2015 381474 2 112 M Determine cause of water damaged ceiling tiles and replace tiles
371528 03/25/2015 381476 2 116 M Repair or replace emergency lighting relay. Emergency light always on
371529 03/25/2015 381478 2 119A M Determine cause of water damaged ceiling tiles and replace tiles
371530 03/25/2015 381480 2 120 M Repair or replace leaking faucet on sink closest to door
371510 03/25/2015 381437 2 121 M Cap open 3 inch PVC pipe in interior courtyard west of 2-109
371507 03/25/2015 381431 2 121 M Provide cover on exposed electrical junction box on west wall of courtyard behind 1-112
371512 03/25/2015 381441 3 103 M Secure loose door knob on door to exterior
357754 03/25/2015 351587 3 107 M Repair damaged and loose vinyl wall covering
371516 03/25/2015 381449 3 114 M Remove damaged pencil sharpener at rear door
371511 03/25/2015 381439 3 116 M Remove illuminated exit sign in interior corridor at corridor 3-105. Use this sign to replace the missing exit sign in 7-110
371513 03/25/2015 381443 3 120 M Determine cause of water damaged ceiling tiles in interior corridor and replace tiles
371467 03/25/2015 381345 3 124A M Secure loose toilet partition
371466 03/25/2015 381343 3 126 M Secure switch box for restroom lights to wall
371456 03/25/2015 381321 4 104 M Determine cause of water damaged ceiling tiles and replace tiles
371515 03/25/2015 381447 4 110 M Adjust corridor door to latch properly
371462 03/25/2015 381335 5 0000 M Termites are in cabinets and casework through out building. Eliminate termites and repair damage
371523 03/25/2015 381464 5 112 M Repair exhaust fan in bathroom
371522 03/25/2015 381462 5 116 M Repair damaged soffit above windows inside of room
371463 03/25/2015 381337 5 117 M Label all circuits on electrical panel L4B
371464 03/25/2015 381339 5 119 M Breaker 15 on panel L5B tripped. Repair circuit
371465 03/25/2015 381341 5 119 M Close open electrical gutter
357731 03/25/2015 351534 6 0000 M Repair uneven sidewalk NW of building 6 at Oak tree
371509 03/25/2015 381435 6 101 M Secure loose door knob on door to exterior corridor
371519 03/25/2015 381455 6 101A M Replace missing ceiling tiles
371518 03/25/2015 381453 6 103 M Replace missing door for tall cabinet
371517 03/25/2015 381451 6 108 M Secure thermostat to wall
371443 03/25/2015 381294 7 105 M Remove pencil sharpener without cover at door
371505 03/25/2015 381427 7 110 M Replace missing illuminated exit sign
371506 03/25/2015 381429 7 110 M Repair light in exit sign
371452 03/25/2015 381312 7 112 M Repair latch for panel L3A
371453 03/25/2015 381314 7 112 M Secure cover for panel L3B
371442 03/25/2015 381292 7 115 M Remove wires in liquid tight conduit to water heater or wire water heater
371495 03/25/2015 381406 8 108 M Adjust door to latch properly
371496 03/25/2015 381408 8 109 M Secure hanging exit sign
371497 03/25/2015 381410 8 119A M Repair leaking flush valve on handicapped toilet
371498 03/25/2015 381412 8 119A M Anchor handicapped toilet to floor
357762 03/25/2015 351605 9 114 M Repair damaged lockers. Twisted and bent doors
371487 03/25/2015 381391 9 114A M Determine cause of water damaged ceiling tiles and replace tiles
371490 03/25/2015 381397 9 117 M Provide cover over old clock box
371489 03/25/2015 381393 9 117A M Secure loose faucet to sink
371484 03/25/2015 381383 9 118 M Repair or replace damaged toilet partition. Replace missing laminate on partitions
371486 03/25/2015 381387 9 118 M Replace missing and broken ceramic wall and base tiles
371350 03/25/2015 381090 00 0 O No access was available to 1-111, 1-124 and 2-106. Please provide access to these rooms during the report review meeting
371493 03/25/2015 381402 10 104 O Replace bulbs in light fixture
371423 03/25/2015 381249 11 122 O Prohibit charging batteries in room
357821 03/25/2015 351735 2 105 O Keep area clear to emergency electrical disconnect to allow ready access
371514 03/25/2015 381445 3 102 O Remove and prohibit fabric covering window in door
371469 03/25/2015 381349 3 112 O Remove and prohibit paper covering window in door
371472 03/25/2015 381357 3 113 O Post sign indicating evacuation routes. Contact FMC for assistance
371455 03/25/2015 381319 4 104 O Keep area clear to emergency electrical disconnect and shut off valves to allow ready access
357786 03/25/2015 351658 9 110 C Provide illuminated exit sign to 9-111
357785 03/25/2015 351656 9 120 C Provide illuminated exit sign to 9-119
371433 03/25/2015 381274 1 126 MS Provide current inspection tag for fire extinguisher
371426 03/25/2015 381256 11 105 MS Provide current inspection tag for fire extinguisher
371428 03/25/2015 381262 11 127 MS Recharge fire extinguisher
371440 03/25/2015 381288 15 190 MS Provide current inspection tag for fire extinguisher
371457 03/25/2015 381324 16 180 MS Provide current inspection tag for fire extinguisher
371502 03/25/2015 381421 16 191A MS Provide current inspection tag for fire extinguisher
371444 03/25/2015 381296 16 106 OS Remove table at door to maintain clear aisle to exit
357775 03/25/2015 351633 16 291A OS Remove storage from electrical room
371441 03/25/2015 381290 2 117 OS Provide clear access to fire extinguisher
371473 03/25/2015 381359 3 117 OS Provide clear access to fire extinguisher and fire alarm pull station
371531 03/25/2015 381482 4 107 OS Remove desk partially blocking door to exterior
357787 11/12/2014 351660 10 108B M Repair panel HB to latch
270528 11/12/2014 161768 11 102 M Provide annual maintenance of temporary stage to insure all bolts are installed and tightly connected, all bracing is installed, stairs are secure and tight, and plywood flooring is in good condition as per Bill Brown's memo dated 10/3/2005, and provide documentation that stage is safe to use. Stage removed
324646 11/12/2014 279446 11 127 M Replace heavily rusted grille on ceiling in electrical room
357813 11/12/2014 351716 16 002 M Repair holes in corridor wall at main entry adjacent to 16-109
347158 11/12/2014 328096 5 104 M Replace missing thermostat cover
357798 11/12/2014 351683 8 113A M Repair leaking supply line for 1st toilet
357779 11/12/2014 351643 9 102A M Determine cause of water damaged ceiling tiles and replace tiles and replace missing tiles
357807 11/12/2014 351702 9 105 M Replace missing escutcheon on supply line for last toilet
357806 11/12/2014 351700 9 110 M Replace broken ceramic base tile
357759 11/12/2014 351598 9 112 M Repair damaged flooring at SW and NE corners of room
228008 11/12/2014 4166 00 0000 C Provide signage indicating room name and number at appropriate height with raised and Braille characters. Cited on ADA report
357827 11/12/2014 351748 2 105 C Provide ventilation to exterior for range on west wall
357720 07/29/2014 351511 10 109 M Close and lock open EMS cabinet
357833 07/29/2014 351760 5 108 M Close and lock open EMS cabinet
357832 07/29/2014 351758 5 109 M Close and lock all open cabinets
357828 07/29/2014 351750 5 119 M Close and lock all open cabinets
357820 07/29/2014 351732 7 112 M Cover and lock open fire alarm and sound terminal cabinets. Room signed 7-119A
357800 07/29/2014 351687 8 116 M Close and lock all open cabinets
357793 04/15/2014 351673 00 0000 M Repair uneven pavers in interior courtyard between buildings 8 and 10
357705 04/15/2014 351479 00 0000 M Replace lock on gate of fencing around pump enclosure west of building 10
320816 04/15/2014 270476 00 0000 M Paint building number on exterior wall of all buildings to be visible to fire rescue personnel
357698 04/15/2014 351466 1 126 M Repair damaged ceiling grid
357825 04/15/2014 351744 1 130 M Repair leaking union on top of water heater
357788 04/15/2014 351662 10 108B M Provide cover on open fire alarm terminal cabinet
357797 04/15/2014 351681 11 101 M Provide permanent number on maximum occupancy signage. Max occupancy is 365
357712 04/15/2014 351495 11 102 M Provide warning strip along edge of stage
357790 04/15/2014 351666 11 104A M Close and lock open EMS box
357791 04/15/2014 351668 11 104A M Wire damper motor correctly. Fitting pulled out of motor
357704 04/15/2014 351477 11 107 M Secure loose door knob on door to cafeteria and replace missing screw in latch
357703 04/15/2014 351475 11 108A M Secure loose faucet
357721 04/15/2014 351513 11 112 M Replace GFCI outlet to right of double sink that has no power. See Kitchen manager
357725 04/15/2014 351521 11 122 M Close and lock open EMS box
357716 04/15/2014 351503 11 124 M Repair leaking overpressure relief valve for water heater
357738 04/15/2014 351549 13 190 M Close and lock open EMS cabinets
357737 04/15/2014 351547 14 190 M Close and lock open EMS cabinets
357732 04/15/2014 351536 15 190 M Close and lock open EMS cabinets
357733 04/15/2014 351538 15 190 M Repair emergency lighting
357734 04/15/2014 351540 15 190 M Provide 1 half inch KO seal in emergency light box
357735 04/15/2014 351542 16 001 M Adjust door at bottom of stairs to latch properly
357736 04/15/2014 351544 16 001 M Repair or replace damaged door at bottom of stairs
357817 04/15/2014 351724 16 001 M Replace missing escutcheon on fire sprinkler head in stair enclosure
357764 04/15/2014 351609 16 109 M Secure loose handicapped grabrail
357765 04/15/2014 351611 16 109 M Caulk sinks to wall
357767 04/15/2014 351615 16 111 M Secure loose handicapped grabrail
357768 04/15/2014 351617 16 111 M Caulk sinks to wall
357769 04/15/2014 351620 16 111 M Provide cover for exposed electrical outlet in handicapped stall
357814 04/15/2014 351718 16 190 M Determine cause of water damaged ceiling tiles and replace tiles and replace missing tiles
357727 04/15/2014 351525 16 191 M Close and lock 2 open EMS cabinets
357726 04/15/2014 351523 16 191A M The surge suppressor for panel L5H is not lit. Repair or replace surge suppressor
357771 04/15/2014 351624 16 192 M Close and lock open EMS cabinets
357866 04/15/2014 351838 16 201 M Eliminate wasp nest outside of west windows and eliminate ants in classroom
357865 04/15/2014 351836 16 202 M Determine cause of water damaged ceiling tiles and replace tiles
357864 04/15/2014 351834 16 204 M Secure pencil sharpener to wall. Backing is loose
357863 04/15/2014 351832 16 205 M Replace missing door stop
357774 04/15/2014 351630 16 213 M Secure loose handicapped grabrail
357773 04/15/2014 351628 16 280 M Replace missing escutcheon on fire sprinkler head
357804 04/15/2014 351695 2 0000 M Replace broken metal cover plate for panic bars in exterior corridor adjacent to 2-101
357808 04/15/2014 351705 2 0000 M Remove rust from and refinish concrete eyebrow above window of 2-106 on interior courtyard side. Rust is from metal lath and corner bead
357809 04/15/2014 351708 2 0000 M Repair damaged eyebrow above window of 2-120 on interior courtyard side
357739 04/15/2014 351552 2 101 M Repair 3 damaged power poles
357757 04/15/2014 351593 2 117 M Eliminate insect infestation
357810 04/15/2014 351710 2 117 M Replace GFCI outlet that will not trip
357812 04/15/2014 351714 3 0000 M Secure loose astragal on SE set of double doors adjacent to 4-101
357749 04/15/2014 351577 3 102 M Replace latch on emergency escape window to be maximum 54 inches above the floor
357750 04/15/2014 351579 3 102 M Adjust door to latch properly
357751 04/15/2014 351581 3 103 M Replace GFCI outlet that will not trip
357753 04/15/2014 351585 3 107 M Replace latch on emergency escape window to be maximum 54 inches above the floor
357811 04/15/2014 351712 3 113 M Remove old damaged pencil shsrpener on counter top adjacent to door to exterior
357714 04/15/2014 351499 3 125 M Close and lock or latch open fire alarm and sound terminal cabinets
357715 04/15/2014 351501 3 125 M Secure loose cover for panel L2B
357741 04/15/2014 351556 4 101 M Adjust door to exterior to latch properly
324629 04/15/2014 279411 4 104 M Repair inoperable purge fan in science classroom
357740 04/15/2014 351554 4 104A M Close and secure open data box
357835 04/15/2014 351765 5 0000 M Provide chain and lock on gate of fencing around electrical equipment east of 5-115
357834 04/15/2014 351763 5 112 M Secure loose door knob
347156 04/15/2014 328092 5 116 M Repair, replace rotted wooden base boards
357836 04/15/2014 351767 5 117A M Replace missing ceiling tiles
357829 04/15/2014 351752 5 119 M Cover or wire nut all exposed wires in emergency relay cabinet
357742 04/15/2014 351559 6 0000 M Provide lock on gate of fencing around electrical equipment north of building 6
357831 04/15/2014 351756 6 101A M Replace missing ceiling tiles
357701 04/15/2014 351470 6 104 M Replace handicapped door handles. Plastic handles that fit over knob are loose and the knob is hard to operate
357816 04/15/2014 351722 6 105 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to emergency exhaust vent
357730 04/15/2014 351532 7 101 M Secure loose door handle
357823 04/15/2014 351739 7 106 M Repair hanging exit sign
357794 04/15/2014 351675 8 102 M Provide permanent number on maximum occupancy signage. Max occupancy is 59
357792 04/15/2014 351670 8 109D M Replace missing door knob for west door
357802 04/15/2014 351691 8 114 M Close and lock open EMS cabinet
357803 04/15/2014 351693 8 115 M Repair security screen on door louver. Loose and rolled up edges on screen
357801 04/15/2014 351689 8 117 M Close and lock open EMS cabinet
357756 04/15/2014 351591 8 119A M Repair leaking supply line for 3rd toilet
357784 04/15/2014 351653 9 0000 M Provide lock on gate of fencing around AC equipment south of 9-114
357778 04/15/2014 351641 9 102A M Replace 2 GFCI outlets that will not trip
357758 04/15/2014 351596 9 102B M Secure loose louver to door
357746 04/15/2014 351569 9 108 M Reinsulate hot water lines
357805 04/15/2014 351697 9 109 M Provide bushing on panel to protect yellow pig tail where it enters electrical panel
357782 04/15/2014 351649 9 111 M Repair lock on door to 9-112. Lock does not work
357781 04/15/2014 351647 9 112 M Repair hole in north wall of Gym
357795 04/15/2014 351677 9 118 M Replace cracked center toilet
357763 04/15/2014 351607 9 121A M Close and lock open cabinets
357760 04/15/2014 351601 9 123 M Repair or replace damaged door lock
357826 04/15/2014 351746 1 120 O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
357777 04/15/2014 351639 10 108C O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
357776 04/15/2014 351637 10 108D O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
357818 04/15/2014 351726 16 106 O Remove and prohibit plug in air freshener
357830 04/15/2014 351754 2 120A O Store chemicals properly
357745 04/15/2014 351567 3 106 O Keep sink drain filled with water. Room used for storage
357815 04/15/2014 351720 7 107 O Remove and prohibit paper covering window in door
228009 04/15/2014 4168 00 0000 C Provide better drainage between buildings to eliminate standing water
357824 04/15/2014 351741 1 107 MS Recharge fire extinguisher in corridor adjacent to 1-111
357697 04/15/2014 351462 1 126 MS Provide current inspection tag for fire extinguisher
357783 04/15/2014 351651 10 104 MS Provide current inspection tag for fire extinguisher
357772 04/15/2014 351626 16 006 MS Adjust door at top of stairs to latch properly. Door drags on floor
357770 04/15/2014 351622 16 192 MS Provide current inspection tag for fire extinguisher
357761 04/15/2014 351603 9 112 MS Replace missing fire extinguisher
357724 04/15/2014 351519 11 122 OS Prohibit storage of gasoline and gas powered equipment
357796 04/15/2014 351679 11 125 OS Prohibit storage of gasoline
357728 04/15/2014 351528 2 104 OS Prohibit storage of flammable chafing dish fuel. Store in flammable storage cabinet
357748 04/15/2014 351574 3 102 OS Keep area clear at emergency escape window
357752 04/15/2014 351583 3 107 OS Keep area clear at emergency escape window
357744 04/15/2014 351564 3 117 OS Provide clear access to fire extinguisher and fire alarm pull station
357718 04/15/2014 351507 3 120 OS Remove and prohibit desk in exit corridor
357743 04/15/2014 351561 4 107 OS Maintain clear aisle to exit to exterior
357819 04/15/2014 351730 7 112 OS Remove storage from electrical room. Room signed 7-119A
324779 11/13/2013 279743 00 9599 M Repair damaged chain link fencing around irrigation station west of Bldg. 10
324644 11/13/2013 279442 11 124 M Provide current state inspection tag for boiler
357719 11/13/2013 351509 11 127 M Label all circuits on electrical panel L1A. Wrong panel number
347122 11/13/2013 328024 2 101 M Repair deteriorated ceiling finish adjacent to window
347142 11/13/2013 328064 6 105 M Replace missing cover for emergency electrical shut off button
347094 11/13/2013 327968 9 108 M Provide current state inspection tag for boiler
347111 11/13/2013 328002 9 112 M Secure insulation adjacent to scoreboard
324803 11/13/2013 279792 9 112 M Repair damaged wood flooring in front of SE exit doors
324804 11/13/2013 279794 9 112 M Straighten bent rails and repair broken welds at rail supports at both ends of retractable bleachers
347093 11/13/2013 327966 9 123 M Provide current state inspection tag for boiler
347100 11/13/2013 327980 9 126 M Secure loose insulation in mezzanine
324778 04/11/2013 279741 10 108 M Provide door sweep on exterior door to minimize wide gap under door
347102 04/11/2013 327984 10 108A M Remove storage of expired fire extinguisher
347109 04/11/2013 327998 11 101 M Adjust south exterior doors to close and latch properly
347110 04/11/2013 328000 11 103A M Replace missing light bulbs and guards for light fixture, secure open sockets or remove light fixture
347107 04/11/2013 327994 11 112 M Provide panel schedule for electrical panel HK
347108 04/11/2013 327996 11 112 M Adjust door of walk-in freezer to close and latch properly
347105 04/11/2013 327990 11 124 M Repair door to close and latch properly
347103 04/11/2013 327986 11 126 M Repair door to close and latch properly
347085 04/11/2013 327950 16 001 M Replace missing escutcheon on fire sprinkler head at second floor landing
347091 04/11/2013 327962 16 002 M Determine cause of water damaged ceiling tiles and replace tiles, adjacent to 16-171
347078 04/11/2013 327935 16 006 M Adjust first floor corridor doors to close and latch properly
347083 04/11/2013 327946 16 106 M Determine cause of water damaged ceiling tiles and replace tiles
347082 04/11/2013 327944 16 110 M Determine cause of water damaged ceiling tiles and replace tiles
347080 04/11/2013 327940 16 110B M Adjust water pressure for sink, water pressure is very low
347079 04/11/2013 327937 16 112 M Replace missing floor tile
347084 04/11/2013 327948 16 190 M Replace missing ceiling tiles
347092 04/11/2013 327964 16 191 M Adjust door closer to control speed of closing door
347087 04/11/2013 327954 16 202 M Determine cause of water damaged ceiling tiles and replace tiles
347090 04/11/2013 327960 16 218A M Replace missing escutcheon on fire sprinkler head
347124 04/11/2013 328028 2 105 M Water at sinks is not running hot, make necessary repairs
347125 04/11/2013 328030 2 105 M Adjust door closer to control speed of closing door
347163 04/11/2013 328106 2 109 M Adjust door closer on courtyard door to control speed of closing door
347164 04/11/2013 328108 2 109A M Anchor toilet to floor
347149 04/11/2013 328078 2 114 M Adjust door closer to control speed of closing door
347150 04/11/2013 328080 2 117 M Replace missing base on wall adjacent to teachers desk
347151 04/11/2013 328082 2 120 M Adjust door closer on courtyard door to control speed of closing door
347126 04/11/2013 328032 3 0000 M Secure metal grate under drinking fountains adjacent to 3-126
347132 04/11/2013 328044 3 105 M Replace missing base on wall at 3-106
347130 04/11/2013 328040 3 110 M Replace missing ceiling tiles
347129 04/11/2013 328038 3 112 M Replace unnecessary Co2 fire extinguisher with ABC fire extinguisher
347127 04/11/2013 328034 3 117 M Remove unnecessary type K fire extinguisher, replace with ABC fire extinguisher
347165 04/11/2013 328110 3 125 M Fill void in electrical panel H2B
347135 04/11/2013 328050 4 102 M Secure loose data outlet box on west wall
347136 04/11/2013 328052 4 104 M Provide sign indicating location of purge fan, mount sign adjacent to purge fan buttons
347138 04/11/2013 328056 4 105 M Provide sign indicating location of purge fan, mount sign adjacent to purge fan buttons
321116 04/11/2013 271110 4 105 M Repair emergency eye wash. Missing piece
347152 04/11/2013 328084 5 109 M Provide panel schedule for electrical panel H4A
347159 04/11/2013 328098 5 111 M Adjust door closer to control speed of closing door
347155 04/11/2013 328090 5 117 M Replace missing panel schedule for electrical panel L4B
347162 04/11/2013 328104 5 119 M Repair door to close and latch properly
347139 04/11/2013 328058 6 102 M Adjust door closer on exterior door to control speed of closing door
347141 04/11/2013 328062 6 105 M Repair leaking sink faucet
347144 04/11/2013 328068 6 105 M Determine cause of water damaged ceiling tiles and replace tiles
347145 04/11/2013 328070 6 110 M Determine cause of water damaged ceiling tiles and replace tiles
347146 04/11/2013 328072 7 105 M Adjust door closer on exterior door to control speed of closing door
347148 04/11/2013 328076 7 116 M Replace bulbs in light fixture
347120 04/11/2013 328020 8 106 M Replace missing ceiling tiles
347121 04/11/2013 328022 8 109 M Provide sticker or stencil to identify location of fire extinguisher
347116 04/11/2013 328012 8 114 M Adjust door closer to control speed of closing door
347096 04/11/2013 327972 9 102 M Replace broken wall tiles above lockers adjacent to exterior door
347095 04/11/2013 327970 9 108 M Adjust door closer to control speed of closing door
347112 04/11/2013 328004 9 112 M Repair hole in wall below scoreboard
347113 04/11/2013 328006 9 112 M Replace missing base on wall adjacent to 9-119 doors
347098 04/11/2013 327976 9 114 M Repair damaged exit signs (x2)
347114 04/11/2013 328008 9 119 M Adjust door closer to control speed of closing door, adjacent to 9-112
347101 04/11/2013 327982 9 122 M Adjust door closer to control speed of closing door
347099 04/11/2013 327978 9 126 M Repair broken emergency lighting in mezzanine
347167 04/11/2013 328114 00 0000 O Remove chain and padlock from east gate adjacent to bus loop
347117 04/11/2013 328014 1 109 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
347118 04/11/2013 328016 1 111 O Prohibit multi outlet electrical adaptor or replace with surge protector
347119 04/11/2013 328018 1 113 O Prohibit use of surge protector with damaged cord, prohibit plugging microwave into surge protector
347081 04/11/2013 327942 16 108 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
347088 04/11/2013 327956 16 202 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
347089 04/11/2013 327958 16 208 O Remove and prohibit air freshener
347133 04/11/2013 328046 3 102 O Post sign indicating primary and secondary evacuation routes
347128 04/11/2013 328036 3 113 O Post sign indicating primary and secondary evacuation routes
347134 04/11/2013 328048 4 101 O Prohibit plugging surge protector into surge protector
347153 04/11/2013 328086 5 107 O Remove and prohibit air freshener (scented wax warmer)
347157 04/11/2013 328094 5 116 O Prohibit plugging surge protector into surge protector
347143 04/11/2013 328066 6 105 O Prohibit using duct tape to cover purge fan and electrical shut off buttons
347147 04/11/2013 328074 7 104 O Prohibit plugging surge protector into surge protector
347097 04/11/2013 327974 9 104 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
277477 04/11/2013 176871 16 116A C Provide additional fire sprinkler head to provide complete coverage of room
277523 04/11/2013 176963 16 218A C Provide additional fire sprinkler head to provide full coverage in room
347123 04/11/2013 328026 2 105 C Verify or provide ventilation to exterior for hood at stove on west wall
347160 04/11/2013 328100 5 118 MS Recharge fire extinguisher
347104 04/11/2013 327988 11 122 OS Prohibit storage of gas powered equipment
347131 04/11/2013 328042 3 108 OS Maintain clear aisle to corridor exit
347137 04/11/2013 328054 4 104 OS Maintain clear aisle to exterior exit
347154 04/11/2013 328088 5 107 OS Remove and prohibit use of candle
347140 04/11/2013 328060 6 104 OS Provide clear access to fire extinguisher
347115 04/11/2013 328010 9 119 OS Prohibit storage in exit vestibule to maintain clear aisle to exit
324679 04/11/2013 279514 00 0000 CS Provide suitable area for storage and recharging of golf carts and floor cleaning machines
347161 04/11/2013 328102 5 120 FS Secure hanging heat detector
324652 12/19/2012 279459 00 9599 M Secure leaning post for chain link fencing at baseball field north of Bldg. 16
324776 12/19/2012 279737 00 9599 M Repair damaged downspout at SW corner of Building 9
321115 12/19/2012 271108 11 102 M Provide current dated flame resistance label on all stage curtains. Tags dated April of 2004
347106 12/19/2012 327992 12 103 M Replace rusty, damaged grate on door
324638 12/19/2012 279430 3 102 M Replace missing lever on accessible corridor door
324640 12/19/2012 279434 3 103 M Replace missing lever on accessible corridor door
324641 12/19/2012 279436 3 106 M Replace missing lever on accessible corridor door
324642 12/19/2012 279438 3 108 M Replace missing lever on accessible corridor door
324635 12/19/2012 279423 3 112 M Replace missing cover on thermostat adjacent to corridor door
324639 12/19/2012 279432 3 119 M Replace missing lever on accessible corridor door
324637 12/19/2012 279428 4 101 M Replace missing lever on accessible corridor door
321188 12/19/2012 271262 7 115 M Repair or replace leaking water heater
324781 12/19/2012 279747 9 114A M Determine cause of water damaged ceiling tiles and replace tiles
324794 12/19/2012 279774 9 114A M Replace missing lever on accessible door
324793 12/19/2012 279772 9 117 M Replace missing lever on accessible door
324796 12/19/2012 279778 9 118 M Repair broken ceramic tile base along wall under window
324774 12/02/2011 279733 00 0000 M Repair leaking gutters at edge of covered walkways between buildings to eliminate standing water on sidewalks
324647 12/02/2011 279448 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
324788 12/02/2011 279761 1 127A M Repair exhaust fan in clinic bathroom
324785 12/02/2011 279755 1 128 M Repair exhaust fan in men's bathroom
324786 12/02/2011 279757 1 131 M Repair exhaust fan in women's bathroom
324787 12/02/2011 279759 1 132B M Repair exhaust fan in clinic bathroom
320818 12/02/2011 270480 10 105A M Replace burned bulbs in explosion proof light fixture
324777 12/02/2011 279739 10 106 M Repair emergency lighting in mechanical mezzanine
324772 12/02/2011 279729 11 101 M Replace missing ceiling tile at SW corner
324773 12/02/2011 279731 11 101 M Repair damaged corner of wall adjacent to NW exit doors
228089 12/02/2011 4273 11 102 M Provide dated flame resistance label on tan curtain
324669 12/02/2011 279493 16 009 M Replace missing escutcheon on fire sprinkler head at botttom of stairs adjacent to exterior door
324650 12/02/2011 279455 16 115 M Replace missing ceiling tiles above teacher's desk (x2)
324649 12/02/2011 279452 16 280 M Replace missing escutcheon on fire sprinkler head
324664 12/02/2011 279483 2 0000 M Secure loose wood rail to post outside covered walkway adjacent to 2-116
324677 12/02/2011 279508 2 105 M Disconnect power to electrical range or remove at teacher's station - teacher removed knobs but burners can still be turned on easily - exhaust fan button is also missing
324671 12/02/2011 279498 2 108 M Repair broken hinges for all cabinet doors under sink
324632 12/02/2011 279417 3 105 M Replace missing ceiling tile in corridor adjacent to 3-104
324634 12/02/2011 279421 3 117C M Repair exhaust fan in bathroom
324628 12/02/2011 279409 4 104A M Determine cause of water damaged ceiling tiles and replace tiles
324654 12/02/2011 279463 5 120 M Repair chiller lines to elimnate water leak
321189 12/02/2011 271265 7 115 M Provide current inspection tag for hot water heater
324791 12/02/2011 279767 8 113A M Repair door to open and close properly - door rubs on frame
324799 12/02/2011 279784 9 102 M Fill in maximum occupancy sign to read 99 occupants in girls locker
321279 12/02/2011 271466 9 108 M Provide current state inspection tag for boiler
324801 12/02/2011 279788 9 112 M Replace missing panic door hardware on NW exit door
324802 12/02/2011 279790 9 112 M Adjust SE exit doors to latch properly
324795 12/02/2011 279776 9 114 M Repair all broken ceramic tile base along wall under lockers and in shower area
324798 12/02/2011 279782 9 114 M Provide maximum occupancy signage which reads 99 occupancys. Current sign reads 142 occupants in boys locker
324780 12/02/2011 279745 9 116 M Repair emergency lighting in mechanical mezzanine
324797 12/02/2011 279780 9 118 M Replace broken mirrored glass in window between group bathroom and PE office
321278 12/02/2011 271464 9 123 M Provide current state inspection tag for boiler
324771 12/02/2011 279727 00 0000 O Remove broken furniture and glass behind Bldg. 10 to keep site free of hazardous debris
324789 12/02/2011 279763 1 103 O Remove and prohibit air freshener (office facing principal's office)
324790 12/02/2011 279765 1 103 O Prohibit plugging microwave and toaster oven into surge protector - plug appliances directly into permanent electrical outlet (office facing principal's office)
324636 12/02/2011 279425 3 117A O Keep space clean around clothes dryer exhaust duct to eliminate hazardous condition
324657 12/02/2011 279471 5 119 O Replace light fixtures or replace light bulbs in electrical room
324782 12/02/2011 279749 8 101 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
324800 12/02/2011 279786 9 117 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
324784 12/02/2011 279753 1 113 MS Provide current inspection tag for fire extinguisher
324775 12/02/2011 279735 11 112 MS Replace type K fire extinguisher with an ABC fire extinguisher in kitchen under windows
324653 12/02/2011 279461 16 009 MS Adjust fire door to 1st floor corridor to latch properly - door rubs on frame
324651 12/02/2011 279457 16 191 MS Provide current inspection tag for fire sprinkler system - riser tagged quarterly 4/12/2011
324630 12/02/2011 279413 3 101 MS Adjust fire door facing group bathroom to open and close properly - bottom of door rubs on floor
324631 12/02/2011 279415 3 104 MS Remove dog leg hold open device from corridor door
324643 12/02/2011 279440 5 118 MS Provide current inspection tag for fire extinguisher
324623 12/02/2011 279395 6 102 MS Remove hold open device from corridor door
324621 12/02/2011 279392 6 108 MS Remove hold open device from corridor door
321282 12/02/2011 271472 11 104 OS Remove and prohibit storage on stage exit stairs
324645 12/02/2011 279444 11 122 OS Prohibit charging batteries in room
324633 12/02/2011 279419 3 107 OS Relocate storage blocking view of emergency escape window sign
324656 12/02/2011 279468 3 125 OS Remove storage from electrical room
324659 12/02/2011 279473 5 115 OS Rearrange furniture to maintain a minimum 3 ft clear path to back exterior door
324661 12/02/2011 279478 7 112 OS Remove storage from electrical room (labeled 119A)
324792 12/02/2011 279769 8 109 OS Remove musical instruments off floor in front of double exit doors - adjacent to 8-109C
324783 12/02/2011 279751 8 114 OS Remove storage from electrical room
324648 12/02/2011 279450 9 123 OS Remove tables stored in boiler room
277449 12/02/2011 176812 4 0000 CS Modify gate in fencing between Bldgs. 4 & 5 to allow egress at all times and remove padlock from gate
321284 09/07/2011 271476 11 112 M Verify kitchen hood fans are working. Not running at time of inspection. Kitchen staff must turn on fan at hood wash down panel
321185 09/07/2011 271256 3 122 M Repair damaged wall at floor sink.
321273 09/07/2011 271448 00 0000 O Remove wood frame with protruding nails used to rake baseball infields at north property line north of Bldg. 16
255706 09/07/2011 132516 7 116 C Provide continuously operating mechanical exhaust to exterior for chemical storage room
321274 04/26/2011 271451 00 0000 M Replace 2 locks on gates at east properety line at bus loop adjacent to bike rack and on gate with panic bar
320800 04/26/2011 270442 00 0000 M Repair inoperable drinking fountain east of track
321159 04/26/2011 271204 1 101 M Provide tempered or safety glass in fire extinguisher cabinet or remove glazing for cabinet adjacent to 1-112
321169 04/26/2011 271222 1 101 M Replace lightning detector. Not working
321160 04/26/2011 271206 1 123 M Provide tempered or safety glass in fire extinguisher cabinet or remove glazing for cabinet adjacent to 1-118
321162 04/26/2011 271208 1 126 M Replace missing ceiling tiles
321109 04/26/2011 271096 1 130 M Provide current inspection tag for hot water heater
321110 04/26/2011 271098 10 101 M Repair power poles that are coming apart
320821 04/26/2011 270488 10 101B M Secure loose door knob
320822 04/26/2011 270490 10 101C M Secure loose door knob
320820 04/26/2011 270485 10 104 M Provide correct bracket for fire extinguisher
321141 04/26/2011 271166 10 108B M Secure loose cover on panel H8
321112 04/26/2011 271102 10 108C M Repair leaking toilet supply line
321287 04/26/2011 271482 11 116 M Provide certification that emergency generator is operable. Indicator panel in custodian's office indicated low fuel
321290 04/26/2011 271486 11 118 M Repair GFCI outlet that won't trip
321291 04/26/2011 271490 11 124 M Provide current State inspection tag for boiler
321295 04/26/2011 271498 12 102 M Secure loose door knob
321275 04/26/2011 271454 12 103 M Provide correct bracket for fire extinguisher
321143 04/26/2011 271172 14 190 M Adjust door to latch properly
321262 04/26/2011 271424 16 0000 M Provide chain and lock on gate of fencing around pump enclosure east of Bldg. 16
321268 04/26/2011 271436 16 0000 M Repair leak in irrigation system adjacent to NE corner of Bldg. 16
321272 04/26/2011 271444 16 002 M Replace missing end cap on panic bar on south corridor door to exterior
320815 04/26/2011 270474 16 009 M Repair hole in wall at bottom of stairs and provide door stop with backing or provide door stop on floor
321232 04/26/2011 271358 16 110 M Determine cause of water damaged ceiling tiles and replace tiles
320810 04/26/2011 270463 16 112 M Anchor shelving to wall
321267 04/26/2011 271434 16 113 M Determine cause of water damaged ceiling tiles and replace tiles
320808 04/26/2011 270459 16 117 M Determine cause of water damaged ceiling tiles and replace tiles
320811 04/26/2011 270466 16 180 M Provide correct bracket for fire extinguisher
321271 04/26/2011 271442 16 202 M Replace missing escutcheon on fire sprinkler head
321264 04/26/2011 271428 16 205 M Determine cause of water damaged and rust stained ceiling tiles and replace tiles adjacent to door. Investigate possible fire sprinkler leak
321269 04/26/2011 271438 16 216A M Secure loose escutcheon on fire sprinkler head
321265 04/26/2011 271430 16 221 M Replace rusted fire sprinkler head and repair leak
321260 04/26/2011 271419 16 291A M Replace surge suppressor that is in alarm on panel H2
321147 04/26/2011 271177 2 101 M Repair power pole that is coming apart
321167 04/26/2011 271219 2 105 M Adjust door to exterior to latch properly
321242 04/26/2011 271376 2 109A M Anchor toilet to floor
321240 04/26/2011 271373 2 113A M Anchor toilet to floor
321261 04/26/2011 271422 2 117 M Replace GFCI outlets adjacent to SE sink and on north wall that will not trip
321212 04/26/2011 271311 2 121 M Replace missing cover plate on panic hardware on south door from interior courtyard
321214 04/26/2011 271318 2 121 M Eliminate bees on fascia of pavillion in interior courtyard
321234 04/26/2011 271361 3 105 M Repair damaged wall in corridor
321270 04/26/2011 271440 3 108 M Repair or replace broken weather stripping with sharp edges on door to exterior
320805 04/26/2011 270453 3 115 M Replace missing ceiling tiles
320803 04/26/2011 270448 3 119 M Secure loose glazing in fire door to exterior
321186 04/26/2011 271259 3 119A M Repair exhaust fan in bathroom
321183 04/26/2011 271253 3 122 M Provide current inspection tag for hot water heater
321182 04/26/2011 271251 3 125 M Provide panel schedule for panel L2B
321142 04/26/2011 271168 4 102 M Secure loose data outlet to wall adjacent to door to exterior
321152 04/26/2011 271189 4 104 M Repair purge fan. Will not come on
321144 04/26/2011 271174 4 104A M Determine cause of water damaged ceiling tiles and replace tiles
321191 04/26/2011 271267 5 104 M Replace missing base along wall
320806 04/26/2011 270455 5 106 M Provide tempered or safety glass in fire extinguisher cabinet or remove glazing
321196 04/26/2011 271278 5 109 M Provide cover on open data box
321202 04/26/2011 271283 5 109 M Repair or replace damaged door to eliminate gap at bottom of door that allows mice to enter room
320809 04/26/2011 270461 5 118 M Remove sign indicating "Fire Alarm Pull Station Inside"
321192 04/26/2011 271271 5 119 M Provide panel schedule for panel L5B
321218 04/26/2011 271326 5 120 M Secure loose fiberglass insulation at ceiling
321222 04/26/2011 271335 5 120 M Set hinge pins on door
321205 04/26/2011 271298 6 106 M Provide tempered or safety glass in fire extinguisher cabinet or remove glazing
321207 04/26/2011 271301 6 108 M Adjust door to exterior to latch properly
320812 04/26/2011 270468 7 105 M Replace missing ceiling tiles
321256 04/26/2011 271409 7 112 M Secure loose door knob
321158 04/26/2011 271202 8 109 M Secure loose nosings on risers
321108 04/26/2011 271094 8 115 M Provide current inspection tag for hot water heater
321155 04/26/2011 271195 8 116 M Provide panel schedule for panels H6B and unnumbered panel
321156 04/26/2011 271197 8 118A M Anchor and caulk handicapped toilet to floor
321163 04/26/2011 271211 8 118A M Repair leaking toilet supply line
321157 04/26/2011 271199 8 119A M Repair noisey exhaust fan
321281 04/26/2011 271470 9 0000 M Remove tree growing in rain gutter at SE corner of building
321276 04/26/2011 271456 9 102 M Replace damaged door louver
321178 04/26/2011 271240 9 112 M Repair damaged wood flooring in SW corner of Gymnasium adjacent to drinking fountain
321181 04/26/2011 271248 9 112 M Clean dust and dirt of off of A/C return grilles in Gymnasium
320801 04/26/2011 270444 9 112 M Repair damaged exit sign at NE exit of Gym
321236 04/26/2011 271364 9 114 M Replace missing and broken ceramic tile base along wall and benches
321263 04/26/2011 271426 9 114A M Repair or replace leaking washing machine
321277 04/26/2011 271462 9 116 M Replace missing laminate on toilet stall door or replace door
321280 04/26/2011 271468 9 124 M Repair door to open and close properly
320817 04/26/2011 270478 00 0 O No access was available to 1-103, 1-110, 5-118, 5-118A, 9-106, 11-105 and 16-210. Please be prepared to access these rooms during the report review meeting.
321166 04/26/2011 271216 1 104A O Replace tubes in light fixture
321113 04/26/2011 271104 10 108C O Keep floor drain and shower drain filled with water. Once every 2 months pour 1 quart of water down drains
321114 04/26/2011 271106 10 108D O Keep floor drain and shower drain filled with water. Every 2 months pour 1 quart of water down drains
321286 04/26/2011 271480 11 108A O Clean exhaust fan grille
321259 04/26/2011 271416 16 216A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
321258 04/26/2011 271414 16 218A O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
320804 04/26/2011 270451 3 0000 O Remove and prohibit paper covering windows in doors throughout building
321204 04/26/2011 271295 3 103A O Provide clear access to electrical panel
321194 04/26/2011 271274 3 106 O Remove and prohibit paper covering window in door
321118 04/26/2011 271114 3 109 O Remove and prohibit plug in air freshener
321219 04/26/2011 271330 7 101 O Remove and prohibit paper covering windows in doors
321117 04/26/2011 271112 9 0000 O Prohibit parking black Dodge pickup truck on grass area west of Bldg. 9
321154 04/26/2011 271193 2 105 C Provide ventilation to exterior for west range
302251 04/26/2011 229847 11 104 F Relocate heat detector to peak point in mechanical room
320819 04/26/2011 270482 10 104 MS Provide current inspection tag for fire extinguisher
321111 04/26/2011 271100 10 105 MS Provide current inspection tag for fire extinguisher
321283 04/26/2011 271474 11 114 MS Relocate type K fire extinguisher adjacent to ice machine to provide clear access to fire extinguisher
321285 04/26/2011 271478 11 119 MS Provide current inspection tag for fire extinguisher
320813 04/26/2011 270470 16 191A MS Provide current inspection tag for fire extinguisher
320807 04/26/2011 270457 16 291A MS Provide current inspection tag for fire extinguisher
321266 04/26/2011 271432 3 116 MS Provide current inspection tag for fire extinguisher
320802 04/26/2011 270446 3 119 MS Adjust fire door to exterior to latch properly
321294 04/26/2011 271493 11 124 OS Remove storage from boiler room
320814 04/26/2011 270472 16 001 OS Remove and prohibit storage in stair exit to exterior
321209 04/26/2011 271306 3 106 OS Relocate desks to maintain clear aisle to exit to exterior
321179 04/26/2011 271245 3 112 OS Maintain clear aisle to exit to exterior
321221 04/26/2011 271332 7 101 OS Maintain clear aisle to exits
321140 04/26/2011 271164 11 104 CS Provide fire extinguisher in mechanical room
321229 04/26/2011 271345 2 103B FS Provide heat detector in storage room. Room is behind new mechanical room 15-190
238568 01/21/2011 96754 3 117 M Repair exhaust fan for range
302090 04/21/2010 229506 00 9599 M Replace missing section of chain link fencing east of 6-105
302246 04/21/2010 229837 11 122 O Prohibit plugging refrigerator into extension cord in caged area - plug directly into permanent electrical outlet
302239 04/21/2010 229821 3 102 O Prohibit plugging surge protector into surge protector - plug each surge protector directly into permanent electrical outlet
302240 04/21/2010 229824 3 102 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
302241 04/21/2010 229827 3 118 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
302084 04/21/2010 229494 4 103 O Prohibit plugging surge protector into surge protector at teacher's desk - plug each surge protector directly into permanent electrical outlet
302087 04/21/2010 229500 6 102 O Prohibit plugging surge protector into surge protector at teacher's desk - plug each surge protector directly into permanent electrical outlet
302085 04/21/2010 229496 7 102 O Prohibit plugging surge protector into surge protector at teacher's desk - plug each surge protector directly into permanent electrical outlet
302086 04/21/2010 229498 7 103 O Prohibit plugging surge protector into surge protector at teacher's desk - plug each surge protector directly into permanent electrical outlet
255707 04/21/2010 132518 7 104A O Relocate lab chemicals to flammable storage room 7-116(118) adjacent to girls bathroom
297148 04/21/2010 218798 7 109 O Prohibit plugging surge protector into surge protector under teacher's desk
302235 03/23/2010 229814 10 107 M Repair exterior door to open and close properly - door rubs on frame
302259 03/23/2010 229865 11 107 M Repair cracked floor tiles adjacent to exterior door and adjacent to serving counter
302270 03/23/2010 229890 11 111 M Replace broken base tile adjacent to door to dish washing room
302258 03/23/2010 229862 11 112 M Mount fire extinguisher at maximum five feet above floor on south wall - see kitchen manager
302257 03/23/2010 229860 11 117 M Replace crushed dryer duct for clothes dryer
302269 03/23/2010 229888 11 120 M Replace broken emergency release hardware in cooler
302234 03/23/2010 229807 14 190 M Determine cause of water leak from air conditioning unit on north wall and repair
302228 03/23/2010 229798 16 001 M Adjust exterior doors at bottom of stairwell to latch properly
302088 03/23/2010 229502 16 002 M Determine cause of water damaged ceiling tiles and replace tiles in corridor adjacent to 16-190
302231 03/23/2010 229804 16 191A M Repair inoperable air conditioner unit above door
302083 03/23/2010 229492 2 105 M Adjust front door to latch properly
228038 03/23/2010 4255 4 102 M Repair damaged wall adjacent to corridor door
277440 03/23/2010 176793 4 105 M Adjust flow of emergency eye wash and replace missing nozzle
302080 03/23/2010 229486 4 110 M Replace missing cover for panic hardware on exit door in corridor
302249 03/23/2010 229843 5 116 M Repair emergency lighting
302091 03/23/2010 229508 6 104 M Secure or replace loose rubber gasket around window glass
302089 03/23/2010 229504 7 102 M Secure communications junction box to wall adjacent to exterior door
302092 03/23/2010 229510 8 109 M Provide cover for exposed electrical outlet at center of bottom riser
297027 03/23/2010 218536 8 109 M Repair damaged vinyl nosing at risers edge
302237 03/23/2010 229817 8 115 M Secure loose door knob
302224 03/23/2010 229791 9 102A M Determine cause of water damaged ceiling tiles and replace tiles
302223 03/23/2010 229789 9 114A M Determine cause of water damaged ceiling tiles and replace tiles
302244 03/23/2010 229832 1 102 O Prohibit plugging microwave into cart outlet - plug directly into permanent electrical outlet
277616 03/23/2010 177159 11 122 O Remove storage blocking clear access to emergency eye wash/shower
302272 03/23/2010 229895 16 110A O Remove refrigerator from bathroom and prohibit running appliance electrical cord under bathroom sink
302082 03/23/2010 229490 2 105 O Prohibit plugging microwave into surge protector under windows - plug directly into permanent electrical outlet
302081 03/23/2010 229488 2 113C O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
302242 03/23/2010 229830 3 113 O Prohibit plugging microwave into surge protector adjacent to teacher's desk - plug directly into permanent electrical outlet
302247 03/23/2010 229839 5 104 O Prohibit plugging microwave into surge protector adjacent to sink - plug directly into permanent electrical outlet
302248 03/23/2010 229841 5 115 O Remove and prohibit combustible beanbag chairs (x3)
302252 03/23/2010 229849 5 115 O Prohibit plugging surge protector into extension cord, extension cord into surge, etc... Plug each surge protector directly into permanent electrical outlet and eliminate use of 13A extension cords adjacent to east exterior door
297037 03/23/2010 218556 7 109A O Remove and prohibit flammable curtain covering window
302238 03/23/2010 229819 9 117 O Prohibit plugging microwave and refrigerator into surge protector - plug appliances directly into permanent electrical outlet
297224 03/23/2010 218954 00 0000 C Provide exterior signage indicating property address
277599 03/23/2010 177125 17 101 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
302273 03/23/2010 229897 2 105 C Provide ventilation to exterior for range adjacent to refrigerator at teacher's station
302222 03/23/2010 229787 10 106 MS Provide current inspection tag for fire extinguisher
302230 03/23/2010 229802 10 108 MS Replace missing fire extinguisher
302271 03/23/2010 229892 11 112 MS Relocate type K fire extinguisher currently above kitchen sink to be adjacent to dry storage room door
302221 03/23/2010 229785 11 126 MS Provide current inspection tag for fire extinguisher
302217 03/23/2010 229775 16 191 MS Provide current inspection tag for fire extinguisher
302220 03/23/2010 229782 7 112 MS Provide current inspection tag for fire extinguisher
302219 03/23/2010 229779 7 116 MS Provide current inspection tag for fire extinguisher
302218 03/23/2010 229777 9 116 MS Provide current inspection tag for fire extinguisher
302245 03/23/2010 229835 16 101 OS Prohibit use of wedge to hold fire door in open position
302256 03/23/2010 229854 5 115 OS Rearrange furniture to maintain a minimum 3ft clear aisle to east exterior door
302250 03/23/2010 229845 5 116 OS Relocate chairs to maintain 3 ft clear path to exterior door
302226 03/23/2010 229793 9 115 OS Prohibit storage of gas powered leaf blower
255699 10/27/2009 132499 11 112 M Provide current inspection tag for kitchen steamer
277403 10/27/2009 176718 2 105 M Connect duct from back of stove at teacher's station to duct in wall
277443 10/27/2009 176799 4 104 M Secure loose door hardware on outside face of corridor door
296832 10/27/2009 218125 2 105 O Prohibit plugging surge protector into surge protector under teacher's desk
277468 10/27/2009 176851 2 119 O Remove and prohibit flammable curtains from window
277459 10/27/2009 176832 7 104 O Replace missing fire blanket
297150 10/27/2009 218802 7 105 O Prohibit plugging surge protector into surge protector behind aquariums
297021 10/27/2009 218524 1 126 MS Provide current inspection tag for fire extinguisher
277485 10/27/2009 176885 11 109 MS Adjust fire door between serving line and dining room to close properly - door sticks open on floor
297017 10/27/2009 218516 16 291A MS Provide current inspection tag for fire extinguisher
277610 10/27/2009 177147 11 122 OS Prohibit charging batteries in room
277483 10/27/2009 176883 16 0000 OS Prohibit wedging open all doors along corridors
297023 05/05/2009 218528 1 117 M Determine cause of water damaged ceiling tiles and replace tiles
296964 05/05/2009 218406 10 101 M Repair back-up battery for exit signs
296965 05/05/2009 218408 10 105 M Repair light in exit sign above entry door
296966 05/05/2009 218410 10 105A M Repair light fixture in storage room
296962 05/05/2009 218403 11 127 M Secure cover to fire alarm panel on wall
296958 05/05/2009 218393 12 102 M Provide cover on exposed LB junction box
296959 05/05/2009 218395 12 102 M Remove tree blocking back door
296960 05/05/2009 218397 12 103 M Provide cover on exposed electrical junction box above generator
296961 05/05/2009 218401 12 103 M Provide cover on fire alarm box on wall
297025 05/05/2009 218532 1 122 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
297024 05/05/2009 218530 1 124 O Prohibit plugging surge protector into surge protector under desk
277648 05/05/2009 177226 10 105 O Arrange storage in an orderly manner and discard unused storage
277629 05/05/2009 177185 11 105 O Prohibit plugging refrigerator into extension cord - plug directly into permanent electrical outlet and prohibit use of extension cord with multi-outlet end
296932 05/05/2009 218338 11 113 O Prohibit plugging surge protector into surge protector
296948 05/05/2009 218372 11 122 O Prohibit plugging washing machine into extension cord - plug directly into permanent electrical outlet
297022 05/05/2009 218526 1 112 MS Provide current inspection tag for fire extinguisher
296931 05/05/2009 218336 11 112 MS Provide current inspection tag for kitchen hood fire suppression system
296954 05/05/2009 218386 11 123 MS Replace missing CBS block in fire rated wall between boiler and compressor rooms
296957 05/05/2009 218391 11 123 MS Remove storage from compressor room
296967 05/05/2009 218412 10 105 OS Relocate storage to maintain clear aisle to back door
277642 05/05/2009 177213 10 105B OS Prohibit storage of gas powered pressure cleaner and gas can
297226 05/05/2009 218964 11 102 OS Prohibit use of temporary stage until required maintenance is performed and documentation provided that stage is safe to use
296945 05/05/2009 218360 11 122 OS Prohibit storage of gas can - relocate flammables to flammable storage room (17-101) adjacent to generator room
296951 05/05/2009 218376 11 125 OS Prohibit storage of gas powered leaf blower - relocate flammables to flammable storage room
277486 02/06/2009 176888 11 101 M Determine cause of water damaged ceiling tiles and replace tiles at 11-109
277620 02/06/2009 177167 11 105 M Remove light strip above mirror - not used and no bulbs in sockets
277451 02/06/2009 176816 11 112 M Determine cause of ice build up on freezer floor and repair
277603 02/06/2009 177133 12 103 M Provide certification that all student occupied spaces have emergency lights and all are operable
255269 02/06/2009 131589 16 009 M Relocate ADA extended grab handrail at bottom of center wall of stairs to be along side wall
297020 02/06/2009 218522 16 190 M Secure ceiling tile in place
297019 02/06/2009 218520 16 290 M Replace missing ceiling tiles
277430 02/06/2009 176772 3 122 M Repair water fountain adjacent to 3-126
277433 02/06/2009 176778 4 110 M Secure loose door hardware on outside face of doors at end of corridor
296820 02/06/2009 218101 5 101 M Repair back-up battery in exit sign
277379 02/06/2009 176667 5 112 M Secure loose door hardware
296969 02/06/2009 218416 5 117 M Remove inappropriate occupancy sign in CCTV studio
296824 02/06/2009 218109 6 107 M Replace missing ceiling tiles
297155 02/06/2009 218812 7 105 M Replace missing ceiling tiles above aquariums
297026 02/06/2009 218534 8 109 M Replace broken tile at risers
297028 02/06/2009 218538 9 102A M Replace missing ceiling tiles
296968 02/06/2009 218414 9 103 M Repair light fixture in PE storage room
297032 02/06/2009 218546 9 108 M Provide current inspection tag for boiler
297033 02/06/2009 218548 9 123 M Provide current inspection tag for boiler
277664 02/06/2009 177259 10 107A O Prohibit plugging surge protector into surge protector
277665 02/06/2009 177262 10 107A O Prohibit plugging refrigerator and microwave oven into surge protector - plug directly into permanent electrical outlet
277667 02/06/2009 177266 10 108 O Prohibit plugging extension cord into extension cord
296831 02/06/2009 218123 16 105 O Remove and prohibit paper covering window in door
296821 02/06/2009 218103 16 110 O Prohibit plugging surge protector into surge protector
296822 02/06/2009 218105 16 110A O Remove refrigerator from bathroom and prohibit running appliance electrical cord under bathroom sink
277475 02/06/2009 176867 16 116 O Remove cracked mirror
297038 02/06/2009 218558 2 102 O Remove and prohibit flammable curtain covering window
296900 02/06/2009 218272 2 105 O Prohibit plugging microwave into extension cord under window - plug directly into permanent electrical outlet
277406 02/06/2009 176724 2 108 O Prohibit plugging surge protectors into extension cord with multiple outlet end - Plug each surge protector directly into permanent electrical outlet and eliminate use of extension cord
296927 02/06/2009 218328 3 101 O Prohibit plugging surge protector into surge protector behind teacher's desk
277413 02/06/2009 176738 3 103 O Provide rubber cover strips over electrical cords on floor
296912 02/06/2009 218294 3 112 O Prohibit plugging surge protector into surge protector under computer stations at center of room
255689 02/06/2009 132478 3 117 O Prohibit plugging one surge protector into another adjacent to teacher's desk, plug each surge protector directly into wall outlet
296908 02/06/2009 218278 3 118 O Prohibit plugging refrigerator and microwave into cart electrical outlet - plug appliances directly into permanent electrical outlet
277426 02/06/2009 176764 3 119 O Remove and prohibit paper covering walls - maximum amount of each wall that can be covered is 20%
296924 02/06/2009 218319 4 105 O Prohibit plugging surge protector into surge protector adjacent to teacher's desk
277437 02/06/2009 176787 4 107 O Prohibit taping electrical and data cords to floor - provide rubber cover strips over cords
277380 02/06/2009 176669 5 104 O Prohibit plugging surge protector into unacceptable extension cord (non-UL rated cord)
296816 02/06/2009 218092 5 115 O Remove and prohibit combustible beanbag chairs (X2)
296818 02/06/2009 218097 5 117A O Prohibit use of CCTV closet as classroom - space does not meet classroom specifications
296819 02/06/2009 218099 5 117B O Prohibit plugging extension cord into surge protector
296828 02/06/2009 218117 6 102 O Prohibit plugging surge protector into surge protector under teacher's desk
296829 02/06/2009 218119 6 103 O Prohibit plugging surge protector into surge protector adjacent to teacher's desk
296830 02/06/2009 218121 6 103 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
277396 02/06/2009 176703 6 104 O Provide rubber cover strips over electrical cords on floor
296825 02/06/2009 218111 6 105 O Prohibit plugging surge protector into surge protector under teacher's desk
296826 02/06/2009 218113 6 105 O Relocate cart to maintain clear access to emergency eye wash/shower
277389 02/06/2009 176689 6 108 O Prohibit plugging surge protector into surge protector at teacher's desk
297156 02/06/2009 218815 7 101 O Remove and prohibit paper covering window glass
297158 02/06/2009 218818 7 101 O Eliminate extension cord with multiple outlet end under teacher's desk
277454 02/06/2009 176822 7 102 O Provide rubber cover strips on electrical cords on floor
277455 02/06/2009 176824 7 102 O Prohibit plugging surge protector into surge protector
277458 02/06/2009 176830 7 103 O Prohibit plugging surge protector into extension cord at teacher's desk
277461 02/06/2009 176836 7 105 O Provide rubber cover strips over electrical cords on floor
297153 02/06/2009 218807 7 105 O Eliminate extension cord with multiple outlet end behind aquarium
277462 02/06/2009 176838 7 107 O Provide rubber cover strips over electrical cords on floor
277463 02/06/2009 176840 7 108 O Provide rubber cover strips over electrical cords on floor
297029 02/06/2009 218540 8 101 O Prohibit plugging surge protector into surge protector behind desk
277487 02/06/2009 176890 8 105 O Maintain storage room in an orderly manner
277627 02/06/2009 177181 8 109 O Eliminate extension cord with multi-outlet end or replace with minimum 15A cord with single outlet end - at cabinet
297034 02/06/2009 218550 9 117 O Prohibit plugging microwave and refrigerator into surge protector - plug appliances directly into permanent electrical outlet
297035 02/06/2009 218552 9 124 O Maintain storage room in an orderly manner
228015 02/06/2009 4167 00 9599 C Provide fencing around transformer (northwest of Building 4)
228013 02/06/2009 34103 00 9599 C Provide fencing around electrical panels north of Building 7
277634 02/06/2009 177197 8 114 C Provide signage indicating room name and number at appropriate height with raised and Braille characters
297018 02/06/2009 218518 16 191 MS Provide current inspection tag for fire sprinkler system
297016 02/06/2009 218514 16 191A MS Provide current inspection tag for fire extinguisher
255579 02/06/2009 132250 16 291A MS Provide rated sealant between top of wall and ceiling
277386 02/06/2009 176683 6 110 MS Adjust fire doors at end of corridor to close and latch properly
297036 02/06/2009 218554 7 110 MS Adjust fire door to latch properly
277653 02/06/2009 177236 10 101C OS Prohibit storage of flammable paint cleaner
297159 02/06/2009 218820 2 101 OS Relocate desk to maintain clear path to exterior door
296928 02/06/2009 218330 3 101 OS Relocate chairs to maintain clear access to exterior door
296930 02/06/2009 218334 3 102 OS Relocate storage blocking clear view of "Emergency Exit" window
296915 02/06/2009 218301 3 110 OS Prohibit storage of flammable fabric hanging from ceiling tile grid
296918 02/06/2009 218308 4 105 OS Rearrange desks to maintain 3ft clear aisle to exterior door
296926 02/06/2009 218325 4 108 OS Relocate desk blocking exterior door
277382 02/06/2009 176673 5 107 OS Relocate storage and file cabinet blocking clear access to fire extinguisher
296823 02/06/2009 218107 5 108 OS Remove storage from mechanical room
296817 02/06/2009 218094 5 116 OS Relocate chair to maintain clear path to exterior door
296827 02/06/2009 218115 6 105 OS Rearrange tables to maintain 3ft clear aisle to exterior door
277457 02/06/2009 176828 7 103 OS Remove and prohibit extension cord run through ceiling
277399 02/06/2009 176709 7 112 OS Remove storage from electrical room
297030 02/06/2009 218542 8 102 OS Relocate TV cart blocking access to double exit doors
277488 02/06/2009 176892 8 105 OS Prohibit storage of flammable spray paint
297031 02/06/2009 218544 9 109 OS Remove storage from electrical room
277384 03/28/2008 176678 1 119 M Remove partition wall made of wood panelling
277649 03/28/2008 177228 10 102 M Secure loose light fixture
277652 03/28/2008 177234 10 103 M Repair door for electrical panel L8B to close and latch
277647 03/28/2008 177224 10 105 M Provide cover on exposed electrical junction box on underside of roof joist
277640 03/28/2008 177210 10 105C M Remove discharged fire extinguisher
277606 03/28/2008 177138 11 0000 M Replace damaged wheel stop in parking space outside 11-126
277622 03/28/2008 177171 11 104 M Adjust door into 11-102 to latch properly
277607 03/28/2008 177141 11 126 M Adjust door to latch properly
255270 03/28/2008 131591 16 0000 M Remove ADA extended grab handrails from center handrail and interior handrail of stairs 16-001 & 16-006 at intermediate landings and bottom landings
277473 03/28/2008 176862 16 003 M Determine cause of water damaged ceiling tiles and replace tiles outside 16-116
277478 03/28/2008 176873 16 110A M Repair exhaust fan in bathroom
277479 03/28/2008 176875 16 110B M Repair exhaust fan in bathroom
277368 03/28/2008 176643 16 205 M Modify evacuation map to indicate Stair 16-001 as the primary exit & 16-009 as the secondary exit
255593 03/28/2008 132279 16 206 M Modify evacuation map to indicate Stair 16-001 as the primary exit & 16-009 as the secondary exit
256362 03/28/2008 133934 16 216 M Modify evacuation map to indicate Stair 16-006 as the primary exit & 16-009 as the secondary exit
277369 03/28/2008 176645 16 217 M Modify evacuation map to indicate Stair 16-006 as the primary exit & 16-009 as the secondary exit
277597 03/28/2008 177119 17 101 M Replace bulbs in vapor proof light fixtures
277598 03/28/2008 177122 17 101 M Repair door to close and latch properly
277671 03/28/2008 177274 18 101 M Remove or cover open light fixtures in shadehouse building
277673 03/28/2008 177278 18 101 M Replace inoperable 3210 padlock on gate at shadehouse building
277404 03/28/2008 176720 2 106 M Provide sign indicating "Fire Alarm Pull Station Inside"
277405 03/28/2008 176722 2 108 M Replace broken floor tiles at door
277381 03/28/2008 176671 2 113 M Remove unused fire extinguisher from floor
277383 03/28/2008 176676 2 114 M Replace cover on junction box at call button with cover that covers entire junction box
277415 03/28/2008 176742 3 108 M Replace CO2 fire extinguisher with ABC extinguisher
277417 03/28/2008 176746 3 112 M Repair exterior door to open/close and latch properly
277418 03/28/2008 176748 3 115 M Repair hole in wall across from 3-113
277428 03/28/2008 176768 3 125 M Remove unused fire extinguishers
277431 03/28/2008 176774 3 127 M Replace bulbs in vapor proof light fixtures
277432 03/28/2008 176776 3 127 M Replace missing cover over light switch on exterior wall
277448 03/28/2008 176810 4 102 M Adjust exterior door to latch properly
277447 03/28/2008 176808 4 103 M Repair exterior door to open/close and latch properly
277436 03/28/2008 176785 4 112 M Repair broken exit sign - face of sign is missing
277371 03/28/2008 176650 5 101 M Change number on maximum occupancy sign from 70 to 115
277372 03/28/2008 176652 5 117 M Relocate sign indicating maximum occupancy = 9 to be inside room adjacent to door
277374 03/28/2008 176656 5 117 M Repair door into media center to close properly - door sticks in open position
277370 03/28/2008 176648 5 118 M Provide sign indicating "Fire Alarm Pull Station Inside"
277397 03/28/2008 176705 6 104 M Determine cause of water damaged ceiling tiles and replace tiles
277391 03/28/2008 176693 6 108 M Secure loose weatherstripping around window adjacent to exterior door
277400 03/28/2008 176712 6 116 M Replace bulbs in vapor proof light fixtures
277401 03/28/2008 176714 6 116 M Replace missing cover over light switch on exterior wall
277456 03/28/2008 176826 7 102 M Repair cabinet door hanging off its hinges
277612 03/28/2008 177152 8 109 M Replace missing ceiling tiles at slope in ceiling
277636 03/28/2008 177201 8 114 M Determine cause of water on floor of mechanical room and repair
277633 03/28/2008 177194 8 115 M Replace missing inspection log for water heater
277638 03/28/2008 177204 8 118 M Adjust door to open properly - hard to open from inside
277657 03/28/2008 177244 9 102A M Replace missing ceiling tiles
277658 03/28/2008 177246 9 102A M Determine cause of water damaged ceiling tiles and replace tiles
277654 03/28/2008 177238 9 107 M Provide cover on exposed electrical pull box in ceiling
277656 03/28/2008 177242 9 109 M Secure loose bracket for fire extinguisher
277660 03/28/2008 177250 9 123 M Provide correct bracket for fire extinguisher and put extinguisher on bracket
277661 03/28/2008 177252 9 124 M Repair door to close and latch properly
277662 03/28/2008 177254 9 126 M Remove unused fire extinguisher from floor
277663 03/28/2008 177256 9 126 M Secure loose cover on electrical junction box
277651 03/28/2008 177232 10 103 O Remove storage at electrical panel
277645 03/28/2008 177220 10 105 O Remove storage at electrical panels
277646 03/28/2008 177222 10 105 O Provide clear path to electrical panels
277669 03/28/2008 177270 10 108C O Remove and prohibit air freshener spray
277617 03/28/2008 177162 11 116 O Remove storage in front of electrical panels
277482 03/28/2008 176881 16 105 O Remove and prohibit air freshener
277476 03/28/2008 176869 16 116A O Remove and prohibit air freshener
277480 03/28/2008 176877 16 190 O No access was available to this room. Please be prepared to access this room during the report review meeting.
277450 03/28/2008 176814 16 210 O Remove and prohibit paper covering window in door
277527 03/28/2008 176973 16 290 O No access was available to this room. Please be prepared to access this room during the report review meeting.
277402 03/28/2008 176716 2 102 O Remove and prohibit Raid spray
277467 03/28/2008 176849 2 117 O Remove and prohibit paper covering window in door
277469 03/28/2008 176853 2 119 O Remove and prohibit air freshener spray
277409 03/28/2008 176730 3 101 O Remove and prohibit paper covering window in corridor door
277411 03/28/2008 176734 3 104 O Remove and prohibit paint covering window in door
277416 03/28/2008 176744 3 111 O Remove and prohibit paper covering window in door
277420 03/28/2008 176752 3 114 O Remove paper from light fixtures
277423 03/28/2008 176758 3 117 O Remove and prohibit paper covering window in door
277424 03/28/2008 176760 3 117A O Replace bulbs in light fixture
277425 03/28/2008 176762 3 118 O Remove and prohibit air freshener
277445 03/28/2008 176804 4 104 O Remove plant blocking clear access to emergency eye wash
277441 03/28/2008 176795 4 105 O Routinely flush emergency eye wash to keep water running clear
277442 03/28/2008 176797 4 105 O Replace missing fire blanket
277439 03/28/2008 176791 4 107 O Remove excessive amount of cardboard boxes
277435 03/28/2008 176783 4 109A O Remove paper from electrical panel
277377 03/28/2008 176663 5 115 O Prohibit plugging surge protector into surge protector outside 5-114
277378 03/28/2008 176665 5 115 O Remove and prohibit combustible beanbag chairs
277375 03/28/2008 176658 5 116 O Prohibit plugging surge protector into surge protector
277373 03/28/2008 176654 5 117 O Remove excessive storage, flammable backdrops and beanbag chair
277398 03/28/2008 176707 6 104 O Replace missing fire blanket
277394 03/28/2008 176699 6 105 O Replace missing fire blanket
277395 03/28/2008 176701 6 105A O Remove and prohibit air freshener spray
277390 03/28/2008 176691 6 108 O Provide rubber cover strips over electrical cords and prevent cord from hanging from desk and creating tripping hazard
277388 03/28/2008 176687 6 109 O Provide rubber cover strips over electrical cords
277453 03/28/2008 176820 7 101 O Provide rubber cover strips on electrical cords on floor
277452 03/28/2008 176818 7 101A O Remove and prohibit flammable curtain across closet opening
277672 03/28/2008 177276 9 0000 O Prohibit parking on grass area on west side of Bldg. 9
277650 03/28/2008 177230 10 101B C Change swing of door to swing in direction of egress or prohibit room as a classroom
228088 03/28/2008 4200 11 102 C Provide handicapped accessibility to stage
277376 03/28/2008 176660 5 116 C Provide suitable wiring for computer lab to eliminate use of multiple surge protectors
277385 03/28/2008 176681 1 101 F Provide current inspection report in fire alarm log book - latest report dated 2006
277465 03/28/2008 176845 1 126 MS Provide current inspection tag for fire extinguisher
277639 03/28/2008 177207 10 104 MS Provide current inspection tag for fire extinguisher
277644 03/28/2008 177218 10 105 MS Relocate fire extinguisher bracket to be adjacent to exterior door and replace missing extinguisher
277668 03/28/2008 177268 10 108 MS Relocate fire extinguisher to be adjacent to exterior door
277621 03/28/2008 177169 11 103B MS Provide current inspection tag for fire extinguisher
277670 03/28/2008 177272 13 101 MS Replace missing fire extinguisher
277471 03/28/2008 176858 16 171 MS Provide current inspection tag for fire extinguisher
277525 03/28/2008 176967 16 291 MS Provide current inspection tag for fire extinguisher
255575 03/28/2008 132244 16 291 MS Seal openings around ducts and around conduits thru ceiling
277526 03/28/2008 176971 16 291A MS Provide current inspection tag for fire extinguisher
277521 03/28/2008 176960 16 292 MS Adjust fire door to latch properly
277422 03/28/2008 176756 3 114 MS Adjust corridor door to latch properly
277666 03/28/2008 177264 10 107 OS Prohibit running extension cord under door into 10-108
277631 03/28/2008 177190 11 104A OS Keep fixed leaf of double doors at mechanical room closed and latched so operable leaf will close and latch properly
277614 03/28/2008 177155 11 122 OS Prohibit storage of flammable spray paint, baseboard cleaner and gas powered pressure cleaner in caged area
277611 03/28/2008 177150 11 122 OS Prohibit storage of gas can
277609 03/28/2008 177144 11 122 OS Prohibit storage of flammable lighter fluid
277604 03/28/2008 177135 12 103 OS Remove storage from generator room
277481 03/28/2008 176879 16 001 OS Immediately remove desks from bottom of stairwell
277474 03/28/2008 176865 16 116 OS Relocate desk blocking clear path to corridor door
277472 03/28/2008 176860 16 117 OS Prohibit wedging open corridor door
277470 03/28/2008 176855 2 120 OS Remove display board blocking clear access to and visibility of fire alarm pull station
277407 03/28/2008 176726 3 101 OS Relocate computer table blocking clear access to exterior door
277408 03/28/2008 176728 3 101 OS Relocate desk blocking clear path to corridor door and file cabinet within 12" of latch side of door
277410 03/28/2008 176732 3 102 OS Remove posters blocking clear access to emergency escape window
277412 03/28/2008 176736 3 103 OS Arrange desks to provide minimum 3' wide clear path to exterior door
277414 03/28/2008 176740 3 107 OS Remove shelf from cabinet in front of emergency escape window
277419 03/28/2008 176750 3 113 OS Remove table blocking clear path to emergency exit door
277421 03/28/2008 176754 3 114 OS Relocate table blocking clear path to exterior door
277427 03/28/2008 176766 3 125 OS Remove storage from electrical room
277429 03/28/2008 176770 3 126 OS Remove storage from water heater
277446 03/28/2008 176806 4 103 OS Relocate desk blocking clear path to exterior door
277444 03/28/2008 176802 4 104 OS Provide minimum 3' wide clear path to exterior door
277438 03/28/2008 176789 4 107 OS Remove desk and computer blocking clear path to exterior door
277434 03/28/2008 176781 4 109 OS Remove cubby storage unit blocking clear path to exterior door
277393 03/28/2008 176697 6 105 OS Remove desk blocking clear path to exterior door
277392 03/28/2008 176695 6 106 OS Remove desks from corridor
277387 03/28/2008 176685 6 109 OS Relocate computer table blocking clear access to exterior door
277460 03/28/2008 176834 7 104 OS Relocate gardening tools blocking clear path to exterior door
277618 03/28/2008 177164 8 109 OS Remove chair blocking clear path to exterior door
277464 03/28/2008 176843 8 116 OS Remove storage from electrical room
277659 03/28/2008 177248 9 101B OS Prohibit storage of gas can
277655 03/28/2008 177240 9 109 OS Remove storage from electrical room
277466 03/28/2008 176847 1 126 FS Provide heat detector in unoccupied room
255704 11/28/2007 132510 00 0000 M Make manhole cover level with concrete walkway adjacent to flag pole at school entrance
255658 11/28/2007 132416 11 124 M Provide current inspection tag for boiler
255267 11/28/2007 131585 16 006 C Adjust steps to make risers equal
255268 11/28/2007 131587 16 009 C Adjust steps to make risers equal - upper run does not meet allowable tolerances
239410 11/28/2007 98286 00 0000 F Provide certification that fire alarm system has been tested and is fully operational - inspection report was not available for review and panel indicates trouble
228028 11/28/2007 4091 3 102 CS Modify or replace existing emergency escape windows to meet opening requirements
228030 11/28/2007 4092 3 107 CS Modify or replace existing emergency escape windows to meet opening requirements
255238 02/01/2007 131526 P 3562 N/A No violations observed
255219 02/01/2007 131484 P 3567 N/A No violations observed
255220 02/01/2007 131486 P 3568 N/A No violations observed
255239 02/01/2007 131528 P 3572 N/A No violations observed
255221 02/01/2007 131488 P 3574 N/A No violations observed
255222 02/01/2007 131490 P 3575 N/A No violations observed
255628 09/22/2006 132351 00 0000 M Repair light in exit signs adjacent to exit gates between Bldgs. 1 & 8 (x4)
255702 09/22/2006 132506 00 0000 M Modify fire alarm annunciator panel to include new building
255703 09/22/2006 132508 00 0000 M Remove or cap exposed electrial cord and provide K O seal on both junction boxes facing fire alarm annunciator panel at school entrance
255623 09/22/2006 132347 1 125 M Repair light in exit sign
255635 09/22/2006 132370 10 102 M Replace missing grille on exhaust fan in custodial closet
255705 09/22/2006 132512 11 101 M Remove inappropriate occupancy signs (625 occupants)above all exit doors and on exterior wall adjacent to SE exit door
255700 09/22/2006 132501 11 117 M Replace plastic flexible exhaust duct for dryer with a metal duct
255660 09/22/2006 132419 12 103 M Repair or replace broken knob on door
255262 09/22/2006 131571 16 002 M Remove illuminated exit signs above doors into stairwells 16-001 & 16-007 at end of first floor corridor
255266 09/22/2006 131580 16 002 M Remove illuminated exit sign above door into stairwell 16-009 on first floor
255567 09/22/2006 132228 16 115 M Repair leaking fire sprinkler head at center of room
255571 09/22/2006 132237 16 206 M Repair emergency rescue window to open and close easily
255273 09/22/2006 131598 16 215 M Close gap between escutcheon for fire sprinkler head and ceiling above handicapped stall
255274 09/22/2006 131601 16 215 M Close gap between escutcheon for fire sprinkler head and ceiling above handicapped stall
255275 09/22/2006 131603 16 216A M Verify exhaust fan is operational or repair
255276 09/22/2006 131605 16 218A M Verify exhaust fan is operational or repair
255674 09/22/2006 132449 3 116 M Replace safety pin on fire extinguisher
238566 09/22/2006 96750 3 117A M Replace plastic flexible exhaust duct for dryer with a metal duct to eliminate fire hazard
255681 09/22/2006 132461 3 122 M Repair light in exit sign behind gang bathrooms
255686 09/22/2006 132472 4 105 M Replace missing cap on emergency shut off button
255685 09/22/2006 132470 4 109 M Secure loose communications junction box adjacent to exterior door
255676 09/22/2006 132451 4 110 M Replace safety pin on fire extinguisher
255672 09/22/2006 132444 5 110 M Determine cause of water damaged ceiling tiles and replace tiles
255684 09/22/2006 132468 5 118 M Seal window to prohibit leaks
255683 09/22/2006 132466 5 124 M Seal window to prohibit leaks (see media specialist)
255697 09/22/2006 132494 6 104A M Repair electrical outlet (see teacher)
228052 09/22/2006 71029 6 105 M Replace cracked wire glazing in door
255673 09/22/2006 132447 7 104A M Determine cause of water damaged ceiling tiles and replace tiles
255615 09/22/2006 132332 9 102A M Determine cause of water damaged ceiling tiles and replace tiles
255654 09/22/2006 132405 9 104 M Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
255679 09/22/2006 132458 9 108 M Provide current state inspection tag for boiler
255646 09/22/2006 132375 9 114 M Replace broken ceramic tiles under lockers
255613 09/22/2006 132328 9 114A M Determine cause of water damaged ceiling tiles and replace tiles
255648 09/22/2006 132398 9 123 M Provide current state inspection tag for boiler
228110 09/22/2006 34160 P 1373 M Secure and protect insulation on portable unit
228121 09/22/2006 4293 P 3567 M Adjust steps to make risers equal
238525 09/22/2006 96659 P 3567 M Replace missing escutcheon ring for lever on ramp door or patch holes where escutcheon was
228127 09/22/2006 4294 P 3568 M Adjust steps to make risers equal
228134 09/22/2006 4297 P 3574 M Adjust steps to make risers equal
238459 09/22/2006 96519 P 3780 M Adjust steps to make risers equal
228156 09/22/2006 34169 P 4021 M Adjust steps to make risers equal
238500 09/22/2006 96608 P 4023 M Replace damaged handicapped accessible ramp door hardware
238497 09/22/2006 96602 P 4030 M Replace damaged handicapped accessible ramp door hardware
227647 09/22/2006 71030 P 4048 M Replace damaged handicapped accessible ramp door hardware
227666 09/22/2006 71082 P 4415 M Adjust steps to make risers equal
255668 09/22/2006 132434 16 116 O Prohibit use of surge protector to power refrigerator, plug appliances directly into wall outlet
255663 09/22/2006 132424 16 202 O Eliminate 13A extension cord under windows or replace with minimum 15A cord
255692 09/22/2006 132484 2 108 O Remove and prohibit combustible residential couch and chairs
255690 09/22/2006 132480 2 114 O Prohibit plugging one surge protector into another adjacent to computer stations, plug each surge protector directly into wall outlet
255691 09/22/2006 132482 2 120 O Remove and prohibit combustible residential couch
255688 09/22/2006 132476 3 114 O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
255696 09/22/2006 132492 6 101A O Remove and prohibit flammable curtain
255698 09/22/2006 132496 6 104A O Prohibit use of 13A extension cord and multi outlet adaptor - currently both are plugged into a surge protector
255695 09/22/2006 132490 6 109A O Remove and prohibit flammable curtain
255693 09/22/2006 132486 6 109A O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
228101 09/22/2006 4203 00 9500 C Provide covered walkway to portables
228087 09/22/2006 4201 11 102 C Provide engineer's certification for temporary platform stage or remove stage (OK per Bill Brown)
228060 09/22/2006 4183 7 104A C Provide exhaust to exterior for chemical storage room
228109 09/22/2006 4220 P 1373 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228139 09/22/2006 4213 P 3575 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228007 09/22/2006 34055 00 0000 MS Provide keys and cover plate for knox box to allow fire department access
255621 09/22/2006 132343 1 125 MS Provide current inspection tag for fire extinguisher
255701 09/22/2006 132503 11 111 MS Adjust fire door to latch properly
255656 09/22/2006 132413 11 126 MS Provide current inspection tag for fire extinguisher
255271 09/22/2006 131593 16 171 MS Adjust fire door to latch properly
255272 09/22/2006 131596 16 192 MS Provide rated sealant between top of wall and ceiling
255583 09/22/2006 132261 16 292 MS Provide rated sealant between top of wall and ceiling
255678 09/22/2006 132455 3 120 MS Recharge fire extinguisher
255619 09/22/2006 132340 8 114 MS Provide current inspection tag for fire extinguisher
255617 09/22/2006 132335 9 121 MS Close hatch on ceiling
255634 09/22/2006 132364 10 105 OS Relocate storage to maintain a minimum 3 ft clear access to both exit doors
255665 09/22/2006 132430 16 116 OS Remove and prohibit use of toaster oven
255687 09/22/2006 132474 2 101 OS Relocate computer stations to maintain clear aisle to exterior door
255694 09/22/2006 132488 6 109 OS Relocate computer stations to maintain a minimum 3 ft clear aisle to exterior door
255631 09/22/2006 132360 8 109 OS Relocate table blocking access to exit doors adjacent to 8-109C
255651 09/22/2006 132402 9 102B OS Prohibit storage of gas powered pressure cleaner in custodial room
228032 09/22/2006 71012 3 112 CS Provide CO2 fire extinguisher in computer classroom
255259 09/22/2006 131568 0 0 N/A Note: Portables are not in use. They are scheduled for demolition
255218 09/22/2006 131482 P 1373 N/A No violations observed
234654 09/22/2006 91985 P 3777 N/A No violations observed
255240 09/22/2006 131530 P 3779 N/A No violations observed
255223 09/22/2006 131492 P 3780 N/A No violations observed
255224 09/22/2006 131494 P 4021 N/A No violations observed
255225 09/22/2006 131496 P 4023 N/A No violations observed
255242 09/22/2006 131533 P 4027 N/A No violations observed
255243 09/22/2006 131535 P 4028 N/A No violations observed
255244 09/22/2006 131537 P 4029 N/A No violations observed
255226 09/22/2006 131498 P 4030 N/A No violations observed
255245 09/22/2006 131539 P 4032 N/A No violations observed
255227 09/22/2006 131500 P 4048 N/A No violations observed
255246 09/22/2006 131541 P 4050 N/A No violations observed
255228 09/22/2006 131502 P 4415 N/A No violations observed
228011 02/14/2006 4109 00 0000 M Provide verification that all student occupied spaces have emergency lights and all are operable
227685 02/14/2006 34133 11 109 M Repair door coordinator and adjust auto closers to work properly for double doors to serving area
238546 02/14/2006 96710 11 111 M Adjust south door to latch properly
238547 02/14/2006 96712 11 111 M Repair or replace rusted door frame
238563 02/14/2006 96744 3 107 M Secure loose communications junction box to wall adjacent to teacher's desk
228031 02/14/2006 4253 3 108 M Repair damaged wall panel adjacent to corridor door
238567 02/14/2006 96752 3 117 M Adjust exterior door to latch properly
238557 02/14/2006 96732 4 101 M Provide cover for exposed electrical outlet at SE corner
238558 02/14/2006 96734 4 103 M Replace missing ceiling tile/grill on ceiling
228039 02/14/2006 34138 4 103 M Repair damaged wall adjacent to corridor door
238540 02/14/2006 96696 4 104 M Replace missing ceiling tiles
238541 02/14/2006 96698 4 105 M Replace missing ceiling tiles
238543 02/14/2006 96703 4 105 M Adjust water flow for emergency eye wash
228042 02/14/2006 70993 4 105 M Replace missing cap for "Emergency Shut Off" button adjacent to writing board
238542 02/14/2006 96700 4 107 M Replace missing ceiling tiles
238575 02/14/2006 96768 5 114 M Repair exterior door to open and close properly - door sticks
228046 02/14/2006 71072 5 115 M Fill in maximum occupancy sign to indicate actual allowable occupancy
238572 02/14/2006 96762 5 120 M Mount fire extinguisher at maximum five feet above floor
238555 02/14/2006 96728 6 102A M Repair damaged cabinet door
238539 02/14/2006 96694 6 105 M Replace missing ceiling tiles
228054 02/14/2006 71045 6 107 M Remove key lock from corridor door which is a required exit
238549 02/14/2006 96716 7 101 M Replace broken floor tile adjacent to windows
238536 02/14/2006 96688 7 104A M Replace missing ceiling tiles
238551 02/14/2006 96720 7 105 M Replace missing grill on ceiling
238553 02/14/2006 96724 7 107 M Adjust exterior door to latch properly
238537 02/14/2006 96690 7 108 M Replace missing ceiling tiles
238538 02/14/2006 96692 7 109 M Replace missing ceiling tiles
238578 02/14/2006 96774 8 115 M Replace missing grill for exhaust fan
228070 02/14/2006 71075 9 102 M Fill in maximum occupancy sign to indicate actual allowable occupancy
238643 02/14/2006 96916 9 102A M Provide suitable elactrical wiring for vending machine - existing cord was spliced
238642 02/14/2006 96914 9 111 M Replace broken floor tiles
228074 02/14/2006 71076 9 112 M Fill in maximum occupancy sign to indicate actual allowable occupancy
228076 02/14/2006 71077 9 114 M Fill in maximum occupancy sign to indicate actual allowable occupancy
238644 02/14/2006 96918 9 116 M Pad and mark corners of metal angle above ladder which are lower than 6'8"
238476 02/14/2006 96552 P 1373 M Secure loose wall panel adjacent to electrical panel (see teacher)
238447 02/14/2006 96492 P 3562 M Replace missing ceiling tiles
238480 02/14/2006 96561 P 3562 M Adjust ramp door to latch properly
238521 02/14/2006 96651 P 3567 M Repair air conditioner to eliminate leaking condensate water from ceiling tiles
238478 02/14/2006 96557 P 3572 M Adjust ramp door to latch properly
238473 02/14/2006 96546 P 3778 M Replace water damaged floor tiles
238496 02/14/2006 96597 P 3779 M Replace damaged handicapped accessible ramp door hardware
238453 02/14/2006 96507 P 3779 M Determine cause of water damaged ceiling tiles and replace tiles
238469 02/14/2006 96538 P 4023 M Adjust ramp door to latch properly
238470 02/14/2006 96542 P 4023 M Replace water damaged floor tiles
238449 02/14/2006 96497 P 4025 M Replace missing ceiling tiles
238451 02/14/2006 96502 P 4027 M Replace missing ceiling tiles
238460 02/14/2006 96521 P 4027 M Adjust ramp door to latch properly
238454 02/14/2006 96510 P 4028 M Determine cause of water damaged ceiling tiles and replace tiles
238457 02/14/2006 96516 P 4029 M Repair stair door to open and close properly
238511 02/14/2006 96634 P 4030 M Determine cause of water damaged ceiling tiles and replace tiles
238510 02/14/2006 96631 P 4031 M Provide adequate support under ramp posts to prevent bounciness along ramp
238509 02/14/2006 96629 P 4032 M Provide adequate support under ramp posts to prevent bounciness along ramp
238456 02/14/2006 96512 P 4032 M Determine cause of water damaged ceiling tiles and replace tiles
227643 02/14/2006 71026 P 4032 M Replace water damaged floor tiles with turned up edges
238466 02/14/2006 96533 P 4046 M Adjust ramp door to latch properly
238498 02/14/2006 96604 P 4046 M Replace damaged handicapped accessible ramp door hardware
238464 02/14/2006 96529 P 4048 M Adjust ramp door to latch properly
238504 02/14/2006 96619 P 4076 M Secure loose boards on stair landing
238507 02/14/2006 96625 P 4088 M Replace broken floor tiles at center of classroom
238491 02/14/2006 96587 P 4088 M Replace water damaged floor tiles
227665 02/14/2006 71066 P 4415 M Repair roof leak and replace damaged ceiling tiles in boys bathroom
238531 02/14/2006 96675 1 101 O Prohibit plugging one surge protector into another at receptionist's desk
238530 02/14/2006 96670 1 103 O Prohibit plugging one surge protector into another
238544 02/14/2006 96706 10 101 O Prohibit plugging one surge protector into another for computer stations at center
238580 02/14/2006 96779 2 106A O Prohibit use of power strip to power microwave, plug microwave directly into wall outlet
238581 02/14/2006 96781 2 106A O Eliminate and prohibit use of power strip or replace with a surge protector
238561 02/14/2006 96740 3 101 O Prohibit use of surge protector / extension cord to power microwave - plug microwave directly into wall outlet
238564 02/14/2006 96746 3 112 O Prohibit plugging one surge protector into another along west wall and adjacent to teacher's desk
238569 02/14/2006 96756 3 117 O Prohibit plugging one surge protector into another at computer stations
238571 02/14/2006 96760 3 117 O Remove and prohibit combustible residential chairs
238559 02/14/2006 96736 4 104 O Remove paper covering emergency disconnect cabinet door adjacent to writing board
238576 02/14/2006 96770 5 115 O Remove and prohibit combustible bean bag chairs
238556 02/14/2006 96730 6 101A O Prohibit use of surge protector to power microwave, plug microwave directly into wall outlet
238550 02/14/2006 96718 7 104 O Relocate file cabinet blocking access to purge fan button
238552 02/14/2006 96722 7 108 O Prohibit use of extension cord to power refrigerator - Provide a surge protector to power refrigerator or plug appliance directly into wall
238584 02/14/2006 96787 8 101 O Provide cover strip for electrical cords runing across path to secondary exit door and secure cover strip to flooring
238533 02/14/2006 96677 1 101 C Provide additional outlets to eliminate use of multiple surge protectors at receptionist's desk
238583 02/14/2006 96785 2 105 C Provide ventilation to exterior for range along back wall
238570 02/14/2006 96758 3 117 C Provide additional outlets to eliminate use of multiple extension cords
238560 02/14/2006 96738 00 0000 MS Provide current inspection tag for all fire extinguishers
238565 02/14/2006 96748 3 119 MS Remove hold open device from fire door
238574 02/14/2006 96766 5 112 MS Seal void on ceiling around exhust fan grill
238577 02/14/2006 96772 2 117A OS Prohibit storage of flammable spray paint
238562 02/14/2006 96742 3 106 OS Relocate wicker chair to maintain clear path to exterior door
238582 02/14/2006 96783 5 116 OS Relocate TV cart to maintain safe exiting from 5-117 (CCTV secondary exit door)
238573 02/14/2006 96764 5 118 OS Relocate table to provide clear access to fire extinguisher cabinet
238554 02/14/2006 96726 6 108 OS Arrange desks to maintain a minimum 3ft clear aisle to exterior door
238579 02/14/2006 96777 8 109 OS Relocate table blocking clear access to double fire doors
238639 02/14/2006 96908 9 107 OS Prohibit storage of flammable marking paint
238641 02/14/2006 96912 9 108 OS Remove storage from boiler room
238640 02/14/2006 96910 9 124 OS Prohibit storage of flammable marking paint
238462 02/14/2006 96523 P 3779 OS Relocate storage blocking access to stair door
238527 02/14/2006 96667 3 120 FS Secure heat detector to ceiling
238482 02/14/2006 96566 P 3575 FS Secure heat detector to ceiling
238503 02/14/2006 96616 P 3778 FS Secure heat detector to ceiling
227677 09/06/2005 34126 00 9599 M Make manhole cover level with sidewalk adjacent to P-38
228016 09/06/2005 34125 00 9599 M Make manhole covers level with sidewalk between Buildings 4 and 5
228017 09/06/2005 71040 00 9599 M Replace missing covers for two manholes west of P-E10
228018 09/06/2005 71078 00 9599 M Remove electrical conduits which were scattered just west of P-E5
228019 09/06/2005 71090 00 9599 M Repair broken sidewalk between P-E23 & P-E28
228083 09/06/2005 70964 10 101 M Determine cause of water damaged ceiling tiles and replace tiles
227683 09/06/2005 34129 10 102 M Repair exhaust fan in custodial room
228084 09/06/2005 4271 10 108C M Replace broken ceramic tiles in shower
228085 09/06/2005 71071 11 101 M Fill in maximum occupancy sign to indicate actual allowable occupancy
228086 09/06/2005 71048 11 101 M Repair roof leak and replace damaged ceiling tiles
228091 09/06/2005 70965 11 105 M Replace missing ceiling tiles
228092 09/06/2005 70966 11 107 M Determine cause of water damaged ceiling tiles and replace tiles
227684 09/06/2005 4275 11 107 M Repair or replace broken range burners
228093 09/06/2005 71046 11 108A M Anchor toilet to floor
228094 09/06/2005 71047 11 108B M Secure loose faucet to sink
228095 09/06/2005 71079 11 111 M Secure loose guardrail at serving line area
227687 09/06/2005 4276 11 112 M Provide current inspection tag for kitchen steamer
228096 09/06/2005 70967 11 122 M Determine cause of water damaged ceiling tiles and replace tiles in fenced enclosure
227678 09/06/2005 4251 2 105 M Repair ventilation fans for cooking equipment to work properly
228022 09/06/2005 70990 2 105 M Repair electrical outlet behind refrigerator adjacent to teacher's station
228024 09/06/2005 70968 2 108 M Determine cause of water damaged ceiling tiles and replace tiles
228029 09/06/2005 70969 3 103 M Determine cause of water damaged ceiling tiles and replace tiles
228033 09/06/2005 71039 3 113 M Secure loose bottom of partition wall (see teacher)
228034 09/06/2005 70970 3 116 M Determine cause of water damaged ceiling tiles and replace tiles
228035 09/06/2005 70971 3 120 M Determine cause of water damaged ceiling tiles and replace tiles
228036 09/06/2005 71089 3 124A M Repair noisy exhaust fan in bathroom
228040 09/06/2005 70972 4 104 M Determine cause of water damaged ceiling tiles and replace tiles at SE corner
228041 09/06/2005 70994 4 104 M Repair or replace broken nozzle for emergency eye wash
228045 09/06/2005 70973 5 111 M Determine cause of water damaged ceiling tiles and replace tiles
228049 09/06/2005 71044 5 119 M Remove hasp from door to electrical room
228050 09/06/2005 70991 6 101 M Secure loose communication outlet boxes to electrical poles and secure bottom of electrical poles to floor
228051 09/06/2005 70974 6 104 M Determine cause of water damaged ceiling tiles and replace tiles
228053 09/06/2005 70975 6 105A M Determine cause of water damaged ceiling tiles and replace tiles
228055 09/06/2005 70976 6 108 M Determine cause of water damaged ceiling tiles and replace tiles
228057 09/06/2005 70977 7 103 M Determine cause of water damaged ceiling tiles and replace tiles
228058 09/06/2005 71034 7 104 M Secure loose weather strip for exterior door
227681 09/06/2005 34064 7 106 M Repair light in exit signs in corridor adjacent to 7-103 and 7-107
228063 09/06/2005 71073 8 102 M Fill in maximum occupancy sign to indicate actual allowable occupancy
228065 09/06/2005 71074 8 109 M Fill in maximum occupancy sign to indicate actual allowable occupancy
228067 09/06/2005 34143 8 115 M Repair cracked plaster finish on ceiling
227682 09/06/2005 4265 8 115 M Repair ventilation fan
228068 09/06/2005 71010 8 116 M Mount fire extinguisher at maximum five feet above floor
228075 09/06/2005 71018 9 112 M Repair damaged fire extinguisher cabinet at NE corner
228077 09/06/2005 71091 9 114 M Replace broken ceramic tile adjacent to lockers
228078 09/06/2005 71087 9 117 M Secure loose threshold
228081 09/06/2005 71035 9 123 M Repair damaged lock on door - was not able to lock door
228108 09/06/2005 71068 P 1373 M Replace missing awning above stair door which was damaged during hurricane
228113 09/06/2005 71000 P 1452 M Repair emergency lighting
228114 09/06/2005 71037 P 1452 M Repair auto closer on door
228115 09/06/2005 71043 P 1452 M Trim or remove vegetation covering ramp
228116 09/06/2005 71064 P 3562 M Repair roof leak and replace damaged ceiling tiles
228119 09/06/2005 4287 P 3562 M Repair air conditioner to eliminate leaking condensate water from ceiling vents
227691 09/06/2005 4288 P 3562 M Repair or replace deteriorated wood siding adjacent to ramp door
228122 09/06/2005 70995 P 3567 M Repair emergency lighting adjacent to stair door
228123 09/06/2005 71050 P 3567 M Repair roof leak and replace damaged ceiling tiles
228128 09/06/2005 71051 P 3568 M Repair roof leak and replace damaged ceiling tiles
228130 09/06/2005 71065 P 3572 M Repair roof leak and replace damaged ceiling tiles
228131 09/06/2005 71088 P 3572 M Replace missing threshold at ramp door
228135 09/06/2005 70996 P 3574 M Repair emergency lighting adjacent to stair door
228136 09/06/2005 71052 P 3574 M Repair roof leak and replace damaged ceiling tiles
228140 09/06/2005 4290 P 3575 M Adjust steps to make risers equal
227692 09/06/2005 34171 P 3575 M Repair or replace deteriorated wood siding adjacent to ramp door
227694 09/06/2005 34155 P 3777 M Replace moisture damaged floor tiles with curved edges
228143 09/06/2005 71057 P 3777 M Repair roof leak and replace damaged ceiling tiles
228145 09/06/2005 70997 P 3778 M Repair emergency lighting adjacent to ramp door
228146 09/06/2005 71054 P 3778 M Repair roof leak and replace damaged ceiling tiles
228147 09/06/2005 71080 P 3778 M Secure loose stair guardrail
228153 09/06/2005 71081 P 3780 M Replace missing graspable handrail for stairs
228154 09/06/2005 71093 P 3780 M Repair or replace deteriorated wood siding adjacent to ramp door
228157 09/06/2005 71058 P 4021 M Repair roof leak and replace damaged ceiling tiles
228158 09/06/2005 71094 P 4021 M Repair or replace deteriorated wood siding adjacent to ramp door
228160 09/06/2005 71055 P 4023 M Repair roof leak and replace damaged ceiling tiles
228163 09/06/2005 71032 P 4025 M Adjust ramp door to latch properly
228164 09/06/2005 71036 P 4025 M Repair or replace bent latch guard on ramp door
228165 09/06/2005 71041 P 4025 M Provide cover on exposed electrical junction box
228166 09/06/2005 71049 P 4025 M Repair roof leak and replace damaged ceiling tiles
228167 09/06/2005 71059 P 4027 M Repair roof leak and replace damaged ceiling tiles
228168 09/06/2005 71095 P 4027 M Repair or replace deteriorated wood siding adjacent to ramp door
227633 09/06/2005 34108 P 4028 M Remove mold and provide non-slip surface for stairs
227635 09/06/2005 70979 P 4029 M Determine cause of mold on ceiling and repair
227636 09/06/2005 71042 P 4029 M Trim over grown vegetation on west side of portable to maintain a minimum 6 ft clear path from portable stairs
227637 09/06/2005 71060 P 4030 M Repair roof leak and replace damaged ceiling tiles
227640 09/06/2005 71062 P 4031 M Repair roof leak and replace damaged ceiling tiles
227644 09/06/2005 71063 P 4032 M Repair roof leak and replace damaged ceiling tiles
227690 09/06/2005 34164 P 4032 M Repair damaged vertical support under ramp
227648 09/06/2005 70998 P 4048 M Repair emergency lighting adjacent to ramp door
227649 09/06/2005 71025 P 4048 M Repair missing floor tiles
227650 09/06/2005 71061 P 4048 M Repair roof leak and replace damaged ceiling tiles
227651 09/06/2005 71069 P 4048 M Replace damaged soffit above ramp door
227653 09/06/2005 71056 P 4050 M Repair roof leak and replace damaged ceiling tiles
227654 09/06/2005 34168 P 4050 M Adjust steps to make risers equal
227655 09/06/2005 70978 P 4061 M Determine cause of water damaged ceiling tiles and replace tiles
227656 09/06/2005 71013 P 4061 M Replace safety pin on fire extinguisher
227657 09/06/2005 4310 P 4061 M Adjust steps to make risers equal
227702 09/06/2005 34157 P 4075 M Replace broken floor tiles
227689 09/06/2005 34156 P 4076 M Replace missing floor tiles adjacent to door
227661 09/06/2005 71024 P 4088 M Repair water damaged floor tiles
227662 09/06/2005 71053 P 4088 M Repair roof leak and replace damaged ceiling tiles
227663 09/06/2005 70999 P 4415 M Replace missing test button for emergency lighting in boys bathroom
227664 09/06/2005 71027 P 4415 M Repair or replace sub flooring which is causing a soft spot adjacent to teacher's lounge exit door
227695 09/06/2005 4323 P 504 M Replace damaged flooring in bathroom
228107 09/06/2005 4322 P 504 M Adjust steps to make risers equal
228103 09/06/2005 71033 P 504 M Adjust ramp door to latch properly
228104 09/06/2005 71067 P 504 M Repair roof leak and replace damaged ceiling tiles
228105 09/06/2005 71092 P 504 M Repair deteriorated wall finish adjacent to ramp door
228097 09/06/2005 71001 11 122 O Prohibit use of extension cord or surge protector to power appliances
228023 09/06/2005 71007 2 106A O Eliminate or replace surge protector which has exposed wiring
228025 09/06/2005 71028 2 108 O Remove and prohibit combustible residential couch
228027 09/06/2005 34081 2 120 O Remove and prohibit combustible residential couch
228047 09/06/2005 71002 5 116 O Prohibit plugging one surge protector into another
228048 09/06/2005 71003 5 117 O Eliminate use of extension cord with multiple outlets
228056 09/06/2005 71008 7 101 O Eliminate extension cord or replace with minimum 15A cord
228059 09/06/2005 70992 7 104 O Remove paper covering purge fan switch
228061 09/06/2005 71009 7 109 O Eliminate extension cord or replace with minimum 15A cord
228124 09/06/2005 70980 P 3567 O Remove and prohibit flammable fabric covering window in doors
228125 09/06/2005 71021 P 3567 O Remove flammable silk tree from classroom
228129 09/06/2005 71022 P 3568 O Remove flammable silk tree from classroom
228137 09/06/2005 70981 P 3574 O Remove and prohibit flammable curtains and window coverings
228141 09/06/2005 70963 P 3575 O Provide verification that written permission from principal has been provided to keep snake in the classroom and that all required safety precautions are being followed
228142 09/06/2005 71004 P 3575 O Prohibit plugging one surge protector into another adjacent to teacher's desk
228150 09/06/2005 70989 P 3779 O Relocate file cabinet to provide clear access to electrical panel
227641 09/06/2005 70982 P 4031 O Remove and prohibit paper covering window in ramp door
227667 09/06/2005 71005 P 4415 O Prohibit plugging one surge protector into another in teacher's lounge
227669 09/06/2005 34174 00 9599 C Provide engineers evaluation of rusted beam at covered walkway at school entrance (SW corner of Bldg. 1) and repair according to engineer's recommendation
228012 09/06/2005 34102 00 9599 C Provide engineers evaluation of cracked concrete column at covered walkway at school entrance (SW corner of Bldg. 1) and repair according to engineer's recommendation
227674 09/06/2005 4198 10 101 C Provide sign indicating maximum occupancy adjacent to main entrance
228082 09/06/2005 71070 10 101 C Fill in maximum occupancy sign to indicate actual allowable occupancy
227675 09/06/2005 4199 11 101 C Provide sign indicating maximum occupancy adjacent to main entrance
227670 09/06/2005 4093 3 113 C Provide secondary egress for classroom or limit student occupancy to 9 students
227671 09/06/2005 4181 7 104 C If room is used as chemistry lab, provide emergency exhaust system
227672 09/06/2005 4189 8 102 C Provide sign indicating maximum occupancy adjacent to main entrance
227673 09/06/2005 4190 8 109 C Provide sign indicating maximum occupancy adjacent to main entrance
227698 09/06/2005 4241 P 1252 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227700 09/06/2005 34110 P 1417 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227699 09/06/2005 34109 P 1432 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228111 09/06/2005 4245 P 1452 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228112 09/06/2005 4244 P 1452 C Provide handrails along stair at 34-38 inches high with continuous graspable surface
228118 09/06/2005 4211 P 3562 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228120 09/06/2005 4215 P 3567 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228126 09/06/2005 4216 P 3568 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228132 09/06/2005 4212 P 3572 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228133 09/06/2005 4217 P 3574 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228144 09/06/2005 4224 P 3777 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228148 09/06/2005 4221 P 3778 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228151 09/06/2005 4231 P 3779 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228152 09/06/2005 4225 P 3780 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228155 09/06/2005 4226 P 4021 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228159 09/06/2005 4222 P 4023 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228162 09/06/2005 4214 P 4025 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228169 09/06/2005 4232 P 4027 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227632 09/06/2005 4237 P 4028 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227634 09/06/2005 4239 P 4029 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227638 09/06/2005 4233 P 4030 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227639 09/06/2005 4208 P 4031 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227642 09/06/2005 4210 P 4032 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227645 09/06/2005 4227 P 4046 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227646 09/06/2005 4236 P 4048 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227652 09/06/2005 4223 P 4050 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227658 09/06/2005 4229 P 4061 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227701 09/06/2005 4206 P 4075 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227659 09/06/2005 4205 P 4076 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements (Title Office)
227660 09/06/2005 4218 P 4088 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
227668 09/06/2005 4247 P 4415 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228106 09/06/2005 4242 P 504 C Provide engineered foundation and anchoring system for portable and modify existing foundations and anchorage to comply with engineering requirements
228102 09/06/2005 71031 P 504 C Replace damaged handicapped accessible ramp door hardware
228044 09/06/2005 71038 5 108 F Verify or provide heat detector in mechanical room - detector was not visible
227676 09/06/2005 4102 7 111 F Provide fire alarm strobe light in corridor between Buildings 6 and 7
228021 09/06/2005 71014 1 126 MS Relocate fire extinguisher to be adjacent to exit door
228090 09/06/2005 71019 11 104 MS Close hatch on ceiling
227686 09/06/2005 4117 11 112 MS Provide current inspection tag for fire (hood) suppression system
227688 09/06/2005 34068 12 103 MS Provide current inspection tag for fire extinguisher
227679 09/06/2005 34061 2 109 MS Provide current inspection tag for fire extinguisher adjacent to bathroom
227680 09/06/2005 34062 2 113 MS Provide current inspection tag for fire extinguisher adjacent to bathroom
228062 09/06/2005 70983 7 110 MS Adjust fire doors at end of corridor to latch properly
228069 09/06/2005 71015 8 116 MS Provide current inspection tag for fire extinguisher
228072 09/06/2005 71016 9 108 MS Provide current inspection tag for fire extinguisher
228079 09/06/2005 71017 9 121A MS Provide current inspection tag for fire extinguisher
227693 09/06/2005 34070 P 4088 MS Recharge fire extinguisher
227696 09/06/2005 34078 P 504 MS Recharge fire extinguisher
228098 09/06/2005 71023 11 122 OS Prohibit storage of gasoline and gas powered pressure cleaner
228099 09/06/2005 71083 11 127 OS Remove storage from electrical room
228026 09/06/2005 71006 2 116 OS Prohibit running electrical cord across path to back door
228037 09/06/2005 71084 3 125 OS Remove ladders stored in electrical room
228043 09/06/2005 71011 4 105 OS Relocate teacher's desk to provide clear access to fire extinguisher
228066 09/06/2005 70984 8 109 OS Relocate table blocking access to double doors
228071 09/06/2005 71020 9 107 OS Prohibit storage of flammable paint
228073 09/06/2005 71086 9 108 OS Remove storage from boiler room
228080 09/06/2005 71085 9 121A OS Remove storage from electrical room
228117 09/06/2005 70988 P 3562 OS Rearrange furniture to provide a clear path of travel to stair door
228138 09/06/2005 70985 P 3574 OS Relocate desk blocking clear access to stair door
228149 09/06/2005 70987 P 3779 OS Rearrange tables to provide a clear path of travel to stair door
228161 09/06/2005 70986 P 4023 OS Rearrange tables and chairs to provide a clear path of travel to stair door
228014 09/06/2005 4090 00 9599 CS Modify gates beside P-E2 to allow egress at all times
228010 09/06/2005 34056 00 0000 FS Provide certification that fire alarm system has been tested and is fully operational (Report was not available)
228020 09/06/2005 4096 1 104A FS Provide heat detector in closet
228100 09/06/2005 4108 13 0000 FS Provide heat detector in normally unoccupied space
228064 09/06/2005 4103 8 104 FS Provide heat detector in storage room
227697 09/06/2005 34058 P 4076 FS Provide heat detector in room used for storage
234659 09/06/2005 91990 P 3778 N/A No violations observed
234650 09/06/2005 91981 P 3779 N/A No violations observed
234657 09/06/2005 91988 P 4023 N/A No violations observed
234652 09/06/2005 91983 P 4025 N/A No violations observed
234656 09/06/2005 91987 P 4030 N/A No violations observed
234651 09/06/2005 91982 P 4031 N/A No violations observed
234655 09/06/2005 91986 P 4046 N/A No violations observed
234653 09/06/2005 91984 P 4076 N/A No violations observed
234658 09/06/2005 91989 P 4088 N/A No violations observed