Citation ID Inspection date Citation Num. BLDG Room Corr. By Deficiency Description
413270 03/09/2018 471755 1 002 M Adjust door closer on fire doors at 2-001 corridor to control speed of closing doors, too fast
413354 03/09/2018 471927 1 114 M Adjust door closer to control speed of closing door, too fast
413194 03/09/2018 471586 1 118 M Determine cause of water damaged ceiling tiles and replace tiles
413268 03/09/2018 471750 1 118 M Adjust exterior door to latch properly
413269 03/09/2018 471753 1 118 M Repair damaged, bent trim piece on exterior door frame
413349 03/09/2018 471919 1 119A M Determine cause of water damaged ceiling tiles and replace tiles
413343 03/09/2018 471906 1 120 M Determine cause of water damaged ceiling tiles and replace tiles, replace missing tiles
413345 03/09/2018 471909 1 124B M Repair deteriorated wall finish adjacent to urinal and sink
413348 03/09/2018 471916 1 184 M Repair deteriorated wall finish
413346 03/09/2018 471913 1 185 M Repair deteriorated wall finish
413281 03/09/2018 471778 1 199 M Repair hole in east wall
413193 03/09/2018 471583 2 0000 M Repair exhaust fans in all 2nd floor bathrooms except 2-219A, 2-226A, 2-228A, 2-230A
413324 03/09/2018 471866 2 004 M Repair latch for exterior doors at 2-113
413272 03/09/2018 471759 2 006 M Determine cause of water damaged ceiling tiles adjacent to exterior door and replace tiles
413273 03/09/2018 471761 2 007 M Replace missing ceiling tiles adjacent to windows
413328 03/09/2018 471875 2 008 M Determine cause of water damaged ceiling tiles and replace tiles
413274 03/09/2018 471763 2 009 M Repair damaged, peeling wall finish at lower run of stairs
413339 03/09/2018 471896 2 101 M Determine cause of water damaged ceiling tiles and replace tiles
413337 03/09/2018 471893 2 102 M Determine cause of water damaged ceiling tiles and replace tiles
413334 03/09/2018 471888 2 103 M Adjust door closer on exterior door to control speed of closing door
413335 03/09/2018 471891 2 104B M Determine cause of water damaged ceiling tiles and replace tiles
413332 03/09/2018 471883 2 107 M Adjust door closer on exterior door to control speed of closing door
413333 03/09/2018 471886 2 108 M Determine cause of water damaged ceiling tiles and replace tiles
413293 03/09/2018 471804 2 120 M Adjust fire sprinkler head so deflector projects a minimum 1 inch below escutcheon
413295 03/09/2018 471807 2 120 M Determine cause of water damaged ceiling tiles and replace tiles
413279 03/09/2018 471774 2 130 M Determine cause of water damaged ceiling tiles and replace tiles
413297 03/09/2018 471810 2 181 M Repair hole wall adjacent to baseboard
413276 03/09/2018 471767 2 230A M Secure sink to wall
413330 03/09/2018 471879 3 101 M Replace missing belt guard on ventilation fan
393906 03/09/2018 429975 3 102 M Replace missing belt guard on ventilation fan
413291 03/09/2018 471800 P 6324 M Determine cause of water damaged ceiling tiles and replace tiles
413352 03/09/2018 471921 1 119A O Prohibit running damaged extension cord under door into 1-119. Prohibit use of damaged extension cord
413341 03/09/2018 471901 2 101 O Prohibit brown 13A extension cord at microscope or replace with minimum 15A single outlet extension cord
413286 03/09/2018 471789 P 6232 O Prohibit brown 13A extension cord at cream colored lamp or replace with minimum 15A single outlet extension cord
393918 03/09/2018 429999 P 0000 C Modify or improve drainage at portables. Drainage from P-1, P-2 and P-3 runs under units. Drainage from P-5 thru P-8 runs onto paved play courts
413275 03/09/2018 471765 2 021 MS Recharge fire extinguisher in corridor adjacent to 2-229
413280 03/09/2018 471776 1 199 OS Remove storage from mechanical room
413326 03/09/2018 471870 2 002 OS Relocate benches and statute in corridor to maintain clear aisle to exit
413289 03/09/2018 471792 P 6232 OS Relocate desk to maintain clear aisle to east exit door
274789 03/09/2018 171093 P 6323 N/A No violations observed
274787 03/09/2018 171088 P 6324 N/A No violations observed
393946 10/27/2017 430061 1 118 M Eliminate termites and repair termite damage
394041 10/27/2017 430264 2 195 M Repair outside air intake fan motor and re-install belt guard
274810 10/27/2017 171135 1 0000 N/A No violations observed
274812 10/27/2017 171138 2 0000 N/A No violations observed
274813 10/27/2017 171141 3 0000 N/A No violations observed
393923 10/26/2017 430010 00 0000 M Trim exposed tree roots in play fields and at walking track. See Coach Beine
413271 10/26/2017 471757 00 0000 M Make repairs as noted on fire sprinkler inspection report
413284 10/26/2017 471784 1 116A M Modify lockset so it cannot be locked from inside room
413285 10/26/2017 471787 1 116B M Modify lockset so it cannot be locked from inside room
394043 10/26/2017 430268 2 195 M Repair badly rusted door frame and re-install closer arm to frame
274802 10/26/2017 171117 P 6078 N/A No violations observed
274805 10/26/2017 171124 P 6079 N/A No violations observed
274788 10/26/2017 171090 P 6080 N/A No violations observed
274795 10/26/2017 171105 P 6232 N/A No violations observed
274792 10/26/2017 171099 P 6321 N/A No violations observed
274791 10/26/2017 171097 P 6322 N/A No violations observed
393910 04/18/2017 429983 00 0000 M Fill low spots at sidewalks in play fields and play pavilion. See Coach Beine
394044 04/18/2017 430270 2 0000 M Repair exhaust fans in all bathrooms on 2nd floor
393957 04/18/2017 430087 2 101C M Repair exhaust fan in bathroom
393956 04/18/2017 430084 2 103A M Repair exhaust fan in bathroom
393948 03/07/2017 430065 00 0000 M Repair or replace drinking fountain in covered pavilion
393909 03/07/2017 429981 00 0000 M Eliminate ants in play fields. See Coach Beine
394037 03/07/2017 430251 00 0000 M Repair broken concrete walk to 2-194
394011 03/07/2017 430194 00 0000 M Repair roof leak in covered pavilion at south roof drain scupper
393954 03/07/2017 430080 1 0000 M Eliminate ants in office area
394032 03/07/2017 430240 1 004 M Determine cause of water damaged ceiling tiles and replace tiles in corridor at door to interior courtyard
394024 03/07/2017 430224 1 120 M Adjust SE door from Cafeteria to exterior to latch properly
394027 03/07/2017 430230 1 122E M Provide protective cage around fire sprinkler head in walk-in cooler
394028 03/07/2017 430234 1 122F M Provide protective cage around fire sprinkler head in walk-in freezer
393930 03/07/2017 430025 1 123B M Secure sink to wall
393939 03/07/2017 430043 1 124A M Refinish wall at bathroom sinks to provide impervious wall finish
393940 03/07/2017 430046 1 124A M Caulk sinks to wall in bathroom
393942 03/07/2017 430049 1 124A M Caulk toilets to wall
394021 03/07/2017 430219 1 125D M Repair leaking toilet supply line
394038 03/07/2017 430258 1 180 M Replace missing ceiling tiles
394019 03/07/2017 430215 1 182 M Replace missing ceiling tiles at water heater
394017 03/07/2017 430208 2 009 M Seal wall in stair enclosure to prevent leaks and repair damaged wall finish
393958 03/07/2017 430089 2 104A M Caulk sink to wall
393962 03/07/2017 430097 2 114 M Repair leaking toilet supply line
393907 03/07/2017 429977 2 115 M Determine cause of water damaged ceiling tiles and replace tiles at projection screen
394002 03/07/2017 430179 2 119A M Repair exhaust fan in bathroom
394004 03/07/2017 430181 2 119A M Repair wall at bathroom sink to provide impervious wall finish
393944 03/07/2017 430057 2 122 M Secure projector screen bracket to wall
394039 03/07/2017 430260 2 123 M Determine cause of water damaged ceiling tiles and replace tiles
393961 03/07/2017 430095 2 123B M Repair leaking toilet supply line
393908 03/07/2017 429979 2 125 M Secure loose faucet
393960 03/07/2017 430093 2 126A M Repair leaking toilet supply line
394006 03/07/2017 430185 2 180 M Determine cause of water damaged ceiling tiles and replace tiles
394042 03/07/2017 430266 2 195 M Replace missing screws for electrical panel 2M1
394053 03/07/2017 430288 2 205C M Caulk sink to wall
394052 03/07/2017 430286 2 207A M Replace damaged light switch
394048 03/07/2017 430278 2 210 M Repair drinking fountain. Runs too long
394055 03/07/2017 430294 2 213A M Repair leaking toilet supply line
394045 03/07/2017 430272 2 215A M Repair leaking toilet supply line
394047 03/07/2017 430276 2 215A M Repair plumbing to sink. Low water pressure
393945 03/07/2017 430059 2 226 M Repair or replace drinking fountain
393959 03/07/2017 430091 2 230A M Repair leaking toilet supply line
393955 03/07/2017 430082 P 0000 M Provide chain and lock on gate of fencing around electric equipment between P-3 and P-4
393911 03/07/2017 429985 P 6078 M Finish wall patches in bathroom to provide impervious wall finish
393913 03/07/2017 429989 P 6078 M Exterior junction boxes are partially buried. Remove dirt from beneath boxes so they no longer contact ground
393915 03/07/2017 429993 P 6079 M Repair emergency lighting at rear door
393922 03/07/2017 430007 P 6080 M Caulk sink to wall in bathroom
393926 03/07/2017 430014 P 6323 M Repair air conditioning system. Not cooling
393928 03/07/2017 430019 P 6324 M Determine cause of water damaged ceiling tiles and replace tiles
394054 03/07/2017 430291 2 294 O Re-install floor drain grate
394040 03/07/2017 430262 1 191 MS Provide current inspection tag for fire extinguisher or remove un-needed extinguisher
393947 03/07/2017 430063 1 199 MS Provide current inspection tag for fire extinguisher or remove un-needed extinguisher
394051 03/07/2017 430284 2 019 MS Adjust fire door in 2nd floor corridor to stairs at 2-212 to latch properly
394050 03/07/2017 430282 2 021 MS Adjust fire door in 2nd floor corridor at 2-218 to latch properly
394030 03/07/2017 430237 2 005 OS Prohibit hold open device on fire door in corridor by elevator
394049 03/07/2017 430280 2 017 OS Prohibit hold open devices on fire doors from corridor to stairs
393914 03/07/2017 429991 P 6079 OS Maintain 3 foot clear aisle to rear exit
378647 01/14/2016 396999 1 0000 M Replace missing lens cover on light fixture in covered walkway going to the portables from the cafeteria
378621 01/14/2016 396943 1 004 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report
378622 01/14/2016 396945 1 004 M Determine cause of water damaged ceiling tiles and replace tiles
378641 01/14/2016 396987 1 118 M Determine cause of water damaged ceiling tiles in media center and replace tiles
378640 01/14/2016 396985 1 118G M Repair emergency lighting in A/V storage room
378646 01/14/2016 396997 1 120 M Determine cause of water damaged ceiling tiles in Cafeteria adjacent to 1-120A and replace tiles
378645 01/14/2016 396995 1 122 M Clean kitchen hood (date listed on tag shows last cleaning was performed on 5-8-14)
378644 01/14/2016 396993 1 123C M Secure loose toilet seat in staff restroom
378642 01/14/2016 396989 1 196 M Provide current emergency lighting and generator certificate (current date on certificate is 6-30-14)
378643 01/14/2016 396991 1 198 M Repair emergency lighting in main electric room
378631 01/14/2016 396965 2 003 M Repair smoke doors in corridor adjacent to 2-117 to close properly
378625 01/14/2016 396952 2 006 M Determine cause of water damaged ceiling tiles at exit doors at bottom of stairway and replace tiles
378626 01/14/2016 396955 2 006 M Make necessary repairs to fire sprinkler system as indicated on annual inspection report
378629 01/14/2016 396961 2 008 M Determine cause of water damaged ceiling tiles and replace tiles
378628 01/14/2016 396959 2 109 M Determine cause of water damaged ceiling tiles and replace tiles
378630 01/14/2016 396963 2 111 M Determine cause of water damaged ceiling tiles adjacent to exterior exit door and replace tiles
378632 01/14/2016 396967 2 120 M Replace missing escutcheon on fire sprinkler head
378633 01/14/2016 396970 2 182 M Replace broken lens in light fixture
378639 01/14/2016 396983 2 217 M Replace missing escutcheon on fire sprinkler head
378637 01/14/2016 396978 2 224 M Replace missing escutcheon on fire sprinkler head
378636 01/14/2016 396976 2 227 M Secure drinking fountain to sink
378638 01/14/2016 396981 2 294 M Repair air handling unit to prevent condensation water from covering floor (water is coming from beneath unit, unable to tell where the leak is)
378649 01/14/2016 397003 P 6078 M Repair rear door of portable door to close properly
378648 01/14/2016 397001 P 6080 M Repair rear door of portable to close properly
378650 01/14/2016 397005 P 6324 M Determine cause of water damaged ceiling tiles and replace tiles
378620 01/14/2016 396941 00 0000 O Provide name of Lead Crowd Manager who successfully completed the Crowd Management course as indicated in Bulletin # P-14808
378627 01/14/2016 396957 2 102 O Prohibit plugging surge protector into surge protector at computers at half wall
378634 01/14/2016 396972 2 228 O Prohibit plugging surge protector into surge protector at teachers desk
378624 01/14/2016 396950 1 116 MS Recharge fire extinguisher
378635 01/14/2016 396974 2 021 MS Recharge fire extinguisher in second floor corridor adjacent to 2-225
378623 01/14/2016 396948 1 190 OS Remove storage from electrical room (desks)
332936 12/12/2014 297378 00 0000 M Replace missing elbow at bottom of downspout on Pavilion (x2)
367732 12/12/2014 373251 00 9599 M Provide chain and padlock for fire department water main OS&Y valves located south of media center
367729 12/12/2014 373244 00 9599 M Install cap on fire department standpipe connection adjacent to OS&Y water main
367722 12/12/2014 373228 1 004 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to exterior doors
367702 12/12/2014 373185 1 106 M Determine cause of water damaged ceiling tiles and replace tiles
367731 12/12/2014 373249 1 118D M Relocate signage indicating room name and number to 5 ft above floor - current location is too high
367703 12/12/2014 373187 1 191 M Secure loose wall bracket for fire extinguisher
367712 12/12/2014 373207 2 006 M Determine cause of water damaged ceiling tiles and replace tiles adjacent to exterior doors
367713 12/12/2014 373209 2 110 M Adjust water flow for drinking spout
367725 12/12/2014 373235 2 117B M Replace missing ceiling tiles
367716 12/12/2014 373216 2 130 M Determine cause of water damaged ceiling tiles and replace tiles
367704 12/12/2014 373189 2 170 M Provide current inspection tag for elevator
367717 12/12/2014 373218 P 6321 M Adjust water flow for drinking spout
367730 12/12/2014 373246 1 118G O Remove paper covering room name and number with Braille characters
367723 12/12/2014 373230 2 105B O Remove glass mirror behind sink or provide mirror made of tempered glass, safety glass, or stainless steel
367724 12/12/2014 373232 2 107 O Remove and prohibit use of umbrella in classroom - interferes with fire sprinkler system coverage
367714 12/12/2014 373211 2 110 O Prohibit plugging surge protector into surge protector at teacher desk - plug each surge protector directly into wall outlet
367726 12/12/2014 373237 2 121 O Remove and prohibit paper covering electrical outlets adjacent to bathroom
367715 12/12/2014 373214 2 124 O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
367727 12/12/2014 373240 2 129 O Remove and prohibit paper covering electrical outlets on back wall
367710 12/12/2014 373203 2 201A O Eliminate orange extension cord with multi plug outlet adaptor in storage room
367708 12/12/2014 373199 2 213A O Remove box of floor adjacent to bathroom door to eliminate trip hazard - you may relocate to shower area which is not in use
367707 12/12/2014 373195 2 223 O Remove and prohibit plug-in air freshener adjacent to corridor door
367706 12/12/2014 373193 2 225 O Remove mirror or provide mirror made of tempered glass, safety glass, or stainless steel adjacent to sink
367705 12/12/2014 373191 2 226 O Remove and prohibit excessive flammable blue vinyl sheet covering table adjacent to computer stations
367718 12/12/2014 373220 P 6078 O Prohibit plugging surge protector into surge protector under computer stations - plug each surge protector directly into wall outlet
332938 12/12/2014 297383 P 0000 C Modify or improve storm drainage from rear of portables to take rain water away from units (P-5 to P-8)
367728 12/12/2014 373242 1 119 OS Relocate tables to maintain clear path to single exit door adjacent to writing board
367711 12/12/2014 373205 2 201B OS Remove recycling bins from vestibule to maintain clear path to both bathrooms
367709 12/12/2014 373201 2 203 OS Remove and prohibit use of toaster
367719 12/12/2014 373222 P 6079 OS Rearrange furniture to maintain 3 ft clear aisle to both exit doors or reduce furniture as needed to maintain safe egress
367720 12/12/2014 373224 P 6080 OS Relocate furniture to maintain clear path to back exit door
367721 12/12/2014 373226 P 6080 OS Remove shelf unit from bathroom
353444 01/22/2014 342093 00 9599 M Repair leaking OS & Y water main adjacent to 1-193
332930 01/22/2014 297365 1 0000 M Complete work on fire main adjacent to 1-193 (electrical wiring)
317088 01/22/2014 262411 1 118G M Verify or provide current inspection tag for fire sprinkler system (Sprinkler piping is located above the ceiling tile inside classroom and tag was not visible)
353440 01/22/2014 342086 1 122 M Provide current inspection tag for kitchen hood fire suppression system (tag reads 9/2012)
353445 01/22/2014 342096 2 006 M Repair or replace rusted exterior side of door at bottom of stairwell into interior courtyard
353420 01/22/2014 342043 2 170 M Provide current inspection tag for elevator
353425 01/22/2014 342055 2 228 M Secure loose drinking spout to sink
353437 01/22/2014 342079 P 6322 M Secure loose faucet to sink
353436 01/22/2014 342077 P 6323 M Adjust water flow for drinking spout
353442 01/22/2014 342090 1 125 O Prohibit running electrical cord across floor in front of stage exit door adjacent to 1-125C
353441 01/22/2014 342088 1 185 O Keep door to custodial room locked and latched to prohibit student access (in student dining room)
353429 01/22/2014 342063 2 101 O Remove and prohibit paper on ceiling tiles
353430 01/22/2014 342065 2 105 O Remove and prohibit vinyl flammable table cover adjacent to corridor door
353432 01/22/2014 342069 2 107 O Remove and prohibit use of umbrella in classrooms - obstructs fire sprinkler head flow
353431 01/22/2014 342067 2 108 O Remove and prohibit combustible residential chair
353433 01/22/2014 342071 2 113 O Remove and prohibit paper on ceiling tiles
353435 01/22/2014 342075 2 124 O Remove and prohibit paper covering glass windows
353424 01/22/2014 342053 2 201 O Remove and prohibit hanging banner from ceiling
353422 01/22/2014 342047 2 208 O Remove glass mirror above sink or provide mirror made of tempered glass, safety glass, or stainless steel
353428 01/22/2014 342061 2 210 O Eliminate 13A white extension cord with multiple outlet end in front of teacher desk or replace with a surge protector
353427 01/22/2014 342059 2 224 O Remove and prohibit paper on window blinds
353426 01/22/2014 342057 2 226 O Remove and prohibit paper on window blinds
353423 01/22/2014 342049 2 230 O Remove glass mirror above sink or provide mirror made of tempered glass, safety glass, or stainless steel
353438 01/22/2014 342081 P 6080 O Remove glass mirror adjacent to back door or provide mirror made of tempered glass, safety glass, or stainless steel
353439 01/22/2014 342083 P 6232 O Prohibit plugging surge protector into surge protector adjacent to teacher desk - plug each surge protector directly into wall outlet
227963 01/22/2014 24476 2 001 MS Remove hook hold open devices from fire doors in 1st floor corridor (adjacent to 2-101)
353421 01/22/2014 342045 2 204 MS Adjust corridor door to latch properly
353434 01/22/2014 342073 2 004 OS Remove copy machines from corridor adjacent to art classroom 1-113
332912 08/26/2013 297323 1 194 M Replace bottom chord braces for bar joists that were removed to facilitate installation of AC equipment and repair brace embed that has pulled out of wall. Contact Building Department for necessary repairs ( Missing section of angle iron joist brace has a minor impact on the structural integrity - recommended by P. Joyce to NA on 8.26.13)
332937 12/10/2012 297381 00 0000 M Raise grade next to basketball court to eliminate drop off at edge of court
340186 12/10/2012 313179 1 001 M Determine cause of water damaged ceiling tiles in corridor above drinking fountains and replace tiles
340190 12/10/2012 313188 1 006 M Determine cause of water damaged ceiling tiles in bottom landing of stairway and replace tiles
340179 12/10/2012 313167 1 106 M Determine cause of water damaged ceiling tiles and replace tiles
340188 12/10/2012 313183 1 118 M Determine cause of water damaged ceiling tiles adjacent to 1-118D and replace tiles
340193 12/10/2012 313194 1 194 M Repair leaking condensation drain on air handler unit to prevent water standing on floor
340197 12/10/2012 313204 1 198 M Repair emergency lighting in electric room
340202 12/10/2012 313214 2 007 M Determine cause of water damaged ceiling tiles in stairway landing and replace tiles
340199 12/10/2012 313208 2 105 M Determine cause of water damaged ceiling tiles and replace tiles
340201 12/10/2012 313210 2 110 M Determine cause of water damaged ceiling tiles and replace tiles
340204 12/10/2012 313217 2 130 M Determine cause of water damaged ceiling tiles and replace tiles
340209 12/10/2012 313227 P 6078 M Repair emergency lighting at rear door
340208 12/10/2012 313225 P 6079 M Repair emergency lightingat front door
340210 12/10/2012 313230 P 6232 M Repair emergency lighting at front door
340205 12/10/2012 313220 P 6322 M Repair emergency lighting at front door
340207 12/10/2012 313223 P 6324 M Repair emergency lighting at rear door
340184 12/10/2012 313171 1 191 MS Provide current inspection tag for fire extinguisher
340214 12/10/2012 313236 2 006 MS Provide current annual inspection tag for fire sprinkler system
340212 12/10/2012 313232 2 017 MS Recharge fire extinguisher in corridor across from 2-205
340178 12/10/2012 313163 1 101 OS Relocate decorative tree to provide clear access to fire extinguisher at office door
332972 10/01/2012 297452 2 003 MS Provide bottom latching for fire doors in 1st floor corridor adjacent to 2-117 (Latching mechanism on smoke doors are not required, these are smoke doors, as per Victor Chodora)
332974 10/01/2012 297456 2 021 MS Provide bottom latching for fire doors in corridor adjacent to 2-217 (Latching mechanism on smoke stop doors not required, these are smoke stop doors, as per Victor Chodora)
340196 10/01/2012 313199 1 193 CS Provide automatic fire sprinkler coverage in storage room (room has a heat detector and two-hour rated fire walls, as per Victor Chodora)
332940 10/01/2012 297387 1 196 CS Provide automatic fire sprinkler coverage for room. Sprinkler line in place
332941 10/01/2012 297389 2 292 CS Provide automatic fire sprinkler coverage for communication closet. Sprinkler line in room
317108 04/19/2012 262454 1 125 C Provide records that stage rigging has been inspected and conforms to required safety standards
332933 04/11/2012 297369 00 0000 M Remove pipe protruding from play court when volley ball standard is removed, see Coach
332935 04/11/2012 297376 00 0000 M Fill holes in play fields, see Coach
332903 04/11/2012 297302 1 101A M Repair emergency eye wash in Clinic. Not working
332909 04/11/2012 297316 1 101A M Repair leaking sink drain
332905 04/11/2012 297307 1 116B M Replace crushed supply line for trap primer
317110 04/11/2012 262459 1 118A M Provide dated flame resistance label on CCTV studio curtain
332906 04/11/2012 297309 1 118F M Replace GFCI outlet that won't trip
332902 04/11/2012 297300 1 122 M Repair tilting skillet so lid will stay up. This will allow fire suppression heads to properly cover the skillet
332899 04/11/2012 297294 1 124A M Repair leaking sink drain
332901 04/11/2012 297298 1 124B M Secure loose faucet on sink
317109 04/11/2012 262456 1 125 M Provide dated flame resistance label on stage curtain
332911 04/11/2012 297321 1 194 M Provide cover on exposed fire alarm junction box above AHU 1-4
332949 04/11/2012 297408 2 006 M Secure loose outside upper handrail for stairs
332948 04/11/2012 297406 2 104B M Replace missing ceiling tiles
332947 04/11/2012 297403 2 110A M Replace damaged light switch
332968 04/11/2012 297442 2 118 M Remove pencil sharpener adjacent to sink without cover
332965 04/11/2012 297436 2 123B M Repair door lock so door can be unlocked from outside of room
332959 04/11/2012 297426 2 124A M Secure sink to wall
332960 04/11/2012 297428 2 124A M Replace damaged light switch
332956 04/11/2012 297421 2 126B M Determine cause of water damaged ceiling tiles and replace tiles
332957 04/11/2012 297422 2 128 M Secure loose spout on drinking fountain
332955 04/11/2012 297419 2 128 M Replace broken toilet seat
332975 04/11/2012 297459 2 181 M Pad and mark corners of water heater rack which are lower than 6'8"
332962 04/11/2012 297433 2 182 M Replace missing ceiling tiles
332946 04/11/2012 297399 2 191 M Replace Seimens Sentron on panel 2H1. Red indicator light is on
332952 04/11/2012 297413 2 210A M Repair leaking toilet supply line
332953 04/11/2012 297415 2 215A M Replace GFCI outlet that won't trip
332942 04/11/2012 297391 2 217 M Room always hot. Relocate temperature sensor away from corridor door or adjust temperature in room
332943 04/11/2012 297393 2 228A M Repair damaged wall at sink
332939 04/11/2012 297385 P 0000 M Replace missing epoxy paint signs for all bathrooms in portables
332900 04/11/2012 297296 P 6078 M Provide cover for pencil sharpener adjacent to door or remove pencil sharpener
332944 04/11/2012 297395 P 6324 M Repair emergency lighting
332977 04/11/2012 297463 2 106 O Keep shower drain filled with water. Every 2 months pour 1 quart of water down drain
332904 04/11/2012 297305 1 115 C Provide auto closer on corridor door
317087 04/11/2012 262407 1 118A C Provide records that CCTV studio rigging has been inspected and conforms to required safety standards
332898 04/11/2012 297292 1 122 MS Provide current inspection tag for kitchen hood fire suppression system
332954 04/11/2012 297417 2 009 MS Adjust fire door at top of stairs to latch properly
332951 04/11/2012 297411 2 017 MS Adjust fire door in corridor adjacent to 2-270 to latch properly
332910 04/11/2012 297319 1 182 OS Prohibit charging batteries in room
332976 04/11/2012 297461 2 105A OS Keep area within 18" of fire sprinkler head clear and unobstructed
317211 03/22/2011 262685 1 116 M Determine cause of water damaged ceiling tiles and replace tiles
317106 03/22/2011 262450 1 120 M Replace missing cover for data outlet on wall adjacent to stage steps
317107 03/22/2011 262452 1 120 M Replace missing escutcheon on fire sprinkler head in ceiling adjacent to American Flag
317097 03/22/2011 262426 1 182 M Reverse location of washing machine and clothes dryer. Dryer hose is too long and has staff requested easier access to both machines, by switching locations hose does not need to be shortened
317212 03/22/2011 262687 1 193 M Replace missing signage indicating room name and number at appropriate height with raised and Braille characters
317213 03/22/2011 262689 1 194 M Repair door to close properly
317105 03/22/2011 262446 1 194 M Repair emergency lighting test button
317093 03/22/2011 262417 2 006 M Provide sign on exterior stairwell door indicating FDCV (fire department control valve) per Palm Beach County Fire Rescue
317094 03/22/2011 262424 2 006 M Repair exterior door to close properly
317050 03/22/2011 262330 2 009 M Replace broken window glass in door @ second floor landing
317081 03/22/2011 262397 2 109 M Determine cause of water damaged ceiling tiles and replace tiles
317080 03/22/2011 262394 2 120 M Adjust fire sprinkler head so deflector projects a minimum 1" below escutcheon
317121 03/22/2011 262481 P 6078 M Repair door to close properly
317119 03/22/2011 262477 P 6079 M Repair door to close properly
317099 03/22/2011 262433 1 119A O Prohibit white 13A multi outlet extension cord or replace with minimum 15A cord
317082 03/22/2011 262399 2 102 O Prohibit plugging surge protector into surge protector
317048 03/22/2011 262325 2 205A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
317049 03/22/2011 262328 2 218 O Remove and prohibit air freshener (sticks in oil)
317112 03/22/2011 262461 P 6080 O Prohibit plugging surge protector into surge protector @ computers
317114 03/22/2011 262465 P 6080 O Prohibit plugging surge protector into extension cord adjacent to teacher's desk
317116 03/22/2011 262471 P 6080 O Remove excessive flammable wall coverings and decorations. Limit coverage area to 20% of each wall, prohibit hanging papers on ceiling
317122 03/22/2011 262484 P 6321 O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
317206 03/22/2011 262674 P 6322 O Remove and prohibit air freshener
317207 03/22/2011 262676 P 6322 O Provide minimum one foot blank wall space on lock side of (rear) door
317208 03/22/2011 262678 P 6323 O Prohibit plugging microwave and refrigerator into surge protector - plug directly into permanent electrical outlet
317209 03/22/2011 262680 P 6323 O Remove and prohibit (flammable) plastic dolphin sheet on wall
227961 03/22/2011 24500 2 001 C Provide magnetic release hold open devices for fire doors in 1st floor corridor (adjacent to 2-101)
317100 03/22/2011 262437 1 120 MS Provide current inspection tag for fire extinguisher
317102 03/22/2011 262439 1 122 MS Provide current inspection tag for type K fire extinguisher
317089 03/22/2011 262414 2 006 MS Provide current inspection tag for fire sprinkler system
317046 03/22/2011 262322 2 204 MS Provide current inspection tag for fire extinguisher
317118 03/22/2011 262475 P 6079 OS Maintain clear aisle to rear exit door
317204 03/22/2011 262669 P 6321 OS Maintain clear aisle to rear exit door
317205 03/22/2011 262672 P 6321 OS Provide clear access to fire extinguisher
317083 03/22/2011 262401 2 102 CS Provide CO2 fire extinguisher for computer lab
317085 03/22/2011 262403 1 101 FS Make repairs as noted on fire alarm report
275176 11/17/2010 171912 00 0000 C Provide suitable area for charging batteries for floor cleaning machines (Bldg. 3 approved per Victor Chodora Nov. 2010)
317210 11/17/2010 262683 1 8088 C Replace exit sign @ exterior stage with lighted exit sign, keep directional arrow/chevron the same
302900 04/16/2010 231268 1 0000 M Determine cause of water damaged ceiling tiles adjacent to 1-106 and replace tiles
302901 04/16/2010 231270 1 106 M Determine cause of water damaged ceiling tiles and replace tiles
302898 04/16/2010 231264 1 116 M Determine cause of water damaged ceiling tiles and replace tiles
302894 04/16/2010 231256 1 120 M Repair broken drinking fountains
302893 04/16/2010 231254 1 196 M Repair emergency lighting
302881 04/16/2010 231228 2 117A M Repair loose door handle on bathroom door
302882 04/16/2010 231230 2 119A M Replace damaged/rusty fire sprinkler head
302880 04/16/2010 231226 2 192 M Mount fire extinguisher at maximum five feet above floor
302831 04/16/2010 231118 2 225 M Secure loose escutcheon on fire sprinkler head
296630 04/16/2010 217701 P 0000 M Verify that bathroom wall finish in portables is impervious or provide impervious wall finish for bathroom walls in all concreteables
302889 04/16/2010 231245 P 6078 M Eliminate wasp nest in rear door latch hole
302888 04/16/2010 231243 P 6079 M Adjust rear door to close properly
302885 04/16/2010 231237 P 6080 M Remove and prohibit excessive flammable wall coverings, limit coverage area to 20% of wall
302891 04/16/2010 231249 P 6232 M Eliminate wasp nest above rear door
302883 04/16/2010 231232 P 6322 M Replace missing ceiling tiles
302899 04/16/2010 231266 1 112 O Remove and prohibit air freshener
302895 04/16/2010 231258 1 119 O Prohibit black multi outlet extension cord adjacent to TV or replace with minimum 15A single outlet cord
302838 04/16/2010 231133 2 107 O Remove and prohibit excessive flammable wall coverings
302839 04/16/2010 231135 2 109 O Prohibit plugging surge protector into extension cord @ document camera
302840 04/16/2010 231137 2 109C O Remove flammable wall covering (plastic tablecloth)
302842 04/16/2010 231141 2 113 O Mount sign indicating evacuation routes
302879 04/16/2010 231224 2 113B O Prohibit storage (on top shelf) which dislocates ceiling tile
302841 04/16/2010 231139 2 115 O Remove and prohibit flammable plastic tablecloths
302836 04/16/2010 231128 2 122B O Keep area within 18" of fire sprinkler head clear
296836 04/16/2010 218133 2 123A O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
302835 04/16/2010 231126 2 123A O Prohibit plugging microwave into extension cord - plug directly into permanent electrical outlet
302823 04/16/2010 231101 2 201 O Prohibit brown 13A extension cord @ document camera or replace with minimum 15A single outlet cord
302824 04/16/2010 231103 2 203 O Prohibit plugging surge protector into extension cord
302826 04/16/2010 231107 2 204 O Prohibit plugging surge protector into extension cord
302827 04/16/2010 231110 2 222 O Remove and prohibit combustible beanbag chairs
302825 04/16/2010 231105 2 222A O Remove and prohibit air freshener
302828 04/16/2010 231112 2 223 O Prohibit flammable plastic tablecloth
302884 04/16/2010 231234 P 6080 O Remove and prohibit paper covering window in door
274567 04/16/2010 170615 1 118G C Provide illuminated exit sign at exit door into 1-118
274574 04/16/2010 170630 2 0000 C Provide signage indicating name and number at appropriate height with raised and Braille characters for all stairwells and corridors
227966 04/16/2010 63738 2 002 C Provide intermediate handrails for stairs greater than 88" wide ( Waived by Victor Chodora, 4/22/2010, Angel Goitia review plans, current stairs w/o handrail are sufficent for occupant load)
227981 04/16/2010 63764 2 213 C Provide emergency eye wash/shower in science room
302822 04/16/2010 231099 00 0000 MS Provide current inspection tags for fire extinguishers
302897 04/16/2010 231262 1 118G MS Provide current inspection tag for fire sprinkler system
302892 04/16/2010 231252 1 194 MS Recharge fire extinguisher
302896 04/16/2010 231260 1 118A OS Prohibit flammable plastic tablecloths
302837 04/16/2010 231130 2 124 OS Prohibit hold open devices on fire door
302833 04/16/2010 231122 2 128 OS Prohibit hold open devices on fire door
296834 04/16/2010 218130 2 128 OS Remove and prohibit use of toaster oven
302834 04/16/2010 231124 2 129 OS Prohibit hold open devices on fire door
302829 04/16/2010 231114 2 226 OS Prohibit hold open devices on fire door
302830 04/16/2010 231116 2 226B OS Prohibit flammable plastic tablecloth
302832 04/16/2010 231120 2 227 OS Prohibit hold open devices on fire door
302890 04/16/2010 231247 P 6078 OS Prohibit flammable plastic grass decorations
302886 04/16/2010 231239 P 6080 OS Prohibit flammable plastic grass and tablecloths
302887 04/16/2010 231241 P 6080 OS Remove and prohibit candles
296833 10/30/2009 218127 1 199 M Replace (damaged) rusted door and frame
296609 10/30/2009 217660 1 119 O Prohibit plugging surge protector into surge protector
274610 10/30/2009 170703 2 110 O Remove and prohibit excessive flammable decorations on walls - limit paper covering walls to maximum 20% of wall area
296837 10/30/2009 218136 2 125 MS Adjust (corridor) fire door to latch properly
296564 04/27/2009 217557 1 115 M Determine cause of water damaged ceiling tiles and replace tiles, replace missing tiles
296617 04/27/2009 217673 1 120 M Repair drinking fountain, water does not work
296626 04/27/2009 217694 1 124C M Secure hanging ceiling tiles
296848 04/27/2009 218159 2 101C M Repair exhaust fan in bathroom
296845 04/27/2009 218152 2 105A M Replace missing escutcheon on fire sprinkler head
296842 04/27/2009 218145 2 113A M Repair exhaust fan at kiln
296838 04/27/2009 218138 2 119 M Adjust air conditioning, classroom is very loud due to vibrations from A/C
296849 04/27/2009 218161 2 204 M Adjust air conditioning in computer room, room is too warm
296853 04/27/2009 218169 2 290 M Provide cover on exposed electrical junction boxes
296859 04/27/2009 218181 2 292 M Mount fire extinguisher at maximum five feet above floor
296866 04/27/2009 218196 2 294 M Provide cover on exposed electrical junction box
296560 04/27/2009 217545 1 102 O Provide correct cover for data outlet and replace damaged data cable
296562 04/27/2009 217555 1 113 O Prohibit plugging surge protector into surge protector on media cart
296613 04/27/2009 217668 1 119 O Prohibit white 13A extension cord or replace with minimum 15A single outlet cord
296608 04/27/2009 217658 1 119B O Prohibit plugging surge protector into surge protector
296619 04/27/2009 217678 1 122G O Prohibit brown 13A extension cord or replace with minimum 15A single outlet cord
296622 04/27/2009 217684 1 123 O Prohibit plugging white microwave into extension cord - plug directly into permanent electrical outlet
296623 04/27/2009 217688 1 125C O Remove and prohibit air freshener
296625 04/27/2009 217690 1 125E O Prohibit plugging extension cord into surge protector
296851 04/27/2009 218165 2 205 O Prohibit plugging surge protector into extension cord
296850 04/27/2009 218163 2 206 O Remove flammable wall covering (straw/bamboo panels)
296854 04/27/2009 218171 2 207 O Prohibit plugging surge protector into extension cord
296857 04/27/2009 218177 2 210 O Prohibit plugging surge protector into extension cord
296858 04/27/2009 218179 2 212 O Provide approved rubber cover strip for electrical cords to prevent tripping hazard
296861 04/27/2009 218185 2 221 O Remove and prohibit combustible stuffed animal (monster)
296864 04/27/2009 218192 2 223A O Prohibit plugging microwave into surge protector - plug directly into permanent electrical outlet
296868 04/27/2009 218200 2 229 O Keep area within 18" of fire sprinkler head clear
296870 04/27/2009 218204 2 230 O Prohibit plugging surge protector into surge protector
296869 04/27/2009 218202 2 230B O Remove and prohibit combustible beanbag chair and large stuffed animals
296628 04/27/2009 217697 P 6080 O Remove and prohibit air freshener
296620 04/27/2009 217682 1 197 MS Recharge fire extinguisher
296872 04/27/2009 218208 2 195 MS Provide current inspection tag for fire extinguisher
296852 04/27/2009 218167 2 290A MS Provide current inspection tag for fire extinguisher
296865 04/27/2009 218194 2 293 MS Provide current inspection tag for fire extinguisher
296846 04/27/2009 218154 3 102 MS Provide current inspection tag for fire extinguisher
296561 04/27/2009 217553 1 111 OS Remove and prohibit use of space heater
296565 04/27/2009 217564 1 182 OS Prohibit charging batteries in room
296847 04/27/2009 218157 2 104 OS Prohibit running electrical cord into ceiling
296843 04/27/2009 218147 2 109 OS Maintain clear aisle to (exterior) exit
296840 04/27/2009 218142 2 115 OS Remove and prohibit candles
296855 04/27/2009 218173 2 207 OS Remove and prohibit candles
296856 04/27/2009 218175 2 210 OS Remove and prohibit candles
296860 04/27/2009 218183 2 218 OS Remove and prohibit use of toaster
296862 04/27/2009 218187 2 221 OS Prohibit running electrical cord through ceiling
296863 04/27/2009 218190 2 223A OS Remove and prohibit use of toaster oven
296867 04/27/2009 218198 2 225A OS Remove and prohibit use of toaster oven
296871 04/27/2009 218206 2 226 OS Remove and prohibit candles
296629 04/27/2009 217699 P 6080 OS Prohibit electrical cord under carpet
274619 01/28/2009 170722 2 0000 M Replace cracked wire glass in exterior door at bottom of stairwell adjacent to 2-128
274576 01/28/2009 170635 2 0000 M Repair damaged tread covers on stairs adjacent to 2-180
274570 01/28/2009 170622 1 118G C Provide emergency lighting in room used as classroom
274771 01/28/2009 171056 1 122 C Install GFCI outlet next to ice machine
274620 01/28/2009 170724 2 0000 MS Adjust fire doors at bottom of stairwell adjacent to 2-128 to close and latch properly
274581 02/26/2008 170645 1 0000 M Replace broken cover for pull box in sidewalk outside 1-194
274566 02/26/2008 170613 1 118D M Replace missing escutcheon on fire sprinkler head
274772 02/26/2008 171058 1 122D M Seal gap between fire sprinkler escutcheon and ceiling
274586 02/26/2008 170655 1 182 M Replace missing escutcheon on fire sprinkler head in cage area
274773 02/26/2008 171060 1 196 M Provide certification that all student occupied spaces have emergency lights and all are operable
274577 02/26/2008 170637 2 0000 M Repair exterior doors at bottom of stair adjacent to 2-180 to open/close properly
274608 02/26/2008 170699 2 102 M Seal gap between fire sprinkler head and ceiling
274641 02/26/2008 170766 2 103 M Determine cause of water damaged ceiling tiles adjacent to windows and replace tiles
274613 02/26/2008 170709 2 118 M Replace missing signage indicating room name and number
274628 02/26/2008 170740 2 119A M Replace damaged caulk behind sink
274616 02/26/2008 170716 2 124 M Repair GFCI outlet adjacent to sink - according to teacher, GFCI trips whenever she uses outlet
274621 02/26/2008 170726 2 130 M Determine cause of water damaged ceiling tiles and replace tiles
274603 02/26/2008 170689 2 230A M Repair door hardware - when lever handle is turned from inside, latch sticks inside door
274592 02/26/2008 170667 2 290 M Remove sign indicating "Fire Extinguisher Inside"
274800 02/26/2008 171112 P 0000 M Provide locks on gates for fence enclosure for electrical panels between P-3 & P-4
274793 02/26/2008 171101 P 6321 M Repair light in exit sign
274794 02/26/2008 171103 P 6321 M Provide cover on exposed electrical junction box in bathroom
274569 02/26/2008 170619 1 118G O Post sign indicating evacuation routes with exiting through door into 1-118
274571 02/26/2008 170624 1 118G O Remove and prohibit paper/plastic covering window in exit door leading into 1-118
274583 02/26/2008 170649 1 119 O Eliminate orange extension cord or replace with minimum 15A cord
274584 02/26/2008 170651 1 119 O Prohibit plugging surge protector into extension cord and prohibit use of 13A extension cord with multi-outlet end
274587 02/26/2008 170657 1 182 O Remove storage from top shelves of shelving adjacent to cage area fencing (on both sides of fencing) to provide adequate fire sprinkler coverage for both receiving and cage areas
274640 02/26/2008 170764 2 103 O Provide verification that written permission from principal has been provided to keep iguana in the classroom and that all required safety precautions are being followed
274637 02/26/2008 170758 2 105 O Provide verification that written permission from principal has been provided to keep iguana in the classroom and that all required safety precautions are being followed
274636 02/26/2008 170756 2 107 O Provide verification that written permission from principal has been provided to keep iguana in the classroom and that all required safety precautions are being followed
274609 02/26/2008 170701 2 108B O Remove and prohibit Roach spray
274633 02/26/2008 170750 2 113 O Post sign indicating evacuation routes
274632 02/26/2008 170748 2 114 O Prohibit use of Staff Bathroom by students (being used by students in 2-115)
274630 02/26/2008 170744 2 117 O Prohibit leaving extension cord plugged in when not in use
274631 02/26/2008 170746 2 117B O Remove storage within 18" of fire sprinkler heads
274614 02/26/2008 170711 2 118 O Remove and prohibit air freshener
274627 02/26/2008 170738 2 119B O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
274617 02/26/2008 170718 2 126B O Prohibit plugging microwave oven into surge protector - plug directly into permanent electrical outlet
274624 02/26/2008 170732 2 128A O Prohibit plugging refrigerator and microwave oven into surge protector - plug directly into permanent electrical outlet
274625 02/26/2008 170734 2 128A O Prohibit plugging surge protector into extension cord
274622 02/26/2008 170728 2 130 O Remove and prohibit paper covering window in door
274596 02/26/2008 170675 2 222 O Remove and prohibit air freshener
274598 02/26/2008 170679 2 224A O Remove and prohibit air freshener spray
274604 02/26/2008 170691 2 225 O Remove and prohibit air freshener
274601 02/26/2008 170685 2 230B O Prohibit covering sign indicating room name and number
274602 02/26/2008 170687 2 230B O Remove storage within 18" of fire sprinkler heads
274777 02/26/2008 171068 P 6080 O Remove paper covering electrical panel
274779 02/26/2008 171072 P 6080 O Eliminate extension cord or replace with minimum 15A cord
227960 02/26/2008 65452 2 106 C Provide signage indicating room name and number, (2-106), at appropriate height with raised and Braille letters for ESE bathroom adjacent to 2-108
274565 02/26/2008 170611 00 0000 MS Provide current inspection tags for all fire extinguishers throughout campus
274582 02/26/2008 170647 1 118G MS Provide current inspection tag for fire sprinkler system
274590 02/26/2008 170663 2 0000 MS Adjust fire doors at top of stairwell adjacent to 2-201 to close and latch properly
274575 02/26/2008 170632 2 0000 MS Adjust fire doors at bottom of stairwell adjacent to 2-180 to latch properly
274600 02/26/2008 170683 2 0000 MS Adjust fire doors at top of stairwell adjacent to 2-228 to close and latch properly
274612 02/26/2008 170707 2 0000 MS Adjust fire doors in 1st floor corridor adjacent to 2-117 to close and latch properly
274588 02/26/2008 170659 1 101 OS Remove plant blocking clear access and visibility of fire extinguisher cabinet
274564 02/26/2008 170609 1 101A OS Prohibit wedging open corridor door
274560 02/26/2008 170601 1 106 OS Prohibit wedging open fire door at vault
274561 02/26/2008 170603 1 106 OS Prohibit use of vault for student space
274563 02/26/2008 170607 1 109 OS Remove and prohibit candles
274572 02/26/2008 170626 1 118 OS Prohibit blocking exit door leading out of 1-118G
274568 02/26/2008 170617 1 118G OS Provide clear path to exit door leading into 1-118
274770 02/26/2008 171054 1 125 OS Remove storage (piano) blocking clear access to fire extinguisher
274579 02/26/2008 170641 1 182 OS Prohibit running electrical cord through doorway into 1-182A
274585 02/26/2008 170653 1 182 OS Prohibit charging batteries in room
274562 02/26/2008 170605 1 190 OS Remove storage from electrical room
274580 02/26/2008 170643 1 195 OS Remove flourescent bulbs from communications room
274589 02/26/2008 170661 2 0000 OS Prohibit wedging open fire doors at top of stairwell adjacent to 2-201
274573 02/26/2008 170628 2 0000 OS Prohibit wedging open corridor doors at bottom of stairwell adjacent to 2-180
274642 02/26/2008 170768 2 101B OS Remove and prohibit use of toaster oven
274607 02/26/2008 170697 2 102 OS Remove desk adjacent to corridor door to provide minimum 12" clear on latch side of door
274639 02/26/2008 170762 2 103 OS Remove desk adjacent to corridor door to provide minimum 12" clear on latch side of door
274638 02/26/2008 170760 2 105 OS Remove desk adjacent to corridor door to provide minimum 12" clear on latch side of door
274634 02/26/2008 170752 2 107 OS Prohibit wedging open corridor door
274635 02/26/2008 170754 2 107 OS Remove desk adjacent to corridor door to provide minimum 12" clear on latch side of door
274629 02/26/2008 170742 2 117 OS Remove desk adjacent to corridor door to provide minimum 12" clear on latch side of door
274626 02/26/2008 170736 2 117 OS Prohibit wedging open corridor door
274615 02/26/2008 170713 2 124 OS Prohibit running electrical cord through door into 2-122B
274623 02/26/2008 170730 2 127 OS Remove desk adjacent to corridor door to provide minimum 12" clear on latch side of door
274618 02/26/2008 170720 2 128 OS Remove and prohibit warming plate behind teacher's desk
274578 02/26/2008 170639 2 180 OS Prohibit charging batteries in room
274591 02/26/2008 170665 2 206 OS Remove desk adjacent to corridor door to provide minimum 12" clear on latch side of door
274593 02/26/2008 170669 2 208 OS Remove and prohibit lunchboxes on floor outside corridor door
274594 02/26/2008 170671 2 211 OS Prohibit wedging open corridor door
274606 02/26/2008 170695 2 211 OS Remove table adjacent to corridor door to provide minimum 12" clear on latch side of door
274597 02/26/2008 170677 2 222B OS Prohibit use of closet as student space (desks and chairs in room)
274605 02/26/2008 170693 2 225 OS Remove desk adjacent to corridor door to provide minimum 12" clear on latch side of door
274599 02/26/2008 170681 2 226B OS Prohibit use of closet as student space (desk and chair in closet)
274804 02/26/2008 171120 P 6078 OS Relocate file cabinet blocking clear path to rear door
274780 02/26/2008 171074 P 6080 OS Relocate shelving blocking clear path to rear door
274782 02/26/2008 171077 P 6080 OS Remove hanging flowers across rear door
274785 02/26/2008 171082 P 6080 OS Remove garden hose from concrete slab outside rear door - prevents door from opening properly and creates tripping hazard
274796 02/26/2008 171107 P 6232 OS Relocate file cabinets blocking clear path to rear door
274797 02/26/2008 171109 P 6232 OS Remove and prohibit use of toaster oven and toaster
254697 10/24/2007 130371 1 0000 M Label emergency generator disconnect switch on exterior wall at 1-196
227954 10/24/2007 24503 1 122 M Provide current inspection tag for kitchen boiler (steamer)
274790 10/24/2007 171095 P 6323 M Determine cause of water damaged ceiling tiles and replace tiles
238931 10/24/2007 97434 2 0000 C Provide edge protection at free edge of smoke stop doors in first and second floor corridors to prevent doors from accidentally being closed (no longer required by code)
254703 10/24/2007 130384 2 0000 MS Adjust fire door in corridor adjacent to 2-217 to latch properly
238934 10/24/2007 97440 2 292 CS Provide automatic fire sprinkler coverage for electronic systems room
254678 09/14/2006 130332 1 0000 M Install cap on fire department standpipe adjacent to 1-193
254681 09/14/2006 130341 1 106 M Determine cause of water damaged ceiling tiles and replace tiles
227946 09/14/2006 63724 1 113 M Adjust fire sprinkler head to project minimum 1" below ceiling
254692 09/14/2006 130361 1 182B M Reset ceiling tile at sprinkler head
254687 09/14/2006 130352 1 194 M Exterminate ants in electrical room
254679 09/14/2006 130338 1 194 M Repair emergency lighting
254644 09/14/2006 130261 2 107A M Repair exhaust fan in bathroom
254645 09/14/2006 130264 2 109C M Reinstall paper towel dispenser that fell off of wall
254648 09/14/2006 130267 2 117A M Secure loose door handle
227972 09/14/2006 24482 2 123B M Repair lock on bathroom door to unlock from the outside
238938 09/14/2006 97448 2 215A M Repair exhaust fan in bathroom
254700 09/14/2006 130380 2 215B M Repair exhaust fan in bathroom
254701 09/14/2006 130382 2 290 M Provide cover on exposed electrical junction box
254704 09/14/2006 130389 2 294 M Provide cover on exposed electrical junction box
254663 09/14/2006 130301 P 6078 M Adjust east door to latch properly
254684 09/14/2006 130345 1 116 MS Provide current inspection tag for fire extinguisher (6/04)
227948 09/14/2006 24468 1 118G MS Provide current inspection tag for fire sprinkler system and provide method to test system (system access is above ceiling)
254709 09/14/2006 130392 2 002 MS Adjust fire door at top of stairs to latch properly
227987 09/14/2006 68406 3 102 OS Prohibit storage of gas powered equipment and remove flammable storage sign
238900 09/20/2005 97380 00 0000 M Provide lock for gate in fencing around propane gas tank and install cover over exposed valves and pressure gauge on tank
227944 09/20/2005 24501 00 0000 M Provide certification that all student occupied spaces have emergency lights and all are operable
238887 09/20/2005 97359 1 120 M Provide number on maximum occupancy sign (occupancy = 456)
238891 09/20/2005 97369 1 122B M Repair exhaust fan in bathroom
238921 09/20/2005 97410 1 122E M Repair walk in freezer door to close completely and seal
238904 09/20/2005 97392 1 125B M Chain cylinder to wall
238909 09/20/2005 97402 1 196 M Provide certification that emergency generator is fully functional. Transfer switch indicated SYSTEM ALERT and many warning lights were illuminated on the generator
238943 09/20/2005 97458 2 001 M Repair torn stair nosing on upper flight of west stairs
238881 09/20/2005 97344 2 001 M Determine cause of water damaged ceiling tiles in vestibule at west stairs and replace tiles
238941 09/20/2005 97454 2 002 M Repair or replace damaged exit sign in corridor at 2-294
238885 09/20/2005 97355 2 101 M Determine cause of water damaged ceiling tiles and replace tiles at 2-101A
238933 09/20/2005 97438 2 117A M Caulk toilet to floor
238936 09/20/2005 97444 2 124A M Secure sink to wall
238937 09/20/2005 97446 2 125A M Repair exhaust fan in bathroom
238935 09/20/2005 97442 2 129B M Secure sink to wall
238886 09/20/2005 97357 2 181 M Repair hole in wall
238942 09/20/2005 97456 2 205C M Secure sink to wall
238940 09/20/2005 97452 2 207A M Repair exhaust fan in bathroom
238939 09/20/2005 97450 2 208A M Repair exhaust fan in bathroom
238945 09/20/2005 97462 2 209A M Determine cause of water damaged ceiling tiles and replace tiles
238944 09/20/2005 97460 2 290 M Sign room ROOF ACCESS
238883 09/20/2005 97348 00 0000 O No access was available to 1-124A & 1-124B . Please be prepared to access these rooms during the report review meeting.
238893 09/20/2005 97371 00 0000 MS Provide current inspection tag all for fire extinguishers on campus
238902 09/20/2005 97389 1 198 MS Seal penetration in north enclosure wall to prevent spread of fire or smoke
227962 09/20/2005 63745 2 001 MS Adjust smoke stop doors adjacent to 2-117 to latch properly
238932 09/20/2005 97436 2 002 MS Adjust fire doors in corridor at 2-217 to latch properly
227982 09/20/2005 68403 2 213 MS Provide current inspection tag for fire extinguisher
238906 09/20/2005 97399 1 116 OS Prohibit storage of flammable aerosol cans
238890 09/20/2005 97361 1 119 OS Remove storage at east exit
227956 09/20/2005 24490 1 182 OS Prohibit recharging batteries in room
227959 09/20/2005 68424 1 199 OS Remove storage from mechanical room
238884 09/20/2005 97353 2 001 OS Remove copier in corridor at exit doors adjacent to 2-111
238905 09/20/2005 97395 2 105B OS Prohibit electrical cord from running through door opening to room 2-105
227976 09/20/2005 63758 2 180 OS Prohibit recharging batteries in room
227945 10/19/2004 68404 00 0000 M Chain up valve handles on fire main at exterior, west of 1-118G
227989 10/19/2004 24462 1 118 M Provide number on sign indicating maximum occupancy adjacent to main entrance
227947 10/19/2004 63726 1 118A M Repair cracked plaster adjacent to door leading into 1-118C
227950 10/19/2004 68402 1 120 M Repair fly fan above door at 1-125E to run
227951 10/19/2004 68425 1 120 M Remove mold from wall above windows to courtyard at 1-125E and eliminate source of mold
227990 10/19/2004 63731 1 122 M Relocate double gas burner to sit properly under suppression system nozzle and paint proper location of equipment under hood suppression system on floor
227991 10/19/2004 63733 1 122D M Replace rusted fire sprinkler head
227955 10/19/2004 68412 1 124A M Secure sink to wall
227992 10/19/2004 63735 1 125 M Remove computer line across doors and through door into 1-125E
227993 10/19/2004 63737 1 180 M Secure loose ceiling tile
227958 10/19/2004 68409 1 196 M Provide certification that emergency generator is operable (Overcrank warning light is on and transfer switch is in alert and indicates that system is not in auto mode)
227964 10/19/2004 68410 2 001 M Remove paint from fire rating tags on fire doors in corridor at 2-101
227965 10/19/2004 68426 2 001 M Repair deteriorated wall finish in stair lobby at 2-180
227968 10/19/2004 68413 2 104A M Secure sink to wall
227994 10/19/2004 24478 2 108 M Replace rusted fire sprinkler head
227969 10/19/2004 68422 2 111A M Secure sink to wall
227970 10/19/2004 68414 2 117A M Anchor toilet to floor
227971 10/19/2004 68415 2 117A M Reinstall handicapped grabrail that came off of wall
227973 10/19/2004 68416 2 123B M Secure sink to wall
227974 10/19/2004 68417 2 124A M Secure sink to wall
227995 10/19/2004 63755 2 125 M Adjust lever door handle on inside face of corridor door
227975 10/19/2004 68418 2 125A M Secure sink to wall
227979 10/19/2004 68407 2 202 M Anchor shelving to wall
227980 10/19/2004 24519 2 208A M Repair exhaust fan in bathroom and secure loose grill
227996 10/19/2004 24522 2 209C M Repair exhaust fan in bathroom
227997 10/19/2004 63763 2 209C M Replace fire sprinkler head covered with paint
227998 10/19/2004 24523 2 210A M Repair exhaust fan in bathroom
227999 10/19/2004 24524 2 211A M Repair exhaust fan in bathroom
227983 10/19/2004 68419 2 213A M Secure sink to wall
227984 10/19/2004 68420 2 214C M Secure sink to wall
227985 10/19/2004 68421 2 222A M Secure sink to wall
227986 10/19/2004 68408 2 280 M Anchor shelving to wall
228000 10/19/2004 63721 1 101 O Relocate tree blocking clear access to fire extinguisher
228002 10/19/2004 63728 1 119 O Eliminate extension cord or replace with minimum 15A cord
228003 10/19/2004 65455 1 123A O Eliminate extension cord or replace with minimum 15A cord
227957 10/19/2004 68401 1 182 O Maintain clear access to emergency eye wash
228005 10/19/2004 65453 2 115 O Eliminate multi-outlet adaptor adjacent to window
227988 10/19/2004 24463 1 119 C Provide number on sign indicating maximum occupancy adjacent to main entrance
227949 10/19/2004 68423 1 120 C Install maximum occupancy signage adjacent to main entry, inside of room
227952 10/19/2004 63730 1 122 C Provide fire suppression system nozzle in chain broiler, if broiler is used
227953 10/19/2004 63732 1 122 MS Provide current inspection for fire suppression system (dated 7/03)
227967 10/19/2004 68400 2 002 MS Adjust fire door at top of stairs to latch
227977 10/19/2004 68405 2 191 MS Seal penetration in ceiling to prevent spread of fire or smoke
228001 10/19/2004 63722 1 102 OS Prohibit candles in room
228004 10/19/2004 65454 2 0000 OS Prohibit wedging open corridor doors
227978 10/19/2004 68411 2 192 FS Provide heat detector in electric room (room is not sprinklered)